As of: 09/24/19 FRAMING-ARCADIA-AFG451T-WINDLOAD.pdf Scale: Function: Description: Detail: OF SHEET AFG451T Series 2" X 4 1/2" Offset Glazed For 1" Glass Storefront Design Criteria N.T.S. 1 5 I = 2.951 IN 4 3 S = 1.275 IN I = 5.161 IN 4 TB251 TB251 WITH STEEL REINFORCEMENT 1 3/8" X 2 3/8" X 1/4" I = 1.526 IN 4 3 S = 1.055 IN I = 2.818 IN 4 TB555 TB555 WITH STEEL REINFORCEMENT 1 1/4" X 2" X 1/4" Windload Charts · Mullions are assumed to be single span, simple beam elements, uniformly loaded and adequately braced to prevent lateral-torsional buckling. All other complex design conditions shall be reviewed by Arcadia or a design professional. · Aluminum extrusions shall be 6063-T6 alloy. Allowable stresses to be derived per Aluminum Design Manual. Deflection limitation of mullions shall be in accordance with AAMA TIR-A11 of L/175 for spans up to 13’-6” and L/240 + 1/4” for all others where L is equal to the span of mullion. · A design professional shall be consulted to confirm that no lite of glass deflects more than H/175 or 3/4”, whichever is less, where H indicates the height of glass. · For mullions containing steel reinforcement, the reinforcement is assumed to be installed for the full length of the mullion. A design professional shall be consulted for instances where steel reinforcement is installed for a partial length of the mullion span. · Windload pressure determinations shall be per ASCE 7 and according to local governing codes. A professional engineer shall be consulted for the most current laws and local building codes. · Selection of perimeter fasteners and attachment of glazing system to building structure are project specific and therefore shall be reviewed and determined by a design professional. · Arcadia assumes no responsibility for selecting the appropriate systems for specific projects. Consult Your Local Arcadia Representative For Special Applications Not Covered By These Curves. MULLION HEIGHT IN FEET MULLION SPACING IN FEET A B E C D MULLION HEIGHT IN FEET MULLION SPACING IN FEET A B E C D MULLION HEIGHT IN FEET MULLION SPACING IN FEET A B E C D MULLION HEIGHT IN FEET MULLION SPACING IN FEET A B E C D A = 16 P.S.F. (766 Pa) B = 20 P.S.F. (958 Pa) C = 25 P.S.F. (1197 Pa) D = 30 P.S.F. (1436 Pa) E = 40 P.S.F. (1915 Pa)

Upload: others

Post on 24-Mar-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

As of: 09/24/19FRAMING-ARCADIA-AFG451T-WINDLOAD.pdf

Scale:

Function:Description:

Detail:OFSHEET

Z:\05 NEW WINDLOAD DEADLOAD\ARCADIA ( STEVEN TOU)\02_OFFSET GLAZING\FRAMING-ARCADIA-AFG451T-WINDLOAD.DWGSTou

AFG451T Series 2" X 4 1/2" Offset Glazed For 1" Glass

Storefront Design Criteria N.T.S. 1 5

I = 2.951 IN 4

3S = 1.275 INI = 5.161 IN 4

TB251 TB251 WITHSTEEL REINFORCEMENT

1 3/8" X 2 3/8" X 1/4"

I = 1.526 IN 4

3S = 1.055 INI = 2.818 IN 4

TB555 TB555 WITHSTEEL REINFORCEMENT

1 1/4" X 2" X 1/4"

Windload Charts

· Mullions are assumed to be single span, simple beam elements, uniformly loaded and adequately braced to prevent lateral-torsional buckling. All other complex design conditions shallbe reviewed by Arcadia or a design professional.

· Aluminum extrusions shall be 6063-T6 alloy. Allowable stresses to be derived per Aluminum Design Manual. Deflection limitation of mullions shall be in accordance with AAMATIR-A11 of L/175 for spans up to 13’-6” and L/240 + 1/4” for all others where L is equal to the span of mullion.

· A design professional shall be consulted to confirm that no lite of glass deflects more than H/175 or 3/4”, whichever is less, where H indicates the height of glass.· For mullions containing steel reinforcement, the reinforcement is assumed to be installed for the full length of the mullion. A design professional shall be consulted for instances where

steel reinforcement is installed for a partial length of the mullion span.· Windload pressure determinations shall be per ASCE 7 and according to local governing codes. A professional engineer shall be consulted for the most current laws and local building

codes.· Selection of perimeter fasteners and attachment of glazing system to building structure are project specific and therefore shall be reviewed and determined by a design professional.· Arcadia assumes no responsibility for selecting the appropriate systems for specific projects.

Consult Your Local Arcadia Representative For Special Applications Not Covered By These Curves.

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

ECD

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

MULL

ION

HEIG

HT IN

FEE

TMULLION SPACING IN FEET

AB

E

CD

A = 16 P.S.F. (766 Pa)B = 20 P.S.F. (958 Pa)C = 25 P.S.F. (1197 Pa)D = 30 P.S.F. (1436 Pa)E = 40 P.S.F. (1915 Pa)

As of: 08/08/16FRAMING-ARCADIA-AFG451T-WINDLOAD.pdf

Scale:

Function:Description:

Detail:OFSHEET

AFG451T Series 2" X 4 1/2" Offset Glazed For 1" Glass

Storefront Design Criteria N.T.S. 2 5

TB557 / TB205 TB557 / TB205 WITHSTEEL REINFORCEMENT

1 3/8" X 2 7/16" X 1/4"

I = 2.706 IN 4

3S = 1.112 IN

TB265

Windload Charts

· Mullions are assumed to be single span, simple beam elements, uniformly loaded and adequately braced to prevent lateral-torsional buckling. All other complex design conditions shallbe reviewed by Arcadia or a design professional.

· Aluminum extrusions shall be 6063-T6 alloy. Allowable stresses to be derived per Aluminum Design Manual. Deflection limitation of mullions shall be in accordance with AAMATIR-A11 of L/175 for spans up to 13’-6” and L/240 + 1/4” for all others where L is equal to the span of mullion.

· A design professional shall be consulted to confirm that no lite of glass deflects more than H/175 or 3/4”, whichever is less, where H indicates the height of glass.· For mullions containing steel reinforcement, the reinforcement is assumed to be installed for the full length of the mullion. A design professional shall be consulted for instances where

steel reinforcement is installed for a partial length of the mullion span.· Windload pressure determinations shall be per ASCE 7 and according to local governing codes. A professional engineer shall be consulted for the most current laws and local building

codes.· Selection of perimeter fasteners and attachment of glazing system to building structure are project specific and therefore shall be reviewed and determined by a design professional.· Arcadia assumes no responsibility for selecting the appropriate systems for specific projects.

Consult Your Local Arcadia Representative For Special Applications Not Covered By These Curves.

I = 5.061 IN 4I = 2.679 IN 4

3S = 0.977 IN1

3S = 0.118 IN2

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

MULL

ION

HEIG

HT IN

FEE

TMULLION SPACING IN FEET

A

B

E

CD

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

I = 3.701 IN 4

TB555 WITHSTEEL REINFORCEMENT

1 1/4" X 1 15/16"

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

A = 16 P.S.F. (766 Pa)B = 20 P.S.F. (958 Pa)C = 25 P.S.F. (1197 Pa)D = 30 P.S.F. (1436 Pa)E = 40 P.S.F. (1915 Pa)

As of: 10/23/19FRAMING-ARCADIA-AFG451T-WINDLOAD.pdf

Scale:

Function:Description:

Detail:OFSHEET

Z:\05 NEW WINDLOAD DEADLOAD\ARCADIA ( STEVEN TOU)\02_OFFSET GLAZING\FRAMING-ARCADIA-AFG451T-WINDLOAD.DWGSTou

AFG451T Series 2" X 4 1/2" Offset Glazed For 1" Glass

Storefront Design Criteria N.T.S. 3 5

TB558 / TB205 TB558 / TB205 WITHSTEEL REINFORCEMENT

1 3/8" X 2 1/4" X 10 GA.

Windload Charts

· Mullions are assumed to be single span, simple beam elements, uniformly loaded and adequately braced to prevent lateral-torsional buckling. All other complex design conditions shallbe reviewed by Arcadia or a design professional.

· Aluminum extrusions shall be 6063-T6 alloy. Allowable stresses to be derived per Aluminum Design Manual. Deflection limitation of mullions shall be in accordance with AAMATIR-A11 of L/175 for spans up to 13’-6” and L/240 + 1/4” for all others where L is equal to the span of mullion.

· A design professional shall be consulted to confirm that no lite of glass deflects more than H/175 or 3/4”, whichever is less, where H indicates the height of glass.· For mullions containing steel reinforcement, the reinforcement is assumed to be installed for the full length of the mullion. A design professional shall be consulted for instances where

steel reinforcement is installed for a partial length of the mullion span.· Windload pressure determinations shall be per ASCE 7 and according to local governing codes. A professional engineer shall be consulted for the most current laws and local building

codes.· Selection of perimeter fasteners and attachment of glazing system to building structure are project specific and therefore shall be reviewed and determined by a design professional.· Arcadia assumes no responsibility for selecting the appropriate systems for specific projects.

Consult Your Local Arcadia Representative For Special Applications Not Covered By These Curves.

I = 6.469 IN 4I = 5.138 IN 4

3S = 2.181 IN1

3S = 0.118 IN2

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

MULL

ION

HEIG

HT IN

FEE

TMULLION SPACING IN FEET

AB

E

CD

A = 16 P.S.F. (766 Pa)B = 20 P.S.F. (958 Pa)C = 25 P.S.F. (1197 Pa)D = 30 P.S.F. (1436 Pa)E = 40 P.S.F. (1915 Pa)

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

TB238 / TB237

I = 4.094 IN 4

3S = 1.087 IN1

3S = 0.692 IN2

AB

E

CD

I = 5.673 IN 4

TB238 / TB237 WITHSTEEL REINFORCEMENT

1 1/2" X 2" X 1/4"

As of: 10/23/19FRAMING-ARCADIA-AFG451T-WINDLOAD.pdf

Scale:

Function:Description:

Detail:OFSHEET

Z:\05 NEW WINDLOAD DEADLOAD\ARCADIA ( STEVEN TOU)\02_OFFSET GLAZING\FRAMING-ARCADIA-AFG451T-WINDLOAD.DWGSTou

AFG451T Series 2" X 4 1/2" Offset Glazed For 1" Glass

Storefront Design Criteria N.T.S. 4 5

TBD251 TBD251 WITHSTEEL REINFORCEMENT

1 1/4" X 2 3/8" X 10 GA.

Windload Charts

· Mullions are assumed to be single span, simple beam elements, uniformly loaded and adequately braced to prevent lateral-torsional buckling. All other complex design conditions shallbe reviewed by Arcadia or a design professional.

· Aluminum extrusions shall be 6063-T6 alloy. Allowable stresses to be derived per Aluminum Design Manual. Deflection limitation of mullions shall be in accordance with AAMATIR-A11 of L/175 for spans up to 13’-6” and L/240 + 1/4” for all others where L is equal to the span of mullion.

· A design professional shall be consulted to confirm that no lite of glass deflects more than H/175 or 3/4”, whichever is less, where H indicates the height of glass.· For mullions containing steel reinforcement, the reinforcement is assumed to be installed for the full length of the mullion. A design professional shall be consulted for instances where

steel reinforcement is installed for a partial length of the mullion span.· Windload pressure determinations shall be per ASCE 7 and according to local governing codes. A professional engineer shall be consulted for the most current laws and local building

codes.· Selection of perimeter fasteners and attachment of glazing system to building structure are project specific and therefore shall be reviewed and determined by a design professional.· Arcadia assumes no responsibility for selecting the appropriate systems for specific projects.

Consult Your Local Arcadia Representative For Special Applications Not Covered By These Curves.

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

MULL

ION

HEIG

HT IN

FEE

TMULLION SPACING IN FEET

AB

E

CD

I = 2.857 IN 4

3S = 1.215 INI = 4.923 IN 4

TB266 TB266 WITHSTEEL REINFORCEMENT

1 1/2" X 2 3/8" X 10 GA.

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

I = 2.915 IN 4

3S = 1.264 INI = 4.293 IN 4

A = 16 P.S.F. (766 Pa)B = 20 P.S.F. (958 Pa)C = 25 P.S.F. (1197 Pa)D = 30 P.S.F. (1436 Pa)E = 40 P.S.F. (1915 Pa)

As of: 08/08/16FRAMING-ARCADIA-AFG451T-WINDLOAD.pdf

Scale:

Function:Description:

Detail:OFSHEET

AFG451T Series 2" X 4 1/2" Offset Glazed For 1" Glass

Storefront Design Criteria N.T.S. 5 5

TBD265

Windload Charts

· Mullions are assumed to be single span, simple beam elements, uniformly loaded and adequately braced to prevent lateral-torsional buckling. All other complex design conditions shallbe reviewed by Arcadia or a design professional.

· Aluminum extrusions shall be 6063-T6 alloy. Allowable stresses to be derived per Aluminum Design Manual. Deflection limitation of mullions shall be in accordance with AAMATIR-A11 of L/175 for spans up to 13’-6” and L/240 + 1/4” for all others where L is equal to the span of mullion.

· A design professional shall be consulted to confirm that no lite of glass deflects more than H/175 or 3/4”, whichever is less, where H indicates the height of glass.· For mullions containing steel reinforcement, the reinforcement is assumed to be installed for the full length of the mullion. A design professional shall be consulted for instances where

steel reinforcement is installed for a partial length of the mullion span.· Windload pressure determinations shall be per ASCE 7 and according to local governing codes. A professional engineer shall be consulted for the most current laws and local building

codes.· Selection of perimeter fasteners and attachment of glazing system to building structure are project specific and therefore shall be reviewed and determined by a design professional.· Arcadia assumes no responsibility for selecting the appropriate systems for specific projects.

Consult Your Local Arcadia Representative For Special Applications Not Covered By These Curves.

MULL

ION

HEIG

HT IN

FEE

T

MULLION SPACING IN FEET

AB

E

CD

I = 2.771 IN 4

3S = 1.118 IN

A = 16 P.S.F. (766 Pa)B = 20 P.S.F. (958 Pa)C = 25 P.S.F. (1197 Pa)D = 30 P.S.F. (1436 Pa)E = 40 P.S.F. (1915 Pa)

As of: 10/23/19FRAMING-ARCADIA-AFG451T-DEADLOAD.pdf

Scale:

Function:Description:

Detail:OFSHEET

Z:\05 NEW WINDLOAD DEADLOAD\ARCADIA ( STEVEN TOU)\02_OFFSET GLAZING\FRAMING-ARCADIA-AFG451T-DEADLOAD.DWGSTou

AFG451T Series 2" X 4 1/2" Offset Glazed For 1" Glass

Storefront Design Criteria N.T.S. 1 2Deadload Charts for 1" Glass (7.00 PSF)

I = 0.320 IN4

CURVE REPRESENTATION

3S = 0.233 IN

GLAS

S HE

IGHT

IN F

EET

MULLION WIDTH IN FEET TB427 - 1" GLASS

A (- - - -) = 1/8 PTS.B (------) = 1/4 PTS.

AB

I = 0.232 IN4

3S = 0.164 IN

TBD435 - 1" GLASS

AB

Deadload Charts

I = 0.408 INS = 0.357 IN

A

B

4

3

GLAS

S HE

IGHT

IN F

EET

MULLION WIDTH IN FEET TBD428 - 1" GLASS

I = 0.255 INS = 0.173 IN

AB

4

3

GLAS

S HE

IGHT

IN F

EET

MULLION WIDTH IN FEET TBD436 - 1" GLASS

MULLION WIDTH IN FEET

GLAS

S HE

IGHT

IN F

EET

AB

TB436 - 1" GLASS

I = 0.229 IN4

3S = 0.161 IN

As of: 10/23/19FRAMING-ARCADIA-AFG451T-DEADLOAD.pdf

Scale:

Function:Description:

Detail:OFSHEET

Z:\05 NEW WINDLOAD DEADLOAD\ARCADIA ( STEVEN TOU)\02_OFFSET GLAZING\FRAMING-ARCADIA-AFG451T-DEADLOAD.DWGSTou

AFG451T Series 2" X 4 1/2" Offset Glazed For 1" Glass

Storefront Design Criteria N.T.S. 2 2Deadload Charts for 1" Glass (7.00 PSF)

I = 0.421 IN4

CURVE REPRESENTATION

3S = 0.373 IN

MULLION WIDTH IN FEET

GLAS

S HE

IGHT

IN F

EET

MULLION WIDTH IN FEETGL

ASS

HEIG

HT IN

FEE

TTB557 - 1" GLASS

A

B

A (- - - -) = 1/8 PTS.B (------) = 1/4 PTS.

TB558 - 1" GLASS

AB

I = 0.596 IN4

3S = 0.515 IN

Deadload Charts