windows-1256''motor branch circuit

Upload: shady-alsrougy

Post on 04-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    1/32

    Motor Branch Circuit

    41

    Good friends are hard to find, harder to leave, and impossible to forget

    4. Motor Branch CircuitBe careful, it may be dangerous

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    2/32

    Motor Branch Circuit

    42

    4.1. Motors overheating Protection

    4.1.1. Overheating reasons

    Thermal overload with slow variation

    Overload condition or loss of cooling that produces a rise of temperature that is sufficiently slow that the

    temperature of the thermal protector or detector follows it without appreciable delay. Some of the ways in which a thermal overload with slow variation may be caused are:

    Defects in ventilation or the ventilation system due to excessive dust in the ventilation ducts, or dirt

    on windings or frame cooling ribs, etc

    An excessive rise in ambient temperature or the temperature of the cooling medium

    Gradual increasing mechanical overload

    Prolonged voltage drop, over-voltage or unbalance in the machine supply

    Excessive duty on a motor rated for intermittent duty

    Frequency deviations

    Thermal overload with rapid variation

    Overload condition or loss of cooling that produces a rise of temperature that is too rapid for the

    temperature of the thermal protector or detector to follow without appreciable delay resulting in a

    significant temperature difference between the thermal device and the part to be protected.

    Some of the ways in which a thermal overload with rapid variation may be caused are:

    Stalling the motor

    Phase failure

    Starting under abnormal conditions, for example, inertia too great, voltage too low, load torque

    abnormally high

    Sudden and significant increase in load

    Starting repeatedly during a short time

    4.1.2. Motor protection requirements

    The motor can withstand Stalling, starting current and Overload for a limited periods.

    A thermal limit curve is a plot of the maximum permissible safe time versus line current in the windings of

    the machine under conditions other than normal operation. It represents the following three situations:

    a) Locked rotor

    b) Starting and acceleration

    c)

    Running overload

    The thermal limit curve is intended to be used in conjunction with the machine time-current curve for a

    normal start to set the machine protective devices for the thermal protection of the machine during starting

    and running conditions.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    3/32

    Motor Branch Circuit

    43

    Figure 4-1 Typical thermal limit curves per IEEE 620-1996

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    4/32

    Motor Branch Circuit

    44

    4.1.3. Motor Overheating protection devices

    IEC 60204

    7.3 Protection of motors against overheating Protection of motors against overheating shall be provided for each motor rated at more than 0,5 kW.

    Protection of motors against overheating can be achieved by:

    Overload protection (7.3.2),

    NOTE 1 Overload protective devices detect the time and current relationships (I2t ) in a circuit that

    are in excess of the rated full load of the circuit and initiate appropriate control responses.

    Over-temperature protection (7.3.3), or

    NOTE 2 Temperature detection devices sense over-temperature and initiate appropriate control

    responses.

    Current-limiting protection (7.3.4)

    Automatic restarting of any motor after the operation of protection against overheating shall be prevented

    where this can cause a hazardous situation or damage to the machine or to the work in progress.

    7.3.2 Overload protection

    Where overload protection is provided, detection of overload(s) shall be provided in each live conductor

    except for the neutral conductor. However, where the motor overload detection is not used for cable

    overload protection (see also Clause D.2), the number of overload detection devices may be reduced at the

    request of the user (see also Annex B).

    For motors having single-phase or DC power supplies, detection in only one unearthed live conductor is

    permitted. Where overload protection is achieved by switching off, the switching device shall switch off all live

    conductors. The switching of the neutral conductor is not necessary for overload protection.

    Where motors with special duty ratings are required to start or to brake frequently (for example, motors for

    rapid traverse, locking, rapid reversal, sensitive drilling) it can be difficult to provide overload protection with

    a time constant comparable with that of the winding to be protected. Appropriate protective devices

    designed to accommodate special duty motors or over-temperature protection (see 7.3.3) can be necessary.

    For motors that cannot be overloaded (for example torque motors, motion drives that either are protected

    by mechanical overload protection devices or are adequately dimensioned), overload protection is not

    required.

    7.3.3 Over-temperature protection

    The provision of motors with over-temperature protection (see IEC 60034-11) is recommended in situations

    where the cooling can be impaired (for example dusty environments).

    Depending upon the type of motor, protection under stalled rotor or loss of phase conditions is not always

    ensured by over-temperature protection, and additional protection should then be provided.

    Over-temperature protection is also recommended for motors that cannot be overloaded (for example

    torque motors, motion drives that are either protected by mechanical overload protection devices or are

    adequately dimensioned), where the possibility of over-temperature exists (for example due to reducedcooling).

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    5/32

    Motor Branch Circuit

    45

    4.1.4. Current dependent devices

    Figure 4-2 Typical Overload Relay

    Bimetal Overload Relays

    Consists of a small heater element wired in series with the motor and a bimetal strip that can be used as a

    trip lever. The bimetal strip is made of two dissimilar metals bonded together. The two metals have different thermal

    expansion characteristics, so the bimetal strip bends at a given rate when heated.

    Under normal operating conditions, the heat generated by the heater element will be insufficient to cause

    the bimetal strip to bend enough to trip the overload relay.

    As current rises, heat also rises. The hotter the bimetal strip becomes, the more it bends. In an overload

    condition, the heat generated from the heater will cause the bimetal strip to bend until the mechanism is

    tripped, stopping the motor.

    Figure 4-3

    Ambient Compensated Bimetal Overload Relay

    In certain applications (such as a submersible pump), the motor may be installed in a location having aconstant ambient temperature. However, the motor control and overload relay may be installed in a location

    with a varying ambient temperature. In such cases, the trip point of the overload relay will vary with the

    temperature of the surrounding air as well as current lowing through the motor, which can lead to

    premature and nuisance tripping.

    Ambient compensated bimetal overload relays are designed to overcome this problem. A compensated

    bimetal strip is used along with a primary bimetal strip. As the ambient temperature changes, both bimetal

    strips will bend equally and the overload relay will not trip the motor. However, current low through the

    motor and the heater element will affect only the primary bimetal strip. In the event of an overload

    condition, the primary bimetal strip will engage the trip unit.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    6/32

    Motor Branch Circuit

    46

    Figure 4-4

    Overload relay set value

    For continuous run motor, the overload relay must be selected such that it has a set value equal to motor

    nameplate full load current.

    This ensures that the motor doesnt run overloaded for any time and no increase of temperature.

    Condition:

    Overload relays applied must be able to carry full starting current for the entire

    acceleration period without nuisance trip.

    The previous condition can be accomplished by using higher class overload relay which preclude the need for

    selection of a higher trip current.

    A Class 20 or Class 30 overload relay will provide a longer motor acceleration time than a Class 10 or Class 20,

    respectively.

    Overload relays trip class

    Overload relays are rated by a trip class which defines the length of time it will take for the relay to trip in an

    overload condition.

    IEC 947-4-1 (Abstract)

    8.2.1.5.1 Limits of operation of time-delay overload relays when all poles are energized

    Trip time from the following state

    Cold Hot Hot Cold

    at 1.05 Ir at 1.2 Ir at 1.5 Ir at 7.2 Ir

    Class

    10A > 2 hrs < 2 hrs < 2 mins 2 s < tp < 10 s10 > 2 hrs < 2 hrs < 4 mins 4 s < tp < 10 s

    20 > 2 hrs < 2 hrs < 8 mins 6 s < tp < 20 s

    30 > 2 hrs < 2 hrs < 12 mins 9 s < tp < 30 s

    Cold state: initial state without previous load

    Hot state: thermal equilibrium reached at Ir

    Ir: setting current of the overload relay

    Example

    A motor has an accelerating time of

    = 7, a full-load current of

    =1.1and a locked-rotor current

    of = 6 . Tesys LRD-08 (From Schneider Electric) will be used as overload relay. Figure 4-5 shows the time-current characteristic of the overload used, Will the overload relay nuisance trip?

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    7/32

    Motor Branch Circuit

    47

    Figure 4-5 Trip curve for LRD overload relay

    The trip time for different rms current must be calculated, the rms value of the current is given by

    = + + + + + + (4.1)

    From equation (4) with n = 2 and solving for time , we get= + = 1 + (4.2)

    For =1.5 . = 1 + 6 1.51.11.51.1 1.1 7 =1 6 1 . 0 1 2 (4.3)

    Table 4-1 was devolved by calculating different trip times using equation (4.2)

    Table 4-1 . Time Period (s)6 5.75

    5 8.394 13.42

    3 25.16

    2 67.09

    1.5 161.01

    Values from Table 4-1 are plotted on the overload relay time current characteristic shown in Figure 4-5

    We can conclude that Class 10A overload relay will cause a nuisance trip while Class 20 will not.

    NEC requirements

    For the previous condition, if the selection of higher trip class is not sufficient for starting, then the use of an

    overload relay of higher trip current become necessary.

    In this case use the NEC to detect whether your selection meets the minimum safety requirements or not.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    8/32

    Motor Branch Circuit

    48

    NEC ARTICLE 430 Motors, Motor Circuits, and Controllers

    III. Motor and Branch-Circuit Overload Protection

    430.32 Continuous-Duty Motors

    More Than 1 Horsepower.

    Each motor used in a continuous duty application and rated more than 1 hp shall be protected against

    overload by one of the means in 430.32(A)(1) through (A)(4).

    Separate Overload Device

    A separate overload device that is responsive to motor current. This device shall be selected to trip or shall

    be rated at no more than the following percent of the motor nameplate full-load current rating:

    Motors with a marked service factor 1.15 or greater 125%

    Motors with a marked temperature rise 40C or less 125%

    All other motors 115%

    Modification of this value shall be permitted as provided in430.32(C)

    Phase Loss

    Table 4-2 shows the approximate effect upon line currents resulting from possible phase loss conditions.

    With one thermal unit per phase, if the motor is running at full load current, normal overload protection

    produces a trip for all phase loss conditions.

    If a motor is running lightly loaded at the time of the phase loss, however, the increases line current could

    still fall within the tripping current of the overload relay, this could cause serious problem

    If an application were such that the motor continuously run lightly loaded, overload protection could be

    selected based upon the actual current that removing this problem

    If the load varies, the only way to ensure protection against loss of phase is to provide a separate device

    designed for that purpose.

    Table 4-2 Line currents in case of phase loss

    Status of power supply Phase Loss During Reaction of Motor Resultant Line current

    Primary phase loss

    (Before Transformer)

    Start attempt Dont start 0.5 LRA, 0.5 LRA, LRA

    Running Continuous to run 1.15 FLA, 1.15 FLA, 2.3 FLA

    Secondary phase loss

    (After Transformer)

    Start attempt Dont start 0.87 LRA, 0.87 LRA, 0

    Running Continuous to run 1.73 FLA, 1.73 FLA, 0

    Overload relay with intermittent duty cycle

    Overload relays are not suitable for high starting duty or large numbers of switching operations. Differences

    in the thermal time constants for the overload relay and the motor results in unnecessary early tripping

    when the protection switch is set to rated current.

    Example

    A motor has a full-load current of 6 A and a locked-rotor current of 36 A. its operating cycle is:

    5 sec accelerating time, 30 sec run time, and 90 sec off time

    Will a properly selected thermal overload relay trip

    The RMS value of the current is given by

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    9/32

    Motor Branch Circuit

    49

    = 36 5 + 6 305 + 3 0 + 9 0 =7.8 Since 7.8 is about 130% of 6, the overload should eventually trip because a properly selected overload should

    produce a protection level within 115% (According to NEC)

    4.1.5. Temperature dependent devices

    Thermistor protection relay for use with PTC thermistor probes

    Thermistor protection units continuously monitor the temperature of the machines to be protected by

    means of PTC thermistor probes embedded in the machine windings.

    Thermistor probes

    Thermistors are solid state temperature sensors that behave like temperature-sensitive resistors; hence their

    name is a contraction of "thermal" and "resistor".

    There are two types : Positive Temperature Coefficient PTC (resistance increase with temperature) and

    Negative Temperature Coefficient NTC (resistance decrease with temperature). PTC thermistors are the most common in motor protection.

    If the nominal operating temperature (NOT) of the thermistor probes is reached, rapid change in resistance

    will result.

    Figure 4-6 Thermistor probes Figure 4-7 Thermistor resistance-temperature curve

    Commercial available PTC resistor sensor has a cold state resistor between 50 150 at 20 and warmstate resistor (NOT) of10000

    The PTC thermistor temperature sensors must be selected depending on:

    The motor insulation class IEC Publication 60034-11

    The motor utilization category

    The special characteristics of the motor, such as conductor cross-sections of the windings,

    permissible overload factor etc

    Special conditions prescribed by the user, such as permissible ambient temperature, risks resulting

    from locked rotor, extent of permitted overloading etc

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    10/32

    Motor Branch Circuit

    410

    Table 4-3 Possible selection of OT temperature corresponding to different insulation classes

    Insulation Class Possible Selection of NOT Temperature

    B 110

    F 140

    H 160

    In the case of three- phase squirrel cage motors for instance, three sensors are embedded in the stator

    winding. For pole-changing motors with one winding (Dahlander connection), 3 sensors are also sufficient.

    However, pole-changing motors with two windings require 6 sensors.

    Thermistor protection relay

    Thermistor protection relay convert the rapid increase in resistance into a switching function (Usually done

    by heating a bimetal strip) which can be used to switch off the motor or as a signal.

    Figure 4-8 Thermistor protection relay

    4.1.6. Comparison

    Current-dependent protection is particularly effective in the case of a locked rotor.

    For standard duty with short start-up times and starting currents that are not excessive and for low numbers

    of switching operations, Current-dependent protection provides adequate protection.

    For high starting duty, large numbers of switching operations and Impaired cooling Current-dependent

    protection is not suitable

    Table 4-4 Current vs. Temperature dependent protection devices

    Protection of the motor under the following conditions Using bimetal Using thermistor

    Overload in continuous operation + +Extended starting and stopping (+) +

    Switching to stalled rotor (stator-critical motor) + +

    Switching on stalled rotor (rotor-critical motor) (+) (+)

    Single-phasing + +

    Intermittent operation +

    Excessive frequency of operation +

    Voltage and frequency fluctuations + +

    Increased coolant temperature +

    Impaired cooling +

    + Full protection

    (+) Partial protection

    No protection

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    11/32

    Motor Branch Circuit

    411

    4.2. Control element

    4.2.1. Contactor

    Most motor applications require the use of remote control devices to start and stop the motor. Magnetic

    contactors (similar to the ones shown below) are commonly used to provide this function.

    IEC 60947-12.2.12 Contactor (mechanical)

    Mechanical switching device having only one position of rest, operated otherwise than by hand, capable of

    making, carrying and breaking currents under normal circuit conditions including operating overload

    conditions.

    NOTE Contactors may be designated according to the method by which the force for closing the main

    contacts is provided.

    2.2.14 Contactor relay

    Contactor used as a control switch.

    4.2.2. Basic Electromechanical Contactor Operation

    The following illustration shows the interior of a basic contactor. There are two circuits involved in the

    operation of a contactor: the control circuit and the power circuit.

    The control circuit is connected to the coil of an electromagnet, and the power circuit is connected to the

    stationary contacts.

    Figure 4-9

    The operation of this electromagnet is similar to the operation of the electromagnet we made by wrapping

    wire around a soft iron core.

    When power is supplied to the coil from the control circuit, a magnetic field is produced, magnetizing the

    electromagnet.

    Figure 4-10

    The magnetic field attracts the armature to the magnet, which in turn closes the contacts. With the contacts

    closed, current flows through the power circuit from the line to the load.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    12/32

    Motor Branch Circuit

    412

    When current no longer flows through the power circuit, the electromagnets coil is de-energized, the

    magnetic field collapses and the movable contacts open under spring pressure.

    4.2.3. Contactor in control circuit

    The following schematic shows the electromagnetic coil of a contactor connected to the control circuit

    through a switch (SW1).

    The contacts of the contactor are connected in the power circuit to the AC line and a three-phase motor.

    When SW1 is closed the electromagnetic coil is energized, closing the M contacts and applying power to

    the motor.

    Opening SW1 de-energizes the coil, opening the M contacts and removing power from the motor.

    Figure 4-11

    4.2.4. Contactors utilization categories

    The utilization category determines the operating frequency and endurance of a contactor. The category

    depends on the type of load. If the load is a motor; the category also depends on the service classification.

    Table 4-5

    Category lc /le cos Type of load Contactor usage Typical applications

    AC1 1 0.8 non-inductive energisation Heating, distribution

    AC2 2 0.65 slip-ring

    motors

    starting , switching off during

    running, regenerative

    braking inching

    wire drawing machines

    AC3 2 0.45 for le < 100A

    0.35 for le > 100A

    squirrel-cage

    motors

    Starting, switching off during

    running

    compressors, lifts, mixing,

    pumps, escalators, fans,

    conveyers, air-conditioning

    AC4 6 0.45 for le < 100A

    0.35 for le > 100A

    squirrel-cage

    motors

    starting, switching off during

    running, regenerative

    braking, plugging, inching

    printing machines, wire

    lc : Current made or broken

    le: rated operational current

    AC3 utilization category

    This category covers asynchronous squirrel-cage motors that are switched off during running. This is the

    most common situation (85 % of all cases).

    The control device establishes the starting current and interrupts the rated current at a voltage equal toapproximately one-sixth of the rated value. Current interruption is carried out with no difficulty.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    13/32

    Motor Branch Circuit

    413

    Figure 4-12 AC3 utilization category, the contactor interrupts the rated current of the motor.

    AC4 utilization category

    This category covers asynchronous squirrel-cage or slip-ring motors capable of operating under regenerative-

    braking or inching (jogging) conditions.

    The control device establishes the starting current and is capable of interrupting the starting current at a

    voltage that may be equal to that of the mains.

    Such difficult conditions require oversizing of the control and protective devices with respect to category

    AC3.

    Figure 4-13 AC4 utilization category, the contactor must be capable of interrupting the starting current Id.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    14/32

    Motor Branch Circuit

    414

    4.3. Starter

    IEC 60947-1

    2.2.15 Starter

    Combination of all the switching means necessary to start and stop a motor, in combination with suitable overload

    protection

    Figure 4-14 Starter

    4.3.1. Starting methods

    The most common starting methods for asynchronous squirrel-cage motors are detailed below

    Direct starting

    With direct starting, the DOL (Direct On Line) starter, with the closing of line contactor KM1, the line voltage

    is applied to the motor terminals in a single operation. Hence a squirrel-cage motor develops a high starting

    torque with a relatively reduced acceleration time.

    This method is generally used with small and medium power motors which reach full working speed in a

    short time.

    Figure 4-15 D.O.L. starter with contactor and O/L relay Figure 4-16 Torque/speed curve at Star-Delta start

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    15/32

    Motor Branch Circuit

    415

    These advantages are, however, accompanied by a series of drawbacks, including, for example:

    high current consumption and associated voltage drop which may cause damages to the other parts

    of the system connected to the network

    violent acceleration which has negative effects on mechanical transmission components (belts,

    chains and mechanical joints), reducing working life

    Other types of starting for squirrel-cage motors are accomplished by reducing the supply voltage of the

    motor: this leads to a reduction in the starting current and of the motor torque, and an increase in the

    acceleration time.

    Star-Delta starter

    The most common reduced voltage starter is the Star-Delta starter (Y-), in which

    The motor is designed to operate in delta connection winding.

    on starting, the stator windings are star-connected, thus achieving the reduction of peak inrush

    current;

    once the normal speed of the motor is nearly reached, the switchover to delta is carried out

    After the switchover, the current and the torque follow the progress of the curves associated withnormal service connections (delta).

    As can be easily checked, starting the motor with star-connection gives a voltage reduction of3, and thecurrent absorbed from the line is reduced by 1/3 compared with that absorbed with delta-connection.

    The start-up torque, proportional to the square of the voltage, is reduced by 3 times, compared with the

    torque that the same motor would supply when delta-connected.

    This method is generally applied to motors with power from 15 to 355 kW, but intended to start with a low

    initial resistant torque.

    Figure 4-17 Star-delta starter with contactors and O/L relay - Torque/speed curve

    4.3.2. Motor Starter in a Control Circuit

    The following diagram shows the electrical relationship of the contactor and overload relay. The contactor

    (highlighted with the darker grey) includes the electromagnetic coil, the main motor contacts, and the

    auxiliary contacts. The overload relay, highlighted by the lighter grey, includes the OL heaters and overload

    contacts.

    The contactor and the overload relay have additional contacts (known as auxiliary contacts) for use in thecontrol circuit.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    16/32

    Motor Branch Circuit

    416

    In this circuit, a normally closed OL contact has been placed in series with the M contactor coil and L2.

    A normally open M auxiliary contact (Ma) has been placed in parallel with the Start pushbutton.

    Figure 4-18

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    17/32

    Motor Branch Circuit

    417

    4.4. Starter short Circuit Protection

    4.4.1. Development of the short-circuit current (far from generator)

    A simplified network comprises a source of constant AC power, reactance X and resistance R is shown below

    Here, X and R replace all components such as cables, conductors, transformers and motors.

    Figure 4-19

    When a fault occurs between A and B, the negligible impedance between these points results in a very high

    short-circuit current that is limited only be impedance .

    The following differential equation can be used to describe the short circuit process:

    Where is the phase angle at the point in time of the short circuit.

    Equation (4.5) is Inhomogeneous first order differential equation can be solved by determining the

    homogenous solution

    i and a particular solution

    i

    For particular solution, we obtain:

    The homogenous solution yields:

    The total short circuit current is composed of both components:

    For far-from-generator short circuit, the short circuit current is therefore made up o a constant AC periodic

    component and a decaying DC periodic component.

    Figure 4-20 Shows the time behavior of the short circuit current for the occurrence of far-from-generator

    The peak value used to determine the making capacity of the required circuit breakers and to define theelectrodynamic forces that the installation as a whole must be capable of withstanding can be calculated

    from

    Where = 1.02 + 0.98 e

    = + (4.4)

    + = 2 sin + (4.5)

    = + = + (4.6)

    = 2 sin + = 2 sin + (4.7)

    = 2 sin (4.8)

    = 2 sin + sin (4.9)

    = (4.10)

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    18/32

    Motor Branch Circuit

    418

    Figure 4-20 Time behavior of the short circuit current for the occurrence of far-from-generator

    4.4.2. Short Circuit current calculations (Impedance Method)

    Calculation of =

    Where

    U: (phase-to-phase voltage) corresponds to the transformer no-load voltage

    : as given in (4.4)

    : Sum of all series resistances upstream of the fault: Sum of all series resistances upstream of the fault

    Transformer no-load voltage is 3 to5% greater than the on-load voltage across the terminals. For example, in380 V networks, the phase-to-phase voltage adopted is U = 399 V

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    19/32

    Motor Branch Circuit

    419

    Determining the various short-circuit impedances

    Upstream network impedance referred to secondary in m

    Where

    : The no-load phase-to-phase voltage of the network in V

    : Short-circuit power in KVA (Data supplied by the power distributor) Resistance: negligible

    Reactance:

    Internal transformer impedance referred to secondary in m

    where

    : No-load phase-to-phase voltage of the transformer (V)

    : Transformer KVA rating; : Voltage that must be applied to the primary winding of the transformer for the rated current to

    flow through the secondary winding, when the LV secondary terminals are short circuited.

    For public distribution MV / LV transformers, the values ofuhave been set by the European Harmonizationdocument HD 428-1S1 issued in October 1992

    Resistance in m

    Where:

    : Windings losses in (KW) : Transformer rated current (A)

    Reactance in m

    Line impedance

    Resistance in m

    Where

    : Resistivity in mmm2/m

    : Length in m

    : Cross section area in mm2

    The resistivity of copper is = 21 m mm/m while for aluminum is = 33 m mm/m

    = (4.11)

    = (4.12)

    =

    100

    (4.13)

    Rating (kVA) of the MV / LV transformer 630 800 1,000 1,250 1,600 2,000

    Short-circuit voltage (%) 4 4.5 5 5.5 6 7

    = 3 (4.14)

    = (4.15)

    = (4.16)

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    20/32

    Motor Branch Circuit

    420

    Reactance in m

    Table 4-6 Cables reactance values depending on the wiring system

    Wiring system Busbars Three-

    phase

    Spaced single-

    core

    Touching

    single core

    cables

    (triangle)

    3 touching

    cables (flat)

    3 d spaced

    cables (flat)

    d = 2r d = 4r

    Diagram

    Reactance per

    unit length

    values

    recommended in

    UTE C 15-105

    (m/m)

    0.08 0.13 0.08 0.09 0.13 0.13

    Average

    reactance

    per unit length

    values (m/m)

    0.15 0.08 0.15 0.085 0.095 0.145 0.19

    Extreme

    reactance

    per unit length

    values (m/m)

    0.12-0.18 0.06-0.1 0.1-0.2 0.08-0.09 0.09-0.1 0.14-

    0.15

    0.18-

    0.20

    LV circuit breakers Resistance: negligible

    Reactance: Value of 0.15 m is typical

    4.4.3. How do short circuit damage motor starter?

    Since we are concerned with the damage to the motor starter caused by the short circuit, lets look briefly at

    what causes that damage before we address how Type 2 coordination is achieved.

    There are two things that cause short circuit damage; one is magnetic forces and the second is excessive

    heat. Both of these are a function of the current.

    Magnetic forces are a function of the instantaneous peak let-through current (Ip) passed by the SCPD.

    This is the current that flows in the circuit before the SCPD can respond to the current and open the

    circuit.

    Magnetic forces put physical stress on the starter. The forces cause the contacts of the starter to

    blow apart and can cause the housing of the starter to fracture, both of which can render the

    starter inoperable.

    Excessive heat is a function of let-through energy (I2t), the current squared over a period of time, during the

    clearing of the short circuit fault current by the SCPD. Excessive heat generally causes the contacts of the

    motor starter to weld.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    21/32

    Motor Branch Circuit

    421

    4.4.4. How can short circuit damage to motor starter be minimized?

    There are a number of ways that the damage can be minimized including: using physically larger, more

    rugged starters and using better protecting short circuit protective devices.

    In general, the ability of a starter to withstand a short circuit fault current (and not be damaged) is a function

    of its physical size and construction. Typically, starters of approximately the same physical size will be

    capable of withstanding the same amount of short circuit fault current.

    Damage to a starter caused by magnetic forces can be minimized by increasing the electrical

    clearances between current paths and supporting the current carrying parts with more insulating

    material (robust moldings with large cross sectional areas).

    Damage caused by excessive heat can be minimized by incorporating larger current carrying parts

    with higher contact mass in the starter.

    Larger parts can absorb more heat, reducing the possibility of the parts welding. The disadvantage of trying

    to minimize damage with this approach is that it increases the size of starter, which in turn increases the size

    of the control panel and ultimately the facility. In addition, more material equates to higher costs.

    A second way to limit damage to a motor starter is to use better protecting (faster acting, more current

    limiting) short circuit protective devices.

    Since short circuit damage is a function of the current passed by the SCPD, limiting that current will minimize

    the damage to the starter.

    4.4.5. Current Limiting MCCB as SCPD

    IEC 60947-2

    2.3 Current-limiting circuit-breaker

    A circuit-breaker with a break-time short enough to prevent the short-circuit current reaching its otherwise

    attainable peak value.IEC 60947-1

    2.5.5 prospective current (of a circuit and with respect to a switching device or a fuse)

    current that would flow in the circuit if each pole of the switching device or the fuse were replaced by a

    conductor of negligible impedance

    2.5.6 prospective peak current

    peak value of a prospective current during the transient period following initiation

    Figure 4-21 Figure 4-22 shows the limit curve for Tmax T2L160, In160 circuit-breaker.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    22/32

    Motor Branch Circuit

    422

    The x-axis shows the effective values of the symmetrical prospective short-circuit current, while the y-axis

    shows the relative peak value. The limiting effect can be evaluated by comparing, at equal values of

    symmetrical fault current, the peak value corresponding to the prospective short-circuit current (curve A)

    with the limited peak value (curve B).

    Circuit-breaker T2L160 with thermomagnetic release In160 at 400 V, for a fault current of 40 kA, limits the

    short-circuit peak to 16.2 kA only, with a reduction of about 68 kA compared with the peak value in the

    absence of limitation 84 kA).

    Figure 4-22

    4.4.6. Types of co-ordination

    Achieving proper co-ordination means matching the characteristics of SCPD and the downstream equipment

    including cables to ensure that the let-through energy and peak cut-off current do not rise above the levels

    that the starter can withstand

    4.4.7. How is certified Type 2 co-ordination achieved?

    The only way to ensure Type 2 co-ordination is to carry out exhaustive tests (found in IEC 60947-4) on

    particular MCCB with the starter. Usually Starter and MCCB manufacturers do this test on different combination of them, so all we have to do

    is select a prober one from the manufacturers coordination tables

    IEC 60947-4-1

    8.2.5 Co-ordination with short circuit protective devices

    Two types of co-ordination are permissible

    Type 1 co-ordination requires that, under short-circuit conditions, the contactor or starter shall cause no

    danger to persons or installation and may not be suitable for further service without repair and replacement

    of parts.

    Type 2 co-ordination requires that, under short-circuit conditions; the contactor or starter shall cause no

    danger to persons or installations and shall be suitable for further use.

    The risk of contact welding is recognized, in which case the manufacture shall indicate the measures to

    be taken as regards the maintenance of the equipment

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    23/32

    Motor Branch Circuit

    423

    4.4.8. Example of Coordination Tables

    Table 4-7 ABB

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    24/32

    Motor Branch Circuit

    424

    Table 4-8 Schneider Electric

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    25/32

    Motor Branch Circuit

    425

    4.5. Cables

    4.5.1. Select the cable type

    The following parameters are used to select the cable type:

    Conductive material (copper or aluminum)

    The choice depends on cost, dimension and weight requirements, resistance to corrosive environments

    (chemical reagents or oxidizing elements).

    In general, the carrying capacity of a copper conductor is about 30% greater than the carrying capacity of an

    aluminum conductor of the same cross section.

    An aluminum conductor of the same cross section has an electrical resistance about 60% higher and a weight

    half to one third lower than a copper conductor.

    Insulation material (none, PVC, XLPE-EPR)

    The insulation material affects the maximum temperature under normal and short-circuit conditions and

    therefore the exploitation of the conductor cross section

    Table 4-9 - Maximum operating temperatures for types of insulationType of insulation Temperature limit ( C )

    Polyvinyl-chloride (PVC) 70 at the conductor

    Cross-linked polyethylene (XLPE) and ethylene propylene rubber (EPR) 90 at the conductor

    Mineral (PVC covered or bare exposed to touch) 70 at the sheath

    Mineral (bare not exposed to touch and not in contact with combustible material) 105 at the sheath

    Conductor type

    The type of conductor (bare conductor, single-core cable without sheath, single- core cable with sheath,

    multi-core cable) is selected according to mechanical resistance, degree of insulation and difficulty of

    installation (bends, joints along the route, barriers...) required by the method of installation.

    4.5.2. Cable Sizing

    Step 1: Load current calculation

    Load current in A for a three-phase system is calculated by the following formula:

    Where

    : rated load input power (W): Operating line voltage (V)

    : Power factor

    Step 2: Methods of installation

    To define the current carrying capacity of the conductor and therefore to identify the correct cross section

    for the load current, the standardized method of installation that better suits the actual installation situation

    must be identified among those described in Appendix B

    Step 3: Correction factor for temperature The current carrying capacity of the cables that are not buried in the ground refers to 30 C ambienttemperature. If the ambient temperature of the place of installation is different from this reference

    temperature, the correction factor k1 on Table 4 shall be used, according to the insulation material.

    = 3 (4.17)

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    26/32

    Motor Branch Circuit

    426

    Table 4-10 Correction factor for ambient air temperature other than 30 C

    Step 4: Correction factor for grouping The cable current carrying capacity is influenced by the presence of other cables installed nearby. The heat

    dissipation of a single cable is different from that of the same cable when installed next to the other ones.

    The factor is tabled according to the installation of cables laid close together in layers or bunchesTable 4-11 Groupping reduction factor

    Step 5: Apparent load current

    Calculate the value of current by dividing the load current (or the rated current of the protective device)by the product of the correction factors calculated:

    Step 6: Determine the cross sectional area

    From Table 4-12 or from Table 4-13 , depending on the method of installation, on insulation and conductive

    material and on the number of live conductors, determine the cross section of the cable with capacity

    The actual cable current carrying capacity is calculated by

    =

    (4.18)

    = (4.19)

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    27/32

    Motor Branch Circuit

    427

    Table 4-12 Current carrying capacity of cables with PVC or EPR/XLPE insulation (method A-B-C)

    Table 4-13 Current carrying capacity of cables with PVC or EPR/XLPE insulation (method E-F-G)

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    28/32

    Motor Branch Circuit

    428

    4.5.3. Example of Cable sizing in a balanced three- phase circuit

    load current: 100 A

    conductor material: copper

    insulation material: PVC

    type of cable: multi-core

    installation: cables bunched on horizontal perforated tray

    Installation conditions:

    ambient temperature: 40 C

    adjacent circuits with three-phase circuit consisting of 4 single-core cables, 4x50 mm2

    three-phase circuit consisting of one multi-core cable, 1x(3x50) mm2

    three-phase circuit consisting of 9 single-core (3 per phase) cables, 9x95

    mm2

    single-phase circuit consisting of 2 single-core cables, 2x70 mm2

    Type of installation

    In Appendix A, it is possible to find the reference number of the installation and the method of installation to

    be used for the calculations. In this example, the reference number is 31, which corresponds to method E

    (multi-core cable on tray).

    Correction factor of temperature

    From Table 4-10, for a temperature of 40 C and PVC insulation material,

    =0.87 Correction factor of grouping

    For the multi-core cables grouped on the perforated tray see Table 5.

    As a first step, the number of circuits or multi-core cables present shall be determined; given that:

    each circuit a), b) and d) constitute a separate circuit;

    circuit c) consists of three circuits, since it is composed by three cables in parallel per phase;

    The cable to be dimensioned is a multi-core cable and therefore constitutes a single circuit;

    The total number of circuits is 7.

    Referring to the row for the arrangement (cables bunched) and to the column for the number of circuits (7)

    After and have been determined, is calculated by:

    From Table 4-13, for a multi-core copper cable with PVC insulation, method of installation E, with three

    loaded conductors, a cross section with current carrying capacity of =212.85 , is obtained. A 95 mm2 cross section cable can carry, under Standard reference conditions, 238 A.

    The current carrying capacity, according to the actual conditions of installation, is

    =0.54 = = 1000.870.54 =212.85

    =2380.870.54=111.81

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    29/32

    Motor Branch Circuit

    429

    4.5.4. Cables Protection against overload

    The Standard IEC 60364-4-43 Electrical installation of buildings - Protection against overcurrent specifies

    coordination between conductors and overload protective devices (normally placed at the beginning of the

    conductor to be protected)

    IEC 60364-4-43

    433.1 (433.2) Co-ordination between conductors and overload protective devices

    The operating characteristics of a device protecting a cable against overload shall satisfy the two following

    conditions:

    Where

    the current for which the circuit is designed

    the continuous current-carrying capacity of the cable (see clause 523)

    the nominal current of the protective deviceNOTE For adjustable protective devices, the nominal current , is the current setting selected The current ensuring effective operation in the conventional time of the protective device.

    The current ensuring effective operation of the protective device is given in the product standardor may be provided by the manufacturer.

    NOTE Protection in accordance with this clause does not ensure complete protection in certain cases, for

    example sustained overcurrent less than , nor will it necessarily result in an economical solution. Thereforeit is against assumed that the circuit is so designed that small overloads of long duration will not frequently

    occur

    (4.20) 1 . 4 5 (4.21)

    According to first condition to correctly choose the protective device, it is necessary to check that the circuit-

    breaker has a rated (or set) current that is:

    Slightly higher than the load current, to prevent unwanted tripping;

    Lower than the current carrying capacity of the cable, to prevent cable overload.

    The Standard allows an overload current that may be up to 45% greater than the current carrying capacity of

    the cable but only for a limited period (conventional trip time of the protective device).

    The verification of second condition is not necessary in the case of circuit-breakers because the protective

    device is automatically tripped if:

    = 1 . 3 for circuit-breakers complying with IEC 60947-2 (circuit-breakers for industrial use);

    =1 . 4 2 for circuit-breakers complying with IEC 60898 (circuit-breakers for household andsimilar installations).

    Therefore, for circuit-breakers, if , the formula 1 . 4 5 will also be verified.

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    30/32

    Motor Branch Circuit

    430

    4.5.5. Protection against short-circuit

    A cable is protected against short-circuit if the specific let-through energy of the protective device (I2t) is

    lower or equal to the withstood energy of the cable (k2S

    2):

    Where

    the effective short-circuit current expressed as r.m.s. value (A)the short circuit duration (s)

    factor taking account of the resistivity, temperature coefficient and heat capacity of the

    conductor material, and the appropriate initial and final temperatures.

    the cable cross section (mm2)

    in the case of conductors in parallel it is the cross section of the single conductor

    is the specific let-through energy of the protective device which can be read on the curves supplied bythe manufacturer or from a direct calculation in the case of devices that are not limiting and delaying;

    depends on the cable insulating and conducting material. The values of the most common installations are

    shown in Table 1.Table 4-14 Values of k for phase conductor

    Conductor insulation

    PVC300

    mm2

    PVC>300

    mm2

    EPR

    XLPE

    Rubber

    60 C

    Mineral

    PVC Bare

    Initial temperature C 70 70 90 60 70 105

    Final temperature C 160 140 20 200 160 250

    Material of conductor:

    Copper 115 103 143 140 115 135/115

    a

    Aluminum 76 68 94 93 - -

    in-soldered joints in copper

    conductors

    115 - - - - -

    aThis value shall be used for bare cables exposed to touch.

    NOTE 1 Other values of k are under consideration for.

    small conductors (particularly for cross section less than 10 mm2);

    duration of short-circuit exceeding 5 s;

    other types of joints in conductors;

    Bare conductors.

    NOTE 2 The nominal current of the short-circuit protective device may be greater than the current carrying

    capacity of the cable

    NOTE 3 The above factors are based on IEC 60724.

    Example

    For the simplified network shown in Figure 4-23

    Figure 4-23

    If a fault occur at point F, with short circuit current available = 40 , T2S160MA 100 MCCB is used forcable protection against short circuit, is it capable to do so?

    (4.22)

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    31/32

    Motor Branch Circuit

    431

    A current limiting MCCB must break the fault in less than half cycle 0.01 sec, the current that 16 mm2 copper

    cable can withstand for this time is given by:

    From the circuit breaker limiting curve, it can be shown that it limit the 40 KA prospective fault current to 10

    KA only, so the circuit breaker is able to protect the cable under this fault

    Figure 4-24 T2 160 Limiting curve

    = = 115 160.01 =18.400(4.23)

  • 7/29/2019 Windows-1256''Motor Branch Circuit

    32/32

    Motor Branch Circuit

    References1. IEEE Std C37.96-2000 IEEE Guide for AC Motor Protection

    2. IEEE Std 620-1996 IEEE Guide for the Presentation of Thermal Limit Curves for Squirrel Cage Induction

    Machines

    3. IEC 60204-1 Safety of machinery - Electrical equipment of machines Part 1: General requirements

    4. IEC 60947 Low-voltage switchgear and control gear Part 1: General rules

    Part 2: Circuit-breakers

    Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units

    Part 4-1: Electromechanical contactors and motor-starters

    5. National Electrical Code NEC 2008 Edition

    6. Motor and Branch-Circuit overload protection: A Guide in solving problems

    7. Siemens Course: Control Components

    8. IEC 60909-2 Short-circuit currents in three-phase AC systems Part 2: Data for short-circuit current

    calculations

    9. Schneider-electric Cahier technique no. 158: Calculation of short-circuit currents

    10.PAUL E. ALWIN: IEC Type 2 Coordination for Short Circuit Protection of Motor Starters, IEEE 1993 Annual

    Textile, Fiber and Film Industry Technical Conference, 1993.

    11. IEC 60364-4-4 Electrical installations of buildings

    Part 4-43: Protection for safety - Protection against overcurrent

    Part 5-52: Selection and erection of electrical equipment - Wiring systems

    12.Electrical installation handbook -ABB

    13.Electrical Installation Guide according to IEC International Standards- Schneider Electric