wireless tecs w/coordinator important to note – objective of

14
Wireless TECs w/Coordinator

Upload: others

Post on 03-Feb-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Wireless TECs w/Coordinator

Presenter
Presentation Notes
Important to note – objective of this product is a niche to reduce the cost of retrofit opportunities or projects that require prohibitive comm trunk costs. If an equipment or automation retrofit is occuring – this option could reduce cost substantially. Integration into Metasys NAE can be accomplished through BACnet IP or BACnet MSTP. All current TEC products will be wireless communication capable -

Wireless TECs w/Coordinator

FX40

Wireless Coordinator

Zigbee Ready Communication Module

2.4 Ghz based on 802.15.4 mesh

All TEC models to be wireless capable

Approx. 30 TEC’s / Coordinator, 100 per NAE trunk

Auto Configuring Database

Simple, software set-up utility

Elementary tech training required

Scalable – multiple Coordinators / System

JCI open protocol – BACnet IP and MS/TP

Presenter
Presentation Notes
Important to note – objective of this product is a niche to reduce the cost of retrofit opportunities or projects that require prohibitive comm trunk costs. If an equipment or automation retrofit is occuring – this option could reduce cost substantially. Integration into Metasys NAE can be accomplished through BACnet IP or BACnet MSTP. All current TEC products will be wireless communication capable -

Application ScopeWireless TECs w/Coordinator

• Targeted at retrofit applications where installing a communication trunk is cost prohibitive or disruption to the current business or infrastructure is sensitive.

• New construction where installing communication trunk in a region requires higher cost code / labor compliance.

• Early adopter in wireless technology

Wireless TECs w/CoordinatorStaged Versions

Single Stage

Unit heaters, fan coil unit, and single-stage packaged heating/cooling equipment

Heat Pump

Heat pump with up to 3 heating/2 cooling stages

Multi-Stage

Multi-staged packaged heating/cooling stages

Economizer

Packaged rooftop units with economizers

2-4 Pipe Fan Coil and Zoning VersionsOutputs for Valves & Dampers

2 On/Off outputs

2 Floating outputs

1 or 2 Proportional outputs

Fan Control

None (zone version)

1, 2 or 3 speed

Dehumidification Capability

Presenter
Presentation Notes
All of the current TEC’s will be capable of the wireless communication capability.

Wireless

– Focus of wireless development on replacing the network wiring.

– This allows for centralization of stand-alone equipment.

– No need to run Extra-Wiring for communication which in turn lowers installation costs.

– Benefits well suited to retrofit projects on existing equipment.

– Wired Network interface replaced with Wireless 802.15.4 (ZigBee) radio.

– Network image from wired world duplicated.

The Wireless Coordinator & Thermostats– Wireless Coordinator developed to

provide a simple way in which to integrate wireless thermostats into today’s “open-systems”

– Coordinator provides wireless network access point.

– Also serves as thermostat / network configuration tool.

– Converts 802.15.4 – JCI wireless thermostat messages to familiar BACnet objects

– Supports 30 JCI Thermostats per coordinator.

– Connects easily to BACnet IP or MS/TP network for integration.

Zoning

VT7300 Fan Coil

Roof Top/ Heat Pump

TEC with PIR Sensor

Wireless Coordinator

– Existing Wiring from Equipment (Y-W-G) re-used.

– TEC wireless network thermostat transmits data wirelessly to gateway:

– Occupancy.

– Room set points

– equipment status

Wireless thermostat

Wireless thermostat

Y, W, R, G Interface

RTU

I/o Wiring

Total System Architecture

Wireless messages converted to Open protocol for integration at supervisor level.

BACnet IP

BACnet MS/TP

Network Field Wiring Eliminated!

Supervisory Controller

Mesh Topology Wireless Network

Hardwired & WirelessWireless TECs w/Coordinator

Must select wireless coordinator location to ensure within wireless mesh.Local setup of thermostat to include PAN ID and Channel (wireless frequency)Local configuration of the wireless coordinator to ensure all PAN ID, Channel match specified TEC’s.No daisy chain wiring of the RS485 trunk and potential for improper wiring!

Application ScopeWireless TECs w/Coordinator

Application ScopeWireless TECs w/Coordinator

Typical Retrofit Application– Hotel project with existing multispeed

fan coil units.

– Fan coils controlled by existing electronic thermostats.

– Existing controls do not support centralization.

– Thermostats replaced with VT7000 series wireless thermostat.

– After some brief address settings and gateway configuration the wireless mesh is functional.

– Information ready for integration.

Tec Wireless Coordinator Installed on each floor.

Coordinator(s) connected with Category 5 riser.

Integration accomplished over IP network at supervisory controller.