wires and cables for industrial applications - · pdf filewire+cable division 8330...
TRANSCRIPT
HUBER+SUHNER Excellence in Connectivity Solutions
8404
7253
/12.
2007
HUBER+SUHNER – Excellence in Connectivity Solutions
HUBER+SUHNER is a leading global supplier of componentsand systems for electrical and optical connectivity incommunications, industrial and trans portation markets.HUBER+SUHNER can draw on core competences in the
areas of high frequency technology, fibre optics, cables andpolymers. Working in close collaboration with our customersaround the globe, we strive for excellence in the developmentand manufacturing of high quality products.
COMMUNICATION INDUSTRY TRANSPORTATION
Communication Networks/Communication Equipment Railway/Automotive Instrumentation/Space+Defence/Industrial Wiring
HUBER+SUHNER AGWire+Cable Division8330 Pfäffikon ZH, SwitzerlandPhone +41 (0)44 952 22 11Fax +41 (0)44 952 26 70www.hubersuhner.com
WAIVERIt is exclusively in written agreements that we provide our customers with warrants and represen-tations as to the technical specifications and/or the fitness for any particular purpose. The facts and figures contained herein are carefully compiled to the best of our knowledge, but they are intended for general informational purposes only.
HUBER+SUHNER is certified according to ISO 9001 and ISO 14001.
Cab
les
Asse
mblies
Connectors
RADIO FREQUENCY
AntennasLightning
Protection
FIBEROPTIC LOWFR
EQUEN
CY
Cables
Assemblies
ConnectorsMasterline Systems Wires+Cables
Connec
tors
Harne
sses
Syste
ms
WIRES AND CABLESFOR INDUSTRIAL APPLICATIONS
Edition 2008
WIR
ES A
ND
CA
BLES
FO
R IN
DU
STRI
AL
APP
LIC
ATI
ON
S
FURTHER CATALOGUES
RADOX® wires and cables for the coil winding industryItem Nr. 84022718
RADOX® solar system solutions for photovoltaic installationsItem Nr. 84017606
HUBER+SUHNER 1
Intro
duct
ion
Wires and cables for industrial applications
Introductionpages 3 – 19
Flexible single cores, cables andwires RADOX® 125,RADOX® 155, KDJ-11pages 20 – 49
Flexible single cores, cablesand wires UL recognisedpages 50 – 77
RADOX® system cablespages 78 – 113
RADOX® solar cablespages 114 – 125
RADOX® FR safety cables with circuit integrity in case of firepages 126 – 147
Technical informationpages 149 – 179
2 HUBER+SUHNER
HUBER+SUHNER 3
Intro
duct
ion
RADOX® by HUBER+SUHNER -
for the toughest conditions
RADOX® is the brand name for a HUBER+SUHNER electron beam crosslinked plastic compound based on polyolefin copolymers. It's high temperature resistance, flame retardance, reduced wall thickness and easy processability make it the ideal insulating material for wires and cables in the coil winding industry.
We can also provide customer specific solutions.
All our cables fully comply with the European directives 76/769/EWG, 2003/11/EG, 2000/53/EG, 2003/53/EG and 2002/95/EG (RoHS).
4 HUBER+SUHNER
HUBER+SUHNER 5
Intro
duct
ion
Single core/multi core cables for power and
signal transmission in industrial applications
Multi core cables, single core cables and system solutionsRADOX• ® multi core and single core cablesRADOX• ® eco-F single core cablesRADOX• ® UL cables
RADOX® multi core and single core cables have a high power handling capacity and heat resistance. They have been specifically designed for the construction of high-performance, compact and light-weight equip-ment.
outstanding heat resistance•high power handling capacity •ruggedness and compact design•high flexibility•easy processing•
Electronic control systems automatically control processes, transmit data and govern motions such as swivelling and conveying etc. The reliability and uptime of such highly automated, complex technical systems isnecessary to ensure the efficiency of state-of-the-art production processes. Trouble-free power supply must also be assured at all times. Our cables and system solutions are therefore applied precisely in areas where dependability is a top priority and outstanding heat resistance, high power handling capacity, ruggedness and compact design are a must.
6 HUBER+SUHNERStabag Apparatebau AG, Balzers
HUBER+SUHNER 7
Intro
duct
ion
Single core/multi core cables for power and
signal transmission in automation applications
Top quality cables for industrial automation applications with a long service life
RADOX• ® multi core and single core cableshybrid cables•
Our single core and multi core cables are distinguished by their thin insu-lation walls and their tight bending radius. The hybrid cables offer a multi functional solution in a single cable.
thin insulation walls •tight bending radii•high flexibility•abrasion resistance •high power handling capacity •long service life •
The field of industrial automation has extremely rigorous demands on the performance and quality of the cables used. A cable will achieve top performance only if it offers absolute flexibility and a long service life. In addition, these products must satisfy highly specific customer requirements. Our modular system is the ideal solution for responding to such needs.
8 HUBER+SUHNER
HUBER+SUHNER 9
Intro
duct
ion
RADOX® eco-F and RADOX® 155 are flexible single core and multi core cables offering excellent resistance to heat, hot pressure and aging. The electronically crosslinked insulation offers high mechanical ruggedness. It will not melt and is resistant to most media as well as insulating varnishes and impregnating resins. Brief exposure to heat up to +280 °C will not have any lasting effect.
The insulation of RADOX® eco-F is halogen free and will not release any corrosive gases in case of a fire. It generates minimum smoke, and its flame retarding properties prevent fires from spreading.
You will find more detailed information and the description of additional products for the coil winding products industry in the "RADOX® wires and cables for the coil winding industry" catalogue, item no. 84022718.
Single core/multi core cables for power and
signal transmission in coil winding applications
Flexible single core cables and wires for coil winding productsRADOX• ® 155, wires and flexible cablesRADOX• ® eco-FRADOX UL and KDJ cables•
These transmission lines offer high power handling capacity and heat resistance. They require little space and therefore allow the construction of high performance yet compact and light weight equipment.
10 HUBER+SUHNER
HUBER+SUHNER 11
Intro
duct
ion
Our RADOX® insulation material for cables was developed with special applications in mind which require high reliability even under adverse environmental conditions. It offers excellent resistance to heat and chemi-cals as well as to electrical and mechanical stressing. Our single-core and multi-core cable solutions for marine applications are suitable for sta-tionary as well as mobile uses. They have small diameters, standardised dimensions and require only a short time to install.
Single core and multi core cables for power
and signal transmission in marine applications
Marine cables with GL, DNV and BV approvalsRADOX• ® 125RADOX• ® 125 IEC marine transmission lineRADOX• ® MFH control, data and power transmission lines for marine applications
These cable types are particularly distinguished by their resistance to fuels and lubricants, alkalis and acids.
light weight, space saving hybrid solutions meeting the most rigorous •demandshighly abrasion resistant single cores for corrugated copper cables•customised, multifunctional system cables•versatile cable and element combinations•high temperature data bus for marine applications•
12 HUBER+SUHNER
HUBER+SUHNER 13
Intro
duct
ion
Single core and multi core cables for power
and signal transmission in solar applications
Solar cables with TÜV and UL approvalRADOX• ® solar cable single and multiple core/screenedRADOX• ® SMARTRADOX• ® SolarLink
RADOX® solar cables are flexible single core and multi core cables that have been specially designed for the wiring of solar systems.
range of application –40 °C to +120 °C•short circuit strength up to +280 °C•RADOX• ® electronic cross linked materials will neither melt nor flow even when exposed to high temperatureshigh UV, ozone and hydrolysis resistance •excellent mechanical ruggedness and resistance to water, oils and •chemicalsproven of many years of field application worldwide•TÜV and UL approvals•connectors and connection boxes available •
RADOX® solar cables are extremely rugged and abrasion-resistant and are capable of withstanding extreme mechanical stressing. Their high temperature and excellent weatherproof ensure a long service life of the cable. Thanks to the technology and high precision of RADOX® products, these outstanding characteristics are achieved also with small diameters.
14 HUBER+SUHNER
HUBER+SUHNER 15
Intro
duct
ion
Single core and multi core cables for power
and signal transmission in safety applications
High grade cables fulfilling various international fire protection regulations
PURGI•RADOX• ® FR AUS RADOX• ® MFH
Our safety cables have been designed for service in adverse and humid environments.
maintenance of functions in case of fire •application in rough and humid environments•high flexibility•approved by major international standardisation bodies•customised cables•
Installations in buildings and systems with a high person density or high property value – computer centres, hospitals, high-rise buildings, airports, railway stations, public buildings, museums, railway and road tunnels – require high grade cables designed to the necessary standards.These cable families are distinguished by their precisely defined charac-teristics and the fact that they will maintain their functions in case of fires. They have been approved by the major international standardisation bod-ies (IEC/CENELEC/BS/AS).
16 HUBER+SUHNER
HUBER+SUHNER 17
Intro
duct
ion
Single core/multi core cables for power and
signal transmission in defence applications
Unpredictabel conditions, fulfilment of extreme environmental and operating requirements while meeting top quality standards.
RADOX• ® single core and multi core cablesVG transmission lines•Hybrid cables•
RADOX® single core and multi core cables have been developed and are produced for high grade defence solutions.
wide temperature range•stationary as well as mobile applications•small overall diameter•flexible and rugged•light weight and space saving solutions •chemical and mechanical resistance•
HUBER+SUHNER develops and produces high grade solutions that are suitable for the most extreme environmental conditions. They can be installed in very tight spaces and will satisfy even the most stringent demands.HUBER+SUHNER is the professional partner in the development and production of system solutions which incorporate all our knowledge and engineering expertise.
18 HUBER+SUHNER
Preferred fields of application
Cable type Industry Automation
RADOX® 125 flexible single core page 22
RADOX® 125 RW, reduced wall thickness page 24
RADOX® 125 IEC marine single core
RADOX® 125 solid wire page 28
RADOX® eco-F page 30
RADOX® 155 flexible single core page 32
RADOX® 155 S high resistance to oil page 34
RADOX® 155 S RW, reduced wall thickness page 36
RADOX® 155 solid wire page 38
KDJ 11, flexible single core page 40
RADOX® 125 multi core cables, screened and unscreened page 42
RADOX® 155 multi core cables, screened and unscreened page 46
RADOX® UL/CSA flexible single core page 52
RADOX® UL/CSA solid wire page 60
RADOX® UL/CSA multi core cables, screened and unscreened page 62
System cables page 78 page 78
MIL and VG 95218 div. types page 100
RADOX® MFH-S page 110
Hybrid cables page 112 page 112
RADOX® Solar single core cables
RADOX® Solar multi core cables, screened and unscreened
RADOX® FR
HUBER+SUHNER 19
Coil winding(catalogue no.
84022718)Marine
Solar (catalogue no. 84017606)
Safety Defence
page 22 page 22
page 26
page 28
page 30
page 32
page 38
page 42
page 52
page 78
page 100
page 110 page 110
page 112 page 112
page 116
page 122
page 126
20 HUBER+SUHNER
RADOX® 125, flexible single core 22
RADOX® 125 RW, reduced wall thickness 24
RADOX® 125 IEC marine single core 26
RADOX® 125 solid wire 28
RADOX® eco–F 30
RADOX® 155, flexible single core 32
RADOX® 155 S, high resistance to oil 34
RADOX® 155 S RW, reduced wall thickness 36
RADOX® 155, solid wire 38
RADOX® KDJ–11, flexible single core 40
RADOX® 125, multi core cable 42
RADOX® 125, multi core cable, screened 44
RADOX® 155, multi core cable 46
RADOX® 155, multi core cable, screened 48
RADOX® 125, RADOX® 155, KDJ–11
Flexible single cores, multi core cables and wires
All our cables fully comply with the European directives 76/769/EWG, 2003/11/EG, 2000/53/EG, 2003/53/EG and 2002/95/EG (RoHS).
HUBER+SUHNER 21
RAD
OX®
125
, RA
DO
X® 1
55,
KDJ
halogen free, flame retardant•
excellent high and low temperature resistance, robust•
very good chemical and mechanical properties•
flexible, easy to strip, soldering resistant•
wide temperature range•
no melting and flowing at high temperatures due to electron beam •crosslinked insulation material – RADOX®
complies with IEC 60332–3–24 C•
suitable for outdoor applications•
22 HUBER+SUHNER
RADOX® 125
Flexible single core
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, white goods and lighting fixtures.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125
extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating Uo/U 0.50 mm2 450 / 750 V ACTest voltage 0.50 mm2 2500 V ACVoltage rating Uo/U 0.50 mm2 600 / 1000 V ACTest voltage 0.50 mm2 3500 V ACTemperature range –40 °C up to +125 °C
Fire testsContent of halogen acid gas IEC 60754–1, EN 50267–2–1 0 mg/gCorrosivity of combustion gases IEC 60754–2, EN 50267–2–3Smoke density IEC 61034–2, EN 50268–2
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•flexible, easy to strip and •processflame retardant•high resistance to thermal •pressurehigh abrasion resistance•oil–resistant•
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 23
Cross section Conductor Core Weight Bending radius
nom.Construction
nom. Ø max. R20 IEC 60228 Ø nom. min.
mm2 n x mm Ø mm max. /km mm kg/100m
0.25 19 x 0.13 0.6 85.9 1.45 ± 0.05 0.4 3 x Ø
0.34 19 x 0.16 0.8 52.1 1.60 ± 0.10 0.5 3 x Ø
0.50 19 x 0.18 0.9 40.1 1.70 ± 0.10 0.7 3 x Ø
0.75 24 x 0.20 1.15 26.7 2.20 ± 0.10 1.1 3 x Ø
1.0 32 x 0.20 1.3 20.0 2.60 ± 0.10 1.5 3 x Ø
1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 1.9 3 x Ø
2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 3.0 3 x Ø
4.0 56 x 0.30 2.6 5.09 4.15 ± 0.15 4.6 3 x Ø
6.0 81 x 0.30 3.4 3.39 4.95 ± 0.15 6.5 3 x Ø
10 78 x 0.40 4.4 1.95 6.15 ± 0.15 11 3 x Ø
16 119 x 0.40 5.4 1.24 7.35 ± 0.15 16.5 3 x Ø
25 182 x 0.40 6.7 0.795 8.9 ± 0.2 25 3 x Ø
35 266 x 0.40 7.9 0.565 10.3 ± 0.2 34.5 3 x Ø
50 378 x 0.40 9.4 0.393 12.1 ± 0.25 50 4 x Ø
70 348 x 0.50 11.5 0.277 14.4 ± 0.25 68 4 x Ø
95 444 x 0.50 12.9 0.210 16.0 ± 0.3 89 4 x Ø
120 551 x 0.50 14.8 0.164 18.1 ± 0.3 110 4 x Ø
150 722 x 0.50 17.0 0.132 20.5 ± 0.3 142 4 x Ø
185 874 x 0.50 18.5 0.108 22.2 ± 0.3 171 4 x Ø
240 1147 x 0.50 21.3 0.0817 25.4 ± 0.3 225 4 x Ø
Other cross sections on request.
Extract from our delivery programme
RADOX® 125
Flexible single core
24 HUBER+SUHNER
RADOX® 125 RW
Flexible single core – reduced wall thickness
ApplicationProtected and fixed installation inside electrical equipment.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125
extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating Uo/U 300 / 500 V ACTest voltage 2500 V ACTemperature range (UL rating) –40 °C up to +125 °CMin. bending radius 3 x core–Ø
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•flexible, easy to strip and •processflame retardant•high resistance to heat pressure•high abrasion resistance•reduced wall thickness•soldering resistant•
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 25
Cross section Conductor Core Weight
nom. Construction nom. Ø max. R20 IEC 60228 Ø nom.
mm2 n x mm Ø mm max. /km mm kg/100 m
0.35 19 x 0.16 0.77 53.1 1.25 + 0.05 0.41
0.50 19 x 0.18 0.9 40.1 1.40 + 0.05 0.56
0.75 19 x 0.23 1.1 26.7 1.65 + 0.05 0.83
1.0 9 x 0.25 1.25 21.5 1.75 + 0.05 1.00
Other cross sections on request.
Extract from our delivery programme
RADOX® 125 RW
Flexible single core – reduced wall thickness
26 HUBER+SUHNER
RADOX® 125 IEC
Marine single core
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of general power devices, lighting and switchboards.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125
extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating Uo/U 600 / 1000 V ACTest voltage 3500 V ACTemperature range –40 up to +120 °CTemperature range IEC 60092 +85 °CShort circuit temperature +280 °CShort circuit temperature IEC 60092 +250 °CMin. bending radius Ø < 12 mm 3 x core–Ø Ø > 12 mm 4 x core–Ø
ApprovalsDET NORSKE VERITAS (DNV)Classification of ships and mobile offshore units, IEC 60092–353, IEC 60332–3 cat. A, IEC 61034–2, IEC 60754–2 (cross section 1.5 – 300 mm2)
BUREAU VERITAS (BV)Classification of steel ships, IEC 60092–353, IEC 60332–3 cat. A, IEC 61034–2, IEC 60754–2(cross section 1.5 – 300 mm2)
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•flame retardant•high abrasion resistance•soldering resistant•low smoke•easy to strip and process•flexible•electron beam crosslinked•insulation
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 27
Cross section Conductor Core Weight
nom. nom. Ø max. R20 IEC 60228 Ø nom.
mm2 n x mm Ø mm max. /km mm kg/100 m
0.5 19 x 0.18 0.95 40.1 2.45 ± 0.10 1.1
0.75 24 x 0.20 1.2 26.7 2.65 ± 0.10 1.3
1.0 32 x 0.20 1.3 20.0 2.80 ± 0.10 1.6
1.5 30 x 0.25 1.6 13.7 3.10 ± 0.10 2.2
2.5 50 x 0.25 2.1 8.21 3.55 ± 0.10 3.1
4.0 56 x 0.30 2.6 5.09 4.25 ± 0.15 4.8
6.0 81 x 0.30 3.4 3.39 4.95 ± 0.15 6.5
10 78 x 0.40 4.4 1.95 5.95 ± 0.15 11.0
16 119 x 0.40 5.4 1.24 6.95 ± 0.15 16.3
25 182 x 0.40 6.7 0.795 8.70 ± 0.20 24.4
35 266 x 0.40 7.9 0.565 9.90 ± 0.20 34.3
50 378 x 0.40 9.4 0.393 11.6 ± 0.20 50.2
70 348 x 0.50 11.5 0.277 14.0 ± 0.25 68.8
95 444 x 0.50 12.9 0.210 15.4 ± 0.25 87.9
120 551 x 0.50 14.8 0.164 17.5 ± 0.30 109
150 722 x 0.50 17.0 0.132 20.1 ± 0.30 140
185 874 x 0.50 18.5 0.108 22.0 ± 0.30 170
240 1147 x 0.50 21.3 0.0817 25.0 ± 0.30 226
300 1443 x 0.50 23.9 0.0654 27.8 ± 0.30 276
Other cross sections on request.
RADOX® 125 IEC
Marine single core
Extract from our delivery programme
Fire testsFlame propagation:Verical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cables EN 50266–2–2, IEC 60332–3–22 Category AContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2
28 HUBER+SUHNER
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of switch-boards, magnets and transformers.
Composition of the cable Conductor stranded bare or tin plated copper, acc. to IEC 60228, class 1 Insulation RADOX® 125
extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating Uo/U 0.50 mm2 450 / 750 V ACTest voltage 0.50 mm2 2500 V ACVoltage rating Uo/U 0.50 mm2 600/1000 V ACTest voltage 0.50 mm2 3500 V ACTemperature range –40 °C up to +125 °CMin. bending radius 3 x wire–Ø
RADOX® 125
Solid wire
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•flame retardant•high resistance to heat pressure•high abrasion resistance•easy to process•soldering resistant•
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 29
Cross section Conductor Core Weight
nom Ø max. R20 IEC 60228 Ø nom.
mm2 mm max. /km mm kg/100 m
0.25 0.6 61.3 1.40 ± 0.10 0.4
0.50 0.8 36.7 1.90 ± 0.10 0.8
0.75 1.0 24.8 2.10 ± 0.10 1.0
1.0 1.15 18.2 2.35 ± 0.10 1.4
1.5 1.4 12.2 2.60 ± 0.10 1.9
2.5 1.8 7.56 3.10 ± 0.10 3.0
Other cross sections on request.
Extract from our delivery programme
RADOX® 125
Solid wire
30 HUBER+SUHNER
RADOX® eco–F
Flexible single core
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, white goods, lighting fixtures, etc.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® eco–F, extruded and electron beam crosslinked polyolefin
Core colours various, on request
Technical dataVoltage rating Uo/U 450 / 750 V ACTest voltage 2500 V ACMin. operating temperature –40 °CMax. continuous conductor temperature +155 °CMax. continuous conductor temperatureat short circuit ( max. 5s ) fixed +250 °C flexing +200 °CMin. bending radius 3 x core–Ø
Fire testsContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•easy to process•flame retardant•soldering resistant•flexible•resistant to impregnation resins •and varnishes
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 31
Cross section Conductor Core Weight
nom. Construction nom. Ø max. R20 IEC 60228 Ø nom.
mm2 n x mm Ø mm max. /km mm kg/100 m
0.25 19 x 0.13 0.6 85.9 1.35 ± 0.05 0.4
0.34 19 x 0.16 0.8 52.1 1.60 ± 0.10 0.6
0.50 19 x 0.18 0.9 40.1 1.71 ± 0.10 0.7
0.75 19 x 0.23 1.1 26.7 1.90 ± 0.10 1.0
1.0 19 x 0.26 1.2 20.0 2.15 ± 0.10 1.2
1.5 30 x 0.25 1.5 13.7 2.45 ± 0.10 1.8
2.5 50 x 0.25 2.1 8.21 3.05 ± 0.10 2.8
4.0 56 x 0.30 2.6 5.09 3.65 ± 0.15 4.7
Other cross sections on request.
Extract from our delivery programme
RADOX® eco–F
Flexible single core
32 HUBER+SUHNER
RADOX® 155
Flexible single core
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, magnets and transformers.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 155
extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating Uo/U 0.50 mm2 450 / 750 V ACTest voltage 0.50 mm2 2500 V ACVoltage rating Uo/U 0.50 mm2 600 / 1000 V ACTest voltage 0.50 mm2 3500 V ACTemperature range –55 °C up to +155 °C
excellent high and low tempera-•ture and ozone resistanceweatherproof•easy to process•flame retardant•high resistance to heat pressure•high abrasion resistance•soldering resistant•flexible•resistant to impregnation resins •and varnishes
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 33
Cross section Conuctor Core Weight Bending radius
nom. Construction nom. Ø max. R20 IEC 60228 Ø nom. min.
mm2 n x mm Ø mm max. /km mm kg/100m
0.25 19 x 0.13 0.6 85.9 1.45 ± 0.05 0.4 3 x Ø
0.34 19 x 0.16 0.8 52.1 1.60 ± 0.10 0.5 3 x Ø
0.50 19 x 0.18 0.9 40.1 1.70 ± 0.10 0.7 3 x Ø
0.75 24 x 0.20 1.15 26.7 2.20 ± 0.10 1.1 3 x Ø
1.0 32 x 0.20 1.3 20.0 2.60 ± 0.10 1.5 3 x Ø
1.5 30 x 0.25 1.55 13.7 2.70 ± 0.10 1.9 3 x Ø
2.5 50 x 0.25 2.05 8.21 3.35 ± 0.10 3.0 3 x Ø
4.0 56 x 0.30 2.6 5.09 4.05 ± 0.15 4.6 3 x Ø
6.0 81 x 0.30 3.4 3.39 5.2 ± 0.15 6.5 3 x Ø
10 78 x 0.40 4.4 1.95 6.4 ± 0.15 11 3 x Ø
16 119 x 0.40 5.4 1.24 7.6 ± 0.15 16.5 3 x Ø
25 182 x 0.40 6.7 0.795 9.2 ± 0.2 25 3 x Ø
35 266 x 0.40 7.9 0.565 10.6 ± 0.2 34.5 3 x Ø
50 378 x 0.40 9.4 0.393 12.3 ± 0.25 50 4 x Ø
70 348 x 0.50 11.5 0.277 14.6 ± 0.25 68 4 x Ø
95 444 x 0.50 12.9 0.210 16.3 ± 0.3 89 4 x Ø
120 551 x 0.50 14.8 0.164 18.4 ± 0.3 110 4 x Ø
150 722 x 0.50 17.0 0.132 20.8 ± 0.3 142 4 x Ø
185 874 x 0.50 18.5 0.108 22.5 ± 0.3 171 4 x Ø
240 1147 x 0.50 21.3 0.0817 25.7 ± 0.3 225 4 x Ø
Other cross sections on request.
RADOX® 155
Flexible single core
Extract from our delivery programme
34 HUBER+SUHNER
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, magnets and transformers.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 155S
extruded electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating Uo/U 0.50 mm2 450 / 750 V ACTest voltage 0.50 mm2 2500 V ACVoltage rating Uo/U 0.50 mm2 600 / 1000 V ACTest voltage 0.50 mm2 3500 V ACTemperature range –55 °C up to +155 °CMin. bending radius 3 x core–Ø
RADOX® 155 S
Flexible single core – high oil resistance
excellent high and low tempera-•ture and ozone resistanceweatherproof•high resistance to heat pressure•high abrasion resistance•easy to strip and process•resistant to hydrolysis, oil and •fuelsresistant to impregnation resins •and varnishes
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 35
Cross section Conductor Core Weight
nom. Construction nom. Ø max. R20 IEC 60228 Ø nom.
mm2 n x mm Ø mm max. /km mm kg/100m
0.50 19 x 0.18 0.9 40.1 1.70 ± 0.10 0.7
0.75 24 x 0.20 1.15 26.7 2.20 ± 0.10 1.1
1.0 32 x 0.20 1.3 20.0 2.60 ± 0.10 1.5
1.5 30 x 0.25 1.55 13.7 2.70 ± 0.10 1.9
2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 3.0
Other cross sections on request.
Extract from our delivery programme
RADOX® 155 S
Flexible single core – high oil resistance
36 HUBER+SUHNER
RADOX® 155 S RW
Flexible single core – reduced wall thickness
ApplicationsProtected and fixed installation inside equipment, especially suitable for the connection of motor windings, switchboards, magnets and transformers where space is rare.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 155S
extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating Uo/U 300 / 500 V ACTest voltage 2000 V ACTemperature range –40 °C up to +155 °CMin. bending radius 3 x core–Ø
reduced wall thickness •excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•high resistance to heat pressure•high abrasion resistance•easy to strip and process•resistant to hydrolysis, oil and •fuelsresistant to impregnation resins •and varnishes
RAD
OX®
125
, RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 37
Cross section Conductor Core Weight
nom. Construction nom. Ø max. R20 IEC 60228 Ø nom.
mm2 n x mm Ø mm max. /km mm kg/100 m
0.14 19 x 0.10 0.51 135.5 0.95 ± 0.05 0.3
0.25 19 x 0.13 0.61 86.0 1.10 ± 0.05 0.3
0.35 19 x 0.15 0.80 54.5 1.25 ± 0.05 0.4
0.50 19 x 0.18 0.91 38.2 1.40 ± 0.05 0.6
0.75 19 x 0.22 1.12 25.4 1.65 ± 0.05 0.8
1.0 19 x 0.26 1.26 19.1 1.75 ± 0.05 1.0
1.5 30 x 0.26 1.7 13.0 2.30 ± 0.1 1.6
2.5 50 x 0.26 2.2 7.8 2.85 ± 0.15 2.6
4.0 56 x 0.31 2.75 4.8 3.55 ± 0.15 4.2
Other cross sections on request.
Extract from our delivery programme
RADOX® 155 S RW
Flexible single core – reduced wall thickness
38 HUBER+SUHNER
RADOX® 155
Solid wire
ApplicationsProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, magnets and transformers.
Composition of cable Conductor stranded bare or tin plated copper, acc. to IEC 60228, class 1 Insulation RADOX® 155
extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating Uo/U 0.50 mm2 450 / 750 V ACTest voltage 0.50 mm2 2500 V ACVoltage rating Uo/U 0.50 mm2 600 / 1000 V ACTest voltage 0.50 mm2 3500 V ACTemperature range –55 °C up to +155 °CMin. bending radius 3 x wire–Ø
excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•high resistance to heat pressure•high abrasion resistance•soldering resistant•easy to process•resistant to impregnation resins •and varnishes
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 39
Cross section Conductor Core Weight
nom Ø max. R20 IEC 60228 Ø nom.
mm2 mm max. /km mm kg/100 m
0.25 0.6 61.3 1.40 ± 0.10 0.4
0.50 0.8 36.7 1.90 ± 0.10 0.8
0.75 1.0 24.8 2.10 ± 0.10 1.0
1.0 1.15 18.2 2.35 ± 0.10 1.4
1.5 1.4 12.2 2.60 ± 0.10 1.9
2.5 1.8 7.56 3.10 ± 0.10 3.0
Other cross sections on request.
Extract from our delivery programme
RADOX® 155
Solid wire
40 HUBER+SUHNER
ApplicationWiring of equipment for heating and refrigeration units, chemical plants, wet or humid rooms and rooms with •high ambient temperatures.Compatible to moudling compounds.•Transformer in oil• , class H motors.
Composition of cable Conductor stranded bare copper, acc. to IEC 60228, class 5 Insulation FEP
Core colours various, on request
Technical dataVoltage rating Uo/U 0.50 and 1.0 mm2 300 / 500 V AC 1.50 up to 25 mm2 450 / 750 V ACTest voltage 2500 V ACMax. conductor temperature (continuous) +180 °CShort circuit temperature (max. 5s) +250 °CMax. operating temperature flexing –55 °C fixed –100 °CMin. bending radius flexing 5 x core–Ø fixed 3 x core–Ø
RADOX® KDJ–11
Flexible single core
resistant to solvents, oils, fuels, •alkaline solutions, acids and hydrolysisweatherproof•impermeable to vapour•compact design•mechanical robustness in agres-•sive environment at high and low temperatures
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 41
Cross section Conductor Core Weight
nom. Construction nom. Ø max. R20 IEC 60228 Ø nom.
mm2 n x mm Ø mm max. /km mm kg/100 m
0.50 19 x 0.18 0.91 37.1 1.85 0.8
0.75 24 x 0.20 1.16 24.7 2.10 1.2
1.0 32 x 0.20 1.33 18.5 2.30 1.4
1.5 19 x 0.32 1.63 12.6 2.60 2.0
2.5 50 x 0.25 1.98 7.58 3.20 3.0
4.0 56 x 0.30 2.50 4.70 3.80 4.3
6.0 84 x 0.30 2.98 3.14 4.90 6.8
10 80 x 0.40 3.94 1.87 5.50 11.1
16 126 x 0.40 5.60 1.19 7.50 17.0
Other cross sections on request.
Extract from our delivery programme
RADOX® KDJ–11
Flexible single core
42 HUBER+SUHNER
RADOX® 125
Multi core cable
ApplicationPermanent installation indoor and outdoor for the connection of fixed and loose parts.
Composition of cable Core:
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125 extruded and electron beam crosslinked polyolefin copolymer Core colours 2 up to 5 core acc. to CENELEC HD 308 (see page 155) 6 core and more: black numbered with yellow/green earthing
Fillers (optional) RADOX® 125 Separator glass fabric tape Sheath RADOX® 125M:
extruded and electron beam crosslinked polyolefin copolymer Colour black
Technical dataVoltage rating Uo/U 16 x 0.50 mm2 450 / 750 V ACTest voltage 16 x 0.50 mm2 2500 V ACVoltage rating Uo/U 16 x 0.50 mm2 600 / 1000 V ACTest voltage 16 x 0.50 mm2 3500 V ACTemperature range fixed –40 °C up to +125 °CMin. operating temperature flexing –25 °CMax. conductor temperature at short circuit (max. 5s) +280 °CMin. bending radius fixed 3 x cable–Ø flexing 5 x cable–Ø
Fire testsFlame propagation:Verical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cables EN 50266–2–4, IEC 60332–3–24 Category CContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•flame retardant•soldering resistant•flexible•in case of fire no corrosive •gases and low smoke emissioneasy to strip•
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 43
Cross section Conductor Core Cable Weight
n x mm2Construction nom.
n x mm ØØ max.
mmR20 IEC 60228
max. /kmØ
mmØ
mmnom.
kg/100 m4 x 0.25 19 x 0.12 0.61 88.5 1.45 ± 0.05 5.4 ± 0.3 4.08 x 0.25 19 x 0.12 0.61 88.5 1.45 ± 0.05 7.75 ± 0.3 8.012 x 0.25 19 x 0.12 0.61 88.5 1.45 ± 0.05 8.5 ± 0.3 9.516 x 0.25 19 x 0.12 0.61 88.5 1.45 ± 0.05 9.45 ± 0.3 11.928 x 0.25 19 x 0.12 0.61 88.5 1.45 ± 0.05 12.4 ± 0.4 19.7
2 x 0.5 19 x 0.18 0.9 40.1 1.7 ± 0.10 5.5 ± 0.3 5.14 x 0.5 19 x 0.18 0.9 40.1 1.7 ± 0.10 6.1 ± 0.3 6.516 x 0.5 19 x 0.18 0.9 40.1 1.7 ± 0.10 11.0 ± 0.4 17.92 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 6.6 ± 0.3 6.33 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 7.3 ± 0.3 7.94 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 7.7 ± 0.3 8.85 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 8.6 ± 0.3 10.97 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 10.2 ± 0.4 15.1
10 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 11.7 ± 0.4 19.612 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 12.0 ± 0.4 21.416 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 13.5 ± 0.4 27.540 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 20.3 ± 0.5 61.6
2 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 7.5 ± 0.3 7.43 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 7.9 ± 0.3 9.14 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 8.8 ± 0.3 11.25 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 9.6 ± 0.3 13.67 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 11.4 ± 0.4 –2 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 7.8 ± 0.3 8.63 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 8.3 ± 0.3 11.04 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 9.2 ± 0.3 13.65 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 10.4 ± 0.4 16.87 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 12.3 ± 0.4 23.6
10 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 14.0 ± 0.4 31.112 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 14.4 ± 0.4 34.316 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 16.3 ± 0.5 44.921 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 18.7 ± 0.5 56.727 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 20.8 ± 0.5 69.82 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 9.1 ± 0.3 13.03 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 10.1 ± 0.4 16.64 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 11.3 ± 0.4 20.95 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 12.4 ± 0.4 24.97 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 15.3 ± 0.5 37.92 x 4.0 56 x 0.30 2.6 5.09 4.15 ± 0.15 11.0 ± 0.4 18.74 x 4.0 56 x 0.30 2.6 5.09 4.15 ± 0.15 13.0 ± 0.4 29.85 x 4.0 56 x 0.30 2.6 5.09 4.15 ± 0.15 14.6 ± 0.4 36.74 x 6.0 81 x 0.30 3.4 3.39 4.95 ± 0.15 15.6 ± 0.5 41.82 x 10 78 x 0.40 4.4 1.95 6.15 ± 0.15 15.8 ± 0.5 –3 x 10 78 x 0.40 4.4 1.95 6.15 ± 0.15 17.0 ± 0.5 –4 x 10 78 x 0.40 4.4 1.95 6.15 ± 0.15 19.0 ± 0.5 –5 x 10 78 x 0.40 4.4 1.95 6.15 ± 0.15 21.4 ± 0.5 –4 x 16 119 x 0.40 5.4 1.24 7.35 ± 0.15 22.5 ± 0.5 –5 x 16 119 x 0.40 5.4 1.24 7.35 ± 0.15 24.8 ± 0.5 –4 x 25 182 x 0.40 6.7 0.795 8.9 ± 0.2 26.5 ± 0.6 –5 x 25 182 x 0.40 6.7 0.795 8.9 ± 0.2 30.0 ± 0.6 –4 x 35 266 x 0.40 7.9 0.565 10.3 ± 0.2 30.7 ± 0.6 –5 x 35 266 x 0.40 7.9 0.565 10.3 ± 0.2 34.2 ± 0.6 –4 x 50 378 x 0.40 9.4 0.393 12.1 ± 0.25 35.8 ± 0.7 –
Extract from our delivery programme (Other cross sections on request)
RADOX® 125
Multi core cable
44 HUBER+SUHNER
RADOX® 125
Multi core cable – screened
ApplicationPermanent installation indoor and outdoor for the connection of fixed and loose parts.
Composition of cable Core:
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125 extruded and electron beam crosslinked polyolefin copolymer Core colours 2 up to 5 core acc. to CENELEC HD 308 (see page 155) 6 core and more: black numbered with yellow/green earthing other colours on request
Fillers (optional) RADOX® 125 Separator (optional) plastic tape Screen copper braid, optical coverage: 85 % Separator (optional) plastic tape Sheath RADOX® 125M
extruded and electron beam crosslinked polyolefin copolymer Colour black
Technical dataVoltage rating Uo/U 16 x 0.50 mm2 450 / 750 V ACTest voltage 16 x 0.50 mm2 2500 V ACVoltage rating Uo/U 16 x 0.50 mm2 600 / 1000 V ACTest voltage 16 x 0.50 mm2 3500 V ACTemperature range fixed –40 °C up to +125 °CMin. operating temperature flexing –25 °CMax. conductor temperature at short circuit (max. 5s) +280 °CMin. bending radius fixed 4 x cable–Ø flexing 5 x cable–Ø
Fire testsFlame propagation:Verical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cables EN 50266–2–4, IEC 60332–3–24 Category CContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•flame retardant•soldering resistant•flexible•in case of fire no corrosive •gases and low smoke emissioneasy to strip•
RAD
OX®
125
, RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 45
Cross section Conductor Core Screen Cable Weight
Construction nom.
Ø max. R20 IEC 60228 Ø Ø Ø nom.
n x mm2 n x mm Ø mm max. /km mm mm mm kg/100 m
4 x 0.25 19 x 0.13 0.6 85.9 1.45 ± 0.05 4.1 5.9 ± 0.3 5.2
12 x 0.25 19 x 0.13 0.6 85.9 1.45 ± 0.05 6.9 9.0 ± 0.3 12.4
28 x 0.25 19 x 0.13 0.6 85.9 1.45 ± 0.05 10.4 13.0 ± 0.3 24.9
2 x 0.5 19 x 0.18 0.9 40.1 1.7 ± 0.10 4.0 5.9 ± 0.3 5.7
4 x 0.5 19 x 0.18 0.9 40.1 1.7 ± 0.10 4.8 6.8 ± 0.3 8.0
16 x 0.5 19 x 0.18 0.9 40.1 1.7 ± 0.10 9.0 11.6 ± 0.4 21.5
2 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 4.9 6.9 ± 0.3 7.4
3 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 5.5 7.6 ± 0.3 9.7
4 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 6.2 8.4 ± 0.3 11.7
5 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 6.8 9.3 ± 0.3 14.1
7 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 8.3 10.7 ± 0.4 18.7
25 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 15.6 19.2 ± 0.5 57.3
2 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 5.9 7.9 ± 0.3 10.6
3 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 6.3 8.7 ± 0.3 12.7
4 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 7.0 9.3 ± 0.3 14.4
7 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 9.4 12.1 ± 0.4 23.9
12 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 11.7 14.6 ± 0.4 33.5
2 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 6.3 8.4 ± 0.3 11.8
3 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 6.5 8.7 ± 0.3 13.2
4 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 7.6 10.0 ± 0.4 17.5
5 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 8.7 11.5 ± 0.4 22.8
7 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 10.4 13.1 ± 0.4 29.6
8 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 11.4 14.2 ± 0.4 34.3
12 x 1.5 30 x 0.25 1.55 13.7 2.73 ± 0.10 12.3 15.4 ± 0.5 41.0
2 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 7.7 10.2 ± 0.4 17.5
3 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 8.3 10.8 ± 0.4 20.6
4 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 9.8 12.4 ± 0.4 26.8
5 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 10.4 13.1 ± 0.4 30.9
7 x 2.5 50 x 0.25 2.05 8.21 3.50 ± 0.10 13.2 16.3 ± 0.5 45.9
2 x 4.0 56 x 0.30 2.6 5.09 4.15 ± 0.15 9.2 11.9 ± 0.4 24.4
4 x 4.0 56 x 0.30 2.6 5.09 4.15 ± 0.15 11.2 14.1 ± 0.4 37.1
3 x 6.0 81 x 0.30 3.4 3.39 4.95 ± 0.15 11.6 14.5 ± 0.4 38.8
4 x 6.0 81 x 0.30 3.4 3.39 4.95 ± 0.15 13.3 16.5 ± 0.5 51.7
4 x 10 78 x 0.40 4.4 1.91 6.15 ± 0.15 16.2 19.8 ± 0.5 77.5
4 x 35 266x0.40 7.9 0.565 10.3 ± 0.2 27.2 32.2 ± 0.6 2.17
Other cross sections on request.
Extract from our delivery programme
RADOX® 125
Multi core cable – screened
46 HUBER+SUHNER
RADOX® 155
Multi core cable
ApplicationPermanent installation indoor and outdoor for the connection of fixed and loose parts.
Composition of cable Core:
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 155 extruded and electron beam crosslinked polyolefin copolymer Core colours 2 up to 5 core acc. to CENELEC HD 308 (see page 155) 6 core and more: black numbered with yellow/green earthing other colours on request
Fillers (optional) RADOX® 125 Separator (optional) plastic tape Sheath RADOX® 155
extruded and electron beam crosslinked polyolefin copolymer Colour black
Technical dataVoltage rating Uo/U 16 x 0.50 mm2 450 / 750 V ACTest voltage 16 x 0.50 mm2 2500 V ACVoltage rating Uo/U 16 x 0.50 mm2 600 / 1000 V ACTest voltage 16 x 0.50 mm2 3500 V ACTemperature range fixed –55 °C up to +155 °CMin. operating temperature flexible –40 °CMax. conductor temperature at short circuit (max. 5s) +280 °CMin. bending radius fixed 3 x cable–Ø flexible 5 x cable–Ø
excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•soldering resistant•flexible•easy to strip•
RAD
OX®
125
, RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 47
Cross section Conductor Core Cable Weight
Construction nom. Ø max. R20 IEC 60228 Ø Ø
n x mm2 n x mm Ø mm max. /km mm mm nom.
4 x 0.25 19 x 0.13 0.6 85.9 1.45 ± 0.05 5.4 ± 0.3 3.3
3 x 0.34 19 x 0.15 0.75 57.2 1.55 ± 0.10 5.1 ± 0.3 –
2 x 0.50 19 x 0.18 0.9 40.1 1.7 ± 0.10 5.2 ± 0.3 –
3 x 0.50 19 x 0.18 0.9 40.1 1.7 ± 0.10 5.6 ± 0.3 4.0
8 x 0.50 19 x 0.18 0.9 40.1 1.7 ± 0.10 8.75 ± 0.3 –
16 x 0.50 19 x 0.18 0.9 40.1 1.7 ± 0.10 10.4 ± 0.4 –
3 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 6.7 ± 0.3 5.9
4 x 0.75 24 x 0.20 1.15 26.7 2.2 ± 0.10 7.5 ± 0.3 –
2 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 7.0 ± 0.3 6.1
3 x 1.0 32 x 0.20 1.3 20.0 2.6 ± 0.10 7.6 ± 0.3 7.7
2 x 1.5 30 x 0.25 1.55 13.7 2.7 ± 0.10 7.5 ± 0.3 6.6
3 x 1.5 30 x 0.25 1.55 13.7 2.7 ± 0.10 7.9 ± 0.3 9.2
4 x 1.5 30 x 0.25 1.55 13.7 2.7 ± 0.10 8.8 ± 0.3 11.7
5 x 1.5 30 x 0.25 1.55 13.7 2.7 ± 0.10 10.1 ± 0.4 15.0
3 x 2.5 50 x 0.25 2.05 8.21 3.35 ± 0.10 9.9 ± 0.3 14.6
4 x 2.5 50 x 0.25 2.05 8.21 3.35 ± 0.10 11.0 ± 0.4 18.6
5 x 2.5 50 x 0.25 2.05 8.21 3.35 ± 0.10 11.9 ± 0.4 22.3
Other cross sections on request.
Extract from our delivery programme
RADOX® 155
Multi core cable
48 HUBER+SUHNER
ApplicationPermanent installation indoor and outdoor for the connection of fixed and loose parts.
Composition of cable Core:
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 155 extruded and electron beam crosslinked polyolefin copolymer Core colours 2 up to 5 core acc. to CENELEC HD 308 (see page 155) 6 core and more: black numbered with yellow/green earthing other colours on request
Fillers (optional) RADOX® 125 Separator (optional) plastic tape Screen copper braid, optical coverage: 85 % Separator (optional) plastic tape Sheath RADOX® 155
extruded and electron beam crosslinked polyolefin copolymer Colour black
Technical dataVoltage rating Uo/U 16 x 0.50 mm2 450/750 V ACTest voltage 16 x 0.50 mm2 2500 V ACVoltage rating Uo/U 16 x 0.50 mm2 600/1000 V ACTest voltage 16 x 0.50 mm2 3500 V ACTemperature range fixed –55 °C up to +155 °CMin. operating temperature flexible –40 °CMax. conductor temperature at short circuit (max. 5s) +280 °CMin. bending radius fixed 4 x cable–Ø flexible 5 x cable–Ø
Fire testsFlame propagation:Verical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cables DIN EN 50266–2–5 Category D
excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•soldering resistant•flexible•easy to strip•
RADOX® 155
Multi core cable – screened
RAD
OX®
125,
RA
DO
X® 1
55,
KDJ
HUBER+SUHNER 49
Cross section Conductor Core Screen Cable Weight
Construction nom.
Ø max. R20 IEC 60228 Ø Ø Ø nom.
n x mm2 n x mm Ø mm max. /km mm mm mm kg/100m
2 x 0.25 19 x 0.12 0.61 88.5 1.45 ± 0.05 3.35 5.1 ± 0.3 3.43
6 x 0.25 19 x 0.12 0.61 88.5 1.45 ± 0.05 5.07 6.95 ± 0.15 6.71
4x2x0.25 19 x 0.12 0.61 88.5 1.45 ± 0.05 11.2 14.0 ± 0.4 27.7
4 x 0.5 19 x 0.18 0.9 40.1 1.71 ± 0.10 5.55 7.6 ± 0.15 7.62
16 x 0.5 19 x 0.18 0.9 40.1 1.71 ± 0.10 9.0 11.6 ± 0.4 20.3
3 G 1.5 30 x 0.25 1.61 13.3 2.73 ± 0.10 6.6 8.7 ± 0.3 11.6
10 G 1.5 30 x 0.25 1.61 13.3 2.73 ± 0.10 11.9 14.7 ± 0.4 33.2
26 G 1.5 30 x 0.25 1.61 13.3 2.73 ± 0.10 18.0 22.0 ± 0.5 74.1
8 G 2.5 50 x 0.25 2.06 8.6 3.5 ± 0.10 14.5 17.9 ± 0.5 49.8
9 G 2.5 50 x 0.25 2.06 8.6 3.5 ± 0.10 15.1 18.6 ± 0.5 51.8
Other cross sections on request.
Extract from our delivery programme
RADOX® 155
Multi core cable – screened
50 HUBER+SUHNER
RADOX® UL 1385/CSA AWM I A/Bflexible single core 52
RADOX® UL 3266/CSA AWM I A/Bflexible single core 54
RADOX® UL 3271/CSA AWM I A/Bflexible single core 56
RADOX® UL 3289/CSA CL 1503flexible single core 58
RADOX® UL 3289/CSA CL 1503single core solid wire 60
RADOX® UL 4486/CSA AWM I/II A/Bmulti core cables, 300 V 62
RADOX® UL 4486/CSA AWM I/II A/Bmulti core cables, screened, 300 V 66
RADOX® UL 4486/CSA AWM I/II A/Bmulti core cables, 600 V 70
RADOX® UL 4486/CSA AWM I/II A/Bmulti core cables, screened, 600 V 74
RADOX® UL/CSA
Flexible single cores, multi core cables and wires UL recognised
All our cables fully comply with the European directives 76/769/EWG, 2003/11/EG, 2000/53/EG, 2003/53/EG and 2002/95/EG (RoHS).
HUBER+SUHNER 51
RAD
OX®
UL/
CSA
halogen free, flame retardant•
high temperature resistance•
high mechanical resistance•
flexible, easy to strip, soldering resistant•
temperature range –55 °C up to +150 °C•
voltage rating 300/600 V AC•
flame tests VW–1 and FT1•
52 HUBER+SUHNER
RADOX® UL1385 / CSA AWM I A/B
Flexible single core
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, magnets and transformers.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation 1 electron beam crosslinked polyalcen Insulation 2 electron beam crosslinked polyvinilydenfluorid (PVDF)
Core colours various, on request
Technical dataVoltage rating 600 V ACOperating temperature (UL temperature rating) +125 °CMin. temperature –65 °CMin. bending radius 3 x core–Ø
ApprovalsUL AWM 1385 125 °C, no voltage ratingCSA AWM I A/B 125 °C, 300 V, FT1, FT2
excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•high resistance to heat pressure•high abration reistance•highly resistant to hydrolysis•resistant to impregnation resins •and varnisheseasy to process•soldering resistant insulation•flexible•
RAD
OX®
UL/
CSA
HUBER+SUHNER 53
Cross section Conductor Core Weight
nom.Construction
nom.Ø max.
R20MIL–W–81044/12
Ø nom.
AWG mm2 n x mm Ø mm max. /km mm kg/100 m
28 0.09 7 x 0.13 040 239 0.77 ± 0.05 0.13
26 0.15 19 x 0.10 0.51 150 0.87 ± 0.05 0.19
24 0.25 19 x 0.13 0.61 94.2 1.02 ± 0.05 0.30
22 0.38 19 x 0.16 0.77 59.4 1.18 ± 0.05 0.43
20 0.60 19 x 0.20 0.99 36.7 1.40 ± 0.05 0.65
18 0.93 19 x 0.25 1.23 23.2 1.66 ± 0.05 0.95
16 1.25 19 x 0.29 1.40 15.8 1.83 ± 0.05 1.30
Other cross sections on request.
Extract from our delivery programme
RADOX® UL1385 / CSA AWM I A/B
Flexible single core
54 HUBER+SUHNER
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, magnets and transformers.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5
Insulation RADOX® 125 extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating Uo / U 300 V ACTest voltage 2000 V ACOperating temperature (UL temperature rating) +125 °CMin. temperature –40 °CMin. bending radius 3 x core–Ø
ApprovalsUL Underwriters Laboratories File No. E63322CSA Canadian Standards Association Report No. 69581, 39507
RADOX® UL 3266 / CSA AWM I A/B
Flexible single core
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•high abrasion reistance•resistant to impregnation resins •and varnisheseasy to process•soldering resistant•flexible•
RAD
OX®
UL/
CSA
HUBER+SUHNER 55
Cross section Conductor Core Weight
nom. Construction Ø max. Ø nom.
AWG mm2 n x mm Ø mm mm kg/100 m
26 0.128 19 x 0.10 0.51 1.32 ± 0.05 0.32
24 0.205 19 x 0.13 0.61 1.45 ± 0.05 0.41
22 0.324 19 x 0.16 0.79 1.65 ± 0.10 0.53
20 0.519 19 x 0.20 0.99 1.85 ± 0.10 0.83
18 0.823 19 x 0.25 1.23 2.10 ± 0.10 1.13
(16) 1.50 19 x 0.31 1.55 2.41 ± 0.10 1.65
14 2.08 19 x 0.37 1.86 2.72 ± 0.10 2.33
12 3.31 37 x 0.34 2.35 3.21 ± 0.10 3.53
10 5.26 37 x 0.43 3.02 3.88 ± 0.10 5.61
Other cross sections on request.
Extract from our delivery programme
RADOX® UL 3266 / CSA AWM I A/B
Flexible single core
56 HUBER+SUHNER
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, magnets and transformers.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5
Insulation RADOX® 125S extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating 600 V ACTest voltage 2500 V ACOperating temperature (UL/CSA temperature rating) +125 °CMax. conductor temperature at short circuit (max. 5s) +280 °CMin. operating temperature –65 °C flexing –25 °C fixed –40 °C
StandardsApplicance wiring material CSA C22.2 no. 210.2 AWM I A/B 125°C 600 V FT2Applicance wiring material UL 758 Style 3271
ApprovalsCSA Certificate 1418425UL File E63322
RADOX® UL 3271 / CSA AWM I A/B
Flexible single core
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•flame retardant•high resistance to heat pressure•high abrasion reistance•easy to process•soldering resistant•flexible•
RAD
OX®
UL/
CSA
HUBER+SUHNER 57
Cross section Conductor Core Weight Bending radius
nom.Construction
nom.Ø max. R20 IEC 60228 Ø nom. min.
AWG mm2 n x mm Ø mm max. /km mm kg/100 m
24 (0.241) 19 x 0.13 0.61 85.6 2.22 ± 0.10 0.72 3 x Ø
22 (0.382) 19 x 0.16 0.79 53.2 2.40 ± 0.10 0.92 3 x Ø
20 (0.616) 19 x 0.20 0.99 32.4 2.60 ± 0.10 1.2 3 x Ø
18 (0.963) 19 x 0.25 1.23 20.4 2.85 ± 0.10 1.6 3 x Ø
(16) 1.50 19 x 0.31 1.55 13.0 3.20 ± 0.10 2.1 3 x Ø
14 (2.08) 19 x 0.37 1.86 9.15 3.50 ± 0.10 2.9 3 x Ø
12 (3.31) 37 x 0.34 2.35 5.75 4.0 ± 0.15 4.2 3 x Ø
10 (5.26) 37 x 0.43 3.02 3.62 4.7 ± 0.15 6.4 3 x Ø
(8) 10 80 x 0.40 3.94 1.95 6.4 ± 0.15 12.1 3 x Ø
(6) 16 119 x 0.40 5.4 1.21 8.6 ± 0.2 18.8 3 x Ø
(4) 25 182 x 0.40 6.7 0.795 9.9 ± 0.2 26.8 3 x Ø
(2) 35 266 x 0.40 7.9 0.565 11.1 ± 0.2 36.4 3 x Ø
(1) 50 378 x 0.40 9.4 0.393 13.7 ± 0.25 54.3 4 x Ø
(2/0) 70 348 x 0.50 11.5 0.277 15.8 ± 0.25 72.3 4 x Ø
(3/0) 95 444 x 0.50 12.9 0.210 17.4 ± 0.3 95.5 4 x Ø
(4/0) 120 551 x 0.50 14.8 0.164 19.3 ± 0.3 116 4 x Ø
150 722 x 0.50 17.0 0.132 22.2 ± 0.3 150 4 x Ø
Other cross sections on request.
Extract from our delivery programme
Fire testsFlame propagation:Vertical of a single cable CSA C22.2 no. 0.3 cl. 4.11.1 FT1 > 16 mm2 onlyHorizontal of a single cable CSA C22.2 no. 0.3 cl. 4.11.2 FT2Vertical of a single cable EN 50265–2–1, IEC 60332–1 > 16 mm2 onlyContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2Flame propagation:Horizontal of a single cable UL 1581 sec. 1090Vertical of a single cable UL 1581 sec. 1080 VW–1 > 16 mm2 only
RADOX® UL 3271 / CSA AWM I A/B
Flexible single core
58 HUBER+SUHNER
RADOX® UL 3289/CSA CL 1503
Flexible single core
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, magnets and transformers.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5
Insulation RADOX® 155 extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating 600 V ACTest voltage 2500 V ACOperating temperature (UL temperature rating) +150 °CMin. temperature –55 °C
excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•high resistance to heat pressure•high abrasion resistance•easy to process•soldering resistant•flexible•resistant to impregnation resins •and varnishes
RAD
OX®
UL/
CSA
HUBER+SUHNER 59
Cross section Conductor Core Weight Bending radius
nom. Construction nom. Ø max. Ø nom. min.
AWG mm2 n x mm Ø mm mm kg/100 m
26 0.149 19 x 0.10 0.51 2.13 ± 0.10 0.55 3 x Ø
24 0.205 19 x 0.13 0.61 2.27 ± 0.10 0.66 3 x Ø
22 0.324 19 x 0.16 0.79 2.40 ± 0.10 0.79 3 x Ø
20 0.519 19 x 0.20 0.99 2.61 ± 0.10 1.1 3 x Ø
18 0.823 19 x 0.25 1.23 2.85 ± 0.10 1.5 3 x Ø
(16) 1.50 19 x 0.31 1.55 3.20 ± 0.10 2.1 3 x Ø
14 2.08 19 x 0.37 1.86 3.50 ± 0.10 2.7 3 x Ø
12 3.31 37 x 0.34 2.35 4.00 ± 0.15 4.0 3 x Ø
10 5.26 37 x 0.43 3.02 4.68 ± 0.15 6.1 3 x Ø
(8) 10 80 x 0.40 3.94 6.40 ± 0.15 11.7 3 x Ø
(6) 16 119 x 0.40 5.4 8.90 ± 0.2 18.4 3 x Ø
(4) 25 182 x 0.40 6.7 10.2 ± 0.2 25.8 3 x Ø
(2) 35 266 x 0.40 7.9 11.4 ± 0.2 36.5 3 x Ø
(1) 50 378 x 0.40 9.4 14.0± 0.25 54.3 4 x Ø
(2/0) 70 348 x 0.50 11.5 16.1± 0.3 71.3 4 x Ø
(3/0) 95 444 x 0.50 12.9 17.6± 0.3 93.6 4 x Ø
(4/0) 120 551 x 0.50 14.8 19.3 ± 0.3 113 4 x Ø
Other cross sections on request.
Extract from our delivery programme
RADOX® UL 3289/CSA CL 1503
Flexible single core
60 HUBER+SUHNER
RADOX® UL 3289 / CSA CL 1503
Single core solid wire
ApplicationProtected and fixed installation inside electrical equipment, especially suitable for the connection of motor wind-ings, switchboards, magnets and transformers.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 1
Insulation RADOX® 155 extruded and electron beam crosslinked polyolefin copolymer Core colours various, on request
Technical dataVoltage rating 600 V ACOperating temperature (UL temperature rating) +150 °CMin. temperature –55 °C
excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•high resistance to heat pressure•high abrasion resistance•easy to process•soldering resistant•resistant to impregnation resins •and varnishes
RAD
OX®
UL/
CSA
HUBER+SUHNER 61
Cross section Conductor Core Weight Bending radius
nom. Ø max. Ø nom. min.
AWG mm2 mm mm kg/100 m
24 0.205 0.55 2.15 ± 0.10 0.7 3 x Ø
22 0.324 0.7 2.30 ± 0.10 0.8 3 x Ø
20 0.517 0.8 2.45 ± 0.10 1.0 3 x Ø
18 0.821 1.1 2.70 ± 0.10 1.4 3 x Ø
16 1.31 1.4 3.05 ± 0.10 2.1 3 x Ø
14 2.08 1.8 3.45 ± 0.10 3.1 3 x Ø
12 3.31 2.2 3.80 ± 0.10 4.2 3 x Ø
Other cross sections on request.
Extract from our delivery programme
RADOX® UL 3289 / CSA CL 1503
Single core solid wire
62 HUBER+SUHNER
RADOX® UL4486 / CSA AWM I/II A/B
Multi core cable – halogen free – 300 V
ApplicationPermanent installation indoor and outdoor for the connection of fixed and loose parts.
Composition of cable Cores:
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125 Core colours various, on request
Fillers (optional) RADOX®
Sheath RADOX® 125M Colour grey
Technical dataVoltage rating 300 V ACTest voltage 2000 V ACOperating temperature (UL temperature rating) +125 °CMax. conductor temperature at short circuit (max. 5s) +280 °CMin. operating temperature flexing –25 °C fixed –40 °CMin. bending radius 5 x cable–Ø
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•easy to strip and process•flame retardant•in case of fire no corrosive •gases and low smoke emissionflexible•
RAD
OX®
UL/
CSA
HUBER+SUHNER 63
StandardsApplicance wiring material CSA C22.2 no. 210.2 AWM I/II A/B 125°C 300 V FT1Applicance wiring material UL 758 Style 4486
Fire testsFlame propagation:Vertical of a single cable CSA C22.2 no. 0.3 cl. 4.11.1 FT1Horizontal flame propagation CSA C22.2 no. 0.3 cl. 4.11.2 FT2Vertical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cables EN 50266–2–4, IEC 60332–3–24 Category CContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2Flame propagation:Horizontal flame propagation of an applicance wire UL 1581 sec. 1090Vertical of a single cable UL 1581 sec. 1061Vertical of a single cable UL 1581 sec. 1080 VW–1
ApprovalsCSA Certificate 1241318UL File E63322
RADOX® UL4486 / CSA AWM I/II A/B
Multi core cable – halogen free – 300 V
64 HUBER+SUHNER
Cross section Conductor Core Cable Item no.
nom. Construction nom. R20 IEC 60228 Ø nom. Colours* Ø nom.
n x(G) AWG n x mm Ø max. /km mm mm
2 x 26 19 x 0.10 136 1.37 BU,BN 4.6 ± 0.3 12564229
2 x 24 19 x 0.12 88.5 1.45 BU,BN 4.7 ± 0.3 12567437
2 x 20 19 x 0.20 32.6 1.85 BU,BN 5.5 ± 0.3 12563922
2 x 18 19 x 0.25 21.3 2.10 BU,BN 6.0 ± 0.3 12563923
2 x 16 19 x 0.31 13.7 2.41 BU,BN 6.7 ± 0.3 12563924
2 x 14 19 x 0.37 9.02 2.72 BU,BN 7.3 ± 0.3 12563925
2 x 12 37 x 0.34 5.67 3.21 BU,BN 8.3 ± 0.3 12563926
3 x 26 19 x 0.10 136 1.37 BN,BK,GY 4.8 ± 0.3 12568483
3 x 24 19 x 0.12 88.5 1.45 BN,BK,GY 4.95 ± 0.3 12568485
3 x 20 19 x 0.20 32.6 1.85 BU,BN,BK 5.8 ± 0.3 12563927
3 G 20 19 x 0.20 32.6 1.85 BU,BN,GNYE 5.8 ± 0.3 12564097
3 x 18 19 x 0.25 21.3 2.10 BU,BN,BK 6.4 ± 0.3 12563928
3 G 18 19 x 0.25 21.3 2.10 BU,BN,GNYE 6.4 ± 0.3 12564098
3 x 16 19 x 0.31 13.7 2.41 BU,BN,BK 7.0 ± 0.3 12563929
3 G 16 19 x 0.31 13.7 2.41 BU,BN,GNYE 7.0 ± 0.3 12564099
3 x 14 19 x 0.37 9.02 2.72 BU,BN,BK 7.7 ± 0.3 12563930
3 G 14 19 x 0.37 9.02 2.72 BU,BN,GNYE 7.7 ± 0.3 12564100
3 x 12 37 x 0.34 5.67 3.21 BU,BN,BK 8.8 ± 0.3 12563931
3 G 12 37 x 0.34 5.67 3.21 BU,BN,GNYE 8.8 ± 0.3 12564101
3 x 10 37 x 0.43 3.43 3.88 BU,BN,BK 10.3 ± 0.4 12564198
3 G 10 37 x 0.43 3.43 3.88 BU,BN,GNYE 10.3 ± 0.4 12564199
4 x 26 19 x 0.10 136 1.37 BU, BN,BK,GY 5.25 ± 0.3 12568484
4 x 24 19 x 0.12 88.5 1.45 BU,BN,BK,GY 5.4 ± 0.3 12568486
4 x 18 19 x 0.25 21.3 2.10 BU,BN,BK,GY 7.0 ± 0.3 12563932
4 G 18 19 x 0.25 21.3 2.10 BU,BN,BK,GNYE 7.0 ± 0.3 12564102
4 x 16 19 x 0.31 13.7 2.41 BU,BN,BK,GY 7.8 ± 0.3 12563933
4 G 16 19 x 0.31 13.7 2.41 BU,BN,BK,GNYE 7.8 ± 0.3 12564103
4 x 14 19 x 0.37 9.02 2.72 BU,BN,BK,GY 8.5 ± 0.3 12563934
4 G 14 19 x 0.37 9.02 2.72 BU,BN,BK,GNYE 8.5 ± 0.3 12564104
4 x 12 37 x 0.34 5.67 3.21 BU,BN,BK,GY 9.9 ± 0.3 12563935
4 G 12 37 x 0.34 5.67 3.21 BU,BN,BK,GNYE 9.9 ± 0.3 12564105
4 x 10 37 x 0.43 3.43 3.88 BU,BN,BK,GY 11.5 ± 0.4 12563936
4 G 10 37 x 0.43 3.43 3.88 BU,BN,BK,GNYE 11.5 ± 0.4 12564106
5 x 14 19 x 0.37 9.02 2.72 BU,BN,BK,GY,BK 8.7 ± 0.3 12563937
5 G 14 19 x 0.37 9.02 2.72 BU,BN,BK,GY,GNYE 8.7 ± 0.3 12564107
5 x 12 37 x 0.34 5.67 3.21 BU,BN,BK,GY,BK 10.8 ± 0.4 12563938
5 G 12 37 x 0.34 5.67 3.21 BU,BN,BK,GY,GNYE 10.8 ± 0.4 12564108
5 x 10 37 x 0.43 3.43 3.88 BU,BN,BK,GY,BK 12.6 ± 0.4 12563939
5 G 10 37 x 0.34 3.43 3.88 BU,BN,BK,GY,GNYE 12.6 ± 0.4 12564109
6 x 20 19 x 0.20 32.6 1.85 BK, YE num. 7.5 ± 0.3 12568487
18 x 18 19 x 0.25 21.3 2.10 BK, YE num. 12.6 ± 0.4 12568185
Extract from our delivery programme (Other cross sections on request.)
* abbreviations for core colours see page 154
RADOX® UL4486 / CSA AWM I/II A/B
Multi core cable – halogen free – 300 V
RAD
OX®
UL/
CSA
HUBER+SUHNER 65
Notes
66 HUBER+SUHNER
RADOX® UL4486 / CSA AWM I/II A/B
Multi core cable – screened – halogen free – 300 V
ApplicationPermanent installation indoor and outdoor for the connection of fixed and loose parts.
Composition of cable Cores:
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125 Core colours various, on request
Fillers (optional) RADOX®
Screen tin plated copper braid Separator plastic tape Sheath RADOX® 125M
Colour grey
Technical dataVoltage rating 300 V ACTest voltage 2000 V ACOperating temperature UL temperature rating +125 °CMax. conductor temperature at short circuit (max. 5s) +280 °CMin. operating temperature flexing –25 °C fixed –40 °CMin. bending radius 5 x cable–Ø
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•easy to strip and process•flame retardant•in case of fire no corrosive •gases and low smoke emissionflexible•
RAD
OX®
UL/
CSA
HUBER+SUHNER 67
StandardsApplicance wiring material CSA C22.2 no. 210.2 AWM I/II A/B 125°C 300 V FT1Applicance wiring material UL 758 Style 4486
Fire testsFlame propagation:Vertical of a single cable CSA C22.2 no. 0.3 cl. 4.11.1 FT1Horizontal of a single cable CSA C22.2 no. 0.3 cl. 4.11.2 FT2Vertical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cables EN 50266–2–4, IEC 60332–3–24 Category CContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2Flame propagation:Horizontal flame propagation of an applicance wire UL 1581 sec. 1090Vertical of a single cable UL 1581 sec. 1061Vertical of a single cable UL 1581 sec. 1080 VW–1
ApprovalsCSA Certificate 1241318UL File E63322
RADOX® UL4486 / CSA AWM I/II A/B
Multi core cable – screened – halogen free – 300 V
68 HUBER+SUHNER
RADOX® UL4486 / CSA AWM I/II A/B
Multi core cable – screened – halogen free – 300 V
Cross section Conductor Core Screen Cable Item no.
nom. Construc. nom. R20 IEC 60228 Ø nom. Colours* Ø nom. Ø nom.
n x(G) AWG n x mm Ø max. /km mm mm mm
2 x 20 19 x 0.20 32.6 1.85 BU,BN 4.0 5.9 ± 0.3 12563940
2 x 18 19 x 0.25 21.3 2.10 BU,BN 4.6 6.6 ± 0.3 12563941
2 x 16 19 x 0.31 13.7 2.41 BU,BN 5.3 7.2 ± 0.3 12563942
2 x 14 19 x 0.37 9.02 2.72 BU,BN 6.0 7.9 ± 0.3 12563943
2 x 12 37 x 0.34 5.67 3.21 BU,BN 7.0 8.9 ± 0.3 12563944
3 x 24 19 x 0.12 88.2 1.45 BU,BN,BK 3.7 5.6 ± 0.3 12565389
3 x 20 19 x 0.20 32.6 1.85 BU,BN,BK 4.5 6.4 ± 0.3 12563945
3 G 20 19 x 0.20 32.6 1.85 BU,BN,GNYE 4.5 6.4 ± 0.3 12564110
3 x 18 19 x 0.25 21.3 2.10 BU,BN,BK 5.0 6.9 ± 0.3 12563946
3 G 18 19 x 0.25 21.3 2.10 BU,BN,GNYE 5.0 6.9 ± 0.3 12564111
3 x 16 19 x 0.31 13.7 2.41 BU, BN,BK 5.7 7.6 ± 0.3 12563947
3 G 16 19 x 0.31 13.7 2.41 BU,BN,GNYE 5.7 7.6 ± 0.3 12564112
3 x 14 19 x 0.37 9.02 2.72 BU, BN,BK 6.5 8.3 ± 0.3 12563948
3 G 14 19 x 0.37 9.02 2.72 BU,BN,GNYE 6.5 8.3 ± 0.3 12564113
3 x 12 37 x 0.34 5.67 3.21 BU,BN,BK 7.7 9.6 ± 0.3 12563949
3 G 12 37 x 0.34 5.67 3.21 BU,BN,GNYE 7.7 9.6 ± 0.3 12564114
4 x 24 19 x 0.12 88.2 1.45 WH num. 4.2 6.1 ± 0.3 12565575
4 x 20 19 x 0.20 32.6 1.85 BU,BN,BK,GY 5.2 7.1 ± 0.3 12564504
4 x 18 19 x 0.25 21.3 2.10 BU,BN,BK,GY 5.7 7.6 ± 0.3 12563950
4 G 18 19 x 0.25 21.3 2.10 BU,BN,BK,GNYE 5.7 7.6 ± 0.3 12564115
4 x 16 19 x 0.31 13.7 2.41 BU, BN,BK,GY 6.5 8.4 ± 0.3 12563951
4 G 16 19 x 0.31 13.7 2.41 BU,BN,BK,GNYE 6.5 8.4 ± 0.3 12564116
4 x 14 19 x 0.37 9.02 2.72 BU,BN,BK,GY 7.4 9.3 ± 0.3 12563952
4 G 14 19 x 0.37 9.02 2.72 BU,BN,BK,GNYE 7.4 9.3 ± 0.3 12564117
4 x 12 37 x 0.34 5.67 3.21 BU,BN,BK,GY 8.8 10.7 ± 0.4 12563953
4 G 12 37 x 0.34 5.67 3.21 BU,BN,BK,GNYE 8.8 10.7 ± 0.4 12564118
5 x 14 19 x 0.37 9.02 2.72 BU,BN,BK,GY,BK 8.4 10.4 ± 0.4 12563954
5 G 14 19 x 0.37 9.02 2.72 BU,BN,BK,GY,GNYE 8.4 10.4 ± 0.4 12564119
5 x 12 37 x 0.34 5.67 3.21 BU,BN,BK,GY,BK 9.7 11.6 ± 0.4 12563955
5 G 12 37 x 0.34 5.67 3.21 BU,BN,BK,GY,GNYE 9.7 11.6 ± 0.4 12564120
6 x 28 7 x 0.12 232 1.20 BK,bn,rt,BU,GY,WH 4.4 6.3 ± 0.3 12566635
6 x 20 19 x 0.20 32.6 1.85 BK num. 6.3 8.2 ± 0.3 12564505
6 G 20 19 x 0.20 32.6 1.85 BK num.,GNYE 6.3 8.2 ± 0.3 12564597
8 x 20 19 x 0.20 32.6 1.85 BK num. 7.4 9.3 ± 0.3 12564506
8 G 20 19 x 0.20 32.6 1.85 BK num.,GNYE 7.4 9.3 ± 0.3 12564598
8 x 18 19 x 0.25 21.3 2.10 BK num. 8.5 10.5 ± 0.4 12564507
8 x 16 19 x 0.31 13.7 2.41 BK num. 10.0 12.0 ± 0.4 12564599
3 G 18 + 3 x 2 x 24
19 x 0.2519 x 0.12
21.388.2
2.11.45
BU,RD,GNYE,BN, WH,VT,OG,YE,GN
8.7 10.6 ± 0.4 12581568
Extract from our delivery programme (Other cross sections on request.)
* abbreviations for core colours see page 154
RAD
OX®
UL/
CSA
HUBER+SUHNER 69
Notes
70 HUBER+SUHNER
RADOX® UL4486 / CSA AWM I/II A/B
Multi core cable – halogen free – 600 V
ApplicationPermanent installation indoor and outdoor for the connection of fixed and loose parts.
Composition of cable Cores:
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125 Core colours diverse, on request
Fillers (optional) RADOX®
Sheath RADOX® 125M Colour grey
Technical dataVoltage rating 600 V ACTest voltage 2500 V ACMax. conductor temperature in continuous operation +125 °C 10'000 h +130 °C 3'000 h +145 °C at short circuit (max. 5s) + 280 °CMin. operating temperature flexing –25 °C fixed –40 °CMin. bending radius 5 x cable–Ø
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•easy to strip and process•flame retardant•in case of fire no corrosive •gases and low smoke emissionflexible•
RAD
OX®
UL/
CSA
HUBER+SUHNER 71
StandardsApplicance wiring material CSA C22.2 no. 210.2 AWM I/II A/B 125°C 300 V FT1Applicance wiring material UL 758 Style 4486
Fire testsFlame propagation:Vertical of a single cable CSA C22.2 no. 0.3 cl. 4.11.1 FT1Horizontal of a single cable CSA C22.2 no. 0.3 cl. 4.11.2 FT2Vertical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cables EN 50266–2–4, IEC 60332–3–24 Category CContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2Flame propagation:Horizontal flame propagation of an applicance wire UL 1581 sec. 1090Vertical of a single cable UL 1581 sec. 1061Vertical of a single cable UL 1581 sec. 1080 VW–1
ApprovalsCSA Certificate 1241318UL File E63322
RADOX® UL4486 / CSA AWM I/II A/B
Multi core cable – halogen free – 600 V
72 HUBER+SUHNER
Cross section Conductor Core Cable Item no.
nom. Construction nom. R20 IEC 60228 Ø nom. Colours* Ø nom.
n x (G) AWG n x mm Ø max. /km mm mm1 x 2* 266 x 0.40 0.554 11.1 BK 12.9 ± 0.25 125645161 G 2* 266 x 0.40 0.554 11.1 GNYE 12.9 ± 0.25 125645151 x 1 378 x 0.40 0.385 13.7 BK 16.5 ± 0.3 125645181 G 1 378 x 0.40 0.385 13.7 GNYE 16.5 ± 0.3 12564517
1 x 2/0 348 x 0.50 0.271 15.8 BK 18.6 ± 0.3 125645191 x 3/0 444 x 0.50 0.206 17.3 BK 20.1 ± 0.3 125645202 x 20 19 x 0.20 32.6 2.60 BU,BN 7.0 ± 0.3 125639562 x 18 19 x 0.25 21.3 2.85 BU,BN 7.5 ± 0.3 125639572 x 16 19 x 0.31 13.7 3.20 BU,BN 8.2 ± 0.3 125639582 x 14 19 x 0.37 9.02 3.50 BU,BN 8.8 ± 0.3 125639592 x 12 37 x 0.34 5.67 4.00 BU,BN 9.8 ± 0.3 125639603 x 20 19 x 0.20 32.6 2.60 BU,BN,BK 7.45 ± 0.3 125639613 G 20 19 x 0.20 32.6 2.60 BU,BN,GNYE 7.45 ± 0.3 125641213 x 18 19 x 0.25 21.3 2.85 BU,BN,BK 8.0 ± 0.3 125639623 G 18 19 x 0.25 21.3 2.85 BU,BN,GNYE 8.0 ± 0.3 125641223 x 16 19 x 0.31 13.7 3.20 BU,BN,BK 8.75 ± 0.3 125639633 G 16 19 x 0.31 13.7 3.20 BU,BN,GNYE 8.75 ± 0.3 125641233 x 14 19 x 0.37 9.02 3.50 BU,BN,BK 9.4 ± 0.3 125639643 G 14 19 x 0.37 9.02 3.50 BU,BN,GNYE 9.4 ± 0.3 125641243 x 12 37 x 0.34 5.67 4.00 BU,BN,BK 10.6 ± 0.4 125639653 G 12 37 x 0.34 5.67 4.00 BU,BN,GNYE 10.6 ± 0.4 125641253 G 8 80 x 0.40 1.91 6.40 BK,RD,GNYE 17.0 ± 0.5 12567713
4 G 20 19 x 0.20 33.4 2.60 BU,BK,RD,GNYE 8.3 ± 0.3 125669284 x 18 19 x 0.25 21.3 2.85 BU,BN,BK,GY 8.9 ± 0.3 125639664 G 18 19 x 0.25 21.3 2.85 BU,BN,BK,GNYE 8.9 ± 0.3 125641264 x 16 19 x 0.31 13.7 3.20 BU,BN,BK,GY 9.8 ± 0.3 125639674 G 16 19 x 0.31 13.7 3.20 BU,BN,BK,GNYE 9.8 ± 0.3 125641274 x 14 19 x 0.37 9.02 3.50 BU,BN,BK,GY 10.5 ± 0.4 125639684 G 14 19 x 0.37 9.02 3.50 BU,BN,BK,GNYE 10.5 ± 0.4 125641284 x 12 37 x 0.34 5.67 4.00 BU,BN,BK,GY 11.7 ± 0.4 125639694 G 12 37 x 0.34 5.67 4.00 BU,BN,BK,GNYE 11.7 ± 0.4 125641294 x 10 37 x 0.43 3.43 4.70 BU,BN,BK,GY 13.6 ± 0.4 125639704 G 10 37 x 0.43 3.43 4.70 BU,BN,BK,GNYE 13.6 ± 0.4 125641304 x 6 119 x 0.40 1.25 8.60 BU,BN,BK,GY 25.9 ± 0.6 125645144 G 6 119 x 0.40 1.25 8.60 BU,BN,BK,GNYE 25.9 ± 0.6 125646005 x 24 19 x 0.12 88.5 2.22 WH,GN,YE,GY,BN 8.1 ± 0.3 125659275 x 16 19 x 0.31 13.7 3.20 BU,BN,BK,GY,BK 10.8 ± 0.4 125645085 G 16 19 x 0.31 13.7 3.20 BU,BN,BK,GY,GNYE 10.8 ± 0.4 125646015 x 14 19 x 0.37 9.02 3.50 BU,BN,BK,GY,BK 11.7 ± 0.4 125639715 G 14 19 x 0.37 9.02 3.50 BU,BN,BK,GY,GNYE 11.7 ± 0.4 125641315 x 12 37 x 0.34 5.67 4.00 BU,BN,BK,GY,BK 13.1 ± 0.4 125639725 G 12 37 x 0.34 5.67 4.00 BU,BN,BK,GY,GNYE 13.1 ± 0.4 125641325 x 10 37 x 0.43 3.43 4.70 BU,BN,BK,GY,BK 16.0 ± 0.5 125639735 G 10 37 x 0.34 3.43 4.70 BU,BN,BK,GY,GNYE 16.0 ± 0.5 125641336 G 20 19 x 0.20 33.4 2.60 BN,BU,BK,GNYE,WH 9.8 ± 0.3 125669297 x 24 19 x 0.12 88.5 2.22 BK,YE num. 9.4 ± 0.3 125819679 x 20 19 x 0.20 33.4 2.60 BK,YE num. 12.7 ± 0.4 1256751410 x 18 19 x 0.25 21.3 2.85 BK,YE num. 13.3 ± 0.4 12565173
8 x 2 x 20 19 x 0.20 33.4 2.60 BK,YE num. 20.7 ± 0.5 1256513527 G 18 19 x 0.25 21.3 2.85 BK,YE num., GNYE 20.6 ± 0.5 12565136
15 x 2 x 20 19 x 0.20 33.4 2.60 BK,YE num. 26.7 ± 0.6 12568954
Extract from our delivery programme (Other cross sections on request)
* abbreviations for core colours see page 154
RADOX® UL4486 / CSA AWM I/II A/B
Multi core cable – halogen free – 600 V
RAD
OX®
UL/
CSA
HUBER+SUHNER 73
Notes
74 HUBER+SUHNER
RADOX® UL 4486/CSA AWM I/II A/B
Multi core cable – screened — halogen free — 600 V
ApplicationPermanent installation indoor and outdoor for the connection of fixed and loose parts.
Composition of cable Cores:
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125 Core colours various, on request
Fillers (optional) RADOX®
Screen tin plated copper braid Separator plastic tape Sheath RADOX® 125M
Colour grey
Technical dataVoltage rating 600 V ACTest voltage 2500 V ACOperating temperature (UL temperature rating) +125 °CMax. conductor temperature at short circuit (max. 5s) +280 °CMin. operating temperature flexing –25 °C fixed –40 °CMin. bending radius 5 x cable–Ø
excellent high and low tempera-•ture and ozone resistanceweatherproof•halogen free•easy to strip and process•flame retardant•in case of fire no corrosive •gases and low smoke emissionflexible•
RAD
OX®
UL/
CSA
HUBER+SUHNER 75
StandardsApplicance wiring material CSA C22.2 no. 210.2 AWM I/II A/B 125°C 300 V FT1Applicance wiring material UL 758 Style 4486
Fire testsFlame propagation:Vertical of a single cable CSA C22.2 no. 0.3 cl. 4.11.1 FT1Horizontal of a single cable CSA C22.2 no. 0.3 cl. 4.11.2 FT2Vertical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cables EN 50266–2–4, IEC 60332–3–24 Category CContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2Flame propagation:Horizontal flame propagation of an applicance wire UL 1581 sec. 1090Vertical of a single cable UL 1581 sec. 1061Vertical of a single cable UL 1581 sec. 1080 VW–1
ApprovalsCSA Certificate 1241318UL File E63322
RADOX® UL 4486/CSA AWM I/II A/B
Multi core cable – screened — halogen free — 600 V
76 HUBER+SUHNER
Cross section Conductor Core Screen Cable Item no.
nom. Construct. nom. R20 IEC 60228 Ø nom. Colours* Ø nom. Ø
n x (G) AWG n x mm Ø max. /km mm mm mm
1 x 2* 266 x 0.40 0.554 11.1 BK 12.2 14.1 ± 0.3 12565208
1 G 2* 266 x 0.40 0.554 11.1 GNYE 12.2 14.1 ± 0.3 12565207
1 x 1 378 x 0.40 0.385 13.7 BK 14.8 17.7 ± 0.3 12564525
1 G 1 378 x 0.40 0.385 13.7 GNYE 14.8 17.7 ± 0.3 12564524
1 x 2/0 348 x 0.50 0.271 15.8 BK 16.9 19.8 ± 0.3 12565210
1 x 3/0 444 x 0.50 0.206 17.3 BK 18.4 22.8 ± 0.3 12564526
1 x 4/0 551 x 0.50 0.164 19.2 BK 20.5 25.0 ± 0.3 12564527
2 x 22 19 x 0.16 54.7 2.4 WH num. 5.4 7.3 ± 0.3 12565572
2 x 20 19 x 0.20 32.6 2.60 BU, BN 5.7 7.6 ± 0.3 12563974
2 x 18 19 x 0.25 21.3 2.85 BU, BN 6.3 8.2 ± 0.3 12563975
2 x 16 19 x 0.31 13.7 3.10 BU, BN 7.0 8.9 ± 0.3 12563976
2 x 14 19 x 0.37 9.02 3.50 BU, BN 7.7 9.6 ± 0.3 12563977
2 x 12 37 x 0.34 5.67 4.00 BU, BN 8.7 10.7 ± 0.4 12563978
2 x 8 80 x 0.40 1.96 6.40 BU, BN 13.8 16.8 ± 0.5 12568351
3 x 20 19 x 0.20 32.6 2.60 BU, BN, BK 6.2 8.1 ± 0.3 12563979
3 G 20 19 x 0.20 32.6 2.60 BU, BN, GNYE 6.2 8.1 ± 0.3 12564134
3 x 18 19 x 0.25 21.3 2.85 BU, BN, BK 6.7 8.6 ± 0.3 12563980
3 x 18 19 x 0.25 21.3 2.85 BK, YE num. 6.7 8.6 ± 0.3 12565248
3 G 18 19 x 0.25 21.3 2.85 BU, BN, GNYE 6.7 8.6 ± 0.3 12564135
3 x 16 19 x 0.31 13.7 3.10 BU, BN, BK 7.5 9.4 ± 0.3 12563981
3 G 16 19 x 0.31 13.7 3.10 BU, BN, GNYE 7.5 9.4 ± 0.3 12564136
3 x 14 19 x 0.37 9.02 3.50 BU, BN, BK 8.3 10.3 ± 0.4 12563982
3 G 14 19 x 0.37 9.02 3.50 BU, BN, GNYE 8.3 10.3 ± 0.4 12564137
3 x 12 37 x 0.34 5.67 4.00 BU, BN, BK 9.4 11.3 ± 0.4 12563983
3 G 12 37 x 0.34 5.67 4.00 BU, BN, GNYE 9.4 11.3 ± 0.4 12564138
3 x 8 80 x 0.40 1.96 6.40 BK, YE num. 15.1 18.2 ± 0.5 12565822
3 G 8 80 x 0.40 1.96 6.40 BU, BN, GNYE 15.1 18.2 ± 0.5 12581865
Extract from our delivery programme
* abbreviations for core colours see page 154
Other cross sections on request.
RADOX® UL 4486/CSA AWM I/II A/B
Multi core cable – screened — halogen free — 600 V
RAD
OX®
UL/
CSA
HUBER+SUHNER 77
Cross section Conductor Core Screen Cable Item no.
nom. Construct. nom. R20 IEC 60228 Ø nom. colours* Ø nom. Ø
n x (G) AWG n x mm Ø max. /km mm mm mm
4 x 22 19 x 0.16 54.7 2.4 WH num. 6.6 8.5 ± 0.3 12565574
4 x 18 19 x 0.25 21.3 2.85 BU, BN, BK, GY 7.8 9.7 ± 0.3 12563984
4 x 18 19 x 0.25 21.3 2.85 BK, YE num. 7.8 9.7 ± 0.3 12565247
4 G 18 19 x 0.25 21.3 2.85 BU, BN, BK, GNYE 7.8 9.7 ± 0.3 12564139
4 x 16 19 x 0.31 13.7 3.10 BU, BN, BK, GY 8.7 10.7 ± 0.4 12563985
4 G 16 19 x 0.31 13.7 3.10 BU, BN, BK, GNYE 8.7 10.7 ± 0.4 12564140
4 x 14 19 x 0.37 9.02 3.50 BU, BN, BK, GY 9.3 11.3 ± 0.4 12563986
4 G 14 19 x 0.37 9.02 3.50 BU, BN, BK, GNYE 9.3 11.3 ± 0.4 12564141
4 G 14 19 x 0.37 9.02 3.50 BK, YE num. GNYE 9.3 11.3 ± 0.4 12565206
4 x 12 37 x 0.34 5.67 4.00 BU, BN, BK, GY 10.7 12.7 ± 0.4 12563987
4 G 12 37 x 0.34 5.67 4.00 BU, BN, BK, GNYE 10.7 12.7 ± 0.4 12564142
4 G 12 37 x 0.34 5.67 4.00 BK, YE num. GNYE 10.7 12.7 ± 0.4 12565246
4 G 10 37 x 0.43 3.43 4.70 BK, YE num., GNYE 12.8 15.9 ± 0.5 12565245
4 G 8 80 x 0.40 1.96 6.40 BK, YE num., GNYE 17.1 20.2 ± 0.5 12565244
4 x 6 119 x 0.40 1.25 8.60 BU, BN, BK, GY 22.5 27.3 ± 0.6 12565176
4 G 6 119 x 0.40 1.25 8.60 BK, YE num., GNYE 22.5 27.3 ± 0.6 12565204
4 x 4 182 x 0.40 0.798 9.90 BU, BN, BK, GY 25.6 30.4 ± 0.6 12564523
4 G 4 182 x 0.40 0.798 9.90 BU, BN, BK, GNYE 25.6 30.4 ± 0.6 12564602
4 G 4 182 x 0.40 0.798 9.90 BK, YE num., GNYE 25.6 30.4 ± 0.6 12565241
5 x 18 19 x 0.25 21.3 2.85 BU, BN, BK, GY, BK 8.7 10.7 ± 0.4 12565175
5 x 18 19 x 0.25 21.3 2.85 BK, YE num. 8.7 10.7 ± 0.4 12565202
5 x 14 19 x 0.37 9.02 3.50 BU, BN, BK, GY, BK 10.7 12.7 ± 0.4 12563988
5 G 14 19 x 0.37 9.02 3.50 BU, BN, BK, GY, GNYE 10.7 12.7 ± 0.4 12564143
5 x 12 37 x 0.34 5.67 4.00 BU, BN, BK, GY, BK 12.1 14.0 ± 0.4 12563989
5 G 12 37 x 0.34 5.67 4.00 BU, BN, BK, GY, GNYE 12.1 14.0 ± 0.4 12564144
6 x 14 19 x 0.37 9.02 3.50 BK, YE num. 11.5 13.4 ± 0.4 12581542
4 x 18+2 x 22
19 x 0.2519 x 0.16
21.354.7
2.852.4
WH num. 9.2 11.2 ± 0.4 12565573
12 G 16 19 x 0.31 13.7 3.10 BK, YE num., GNYE 14.0 17.1 ± 0.5 12568520
12 G 14 19 x 0.37 9.02 3.50 BK, YE num., GNYE 15.7 18.8 ± 0.5 12568522
25 G 16 19 x 0.31 13.7 3.10 BK, YE num., GNYE 20.2 24.8 ± 0.5 12568521
25 G 14 19 x 0.37 9.02 3.50 BK, YE num., GNYE 22.9 27.6 ± 0.6 12568523
30 G 14 19 x 0.37 9.02 3.50 BK, YE num., GNYE 23.9 28.7 ± 0.6 12568524
Extract from our delivery programme – continuation
* abbreviations for core colours see page 154.
Other cross sections on request.
RADOX® UL 4486/CSA AWM I/II A/B
Multi core cable – screened — halogen free — 600 V
78 HUBER+SUHNER
MA 12 A1 system element 80
MA 12 E1, single core, screened 82
MA 12 E2, screened pair 84
MA 14 A1, single core 86
MIL 5932 A1, single core 88
MIL 5932 E1, single core, screened 90
MIL 5932/34 E2, E3, E4, screened pair 92
MIL 4412 A1, single core 94
MIL 4412 E1, single core, screened 96
MIL 4412 E2, screened pair 98
VG single cores and cables 100 – 108
RADOX® MFH, power and signal cables, multi core, screend and unscreend 110
Hybrid cables 112 – 113
RADOX® System cables
Single cores, single core cables, multi core cables and wires
All our cables fully comply with the European directives 76/769/EWG, 2003/11/EG, 2000/53/EG, 2003/53/EG and 2002/95/EG (RoHS).
HUBER+SUHNER 79
halogen free, flame retardant•
excellent chemical and mechanical resistance•
flexible, easy to process, soldering resistant•
temperature range –40 °C bis +120 °C•
voltage rating 600 V AC•
dimensions according to MIL–W–81044/12•
easy to strip, easy to process•
RAD
OX®
sys
tem
cab
les
80 HUBER+SUHNER
MA 12 A1
System element
ApplicationDry and protected, flexible and fixed installation inside electrical equipment, elements of control and supply cables and system cables.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation Multi A–12 polyester, extruded polyster
Colours various, on request
Technical dataVoltage rating Uo/U 600 V ACTest voltage 3000 V ACTemperature range –40 °C up to +120 °CMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
halogen free•easy to process•high media and abrasion •resistanceexcellent resistance to high and •low temperaturesflame retardant•high resistance to heat pressure•
HUBER+SUHNER 81
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Weight
nom.Construction
nom.Ø max.
R20MIL–W–81044/12
Ø nom.
AWG mm2 n x mm Ø mm max. /km mm kg/100 m
28 0.09 7 x 0.13 0.40 225.0 0.76 ± 0.05 0.10
26 0.15 19 x 0.10 0.51 135.5 0.87 ± 0.05 0.17
24 0.25 19 x 0.13 0.61 85.96 1.02 ± 0.05 0.30
22 0.38 19 x 0.16 0.79 53.15 1.19 ± 0.05 0.43
20 0.60 19 x 0.20 0.99 32.42 1.40 ± 0.05 0.65
18 0.93 19 x 0.25 1.23 20.44 1.66 ± 0.05 0.95
16 1.25 19 x 0.29 1.40 15.78 1.83 ± 0.05 1.30
14 1.93 19 x 0.35 1.64 10.04 2.27 ± 0.08 1.86
12 2.97 37 x 0.32 2.24 6.63 2.75 ± 0.08 2.87
10 4.74 37 x 0.40 2.77 4.14 3.53 ± 0.1 4.76
–– 0,5 19 x 0.18 0.91 40.1 1.29 ± 0.05 0.52
–– 1,5 37 x 0.22 1.57 13.7 2.10 ± 0.05 1.52
–– 2,5 37 x 0.29 1.97 8.21 2.55 ± 0.08 2.37
–– 4,0 56 x 0.30 2.50 5.09 3.10 ± 0.15 3.80
–– 6,0 84 x 0.30 2.98 3.39 3.65 ± 0.15 5.90
Other cross sections on request.
Extract from our delivery programme
MA 12 A1
System element
82 HUBER+SUHNER
MA 12 E1
Single core – screened
ApplicationDry and protected, flexible and fixed installation inside electrical equipment, elements of control and supply cables and system cables.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation Multi A–12 polyester, extruded polyster
Core colours white or blue EMV screen optimised Sheath Multi A–12 polyester
Colour white
Technical dataVoltage rating Uo/U 600 V ACTest voltage 2500 V ACTemperature range –40 °C up to +120 °CTransfer impedance up to 30 MHz 250 m /mMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
halogen free•easy to process•high media and abrasion •resistanceexcellent resistance to high and •low temperaturesflame retardant•high resistance to heat pressure•constructions and dimensions •acc. to NEMA WC 27500
HUBER+SUHNER 83
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Gewicht
nom.Construction
nom.max. Ø R20 IEC 60228 Ø Outer–Ø nom.
AWG mm2 n x mm Ø mm max. /km mm mm kg/100 m
26 0.15 19 x 0.10 0.51 135.5 0.87 ± 0.05 1.65 ± 0.1 0.17
24 0.25 19 x 0.13 0.61 85.96 1.02 ± 0.05 1.90 ± 0.1 0.30
22 0.38 19 x 0.16 0.79 53.15 1.19 ± 0.05 2.05 ± 0.1 0.43
20 0.60 19 x 0.20 0.99 32.42 1.40 ± 0.05 2.30 ± 0.1 0.65
18 0.93 19 x 0.25 1.23 20.44 1.66 ± 0.05 2.50 ± 0.1 0.95
16 1.25 19 x 0.29 1.40 15.78 1.83 ± 0.05 2.70 ± 0.1 1.30
14 1.93 37 x 0.26 1.80 10.04 2.27 ± 0.08 3.15 ± 0.1 1.97
12 2.97 37 x 0.32 2.24 6.63 2.75 ± 0.08 3.60 ± 0.1 2.87
Other cross sections on request.
Extract from our delivery programme
MA 12 E1
Single core – screened
84 HUBER+SUHNER
MA 12 E2
Screend pair
ApplicationDry and protected, flexible and fixed installation inside electrical equipment, elements of control and supply cables and system cables.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation Multi A–12 polyester, extruded polyester
Core colours white/blue, white/red, white/black, white/greentwo cores twisted
EMV screen optimised Sheath Multi A–12 polyester
Colour white
Technical dataVoltage rating Uo/U 600 V ACTest voltage 2500 V ACTemperature range –40 °C up to +120 °CTransfer impedance up to 30 MHz 250 m /mMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
halogen free•easy to process•high media and abrasion •resistanceexcellent resistance to high and •low temperaturesflame retardant•high resistance to heat pressure•constructions and dimensions •acc. to NEMA WC 27500
HUBER+SUHNER 85
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Weight
nom.Construction
nom.Ø max. R20 IEC 60228 Ø Outer–Ø nom.
AWG mm2 n x mm Ø mm max. /km mm mm kg/100 m
2x26 0.15 19 x 0.10 0.51 138.5 0.87 ± 0.05 2.60 ± 0.1 0.94
2x24 0.25 19 x 0.13 0.61 87.9 1.02 ± 0.05 2.85 ± 0.1 1.33
2x22 0.38 19 x 0.16 0.79 54.4 1.19 ± 0.05 3.15 ± 0.1 1.71
2x20 0.60 19 x 0.20 0.99 33.2 1.40 ± 0.05 3.60 ± 0.1 2.14
2x18 0.93 19 x 0.25 1.23 20.9 1.66 ± 0.05 4.30 ± 0.1 3.38
Other cross sections on request.
Extract from our delivery programme
MA 12 E2
Screend pair
86 HUBER+SUHNER
MA 14 A1
Single core
ApplicationProtected, flexible and fixed installation inside electrical equipment, elements of control and supply cables and system cables.
Composition of cable Conductor stranded tin plated copper, acc. to IEC 60228, class 5Insulation 1 high tech polymerInsulation 2 aromatic polymer
Colours various, on request
Technical dataVoltage rating Uo/U 600 V ACTest voltage 2500 V ACTemperature range –40 °C up to +140 °CMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
halogen free•easy to process•high media and abrasion •resistanceexcellent resistance to high and •low temperaturesflame retardant•high resistance to heat pressure•constructions and dimensions •acc. to MIL–W–81044
HUBER+SUHNER 87
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Weight
nom.Construction
nom.Ø max.
R20MIL–W–81044/12
Ø nom.
AWG mm2 n x mm Ø mm max. /km mm kg/100 m
26 (0.15) 19 x 0.10 0.51 135.5 0.87 ± 0.02 0.18
24 (0.25) 19 x 0.13 0.61 85.96 1.02 ± 0.02 0.30
22 (0.38) 19 x 0.16 0.77 53.15 1.18 ± 0.02 0.43
20 (0.60) 19 x 0.20 0.99 32.42 1.39 ± 0.02 0.65
18 (0.93) 19 x 0.25 1.23 20.44 1.67 ± 0.03 0.95
16 (1.25) 19 x 0.29 1.40 15.78 1.83 ± 0.03 1.30
14 (1.96) 37 x 0.26 1.74 10.8 2.29 ± 0.04 1.97
12 (2.97) 37 x 0.32 2.22 6.63 2.78 ± 0.04 2.87
–– 0.50 19 x 0.18 0.91 40.1 1.30 ± 0.02 0.53
–– 0.75 19 x 0.22 1.12 26.7 1.52 ± 0.03 0.79
–– 1.00 19 x 0.25 1.23 20.0 1.67 ± 0.03 0.94
–– 1.50 37 x 0.22 1.57 13.7 2.04 ± 0.04 1.48
–– 2.50 37 x 0.29 1.97 8.21 2.54 ± 0.04 2.36
Other cross sections on request.
Extract from our delivery programme
MA 14 A1
Single core
88 HUBER+SUHNER
MIL 5932 A1
Single core
ApplicationProtected, flexible and fixed installation inside electrical equipment, elements of control and supply cables and system cables.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5Insulation ETFE–X, extruded fluorcarbon, electron beam crosslinked
Colours various, on request
Technical dataVoltage rating Uo/U 600 V ACTest voltage 2500 V ACTemperature range –65 °C up to +150 °CMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
easy to process•resistant to oils, fuels, lubricants, •alkaline solutions and acidsnotch and abrasion resistant•excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•high resistance to heat pressure•high media and abrasion •resistanceconstructions and dimensions •acc. to MIL–W–22759
HUBER+SUHNER 89
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Weight
nom.Construction
nom.Ø max.
R20MIL–W–81044/12
Ø nom.
AWG mm2 n x mm Ø mm max. /km mm kg/100 m
26 0.15 19 x 0.10 0.51 135.5 0.81 ± 0.05 0.21
24 0.25 19 x 0.13 0.61 85.96 0.94 ± 0.05 0.30
22 0.38 19 x 0.16 0.77 53.15 1.09 ± 0.05 0.42
20 0.60 19 x 0.20 0.99 32.42 1.27 ± 0.05 0.64
18 0.93 19 x 0.25 1.23 20.44 1.52 ± 0.05 0.97
16 1.25 19 x 0.28 1.40 15.78 1.73 ± 0.05 1.25
14 1.93 19 x 0.35 1.68 10.04 2.16 ± 0.08 1.95
12 2.97 37 x 0.32 2.22 6.63 2.62 ± 0.08 2.95
Other cross sections on request.
Extract from our delivery programme
MIL 5932 A1
Single core
90 HUBER+SUHNER
MIL 5932 E1
Single core – screened
ApplicationProtected, flexible and fixed installation inside electrical equipment, elements of control and supply cables and system cables.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5Insulation ETFE–X, extruded fluorcarbon, electron beam crosslinked
Core colours various, on requestEMV screen optimisedSheath ETFE–X, extruded fluorcarbon, electron beam crosslinked
Colour white
Technical dataVoltage rating Uo/U 600 V ACTest voltage 2500 V ACTemperature range –55 °C up to +150 °CMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
easy to process•resistant to oils, fuels, lubricants, •alkaline solutions and acidsnotch and abrasion resistant•excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•high resistance to heat pressure•high media and abrasion •resistanceconstructions and dimensions •acc. to MIL–W–22759
HUBER+SUHNER 91
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Weight
nom. nom. Ø max. R20 IEC 60228 Ø Outer–Ø nom.
AWG mm2 n x mm Ø mm max. /km mm mm kg/100 m
26 0.15 19 x 0.10 0.50 135.5 0.81 ± 0.05 1.64 ± 0.12 0.17
24 0.25 19 x 0.13 0.60 85.96 0.94 ± 0.05 1.76 ± 0.12 0.30
22 0.38 19 x 0.16 0.76 53.15 1.09 ± 0.05 1.90 ± 0.12 0.43
20 0.60 19 x 0.20 0.96 32.42 1.27 ± 0.05 2.09 ± 0.15 0.65
18 0.93 19 x 0.25 1.20 20.44 1.52 ± 0.05 2.35 ± 0.15 0.95
16 1.25 19 x 0.28 1.36 15.78 1.73 ± 0.05 2.55 ± 0.15 1.30
Other cross sections on request.
Extract from our delivery programme
MIL 5932 E1
Single core – screened
92 HUBER+SUHNER
MIL 5932/34 E2, E3, E4
Screened system element
ApplicationFor applications inside electrical equipment and for control and supply cables.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5Insulation ETFE–X, extruded fluorcarbon, electron beam crosslinked
Core colours various, on requesttwo cores twisted
EMV screen optimisedSheath ETFE–X, extruded fluorcarbon, electron beam crosslinked
Colour white
Technical dataVoltage rating Uo/U 600 V ACTest voltage 2500 V ACTemperature range –55 °C up to +150 °CMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
easy to process•resistant to oils, fuels, lubricants, •alkaline solutions and acidsnotch and abrasion resistant•excellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•high resistance to heat pressure•
Figure shows MIL 5932 E2
HUBER+SUHNER 93
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Weight
nom.Construction
nom.Ø max. R20 IEC 60228 Ø Outer–Ø nom.
AWG mm2 n x mm Ø mm max. /km mm mm kg/100 m
26 0.15 19 x 0.10 0.51 140.0 0.81 ± 0.05 2.45 ± 0.12 1.1
24 0.25 19 x 0.12 0.61 88.5 0.94 ± 0.05 2.70 ± 0.12 1.3
22 0.38 19 x 0.16 0.77 54.7 1.09 ± 0.05 2.98 ± 0.12 1.7
20 0.60 19 x 0.20 0.99 33.4 1.27 ± 0.05 3.36 ± 0.12 2.2
18 0.96 19 x 0.25 1.23 21.1 1.52 ± 0.05 3.87 ± 0.12 3.0
16 1.2 19 x 0.29 1.40 14.9 1.73 ± 0.05 4.34 ± 0.13 3.7
14 1.94 19 x 0.36 1.68 10.3 2.15 ± 0.05 5.20 ± 0.13 5.4
Other cross sections on request.
Extract from our delivery programme
MIL 5932/34 E2, E3, E4
Screened system element
94 HUBER+SUHNER
MIL 4412 A1
Single core
ApplicationFor protected installations inside electrical equipment, elements of control and supply cables and system cables.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5Insulation 1 polyalken, extruded polyalken, electron beam crosslinkedInsulation 2 XLPVDF, extruded polyvinylidenfluorid, electron beam crosslinked
Core colours various, on request
Technical dataVoltage rating Uo/U 600 V ACTest voltage 2500 V ACTemperature range –65 °C up to +150 °CMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
flame retardant•easy to process•high media and abrasion •resistanceexcellent high and low tempera-•ture and ozone resistanceweatherproof•constructions and dimensions •acc. to MIL–W–81044
HUBER+SUHNER 95
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Weight
nom.Construction
nom.Ø max.
R20MIL–W–81044/12
Ø nom.
AWG mm2 n x mm Ø mm max. /km mm kg/100 m
28 0.09 7 x 0.13 0.40 225.1 0.76 ± 0.05 0.13
26 0.15 19 x 0.10 0.51 135.5 0.87 ± 0.05 0.19
24 0.25 19 x 0.13 0.61 85.96 1.02 ± 0.05 0.30
22 0.38 19 x 0.16 0.77 53.15 1.18 ± 0.05 0.43
20 0.60 19 x 0.20 0.99 32.42 1.40 ± 0.05 0.65
18 0.93 19 x 0.25 1.23 20.44 1.66 ± 0.05 0.95
16 1.25 19 x 0.29 1.40 15.78 1.83 ± 0.05 1.30
14 1.93 19 x 0.36 1.68 10.04 2.27 ± 0.08 1.97
12 2.97 37 x 0.32 2.22 6.63 2.75 ± 0.08 2.87
Other cross sections on request.
Extract from our delivery programme
MIL 4412 A1
Single core
96 HUBER+SUHNER
MIL 4412 E1
Single core – screened
ApplicationFor protected installations inside electrical equipment, elements of control and supply cables and system cables.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5Insulation 1 polyalken, extruded polyalken, electron beam crosslinkedInsulation 2 XLPVDF, extruded polyvinylidenfluorid, electron beam crosslinked
Core colours various, on requestEMV screen optimisedSheath XLPVDF, electron beam crosslinked
Colour white
Technical dataVoltage rating Uo/U 600 V ACTest voltage 2500 V ACTemperature range –55 °C up to +150 °CTransfer impedance up to 30 MHz 250 m /mMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
flame retardant•easy to process•high media and abrasion •resistanceexcellent high and low tempera-•ture and ozone resistanceweatherproof•constructions and dimensions •acc. to NEMA WC 27500
HUBER+SUHNER 97
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Weight
nom.Construction
nom.Ø max. R20 IEC 60228 Ø Outer–Ø nom.
AWG mm2 n x mm Ø mm max. /km mm mm kg/100 m
26 0.15 19 x 0.10 0.51 135.5 0.87 ± 0.05 1.65 ± 0.1 0.17
24 0.25 19 x 0.13 0.61 85.96 1.02 ± 0.05 1.90 ± 0.1 0.30
22 0.38 19 x 0.16 0.79 53.15 1.19 ± 0.05 2.05 ± 0.1 0.43
20 0.60 19 x 0.20 0.99 32.42 1.40 ± 0.05 2.30 ± 0.1 0.65
18 0.93 19 x 0.25 1.23 20.44 1.66 ± 0.05 2.50 ± 0.1 0.95
16 1.25 19 x 0.29 1.40 15.78 1.83 ± 0.05 2.70 ± 0.1 1.30
14 1.93 19 x 0.36 1.80 10.04 2.27 ± 0.08 3.15 ± 0.1 1.97
12 2.97 37 x 0.32 2.24 6.63 2.75 ± 0.08 3.60 ± 0.1 2.87
Other cross sections on request.
Extract from our delivery programme
MIL 4412 E1
Single core – screened
98 HUBER+SUHNER
MIL 4412 E2
Screened pair
ApplicationFor protected installation inside electrical equipment, elements of control and supply cables and system cables.
Composition of cableConductor stranded tin plated copper, acc. to IEC 60228, class 5Insulation 1 polyalken, extruded polyalken, electron beam crosslinkedInsulation 2 XLPVDF, extruded polyvinylidenfluorid, electron beam crosslinked
Core colours various, on requesttwo cores twisted
EMVscreen optimisedSheath XLPVDF, electron beam crosslinked
Colour white
Technical dataVoltage rating Uo/U 600 V ACTest voltage 2500 V ACTemperature range –55 °C up to +150 °CTransfer impedance up to 30 MHz 200 m /mMin. bending radius 3 x core–Ø
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
easy to process•high resistance to heat pressure•high chemical and abrasion •resistanceexcellent high and low tempera-•ture and ozone resistanceweatherproof•flame retardant•constructions and dimensions •acc. to NEMA WC 27500
HUBER+SUHNER 99
RAD
OX®
sys
tem
cab
les
Cross section Conductor Core Weight
nom.Construction
nom.Ø max. R20 IEC 60228 Ø Outer–Ø nom.
AWG mm2 n x mm Ø mm max. /km mm mm kg/100 m
2 x 26 0.15 19 x 0.10 0.51 138.5 0.87 ± 0.05 2.60 ± 0.1 0.94
2 x 24 0.25 19 x 0.13 0.61 87.9 1.02 ± 0.05 2.85 ± 0.1 1.33
2 x 22 0.38 19 x 0.16 0.79 54.4 1.19 ± 0.05 3.15 ± 0.1 1.71
2 x 20 0.60 19 x 0.20 0.99 33.2 1.40 ± 0.05 3.60 ± 0.1 2.14
2 x 18 0.93 19 x 0.25 1.23 20.9 1.66 ± 0.05 4.30 ± 0.1 3.38
Other cross sections on request.
Extract from our delivery programme
MIL 4412 E2
Screened pair
100 HUBER+SUHNER
ApplicationWiring of electrical/electronic systems, for system cables in defence, aircraft, sensor systems, instrumentation, motors, transformers and industrial automation.
Cross section from to type A 0.25 – 16 mm2
type G 1.5 – 95 mm2
Insulation material type A ETFE type G polyolefin–XVoltage rating Uo/U 600 V AC Number of conductors 1Conductor class VG 95218/BWB specificationJacket –
VG 95218 T020
Type A and type G
temperature range •–55 °C up to +150 °Cresistant to oils, fuels, lubricants, •alkaline solutions and acidsnotch and abrasion resistant•small outer diameter, low weight•flame retardant,•self-extinguishingeasy to strip•easy to process•soldering resistant •
HUBER+SUHNER 101
RAD
OX®
sys
tem
cab
les
ApplicationWiring of electrical/electronic systems, for system cables in defence, aircraft, sensor systems, instrumentation, motors, transformers and industrial automation.
Cross section from to type E 0.15 – 3 mm2
type F 0.15 – 95 mm2
Insulation material type E high tech polymer/aromatic p. type F polyolefin–XVoltage rating Uo/U 600 V AC Number of conductors 1Conductor class VG 95218/BWB specificationJacket –
VG 95218 T020
Type E and type F
temperature range •–55 °C up to +105 °Cresistant to oils, fuels, lubricants, •alkaline solutions and acidsnotch and abrasion resistant•small outer diameter, low weight•flame retardant,•self-extinguishingeasy to strip•easy to process•soldering resistant •
102 HUBER+SUHNER
ApplicationWiring of electrical/electronic systems, for system cables in defence, aircraft, sensor systems, instrumentation, motors, transformers and industrial automation.
Cross section from to 0.25 – 3 mm2
Insulation material type C high tech polymer/aromatic p. type G Polyolefin–XVoltage rating Uo/U 600 V AC Number of conductors 2 – 4Conductor class VG 95218/BWB specificationJacket –
VG 95218 T021
Type C and type E
type C acc. to T020 type E•type E acc. to T020 type A•
HUBER+SUHNER 103
RAD
OX®
sys
tem
cab
les
ApplicationWiring of electrical/electronic systems, for system cables in defence, aircraft, sensor systems, instrumentation, motors, transformers and industrial automation.
Cross section from to 0.25 – 2.5 mm2
Insulation material ETFEVoltage rating Uo/U 600 V AC Number of conductors 1Conductor class VG 95218/BWB specificationSeparator EMV screeningJacket ETFE
VG 95218 T022
Type C screened
temperature range •–55 °C up to +150 °Cresistant to oils, fuels, lubricants, •alkaline solutions and acidsnotch and abrasion resistant•small outer diameter, low weight•flame retardant,•self-extinguishingeasy to strip•easy to process•soldering resistant •
104 HUBER+SUHNER
ApplicationWiring of electrical/electronic systems, for system cables in defence, aircraft, sensor systems, instrumentation, motors, transformers and industrial automation.
Cross section from to 0.25 – 3.0 mm2
Insulation material ETFEVoltage rating Uo/U 600 V AC Number of conductors 2 – 7Conductor class VG 95218/BWB specificationSeparator EMV screeningJacket ETFE
VG 95218 T023
Type F, multi core screened
temperature range •–55 °C up to +150 °Cresistant to oils, fuels, lubricants, •alkaline solutions and acidsnotch and abrasion resistant•small outer diameter, low weight•flame retardant,•self-extinguishingeasy to strip•easy to process•soldering resistant •
HUBER+SUHNER 105
RAD
OX®
sys
tem
cab
les
ApplicationSystem cables in defence, aircraft, sensor systems and instrumentation.
Cross section from to 1.5 – 95 mm2
Insulation material RADOX®
Voltage rating U0/U 600 V AC Number of conductors 1Conductor class VG 95218/BWB specificationSeparator –Jacket RADOX® elastomer S
VG 95218 T024
Type K
temperature range •–40 °C up to +150 °Cweatherproof•resistant to mineral oils and fuels•high abrasion resistance•flame resistant, self-extinguishing•non-melting•flexible•system compatibility with heat •shrink parts according to VG 95343 part 14
106 HUBER+SUHNER
ApplicationSystem cables in defence, sensor systems, instrumentation and ground wires.
Cross section from to 10 – 240 mm2
Insulation material RADOX® elastomer SVoltage rating Uo/U 600 V AC Number of conductors 1Conductor class VG 95218/BWB specification, plain
VG 95218 T025
Type G, high flexible
temperature range •–40 °C up to +150 °Cweatherproof•resistant to mineral oils and fuels•high abrasion resistance•flame resistant, self-extinguishing•non-melting•flexible•system compatibility with heat •shrink parts according to VG 95343 part 14
HUBER+SUHNER 107
RAD
OX®
sys
tem
cab
les
ApplicationControl and supply cables in fixed and moving systems of defence and sensor systems.
Cross section from to 0.4 – 35 mm2
Insulation material ETFEVoltage rating Uo/U 600 V AC Number of conductors 2 – 61Conductor class VG 95218/BWB specificationSeparator –Jacket RADOX® elastomer S
VG 95218 T027
Type B, multi core
temperature range •–40 °C up to +150 °Cweatherproof•resistant to mineral oils and fuels•high abrasion resistance•flame resistant, self-extinguishing•non-melting•flexible•system compatibility with heat •shrink parts according to VG 95343 part 14
108 HUBER+SUHNER
ApplicationControl and supply cables in fixed and moving systems of defence and sensor systems.
Cross section from to 0.25 – 10 mm2
Insulation material ETFEVoltage rating Uo/U 600 V AC Number of conductors 2 – 104Conductor class VG 95218/BWB specificationSeparator EMV screening (type A double screen)Jacket RADOX® elastomer S
VG 95218 T028
Type D and type A, multi core, screened
temperature range •–40 °C up to +150 °Cweatherproof•resistant to mineral oils and fuels•high abrasion resistance•flame resistant, self-extinguishing•non-melting•flexible•system compatibility with heat •shrink parts according to VG 95343 part 14
HUBER+SUHNER 109
RAD
OX®
sys
tem
cab
les
Notes
110 HUBER+SUHNER
RADOX® MFH
MFH–S Signal cable screened and unscreened
MFH–P Power cable
ApplicationFor fixed installations in dry, damp or wet locations, inside and outside of ships, industrial equipment, defenceequipment, buses, other vehicles and railway rolling stock.
Composition of cable Centre (if necessary) RADOX® filler Cores 2 x 0.75 mm2
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 type Multi A 14 A2–0.75 Dual wall insulation high tech polymer Core colours see table two cores twisted
Fillers (optional) RADOX®
EMV screening optimised tin plated copper braid, optical coverage: 85 %Separator textile yarnSheath RADOX® elastomer S FH
Colour black
Technical dataVoltage rating Uo/U 600 / 1000 V ACTest voltage 3500 V ACTemperature range –25 °C up to +120 °CMin. bending radius fixed 12 mm 3 x cable–Ø
12 mm 4 x cable–Ø flexing 12 mm 5 x cable–Ø
12 mm 6 x cable–Ø
Fire testsFlame propagation:Vertial of a single cable EN 50265–2–1, IEC 60332–1Content of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/g
ozone, hydrolysis, chemical •resistantweatherproof•easy to process•leight weight•wide operating temperature •rangehalogen free•flame retardant•
HUBER+SUHNER 111
RAD
OX®
sys
tem
cab
les
Cross section StrandedR20
IEC 60228 ZT max.** Screen CableCore
colours Weight Item Nr.
Ø max. max. Ø Ø nom.
n x mm2 mm /km m /m mm mm kg/100 m
5 x 2 x 0.5 6.7 40.1 80 7.4 9.6 ± 0.3 WH num. 14.5 12566769
21 x 2 x 0.5 13.3 40.1 55 14.4 17.7 ± 0.5 WH num. 48.7 12566772
4 x 2 x 0.75 6.9 26.7 80 7.6 10.0 ± 0.3 WH num. 16.4 12568842
Other cross sections on request.
Extract from our delivery programme
RADOX® MFH
MFH–S Signal cable screened and unscreened
MFH–P Power cable
ApprovalsGERMANISCHER LLOYD Certificate no. 43159–02 HHIEC 60092–359:1999 IEC 60332–1:1999 IEC 60332–3 cat. A: 1992IEC 60754–1:1994 IEC 60754–2:1997 IEC61034–2:1997
112 HUBER+SUHNER
ApplicationControl cable, CCTV for example in tunnels, buildings, airports
Composition of cablecoaxial cable 75 type RG_179–B/U
Inner conductor steel, copper and silver plated Ø: 0.30 mm Insulation PTFE Ø: 1.53 mm Screening silver plated copper braid Ø: 2.00mm Sheath FEP, colour: brown Ø: 2.54 mm
2 pairs of 2 x 0.25 mm2 type Multi A–14 A2–0.25 Conductor tin plated copper Ø: 19 x 0.12 mm Dual wall high tech polymer Ø: 1.02 mm Colours blue/brown, black/grey Ø: 2.04 mm
3 x fillers RADOX®
Separator plastic tape Sheath RADOX® elastomer S FH
Colour black Ø: 7.1 ± 0.3 mm
Technical dataConductor resistance at 20 °C <86.0 /kmVoltage rating 600 V ACTest voltage 2500 VMax. conductor temperature +120 °CMin. operating temperature –25 °CMin. bending radius 10 x cable–Ø
Coaxial cable RG_179-B/U:Impedance 75 Capacitance 63 pF/mVelocity of signal propagation 69 % of the speed of lightAttenuation at 20 °C (typ. value) f = 1 MHz 3.0 dB/100m f = 10 MHz 9.5 dB/100m. f = 100 MHz 30 dB/100m
Hybrid cables
2 x 2 x 0.25 mm2 + 1KO MA14 / REMS FH BK (example out of our product range)
customised solutions•physical and chemical •characteristics according to specificationspower and data transmission•installation of one cable only•small dimensions•low weight•multifunctional•
HUBER+SUHNER 113
RAD
OX®
sys
tem
cab
les
Hybrid cables
3 x 24 AWG + 3 x KO 2253D–02 (example out of our product range)
ApplicationControl cable, CCTV for example in tunnels, buildings, airports
Composition of cable3 coaxial cables 75 type K 02253 D–02
Inner conductor steel, copper and silver plated Ø: 0.30 mm Insulation PTFE Ø: 1.53 mm Screening 1 silver plated copper braid Ø: 2.00 mm Screening 2 silver plated copper braid Ø: 2.50 mm Sheath FEP, colour: brown Ø: 3.00 mm
3 cores 24 AWG type 22759–32A1–24 Conductor tin plated copper Ø: 19 x 0.13 mm Insulation XETFE Ø: 0.94 mm Colours white, blue, orange
Separator plastic tapeEMV screening tin plated copper braid Ø: 7.3 mm
Separator plastic tape Sheath RADOX® elastomer S
Colour black Ø: 9.3 ± 0.3 mm
Technical dataConductor resistance at 20 °C <90.5 /kmVoltage rating 600 VTest voltage 1500 VTransfer impedance f 30 MHz 80 m /mTemperature range (cores) –50 up to +150 °CTemperature range (sheath) –40 up to +150 °C
Coaxial cable K 02253D–02:Impedance 75 Capacitance 63 pF/mVelocity of signal propagation 69 % of the speed of lightAttenuation at 20 °C (typ. value) f = 1 MHz 30 dB/100m f = 10 MHz 9.5 dB/100m f = 100 MHz 30 dB/100mTemperature range –40 up to +150 °C
customised solutions•physical and chemical •characteristics according to specificationspower and data transmission•installation of one cable only•small dimensions•low weight•multifunctional•
114 HUBER+SUHNER
RADOX® solar cables
RADOX® solar cable single core 116
RADOX® SMART 118
RADOX® SolarLink 120
RADOX® solar cable multi core 122
RADOX® solar cable multi core, screened 124
All our cables fully comply with the European directives 76/769/EWG, 2003/11/EG, 2000/53/EG, 2003/53/EG and 2002/95/EG (RoHS).
HUBER+SUHNER 115
RAD
OX®
sola
rcab
les
operating temperature range -40°C up to +120°C•
short circuit strength up to +280°C•
RADOX• ® electron-beam crosslinked materials do not meltor flow, even at high temperatures
high resistance against UV, ozone and hydrolysis•
very high mechanical robustness and resistance against•water, oil and chemicals
compact and flexible•
years of approved applications worldwide•
TÜV an UL approval•
RADOX• ® solar connectors, junction boxes and accessoriesfor photovoltaic installations(see catalogue item no. 84017606)
116 HUBER+SUHNER
RADOX® solar cable
Single core cable
ApplicationSpecifically designed for connecting photovoltaic system components inside and outside of buildings and equip-ment with high mechanical requirements and extreme weather conditions. For permanent installations.
Composition of cableConductor stranded tin plated copper, fine wired, acc. to IEC 60228, class 5Insulation RADOX® blackSheat RADOX®
Colours see table
Technical dataConductor resistance at 20 °C see tableTüV: Voltage rating line to ground Uo 600 V AC Voltage rating line to line U 1000 V AC maximum voltage line to ground 660 V AC maximum voltage line to line Um 1100 V AC maximum voltage line to ground Vo 1000 V DC maximum voltage line to line 1650 V DC test voltage AC 3.5 kV test voltage DC 8.4 kV lower ambient temperature –40°C upper ambient temperature +85°C max. conductor temperature +110°C
Min. bending radius D < 8 mm 4 x cable–Ø D 8 mm 6 x cable–Ø
nominal cross sections with TÜV •approvalspace saving outer diameter•long service life, extremly robust•electron beam, crosslinked insu-•lation and sheathhigh resistance against heat, •cold, oil, abrasion, ozone, UV and weatherimproved characteristics in case •of firehalogen free, flame retardant•flexible, easy to strip•
HUBER+SUHNER 117
RAD
OX®
sola
rcab
les
Cross section Conductor Cable Weight Colour Item no.
Construction nom. R20 IEC 60228 Ø nom. nom.
mm2 n x mm max. /km mm kg/100m
1.5 30 x 0.25 1.52 ± 0.05 4.3 ± 0.15 3.2 black 12558072
2.5* 48 x 0.25 2.01 ± 0.05 5.2 ± 0.15 4.6 red 12529712
2.5* 48 x 0.25 2.01 ± 0.05 5.2 ± 0.15 4.6 blue 12529713
2.5* 48 x 0.25 2.01 ± 0.05 5.2 ± 0.15 4.6 black 12529714
4.0* 56 x 0.30 2.54 ± 0.05 5.8 ± 0.15 6.6 red 12545801
4.0* 56 x 0.30 2.54 ± 0.05 5.8 ± 0.15 6.6 blue 12537896
4.0* 56 x 0.30 2.54 ± 0.05 5.8 ± 0.15 6.6 black 12545802
6.0* 81 x 0.30 3.30 ± 0.10 6.9 ± 0.20 9.2 red 12568182
6.0* 81 x 0.30 3.30 ± 0.10 6.9 ± 0.20 9.2 blue 12568183
6.0* 81 x 0.30 3.30 ± 0.10 6.9 ± 0.20 9.2 black 12552756
10 78 x 0.40 4.30 ± 0.10 8.1 ± 0.15 14.4 black 12537897
16 119 x 0.40 5.30 ± 0.10 9.5 ± 0.20 21.0 black 12567377
25 182 x 0.40 6.60 ± 0.10 11.1 ± 0.20 29.6 black 12567378
35 266 x 0.40 7.80 ± 0.10 12.8 ± 0.25 41.7 black 12567379
50 378 x 0.40 9.30 ± 0.10 15.0 ± 0.25 60.2 black 12567380
70 348 x 0.50 11.40 ± 0.10 17.5 ± 0.30 80.8 black 12567381
95 444 x 0.50 12.80 ± 0.10 19.3 ± 0.30 103.1 black 12567382
120 551 x 0.50 14.60 ± 0.10 21.8 ± 0.30 126.0 black 12567383
150 722 x 0.50 16.80 ± 0.10 24.4 ± 0.30 161.7 black 12567384
*Approvals: TÜV Rheinland design–tested, certificate R 02210086
Other cross sections and colours on request.
Extract from our delivery programme
Fire testsFlame propagation::Vertical of a single cable IEC 60332–1, EN 50265–2–1Content of halogen acid gas IEC 670754–1, EN 50267–2–1 0mg/gCorrosivity of combustion gases IEC 60754–2, EN 50267–2–3Smoke density IEC 61034–2, EN 50268–2
Approvals (2.5 – 6.0 mm2 )Wires for photovoltaic–systems RADOX® solar cable TÜV Rheinland 2 Pfg 1169 certificate R02210086
RADOX® solar cable
Single core cable
118 HUBER+SUHNER
Composition of cableConductor stranded tin plated copper, fine wired, acc. to IEC 60228, class 5Inner insulation RADOX® FIOuter insulation RADOX® FS
Colour black
Technical dataUL: voltage rating 600 V AC test voltage 3.0 kV AC temperature rating 90 °C wet or dry, sunlight resistant
TÜV: Voltage rating line to ground Uo 600 V AC Voltage rating line to line U 1000 V AC maximum voltage line to ground Vo 1000 V DC maximum voltage line to line 1650 V DC test voltage AC 3.5 kV AC test voltage DC 8.4 kV DC lower ambient temperature –40 °C upper ambient temperature +85 °C maximum conductor temperature +110 °CMinimum bending radius 4 x cable–Ø
ApplicationType PV: Suitable for interconnection wiring of grounded and ungrounded photovoltaic power systems as •descriebed in section 690.31 (A) and other parts of the National Electrical Code (NEC), NFPA 70. For single conductor, double--insulated wires installation without using a conduit is permitted according to section 690.35 (D) of the NEC.Type RHH oder RHW--2: Suitable for any of the wiring methods recognised in chapter 3 and as specified in •their respective tables or as permitted elsewhere in the NEC.
Europe:Suitable for the installation methods reference no. 2, 3A, 4A, 5A, 11, 11A, 12, 13, 14, 15, 16, 21, 22A, 23A, •24A, 25, 31A, 32A, 33A, 41, 43, 51, 72, 73, 75 in table 52H of HD 384.5.52 (CH: SEV 1000 section 5.2; DE: DIN VDE 0100--520).
for all climate zones•for reliable and durable con-•nectionswith UL and TÜV approvals•halogen free, flame retardant•lean, powerful and flexible•of proven RADOX• ® quality
RADOX® SMART
Single core cable
HUBER+SUHNER 119
RAD
OX®
sola
rcab
les
Fire testsflame propagation:Vertical FT1 UL 1581 # 1060 L 250 mm, T 60 sVertical EN 60332–1–2 IEC 60332–1–2 50 < L 540 mm Content of halogen acid gas EN 50267–2–1, IEC 60754–1 HCI + HBr 0.5% Corrosivity of combustion gases EN 50267–2–2, IEC 60754–2 pH 4.3, 10 S/mm
Extract from our delivery programme
UL Photovoltaic Wire Type PV, UL subject 4703, UL listed E305787
UL Thermoset–insulated Wires and Cables Type RHH kand RHW–2, UL 44, listed E310273
TÜV Rheinland Wires for photovoltaic–systems 2 Pfg 1169, certificate R60017683
Approvals
RADOX® SMART
Single core cable
Cross section Conductor Cable Weight Item no.
nom. Constr. nom. Ø nom. R20 IEC 60228 Ø nom.
AWG mm2 n x mm nom. mm max. /km mm kg/100 m
14 2.5 48 x 0.26 2.0 8.21 5.3 5± 0.10 5.1 12583222
12 4.0 56 x 0.30 2.5 5.09 6.05 ± 0.10 7.1 12583780
10 6.0 82 x 0.30 3.2 3.39 7.15 ± 0.15 9.9 12583781
Other cross sections and colours on request.
120 HUBER+SUHNER
RADOX® SolarLink
Single core cable
Composition of cableConductor stranded tin plated copper, fine wired, acc. to IEC 60228, class 5Inner insulation RADOX® 155Outer insulation RADOX® 155
Colour black
Technical dataUL: voltage rating 600 V AC test voltage AC 3.0 kV AC temperature rating 90 °C wet or dry, sunlight resistant
TÜV: Voltage rating line to ground Uo 600 V AC Voltage rating line to line U 1000 V AC maximum voltage line to ground Vo 1000 V DC maximum voltage line to line 1650 V DC test voltage AC 3.5 kV AC test voltage DC 8.4 kV DC lower ambient temperature -40 °C upper ambient temperature +85 °C maximum conductor temperature +110 °CMin. bending radius 4 x cable–Ø
ApplicationUnited States:
Type PV: suitable for interconnection wiring of grounded and ungrounded photovoltaic power systems as •described in section 690.31 (A) and other parts of the National Electrical Code (NEC), NFPA 70.For single conductor, double insulated wires installation without using a conduit is permitted according to sec-tion 690.35 (D) of the NEC.Type RHH or RHW-2: suitable for use in any of the wiring methods recognized in chapter 3 and as specified •in their respective tables or as permitted elsewhere in the NEC.
Europe:suitable for the installation mehods reference no. 2, 3A, 4A, 5A, 11, 11A, 12, 13, 14, 15, 16, 21, 22A, 23A, •24A, 25, 31A, 32A, 33A, 41, 43, 51, 72, 73, 75 given in table 52H of HD 384.5.52 (CH: SEV 1000 cl. 5.2; DE: DIN VDE 0100-520).
UL and TÜV approval•double insulated construction •allows for installation without a conduitsmaller outer diameter•of proven • RADOX® qualityvery flexible•
HUBER+SUHNER 121
RAD
OX®
sola
rcab
les
Cross section Conductor Cable Weight Item no..
nom. Constr. nom. Ø max. R20 IEC 60228 Ø nom.
AWG mm2 n x mm nom. mm max. /km mm kg/100 m
14 2.5 48 x 0.26 2.0 8.21 5.35 ± 0.10 5.1 12582664
12 4.0 56 x 0.30 2.5 5.09 6.05 ± 0.10 7.1 12582665
10 6.0 82 x 0.30 3.2 3.39 7.15 ± 0.15 9.9 12583784
Other cross sections and colours on request.
Extract from our delivery programme
UL Photovoltaic Wire Type PV, UL subject 4703, UL listed E305787
UL Thermoset–insulated Wires and Cables Type RHH kand RHW–2, UL 44, listed E310273
TÜV Rheinland Wires for photovoltaic–systems 2 Pfg 1169, certificate R60017683
Approvals
RADOX® SolarLink
Single core cable
Fire testsFlame propagation:Vertical FT1 UL 1581 # 1060 L 250 mm, T 60 sVertical EN 60332–1–2, IEC 60332–1–2 50 < L 540 mm
122 HUBER+SUHNER
ApplicationConnecting photovoltaic system components inside and outside of buildings and equipment with high mechanical requirements and extreme weather influences. For permanent installations.
Composition of cableConductor stranded tin plated copper, fine wired, acc. to IEC 60228, class 5Insulation RADOX® 125
Colour 2 – 5 cores acc. to CENELEC, HD 308 S2 (see page 155) as of 6 cores black-numbered with earth conductor yellow-green (other colours on request)
Sheat RADOX® 125 Colour black
Technical dataVoltage rating 1000V DC or 600 / 1000V ACTest voltage 3500 V ACTemperature range fixed –40 up to +125 °CMin. operating temperature flexing –25 °CMax. conductor temperature (short circuit at max. 5s) + 280 °CMin. bending radius fixed 3 x cable–Ø flexing 5 x cable–Ø
RADOX® solar cable
Multi core cable
high resistance against heat, •ozone and weatherproofextremely mechanically robust, •very long lifetimehalogen free•space saving, easy to install•flame retardant•no corrosive gases and low •smoke occurrence in case of firesoldering resistant•flexible, easy to strip•
HUBER+SUHNER 123
®so
larc
able
s
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cable EN 50266–2–4, IEC 60332–3–24 Category CContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0 mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2
Cross section Conductor Core Cable Weight
mm2 Construction nom.n x mm
Ø nom.mm
Ø nom.mm
Ø nom.mm
nom.kg/100 m
2 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 9.1 ± 0.3 13.0
3 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 10.1 ± 0.4 16.6
4 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 11.4 ± 0.4 20.9
5 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 12.4 ± 0.4 24.9
7 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 15.3 ± 0.5 37.9
2 x 4.0 56 x 0.30 2.60 4.15 ± 0.15 11.0 ± 0.4 18.7
4 x 4.0 56 x 0.30 2.60 4.15 ± 0.15 13.0 ± 0.4 29.8
5 x 4.0 56 x 0.30 2.60 4.15 ± 0.15 14.6 ± 0.4 36.7
4 x 6.0 81 x 0.30 3.40 4.95 ± 0.15 15.6 ± 0.5 41.8
2 x 10.0 78 x 0.40 4.40 6.15 ± 0.15 15.8 ± 0.5 50.4
3 x 10.0 78 x 0.40 4.40 6.15 ± 0.15 17.0 ± 0.5 62.0
4 x 10.0 78 x 0.40 4.40 6.15 ± 0.15 18.9 ± 0.5 77.5
5 x 10.0 78 x 0.40 4.40 6.15 ± 0.15 21.4 ± 0.5 98.3
Other cross sections and colours on request.
Extract from our delivery programme
RADOX® solar cable
Multi core cable
124 HUBER+SUHNER
ApplicationFor connecting photovoltaic system components inside and outside of buildings and equipment with high mechani-cal requirements and extreme weather conditions. For permanent installations.
Composition of cableConductor stranded tin plated copper, fine wired, acc. to IEC 60228, class 5Insulation RADOX® 125
Colour 2 – 5 cores acc. to CENELEC, HD 308 S2 (see page 155) as of 6 cores black-numbered with earth conductor yellow-green (other colours on request)
Screening tin plated copper braidSheat RADOX® 125
Colour black
Technical dataVoltage rating 1000V DC or 600 / 1000V ACTest voltage 3500V ACTemperature range fixed –40 up to +125 °CMin. operating temperature flexing –25 °CMax. conductor temperature (short circuit at max. 5s) +280 °CMin. bending radius fixed 3 x cable–Ø flexing 5 x cable–Ø
RADOX® solar cable
Multi core cable – screened
high resistance against heat, •ozone and weatherproofextremely mechanically robust, •very long lifetimehalogen free•space saving, easy to install•
HUBER+SUHNER 125
®so
larc
able
s
Cross section Conductor Core Screening Cable Weight
mm2Construction nom.
n x mmØ nom.
mmØ nom.
mmØ nom.
mmØ nom.
mmnom.
kg/100 m
2 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 7.7 10.2 ± 0.4 17.5
3 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 8.3 10.8 ± 0.4 20.6
4 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 9.8 12.0 ± 0.4 26.8
5 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 10.4 13.1 ± 0.4 30.9
7 x 2.5 48 x 0.25 2.05 3.50 ± 0.10 13.2 16.3 ± 0.5 45.9
2 x 4.0 56 x 0.30 2.60 4.15 ± 0.15 9.2 11.9 ± 0.4 24.4
4 x 4.0 56 x 0.30 2.60 4.15 ± 0.15 11.2 14.1 ± 0.4 37.1
3 x 6.0 81 x 0.30 3.40 4.95 ± 0.15 11.6 14.5 ± 0.4 38.8
4 x 6.0 81 x 0.30 3.40 4.95 ± 0.15 13.3 16.5 ± 0.5 51.7
Other cross sections and colours on request.
Extract from our delivery programme
Fire testsFlame propagation:Vertical of a single cable EN 50265–2–1, IEC 60332–1Vertical of bunched cables EN 50266–2–4, IEC 60332–3–24 Category CContent of halogen acid gas EN 50267–2–1, IEC 60754–1 0mg/gCorrosivity of combustion gases EN 50267–2–2, IEC 60754–2Smoke density EN 50268–2, IEC 61034–2
RADOX® solar cable
Multi core cable – screened
126 HUBER+SUHNER
RADOX® FR
Safety cables with circuit integrity in case of fire
PURGI, single core cable 128
PURGI, multi core cable 130
PURGI, multi core cable, screened 132
RADOX® FR AUS, single core 134
RADOX® FR AUS, single core cable 136
RADOX® FR AUSmulti core cable, 0.75 – 2.5 mm 138
RADOX® FR AUSmulti core cable, 4.0 – 35 mm 140
RADOX® FR INTERNATIONALcores, single and multi core cable 142
RADOX® FR INTERNATIONAL ALUcommunication cable 146
All our cables fully comply with the European directives 76/769/EWG, 2003/11/EG, 2000/53/EG, 2003/53/EG and 2002/95/EG (RoHS).
HUBER+SUHNER 127
RAD
OX®
FR s
afet
y ca
bles
circuit integrity in case of fire•
highly flame retardant•
low smoke emissions•
low toxicity of fire gases•
electro magnetic compatibility•
128 HUBER+SUHNER
PURGI
Single core cable
ApplicationInstallation on construction sites, machine industry, agriculture and horticulture, chemical industry and workshops as well as for connecting electric equipment in humid and wet environment.
Composition of cable Core stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125 C
extruded and electron beam crosslinked pololefin Colour black
Sheath TPU Colour yellow RAL 1028
Technical dataVoltage rating 450 / 750 V ACTest rating 2500 V ACTemperature range –40 °C up to +90 °CMin. bending radius 6 x cable–Ø
resistant to oils, alkaline •solutions, acids, grease and fuellong service life time•halogen free•microbe and weatherproof•high chemical and mechanical •robustnesshigh abrasion resistance•
HUBER+SUHNER 129
RAD
OX®
FR s
afet
y ca
bles
Cross section No. of wires Conductor Cable Weight Item no.
nom Ø max. Ø nom. R20 IEC 60228 Ø nom.
mm2 mm mm max. /km mm kg / 100 m
16 119 x 0.41 5.30 ± 0.10 1.22 9.4 ± 0.15 19.1 12560556
25 182 x 0.41 6.70 ± 0.10 0.779 11.2 ± 0.20 28.4 12560557
35 259 x 0.41 7.80 ± 0.10 0.554 12.7 ± 0.20 38.9 12560558
50 378 x 0.41 9.30 ± 0.10 0.385 14.85 ± 0.25 50.9 12560559
95 444 x 0.51 12.80 ± 0.10 0.210 19.0 ± 0.30 95.8 12560560
150 722 x 0.51 16.80 ± 0.20 0.132 24.2 ± 0.30 154.2 12560561
185 874 x 0.51 18.30 ± 0.20 0.108 26.1 ± 0.30 184.7 12560562
240 1147 x 0.51 21.10 ± 0.20 0.0817 29.7 ± 0.30 240.8 12560563
300 1443 x 0.51 23.70 ± 0.20 0.0654 32.9 ± 0.30 298.6 12560564
Other cross sections on request.
Extract from our delivery programme
PURGI
Single core cable
130 HUBER+SUHNER
PURGI
Multi core cable
ApplicationInstallation on construction sites, machine industry, agriculture and horticulture, chemical industry and workshops as well as for connecting electric equipment in humid and wet environment.
Composition of cable Core stranded tin plated copper, acc. to IEC 60228, class 5
Insulation RADOX® 125 C extruded and electron beam crosslinked pololefin Core colours acc. to table HD 308 on page 159
Fillers (optional) RADOX®
Sheath TPU Colour yellow RAL 1028
Technical dataVoltage rating 450 / 750 VTest voltage 2500 VTemperature range –40 °C up to +90 °CMin. bending radius 6 x cable–Ø
resistant to oils, alkaline •solutions, acids, grease and fuellong service life time•halogen free•microbe and weatherinproof•high chemical and mechanical •robustnesshigh abrasion resistance•
HUBER+SUHNER 131
RAD
OX®
FR s
afet
y ca
bles
Cross section Conductor Core Cable Weight Core colours* Item no.
Constr. nom. Ø nom. R20 IEC 60228 Ø nom. Ø nom. nom.
n x mm2 n x mm mm max. /km mm mm kg/100 m
3 x 0.75 24 x 0.20 1.10 26.7 2.40 7.3 ± 0.3 6.5 GNYE,BU,BN 12509248
2 x 1 32 x 0.20 1.30 20.0 2.60 7.3 ± 0.3 6.3 BU,BN 12509249
3 x 1 32 x 0.20 1.30 20.0 2.60 7.7 ± 0.3 7.6 GNYE,BU,BN 12509250
4 x 1 32 x 0.20 1.30 20.0 2.60 8.6 ± 0.3 9.7 GNYE,BN,BK,GY 12509251
5 x 1 32 x 0.20 1.30 20.0 2.60 9.4 ± 0.3 11.7GNYE,BU,BN,
BK,GY12516532
2 x 1.5 30 x 0.25 1.56 13.7 3.25 8.8 ± 0.3 9.1 BU,BN 12509252
3 x 1.5 30 x 0.25 1.56 13.7 3.25 9.3 ± 0.3 11.0 GNYE,BU,BN 12509253
4 x 1.5 30 x 0.25 1.56 13.7 3.25 10.6 ± 0.4 14.3 GNYE,BN,BK,GY 12509254
5 x 1.5 30 x 0.25 1.56 13.7 3.25 11.9 ± 0.4 18.0GNYE,BU,BN,
BK,GY12509255
7 x 1.5 30 x 0.25 1.56 13.7 3.25 13.8 ± 0.4 23.8GNYE,BU,
5 x BK12510854
10 x 1.5 30 x 0.25 1.56 13.7 3.25 16.5 ± 0.5 31.1 GNYE,BU,8 x BK 12510855
3 x 2.5 50 x 0.25 2.01 8.21 3.90 11.0 ± 0.4 16.0 GNYE,BU,BN 12509256
4 x 2.5 50 x 0.25 2.01 8.21 3.90 12.4 ± 0.4 21.0 GNYE,BN,BK,GY 12509257
5 x 2.5 50 x 0.25 2.01 8.21 3.90 13.8 ± 0.4 25.3GNYE,BU,BN,
BK,GY12509258
7 x 2.5 50 x 0.25 2.01 8.21 3.90 17.1 ± 0.5 37.8 GNYE,BU,5 x BK 12510859
4 x 4 53 x 0.30 2.54 5.09 4.70 15.0 ± 0.4 29.3 GNYE,BN,BK,GY 12510860
5 x 4 53 x 0.30 2.54 5.09 4.70 16.6 ± 0.5 36.3GNYE,BU,BN,
BK,GY12510861
4 x 6 81 x 0.30 3.30 3.39 5.50 17.7 ± 0.5 41.2 GNYE,BN,BK,GY 12510862
5 x 6 81 x 0.30 3.30 3.39 5.50 19.6 ± 0.5 50.1GNYE,BU,BN,
BK,GY12510863
4 x 10 78 x 0.40 4.30 1.95 6.15 18.9 ± 0.5 57.8 GNYE,BN,BK,GY 12513763
5 x 10 78 x 0.40 4.30 1.95 6.15 21.3 ± 0.5 73.2GNYE,BU,BN,
BK,GY12510864
5 x 16 119 x 0.40 5.30 1.24 7.35 25.5 ± 0.6 107GNYE,BU,BN,
BK,GY12509794
5 x 25 182 x 0.40 6.60 0.795 9.00 29.6 ± 0.6 156GNYE,BU,BN,
BK,GY12516534
Extract from our delivery programme
* Description for core colours see page 154
Other cross sections on request.
PURGI
Multi core cable
132 HUBER+SUHNER
PURGI
Multi core cable – screened
ApplicationInstallation on construction sites, machine industry, agriculture and horticulture, chemical industry and workshops as well as for connecting electric equipment in humid and wet environment.
Composition of cableCores R 125 C
Conductor stranded tin plated copper, acc. to IEC 60228, class 5 Insulation RADOX® 125 C extruded and electron beam crosslinked pololefin Core colours blue, brown, green/yellow
Screening tin plated copper braid, optical coverage: 85 %Separator plastic tapeSheath TPU
Colour yellow RAL 1028
Technical dataVoltage rating 450 / 750 VTest voltage 2500 VTemperature range –40 °C up to +90 °CMin. bending radius 6 x cable–Ø
resistant to oils, alkaline •solutions, acids, grease and fuellong service life time•halogen free•microbe and weatherproof•high chemical and mechanical •robustnesshigh abrasion resistance•
HUBER+SUHNER 133
RAD
OX®
FR s
afet
y ca
bles
Cross section Conductor Core Cable Weight Item Nr.
Construction nom.
Ø nom. R20 IEC 60228 Ø nom. Ø nom. nom.
n x mm2 n x mm mm max. /km mm mm kg / 100 m
3 x 1.5 30 x 0.25 1.56 13.0 3.25 ± 0.10 10.1 ± 0.30 14.5 12560567
3 x 2.5 50 x 0.25 2.01 7.80 3.90 ± 0.10 11.8 ± 0.40 20.2 12560569
5 x 1.5 30 x 0.25 1.56 13.0 3.25 ± 0.10 12.9 ± 0.40 22.8 12560568
5 x 2.5 50 x 0.25 2.01 7.80 3.90 ± 0.10 14.8 ± 0.40 31.5 12560570
Other cross sections on request..
Extract from our delivery programme
PURGI
Multi core cable – screened
134 HUBER+SUHNER
RADOX® FR AUS
Single core cable with circuit integrity in case of fire
ApplicationFor emergency support systems: emergency lighting, smoke spill fans, fire alarms and sprinklers, emergency evacuation intercommunication systems, etc.
Composition of cableCore stranded copper bare acc. to IEC 60228, class 2Flame barrierInsulation RADOX® 125
Technical dataVoltage rating 600 / 1000 VTest voltage 3500 V ACMax. conductor temperature +110 °CMax. conductor temperature (short circuit max. 5s) +280 °C Min. operating temperature flexing –25 °CMin. conductor temperature fixed –40 °CMin. bending radius fixed 6 x cable–Ø flexing 10 x cable–Ø
Fire testsContent of halogen acid gas IEC 60754–1, EN 50267–2–1 0 mg/gCorrosivity of combustion gases IEC 60754–2, EN 50267–2–3Smoke density IEC 61034–2, EN 50268–2Circuit integrity 180 Min. IEC 60331–21Circuit integrity AS/NZS 3013, WS5
halogen free•flame retardant•in case of fire no corrosive •gases and low smokecircuit integrity in case of fire•excellent high and low tempera-•ture, and ozone resistanceweatherproof•easy to strip•
HUBER+SUHNER 135
RAD
OX®
FR s
afet
y ca
bles
Crosssection Conductor Core Item no.
Construction nom.
Ø nom. R20 IEC 60228 Ø nom. Colour Weight nom. Fire load
mm2 n x mm mm max. /km mm kg/100 m kj/m
1.5 7 x 0.54 1.62 11.50 3.50 black 2.5 180 12538125
2.5 7 x 0.69 2.07 7.56 4.10 black 3.7 266 12542736
Other cross sections on request.
Extract from our delivery programme
RADOX® FR AUS
Single core cable with circuit integrity in case of fire
136 HUBER+SUHNER
RADOX® FR AUS
Single core cable with circuit integrity in case of fire
ApplicationFor emergency support systems: emergency lighting, smoke spill fans, fire alarms and sprinklers, emergency evacuation intercommunication systems, etc.
Composition of cableCore stranded copper bare acc. to IEC 60228, class 5Flame barrierInsulation RADOX® 125 (for colours see table)Sheath RADOX® 125 (for colours see table)
Technical dataVoltage rating 600 / 1000 VTest voltage 3500 V ACMax. conductor temperature +110 °CMax. conductor temperature (short circuit max. 5s) +280 °C Min. operating temperature flexing –25 °CMin. conductor temperature fixed –40 °CMin. bending radius fixed 6 x cable–Ø flexing 10 x cable–Ø
Fire testsFlame propagation:Vertical of a single cable IEC 60332–1, EN 50265–2–1Vertical of bunched cables IEC 60332–3–24, EN 50266–2–4 category CContent of halogen acid gas IEC 60754–1, EN 50267–2–1 0 mg/gCorrosivity of combustion gases IEC 60754–2, EN 50267–2–3Smoke density IEC 61034–2, EN 50268–2Circuit integrity 180 Min. IEC 60331–21Circuit integrity AS/NZS 3013, WS5
halogen free•flame retardant•in case of fire no corrosive •gases and low smokecircuit integrity in case of fire•excellent high and low tempera-•ture, and ozone resistanceweatherproof•easy to strip•
HUBER+SUHNER 137
RAD
OX®
FR s
afet
y ca
bles
Crosssection Conductor Core Cable Item no.
Construction ØR20 IEC 60228
Ø Colour Ø nom. Colour Weight nom. Fire load
mm2 n x mm Ø mm max. /km mm mm kg/100 m kJ/m
1 x 1.5 7 x 0.54 1.62 11.5 3.5black
white5.05
orange
orange4.0
12536417
12536419
1 x 2.5 7 x 0.69 2.07 7.56 4.1black
white5.80
orange
orange5.6 467
12536421
12536422
1 x 4.0 7 x 0.88 2.64 4.70 4.8black
white6.50
orange
orange7.8 571
12536424
12536425
1 x 6.0 7 x 1.07 3.21 3.11 5.4black
white7.30
orange
orange10.5 693
12537402
12537403
1 x 10 7 x 1.36 4.08 1.83 6.9black
white9.90
orange
orange18.5 1381
12537405
12537408
1 x 16.0 7 x 1.70 4.85 1.15 7.7black
white10.70
orange
orange24.8 1529
12537410
12537413
1 x 25 7 x 2.15 6.10 0.734 9.4black
white12.50
orange
orange36.4 2049
12537415
12537418
1 x 35 7 x 2.53 7.20 0.524 10.5black
white13.6
orange
orange46.8 2252
12537420
12537423
* Description for core colours see page 154
Other cross sections on request.
Extract from our delivery programme
RADOX® FR AUS
Single core cable with circuit integrity in case of fire
138 HUBER+SUHNER
RADOX® FR AUS – 0.75 bis 2.5 mm2
Multi core cable with circuit integrity in case of fire – LSFH
ApplicationFor emergency support systems: emergency lighting, smoke spill fans, fire alarms and sprinklers, emergency evacuation intercommunication systems, etc.
Composition of cable Cores
Conductor stranded tin plated copper acc, to IEC 60228, class 5 Flame barrier Insulation RADOX® 125 Colours see table
Fillers (optional) RADOX®
Cores Conductor stranded tin plated copper acc, to IEC 60228, class 5 Insulation RADOX® 125 Colour yellow-green
Sheath LSFH Colour see table
Technical dataVoltage rating 0.75 and 1.0 300 / 500 V 1.5 and 2.5 600 / 1000 VTest voltage 3500 VTemperature range fixed –40 °C up to +90 °CMin. bending radius 10 x cable–Ø
Fire testsFlame propagation::Vertical of a single cable IEC 60332–1, EN 50265–2–1Vertical of bunched cables IEC 60332–3–24, EN 50266–2–4 category CContent of halogen acid gas IEC 60754–1, EN 50267–2–1 0 mg/gCorrosivity of combustion gases IEC 60754–2, EN 50267–2–3Smoke density IEC 61034–2, EN 50268–2Circuit integrity 180 Min. IEC 60331–21Circuit integrity AS/NZS 3013, WS5
halogen free•flame retardant•in case of fire no corrosive •gases and low smokecircuit integrity in case of fire•excellent high and low tempera-•ture, and ozone resistanceweatherproof•easy to strip•
HUBER+SUHNER 139
®FR
saf
ety
cabl
es
Crosssection Conductor Core colours* Cable Item no.
Construction nom.
ØR20 IEC 60228
Ø Colour ØWeightnom.
Fire load Colour
mm2 n x mm mm max. /km mm mm kg/100 m kJ / m
2x0.75 7 x 0.37 1.11 24.8 2.5 WH,RD 7.8 8.1 955 RD 12536429
3x0.75 7 x 0.37 1.11 24.8 2.5 WH,RD,BU 8.4 9.6 1055 RD 12536460
4x0.75 7 x 0.37 1.11 24.8 2.5 WH,RD,BK,BU 9.3 11.8 1250 RD 12537006
10x0.75 7 x 0.37 1.11 24.8 2.5 WH numb. 14.5 25.5 2474 RD 12537192
20x0.75 7 x 0.37 1.11 24.8 2.5 WH numb. 19.2 46.6 4274 RD 12548139
2x1.0 7 x 0.43 1.29 18.2 3.1 WH,RD 8.5 9.8 1131 RD 12536434
3x1.0 7 x 0.43 1.29 18.2 3.1 WH,RD,BU 9.1 11.7 1248 RD 12536467
4x1.0 7 x 0.43 1.29 18.2 3.1 WH,RD,BK,BU 10.3 14.8 1519 RD 12537012
2x1.5 7 x 0.53 1.59 12.2 3.4 WH,RD 9.2 12.1 1305 RD 12536444
3x1.5
3G1.57 x 0.53 1.59 12.2 3.4
WH,RD,BU
RD,BK,GNYE9.9 14.5 1446
RD
RD
12536474
12536472
4x1.5
4G1.5 7 x 0.53 1.59 12.2 3.4
WH,RD,BK,BU
WH,RD,BK,GNYE10.9 18.2 1724
RD
RD
12537021
12537024
5G1.5 7 x 0.53 1.59 12.2 3.4 WH,RD,BK,BU,GNYE 12.1 22.8 2125 RD 12537054
7x1.5
7G1.57 x 0.53 1.59 12.2
3.4
3.4
WH numb.
BK numb, GNYE13.1 27.4 2363
RD
RD
12537092
12548140
10x1.5 7 x 0.53 1.59 12.2 3.4 WH numb. 17.4 40.4 3464 RD 12537212
12G1.5 7 x 0.53 1.59 12.2 3.4 WH numb.,GNYE 17.9 44.9 3756 RD 12537232
16x1.5 7 x 0.53 1.59 12.2 3.4 WH numb. 20.3 59.2 4824 RD 12537259
21G1.5 7 x 0.53 1.59 12.2 3.4 WH numb,GNYE 22.6 73.9 5875 RD 12537284
41G1.5 7 x 0.53 1.59 12.2 3.4 WH numb.,GNYE 32.3 144.5 11150 RD 12539462
56G1.5 7 x 0.53 1.59 12.2 3.4 BK numb.,BU,GNYE 36.3 OG 12537326
2x2.5 7 x 0.67 2.01 7.56 3.9 WH,RD 10.6 16.7 1715 RD 12536454
3x2.5
3G2.57 x 0.67 2.01 7.56 3.9
WH,RD,BU
RD,BK,GNYE11.3 20.1 1858
RD
RD
12536486
12536487
4x2.5
4G2.57 x 0.67 2.01 7.56
3.9 WH,RD,BK,BU
WH, RD,BU,GNYE12.6 25.3 1341
RD
RD
12537039
12547477
5G2.5 7 x 0.67 2.01 7.56 3.9 WH,RD,BK,BU,GNYE 14.0 31.7 2525 RD 12537059
7G2.5 7 x 0.67 2.01 7.56 3.9 WH numb.GNYE 15.4 39.6 3231 RD 12537099
11G2.5 7 x 0.67 2.01 7.56 3.9 WH numb.GNYE 20.8 60.5 4828 RD 12537225
12G2.5 7 x 0.67 2.01 7.56 3.9 WH numb.GNYE 20.8 64.6 5188 RD 12567690
21G2.5 7 x 0.67 2.01 7.56 3.9 WH numb.GNYE 26.3 106 7759 RD 12537289
50x2.5 7 x 0.67 2.01 7.56 3.9 WH numb. 40.8 244 17928 RD 12568873
Extract from our delivery programme
* Description for core colours see page 154
Other cross sections on request.
RADOX® FR AUS – 0.75 bis 2.5 mm2
Multi core cable with circuit integrity in case of fire – LSFH
140 HUBER+SUHNER
RADOX® FR AUS – 4.0 – 35 mm2
Multi core cable with circuit integrity in case of fire – RADOX® 125
ApplicationFor emergency support systems: emergency lighting, smoke spill fans, fire alarms and sprinklers, emergency evacuation intercommunication systems, etc.
AufbauCores
Conductor stranded tin plated copper, 4 and 6 mm2
stranded copper bare, 10 up to 120 mm2
Flame barrier Insulation RADOX® 125, colours see table
Fillers (optional) RADOX®
Cores Conductor stranded tin plated copper, 4 and 6 mm2
stranded copper bare, 10 up to 120 mm2
Insulation RADOX® 125 Colours yellow–green
Sheath RADOX® 125 Colour see table
Technical dataVoltage rating 600 / 1000 VTest voltage 3500 V ACMax. conductor temperature +110 °CMax. conductor temperature (short circuit max. 5s) +280 °C Min. operating temperature flexing –25 °CMin. conductor temperature fixed –40 °CMin. bending radius fixed 6 x cable–Ø flexing 10 x cable–Ø
Fire testsFlame propagation::Vertical of a single cable IEC 60332–1, EN 50265–2–1Vertical of bunched cables IEC 60332–3–24, EN 50266–2–4 category CContent of halogen acid gas IEC 60754–1, EN 50267–2–1 0 mg/gCorrosivity of combustion gases IEC 60754–2, EN 50267–2–3Smoke density IEC 61034–2, EN 50268–2Circuit integrity 180 Min. IEC 60331–21Circuit integrity AS/NZS 3013, WS5
halogen free•flame retardant•in case of fire no corrosive •gases and low smokecircuit integrity in case of fire•excellent high and low tempera-•ture, and ozone resistanceweatherproof•easy to strip•
HUBER+SUHNER 141
®FR
saf
ety
cabl
es
Crosssection Conductor Core Cable Item no.
Construction nom.
ØR20 IEC 60228
Ø Colour* ØWeight nom.
Fire load Colour
mm2 n x mm. mm max. /km mm mm kg/100 m kJ / m
2x4
2x47 x 0.86 2.58 4.70 4.4
BK,RD
WH,RD12.1 23.0 2313
OG
RD
12536456
12536459
3x4
3G47 x 0.86 2.58 4.70 4.4
WH,RD,BU
RD,BK,GNYE12.9 28.1 2468
RD
red
12536494
12536496
4x4
4G47 x 0.86 2.58 4.70 4.4
WH,RD,BK,BU
WH,RD,BU,GNYE14.6 36.4 3047
RD
RD
12537048
12537047
5G4 WH,RD,BK,BU,GNYE 16.2 44.9 RD 12537062
2x6 7 x 1.07 3.21 3.11 5.0 WH,RD 13.6 30.5 2892 RD 12537478
3G6 7 x 1.07 3.21 3.11 5.0 RD,BK,GNYE 14.5 37.0 2996 RD 12537996
4G6 7 x 1.07 3.21 3.11 5.0 WH,RD,BU,GNYE 16.4 48.8 1430 RD 12537708
5G6 7 x 1.07 3.21 3.11 5.0 WH,RD,BK,BU,GNYE 18.1 59.8 3778 RD 12537654
2x10 7 x 1.36 4.08 1.83 6.6 BK,RD 17.9 53.8 4378 OG 12537481
3x10
3G107 x 1.36 4.08 1.83 6.6
WH,RD,
BURD,BK,GNYE19.0 63.6
OG
OG
12537490
12537491
4x10
4G107 x 1.36 4.08 1.83 6.6
WH,RD,BK,BU
WH,RD,BU, GNYE21.1 78.3 6144
OG
OG
12537709
12537713
5G10 7 x 1.36 4.08 1.83 6.6 WH,RD,BK,BU,GNYE 22.9 96.1 7132 OG 12537756
3x16 7 x 1.36 4.08 1.83 6.6 WH,RD,BU 20.7 84.5 OG 12537492
4x16 7 x 1.36 4.08 1.83 6.6 WH,RD,BK,BU 23.1 108.3 OG 12537714
4G16 7 x 1.70 4.85 1.15 7.5 WH,RD,BU,GNYE 23.1 75.1 OG 12537718
5G16 7 x 1.70 4.85 1.15 7.5 WH,RD,BK,BU,GNYE 25.2 127.4 7683 OG 12537758
3x25 7 x 2.15 6.10 0.734 9.2 WH,RD,BU 24.4 126.3 OG 12537493
4x25
4G257 x 2.15 6.10 0.734 9.2
WH,RD,BK,BU
WH,RD,BU,GNYE27.0 157.4 1054
OG
OG
12537726
12537730
5G25 7 x 2.15 6.10 0.734 WH,RD,BK,BU,GNYE 30.3 197.5 1176 1 OG 12537759
3x35 7 x 2.53 7.2 0.524 10.3 WH,RD,BU 26.9 160.6 OG 12537494
4x35
4G357 x 2.53 7.2 0.524 10.3
WH,RD,BK,BU
WH,RD,BU,GNYE29.7 203.6 1130 4
OG
OG
12537731
12537735
5G35 7 x 2.53 7.2 0.524 10.3 WH,RD,BK,BU,GNYE 33.6 257.6 1391 2 OG 12537838
Extract from our delivery programme
* Description for core colours see page 154
Other cross sections on request.
RADOX® FR AUS – 4.0 – 35 mm2
Multi core cable with circuit integrity in case of fire – RADOX® 125
142 HUBER+SUHNER
A
B
C
RADOX® FR INTERNATIONAL
Single core, single core or multi core cable with circuit integrity in case of fire
ApplicationFor emergency support systems: emergency lighting, smoke spill fans, fire alarms and sprinklers, emergency evacuation intercommunication systems, etc.
Composition of cableFiller (optional) RADOX®
Cores <1.5 mm2 conductor: stranded tin plated copper OF copper, class 22.5 and 4.0 mm2 conductor: stranded copper bare OF copper, class 2>4.0 mm2 conductor: copper bare ETP copper class 2
Flame barrierInsulation RADOX® 125 crosslinked
Colour HD 308 S2 (see page 155)Sheath RADOX® 125 crosslinked
Colour orange
Technical dataVoltage rating Uo/U 1.0 mm2 470 / 750 VTest voltage 1.0 mm2 2500 V ACVoltage rating Uo/U 1.5 mm2 600 / 1000 VTest voltage 1.5 mm2 3500 V ACMax. conductor temperature +110 °CMax. conductor temperature (short circuit max. 5s) +280 °C Min. operating temperature flexing –25 °CMin. conductor temperature fixed –40 °CMin. bending radius 10 x cable–Ø
halogen free•flame retardant•in case of fire no corrosive •gases and low smokecircuit integrity in case of fire•excellent high and low tempera-•ture, and ozone resistanceweatherproof•easy to strip•
HUBER+SUHNER 143
A
RAD
OX®
FR s
afet
y ca
bles
Extract from our delivery programme
Core (drawing A)
Crosssection
Conductor Core Cable Item no.
nom. Constr. nom. Ø nom. R20 IEC60228 Ø nom. Colour* Ø nom. Weight nom.
mm2 n x mm mm max. /km mm mm kg/100m
0.75 7 x 0.38 1.18 23.8 2.6 BK –– 1.32 12582541
1.0 7 x 0.45 1.37 17.5 2.9 BK –– 1.70 12581260
1.0 7 x 0.45 1.37 17.5 2.9 WH –– 1.70 12581261
1.5 7 x 0.54 1.66 11.7 3.5 BK –– 2.49 12581262
1.5 7 x 0.54 1.66 11.7 3.5 BU –– 2.49 12581263
1.5 7 x 0.54 1.66 11.7 3.5 RD –– 2.49 12581264
2.5 7 x 0.69 2.12 7.11 3.95 BK –– 3.61 12581265
2.5 7 x 0.69 2.12 7.11 3.95 RD –– 3.61 12581266
4.0 7 x 0.88 2.67 4.43 4.55 BK –– 5.31 12581835
6.0 7 x 1.07 3.24 2.96 5.1 BK –– 7.31 12581836
10 7 x 1.36 4.13 1.79 6.0 BK –– 10.9 12581837
16 7 x 1.70 4.90 1.13 6.8 BK –– 16.9 12581838
25 7 x 2.15 6.15 0.712 8.5 BK –– 26.6 12581668
35 7 x 2.53 7.25 0.514 9.6 BK –– 36.0 12581669
Fire testsFlame propagation::Vertical of a single cable IEC 60332–1, EN 50265–2–1Vertical of bunched cables IEC 60332–3–24, EN 50266–2–4 category CContent of halogen acid gas IEC 60754–1, EN 50267–2–1 0 mg/gCorrosivity of combustion gases IEC 60754–2, EN 50267–2–3Smoke density IEC 61034–2, EN 50268–2Circuit integrity 180 Min. IEC 60331–21Circuit integrity AS/NZS 3013, WS5
* Description for core colours see page 154
Other cross sections on request.
RADOX® FR INTERNATIONAL
Single core, single core or multi core cable with circuit integrity in case of fire
144 HUBER+SUHNER
BSingle core cable (drawing B)
Crosssection Conductor Cores Cable Item no.
nom.Construction
nom.Ø nom. R20 IEC60228 Ø nom. Colour* Ø nom. Weight nom.
mm2 n x mm mm max. /km mm mm kg/100 m
1 x 1.5 7 x 0.54 1.66 11.7 3.5 BN 5.05 4.08 12581843
1 x 2.5 7 x 0.69 2.12 7.11 3.95 BN 5.6 5.49 12581844
1 x 4.0 7 x 0.88 2.67 4.43 4.55 BN 6.3 7.57 12581845
1 x 6.0 7 x 1.07 3.24 2.96 5.1 BN 6.85 9.83 12581846
1 x 10 7 x 1.36 4.13 1.79 6.0 BN 9.0 16.3 12581275
1 x 16 7 x 1.70 4.90 1.13 6.8 BN 9.8 22.8 12581276
1 x 25 7 x 2.15 6.15 0.712 8.5 BN 11.5 33.8 12581419
1 x 35 7 x 2.53 7.25 0.514 9.6 BN 12.7 44.2 12581847
Extract from our delivery programme
* Description for core colours see page 154
Other cross sections on request.
RADOX® FR INTERNATIONAL
Single core, single core or multi core cable with circuit integrity in case of fire
HUBER+SUHNER 145
C
RAD
OX®
FR s
afet
y ca
bles
Multi core cable (drawing C)
Cross section Conductor Cores Cable Item no. Note
nom.Construction
nom. Ø nom.R20
IEC 60228 Ø nom. Colour* Ø nom.Weight nom.
mm2 n x mm Ø mm max. /km mm mm kg/100m
2 x 0.75 7 x 0.38 1.18 24.8 2.6 BN,BU 7.1 7.05 12581417
2 x 1.0 7 x 0.45 1.37 18.2 2.9 BN,BU 7.8 5.43 12582190
2 x 1.5 7 x 0.54 1.66 12.2 3.5 BN,BU 7.0 5.01 12581269without sheath
2 x 1.5 7 x 0.54 1.66 12.2 3.5 BN,BU 9.2 12.2 12581270
2 x 2.5 7 x 0.69 2.12 7.41 3.95 BN,BU 7.9 7.25 12581874without sheath
2 x 2.5 7 x 0.69 2.12 7.41 3.95 BN,BU 10.3 16.2 12581748
3 x 0.75 7 x 0.38 1.18 24.8 2.6 BN,BK,GY 7.6 8.75 12581418
3 G 1.5 7 x 0.54 1.66 12.2 3.5 BN,BU,GNYE 9.9 14.8 12581271
3 x 2.5 7 x 0.69 2.12 7.41 3.95 BN,BK,GY 10.9 19.4 12581272
3 G 2.5 7 x 0.69 2.12 7.41 3.95 BN,BU,GNYE 10.9 19.4 12581273
3 x 6.0 7 x 1.07 3.24 3.08 5.1 BN,BK,GY 13.8 35.3 12581925
3 x 16 7 x 1.70 4.90 1.15 6.8 BN,BK,GY 18.8 76.0 12581926
4 G 1.5 7 x 0.54 1.66 12.2 3.5 BN,BK,GY,GNYE 11.0 18.5 12581274
4 G 4.0 7 x 0.88 2.67 4.614.55 bn, BK,GY,GNYE 13.9 34.3 12581422
4 G 6.0 7 x 1.07 3.24 3.08 5.1 BN,BK,GY,GNYE 15.6 45.7 12581423
4 x 10 7 x 1.36 4.13 1.83 6.0 BN,BK,GY,BU 18.9 68.9 12581424
4 x 16 7 x 1.70 4.90 1.15 6.8 BN,BK,GY,BU 20.7 96.2 12581425
4 x 25 7 x 2.15 6.15 0.727 8.5 BN,BK,GY,BU 25.2 148 12581426
4 x 35 7 x 2.53 7.25 0.524 9.6 BN,BK,GY,BU 28.1 194 12581427
5 G 1.5 7 x 0.54 1.66 12.2 3.5 BU,BN,BK,GY,GNYE 12.1 22.4 12581284
5 G 2.5 7 x 0.69 2.12 7.41 3.95 BU,BN,BK,GY,GNYE 13.5 30.3 12581285
5 G 6.0 7 x 1.07 3.24 3.08 5.1 BU,BN,BK,GY,GNYE 17.5 57.6 12581286
5 G 10 7 x 1.36 4.13 1.83 6.0 BU,BN,BK,GY,GNYE 20.6 83.2 12581718
5 G 16 7 x 1.70 4.90 1.15 6.8 BU,BN,BK,GY,GNYE 22.7 118 12581287
10 x 1.5 7 x 0.54 1.66 12.2 3.5 BK,YE num.. 17.4 40.9 12582613
10 x 1.5 7 x 0.54 1.66 12.2 3.5 BK,YE num.. 20.5 59.4 12582614
4 x 25 +1 G 16
7 x 2.157 x 1.70
6.154.90
0.7271.15
8.56.8
BU,BN,BK,GY,GNYE 27.7 171 12581283
Extract from our delivery programme
* Description for core colours see page 154
Other cross sections on request.
RADOX® FR INTERNATIONAL
Single core, single core or multi core cable with circuit integrity in case of fire
146 HUBER+SUHNER
RADOX® FR INTERNATIONAL ALU
Communication cable with circuit integrity in case of fire
AnwendungFor emergency support systems: emergency lighting, smoke spill fans, fire alarms and sprinklers, emergency evacuation intercommunication systems, etc.
Composition of cable Cores <1.5 mm2
Conductor stranded tin plated copper OF copper, class 2 Flame barrier Insulation RADOX® 125 vernetzt Colours white, black numbered
Fillers (optional) RADOX®
Filler stranded tin plated copper OF copper, class 2Screening aluminium tape, plastic coatedSeparator (optional) plastic tapeSheath RADOX® 125 crosslinked
Colour red
Technical dataVoltage rating Uo/U 300 / 500 VTest voltage, 50 Hz, 1 Min. 2000 VTemperature range –40 °C up to +110 °CMin. bending radius 10 x cable–Ø
Fire testsFlame propagation::Vertical of a single cable IEC 60332–1, EN 50265–2–1Vertical of bunched cables IEC 60332–3–24, EN 50266–2–4 category CContent of halogen acid gas IEC 60754–1, EN 50267–2–1 0 mg/gCorrosivity of combustion gases IEC 60754–2, EN 50267–2–3Smoke density IEC 61034–2, EN 50268–2Circuit integrity 180 Min. IEC 60331–21Circuit integrity AS/NZS 3013, WS5
halogen free•flame retardant•in case of fire no corrosive •gases and low smokecircuit integrity in case of fire•excellent high and low tempera-•ture, and ozone resistanceweatherproof•easy to strip•
HUBER+SUHNER 147
RAD
OX®
FR s
afet
y ca
bles
Extract from our delivery programme
Cross section Conductor Cores Filler Cable Item no.
nom.Construction
nom.Ø nom.
R20 IEC 60228
Ø nom. Core numbers Ø nom. Ø nom.Weight nom.
mm2 n x mm Ø mm max. /km mm mm2 mm kg/100m
1 x 2 x 0.5 7 x 0.31 0.97 36.7 2.4 1 + 2 0.97 6.8 6.1 12581936
2 x 2 x 0.5 7 x 0.31 0.97 36.7 2.4 1/2 – 3/4 0.97 11.2 14.2 12581937
3 x 2 x 0.5 7 x 0.31 0.97 36.7 2.4 1/2 – 5/6 0.97 12.1 16.9 12581938
5 x 2 x 0.5 7 x 0.31 0.97 36.7 2.4 1/2 – 9/10 0.97 15.6 25.5 12581939
7 x 2 x 0.5 7 x 0.31 0.97 36.7 2.4 1/2 – 13/14 0.97 16.0 28.6 12581940
10 x 2 x 0.5 7 x 0.31 0.97 36.7 2.4 1/2 – 19/20 0.97 20.0 40.2 12581941
1 x 2 x 0.75 7 x 0.38 1.18 24.8 2.6 1 + 2 1.18 7.3 7.4 12581942
2 x 2 x 0.75 7 x 0.38 1.18 24.8 2.6 1/2 – 3/4 1.18 12.2 17.4 12581943
3 x 2 x 0.75 7 x 0.38 1.18 24.8 2.6 1/2 – 5/6 1.18 12.9 19.9 12581944
5 x 2 x 0.75 7 x 0.38 1.18 24.8 2.6 1/2 – 9/10 1.18 17.2 31.6 12581945
7 x 2 x 0.75 7 x 0.38 1.18 24.8 2.6 1/2 – 13/14 1.18 17.3 35.0 12581946
10 x 2 x 0.75 7 x 0.38 1.18 24.8 2.6 1/2 – 19/20 1.18 21.6 49.0 12581947
1 x 2 x 1.0 7 x 0.44 1.37 18.2 2.9 1 + 2 1.37 7.9 9.0 12581948
2 x 2 x 1.0 7 x 0.44 1.37 18.2 2.9 1/2 – 3/4 1.37 13.5 21.6 12581949
3 x 2 x 1.0 7 x 0.44 1.37 18.2 2.9 1/2 –– 5/6 1.37 14.3 24.8 12581950
5 x 2 x 1.0 7 x 0.44 1.37 18.2 2.9 1/2 – 9/10 1.37 19.1 39.4 12581951
7 x 2 x 1.0 7 x 0.44 1.37 18.2 2.9 1/2 – 13/14 1.37 19.1 43.4 12581952
10 x 2 x 1.0 7 x 0.44 1.37 18.2 2.9 1/2 – 19/20 1.37 24.1 62.2 12581953
1 x 3 x 1.0 7 x 0.44 1.37 18.2 2.9 1 – 3 1.37 8.5 11.3 12581954
1 x 4 x 1.0 7 x 0.44 1.37 18.2 2.9 1 – 4 1.37 9.4 13.8 12581955
1 x 2 x 1.5 7 x 0.54 1.66 12.2 3.5 1 + 2 1.66 9.3 12.5 12581956
2 x 2 x 1.5 7 x 0.54 1.66 12.2 3.5 1/2 – 3/4 1.66 16.0 30.0 12581957
RADOX® FR INTERNATIONAL ALU
Communication cable with circuit integrity in case of fire
* Description for core colours see page 154
Other cross sections on request.
148 HUBER+SUHNER
HUBER+SUHNER 149
Tech
nica
l inf
orm
atio
n
General technical information
Electrical formula 150
Table of three phase current 151
Material characteristics 152
Colour table 154
Material designations 154
Core colours 155
Resistance to cold and heat 156
Standards 157
Conversion AWG 158
Thermal classes of insulating materials according to IEC 60085 161
Wire cross sections 159
Guide to installation 161
Delivery spools 162
EMC screened cables 163 – 164
Protection of equipment 165
Fire test methods 166 – 168
Current carrying capacity 169 – 178
150 HUBER+SUHNER
200 · L · I· u0 · U
200 · L · P· u0 · U2
200 · L · I2
· p0 · P
200 · L · P· p0 · U2
200 · L · I · cos· u0 · U
200 · L · P· u0 · U2
200 · L · I2
· p0 · P
200 · L · P· p0 · U2 · cos2
173 · L · I · cos· u0 · U
100 · L · P· u0 · U2
300 · L · I2
· p0 · P
100 · L · P· p0 · U2 · cos2
PU ·
3400440 · 1
220001.73 · 400 · 0.89 · 0.9
P1.73 · cos · · U
1900230 · 0.77 · 0.79
PU · cos ·
Formulas
Required conductor cross section for electric cables
given Direct current Single phasealternating current
Three phasealternating current
Voltage drop, current
Voltage drop, power
Voltage drop, current
Voltage drop, voltage
Key:
I = Current in ampère A = Conductor cross section in mm2
= Conductivity (copper 56, aluminium 34) uo = Voltage drop in % of the operating voltage
L = Conductor lengths (single) in meters U = Operating voltage in volts
P = Transmission power in watts cos = Power factor (usually assumed to be 0.8)
po = Power loss in % of the transmission power
The formulas stated for alternating and three-phase current do not give any consideration to the inductive resist-ance. This resistance is a function of the distance of the individual con ductors between one another.Determination of the current if the power is known.
Direct current:
I =Example:What is the current that a heating unit of 3.4 kW absorbs at 440 V ? ( = 1)
I = = 7.7 A
P = Rated power in W
U = Voltage in V
l = Current in A
= Efficiency
Alternating current:
l =Example:What is the current consumption of an alternating current motor of 1.9 kW at cos = 0.77 and an efficiency of 79%?The voltage is 230 V, 50 Hz.
I = = 13.6 A
P = Rated power in W
U = Voltage in V
l = Current in A
cos = Phase shift
= Efficiency
Three phase current:l =
Example:What current does a three phase motor of 22 kW consume at 400 V, 50 Hz, with cos = 0,89 and an efficiency of 90% ?
I = 39.7 A
P = Nennleistung in W
U = Aussenleiterspannung in V
l = Aussenleiterstrom in A
cos = Phasenverschiebung
= Wirkungsgrad
Electrical formulas
HUBER+SUHNER 151
A
350
300
250
225
200
150
125
100
80
60
5040
2010
mm2
240
185
150
120
95
70
50
35
25
1610
L = 50 100 150 200 250 300 350 400 450 500 mP = 25 50 75 100 125 150 175 200 KW
I = F (P)
Permissable three phase cable loading at 5% voltage dropPresentation: I = F(L) und I = F(P) cos = 0.82
Example:A power of 70 kW is to be transmitted across a distance of L = 450 m. The funktion I = F(P) gives us 70 kW ~= 130 A (mixed users). The function I = F(L) provides the cable cross section of 95 mm2.
A length of 500 metres would already require a cable of 120 mm2 to ensure that the voltage loss and therefore also the power loss would be in an acceptable and economical range.
Representation: I = F(L) shows that, for example, for 95 mm2 the permissable fuse of 200 A determines the load limit up to L = 300 m, i.e. UV < 5 %.
From 300 m the cross section can no longer be fully utilized.
Perm
issab
le fu
se ra
ting
for f
ixed
insta
llatio
n
Table of three phase current
152 HUBER+SUHNER
Typical characteristics of various insulation and jacket materials for cables
Characteristics of materials
Insulation compounds
Thermoplastics Crosslinked materials
Abbreviations(1) PVC PE PBT-FR TPE-E ETFE FEP PTFE EPR PE-X RX 125 RX 155S RX 155 PVDF-X SIR
CENELEC type TI1 EI6 EI2
Thermical characteristics
Thermal resistance
20’000 h (°C) 70 70 110 110 135 180 250 90 90 120 130 135 135 180
24 h (°C) 100 100 160 160 220 240 300 180 180 200 220 220 220 260
Short circuit (°C) 160 100 160 160 250 250 300 250 250 250 250 250 300 350
Resistance to cold, moved (°C) -5 -55 -40 -40 -55 -55 -70 -40 -55 -40 -55 -55 -55 -55
Mechanical characteristics
Tensile strenght (N/mm2) 12.5 10 25 30 30 10 20 5.0 12.5 12.5 12.5 15 28 5.0
Elongation at break (%) 125 300 200 200 150 200 200 200 200 200 200 300 200 150
Abrasion resistance satisf. good good very good very good satisf. satisf. satisf. very good good very good good very good poor
Flexibilty (2) satisf. poor poor poor poor poor poor very good poor satisf. poor satisf. poor very good
Electrial characteristics
Volume resistivity at20 °C ( cm)
1014 1016 1015 1015 1016 1018 1018 1015 1016 1014 1016 1016 1014 1015
Dielectricconstant at 1 kHz
5.0 2.3 3.7 3.8 2.6 2.2 2.0 3.0 2.4 4.2 2.6 2.8 5.7 3.0
Fire characteristics
Flame retardant yes no yes no yes yes yes no no yes yes yes yes ja
Halogen free no yes yes yes no no no yes yes yes no no no ja
Corrosive combustion gases yes no no no yes yes yes no no no yes yes yes no
Smoke generation strong average average average low low low average average low strong strong low average
Resistance to
Ionizing radiation (kGy) 100 1000 1000 1000 2000 100 1 2000 1000 1000 1000 1000 1000 500
Solvents (3) satisf. satisf. good good very good very good very good satisf. satisf. satisf. good satisf. very good satisf.
Oils and fuels (3) satisf. satisf. good good very good very good very good schlecht satisf. satisf. good satisf. very good satisf.
Acids and alkaline solutions (3) good very good satisf. satisf. very good very good very good very good very good good good good very good satisf.
Water/hydrolysis (3) good very good satisf. satisf. very good very good very good good very good good very good very good very good very good
Weather/UV radiation good schlecht good good very good very good very good good satisf. good good good very good very good
(1) RX = RADOX®, for other abbreviations see following page "Material designations"(2) depends greatly on cable construction(3) influenced by type, time and medium temperature
Important: As the characteristics of compounds may vary widely according to their specific formulation, the values stated in the table must be understood as approximate values referring to typical representatives of their material class.
The data is based on laboratory investigations and practical experience. It is stated to the best of our knowl-edge, but without guarantee. We will gladly advise you in individual cases.
HUBER+SUHNER 153
Tech
nica
l inf
orm
atio
n
Abbreviation (1)
CENELEC type
Sheat compounds
Thermoplastics Crosslinked materials
LSFH TPU CR RX 125A RX 125M RX 125TM REMS REMS FH
TMPU EM2
Thermical characteristics
Thermal resistance
20’000 h (°C) 90 90 60 120 120 120 130 120
24 h (°C) 130 140 120 200 200 200 200 200
Short circuit (°C) 250 200 200 280 280 280 280 280
Resistance to cold, moved (°C) -25 -55 -25 -25 -25 -25 -40 -25
Mechanical characteristics
Tensile strenght (N/mm2) 9.0 25 10 10 9 10 15 10
Elongation at break (%) 125 300 300 125 125 125 300 125
Abrasion resistance good very good good good good good good good
Flexibilty (2) satisf. satisf. very good satisf. good good good good
Electrial characteristics
Volume resistivity at20 °C ( cm)
1013 1012 1010 1014 1012 1012 1012 1012
Dielectricconstant at 1 kHz
5 7 8 4.8 6 5 4.8 5.5
Fire characteristics
Flame retardant yes no yes yes yes yes yes yes
Halogen free yes yes no yes yes yes no yes
Corrosive combustion gases no no yes no no no yes no
Smoke generation low average stark low low low stark low
Resistance to
Ionizing radiation (kGy) 1000 5000 500 1000 1000 1000 1000 1000
Solvents (3) schlecht satisf. satisf. satisf. satisf. satisf. satisf. satisf.
Oils and fuels (3) schlecht good good satisf. good good very good very good
Acids and alkaline solutions (3) satisf. satisf. very good good good very good very good good
Water/hydrolysis (3) satisf. very good good good good very good good good
Weather/UV radiation satisf. good good good good good very good good
(1) RX = RADOX®, for other abbreviations see following page "Material designations"(2) depends greatly on cable construction(3) influenced by type, time and medium temperature
Important: As the characteristics of compounds may vary widely according to their specific formulation, the values stated in the table must be understood as approximate values referring to typical representatives of their material class.
The data is based on laboratory investigations and practical experience. It is stated to the best of our knowl-edge, but without guarantee. We will gladly advise you in individual cases.
Typical characteristics for cables
Characteristics of materials
154 HUBER+SUHNER
ThermoplasticsETFE Ethylene-tetrafluoroethylene copolymerFEP Tetrafluoroethylene-perfluoropropylene copolymerLSFHTM Halogen free, flame retardant material (low smoke free of halogen)PBT FR Flame retardant polybutylene terephthalatePE PolyethylenePTFE PolytetrafluoroethylenePVC PolyvinylchlorideTPC Thermoplastic polyester elastomersTPU Thermoplastic polyurethane
Crosslinked materialsCR Chloroprene rubberEPR Ethylene propylene rubberPE-X Crosslinked polyethylenePVDF-X Crosslinked polyvinylidene fluorideRADOX® 125 Polyolefin copolymerRADOX® 125A Polyolefin copolymerRADOX® 125M Polyolefin copolymerRADOX® 125TM Ethylene acrylate copolymerRADOX® 155 Polyolefin copolymerRADOX® 155S Polyolefin copolymerRADOX® ELASTOMER S (REMS) Ethylene acrylate copolymerRADOX® ELASTOMER S FH (REMS FH) Ethylene acrylate copolymerSIR Silicon rubber
RADOX® is a registered trademark of HUBER+SUHNER for electron beam crosslinked, heat resistant cableinsulations and sheaths.LSFHTM is a registered trademark of HUBER+SUHNER for halogen free, flame retardant cable sheaths.
Material designations
Colour table
BK = black/schwarz•TQ = turquoise/türkis•WH = white/weiss•BN = brown/braun•BU = blue/blau•RD = red/rot•YE = yellow/gelb•
GN = green/grün•GY = grey/grau•OG = orange/orange•VT = violet/violett•PK = pink/rosa•
GNYE = green-yellow/grün-gelb•
HUBER+SUHNER 155
Tech
nica
l inf
orm
atio
n
with yellow-green grounding wire
3 3
4 4
5 5
without yellow-green grounding wire
2 2
3 3
4 4
5 5
Core colours HD 308 S2 vs. HD 308
Example
Core numbers:New Old
HD 308 S2 HD 308
black brown blue grey yellow-green
Old
SEV 1101, 1102
156 HUBER+SUHNER
SIR
PVDF-X
PTFE
RADOX® 155
RADOX® 155S
RADOX® 125TM
RADOX® ELASTOMER S (REMS)
RADOX® ELASTOMER S FH (REMS FH)
RADOX® 125M
RADOX® 125A
RADOX® 125
RADOX® eco-F
FEP
ETFE
EPR
PE-X
LSFH
TPU
CR
PBT-FR
TPE-E
PVC
PE
-50°C 0°C +50°C +100°C +150°C +200°C +250°C +300°C 350°C
20’000 h 24 h
Typical operating temperature ranges of different insulations and sheaths
Resistance to cold and heat
SIR
PVDF-X
PTFE
RADOX® 155
RADOX® 155S
RADOX® 125TM
RADOX® ELASTOMER S (REMS)
RADOX® ELASTOMER S FH (REMS FH)
RADOX® 125M
RADOX® 125A
RADOX® 125
RADOX® eco-F
FEP
ETFE
EPR
PE-X
LSFH
TPU
CR
PBT-FR
TPE-E
PVC
PE
Key: Resistance to cold Resistance to heat
moved 20’000 h 24 h short circuit
HUBER+SUHNER 157
1 2 3 4 5 6 7 8 9
H 03 V V H – F 2 X 0.75
Tech
nica
l inf
orm
atio
n
System for type designation of electric cables according to CENELEC HD 361
Example:light weight PVC sheathed cable, flat
Standards
Block 1:
Type of standardH: Harmonised type
A: Acknowledged national type
Voltage rating UO/U01: 100/100 V
03: 300/300 V
05: 300/500 V
07: 450/750 V
Block 2:
Insulation material Sheat materialR: Ethylen propylen rubber, 90 °C
G: Ethylen vinylacetat
N: Polychloropren rubber
Q: Polyurethane
R: Ethylen propylen rubber, 60 °C
S: Silicon rubber
V: PVC
V2: PVC, 90 °C
V3: PVC, cold resistant
V5 PVC, oil resistant
Z: Crosslinked polyolefin compound,
little corrosive gases, low smoke
Z1: Thermoplastic polyolefin compound,
little corrosive gases, low smoke
Block 1 Block 2 Block 3
1
2
3 4
5
6
7
8
9
Construction featureH: flat, divisible line
H2: flat, non-divisible line
Conductor typeF: stranded (class 5) with flexible cables
H: stranded (class 6) with flexible cables
K: stranded (class 5) with permanently installed cables
R: stranded (class 2)
U: solid (class 1)
Block 3:
Number of cores
Protective earth conductorX: without protecitve earth conductor (yellow-green)
G: with protecitve earth conductor (yellow-green)
Conductor cross section in mm2
158 HUBER+SUHNER
AWG with UL/CSA with MIL
Cross sectionmm2 nom.
Diametermm nom.
Cross sectionmm2 nom.
36 0.013 0.13 –34 0.020 0.16 –32 0.032 0.20 –30 0.051 0.25 0.05728 0.081 0.32 0.09026 0.13 0.40 0.1524 0.21 0.51 0.2422 0.32 0.64 0.3820 0.52 0.81 0.6218 0.82 1.0 0.9616 1.3 1.3 1.214 2.1 1.6 1.912 3.3 2.1 3.010 5.3 2.6 4.78 8.4 3.3 8.66 13 4.1 144 21 5.2 223 27 5.8 –2 34 6.5 341 42 7.3 41
1/0 54 8.3 532/0 67 9.3 673/0 85 10 844/0 107 12 107
Thermalclass
Max. limiting-temperature
Thermalclass
Max. limiting-temperature
Thermalclass
Max. limiting-temperature
Y 90 °C B 130 °C 200 200 °CA 105 °C F 155 °C 220 220 °CE 120 °C H 180 °C 250 250 °C
Metric wire cross section and wire diameters
= American Wire Gauge
Conversion AWG
Thermal classes of insulating materials according to IEC 60085
HUBER+SUHNER 159
Tech
nica
l inf
orm
atio
n
Nom. cross sectionConstruction: number of wires (minimum value)
Strand diameter (approx.) max. direct current at 20 °C
solid, class 1 stranded, class 2 bare tinned
mm2 n x mm n x mm /km /km
0.5 1 x 0.80 7 x 0.30 36.0 36.7
0.75 1 x 1.00 7 x 0.37 24.5 24.8
1 1 x 1.13 7 x 0.43 18.1 18.2
1.5 1 x 1.38 7 x 0.52 12.1 12.2
2.5 1 x 1.78 7 x 0.67 7.41 7.56
4 1 x 2.25 7 x 0.85 4.61 4.70
6 1 x 2.76 7 x 1.04 3.08 3.11
10 1 x 3.57 7 x 1.35 1.83 1.84
16 1 x 4.50 7 x 1.70 1.15 1.16
25 - 7 x 2.16 0.727 0.734
35 - 7 x 2.52 0.524 0.529
50 - 19 x 1.78 0.387 0.391
70 - 19 x 2.16 0.268 0.270
95 - 19 x 2.52 0.193 0.195
120 - 37 x 2.03 0.153 0.154
150 - 37 x 2.25 0.124 0.126
185 - 37 x 2.52 0.0991 0.100
240 - 61 x 2.25 0.0754 0.0762
300 - 61 x 2.52 0.0601 0.0607
400 - 61 x 2.84 0.0470 0.0475
500 - 61 x 3.20 0.0366 0.0369
630 - 91 x 2.97 0.0283 0.0286
Terminals:Because of the larger diameter in classes 2, 5 and 6 compared with class 1, you must select a terminal for these classes that is one nominal cross section larger.
according to IEC 60228 and CENELEC HD 383
table 1
Wire cross section
160 HUBER+SUHNER
Nom. cross sectionConstruction: number of wires (minimum value)
Strand diameter (approx.) max. direct current at 20 °C
mm2
stranded, class 5n x mm
stranded, class 6n x mm
bare /km
tinned/km
0.5 19 x 0.21 25 x 0.16 39.0 40.1
0.75 24 x 0.21 38 x 0.16 26.0 26.7
1 32 x 0.21 50 x 0.16 19.5 20.0
1.5 30 x 0.26 75 x 0.16 13.3 13.7
2.5 50 x 0.26 125 x 0.16 7.98 8.21
4 56 x 0.31 200 x 0.16 4.95 5.09
6 80 x 0.31 174 x 0.21 3.30 3.39
10 77 x 0.41 290 x 0.21 1.91 1.95
16 123 x 0.41 462 x 0.21 1.21 1.24
25 190 x 0.41 722 x 0.21 0.780 0.795
35 266 x 0.41 1012 x 0.21 0.554 0.565
50 385 x 0.41 664 x 0.31 0.386 0.393
70 348 x 0.51 928 x 0.31 0.272 0.277
95 468 x 0.51 1260 x 0.31 0.206 0.210
120 589 x 0.51 1590 x 0.31 0.161 0.164
150 741 x 0.51 1990 x 0.31 0.129 0.132
185 912 x 0.51 2452 x 0.31 0.106 0.108
240 1184 x 0.51 3180 x 0.31 0.0801 0.0817
300 1480 x 0.51 3976 x 0.31 0.0641 0.0654
400 1961 x 0.51 - 0.0486 0.0495
500 1702 x 0.61 - 0.0384 0.0391
630 2146 x 0.61 - 0.0287 0.0292
according to IEC 60228 and Cenelec HD 383
table 2
Wire cross sections
HUBER+SUHNER 161
1. Für das Einziehen von Kabeln mittels Ziehkopf an den Kupfer-1. Für das Einziehen von Kabeln mittels Ziehkopf an den Kupfer-leitern, oder mittels Ziehstrumpf, kann folgende max. Zugkraft leitern, oder mittels Ziehstrumpf, kann folgende max. Zugkraft (P) zugelassen werden:(P) zugelassen werden:
2. Beim Einzeiehn von Kabeln mit zugfester Armierung ist gol-2. Beim Einzeiehn von Kabeln mit zugfester Armierung ist gol-gende max. Zugkraft (P) zulässig:gende max. Zugkraft (P) zulässig:
P = 50 x A (N)A = Summe der Polleiter-Querschnitte (mm2)
P = 9 x D2 (N)D = Kabeldurchmesser über Armierung (mm)
Die Berechnung der erforderlichen Einzugskräfte wird mit den folgenden Formeln durchgeführt:
Tech
nica
l inf
orm
atio
n
Guide to installation
Smallest allowable bending radii for power and signal cables
Conductor type Cable diameter D (mm)Installation method D ≤ 8 8 < D ≤ 12 12 < D ≤ 20 D < 20solid, class 1/stranded, class 2- carefully bend at connection 2D 3D 4D 4D- normal use 4D 5D 6D 6D
stranded, class 5 (HUBER+SUHNER)- fixed 3D 3D 4D 4D- flexing 4D 4D 5D 6D
Allowable tensile stress
1. For installing cables by pulling on the conductors, or by drawing sleeve, the following max. pulling force (P) isallowed::
2. When installing cables with high tensile armouring, the fol-lowing max. pulling force (P) is allowed:
P = 50 x A (N)A = Sum of conductor cross section (mm2)
P = 9 x D2 (N)D = cable diameter over armouring (mm)
The calculation of pulling forces necessary for installation is done using the following formulas:
Pulling force for installation of a straight section withoutelevation difference.
Pulling force for installation of a straight section with elevation difference
P = 10 x G x L x μ P = 10 x G x (L x μ ± h)
with P: pulling force at the end of the stretch (N) with h: elevation difference (m)
G: weight of the cable (kg/m) Coefficient of friction μ
L: length of the section (m) 0.15 – 0.30 installation with rollers
μ: coefficient of friction 0.40 – 0.60installation in cement pipesinstallation in plastic pipes
0.15 – 0.25 – with special lubricating grease
0.15 – 0.30 – with water
N.B.: Very long cable lengths with thermoplastic sheaths can only be pulled into plastic pipes with the aid of lubricants. Local heating, occurring mainly in bends, may cause the cable to melt into the pipe walls.
162 HUBER+SUHNER
l 1l 2
d 1
d 2
d 3
Spool type
One way spoolsNr. 5 Nr. 6 Nr. 7 DIN L L L L LHL LHL LHL LHL LHL LHL
250 355 450/13 450/14 500 710 900 1050 1250 1400 1600d 1 140 140 170 250 355 450 450 500 710 900 1050 1250 1400 1600d 2 65 65 65 160 200 200 312 250 360 450 550 700 700 800d 3 60 60 60 22 36 50 50 50 82 82 82 92 92 92l 1 56 106 135 200 160 244 244 321 430 545 698 726 880 1025l 2 50 100 130 160 150 228 228 305 400 450 600 630 760 900
Tara kg 0.08 0.10 0.15 0.71 1.54 2.48 3.02 3.16 10 36 53 74 120 174
CableØ mm
Cable length per delivery spool m
1 970 2020 3710 81002 500 930 2030 58204 510 1450 940 2240 58806 220 650 420 1000 2610 4770 83808 360 230 560 1470 2680 4710
10 230 150 360 940 1720 301012 250 650 1190 209014 180 480 880 154016 140 370 670 118018 110 290 530 93020 230 430 750 1060 1750 271022 350 620 880 1450 224024 300 520 740 1220 188026 250 450 630 1040 161028 220 380 540 890 138030 190 330 470 780 121032 170 290 410 680 106034 150 260 370 610 94036 130 230 330 540 84038 120 210 290 490 75040 190 260 440 68045 150 210 350 54048 130 180 300 470
Delivery spools
HUBER+SUHNER 163
Tech
nica
l inf
orm
atio
n
The screening of cables can be described by the two coupling quantities of transfer impedance ZT and transfer admittance YT. Both coupling quantities are basically a function of the geometry and the environ-ment; depending on the specific application and requirements, the coupling quantities can be optimised for a given cable.
EMI electromagnetic interferenceEMP electromagnetic pulseESD electrostatic dischargeLEMP lightning electromagnetic pulseNEMP nuclear electromagnetic pulseTEMPEST tap-proofness (eaves-dropping protection)NEXT near end crosstalk
With HUBER+SUHNER, your screening problems will end.We can ensure this thanks to the vast experience accumulated in this field responding to every kind of customer need and collaborating continuously with research institutes..
EMC screened cables
Measurement engineering at HUBER+SUHNERComplies with the following standards:IEC 96-1 and 46 A/DIN 47250/VG 95373/CCITT/...
Screenings for all EMC requirementsHUBER+SUHNER designs, optimises and produces products for a wide variety of performance classes. These products are implemented using different braids, foils, high-permeability intermediate layers, microwave absorbing and semi-conducting layers, mixed screens, etc.
164 HUBER+SUHNER
1
2100m
52
10m52
1m
52
100μ52
10μ52
1μ
D= 1mm
3mm
8mm
15mm
ZT
( Ω )m
2 4 68 2 4 68 2 4 68 2 4 68 2 4 681K 10K 100K 1M 10M 100M
f (Hz)
1
2100m
52
10m52
1m
52
100μ52
10μ52
1μ
D= 1mm
3mm
8mm
15mm
ZT
( Ω )m
2 4 68 2 4 68 2 4 68 2 4 68 2 4 681K 10K 100K 1M 10M 100M
f (Hz)
i2
i2i2i2
l
ZT =u1 i2 ·l
i1u2
YT = [S/m][Ω/m]i1
u2 ·l
l l
V
V
A
u1
u1
Transfer impedance values of single braid screeningApproximate values
The transfer impedance ZT (also called “coupling resistance”) refers to the rela-tionship between the current in one wire and the lon-gitudinal voltage it induces in the other wire (ohmic-inductive coupling)
The transfer admittance YTrefers to the relationship between the voltage in one wire and the leak current it induces in the other line (capacitive coupling).
The cable together with its surroundings form a three-conductor system. It consists of two coupled conduc-tors with one common conductor (screen).Transfer impedance ZT and transfer admittance YT are
cable quantities which are always defined in con-junction with the surroundings of the cable and the construction of the cable itself.
Screened cables from single braid to superscreen
Transfer impedance values ZT as a function of the frequency f and the cable diameter D as parameters
Transfer impedance ZT as a function of the frequency f and of the cablediameter D as parameters
Definition of transfer impedance ZT
Inner conductor
Outer conductor Definition of transfer admittance YT
Transfer impedance values of superscreenApproximate values
EMC screened cables
HUBER+SUHNER 165
Tech
nica
l inf
orm
atio
n
Protect your equipment and machinery from interference and failure
The situationEnvironmental pollution is a modern buzzword. But do you ever think of it as "pollution" by electromagnetic radiation, by "electrosmog"?
Your problemOnly when machinery starts to fail and plant opera-tion is disrupted do the people in charge start think-ing. But things don’t have to reach that point. Non-
screened cables act in the same way as antennas, attracting interference from the outside or radiating it.
Our solutionCopper braids prevent dangerous interferences with cables. At the same time, the interference radiated by the cable is reduced. Our solution consists not only in the specification of a degree of coverage. HUBER+SUHNER also defines the effectiveness of a copper braid as a measurable quantity. This noise immunity is expressed by the transfer impedance (cou-pling resistance) at a given frequency (MHz) in /m.
Optimized, high grade screeningOptimized screening braids enable even the most intractable screening problems to be solved. And in screening cables, we take care to ensure that perform-ance of the screened cables will not be significantly affected in terms of flexibility, workability, weight and dimensions.
single braid
"pipe"
frequency
trans
fer i
mpe
danc
e
+ foil
optimisedsingle braid
Lightning protector (earth)
Fluorescent lamp
Computer
Mai
ns
Main
Radio set
RF oven
optimiseddoublebraid
2nd braid +amorphous metal(superscreen)
doublebraid
166 HUBER+SUHNER
180
125
45° 45°
600
600
100 10
0
55 10
1600
800
30m
in. 2
50
500
100
75
3500
DesignationEN 50266-2-4IEC 60332-3-24
NF C32-070 test 2UIC 895 VE appendix 7
Flame temperatureDetermined by the prescribed
propane gas and air volumes.830 ± 50 °C.
Test duration
Cat. A (7 l compustible material): 40 min.
Cat. B (3.5 l compustible material): 40 min.
Cat. C (1.5 l compustible material): 20 min.
30 min.
ConditionsThe damage by fire shall be maximum 2.5 m from the lower burner end.
The cable piece projecting from the pipe shall be not damaged.
Fire test methods
Fire test methods for electrical wires and cables
DesignationEN 50265-2-1IEC 60332-1
EN 50265-2-2IEC 60332-2
Flame temperatureDetermined by the prescribed
adjustment of the flame.
Determined by the prescribed
adjustment of the flame.
Test durationCable Ø D 25 mm: 60 sCable Ø 25 < D 50 mm: 120 s
20 s
ConditionsThe cable shall be self extinguishing.
The damage by fire shall be more than50 mm from the top fastening clamp.
The cable shall be self extinguishing.
The damage by fire shall be more than50 mm from the top fastening clamp.
fan
pipe Ø 125
ignition flame
oven
air
air air
HUBER+SUHNER 167
G
60°
25 75
250
13
S30°
45° 45°
S
600 100
250
13
180
55
200
B
230-
240
17
50
B
230-
240
250
50-7
5
455
20°
40
125
Tech
nica
l inf
orm
atio
n
Fire test methods
Fire test methods for electrical wires and cables
DesignationMIL-W-22759 and MIL-W-81044VG 95218-2 procedure 4 VG 95218-2 procedure 3
Flame temperature min. 950 °CDetermined by the prescribed
adjustment of the flame.
Test duration 30 sCable Ø D 25 mm: 60 sCable Ø 25 < D 50 mm: 120 s
Conditions
The specimen shall not continue to burn for more than 30 s, and damage by fire shall not exceed 76 mm. Dripping material shall not ignite the tensioned tissue paper (S).
The specimen shall not continue to burn for more than 30 s, and damage by fire shall not exceed 76 mm. Dripping material shall not ignite the tensioned tissue paper (S).
DesignationUL 1581 section 1090Horizontal specimen AWM flame test
UL 1581 section 1061UL 1581 section 1080 (VW1)
Flame temperatureDetermined by the prescribed adjustment of the flame.
Determined by the prescribed adjustment of the flame.
Test duration 30 sSect.1061: 60s flaming,30s pause (3x)Sect.1080: 15s flaming,15s pause (5x)
ConditionsThe rate of the flame propagation shall not exceed 25 mm/min. Dripping material shall not ignite the cotton wool underneath (B).
The paper shall not be burned more than 25%, and the specimen shall not continue to burn for more than 60 s. Dripping material shall not ignite the cotton wool underneath (B).
Papier 10 x 20
168 HUBER+SUHNER
RST
75
3A
150020
350
1200
3000
1000
3000
Fire test methods
Designation
IEC 60331-21, IEC 60331-23DIN VDE 0472-814BS 6387, category C BS 6387, category W
Flame temperatureIEC, DIN VDE: min. 750 °CBS : 950 ± 40 °C.
650 ± 40 °C
Test durationIEC: 90 min. recommendedDIN VDE, BS: 180 min.
30 min.
Conditions
Zwischen den Adern wird eine Prüfspannung angelegt.IEC: power cable: UO/UIEC, DIN VDE: data cable: 110 VDIN VDE: power cable: 230/400 VBS: all UO/UThe fuses shall not blow and the incandescent lamps shall not extinguish.
A test voltage is applied between the cores which equals the mains voltage UO/U. After 15 min. exposure to the flame, the sprinkler is additionally switched on. The fuses shall not blow and the incandescent lamps shall not extinguish.
DesignationEN 50267-2-2IEC 60754-2
EN 50268-2IEC 61034-2
Flame temperature min. 935 °CDetermined by the composition
of the combustion liquid.
Test duration 30 min.. 40 min..
ConditionsThe pH value of the washing water shall be min. 4.3, its conductivity shall not exceed10 S/mm.
The light permeability of the resulting
smoke shall be min. 60%.
lampoven
gas washing bottlessynth. air
specimen 1 g
fan
photocellunit
cabletrouh withcombustion liquid
test chamberheight=3000 mm
recirculation air screening
holder
Fire test methods for electrical wires and cables
HUBER+SUHNER 169
Tech
nica
l inf
orm
atio
n
ScopeThe following tables referring to RADOX® connecting leads and multicore cables give easy and fast support for the layout of apparatus and components.The following remarks are based on today’s state of the art and practical experience as described in the stand-ard IEC 60216, IEC 60287 and IEC 60364. The application of products will frequently vary from the theoreti-cal values of constant ambient temperature, constant current carrying, homogeneous laying and others. That means, in practice the theoretical current carrying will differ from the real values.For a safe layout of apparatus and components it is recommended to carry out a test with the installed connect-ing lead or cable under service conditions.
DefinitionsCurrent load current passed through the cable during operationContinuous operation an operation with constant current whose duration is at least long enough to allow the system to reach thermal equilibrium, but may then go on indefinitelyCurrent rating maximum permissible current under determined operatingPermissible operating temperature maximum permissible temperature on the condutor in continuous operationWire insulated single coreCable bundle with jacket with one ore more insulated single coresConductor temperature temperature of the surface of the core material
General remarksThe current rating of a cable depends on the conductor cross section, on the cable design, on the characteristics of the insulation materials, on the installation conditions and, for larger cross sections, on the frequency (skin and proximity effects). Also, additional heating effects due to higher ambient temperatures, due to heating elements and due to bunching of cables have to be taken into account.The conductor cross section has to be selected in such a way that the actual current load does not exceed the curent rating, i.e. the conductor temperature does not exceed the permissible operating temperature. The deter-mining factor is the appropriate, most unfavourable operating condition, encountered during operation over the whole length of the cable.
Current rating under service conditions (I [A])
I = IN • f1 • f2 • f3 • f4 • f5I [A] Current rating for continuous operation under service conditionsIN[A] Current rating for continuous operation under standard conditionsf1 Reduction factor for increased ambient temperaturef2 Conversion factor for deviated conductor temperature acc. to. temperature index IEC 60216 (20'000 h)f3 Reduction factor for multicore cablesf4 Reduction factor for increased frequencyf5 Reduction factor for bundeled cables
Current carrying capacity
of RADOX® single core and multi core cables
170 HUBER+SUHNER
PCV, CR 70 °C
PE-X, EPR 90 °C
RADOX® 125 120 °C
160 °C 1'250 h
150 °C 2'500 h
140 °C 5'000 h
130 °C 10'000 h
120 °C 20'000 h
110 °C 40'000 h
100 °C 80'000 h
90 °C 160'000 h
80 °C 320'000 h
Standard conditions for current rating (IN [A])The tabled values for the current rating were calculated according to IEC 60287 for the following standardconditions:
continuous operation•single circuit for 3-phase current, single conductor for 1-phase current•30°C ambient temperature and sufficiently large and ventilated spaces, whose ambient temperature is not•appreciably increased by the heat coming from the cables.120 °C conductor temperature•frequency up to 200 Hz•
Installation in air, unrestricted heat dissipation, means that the following installation conditions are observed :distance of the cables from the wall, from the floor, from the ceiling > cable diameter•distance between two adjacent power circuits > 2 x cable diameter•vertical distance between power circuits laid one upon another for individual cables > 2 x cable diameter •and for layers of cables > 200 mmperforated tray with a perforation > 30 % of the total surface•
Open trays are continuous supports with vertical sides, but without cover. A possible perforation accounts for < 30% of the total surface.
Closed ducts are entirely closed. Pipes belong to this category also. The max. filling degree is 60%.
Maximum permitted conductor temperature for vari-ous insulating materials according to IEC 60216 (20'000 h / 50 % elongation at break):
Example RADOX® 125, d.h. 120 °C / 20'000 h
Life time expectationIf crosslinked wires are used at higher temperatures than indicated by the temperature index of IEC 60216, the life time is reduced accordingly. Analogical, the life time will increase at lower temperature. RADOX® 125 for example has a life span of 20'000 h at a conductor temperature of +120 °C, which is approx. 2.5 years. If it is used at another temperature, life time expectations are as follows:
Current carrying capacity
of RADOX® single core and multi core cables
HUBER+SUHNER 171
Tech
nica
l inf
orm
atio
n
Reduction factors for increased ambient temperature (f1)
Ambient temp. [°C] 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115
Reduction factor f1 1 0.97 0.94 0.91 0.88 0.85 0.82 0.78 0.75 0.71 0.67 0.62 0.58 0.53 0.47 0.41 0.33 0.22
Reduction factors for different permissible conductor temperature (f2)
Conductor temp. (°C) 135 120 110 100 90 80
Reduction factor f2 1 0.96 0.91 0.85 0.79
Reduction factors for multicore cables (f3)
No. of cores in cable 3 4 5 7 8 10 14 16 19 20 24 27 33 40 61
Reduction factor f3 1.0 0.80 0.75 0.65 0.62 0.55 0.50 0.48 0.45 0.44 0.40 0.39 0.37 0.35 0.30
Reduction factors for increased frequency (f4)
Frequency [Hz]* 400 600 800 1000 2000 3000 4000 5000 10000
Copper conductorcross section mm2
faktors f4
1.5 1 1 1 1 1 1 1 1 1
2.5 1 1 1 1 1 1 1 1 1
4 1 1 1 1 1 1 1 1 0.98
6 1 1 1 1 1 1 1 0.99 0.93
10 1 1 1 1 1 1 0.96 0.93 0.82
16 1 1 1 1 1 0.95 0.91 0.87 0.76
25 1 1 1 1 0.94 0.88 0.83 0.80 0.69
35 1 1 1 0.98 0.89 0.82 0.77 0.74 0.64
50 1 1 0.97 0.94 0.83 0.76 0.72 0.69 0.59
70 1 0.95 0.91 0.88 0.77 0.71 0.67 0.63 0.54
95 0.98 0.93 0.88 0.84 0.73 0.67 0.63 0.60 0.51
120 0.94 0.88 0.84 0.80 0.69 0.64 0.60 0.57 0.48
150 0.90 0.85 0.80 0.77 0.66 0.61 0.57 0.54 0.46
185 0.88 0.82 0.77 0.74 0.64 0.58 0.54 0.52 0.44
240 0.85 0.77 0.72 0.69 0.60 0.54 0.51 0.48 0.41
300 0.79 0.73 0.69 0.66 0.57 0.52 0.48 0.46 0.39
400 0.75 0.69 0.65 0.63 0.54 0.49 0.46 0.44 0.37
* We recommend that you use a special conductor design for frequencies > 800 Hz and cross sections > 25 mm2 (waveguide design).
Current carrying capacity
of RADOX® single core and multi core cables
172 HUBER+SUHNER
d
d
Current carrying capacity
of RADOX® single cores
Installation method Connecting lead in free air or perforated tray
Number of simultane-ous loaded conductors on each tray 1 2 3 4 6 8 10 16 20 4 6
Reduction factor f5 1 0.87 0.81 0.78 0.75 0.74 0.73 0.72 0.71 0.71 0.62
Copper conductor cross section mm2 Current carrying capacity in [A]
0.50 19 16.4 15.3 14.7 14.2 14.0 13.8 13.6 13.4 13.4 11.7
0.75 24 20.8 19.4 18.6 17.9 17.7 17.4 17.2 17.0 17.0 14.8
1.0 29 24.8 23.1 22.2 21.4 21.1 20.8 20.5 20.2 20.2 17.7
1.5 36 31 29 28 27 26 26 26 25 25 22
2.5 49 43 40 38 37 36 36 35 35 35 30
4 66 57 53 51 49 49 48 47 47 47 41
6 85 74 69 67 64 63 62 61 61 61 53
10 121 105 98 94 91 90 88 87 86 86 75
16 163 142 132 127 122 121 119 117 116 116 101
25 219 191 177 171 164 162 160 158 155 155 136
35 272 237 220 212 204 201 199 196 193 193 169
50 344 299 279 268 258 255 251 248 244 244 213
70 439 382 356 342 329 325 320 316 312 312 272
95 523 455 424 408 392 387 382 377 371 371 324
120 621 540 503 484 466 460 453 447 441 441 385
150 723 629 586 564 542 535 528 521 513 513 448
185 825 718 668 644 619 611 602 594 586 586 512
240 996 867 807 777 747 737 727 717 707 707 618
300 1150 1001 932 897 863 851 840 828 817 817 713
400 1473 1282 1194 1149 1105 1091 1076 1061 1046 1046 914
HUBER+SUHNER 173
Tech
nica
l inf
orm
atio
n
8 10 16 20 4 6 8 10 16 20 4 6 8 10 16 20
0.57 0.53 0.47 0.45 0.67 0.59 0.54 0.50 0.45 0.43 0.71 0.58 0.52 0.48 0.41 0.38
10.8 10.0 8.9 8.5 12.7 11.2 10.2 9.5 8.5 8.1 13.4 11.0 9.8 9.1 7.7 7.2
13.6 12.7 11.2 10.8 16.0 14.1 12.9 12.0 10.8 10.3 17.0 13.9 12.4 11.5 9.8 9.1
16.2 15.1 13.4 12.8 19.1 16.8 15.4 14.3 12.8 12.3 20.2 16.5 14.8 13.7 11.7 10.8
20 19 17 16 24 21 19 18 16 15 25 21 19 17 15 14
28 26 23 22 33 29 26 24 22 21 35 28 25 23 20 19
38 35 31 30 44 39 36 33 30 28 47 38 34 32 27 25
49 45 40 38 57 50 46 43 38 37 61 49 44 41 35 32
69 64 57 54 81 71 65 61 54 52 86 70 63 58 50 46
93 86 77 73 109 96 88 82 73 70 116 95 85 78 67 62
125 116 103 99 147 129 118 110 99 94 155 127 114 105 90 83
155 144 128 122 182 160 147 136 122 117 193 158 141 131 112 103
196 182 162 155 230 203 186 172 155 148 244 200 179 165 141 131
250 233 206 198 294 259 237 220 198 189 312 255 228 211 180 167
298 277 246 235 350 309 282 262 235 225 371 303 272 251 214 199
354 329 292 279 416 366 335 311 279 267 441 360 323 298 255 236
412 383 340 325 484 427 390 362 325 311 513 419 376 347 296 275
470 437 388 371 553 487 446 413 371 355 586 479 429 396 338 314
568 528 468 448 667 588 538 498 448 428 707 578 518 478 408 378
656 610 541 518 771 679 621 575 518 495 817 667 598 552 472 437
840 781 693 663 987 870 796 737 663 634 1046 855 766 708 604 560
Continuous current ratingconductor temperature 120 °C, ambient temperature 30°C
174 HUBER+SUHNER
Installation method on floor or wall fixed on a ceiling or under floor
Number of simultane-ous loaded conductors on each tray 1 2 3 4 1 2 3 4 5 6 7 8
Reduction factor f5 1 0.87 0.79 0.75 0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62
Copper conductor cross section mm2 Current carrying capacity in [A]
0.50 18 15.3 14.2 13.5 17.1 14.5 12.9 12.2 11.9 11.5 11.3 11.1
0.75 23 19.3 17.9 17.0 21.6 18.4 16.3 15.4 15.0 14.5 14.3 14.1
1.0 27 23.0 21.4 20.3 25.7 21.9 19.5 18.4 17.9 17.3 17.1 16.8
1.5 34 29 27 25 32 27 24 23 22 22 21 21
2.5 46 39 37 35 44 38 33 32 31 30 29 29
4 63 53 49 47 59 51 45 43 41 40 39 39
6 81 69 64 61 77 66 58 55 53 52 51 50
10 115 98 91 86 109 93 83 78 76 74 72 71
16 155 132 122 116 147 125 111 105 102 99 98 96
25 208 177 164 156 198 169 150 141 137 133 131 129
35 258 220 204 194 245 209 186 176 171 165 163 160
50 327 278 258 245 310 265 235 222 216 209 206 203
70 417 354 329 313 396 338 300 284 275 267 263 259
95 497 422 393 373 472 402 358 338 328 318 313 308
120 590 501 466 442 560 478 425 401 389 378 372 366
150 687 584 543 515 653 556 495 467 453 440 433 426
185 784 666 619 588 745 635 564 533 517 502 494 486
240 946 804 747 710 899 766 681 643 624 606 596 587
300 1093 929 863 819 1038 885 787 743 721 699 688 677
400 1352 1150 1069 1114 1285 1096 974 920 893 866 852 839
or
Current carrying capacity
of RADOX® single cores
HUBER+SUHNER 175
Tech
nica
l inf
orm
atio
n
in conduit, in a void or in a pipe
9 1 2 3 4 5 6 7 8 9 10 12 14 16 20
0.61 1 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.38
11.0 14.4 11.5 10.1 9.3 8.6 8.2 7.8 7.5 7.2 6.9 6.5 6.2 5.9 5.5
13.9 18.2 14.5 12.7 11.8 10.9 10.4 9.8 9.4 9.1 8.7 8.2 7.8 7.4 6.9
16.5 22 17.3 15.2 14.1 13.0 12.3 11.7 11.3 10.8 10.4 9.7 9.3 8.9 8.2
21 27 22 19 18 16 15 15 14 14 13 12 12 11 10
28 37 30 26 24 22 21 20 19 19 18 17 16 15 14
38 50 40 35 33 30 29 27 26 25 24 23 22 21 19
49 65 52 45 42 39 37 35 34 32 31 29 28 27 25
70 92 74 64 60 55 52 50 48 46 44 41 40 38 35
94 124 99 87 81 74 71 67 64 62 59 56 53 51 47
127 166 133 117 108 100 95 90 87 83 80 75 72 68 63
158 207 165 145 134 124 118 112 107 103 99 93 89 85 79
199 261 209 183 170 157 149 141 136 131 125 118 112 107 99
254 334 267 234 217 200 190 180 173 167 160 150 143 137 127
303 397 318 278 258 238 227 215 207 199 191 179 171 163 151
360 472 378 330 307 283 269 255 245 236 227 212 203 194 179
419 549 440 385 357 330 313 297 286 275 264 247 236 225 209
478 627 502 439 408 376 357 339 326 314 301 282 270 257 238
577 757 606 530 492 454 431 409 394 378 363 341 325 310 288
666 874 699 612 568 524 498 472 454 437 420 393 376 358 332
825 973 779 682 633 584 555 526 506 487 468 438 419 399 370
Continuous current ratingconductor temperature 120 °C, ambient temperature 30°C
176 HUBER+SUHNER
0.3 d
Installation method Multicore cables in free air or perforated trays
Number of simultane-ous loaded conductors on each tray 1 2 3 4 6 8 10 16 20 4 6
Reduction factor f5 1 0.87 0.81 0.78 0.75 0.74 0.73 0.72 0.71 0.71 0.62
Copper conductor cross section mm2 Current carrying capacity in [A]
0.50 14.5 12.6 11.7 11.3 10.9 10.7 10.6 10.4 10.3 10.3 9.0
0.75 18.5 16.1 15.0 14.4 13.9 13.7 13.5 13.3 13.1 13.1 11.5
1.0 22 19.1 17.8 17.2 16.5 16.3 16.1 15.8 15.6 15.6 13.6
1.5 28 25 23 22 21 21 21 21 20 20 18
2.5 38 34 31 30 29 29 28 28 27 27 24
4 51 44 42 40 39 38 38 37 37 37 32
6 66 58 54 52 50 49 49 48 47 47 41
10 95 83 77 75 72 71 70 69 68 68 59
16 128 112 104 100 96 95 94 93 91 91 80
25 167 146 136 131 126 124 122 121 119 119 104
35 205 179 167 160 154 152 150 148 146 146 128
50 257 224 209 201 193 191 188 186 183 183 160
70 325 283 264 254 244 241 238 234 231 231 202
95 382 333 310 298 287 283 279 276 272 272 237
120 443 386 359 346 333 328 324 319 315 315 275
Current carrying capacity
of RADOX® multi core cables
HUBER+SUHNER 177
Tech
nica
l inf
orm
atio
n
8 10 16 20 4 6 8 10 16 20 4 6 8 10 16 20
0.57 0.53 0.47 0.45 0.67 0.59 0.54 0.50 0.45 0.43 0.71 0.58 0.52 0.48 0.41 0.38
8.3 7.7 6.8 6.5 9.7 8.6 7.8 7.3 6.5 6.2 10.3 8.4 7.5 7.0 5.9 5.5
10.5 9.8 8.7 8.3 12.4 10.9 10.0 9.3 8.3 8.0 13.1 10.7 9.6 8.9 7.6 7.0
12.5 11.7 10.3 9.9 14.7 13.0 11.9 11.0 9.9 9.5 15.6 12.8 11.4 10.6 9.0 8.4
16 15 14 13 19 17 16 14 13 13 20 17 15 14 12 11
22 21 18 18 26 23 21 19 18 17 27 23 20 19 16 15
30 28 24 23 35 31 28 26 23 22 37 30 27 25 21 20
38 35 32 30 45 39 36 33 30 29 47 39 35 32 28 26
55 51 45 43 64 57 52 48 43 41 68 56 50 46 39 37
73 68 61 58 86 76 70 64 58 56 91 75 67 62 53 49
96 89 79 76 112 99 91 84 76 72 119 97 87 81 69 64
117 109 97 93 138 121 111 103 93 89 146 119 107 99 85 78
147 137 121 116 173 152 139 129 116 111 183 150 134 124 106 98
186 173 153 147 218 192 176 163 147 140 231 189 169 156 134 124
218 203 180 172 256 226 207 191 172 165 272 222 199 184 157 146
253 235 209 200 297 262 240 222 200 191 315 257 231 213 182 169
Continuous current ratingconductor temperature 120 °C, ambient temperature 30°C
178 HUBER+SUHNER
Installation method on floor or wall fixed on a ceiling or under floor
Number of simultane-ous loaded conductors on each tray 1 2 3 4 1 2 3 4 5 6 7 8
Reduction factor f5 1 0.87 0.79 0.75 0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62
Copper conductor cross section mm2 Current carrying capacity in [A]
0.50 13.5 11.5 10.7 10.1 12.8 10.9 9.7 9.2 8.9 8.6 8.5 8.4
0.75 17 14.5 13.4 12.8 16.2 13.8 12.2 11.6 11.2 10.9 10.7 10.5
1.0 20 17.0 15.8 15.0 19.0 16.2 14.4 13.6 13.2 12.8 12.6 12.4
1.5 26 23 21 20 25 22 19 18 18 17 17 17
2.5 35 30 28 27 34 29 26 24 24 23 23 22
4 48 41 38 36 46 39 35 33 32 31 31 30
6 62 53 49 47 59 51 45 43 41 40 40 39
10 88 75 70 66 84 72 64 60 59 57 56 55
16 116 99 92 87 111 94 84 79 77 75 74 72
25 154 131 122 116 147 125 111 105 102 99 98 96
35 190 162 151 143 181 154 137 130 126 122 120 118
50 239 204 189 180 228 194 173 163 158 153 151 149
70 299 255 237 225 285 243 216 204 198 192 189 186
95 351 299 278 264 334 285 253 239 232 225 222 218
120 405 345 320 304 385 329 292 276 268 260 256 252
oder
Current carrying capacity
of RADOX® multi core cables
HUBER+SUHNER 179
Tech
nica
l inf
orm
atio
n
in conduit, in a void or in a pipe
9 1 2 3 4 5 6 7 8 9 10 12 14 16 20
0.61 1 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.38
8.2 10.8 8.6 7.6 7.0 6.5 6.2 5.8 5.6 5.4 5.2 4.9 4.6 4.4 4.1
10.4 13.6 10.9 9.5 8.8 8.2 7.8 7.3 7.1 6.8 6.5 6.1 5.8 5.6 5.2
12.2 15.8 12.6 11.1 10.3 9.5 9.0 8.5 8.2 7.9 7.6 7.1 6.8 6.5 6.0
16 21 17 15 14 13 12 12 11 11 11 10 10 9 8
22 28 23 20 19 17 16 16 15 14 14 13 13 12 11
30 38 31 27 25 23 22 21 20 19 19 18 17 16 15
38 48 39 34 32 29 28 26 25 24 24 22 21 20 19
54 67 54 47 44 41 39 37 35 34 33 31 29 28 26
71 89 72 63 58 54 51 49 47 45 43 41 39 37 34
94 119 96 84 78 72 68 65 62 60 58 54 52 49 46
116 147 118 103 96 89 84 80 77 74 71 67 64 61 56
146 184 148 129 120 111 105 100 96 92 89 83 80 76 70
183 234 188 164 153 141 134 127 122 117 113 106 101 96 89
215 275 220 193 179 165 157 149 143 138 132 124 119 113 105
248 338 271 237 220 203 193 183 176 169 163 153 146 139 129
Continuous current ratingconductor temperature 120 °C, ambient temperature 30°C