wiring diagramsdms.hvacpartners.com/docs/1005/public/0a/48hj-3w.pdfmotormaster iv control wiring...
TRANSCRIPT
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 111 Catalog No. 534-80109 Printed in U.S.A. Form 48HJ-3W Pg 1 1-03 Replaces: 48/50HJ-7W,
48/50HJ-8WBook 1 4Tab 1a 6a
Wiring Diagrams
*Low NOx/California Compliant Units.†Applies to Low NOx Units.
*Durablade Economizer was a factory-installed option (FIOP) until 2/15/02, it is currently available only as a field-installed accessory.†EconoMi$er wiring in Fig. 18 is generic (for units produced from 5/99-2/02) with the exception of the way the power exhaust switch is wired.
Refer to Fig. 21 and 22 for more detailed power exhaust switch information.
UNIT WIRING DIAGRAMSUnit Volt-Ph-Hz Type From Label Fig. No.
48HJD/E/F004,005208/230-3-60 Schematic/Component Arrangement 50HJ501028 1
460-3-60 Schematic/Component Arrangement 50HJ501029 2
48HJG/H/K/L/M/N004,005*208/230-3-60 Schematic/Component Arrangement 50HJ501028 1
460-3-60 Schematic/Component Arrangement 50HJ501029 248HJE/F/R/T004,005 and 48HJS005 575-3-60 Schematic/Component Arrangement 50HJ501030 3
48HJD/E/F/L/M/N/R/S/T004-006† 208/230-1-60 Schematic/Component Arrangement 50HJ501027 4
48HJG/H/K/L/M/N006*208/230-3-60 Schematic/Component Arrangement 50HJ501031 5
460-3-60 Schematic/Component Arrangement 50HJ501029 2
48HJD/E/F/R/S/T006,007208/230-3-60 Schematic/Component Arrangement 50HJ501031 5
460-3-60 Schematic/Component Arrangement 50HJ501032 6575-3-60 Schematic/Component Arrangement 50HJ501033 7
48HJD/E/F/R/S/T008-014208/230-3-60 Schematic/Component Arrangement 50HJ501296 8
460-3-60 Schematic/Component Arrangement 50HJ501297 9575-3-60 Schematic/Component Arrangement 50HJ501298 10
OPTION AND ACCESSORY WIRINGDescription 48HJ Unit Size Fig. No. Serial NumberApollo Controls Wiring Including Indoor Air Quality 004-014 11 From 2492Gxxxxx
Apollo Thermostat Wiring — Typical004-007 12
From 0395Gxxxxx008-014 13
Convenience Outlet Schematic 004-014 14 From 0798GxxxxxDurablade Economizer Wiring 004-014 15 From 3295Gxxxxx*
Differential Enthalpy Control (Durablade) 004-014 16 From 3295Gxxxxx*Solid-State Enthalpy Control (Durablade) 004-014 17 From 3295Gxxxxx*
EconoMi$er Wiring 004-014 18 2099Gxxxxx-0702Gxxxxx†EconoMi$er Dry Bulb Sensor Wiring 004-014 19 2099Gxxxxx-0702GxxxxxEconoMi$er Enthalpy Sensor Wiring 004-014 20 2099Gxxxxx-0702GxxxxxEconoMi$er Power Exhaust Wiring with the Switch in the Actuator 004-014 21 2099Gxxxxx-4501GxxxxxEconoMi$er Power Exhaust Wiring with the Switch Outside the Actuator 004-014 22 4501Gxxxxx-0702Gxxxxx
EconoMi$er2 Wiring 004-014 23 From 0802GxxxxxDifferential Enthalpy Wiring (EconoMi$er2) 004-014 24 From 0802GxxxxxFire and Smoke Control Wiring (EconoMi$er2) 004-014 25 From 0802GxxxxxIndoor Air Quality Sensor Wiring (EconoMi$er2) 004-014 26 From 0802GxxxxxPower Exhaust, 208/230, 575 V Units (EconoMi$er2) 004-014 27 From 0802GxxxxxPower Exhaust for 460 V Units (EconoMi$er2) 004-014 28 From 0802GxxxxxEconoMi$er2 with PremierLink™ or 4-20 mA Control 004-014 29 From 0802Gxxxxx
Factory-Installed Non-fused Disconnect 004-014 30 From 0395Gxxxxx
MoistureMi$er™ Dehumidification Package Humidistat Wiring (Typical) 004-007 31 From 1296Gxxxxx008-014 32 From 1296Gxxxxx
Motormaster® I Control Wiring Details 004-014 33
Motormaster II Control Wiring Schematic004-007 34008-014 35
Motormaster IV Control Wiring Schematic004-007 36008-014 37
Novar Controls Wiring (EMT3051) 004-014 38 From 2900GxxxxxNovar Controls Wiring (EMT2024) 004-014 39 From 2900GxxxxxPremierLink Controls Wiring 004-014 40 From 4601GxxxxxPremierLink Controls Wiring with Dual Terminal Block 004-014 41 From 4002GxxxxxPremierLink Controls with Dual Terminal Block and 62AQ 004-014 42 From 2102GxxxxxSmoke Detector Shutdown — Single-Phase 004-014 43 From 0802GxxxxxSmoke Detector Shutdown — Three-Phase 004-014 44 From 0802GxxxxxTime Guard II Device 004-014 45Two-Position Damper Wiring 004-014 4662AQ Energy Recycler
Factory-Installed 62AQ Energy$Recycler Wiring — COBRA™ Energy Recovery Units008-012 47
From 4902Gxxxxx014 48
Typical COBRA Energy Recycler Wiring with PremierLink Controls 004-014 49 004-007 Units: From 4502Gxxxxx008-014 Units: From 4902GxxxxxTypical COBRA Energy Recycler Wiring with Standard Controls 004-014 50
Field-Installed 62AQ Energy$Recycler Accessory Wiring (Typical) 004-014 51
48HJ004-014Single Package Rooftop
Gas Heating/Electric Cooling Units
2
OPERATING SEQUENCE
Unit Produced Before 2/18/02COOLING, UNITS WITHOUT ECONOMIZER — Whenthermostat calls for cooling, terminals G and Y1 are energized.The indoor (evaporator) fan contactor (IFC), OFC (outdoor-fancontactor), and compressor contactor no. 1 (C1) are energized.Indoor (evaporator) fan motor (IFM), compressor no. 1, andcondenser fans start. The outdoor (condenser) fan motors(OFMs) run continuously while unit is cooling. For units with2 stages of cooling, if the thermostat calls for a second stage ofcooling by energizing Y2, compressor contactor no. 2 (C2) isenergized and compressor no. 2 starts.
When the thermostat is satisfied, C1 and C2 are deenergizedand the compressors and OFMs shut off. After a 30-second de-lay, the IFM shuts off. If the thermostat fan selector switch is inthe ON position, the evaporator motor will run continuously.COOLING, UNITS WITH DURABLADE ECONO-MIZER — When the outdoor-air temperature is above theoutdoor-air thermostat (OAT) setting and the room thermostatcalls for cooling, the compressor contactor no. 1 is energized tostart compressor no. 1 and outdoor (condenser) fan motors(OFMs). The indoor (evaporator) fan motor (IFM) is energizedand the economizer damper moves to the minimum position.Upon a further call for cooling, compressor contactor no. 2 willbe energized, starting compressor no. 2. After the thermostat issatisfied and the IFM is deenergized, the damper moves to thefully closed position.
When the outdoor-air temperature is below the OAT settingand the thermostat calls for Y1 and G, the economizer dampermoves to the minimum position when the evaporator fan starts.The first stage of cooling is provided by the economizer. If thesupply-air temperature is above 57 F (14 C), a switch on thesupply-air thermostat is closed between the T2 terminal and the24 vac terminal. This causes the damper to continue to modu-late open until the supply-air temperature falls below 55 F(13 C) or the damper reaches the fully open position.
When the supply-air temperature is between 55 F and 52 F(13 C and 11 C), the supply-air thermostat has open switchesbetween the T2 and 24 vac terminals and between the T1 and24 vac terminals. This causes the economizer damper to remainin an intermediate open position.
If the supply-air temperature falls below 52 F (11 C), aswitch on the supply-air thermostat is closed between the T1terminal and the 24 vac terminal. This causes the damper tomodulate closed until the supply-air temperature rises above55 F (13 C) or the damper reaches the minimum position.
When the supply-air temperature is between 55 F and 57 F(13 C and 14 C), the supply-air thermostat has open switchesbetween the T2 and 24 vac terminals. This causes the econo-mizer damper to remain in an intermediate open position.
If the outdoor air alone cannot satisfy the cooling require-ments of the conditioned space, economizer cooling is integrat-ed with mechanical cooling, providing second-stage cooling.Compressor no. 1 and condenser fans will be energized, andthe position of the economizer damper will be determined bythe supply-air temperature. Compressor no. 2 is locked out.
When the second stage of cooling is satisfied, the compres-sor and OFMs will be deenergized. The damper position willbe determined by the supply-air temperature.
When the first stage of cooling is satisfied, the IFM shuts offafter a 30-second delay. The damper then moves to fully closedposition.COOLING, UNITS WITH ECONOMI$ER — When theoutdoor-air temperature (OAT) is above the ECON SP set pointand the room thermostat calls for Stage 1 cooling (R to G +Y1), the indoor (evaporator) fan motor (IFM) is energized andthe EconoMi$er damper modulates to minimum position. The
compressor contactor is energized to start the compressor andoutdoor (condenser) fan motor (OFM). After the thermostat issatisfied, the damper modulates to the fully closed positionwhen the IFM is deenergized.
When the OAT is below the ECON SP setting and the roomthermostat calls for Stage 1 cooling (R to G + Y1), theEconoMi$er modulates to the minimum position when theIFM is energized. The EconoMi$er provides Stage 1 of coolingby modulating the return and outdoor air dampers to maintain a55 F supply air set point. If the supply-air temperature (SAT) isgreater than 57 F, the EconoMi$er modulates open, allowing agreater amount of outdoor air to enter the unit. If the SAT dropsbelow 53 F, the outdoor air damper modulates closed to reducethe amount of outdoor air. When the SAT is between 53 and57 F, the EconoMi$er maintains its position.
If outdoor air alone cannot satisfy the cooling requirementsof the conditioned space, and the OAT is above the MECHCLG LOCKOUT set point, the EconoMi$er integrates freecooling with mechanical cooling. This is accomplished by thestrategies below.NOTE: Compressor has a 2-minute Minimum On, MinimumOff, and Interstage delay timer.
1. If Y1 is energized, and the room thermostat calls for Y2(2-stage thermostat), compressor no. 1 and OFM areenergized. The EconoMi$er damper is maintained at itscurrent position.
2. If Y1 is energized for more than 20 minutes, and Y2 isnot energized (whether or not a 2-stage thermostat isused), compressor no. 1 and OFM are energized. TheEconoMi$er damper is maintained at its current position.
3. If Y1 is energized, and compressor no. 1 is already ener-gized (see Step 2) and the room thermostat calls for Y2,the compressor contains to operate. If Y2 remainsenergized for more than 20 minutes, compressor no. 2 isenergized.
NOTE: Compressor no. 2 cannot be energized unless there is asignal for Y2 from the space thermostat.
4. If compressor no. 2 is energized, and the Y2 signal fromthe thermostat is satisfied, compressors 1 and 2 are deen-ergized. Reasserting Y2 will start compressor no. 1 and(after a 20-minute interstage delay) compressor no. 2.
5. If compressor no. 1 is energized and the thermostat is sat-isfied, compressor no. 1, the OFM, and IFM are deener-gized and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT setpoint, the compressors remain off.HEATING, UNITS WITHOUT ECONOMIZER — Whenthe thermostat calls for heating, terminal W1 is energized. Inorder to prevent thermostat short-cycling, the unit is lockedinto the Heating mode for at least 1 minute when W1 is ener-gized. The induced-draft motor (IDM) is then energized andthe burner ignition sequence begins. The IFM is energized45 seconds after a flame is ignited. When additional heat isneeded, W2 is energized and the high-fire solenoid on the maingas valve (MGV) is energized. When the thermostat is satisfiedand W1 and W2 are deenergized, the IFM stops after a45-second time-off delay.HEATING, UNITS WITH ECONOMIZER/TWO-POSITION DAMPER — When the thermostat calls for heat-ing, terminal W1 is energized. In order to prevent thermostatshort-cycling, the unit is locked into the Heating mode for atleast 1 minute when W1 is energized. The induced-draft motoris then energized and the burner ignition sequence begins. TheIFM is energized 45 seconds after a flame is ignited and thedamper moves to the minimum position. If the two-positiondamper is used, the outdoor-air damper opens to the minimumposition whenever the evaporator fan runs. When additionalheat is needed, W2 is energized and the high-fire solenoid on
3
the main gas valve (MGV) is energized. When the thermostatis satisfied and W1 and W2 are deenergized, the IFM stops af-ter a 45-second time-off delay. The economizer damper thenmoves to the fully-closed position. When using continuous fan,the damper will remain in the minimum position.
Units Produced After 2/17/02COOLING UNITS WITHOUT ECONOMI$ER2 — Whenthermostat calls for cooling, terminal G and Y1 are energized.The indoor-fan contactor (IFC), compressor contactor no. 1(C1) and outdoor-fan contactor (OFC) are energized.Evaporator-fan motor, compressor no. 1, and both condenserfans start. The outdoor-fan motor(s) run continuously whileunit is cooling.
When the thermostat is satisfied, C1 and C2 are deenergizedand the compressors and outdoor (condenser) fan motors(OFM) shut off. After a 30-second delay, the indoor (evapora-tor) fan motor (IFM) shuts off. If the thermostat fan selectorswitch is in the ON position, the evaporator-fan motor will runcontinuously.HEATING UNITS WITHOUT ECONOMI$ER2 — Whenthe thermostat calls for heating, terminal W1 is energized. Inorder to prevent thermostat short-cycling, the unit is lockedinto the Heating mode for at least 1 minute when W1 is ener-gized. The induced-draft motor (IDM) is then energized andthe burner ignition sequence begins. The indoor (evaporator)fan motor (IFM) is energized 45 seconds after a flame isignited. On units equipped for two stages of heat, whenadditional heat is needed, W2 is energized and the high-firesolenoid on the main gas valve (MGV) is energized. When thethermostat is satisfied and W1 and W2 are deenergized, theIFM stops after a 45-second time-off delay.COOLING UNITS WITH ECONOMI$ER2 — When freecooling is not available, the compressors will be controlledby the zone thermostat. When free cooling is available, theoutdoor-air damper is positioned through the use of aProportional-Integral (PI) control process to provide a 55 Fsupply-air temperature into the zone. If the mixed-air tempera-ture is below the lower end of the set point of 50 F, then theoutside-air dampers will modulate to minimum position. If themeasured temperature is within the 50 to 56 F range, then theoutside dampers will hold their current position. If the mixed-air temperature is above 56 F, then the outside-air dampers willmodulate open until the temperature is within range or theymodulate to the fully open position.
If outdoor air alone cannot satisfy the cooling requirementsof the conditioned space, and the OAT is above the outdoor airmechanical lockout temperature set point (fixed; opens at 35 F,closes at 50 F), the EconoMi$er2 integrates free cooling withmechanical cooling as follows:
Thermostat first stage call for cooling (Y1) usesEconoMi$er2 damper for free cooling.Thermostat second stage call for cooling uses EconoMi$er2damper for free cooling, plus compressor no. 1 for mechan-ical cooling.
NOTE: During EconoMi$er2 operation (damper aboveminimum position) compressor no. 2 will not operate (sizes008-014).
The high ambient temperature (dry bulb) lockout (fixed):opens at 76 F, closes at 52 F.
If the enthalpy of the outside air is too high, the outside airdampers will modulate to minimum position.
If mechanical cooling is used with free cooling, the outdoor-air damper will be locked into its current position when thecompressor starts. If the increase in cooling capacity causes thesupply-air temperature to drop below 45 F, then the outdoor-airdamper position will be decreased to the minimum position. Ifthe supply temperature continues to fall, the outdoor-air damp-er will close.
If optional power exhaust is installed, as the outdoor-airdamper opens and closes, the power exhaust fans will be ener-gized and deenergized.
If field-installed accessory CO2 sensors are connected to theEconoMi$er2 control, a PI-controlled demand ventilation strat-egy will begin to operate. As the CO2 level in the zone increas-es above the CO2 set point, the minimum position of the damp-er will be increased proportionally. As the CO2 level decreasesbecause of the increase in fresh air, the outdoor-air damper willbe proportionally closed.HEATING UNITS WITH ECONOMI$ER2 — When the roomtemperature calls for heating, terminal W1 is energized. To pre-vent thermostat short-cycling, the unit is locked into the Heatingmode for at least 1 minute when W1 is energized. The induced-draft motor is energized and the burner ignition sequence begins.The indoor (evaporator) fan motor (IFM) is energized 45 sec-onds after a flame is ignited and the damper moves to the mini-mum position. On units equipped for two stages of heat, whenadditional heat is needed, W2 is energized and the high-fire sole-noid on the main gas valve (MGV) is energized. When the ther-mostat is satisfied and W1 is deenergized, the IFM stops after a45-second time-off delay. The economizer damper then movesto the fully closed position. When using continuous fan, thedamper will remain in the minimum position.UNITS WITH MOISTUREMI$ER™ DEHUMIDIFICA-TION PACKAGE — When thermostat calls for cooling,terminals G and Y1 are energized. The indoor (evaporator) fanmotor (IFM), compressor (C), and outdoor (condenser) fanmotor (OFM) start. The OFM runs continuously while the unitis in cooling. As shipped from the factory, MoistureMi$erdehumidification circuit is always energized. If MoistureMi$ercircuit modulation is desired, a field-installed, wall-mountedLC Humidistat or humidistat are required.
If the MoistureMi$er humidistat is installed and calls for theMoistureMiser subcooler coil to operate, the humidistatinternal switch closes. This energizes and closes the liquid linesolenoid valve coil (LLSV) of the MoistureMi$er circuit,forcing the hot liquid refrigerant of the liquid line to enter thesubcooler coil. As the hot liquid passes through the subcoolercoil, it is exposed to the cold supply airflow coming off fromthe evaporator coil and the liquid is further cooled to a temper-ature approaching the evaporator coil leaving-air temperature.The state of the refrigerant leaving the subcooler coil is ahighly subcooled liquid refrigerant. The liquid then enters athermostatic expansion valve (TXV) where the liquid isdropped to a lower pressure. The TXV does not have apressure drop great enough to change the liquid to a 2-phasefluid. The TXV can throttle the pressure drop of the liquidrefrigerant and maintain proper conditions at the compressorsuction valve over a wide range of operating conditions. Theliquid then enters a second fixed restrictor expansion device fora second pressure drop to a 2-phase fluid. The liquid proceedsto the evaporator coil at a temperature lower than normal cool-ing operation. This lower temperature is what increases thelatent capacity of the rooftop. The 2-phase refrigerant passesthrough the evaporator and is changed into a vapor. The airpassing over the evaporator coil will become colder thanduring normal operation as a result of the colder refrigeranttemperatures. However, as it passes over the subcooler coil, theair will be warmed slightly.
As the refrigerant leaves the evaporator, the refrigerantpasses a low-pressure switch in the suction line. This low-pressure switch will de-activate the MoistureMi$er packagewhen the suction pressure reaches 60 psig. The low-pressureswitch is an added safety device to protect against evaporatorcoil freeze-up. The low-pressure switch will only de-activateand open the liquid line solenoid valve in the MoistureMi$ercircuit. The compressors will continue to run as long as there isa call for cooling, regardless of the position of the low-pressureswitch. The solenoid valve and the MoistureMi$er package
4
will be re-activated only when the call for cooling has beensatisfied, the low-pressure switch has closed, and a new call forcooling exists. The crankcase heaters on the scroll compressorprovide additional protection for the compressor due to theadditional refrigerant charge in the subcooler.
When the humidistat is satisfied, the humidistat internalswitch opens cutting power to and opening the LLSV. The
refrigerant is routed back through the evaporator and the sub-cooler coil is removed from the refrigerant loop.
When the thermostat is satisfied, C1 is deenergized and thecompressor and OFM shut off. After a 30-second delay, theIFM shuts off. If the thermostat fan selector switch is in the ONposition, the IFM will run continuously.
LEGEND
NOTES FOR FIG. 11. If any of the original wire furnished must be replaced, it must be replaced
with type 90° C wire or its equivalent.2. Three-phase motors are protected under primary single phasing
conditions.3. Thermostat: HH07AT170, 172 Subbase: HH93AZ176, 177, 178, and
179.
4. Set heat anticipator at .14 amp for 1st stage and .14 amp for 2nd stage.5. Use copper conductors only.6. TRAN is wired for 230-v unit. If unit is to be run with 208-v power supply
disconnect BLK wire from 230-v tap (ORN) and connect to 208-v tap(RED). Insulate end of 230-v tap.
NOTES FOR FIG. 2, 3, 6 ,71. If any of the original wire furnished must be replaced, it must be replaced
with type 90° C wire or its equivalent.2. Three-phase motors are protected under primary single phasing
conditions.
3. Thermostat: HH07AT170, 172 Subbase: HH93AZ176, 177, 178, and179.
4. Set heat anticipator at .14 amp for 1st stage and .14 amp for 2nd stage.5. Use copper conductors only.
NOTES FOR FIG. 5, 8-101. If any of the original wire furnished must be replaced, it must be replaced
with type 90° C wire or its equivalent.2. Three-phase motors are protected under primary single phasing
conditions.3. Thermostat: HH07AT170, 172, 174 and P272-2783 Subbase:
HH93AZ176, 178 and P272-1882, 1883.
4. Set heat anticipator for first stage at 0.14 amp, second stage at 0.2 amp.For 48HJ008 and 009 low heat, set both first and second stage at0.14 amp.
5. Use copper conductors only.6. TRAN is wired for 230-v unit. If unit is to run with 208 v power supply,
disconnect BLK wire from 230-v tap (ORN) and connect to 200-v tap(RED). Insulate end of 230-v tap.
NOTES FOR FIG. 41. If any of the original wire furnished must be replaced, it must be replaced
with type 90° C wire or its equivalent.2. Thermostat: HH07AT170, 172 Subbase: HH93AZ176, 177, 178, and
179.3. Set heat anticipator at .14 amp for 1st stage and .14 amp for 2nd stage.
4. Use copper conductors only.5. TRAN is wired for 230-v unit. If unit is to be run with 208-v power supply
disconnect BLK wire from 230-v tap (ORN) and connect to 208-v tap(RED). Insulate end of 230-v tap.
AHA — Adjustable Heat AnticipatorAWG — American Wire GageC — Contactor, CompressorCAP — CapacitorCB — Circuit BreakerCC — Cooling CompensatorCER — Compressor Energy Recycler RelayCH,CCH — Crankcase HeaterCLO — Compressor LockoutCO2 — Carbon DioxideCOC — Cool Changeover RelayCOH — Heat Changeover RelayCOM — CommonCOMMS — CommunicationsCOMP — Compressor MotorCR — Cooling Relay, Compressor RelayCTD — Compressor Time DelayD — DiodeDAT — Discharge Air ThermistorDB — Defrost BoardDDC — Direct Digital ControlsDFT — Defrost ThermostatDM — Damper MotorDX — Direct Expansion Coil SensorEC — Enthalpy ControlECON — EconomizerEFC — Exhaust Fan ContactorEPS — Emergency Power Supply
(Nine Volt Battery)EQUIP — EquipmentER — Economizer RelayFC — Supply Air ContactorFPT — Freeze Protection ThermostatFR — Fan RelayFSS — Filter Status SwitchFU — FuseGND — GroundHM — Humidity RelayHPS — High-Pressure SwitchHR — Heater Relay
HS — Hall Effect SensorHT — HeatHU — HumidistatHV — High-VoltageI — IgnitorIAQ — Indoor Air QualityIDM — Induced-Draft MotorIFC — Indoor-Fan ContactorIFM — Indoor-Fan MotorIFMOVL — Indoor-Fan Motor Overload SwitchIFR — Indoor-Fan RelayIGC — Integrated Gas Unit ControllerLED — Light-Emitting DiodeLLSV — Liquid Line Solenoid ValveLPS — Low-Pressure SwitchLS — Limit SwitchLTLO — Low Temp Cooling LockoutMGV — Main Gas ValveMTR — MotorNC — Normally ClosedNO — Normally OpenOAT — Outdoor-Air ThermostatOATC — Outdoor Air Thermostat (Cool)OATH — Outdoor Air Thermostat (Heat)OCR — Occupied RelayOFC — Outdoor-Fan ContactorOFM — Outdoor-Fan MotorOLR — Overload RelayP — PlugPL — Plug AssemblyPWR — PowerQT — Quadruple TerminalR — RelayRS — Rollout SwitchRV — Reversing ValveRVS — Reversing Valve SolenoidSAT — Supply-Air Thermostat,
Standard Air TemperatureSEN — Sensor
SW1 — Switch Fully OpenSW2 — Switch Fully ClosedSW3 — Switch Minimum Vent PositionSW4 — Switch Maximum Vent PositionS-LPS — Low-Pressure Switch (Subcooler Only)TB — Terminal BlockTC — Thermostat-CoolingTDR — Time-Delay RelayTEMP — Temperature Volume and TemperatureTH — Thermostat-HeatingTRAN — TransformerVTS — Carrier Temp SystemVVT — Variable Volume and Temperature
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice Marked
Motormaster IV Controller (32LH900003 Pressure Switch)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only;not to represent wiring.
5
Fig. 1 — Schematic/Component Arrangement, 48HJD/E/F/G/H/K/L/M004,005;208/230-3-60
See Legend on page 4.
6
Fig. 2 — Schematic/Component Arrangement, 48HJD/E/F/G/H/K/L/M/N004-005, 48HJG/H/K/L/M/N006;460-3-60
See Legend on page 4.
7
Fig. 3 — Schematic/Component Arrangement, 48HJE/F/R/T004-005, 48HJS005;575-3-60
See Legend on page 4.
8
Fig. 4 — Schematic/Component Arrangement, 48HJD/E/F/L/M/N/R/S/T004-006;208/230-1-60
See Legend on page 4.
9
Fig. 5 — Schematic/Component Arrangement, 48HJG/H/L006, 48HJD/E/F/K/M/N/R/S/T006-007;208/230-3-60
See Legend on page 4.
10
Fig. 6 — Schematic/Component Arrangement, 48HJD/E/F/R/S/T006-007;460-3-60
See Legend on page 4.
11
Fig. 7 — Schematic/Component Arrangement, 48HJD/E/F/R/S/T006-007;575-3-60
See Legend on page 4.
12
Fig. 8 — Schematic/Component Arrangement, 48HJD/E/F/R/S/T008-014;208/230-3-60
208/230-3-60 SCHEMATIC
See legend on page 3.
See Legend on page 4.
13
460-3-60 SCHEMATIC
Fig. 9 — Schematic/Component Arrangement, 48HJD/E/F/R/S/T008-014;460-3-60
See Legend on page 4.
14
575-3-60 SCHEMATIC
Fig. 10 — Schematic/Component Arrangement, 48HJD/E/F/R/S/T008-014;575-3-60
See Legend on page 4.
15
GR
OU
ND
TR
AN
24 V
AC
20 V
A(F
IELD
SU
PP
LIE
D)
24 V
H G
24
VA
CO
R+
- 2
4 V
DC
2 1
8 7
6 5
4 3
2 1
+ +-2-
10V
DC
SIG
CO
M (
J5-3
)4-
20m
A (
J5-2
)
NC
CO
MN
O
ALA
RM
RE
LAY
CO
NTA
CT
S
TAN
VIO
WH
TR
ED
OA
T
VIO
PN
KD
AT
EC
AC
CE
SS
OR
YO
NLY
OA
TC
OM
OA
H+
15V
RA
TC
OM
RA
H+
15V
CO
2+
CO
2 C
OM
DA
TC
OM
RE
M P
OT
CO
M
LED
CO
M
CO
NT
RO
LLE
R
B1 Y1
Y2
G CO
MA
O
24 V
AC
24 C
OM
GN
D
CLG
1
CLG
2
EC
ON
OM
I$E
R O
PT
ION
/AC
CE
SS
OR
Y
RE
D
BLU
PN
K
BR
NG
RN
DM
YE
L
WH
TB
LK
FAN
HE
AT
2H
EA
T 1
NC
HE
AT
1H
EA
T/F
AN
CO
MC
OO
L 2
CO
OL
1C
OO
L C
OM
R C GR
OU
ND
24 V
AC
/10
VA
AU
XIL
IAR
YR
ELA
Y**
TO
CA
RR
IER
HV
AC
UN
ITF
IELD
SU
PP
LIE
DW
IRIN
G
13 12 11 10 9 8 7 6 5 4 3 2 1S
ING
LE Z
ON
ER
ELA
Y P
AC
KW
ITH
AU
XIL
AR
YR
ELA
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
SIN
GLE
ZO
NE
RE
LAY
PA
CK
CIR
CU
IT B
OA
RD
OA
TS
AT
DX
FAN
STA
TU
S
IAQ
STA
TU
S†W
HT
RE
DB
LUY
EL
GR
N
WH
TR
ED
GR
NB
LK
GR
NB
LK
FIL
TE
RS
TAT
US
HU
MID
ITY
SE
NS
OR
TS
P01
TE
RM
INA
LN
UM
BE
R#1 #2 #1
0#1
1
#10
#11
AD
DIT
ION
AL
SE
NS
OR
S*BLK
RE
D
RE
MO
TE
RO
OM
TE
MP.
SE
NS
OR
NE
TW
OR
KB
LKR
ED
GR
N
IND
OO
R A
IR Q
UA
LIT
Y (
CO
) S
EN
SO
R(3
3ZC
SE
NC
O2)
TY
PIC
AL
WIR
ING
DIA
GR
AM
2
12
34
FAN
RV
CO
OL
HE
AT
FIE
LD-
INS
TALL
ED
JUM
PE
RS
††
*Filt
er s
tatu
s sw
itch
and
hum
idity
sen
sor
cann
ot f
unct
ion
sim
ulta
-ne
ousl
y. O
nly
one
sens
or c
an b
e w
ired.
†Suc
h as
a C
O2
sens
or.
**S
et a
uxili
ary
optio
n to
“2”
— I
AQ
Con
trol
per
VT
S o
r V
VT
Ins
talla
tion
Inst
ruct
ions
.††
Fie
ld-in
stal
led
Jum
pers
bet
wee
n 3,
4 an
d 5,
7.N
OT
E:
Whe
n si
ngle
zon
e re
lay
pack
is
used
on
a V
VT
Mon
itor
Onl
yS
yste
m, t
he m
onito
r th
erm
osta
t can
not c
ontr
ol a
dam
per.
Fig
. 11
— A
po
llo C
on
tro
ls W
irin
g —
Incl
ud
ing
Ind
oo
r-A
ir Q
ual
ity
See
Leg
end
on p
age
4.
16
Fig. 12 — Apollo Thermostat Wiring — 48HJ004-007 (Typical)
Fig. 13 — Apollo Thermostat Wiring — 48HJ008-014 (Typical)
See Legend on page 4.
See Legend on page 4.
17
Fig. 14 — Convenience Outlet Schematic
Fig. 15 — Durablade Economizer Schematic
See Legend on page 4.
See Legend on page 4.
18
620 ohmJUMPER
}24 VAC SUPPLY FROMECONOMIZER CONTROLSECTION (RED TO TR,BRN TO TR1)TO SENSOR MOUNTEDON BACK OF CONTROL
}
GRAY WIRE FROMECONOMIZER HARNESS
RED WIRE FROMECONOMIZER SWITCH 3(NORMALLY CLOSED)
TR TR1
SO +
+SR
2 3
1
LED
AB
CD
LED
AB C
D
TR TR1
SO
SR
23
1
+
+ S+
(HH57AC078SENSOR)
24 VAC SUPPLY FROMECONOMIZER CONTROLSECTION (RED TO TR,BRN TO TR1)
TO SENSOR MOUNTEDON BACK OF CONTROL
GRAY WIRE FROMECONOMIZER HARNESS
RED WIRE FROMECONOMIZER SWITCH 3(NORMALLY CLOSED)
See Legend on page 4.NOTE: Switches shown in high enthalpy state. Terminals 2and 3 close on enthalpy decrease.
Fig. 17 — Solid-State Enthalpy Control(Durablade Economizer)
*Wiring is generic for all EconoMi$ers with the exception of the actuator. Refer to Fig. 21 and 22 for specific actuator production dates.
Fig. 18 — EconoMi$er Wiring for Units Produced 5/16/1999 through 2/15/2001*
See Legend on page 4.NOTES:
1. Remove factory-installed jumper across SR and +before connecting wires from HH57AC078 sensor.
2. Switches shown in high outdoor-air enthalpy state.Terminals 2 and 3 close on low outdoor-air enthalpyrelative to indoor air enthalpy.
Fig. 16 — Differential Enthalpy Control(Durablade Economizer)
See Legend on page 4.
19
OUTDOORAIRSENSOR
TEMPTEMP
COMOUTPWR
BROWN
VIOLET
WHITERED
BROWNTEMPTEMPCOMOUTPWR
RETURNAIRSENSOR
VIOLETWHITE
RED
OAT
COM
OAH
+15 V
RAT
COM
RAH
+15 V
ECONOMI$ERCONTROLLER
PINK TEMP
TEMPVIOLET
SUPPLY AIRTEMPERATURE SENSOR
V+ 24
COM VAC
SENSORCO2
(+)COMDAT
COMREM POT
COMLED
COM
CO2
CO2
Fig. 19 — EconoMi$er Dry Bulb Sensor Wiring
Fig. 20 — Wiring Diagram for Field-Installed Enthalpy Sensors
See Legend on page 4.
See Legend on page 4.
20
4-PINCONNECTOR
PLUG
L1
L2
GREEN
112 2
3 34 4
GND
230 VAC1 PHASE
GREEN/YELLOW
3
2
1
5 8
6 9 B
A74
LT. BLUE
BLACKBROWN
C1
BLUE
GREEN/YELLOW
3
2
1
5 8
6 9 B
A74
LT. BLUE
BLACKBROWN
C1
BLUE
FAN 2
FAN 1
BLACK
BLACK
BLACK
R124 VAC
R224 VAC
BLACK
BLUE
1
2
3BROWN
ORANGE
3-PINCONNECTOR
PLUG
YELLOW
RED YEL
H1
BLU GRAY
H4
SECONDARY230VAC
X4 X1
HT
01
AH
85
0(4
60
VA
C)
RED
H1
GRAY
H2
SECONDARY230VAC
X4 X1
HT
01
AH
85
9(5
75
VA
C)
2313
11 21230VAC
OR
BLACK L1
BLUE L2
COMPRESSOR 1CONTACTOR
FIELD SUPPLIEDWIRING
GREEN GND
2 x 4 IN.HANDY BOX
X3X2
H2H3
X2 X3
TO FUSEDDISCONNECT
TOPSWITCH
BOTTOMSWITCH
RED
RED
ORANGE
YELLOW
BROWN1 COM
CONNECTS TO2-PIN CONNECTORIN ECONOMIZER
CONNECTS TO THE3-PIN CONNECTORPLUG ON POWER EXHAUST
3
1COM
NCNO
COM
NCNO
22
+24 VAC
TOP SWITCHCAM POSITION
INDICATOR
BOTTOMSWITCH
TOPSWITCHWIRE TIE
ANCHOR HOLE
Fig. 21 — EconoMi$er Power Exhaust with the Switch Inside the Actuator(Units Produced 5/16/1999 - 11/5/2001)
Fig. 22 — EconoMi$er Power Exhaust with Switch Outside of Actuator(Units Produced 11/5/2001 - 2/15/2002)
See Legend on page 4.
See Legend on page 4.
21
+ +
+
+
+
- -
-
2-10VOUT
RED
RUN
BLACK
WHITE
24 VAC HOT
TR
BLACKBROWN
BROWN
BLACK
BLACK
GRAY
BLUE
YELLOW
VIOLETVIOLET
VIOLET
PINKPINK
RED
WHITE
WHITE
BROWN
ORANGE
620 OHMRESISTOR
820 OHMRESISTORSO
NOTE 8
5
1
3
1K1S
1S1
2K
2
4
T
P P1
Q Q1
AQ
SD1SD
AC AC1
PG PG1
ECONOMIZERDRY BULBSENSOR
Compressor Lockout N.C.
YELLOW
GRAY
BLUE
TAN
INDOORFAN
EXHAUSTFAN
UNITCONTROL
FREECOOL
MAXIMUMPOSITION
ADJUSTMENT 2-10 VDCCO2 SENSOR
HARNESSAND PLUG
MINIMUMPOSITION
ADJUSTMENT
AQ1
T1
SR
TR124 VAC COM
ACTUATOR
4
3
5
2
8
6
7
1
10
11
9
12}NOTE 9
NOTE 6
NOTE 1
NOTE 5
NOTE 7
NOTE 2
NOTE 4
NOTE 3
ECONOMISER2 CONTROLLER
NOTES:1. The standard EconoMi$er2 is shipped with a fixed dry bulb sensor. (Open 67 F — Close 52 F.) An adjustable dry bulb or enthalpy sensor can
replace the fixed dry bulb. (See Note 6.)2. CO2 sensor is optional. Field-installed accessory. See rooftop price pages for ordering data and pricing. Power for CO2 sensor should be pro-
vided by field-supplied transformer.3. The HVAC unit is shipped with a jumper plug attached to the EconoMi$er2 harness. Remove the jumper plug and save for future use if econ-
omizer is removed. Connect the male side of plug (shown above) to the female side in HVAC unit.4. 1S is an electronic switch that closes when powered by a 24 vac input.5. Factory-installed 620-ohm, 1 watt, 5% resistor should be removed only when a HH57AC078 enthalpy sensor or CROASENR001A00 adjust-
able dry bulb is added to SR and + for differential sensing.6. When replacing the fixed dry bulb sensor with an enthalpy or adjustable dry bulb, remove the 820-ohm resistor.7. Compressor lockout (Open 35 F — Close 50 F).8. See EconoMi$er2 Installation Instructions for details on locating and wiring supply air (mixed air) sensor.9. Switch on actuator must be in run position for economizer to operate.
10. A 2-stage thermostat is recommended.11. Before troubleshooting wiring, ensure that all the correct sensors have been installed (refer to EconoMi$er2 Installation Instructions).
Fig. 23 — EconoMi$er2 Wiring (For Units Produced 2/18/2002 - Present)
HH57AC078 DIFFERENTIALENTHALPY ORCROASENPOO1A00DIFFERENTIALADJUSTABLE DRY BULB
HH57AC078 ENTHALPY ORCROASENPOO1A00ADJUSTABLEDRY BULB
(NOTE 1)
(NOTE 2)
ECONOMISER2CONTROLLER
+
+
+
+
S
S
SO
TAN
TAN
VIOLET
VIOLET
SR
Fig. 24 — Differential Enthalpy Wiring for EconoMi$er2
See Legend on page 4.
See Legend on page 4.
NOTES:1. Violet wire from SO terminal has a factory-installed 820-ohm in-line
resistor. This resistor must be removed when replacing the standardfixed dry bulb with an optional enthalpy or adjustable dry bulb.
2. The standard economizer has a 620-ohm resistor between terminals SRand +. This resistor must be removed when adding differential enthalpyor differential adjustable dry bulb.
22
+ +
+
+
- -
2-10VOUT
RED
BLACK
WHITE
24 VAC HOT
TR
BLACKBROWN
BROWN
BLACK
BLACK
GRAY
BLUE
YELLOW
VIOLETVIOLET
VIOLET
PINKPINK
RED
WHITE
WHITE
BROWN
ORANGE
620 OHMRESISTOR
820 OHMRESISTORSO
5
1
3
1K1S
1S1
2K
2
4
T
P P1
Q Q1
AQ
SD1
SHUTDOWN
FIRE AND SMOKE CONTROL
AIR CHANGE
PURGE
SD
AC AC1
PG PG1
ECONOMISER2DRY BULBSENSOR
Compressor Lockout N.C.
YELLOW
GRAY
BLUE
TAN
INDOORFAN
EXHAUSTFAN
UNITCONTROL
FREECOOL
MAXIMUMPOSITION
ADJUSTMENT
HARNESSAND PLUG
MINIMUMPOSITION
ADJUSTMENT
AQ1
T1
SR
TR124 VAC COM
ECONOMISER2 CONTROLLERACTUATOR
4
3
5
2
8
6
7
1
10
11
9
12}
ECONOMISER2
Fig. 25 — Fire and Smoke Control Wiring for EconoMi$er2
Fig. 26 — Indoor Air Quality Sensor Wiring for EconoMi$er2
See Legend on page 4.
See Legend on page 4.
23
GREEN - YELLOW
GR
EE
N -
YE
LLO
W
GREEN
TAN TAN
TAN
WH
ITE
RE
DB
LAC
K
GRAY GRAY
GR
AY
BLA
CK
BLA
CK
BLACKBLACK EXH.FAN #1
EXH.FAN #2
GRD.
GRD.
BLU
E
BLU
E
BROWN BROWN
RELAY
TO HVAC UNITCONTROL BOX(SEE NOTE 4)
TO ECONOMISER2ACTUATOR
(SEE NOTE 2)
24 VACHOT
24 VACCOM
EXH FAN
+
3
1
2
3
A B
1 3
7 9
4 6
33
11
22
44
4
BLACK
REDEND
SWITCHPLUG
ECONOMISER2CONTROLLER(SEE NOTE 2)POWER LINE
PLUG
C1 C2
TRANSFORMERNO. HT01AH859
1
2
4
(SEENOTE 3)
575V
TO 575V POWER
PRIMARY
SECONDARY
220V
BLA
CK
RE
D
1
2
4
3
OR
FIELDSUPPLIED
FUSEDDISCONNECT
FIELD SUPPLIED2 x 4 JUNCTION BOX
GROUND
FOR 575-V POWER SUPPLY
FOR 208/230-V SEPARATEPOWER SUPPLY
NOTES:1. 575 V transformer No. HT01AH859 is ordered separately from power exhaust.2. EconoMi$er2 actuator and controller are shipped with the EconoMi$er2 — not with power exhaust.3. Connections from End Switch plug to the EconoMi$er2 controller are made by installer.4. If a single power source is to be used, size wire to include power exhaust MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the fol-lowing formula:MCA New = MCA unit only + MCA of Power ExhaustFor example, using a 48HJD006---5 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust.MCA New = 28.9 amps + 1.6 amps = 30.5 ampsIf the new MCA does not go over the MOCP published, then MOCP would not change. The MOCP in this example is 35 amps, the MCA Newis below 35, therefore the MOCP is OK. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separatepower, the MOCP for the power exhaust will be 15 amps per NEC.
Fig. 27 — EconoMi$er2 Power Exhaust Wiring — 208/230 V and 575 V Units
See Legend on page 4.
24
WHITE
GREEN-YELLOW
GRD
WH
ITE
BLA
CK
BLA
CK
WH
ITE
TAN
GRAY
+
GR
AY
GRAY
TAN
BLA
CK
RE
D
BLUEBLUE
RED
GREEN
AA BB
89
11 22 33
77
54 66
EXH.FAN #1
EXH.FAN #2
RELAY #1
3
1
2
3
1
2
4
33
11
22
44
4
BLACKBLACK
BR
OW
N
BR
OW
N
POWERLINEPLUG
RELAY #2
45
8
EXHFAN
ENDSWITCH
PLUG
24VHOT
24VCOM
OR
1
2
4
3
FIELD SUPPLIED2 x 4 JUNCTION BOX
GROUND
FIELDSUPPLIED
FUSEDDISCONNECT
SEPARATEPOWERSOURCE
GR
EE
N
RE
D
WH
ITE
BLA
CK
GRAYGRAY
9
GRAY
GRAY
RUN TO HVAC UNITCONTROL BOX.
(NOTE 3)
(NOTE 2)
ECONOMISER2CONTROLLER(NOTE 1)
TO ECONOMISER2ACTUATOR(NOTE 1)
NOTES:1. 575 V transformer No. HT01AH859 is ordered separately from power exhaust.2. EconoMi$er2 actuator and controller are shipped with the EconoMi$er2 — not with power exhaust.3. Connections from End Switch plug to the EconoMi$er2 controller are made by installer.4. If a single power source is to be used, size wire to include power exhaust MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the fol-lowing formula:MCA New = MCA unit only + MCA of Power ExhaustFor example, using a 48HJD006---5 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust.MCA New = 28.9 amps + 1.6 amps = 30.5 ampsIf the new MCA does not go over the MOCP published, then MOCP would not change. The MOCP in this example is 35 amps, the MCA Newis below 35, therefore the MOCP is OK. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separatepower, the MOCP for the power exhaust will be 15 amps per NEC.
Fig. 28 — EconoMi$er2 Power Exhaust Wiring — 460 V Units
See Legend on page 4.
25
4
3
5
2
8
6
7
1
10
11
9
12
PINK
VIOLET
BLACK
BLUE
YE
LLO
W
NOTE 1
NOTE 3
RUN
500 OHMRESISTOR
-+
OPTIONAL COSENSOR 4 - 20 mA
OUTPUT
50HJ540573ACTUATORASSEMBLY
RED
WHITE
ECONOMISER2 PLUG
DIRECT DRIVEACTUATOR
2
NOTES:1. Switch on actuator must be in run position for economizer to operate.2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen-
sor or HH57A077 enthalpy sensor.3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
Fig. 29 — EconoMi$er2 Wiring (With PremierLink™ or 4-20 mA Control)
Fig. 30 — Factory-Installed Non-Fused Disconnect Wiring
See Legend on page 4.
See Legend on page 4.
26
Fig. 31 — Typical MoistureMi$er™ Dehumidification Package Humidistat Wiring, 48HJ004-007(208/230-V Unit Shown)
Fig. 32 — Typical MoistureMi$er Dehumidification Package Humidistat Wiring, 48HJ008-014(208/230-V Unit Shown)
See Legend on page 4.
See Legend on page 4.
27
48/50HJ004-007
48/50HJ008-014
Fig. 33 — Motormaster® I Control Wiring Details
NOTE: Motormaster II transformer is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap. Refer tocolor code.
Fig. 34 — Motormaster II Control Wiring Schematic Size 004-007 Units
See Legend on page 4.
See Legend on page 4.
28
YEL
BLK
23
21
13
11
OUTDOORFAN
CONTACTOR
OFM
BLK BLK
MM IV
BLK
YEL
BRN
YEL
BRN
YELYEL
31
4 6
H C F
BRN
BRN
QT CAP 1
OUTDOORFAN
CONTACTOR
OFM
OFM
BLK
MM IV
NOTE: Motormaster® II transformer is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap. Refer tocolor code.
Fig. 35 — Motormaster II Control Wiring Schematic Size 008-014 Units
Fig. 36 — Motormaster IV Control WiringSchematic — Sizes 004-007
Fig. 37 — Motormaster IV Control WiringSchematic — Sizes 008-014
See Legend on page 4.
See Legend on page 4. See Legend on page 4.
29
Fig. 38 — Novar Controls Wiring, EMT3051
Fig. 39 — Novar Controls Wiring, EMT2024
See Legend on page 4.
See Legend on page 4.
30
OFC;C1(008-014)
(004-007)P.S.
P.S.
}
}
}
FIELD COMMON
POWER EXHAUST/ENERGY RECYCLER
COMMUNICATIONS
DEFROST BOARD
TL
DR DR
DR
BLU
BLU
COOLINGUNIT ONLY
„ …HP ONLY
IGC
TB4
MGV
RED
ORN
ORN
BLU
YEL
RED
SPACE TEMP./ SETPOINT ADJUSTMENT
INDOOR AIRQUALITY SENSOR
WHTPNKBRN
WHT
REDBLK
BRN
WHT
OPTIONALACCESSORY
VIO
GRA
GRA
PNKORN
VIOVIO
PNK
PNK
GRA
RED
BLK
RED
BLU
BLU
YEL
YEL
WHT
BLK
ORN
PNK
BRN
BLU
BLUREDBRN
BRNBLK
YEL
ORN
PNK
GRAGRA
BLU
GRA ORN
PNK
PNKORN
WHT
ORN
VIO
BLK
BLK
ORN
GRA
ORN
ORN
BLK
BLK
BLK ORN
VIO
WHT
WHT
WHT
ORN
GRA
WHT
PNK
ORN
VIO
ORN
ORN
VIO
VIO
ORN
IFC
HR1
1
7
4
9
2
3
5
6
8
HR2 13
HR1 C2C1
OF2OF1
R
R
DFT
C
Y
O
C
C
C
CW2
A
T
BTIMER
RDT
5IFR
6
2 4
1
2
C1
D2
W2/H
W1/M
D1/P
C2/C
7
12
11
9
5
1
4
3
2
8
10
6
7
12
11
9
5
1
4
3
2
8
10
6
GVR
CR
BR
L2
L2
L2
L1BM
RTFU
C
CM
1 2 3
J1
FANLOGIC
SAFETYLOGIC
HVTRAN
GVR
J2
W
IFO
5 AMPG
R
RS
RS
LS
LS
CS
CS
GV
YEL
GVFS
C
21
3
CLO 1
X
LOGIC 21
3
CLO 2
X
PremierLink
J1
J5
J6
J4
J8J7J9J2COMMS 0-20mA PP/MP RELAYSPWR
AN
ALO
GD
ISC
RE
TE
0-20m
AIN
HK50AA039
2TR
TR1 3ACCUSENSOR
SAT
OAT
GAS HEATING UNIT ONLY
GAS HEATING UNIT ONLY
3
K1
LOGIC
ECONOMISER2
*
PNK
BRN
WHT
X
W2
C
W1
Y2
Y1
G
R
CONNECTIONBOARD
W2
C
Y1
G
R
Y2
W1
CONNECTIONBOARD
C
G
R
Y2
W1
X
CONNECTIONBOARD
W2
C
Y1
G
R
Y2
W1
X
DDC CONTROL THERMOSTAT CONTROL
24 VAC
RMTOCC
CMPSAFE
FSD
NOT USED
C
X
SFS
*When connecting DDC or thermostat controls, wire to connection board. Do not wire directly to PremierLink™ board.
Fig. 40 — Typical PremierLink Controls Wiring
See Legend on page 4.
31
TB - 1R
Y1
Y2
W1
W2
G
C
X
1
2
3
4
5
6
7
8
TB - 3
1
2
3
4
5
6
7
8
TB - 2
1
2
3
4
5
6
7
8
J6A
NA
LO
GJ5
0 - 20 mA
INJ4
DIS
CR
ET
E
J1PWR
J2COMMS
J90-20 mA
J8Relays
HK50AA039
BRN
BRN WHT
WHT
RED
PNK
PNK
ORNORN
ORN
ORN
GRA
GRAORN
RED
J7PP/MP
WHT
BLK
RED
RED
PNK
WHT
BLK
PNK
WHT
BLU
ORN
YEL
GRN
BRN
BRN
RED
RED
BRN
BRN
BLK
BLK
BRN
BRN
BLU
BLU
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
PNK
PNK
VIO
VIO
GRA
ORN
PNK
PNK
ACCUSENSOR
TR
TR1 3
2
GRA
GRA
GRA
GRA
GRA
SAT
BRNORN
BLK
RED
Space Temp./ SetPoint Adjustment
Indoor AirQuality Sensor
OAT
PNK
VIO
YEL
YEL
BLU
BLU
EconomiSer24 - 20mA
BLK
RED
WHT
PremierLink
GRN
YEL
BLU
BLU
BLU
Outdoor AirQuality Sensor
Power Exhaust/Energy Recycler
CCNComm.
RMTOCC
SFS
CMPSAFE
FSD
RTU TerminalBoard
Fig. 41 — PremierLink™ Controls with Dual Terminal Block (Units Produced 10/02 - Present)
See Legend on page 4.
32
See Legend on page 4.
Fig. 42 — PremierLink™ Controls with Dual Terminal Block and 62AQ Energy$Recycler
33
SMOKE DETECTOR
THERMOSTAT TERMINALBOARD
RC RRED
SMOKE DETECTOR
IGC BOARD
BMBLACK BLACK
IFM
SMOKE DETECTOR
THERMOSTAT TERMINALBOARD
RC RRED
SMOKE DETECTOR
IGC BOARD
IFOBLACK BLACK
IFC
NOTE: Break the Red wire from terminal “RC” on thermostat to terminal “R” on the terminal board.
Fig. 43 — Smoke Control Unit — Shutdown Wiring(48HJ004-014 Single-Phase Units)
NOTE: Break the Black wire from terminal “BM” on the IGC board to the indoor-fan motor (IFM).
NOTE: Break the Red wire from terminal “RC” on thermostat to terminal “R” on the terminal board.
Fig. 44 — Smoke Control Unit — Shutdown Wiring(48HJ004-014 3-Phase Units)
NOTE: Break the Black wire from terminal “IFO” on the IGC board to the “IFC” terminal.
See Legend on page 4.
See Legend on page 4.
34
FROMTHERMOSTAT“Y1” ORECONOMIZER
2 1 3
CLO
BRN
BRN
CorCR
COMPRESSORSAFETIES
TIME GUARD® II
T1 T3 T2
FROMTHERMOSTAT“Y2” ORECONOMIZER
TIME GUARD II
T1 T3 T2
COMPRESSORSAFETIES
CR
BRN
SINGLE COMPRESSOR UNITS
DUAL COMPRESSOR UNITS
Fig. 45 — Time Guard II Control Wiring
Fig. 46 — Two-Position Damper Wiring
See Legend on page 4.
See Legend on page 4.
35
Fig. 47 — Factory-Installed 62AQ Energy$Recycler, 208/230-V COBRA™ Energy Recovery Units —Size 008-012
See Legend on page 4.
36
Fig. 48 — Factory-Installed 62AQ Energy$Recycler, 208/230-V COBRA™ Energy Recovery Unit —Size 014
See Legend on page 4.
37
SIG COM
SPACE TEMPERATURE SENSOR(33ZCT56SPT)
W2
R
Y1
Y2
W1
G
C
X
HM
OC
T STAT
UNIT
W2
W1
W2
W1
HM
HM
CONTROL BOX
CONTROLBOX
8 7 6 5 4 3 2 12 1
H G 24 VACOR
24 VDC
NC ALARMRELAYCONTACTS
COMNO }
0-10VDC
4-20mA
+
+-
+ -
12345678
BLUBRNBLK
COM4-20mA
TB2 TB1
PREMIERLINKCONTROLS
HM
R
HUMIDISTAT
INDOOR AIR QUALITY (CO ) SENSOR2
2 3 4 5 61
SW1
SEN SET
Cool Warm
BRN (GND)BLU (SPT)
RED(+)WHT(GND)
BLK(-) CCN COM
SENSOR WIRING
JUMPERTERMINALSAS SHOWN
BLK(T56)
Fig. 49 — COBRA™ Energy Recycler — Wiring with PremierLink™ Controls
See Legend on page 4.
38
W2
R
Y1
Y2
W1
G
C
X
HM
OC
T STAT
UNIT
W2
W1
W2
W1
HM
HM
R
BASE UNITCONNECTION
BOARD
CONTROL BOX
CONTROLBOX
THERMOSTATCONNECTION
BOARD
G
C
Y1Y2
W1
W2OC
DEHUM
LIGHT COMMERCIAL THERMIDISTAT
CONNECTIONBOARD
Fig. 50 — COBRA™ Energy Recycler — Wiring with Standard Controls
See Legend on page 4.
39
Fig. 51 — Typical Wiring Schematic for 62AQ Energy$Recycler as a Field-Installed Accessory
See Legend on page 4.NOTES:
1. If any of the original wire furnished must be replaced, it must bereplaced with type 90° C wire or its equivalent.
2. Use copper conductors only.3. TRAN is wired for 230 v unit. If unit is to be run with 208 v power
supply, disconnect BLK wire from 230 v terminal and connect to208 v terminal.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 111 Catalog No. 534-80109 Printed in U.S.A. Form 48HJ-3W Pg 40 1-03 Replaces: 48/50HJ-7W,
48/50HJ-8WBook 1 4Tab 1a 6a
Copyright 2003 Carrier Corporation