workability of concretes produced with oarse · 3 sp: sikaplast 898 produced by sika; water: tap...

12
WORKABILITY OF CONCRETES PRODUCED WITH COARSE RECYCLED AGGREGATES João Paulo Freitas Costa Lavado Extended Abstract Dissertation to obtain the Master Degree in Civil Engineering Supervisors Professor Doutor José Alexandre de Brito Aleixo Bogas Professor Doutor Jorge Manuel Caliço Lopes de Brito Jury President: Professor Doutor Nuno Gonçalo Cordeiro Marques de Almeida Supervisor: Professor Doutor José Alexandre de Brito Aleixo Bogas Member: Professor Doutor Pedro Miguel Soares Raposeiro da Silva June 2017

Upload: others

Post on 13-Apr-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

WORKABILITY OF CONCRETES PRODUCED WITH COARSE

RECYCLED AGGREGATES

João Paulo Freitas Costa Lavado

Extended Abstract

Dissertation to obtain the Master Degree in Civil Engineering

Supervisors

Professor Doutor José Alexandre de Brito Aleixo Bogas

Professor Doutor Jorge Manuel Caliço Lopes de Brito

Jury

President: Professor Doutor Nuno Gonçalo Cordeiro Marques de Almeida

Supervisor: Professor Doutor José Alexandre de Brito Aleixo Bogas

Member: Professor Doutor Pedro Miguel Soares Raposeiro da Silva

June 2017

Page 2: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced
Page 3: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

1

WORKABILITY OF CONCRETES PRODUCED WITH COARSE

RECYCLED AGGREGATES

João Paulo Freitas Costa Lavado, [email protected]

Supervisor: Prof. Dr. José Alexandre de Brito Aleixo Bogas

Co-Supervisor: Prof. Dr. Jorge Manuel Caliço Lopes de Brito

Abstract

The main purpose of this dissertation is to study the behaviour of concrete in the fresh state when coarse

recycled concrete aggregates are incorporated in the mix. Thus, three families of concrete with w/c ratios

of 0.55, 0.45 and 0.35 were prepared. The following tests were used: slump; flow table; inverted cone;

Vebe. The experimental results showed that concrete with coarse recycled concrete aggregates tend to

have a similar behaviour when 0.55 w/c ratio is used, mainly because in this type of concrete the paste

plays the main role in terms of workability. In lower w/c ratios, such as 0.35 and 0.45, the shape and

texture become more relevant leading to mixes with less fluidity and consistency. The mixes also

showed lower fluctuations in their fresh state for small variations in paste volume.

Keywords: Recycled coarse concrete aggregates; rheology; slump; spread; workability; loss of workability.

1. Introduction

1.1. Preliminary remarks

This study is intended to be a contribution to better understand the properties of concrete produced with

recycled aggregates (RA), leading to better solutions from an environmental and economic point of view.

The overall study has a major importance due to the high environmental impacts generated by the con-

struction sector: extraction of large quantities of raw materials, high energy consumption and significant

production of pollutants and waste.

CDW (construction and demolition wastes) result from: new construction, rehabilitation, reconstruction,

natural disasters, and building demolition. In Western Europe, the highest percentage of waste comes

from rehabilitation and demolition (80%). In Denmark, rehabilitation contributes with 20-25%, while

70-75% of waste comes from demolition (Mália 2010).

Having in mind the enormous cost with transportation, landfill disposal and treatment, recycled material

use is seen as an attractive alternative, also because it reduces the depletion of natural resources, limits

Page 4: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

2

the high energetic/environmental impacts in traditional concrete production, and increases the life-cycle

of aggregates and concrete.

1.2. Scope and methodology of the investigation

The use of RA in concrete is still not consensual, and various studies are being made to better understand

its effects. In general replacing part or all natural aggregates (NA) with RA tends to produce concrete with

worst properties. This is true when replacing the coarse or the fine fraction, with major consequences on

the last ones (Brito 2005). The type of RA and concrete composition are two major factors that influence

concrete properties, and that is one of the reasons for some different conclusions in the literature.

The major’s differences between recycled concrete aggregates (RCA) and NA are:

higher absorption, affecting workability, w/c ratio, mechanical and durability properties of concrete;

lower compactness, with consequences on crushing strength and elasticity modulus of aggregates.

This happens because RCA have mortar attached to the original natural aggregates. The amount of

mortar attached to the aggregate has a direct relation with its size: smaller aggregates have more mortar

attached to them. Natural fines and cement are the constituents of this mortar with high porosity and

water absorption.

Analysing international and national experimental campaigns was the primary stage of this investigation.

The collected information constituted a repository that refers the most important properties of the aggre-

gates, the experimental test results, and the conclusions of each campaign. With high water absorption

of RAC it is necessary to have special attention when mixing all the components of concrete. It is very

important to compensate the water these aggregates will absorb so the effective w/c ratio remains the

same. Various campaigns did not have this in consideration, producing some inconsistent conclusions.

Afterwards, the experimental program was planned and executed. Recycled coarse concrete aggre-

gates (RCCA) and natural coarse aggregates (NCA) were characterized, but the results are not listed

in detail in this abstract. 20 concrete mixes where produced, varying the w/c ratio, 0.3, 0.4 and 0.5, paste

volume, and coarse aggregate replacement ratio. Super-plasticizer (SP) content was used in the mixes

with 0.3 and 0.4 w/c ratio to achieve the S3 class slump and still have maximum compactness according

to the Faury method.

Subsequently, the experimental results were discussed in detail. Correlations were established between

the properties of the recycled concrete coarse aggregates concrete (RCCAC) and of the reference con-

crete with NA (NAC).

2. Experimental program

2.1. Materials

RCCA: two types of RCA were used: type 1 being the remaining of a previous campaign that suf-

fered primary and secondary crushing, and type 2 with only primary crushing using a concrete jaw

crusher. The concrete was the same for both types of RCA and came from the precast industry.

NA: the NA used were gravel 1 and 2, “rice grain”, and coarse and fine sand;

Cement: ordinary CEM I 42.5 R Portland cement, produced in SECIL Outão;

Page 5: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

3

SP: SikaPlast 898 produced by Sika;

Water: tap water was used for mixing and curing.

2.2. Mix design

Three concrete mixes were produced with water/cement ratio of 0.5, 0.4, and 0.3. The ones produced

with NA only were referred as references concrete, because they were the ones that served for com-

parison purposes. From these mixes RCCAC were produced replacing coarse NA with coarse RA. The

reference concrete mixes were designed to have a slump of 140 ± 10 mm. The proportions of the ma-

terials were determined on the basis of absolute volume of the constituents. The composition of the

NAC’s mixes is given in Table 1. The characteristics of the reference concrete are:

Slump class: S3;

Blinder: CEM I 42.5 R;

Aggregates’ maximum size: 22.5 mm.

Table 1 - Mixture proportions of natural aggregate concrete (NAC) mixes

2.3. Testing of aggregates

The particle size distribution was determined in accordance with EN 933-1 and EN 933-2; the particle

density and water absorption were measured following EN 1097-6; the water content was determined in

accordance with EN 1097-5; the water absorption over time, especially important when using RA, was

determined using a modified version of the test described in EN 1097-6, based on the work of Ferreira

(2007); the apparent bulk density and void percentage were measured following EN 1097-3; the aggre-

gates’ resistance to abrasion was measured by the Los Angeles test following LNEC E-237; the shape

index was measured following EN 933-4; and the flatness index was determined according to EN 933-3.

2.4. Testing of fresh concrete

Concrete was produced using a revolving drum concrete mixer. For each mix the slump in Abrams’ cone

following EN 12350-2 and the spread in the flow table test described in EN 12350-5 were tested. After-

wards concrete’s fresh density and air content were determined according to EN 12350-6 and

EN 12350-7, respectively.

At the starting point, i.e. when the mix is finished, the Vebe test defined in EN 12350-3 and the inverted

cone test, an empirical test widely used on site, described by Bogas (2011), were also performed.

NAC55 NAC45 NAC35

Natural aggregates

Type Volume (m3/m3) Volume (m3/m3) Volume (m3/m3)

Gravel 2 0,217 0,218 0,223

Gravel 1 0,105 0,108 0,112

“Rice grain” 0,079 0,078 0,082

Coarse sand 0,178 0,183 0,186

Fine sand 0,100 0,085 0,075

Total 0,679 0,672 0,678

Component Volume (m3/m3) Volume (m3/m3) Volume (m3/m3)

Cement 0,115 0,131 0,148

Water 0,193 0,180 0,158

SP (%) 0,0 0,2 0,5

Page 6: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

4

Performing all the four test proved impossible when studying the loss of workability over time, because

a lot of water evaporated in the first moments, showing unreliable results.

2.5. Testing of hardened concrete

The 28-day compressive strength of concrete was determined in accordance with EN 12390-3.

Three cubes were filled for each mix when all the previous test were executed and three cubes were

also filled when analyzing the loss of workability over time in the first moments after mixing (around 5

minutes) to understand whether there is an impact in compressive strength when concrete is placed and

vibrated after the curing process starts.

3. Results and discussion

Concrete density were analyzed for NAC and for the mixes produced with the two types of CRA.

Contrary to what was expected, concrete density decreased from the 0.55 to the 0.45 w/c ratio and

increased, as expected, in the mixes with w/c of 0.35, for both NAC and RCCAC.

This can be justified by the fact that the mixes with different w/c ratios were also prepared with different

paste and aggregate volume, e.g. the mix with w/c of 0.55 is associated with a larger paste volume,

which corresponds to a decrease in the sand volume that has higher density. Thus, it was not possible

to directly correlate the w/c ratio with the density of concrete, since the proportion of the materials con-

stituting the mix, namely the aggregate-paste ratio, were modified.

When comparing the three types of concrete, it is possible to see a correlation: when replacing NCA

with RCCA-1 concrete density decreases 3% and when replaced with RCCA-2 it decreases 6%. This

differences are directly related to the mortar attached to the RCCA. Furthermore due to its higher po-

rosity, rougher texture and less rounded geometry, concrete tends to contain more air, affecting the

density of concrete in the fresh state.

When decreasing the w/c ratio and incorporating SP, the air content increased both in RCCAC and

NAC. However, this effect was more pronounced in RCCAC. It is important to highlight that the air con-

tent was less than 1.6% (16 l/m3) for all mixes produced in this study associated with a Dmax of 22.4 mm,

which is a low value, similar to what is common in standard concrete with Dmax of 25.4 mm (15 l/m3) in

ACI613, referred to by Coutinho (1988). In summary, it can be concluded that the incorporation of RCCA

will not significantly influence the air content.

Concrete with NAC was formulated in order to obtain a slump around 140 mm. For RCCAC the purpose

was to have the same composition, i.e. concrete with similar particle size distribution, same cement

content and equal amount of free water in the mix. Thus, a direct replacement of the coarse fraction was

made and the water was added to the mix to compensate the higher absorption of this type of aggre-

gates. Therefore it was possible to compare the influence of the physical characteristics of the aggre-

gates, such as shape, texture, density and specific surface.

The slump measured in Abrams’ cone is essentially influenced by the yield stress of the concrete. In

fact, the motion stops when the forces of gravity, exerted by the concrete's own weight, equal the yield

stress (Bogas 2011).

Page 7: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

5

For concrete produced with NA or RCCA-1 similar slump values were obtained (Figure 1). Thus, the higher

porosity of the RCCA-1 and its more rugged texture had no significant influence on the yield stress. In mixes

produced with RCCA-2 slump was about 38% lower, evidencing an increase in the yield stress. This can

be justified by the interlocking forces that are generated between the particles, as these have more irregular

forms and rougher textures, which hinder the movement of concrete. Thus, despite workability being es-

sentially affected by the shape of the aggregates, it is possible to produce RAC with similar workability to

conventional concrete, if the crushing process produces aggregates with shapes similar to the NA.

Figure 1 - Fresh state tests for concretes with w/c ratio of 0.55

The inverted cone test forces concrete to pass through the lower aperture of the Abrams’ cone. This

test is more affected by the viscosity of concrete, which translates the flow rate of the mix. For more

viscous concrete, concrete has more difficulty in flowing through the opening, resulting in longer flowing

times. The shape of the funnel also evaluates the passing capacity, moving the particles closer to each

other, increasing the number of contacts between the aggregates and hindering their relative movement.

Figure 1 shows larger flow times for RCCAC-2 concrete and lower times for RCCAC-1 concrete when

compared to the time obtained for NAC. The geometric characteristics of RCCAC-2 led to a greater

entanglement between particles that increased the viscosity of concrete. The larger flow time in concrete

with RCCA results also from the fact that the force that mobilizes the test (self-weight) is lower in con-

crete with recycled aggregates. For the same reason, the similar lower value between NAC and concrete

with RCCA-1 may mean a more fluid behavior of the recycled aggregates concrete.

Despite the difference observed in the inverted cone test, the results of the flow table test indicate similar

viscosity in NAC and RCCAC-1. Both mixes had average diameters close to 45 cm. In RCCAC-2, the

smallest average diameter (40 cm) and higher time in the Vebe test confirms the higher viscosity of

these mixes compared to the other ones tested. Simultaneous analysis of the results of the inverted

cone and flow table suggests that RCCAC-1 mixes may be associated with greater flow capacity thru

narrow spaces.

It is also important to note that none of the mixes showed signs of segregation or exudation in all the

tests performed. Thus, it is possible to say that the worst characteristics of RCCAC-2 do not imply

14,1

3,09

45

1,91

13,8

2,03

45,25

1,68

8,75

4,13

40

2,59

0

5

10

15

20

25

30

35

40

45

50

slump inverted cone spread table Vebe test

Slu

mp

(cm

) /

Inve

rted

co

ne

tim

e (s

) /

spre

ad (

cm )

/ V

ebe

tim

e (s

)

NAC RCCAC-1 RCCAC-2

Page 8: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

6

changes in the stability of the 0.55 w/c ratio mixes.

To achieve the same slump class, when analysing mixes with lower w/c ratio, SP was added. SP tends

to have an important effect on the yield stress and a smaller one on viscosity.

Figure 2 shows that SP was efficient when used in NAC and RAC produced with the same contents, in

terms of aggregate, cement and water. Only when 0.35 w/c ratio was prepared, associated with more

relevant SP content, some significant differences were detected.

Figure 2 - Slump, flow time, spread and Vebe time for concrete mixes with different w/c ratio

In order to make SP efficient when used in RAC, the pre-saturation of RCCA was performed.

In 0.55 and 0.45 w/c mixes the higher paste volume controls the viscosity’s decrease. This trend is

observed in NAC but also in RCA. However with recycled aggregates the flow time and the spread were

inconsistent: although the spread remained similar to that of NAC the flow time increased a lot. The

imbrication of the particles seems to be higher in RCCAC, which makes it more difficult to pass through

narrow areas and to flow.

In mixes with 0.35 w/c ratio, associated with lower water content and lower paste volume, there is al-

ready a significant increase in viscosity, translated in a longer flow and lower spread diameter.

NAC55 RC55 NAC45 RC45 NAC35 RC35

0

2

4

6

8

10

12

14

16

Slu

mp

(cm

)

Slump

NAC55 RC55 NAC45 RC45 NAC35 RC35

0

2

4

6

8

10

12

14

16

18

Flo

w t

ime

(s)

Inverted cone

NAC55 RC55 NAC45 RC45 NAC35 RC35

0

5

10

15

20

25

30

35

40

45

50

Ave

rage

sp

read

(cm

)

Flow table

NAC55 RC55 NAC45 RC45 NAC35 RC35

0,0

0,5

1,0

1,5

2,0

2,5

3,0

3,5

4,0

4,5

Veb

e ti

me

(s)

Vebe test

Page 9: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

7

The Vebe test allows concluding that NAC and RCCAC with 0.55 w/c ratio have similar behaviour when

compacted. This was also noticed when the cubes for the compressive strength test were vibrated.

When lower w/c ratio mixes where produced the differences became more relevant. This may be related

with the fact that vibration is less efficient for more porous particles (Bogas 2011).

The loss of mortar from the aggregates during the mixing process increases the fines content. This

affects the size distribution and the surface area of the solid material of the mixes, making them more

susceptible to the variation of w/c ratio.

Mortsell et al. (1996) studied the behaviour of concrete in the fresh state, suggested the design and anal-

ysis of a type of curves, named "S-curves". Basically, these curves give an idea of the evolution of a given

property when the amount of paste in the mix varies, keeping the remaining parameters constant.

The S-curves were built experimentally taking into account the slump and flow table tests for various

mixes with different paste volumes (Figure 3). When replacing the CNA with RCA of similar character-

istics, the rheological behaviour of concrete tends to be similar, both in terms of slump and spread.

Figure 3 - S-Curves for NAC and RCCAC

On the other hand, concrete with RCCA-2 presents a different behaviour. These mixes produced with

aggregates subjected to primary crushing only tend to have less vertical S-curves. This is an indicator

that they are less sensitive to paste volume variations.

When analysing the loss of workability over time, it is also important to separate yield stress from viscosity.

The loss of slump in 0.55 w/c ratio mixes is small in the first 30 minutes (Figure 4). The loss becomes

more significant after 30 minutes, with a reduction of about 50% and 60%. The fact that a slightly higher

initial slump was obtained in RCCAC-1 conditions the analysis of the slump variation over time when

comparing the two mixes. Still, and considering that the slump class is the same, it can be considered

that the variation of 2 cm did not significantly influence the results. In the initial instants, the loss of

workability is mostly associated with slight losses of water by evaporation in the mix. At later ages, other

phenomena, such as the hydration reactions, justify the higher losses. Regardless of the phenomena

that led to the observed losses of workability, these occurred at the paste level, without influence of the

type of aggregate.

The introduction of SP led to higher slump losses shortly after the first 30 minutes. The SP tends to lose

Page 10: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

8

its efficiency over time especially when it is progressively involved by the new hydration products.

In Figure 4 it is possible to observe that in absolute terms very similar values were obtained in the two

mixes with 0.45 w/c ratio.

Figure 4 - Loss of slump over time for NAC and RCCAC

In the mixes with 0.35 w/c ratio the evolution of the workability loss in RCCAC was not as expected.

RCCAC had lower losses compared to NAC in the first 30 minutes and higher losses after 90 minutes.

Taking into account the absolute values, it is possible that the higher initial value of the slump in RCCAC

conditioned the remaining test. The fact that it is more fluid in the first instants means that losses by

water evaporation do not cause such a significant impact on the loss of water.

The higher loss of workability observed in RCCAC may be related to the progressive loss of mortar from

RCCA during mixing, increasing the specific surface area of the solid material and consequently reduc-

ing the free water available in the mix. This assumes greater relevance in mixes that initially have a

higher content of fines.

The loss of spread over time was also determined. The results of this test for NAC and RCCAC and for

the three w/c ratios are analysed are presented in Figure 5.

Once again in 0.55 w/c ratio mixes the loss was only significant after 60 minutes. This is valid for NAC

and RCCAC.

The fact that in the first few minutes there were lower spread losses in RCCAC may be related to the

higher fines content from the attached mortar that tends to become loose from these aggregates when

they are inserted In the concrete mixer causing a lubrication effect and reducing the viscosity. For larger

volumes of material loss, the effect may be the contrary, since there is an increase in the surface area

of the solid material. In fact, as reported by Tattersall and Banfill (1983), there is an optimum content of

00:00 00:30 01:00 01:30

0%

20%

40%

60%

80%

100%

120%

Var

iati

on

of

the

slu

mp

in r

elat

ion

to

th

e in

itia

l in

stan

t

Instant (hours:minutes)

Loss of slump (NAC55)Loss of slump (RC55)Loss of slump (NAC45)Loss of slump (RC45)Loss of slump (NAC35)

12,1

14,413,7

14,7

12,1

14,9

11,4

14

8,2 8,1

6,4

8,7

6,4

7,4

5,5

4,23,4

3,94,5

5,5

3,6

2,3

1,1

00

2

4

6

8

10

12

14

16

NAC55 RC55 NAC45 RC45 NAC35 RC35

Slu

mp

(cm

)

0 minutos 30 minutos

60 minutos 90 minutos

Page 11: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

9

fines after which the compactness and workability of the blends decrease. This would justify the fact that

mixes with lower w/c ratio are more sensitive to higher workability losses.

Figure 5 - Loss of spread over time for NAC and RCCAC

Analysing the compressive strength of the mixes (Table 2), it is possible to notice a decrease when

using RCCA. It is interesting to note that concrete produced with RCCA-2 that suffered only primary

crushing had similar compressive strength. This may be related to the fact that this analysis was per-

formed only in higher w/c ratio mixes, in which case the strength of the paste was conditioning to the

concrete strength. The fact that the compressive strength does not decrease substantially for this type

of aggregates can be further explained in the literature because the more angular and irregular the

aggregates are the better the bond between the paste and the aggregate is (Mehta and Monteiro 1994).

It is important to remember that the RCCA used in this experimental campaign were sourced from a

high-strength concrete.

Table 2 - Compressive strength of NAC and RCCAC

00:00 00:30 01:00 01:30

0%

20%

40%

60%

80%

100%

120%

Var

tiat

ion

of

spre

ad in

rel

atio

n t

o t

he

init

ial i

nst

ant

Instant (hours:minutes)

Loss of spread (NAC55)

Loss of spread (RC55)

Loss of spread (NAC45)

Loss of spread (RC45)

Loss of spread (NAC35)

Loss of spread (NC35)

42,75 43,5 43,25

46,5

38

47,25

43,2545,25

38

44,5

32,2533,5

36,25

41

35

38

29,25 29,5

36,7538

34,2536

25,5 25

0

5

10

15

20

25

30

35

40

45

50

NAC55 RC55 NAC45 RC45 NAC35 RC35

Spre

ad (

cm)

0 minutes 30 minutes

60 minutes 90 minutes

Concrete w/c fcm (MPa) Variation to NAC

NAC

0.35 78.52 0.00%

0.45 63.14 0.00%

0.55 52.29 0.00%

RCCAC-1

0.35 70.63 -10.05%

0.45 55.75 -11.71%

0.55 49.47 -5.39%

RCCAC-2

0.35 - -

0.45 - -

0.55 49.11 -6.10%

Page 12: WORKABILITY OF CONCRETES PRODUCED WITH OARSE · 3 SP: SikaPlast 898 produced by Sika; Water: tap water was used for mixing and curing. 2.2. Mix design Three concrete mixes were produced

10

It was also possible to confirm that there is no significant loss in compressive strength when casting and

vibrating concrete after one hour and thirty minutes in both NAC and RCCAC. After this time concrete

has already started the setting process, making it more difficult to vibrate. In this case, the concrete

required a higher vibration energy that would make it difficult to operate on site.

4. Conclusions

This study makes it possible to demonstrate that tests that indirectly assess the rheology of concrete,

when affected by more than one parameter or factor, make their analysis complex, in particular with

regard to the establishment of comparisons between different types of concrete.

In general, it was possible to see that mixes with w/c of 0.35 and with SP tended to be more difficult to

work that the ones with w/c of 0.55, even though both mixes have the same slump. It means that other

parameters, such as the viscosity of the mixes, are also relevant when evaluating the workability.

In summary, it can be concluded from this study that workability is affected when replacing NA by RCCA

subjected to only one crushing phase. For RCCA with similar shape and texture as the NA and for mixes

with high w/c ratio, it seems that the paste plays the leading role in workability. For lower w/c ratio mixes

with SP, the loss of mortar attached to the aggregates, the higher water absorption and the irregular

shape and texture seem to make the behaviour of RCCAC different from that of NAC: making RCCAC

more fluid in the first ages but with higher losses afterwards.

5. References

BOGAS, J. (2011). - Caracterização de betões estruturais com agregados leves de argila expandida.

Tese de Doutoramento em Engenharia Civil. Volume I e II, Instituto Superior Técnico, Lisboa.

BRITO, J. (2005) - Agregados reciclados e a sua Influência nas propriedades dos betões. Lição de

síntese para provas de agregação, Instituto Superior Técnico, Lisboa.

HU, C., & DE LARRARD, F. (1996) - The rheology of fresh high performance concrete, in Cement and

Concrete Research, V. 26, N.º 2, pp. 283-294.

MÁLIA, M. (2010) - Indicadores de resíduos de construção e demolição. Dissertação de mestrado em

Engenharia Civil, Instituto Superior Técnico, Lisboa.

MEHTA, P. K., MONTEIRO, P. J. M. (1994) - Concreto: Estrutura, Propriedades, Materiais, São Paulo,

Pini.

MORTSELL, E., SMEPLASS, S., HAMMER, T.A., & MAGE, M. (1996) - FLOWCYL - How to determine

the flow properties of the matrix phase of high performance concrete. 4th International Symposium on

Utilization of High-strength / High-performance Concrete, Paris.

SANCHEZ, M. (2004) - Estudio sobre la utilización de árido reciclado para la fabricación de hormigón

estructural, Tese de Doctoramiento, Universidad Politécnica de Madrid, Madrid.

TATTERSALL, G. H., BANFILL, P. F. G. (1983) - The rheology of fresh concrete, Pitman.