wsa brochure_en

18
IT Cooling Solutions STULZ Explorer Screw Cooling performance for your critical application

Upload: glenn-gradwell

Post on 06-Apr-2017

197 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: WSA brochure_EN

IT Cooling Solutions

STULZ Explorer Screw Cooling performance for your critical application

Page 2: WSA brochure_EN

2

HIGHDENSITYCOOLING

CHILLERUNITS

ROOMCOOLING

AIRHANDLINGUNITS

MODULARDATA CENTERCOOLING

DIRECT FREE

COOLING INDIRECT FREE COOLING

DATACENTER

COOLING

The Whole Range of Cooling Solutions from a Single Source

For more than 40 years, sensitive information and communication technology has been cooled by air conditioning systems made by STULZ – everywhere in the world.Our formula for success is both simple and sophisticated:we are engineers with a vision and business people who knowa lot about technology.

STULZ products and services are the result of many thousandsof projects. This wealth of experience, our power of innovation,

and our know-how enable us to offer our customers the whole spectrum of our cooling products and services at the highest quality level.Around the globe, our entire range of products and servicescomplies with international standards.

Page 3: WSA brochure_EN

3

STULZ Explorer Screw – Cooling performance for your critical applicationThe new STULZ Explorer range with screw compressors, extend the range of high-efficiency chillers for industrial application, data centre and comfort, boasts a cooling capacity from 380 to 1200 kW.The ever-increasing need to reduce operating consumption either in industrial processes, data centre and comfort has led to the realization of a range that is strongly orientated to maximum performance in terms of efficiency, while maintaining strength and reliability.

The STULZ Explorer Screw chillers ensure maximum efficiency and precision thanks to:

- Environmentally friendly refrigerant R134a- Screw compressors equipped with slide valve- Electronic thermostatic valves controlled by electronic controller Stulz C2020- Shell & tube evaporator and “W-shape” Microchannel condenser coils- Modulating fans adjustment.

4 Features and Options Reliable performance

6 Free Cooling Efficient solutions with Indirect

Free Cooling

8 Efficiency Minimal energy consumption

9 Control and Monitoring Microprocessor-controlled

monitoring

14 Production Sites Close to you all over the world 16 STULZ Worldwide Global expertise in chiller cooling

from over 1,000 successful projects

Contents

Page 4: WSA brochure_EN

4

Features and Options

Efficiency

Design

Free Cooling (FC)The entire STULZ Explorer Screw range is available in Free Cooling version, with air/water (non freezable mixture) exchanger coils integrated in all the models and able to provide the entire cooling capacity of the chillers even from temperatures close to 0°C.Thanks to Stulz C2020 electronic controller the operation of the Free Cooling system is optimized according to the external temperature; by mixing the Chiller and Free Cooling functions it fully exploits heat recovery from the cold external air and reduce the electrical consumption.

Energy rating The STULZ Explorer chiller range fulfill the requirements of higher Energy Classes. According to the sizes and versions the energy class can be A or B, with an EER that can easily exceed the value of 3 under nominal Eurovent con-ditions and can achieve seasonal yield at highest levels.

Condensing battery with W-shape geometry The MicroChannel condenser coils are entirely made in aluminum and expressly designed and realized to maximize the yield of the chillers, preserving reduced dimensions. The W-shape geometry has an angle designed, tested and proven specifically to avoid points of failure of the batteries and the imbalance of the refrigerant circuits. The use of a W-shape geometry ensures an optimal air flow through the coils, allowing to reduce the noise of the refrigerator both in Chiller or Free Cooling mode.

EEV electronic expansion valve The evaporation of the refrigerant gas into the cooling circuits is guaranteed by latest generation electronic thermostatic valves. Together with appropriate pressure switches, temperature probes and the electronic controller Stulz C2020 the valves optimize the thermal exchange into the evaporator, preserving the upstream and downstream components from high temperatures or icing.The operating and calibration logic of the electronic thermostatic valves lies in the electronic controller Stulz C2020.

Reliability at high level The units are designed and realized to obtain the maximum strength and flexibility, ensuring the integrity of the machine both during the transport on truck or container, than in the continuous exposure to atmospheric agents. The disposition of internal components is conceived to ease the ordinary maintenance and ensure a long service life of the chiller.The double cooling circuit with screw compressors equipped with splitter control, is able to adapt at different thermal loads, optimizing the operating of the chiller and guaranteeing the longevity of the components also in intensive use (H24/365)

Low Noise (SL)The low noise version (UNI EN 14511) reduces considerably the sound pressure level of the entire chiller, thanks to the adoption of appropriate solutions, like:- acoustic insulation of each compressor and pump (if installed)- fans speed reduction, with check of the condensing coils size

Quick connectionsAll hydraulic connections are equipped with rapid connections for a greater ease of installation and possible maintenance.

Outdoor installation WSA Explorer is designed to be used on any outdoor installation. The electrical panel, with IP54 protection, guarantees an adequate security for electric and electronic components. The different options allow a further extension of the operating limits both at low and high temperatures, with enhanced protection for highly corrosive environments.

Page 5: WSA brochure_EN

5

Modular unit sizes

H x W x D (mm)

2,478 x 2,278 x 4,240

H x W x D (mm)

2,478 x 2,278 x 6,960

H x W x D (mm)

2,478 x 2,278 x 8,080

H x W x D (mm)

2,478 x 2,278 x 11,920WSA 480WSA 640

Electronic Control WEBThe STULZ Explorer Screw range is equipped and controlled by the electronic controller Stulz C2020, designed and realized by Stulz for better manage the chillers.New specific functions were implemented to better control the screw compressors, keeping the affability and precision which already distinguish the chillers.The controller has a color Touch-screen display for easily manage and checking the operation of the chiller.Pre-loaded or optionals communication protocols allow to expand the manage-ment and the checking of the chiller to informatic devices, even remotely through intranet, internet or gsm.Sequencing, Emergency cooling and redundancy are pre-loaded functions which allow the communication be-tween more chillers to better meet the request of the users.

Hydronic Group (HK)Hydronic group with pumps on the inlet (except for WSA160-220).The Hydronic group is available with:- 1 pump, head pressure available 1,5-2 bar - 2 pumps in redundancy, managed by Stulz C2020- 1 pump with inverter: air flow electronic adjustment - 2 pumps with inverter: redundancy with air flow electronic adjustmentThe hydronic group is designed for pressurized closed circuit

Protective treatment on the coilsProtective cataphoresis or epoxy treatment, in order to enhance the coils resistance in aggressive environments. The treatment is a standard on the coils of the Free Cooling version.

Protective gridsThe protective grids in zinc coated metal sheet painted with epoxy powders guarantee the proper airflow in the condensers while preventing access to the components.Anti-vibration mountsSupports specifically designed to

Control Options

bear the chiller's weight and eliminate transmission of the vibrations to the underlying structure during operation.

Flow switchComponent that verifies the flow of the fluid in the circuit. Installed on the return pipe to the chiller. The flow switch is electrically connected to the C2020 control and reports the absence of fluid circulation, preventing damage to the hydraulic components.

Soft startDevice for reducing mechanical stress during compressor start-up. The device partialises the starting current of the compressors by reducing the stress on the power supply line and preserving the compressors' components.

WSA 320WSA 360WSA 380WSA 440

WSA 250WSA 280WSA 300

WSA 160WSA 220

Page 6: WSA brochure_EN

6

STULZ Explorer units (WSA160 to WSA640) can be selected with onboard Free Cooling, while versions with a higher cooling capacity are designed for connection to a dry cooler unit. Chillers with integrated Free Cooling are provided with Free Cooling coils for the water circuit, a three-way valve and a hydronic group with 1 pump. As standard, the Free Cooling configuration also includes the cataphoresis treatment of Microchannel condensing coils in order to avoid galvanic corrosion due to the proximity of other water exchangers. The cost effectiveness of a system with integrated Free Cooling and its ROI (return on investment) depend on the working conditions, the cooling unit efficiency and the climatic conditions on the installation site.

All these factors are integrated into STULZ selection software, which is able to simulate chiller operating conditions in more than 300 cities in the world, calculating the annual saving of money and energy (kWh) very accurately. For instance, it is possible to enter the altitude value of the installation and to factor in the density of air in the chiller performance calculation. The kWh cost can also be varied. During the simulation, the software also takes the variation of fans speed in Mix-Mode (combination between Free Cooling and compressor cooling) into consideration.

In temperate climates north and south of the equatorial zone, the energy-saving advantages of Indirect Free Cooling can be fully exploited. Electricity consumption for data center air condi-tioning will drop by up to 60%.

Temperate climate

Free Cooling

Percentage and number of hours per year of temperatures up to and including 18 °C(up to 27 °C possible according to ASHRAE TC 9.9 – 2011)

Hamburg London Moscow Canberra Madrid Istanbul New York BeijingJohannes-

burgParis

Sao Paulo

Annual no. of hours below 18 °C 1

7,660 7,010 7,529 6,492 5,637 5,444 5,577 5,341 5,667 6,708 3,219

Percentage 2 87% 80% 86% 74% 64% 62% 64% 61% 65% 77% 37%

Annual no. of hours below 27 °C 1

8,720 8,727 8,728 8,399 7,817 8,198 8,114 7,865 8,637 8,593 8,312

Percentage 2 99.5% 99.6% 99.6% 96% 89% 94% 93% 90% 99% 98% 95%

1 Hours per year of temperatures up to and including 18 °C / 27 °C2 Yearly percentage of hours with temperatures up to and including 18 °C / 27 °C

Page 7: WSA brochure_EN

7

SUM

MER

MO

DE

MIX

ED M

ODE

WIN

TER

MO

DE

Page 8: WSA brochure_EN

8

STULZ Explorer chillers were developed to cover an entire range of applications (from process industry to data centers). STULZ Explorer units are designed for a high energy class (Class A) or to work in extreme environmental conditions. They also come in very precise configurations with temperature controls dedicated to the application.

In almost all applications, the thermal load and ambient temperature conditions are highly variable. STULZ Explorer units closely match all environmental and load conditions, achieving a high seasonal efficiency (ESEER) – even higher than 5. High ESEER values lead to significant energy savings.

Efficiency

ESEERPartial load Weighting coeff. Air temperature100% 3% (0.03) 35 °C75% 33% (0.33) 30 °C50% 41% (0.41) 25 °C25% 23% (0.23) 20 °C

ESEER

The seasonal energy efficiency index (seasonal energy efficiency ratio) is a parameter that indicates the seasonalefficiency of an air conditioner or a refrigerator group.

ESEER = 0.03 x EER100% + 0.33 x EER75% + 0.41 x EER50% + 0.23 x EER25%

3.6

4.6

3.8

4.8

3.4

4.4

3.2

4.2

3

4

2.825% 50% 100%75%

EER

Efficiency at partial load (water 7/12 °C, air 35 °C)

Page 9: WSA brochure_EN

9

The “mind” of the STULZ Explorer Screw chiller is the Stulz C2020 electronic control, developed by Stulz to achieve the best performance from every component. In the Stulz Explorer range with screw compressors have been implemented new functions in order to obtain the best management of the new components. Memory and calculation speed are increased, allowing a better and faster control of all the components and preserving the durability of the units. The numerous functions and parameters are summarized in a few simple steps and screens, which allow the user to easily keep under control the chiller correct operation. A 7” liquid crystal display with touch screen acts as an interface between the user and the chiller. The display reports all the information on: operation status, working time, alarm history and alarm signals. Furthermore it allows to start, stop and modify the chiller operation.

C 2020 Electronic Controller is equipped with the following pre-loaded functions :

• Sequencing = to connect through a specific line more chillers and manage the components as a unique chiller

• Emergency Cooling = to activate the chillers in the same line, in case the active chiller cannot make up for the overload of the user.

• Redundancy = activates alternatively the chillers and guarantees the service continuity in case of fault of a chiller.

• ModBus RTU = to manage remotely the chiller through standard interfaces

• Stulz Protocol = to connect the chiller to the Stulz supervision components

• Unloading = guarantees the chiller partialised operation even at high temperatures

• Antifreeze

C 2020 Electronic Controller is equipped with the following pre-loaded functions :

• Sequencing = to connect through a specific line more chillers and manage the components as a unique chiller

• Emergency Cooling = to activate the chillers in the same line, in case the active chiller cannot make up for the overload of the user.

• Redundancy = activates alternatively the chillers and guarantees the service continuity in case of fault of a chiller.

• ModBus RTU = to manage remotely the chiller through standard interfaces

• Stulz Protocol = to connect the chiller to the Stulz supervision components

• Unloading = guarantees the chiller partialised operation even at high temperatures

• Antifreeze

C 2020 Electronic Controller manages :

• Compressors = start, switching off and slide valve partialisation, within the limits provided by the supplier

• Fans = depending on the power requested and on the active function (chiller, Free Cooling) sets the fans speed, to guarantee the maximum yield with lesser noise and electric consumption

• Electronic Thermostatic Valves = partialises the refrigerant evaporation to obtain the requested power with the lesser electrical consumption

• Fluid side pumps (where expected) = the electronic control manages the redundancy in case of installation of 2 pumps, in order to maintain the working time of the pumps as similar as possible.

• Free Cooling circuit = partialising the 3-ways valve, it takes advantage of the entire cooling capacity recoverable from the ambient air.

Electronic Control STULZ C2020

Page 10: WSA brochure_EN

10

Product Structure

Air Cooled ScrewSW

A3°digitConfigurationA axial fans

3

2

0

4°digit

5°digit

6°digit

Cooling Capacity160 376 kW (1) 320 738 kW (1)

220 482 kW (1) 360 844 kW (1)

250 567 kW (1) 380 911 kW (1)

280 630 kW (1) 440 1032 kW (1)

300 672 kW (1) 480 1122 kW (1)

(1) at 50 Hz, W7L35 640 1260 kW (1)

27°digitEvaporation Temperature1 Outlet water > 15°C

2 Outlet water ≤ 15°C (standard)

8°digit CVersionC chiller

D chiller with treated MCH coils

F Free Cooling

G Free Cooling + Epoxy condensing coils

I Free Cooling + Cataphoresis condensing coils

N9°digitNoise LevelN Standard

S Low Noise

10°digit A Power SupplyA 400V / ~3 / 50Hz

B 460V / ~3 / 60Hz

N11°digitHydraulic Circuit 0 No pumps

1 n°1 pump standard

2 n°2 pumps standard

3 n°1 pump with inverter

4 n°2 pumps with inverter

12°digit 0 Heat Recovery0 none

D partial recovery (t.b.d.)

T total recovery (t.b.d.)

0

0

0

Options (change accordingly to the selected options)13°digit

14°digit

15°digit

2°digit

1°digit

Page 11: WSA brochure_EN

11

Technical Data – WSA StandardModel WSA-160 WSA-220 WSA-250 WSA-280 WSA-300 WSA-320

GeneralCooling capacity kW 376 482 568 631 673 739Power Consumption 121 164 178 203 226 237Working limits ambient temperature °C -18* / +46 -18* / +46 -18* / +46 -18* / +46 -18* / +46 -18* / +46Working limits water outlet temperature °C -5* / +25 -5* / +25 -5* / +25 -5* / +25 -5* / +25 -5* / +25Refrigerant Type R134a R134a R134a R134a R134a R134aPower supply V/ph/Hz 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50Secondary power supply Vac 230 230 230 230 230 230Max. power consumption kW 336 412 459 495 495 646Max. absorbed current A 196 240 268 290 290 347Starting current A 586 750 875 946 946 802Height x width x depth mm 2473 x 2278 x 4240 2473 x 2278 x 4240 2473 x 2278 x 6960 2473 x 2278 x 6960 2473 x 2278 x 6960 2473 x 2278 x 8080Noise level dB(A) 68,9 70,5 69,2 69,6 69,6 70,62CompressorCooling Circuit n° 2 2 2 2 2 2Semi-Hermetic Double Screw compressor n° 2 2 2 2 2 2Partialization % 12,5…100 12,5…100 12,5…100 12,5…100 12,5…100 12,5…100Max. power consumption kW 176 220 392 262 262 310Max. absorbed current A 288 364 240 428 428 560Power consumption W7L35 kW 105 148 154 179 202 205Absorbed current W7L35 A 163 243 258 296 313 328FansAxial fans n° 8 8 12 12 12 16Fan flow m³/h 148820 144240 215045 215045 215045 278715Max. Power consumption kW 17,6 17,6 26,4 26,4 26,4 35,2Max. absorbed current A 37,8 37,8 56,8 56,8 56,8 75,7Power Consumption W7L35 kW 16 16 24 24 24 32Absorbed Current W7L35 A 34,4 34,4 51,6 51,6 51,6 68,8HydraulicCoolant liquid Type Water + max 40% glycolInlet temperature °C 12 12 12 12 12 12Outlet temperature °C 7 7 7 7 7 7Water flow m³/h 64 83 97 108 115 127Pressure drops kPa 44 35 36 38 35 43Water connections Inches 6 6 6 6 6 6EEREER 3,10 2,94 3,18 3,11 2,97 3,12ESEER 4,43 4,65 4,52 4,58 4,45 4,53IPLV 4,35 4,55 4,48 4,58 4,45 4,37

Evaporator water (in/out) 12/7 °C; condenser air (in) 35 °C;Average sound pressure level at 10 m distance; unit in a free field on a reflective surface.According to ISO 3744. Unit at full capacity. Pump contribution is not considered.*In case of applications with an output fluid temperature below +5 °C, please contact the manufacturer.

Technical Data – WSA StandardModel WSA-360 WSA-380 WSA-440 WSA-480 WSA-640

GeneralCooling capacity kW 845 912 1032 1122 1260Power Consumption 271 294 354 351 431Working limits ambient temperature °C -18* / +46 -18* / +46 -18* / +46 -18* / +46 -18* / +46Working limits water outlet temperature °C -5* / +25 -5* / +25 -5* / +25 -5* / +25 -5* / +25Refrigerant Type R134a R134a R134a R134a R134aPower supply V/ph/Hz 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50Secondary power supply Vac 230 230 230 230 230Max. power consumption kW 706 706 726 844 1018Max. absorbed current A 387 387 445 499 609Starting current A 861 861 992 1134 1488Height x width x depth mm 2473 x 2278 x 8080 2473 x 2278 x 8080 2473 x 2278 x 8080 2473 x 2278 x 11920 2473 x 2278 x 11920Noise level dB(A) 70,8 70,8 71,7 72,6 74,0Cooling circuitCooling Circuit n° 2 2 2 2 2Semi-Hermetic Double Screw compressor n° 2 2 2 2 2Partialization % 12,5…100 12,5…100 12,5…100 12,5…100 12,5…100Max. power consumption kW 350 350 408 444 554Max. absorbed current A 620 620 640 720 894Power consumption W7L35 kW 239 262 322 303 383Absorbed current W7L35 A 376 392 479 485 623FansAxial fans n° 16 16 16 24 24Fan flow m³/h 278715 288480 288480 418070 418070Max. Power consumption kW 35,2 35,2 35,2 52,8 52,8Max. absorbed current A 75,7 75,7 75,7 113,5 113,5Power Consumption W7L35 kW 32 32 32 48 48Absorbed Current W7L35 A 68,8 68,8 68,8 103 103HydraulicCoolant liquid Type Water + max 40% glycolInlet temperature °C 12 12 12 12 12Outlet temperature °C 7 7 7 7 7Water flow m³/h 145 156 177 193 216Pressure drops kPa 32 38 32 41 49Water connections Inches 8 8 8 8 8EEREER 3,12 3,10 2,91 3,19 2,92ESEER (ISO14511) 4,76 4,65 4,66 4,64 4,53IPLV 4,6 4,56 4,55 4,47 4,48

Page 12: WSA brochure_EN

12

Technical Data – WSA Free CoolingModel WSA-160FC WSA-220FC WSA-250FC WSA-280FC WSA-300FC WSA-320FC

GeneralCooling capacity kW 366 469 552 594 652 721Power Consumption 126 172 185 212 237 247Working limits ambient temperature °C -18* / +46 -18* / +46 -18* / +46 -18* / +46 -18* / +46 -18* / +46Working limits water outlet temperature °C -5* / +25 -5* / +25 -5* / +25 -5* / +25 -5* / +25 -5* / +25Refrigerant Type R134a R134a R134a R134a R134a R134aPower supply V/ph/Hz 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50Secondary power supply Vac 230 230 230 230 230 230Max. power consumption kW 336 412 459 495 495 646Max. absorbed current A 196 240 268 290 290 347Starting current A 586 750 875 946 946 802Height x width x depth mm 2473 x 2278 x 4240 2473 x 2278 x 4240 2473 x 2278 x 6960 2473 x 2278 x 6960 2473 x 2278 x 6960 2473 x 2278 x 8080Noise level dB(A) 68,9 70,5 69,2 69,6 69,6 70,6Cooling circuitCooling Circuit 2 2 2 2 2 2Semi-Hermetic Double Screw compressor n° 2 2 2 2 2 2Partialization % 12,5…100 12,5…100 12,5…100 12,5…100 12,5…100 12,5…100Max. power consumption kW 176 220 392 262 262 310Max. absorbed current A 288 364 240 428 428 560Power consumption W7L35 kW 110 156 161 187 212 215Absorbed current W7L35 A 169,4 253,9 267,1 307,9 326,9 342,0FansAxial fans n° 8 8 12 12 12 16Fan flow m³/h 122250 120127 177851 177851 177851 224542Max. Power consumption kW 17,6 17,6 26,4 26,4 26,4 35,2Max. absorbed current A 37,8 37,8 56,8 56,8 56,8 75,7Power Consumption W7L35 kW 16 16 24 24 24 32Absorbed Current W7L35 A 34,4 34,4 51,6 51,6 51,6 68,8HydraulicCoolant liquid Type Water + max 40% glycolInlet temperature °C 12 12 12 12 12 12Outlet temperature °C 7 7 7 7 7 7Water flow m³/h 64,4 82,7 97,4 108,2 115,4 126,8Pressure drops kPa 44,01 34,75 35,56 38,25 35,4 42,77Water connections Inches 6 6 6 6 6 6Free CoolingCooling Capacity W10L kW 376 472 552 611 660 740Temperature of total FC °C 0,5 -2 0,5 -0,7 -1,7 0Flow of fluid to be cooled m³/h 65 81 95 105 113 127Pressure drop kPa 46 72 23 27 31 45EEREER 2,91 2,72 2,99 2,81 2,76 2,92ESEER (ISO14511) 4,33 4,39 4,50 4,39 4,34 4,44IPLV 4,23 4,43 4,35 4,3 4,29 4,28

Technical Data – WSA Low NoiseModel WSA-160SL WSA-220SL WSA-250SL WSA-280SL WSA-300SL WSA-320SL

GeneralCooling capacity kW 360 442 534 589 627 689Power Consumption 122 175 183 212 239 245Working limits ambient temperature °C -18* / +46 -18* / +46 -18* / +46 -18* / +46 -18* / +46 -18* / +46Working limits water outlet temperature °C -5* / +25 -5* / +25 -5* / +25 -5* / +25 -5* / +25 -5* / +25Refrigerant Type R134a R134a R134a R134a R134a R134aPower supply V/ph/Hz 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50Secondary power supply Vac 230 230 230 230 230 230Max. power consumption kW 336 412 459 495 495 646Max. absorbed current A 196 240 268 290 290 347Starting current A 586 750 875 946 946 802Height x width x depth mm 2473 x 2278 x 4240 2473 x 2278 x 4240 2473 x 2278 x 6960 2473 x 2278 x 6960 2473 x 2278 x 6960 2473 x 2278 x 8080Noise level dB(A) 68,9 70,5 69,2 69,6 69,6 70,6Cooling CircuitCooling Circuit n° 2 2 2 2 2 2Semi-Hermetic Double Screw compressor n° 2 2 2 2 2 2Partialization % 12,5…100 12,5…100 12,5…100 12,5…100 12,5…100 12,5…100Max. power consumption kW 176 220 392 262 262 310Max. absorbed current A 288 364 240 428 428 560Power consumption W7L35 kW 105 148 154 179 202 205Absorbed current W7L35 A 163 243 258 296 313 328FansAxial fans n° 8 8 12 12 12 16Fan flow m³/h 111280 99570 147655 147655 147655 186770Max. Power consumption kW 17,6 17,6 26,4 26,4 26,4 35,2Max. absorbed current A 37,8 37,8 56,8 56,8 56,8 75,7Power Consumption W7L35 kW 10 10 15 15 15 20Absorbed Current W7L35 A 20 20 30 30 30 40HydraulicCoolant liquid Type Water + max 40% glycolInlet temperature °C 12 12 12 12 12 12Outlet temperature °C 7 7 7 7 7 7Water flow m³/h 62 76 92 101 107 118Pressure drops kPa 32 33 31 37 28 33Water connections Inches 6 6 6 6 6 6EEREER 2,94 2,52 2,91 2,77 2,61 2,81ESEER (ISO14511) 4,59 4,64 4,65 4,66 4,49 4,64IPLV 4,63 4,57 4,7 4,71 4,52 4,57

STANDARD - LOW NOISEEvaporator water (in/out) 12/7 °C; condenser air (in) 35 °C;Average sound pressure level at 10 m distance; unit in a free field on a reflective surface.According to ISO 3744. Unit at full capacity. Pump contribution is not considered.*In case of applications with an output fluid temperature below +5 °C, please contact the manufacturer.

FREE COOLING30% Glycol-Water solution. Evaporator solution IN/OUT= 15/10 °C; Condenser air 30 °CAverage sound pressure level, at 10m distance, unit in a free field on a reflective surface. Unit at full capacity. According to ISO 3744. Pumps contribution is not considered*In case of applications with output fluid temperature below 0°C, please contact the manufacturer

Page 13: WSA brochure_EN

13

Technical Data – WSA Free CoolingModel WSA-360FC WSA-380FC WSA-440FC WSA-480FC WSA-640FC

GeneralCooling capacity kW 822 888 1004 1088 1225Power Consumption 283 306 370 366 451Working limits ambient temperature °C -18* / +46 -18* / +46 -18* / +46 -18* / +46 -18* / +46Working limits water outlet temperature °C -5* / +25 -5* / +25 -5* / +25 -5* / +25 -5* / +25Refrigerant Type R134a R134a R134a R134a R134aPower supply V/ph/Hz 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50Secondary power supply Vac 230 230 230 230 230Max. power consumption kW 706 706 726 844 1018Max. absorbed current A 387 387 445 499 609Starting current A 861 861 992 1134 1488Height x width x depth mm 2473 x 2278 x 4240 2473 x 2278 x 4240 2473 x 2278 x 6960 2473 x 2278 x 6960 2473 x 2278 x 6960Noise level dB(A) 70,8 70,8 71,7 72,6 74,0Cooling circuitCooling Circuit n° 2 2 2 2 2Semi-Hermetic Double Screw compressor n° 2 2 2 2 2Partialization % 12,5…100 12,5…100 12,5…100 12,5…100 12,5…100Max. power consumption kW 350 350 408 444 554Max. absorbed current A 620 620 640 720 894Power consumption W7L35 kW 251 273 337 318 403Absorbed current W7L35 A 393,0 407,6 501,2 505,8 650,6FansAxial fans n° 16 16 16 24 24Fan flow m³/h 224542 240253 240253 336812 336812Max. Power consumption kW 35,2 35,2 35,2 52,8 52,8Max. absorbed current A 75,7 75,7 75,7 113,5 113,5Power Consumption W7L35 kW 32 32 32 48 48Absorbed Current W7L35 A 68,8 68,8 68,8 103 103HydraulicCoolant liquid Type Water + max 40% glycolInlet temperature °C 12 12 12 12 12Outlet temperature °C 7 7 7 7 7Water flow m³/h 145 156,4 177,1 192,5 216,2Pressure drops kPa 32,24 38,07 31,99 40,68 49,2Water connections Inches 8 8 8 8 8Free CoolingCooling Capacity W10L kW 835 879 1004 1100 1237Temperature of total FC °C -1,5 -1,3 -3 0 -1,3Flow of fluid to be cooled m³/h 144 151 173 189 213Pressure drop kPa 52 64 80 44 51EEREER 2,91 2,91 2,72 2,97 2,72ESEER (ISO14511) 4,55 4,41 4,30 4,49 4,40IPLV 4,46 4,42 4,41 4,32 4,32

Technical Data – WSA Low NoiseModel WSA-360SL WSA-380SL WSA-440SL WSA-480SL WSA-640SL

GeneralCooling capacity kW 780 851 958 1053 1167Power Consumption 283 307 379 363 453Working limits ambient temperature °C -18* / +46 -18* / +46 -18* / +46 -18* / +46 -18* / +46Working limits water outlet temperature °C -5* / +25 -5* / +25 -5* / +25 -5* / +25 -5* / +25Refrigerant Type R134a R134a R134a R134a R134aPower supply V/ph/Hz 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50Secondary power supply Vac 230 230 230 230 230Max. power consumption kW 706 706 726 844 1018Max. absorbed current A 387 387 445 499 609Starting current A 861 861 992 1134 1488Height x width x depth mm 2473 x 2278 x 8080 2473 x 2278 x 8080 2473 x 2278 x 8080 2473 x 2278 x 11920 2473 x 2278 x 11920Noise level dB(A) 70,8 70,8 71,7 72,6 74,0CompressorCooling Circuit n° 2 2 2 2 2Semi-Hermetic Double Screw compressor n° 2 2 2 2 2Partialization % 12,5…100 12,5…100 12,5…100 12,5…100 12,5…100Max. power consumption kW 350 350 408 444 554Max. absorbed current A 620 620 640 720 894Power consumption W7L35 kW 239 262 322 303 383Absorbed current W7L35 A 376 392 479 485 623FansAxial fans n° 16 16 16 24 24Fan flow m³/h 186770 199135 199135 280155 280155Max. Power consumption kW 35,2 35,2 35,2 52,8 52,8Max. absorbed current A 75,7 75,7 75,7 113,5 113,5Power Consumption W7L35 kW 20 20 20 30 30Absorbed Current W7L35 A 40 40 40 60 60HydraulicCoolant liquid Type Water + max 40% glycolInlet temperature °C 12 12 12 12 12Outlet temperature °C 7 7 7 7 7Water flow m³/h 134 146 164 181 200Pressure drops kPa 28 36 42 181 200Water connections Inches 8 8 8 8 8EEREER 2,75 2,77 2,52 2,90 2,57ESEER (ISO14511) 4,78 4,67 4,59 4,72 4,53IPLV 4,68 4,65 4,53 4,67 4,52

STANDARD - LOW NOISEEvaporator water (in/out) 12/7 °C; condenser air (in) 35 °C;Average sound pressure level at 10 m distance; unit in a free field on a reflective surface.According to ISO 3744. Unit at full capacity. Pump contribution is not considered.*In case of applications with an output fluid temperature below +5 °C, please contact the manufacturer.

FREE COOLING30% Glycol-Water solution. Evaporator solution IN/OUT= 15/10 °C; Condenser air 30 °CAverage sound pressure level, at 10m distance, unit in a free field on a reflective surface. Unit at full capacity. According to ISO 3744. Pumps contribution is not considered*In case of applications with output fluid temperature below 0°C, please contact the manufacturer

Page 14: WSA brochure_EN

14

Europe, America and Asia

The humidity of the tropics and arid heat of the desert requirecompletely different air conditioning solutions from the moderateclimes of the Northern Hemisphere. In addition, the demands ofEuropeans and Americans differ completely from those of Indiansand Chinese. Only by producing in the relevant market can youknow precisely what your customers want. This is why STULZ hasproduction sites in the world’s major growth regions. All overthe world, customers put their trust in product lines that answerperfectly to their requirements.

Co-operating globally, producing locally: For every region, STULZsupplies tailor-made products for individual requirements.

PRODUCTION SITES

Page 15: WSA brochure_EN

15

USA, Frederick, Maryland

America

Germany, Hamburg

Italy, Valeggio sul Mincio

China, Hangzhou China, Shanghai

India, Mumbai

Asia

Europe

Europe, America and Asia

Page 16: WSA brochure_EN

16

For more information, visit us at www.stulz.com

STULZ Worldwide

Headquarters Germany

Subsidiary companies Australia Austria Belgium China France Germany Great Britain India Italy Mexico Netherlands New Zealand Poland Singapore South Africa Spain USA

Production Germany China India Italy USA

Partners www.stulz.com/worldwide

Close to you all over the world: with 17 subsidiaries, 6 production sites and sales and service partners in more than 120 countriesIn 1971, we began specialising in the development and production of precision air conditioning units and chillers for data centers. Customers all over the world put their trust in our products and technical expertise. We continually invest in the latest technology and the qualified training of our employees and partners. From project planning and rollout to maintenance and service, we have systems and solutions for data centers of all sizes and with the most diverse requirements. Take advantage of our know-how.

16

STULZ business dataFounding year: 1947Number of STULZ A/C Systems employees worldwide: approx. 2,100Sales volume STULZ A/C Systems, worldwide: approx. €360 million

Page 17: WSA brochure_EN

17

German engineering In 1971, we began specialising in the development and production of precision air conditioning units and chillers for data centers. That‘s a wealth of experience – gathered from the many thousands of projects that we have implemented worldwide in the past 40 years. We have systems and solutions for data centres of all sizes and with the most diverse requirements. Take advantage of our know-how.

Custom-made

In line with your budget, STULZ draws up a detailed quotation based on your requirements in terms of performance, availability, required space and cost. Our specialists will put together an individual air conditioning system for you. In it, the internal precision air conditioning systems and external chillers are always viewed as an integrated system. And we will help you to draw up service specifications and invitations to tender.

Quality standards

STULZ delivers the best possible reliability levels by manufacturing its precision air conditioning units and chillers using high-quality components that meet very strict production standards. Every completed chiller undergoes comprehensive live mechanical and electrical testing on our running test bench. There‘s no other way to achieve 100% reliability.

17

Global expertise in chiller cooling from over 1,000 successful projects

Outdoor air-cooled Global Germany-wide Installed kW worldwide

Projects < 100 kW > 443 > 200 > 32,179

Projects 100 - 800 kW > 278 > 130 > 106,520

Total > 721 > 330 > 138,699