x800f

Upload: salah-osman

Post on 08-Apr-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/7/2019 X800F

    1/4

  • 8/7/2019 X800F

    2/4

    This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom

    without notice, in a constant effort to improve the quality of its products.

    SDMO Industries 12bis rue de la Villeneuve CS 92848 29 228 BREST CEDEX 2

    Tel +33 (0)2 98 41 41 41 Fax : +33 (0)2 98 41 63 07 www.sdmo.com

    ENGINE SPECIFICATIONS

    Motor modelMTU 12V2000G63F , 4-temps, TURBO , AIR/AIR

    12 X

    Cylinder arrangement V

    Displacement (C.I.) 23.89

    Bore (mm) X Stroke (mm) 130 X 150

    Compression ratio 16 : 1

    DATA Speed (RPM) 1500

    Pistons speed (m/s) 7.5

    GENERAL DATA Maximum stand-by power at rated RPM (kW) 652

    Frequency regulation (%) 0.5

    BMEP (bar) 19.99

    Governor type ELEC

    Exhaust gas temperature (F) 525

    EXHAUST SYSTEM Exhaust gas flow (L/s) 2210Max. exhaust back pressure (mm CE) 500

    Consumption @ 110% load (L/h) 159.2

    Consumption @ 100% load (L/h) 145.6

    FUEL SYSTEM Consumption @ 75% load (L/h) 108

    Consumption @ 50% load (L/h) 73

    Maximum fuel pump flow (L/hr) 450

    Oil capacity (L) 82

    Min. oil pressure (bar) 4

    OIL Max. oil pressure (bar) 6.5

    Oil consumption 100% load (L/h) 0.73

    Carter oil capacity (L) 67

    THERMAL

    BALANCEHeat rejection to exhaust (kW) 486

    Radiated heat to ambiant (kW) 45

    Haet rejection to coolant (kW) 260

    AIR INTAKE AIR INTAKE_entree_max% 150

    Intake air flow (L/s) 880

    Radiator & Engine capacity (L) 180

    Max water temperature (C) 97

    Outlet water temperature (C) 93

    Fan power (kW) 26

    COOLANT SYSTEM Fan air flow w/o restriction (m3/s) 16.2

    Available restriction on air flow (mm CE) 20

    Type of coolant COOLELF-MDX

    Thermostat (C) 75-88

    Emissions PM (g/kW.h) N/A

    EMISSIONS Emission CO (g/kW.h) N/A

    Emissions HCNOx (g/kWh) N/A

    Emission HC (g/kW.h) N/A

  • 8/7/2019 X800F

    3/4

    This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom

    without notice, in a constant effort to improve the quality of its products.

    SDMO Industries 12bis rue de la Villeneuve CS 92848 29 228 BREST CEDEX 2

    Tel +33 (0)2 98 41 41 41 Fax : +33 (0)2 98 41 63 07 www.sdmo.com

    ALTERNATOR SPECIFICATIONS

    Alternator brand LEROY SOMER

    Alternator LSA491M6

    Number of phase 3

    Power factor (Cos Phi) 0.8

    Altitude (m)

  • 8/7/2019 X800F

    4/4

    This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom

    without notice, in a constant effort to improve the quality of its products.

    SDMO Industries 12bis rue de la Villeneuve CS 92848 29 228 BREST CEDEX 2

    Tel +33 (0)2 98 41 41 41 Fax : +33 (0)2 98 41 63 07 www.sdmo.com

    CONTROL PANEL

    #STD_COFFRETStandard

    M80

    M80Specifications : Tachometer, Emergency stop button, clientconnection terminal strip, EC certifiedEngine parameters :Hours counter, Oil pressure gauge,Water temperature indicator, Oil pressure indicator

    Option TELYSTELYSSpecifications : Frequency meter, Ammeter, VoltmeterAlarms and faults : Oil pressure, water temperature, No

    start-up, Overspeed, Min/max alternator, Min/max batteryvoltage, Low fuel level, Emergency stopEngine parameters : Hours counter, Oil pressure, Watertemperature, Engine speed, Battery voltage, Fuel level

    Option KERYSKERYSSpecifications : Frequency meter, Ammeter, VoltmeterAlarms and faults : Oil pressure, water temperature, Nostart-up, Overspeed, Min/max alternator, Min/max batteryvoltage, Low fuel level, Emergency stopEngine parameters : Hours counter, Oil pressure, Watertemperature, Engine speed, Battery voltage, Fuel levelAdditional specifications :Website, Troubleshooting,Assistance and Maintenance, Plotting and logging, Load

    impact, 8 configurations available, Compliance withinternational standards...

    #OPT1

    #OPT2

    #OPT3