Maintenance-Free Sealed Lead Acid Battery. Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%. Design LifeFloat Charging VoltageUp to 10 Years in Standby Service at 2513.5 ~ 13.8 VDC/Unit at 25(77) Eurobat (20) : 10-12 years, Long Life Equalization Charging Voltage Operating Temperature Range14.4 ~ 15.0 VDC/Unit at 25(77) Self DischargeLess than 10% after 90 days, can be stored up to 6 months at 25(77); Fully recharging is required before usage, and charged sooner if stored Storage: -15~ 40(5~104) at higher temperature than 25(77). Design according with IEC 60896-21/22:2004 Nominal Capacity 1447A 18.3A Terminal Breaking Torque 138.6 Kgf·cm / 120.3 Lbf· in / 13.58 N·m Flame Retardant Polypropylene (UL 94-V0) Length (L) 228.0±2.5 mm 8.98±0.10 inch Width (W) 138.4±1.5 mm 5.45±0.06 inch Container Height (h) 201.3±2.5 mm 7.93±0.10 inch Overall Height (H) 206.3±2.5 mm 8.12±0.10 inch F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN 1.60V 322 255 230 209 174 149 112 89.5 65.6 47.8 38.1 27.8 1.67V 287 233 211 195 165 145 110 88.2 65.0 47.4 37.9 27.6 1.70V 269 220 202 187 160 141 108 87.1 64.5 47.1 37.7 27.5 1.75V 243 200 185 170 150 133 104 84.4 63.1 46.3 37.2 27.3 1.80V 208 177 163 153 136 121 97.8 80.2 60.6 44.8 36.2 26.8 1.85V 174 151 145 134 118 108 87.7 73.1 56.6 42.3 34.4 25.7 F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN 1.60V 3134 2536 2341 2140 1840 1610 1229 1002 752 551 442 324 1.67V 2906 2387 2197 2022 1773 1556 1209 990 746 548 440 323 1.70V 2772 2318 2115 1959 1735 1520 1195 980 741 545 438 322 1.75V 2520 2127 1965 1841 1627 1443 1161 956 728 537 433 320 1.80V 2308 1921 1806 1706 1491 1343 1094 910 702 522 423 315 1.85V 1847 1733 1595 1488 1333 1224 994 839 661 496 405 303 **Preliminary spec sheet Issued: 181217 Tel: +31(0)180-418-140 Tel: +886-2-2880-5600 Fax: +31(0)180-418-327 Fax: +866-2-2888-3300 Tel: +86-10-5820-5336, 5820-5338 Fax: +86-10-5820-3053 Fax: +86-755-8831-6075 Fax: +86-21-5046-1046 Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872) Fax: +1-817-244-4445 SHENZHEN OFFICE (CHINA) SHANGHAI OFFICE (CHINA) BEIJING OFFICE (CHINA) Tel: +86-755-8831-6488, 8831-6775 Tel: +86-21-5046-1622, 5046-0833 BUSINESS HEADQUARTERS Tel: +886-2-2880-5600 Fax: +866-2-2888-3300 USA OFFICE EUROPE (EMEA) OFFICE TAIPEI OFFICE Constant Current Discharge Characteristics Unit: A (25, 77) Constant Power Discharge Characteristics Unit: W (25, 77) Recognized under UL 1989, and certified by ISO 9001, 14001. Sales Offices Dimensions Short Circuit Current Maximum Charge Current Terminal types I2 thread lead alloy terminal to accept M6 bolt Container Material Internal Resistance Approx. 5.60 mΩ Nominal Operating Temperature : 25(77) Discharge : -15~ 50(5~122) Charge: -15~ 40(5~104) Specification Nominal Voltage 12V (6 cells per unit) 2200W @5min-rate to 9.60V per PCS @25(77) Weight Approx. 16.50 Kg (36.37 lbs) Maximum Discharge Current 400A (5sec) Design for Standby Power Applications XPL series XPL2200 12V 2200W Valve Regulated Lead Acid Battery

Upload: others

Post on 28-Sep-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: XPL series XPL2200 12V 2200W - toshiba.com · 1.67v 368 296 271 247 212 183 138 110 80.4 57.1 44.8 31.8 1.70v 348 283 259 238 205 178 135 108 79.7 56.7 44.5 31.7 1.75v 315 258 237

Maintenance-Free Sealed Lead Acid Battery.

Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.

【Design Life】 【 Float Charging Voltage】

Up to 10 Years in Standby Service at 25℃ 13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)

Eurobat (20℃) : 10-12 years, Long Life 【Equalization Charging Voltage 】

【 Operating Temperature Range】 14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)

【 Self Discharge】

Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);

Fully recharging is required before usage, and charged sooner if stored

Storage: -15℃ ~ 40℃ (5℉~104℉) at higher temperature than 25℃ (77℉).

Design according with IEC 60896-21/22:2004

Nominal Capacity

1447A

18.3A

Terminal Breaking Torque 138.6 Kgf·cm / 120.3 Lbf·in / 13.58 N·m

Flame Retardant Polypropylene (UL 94-V0)

Length (L) 228.0±2.5 mm 8.98±0.10 inch

Width (W) 138.4±1.5 mm 5.45±0.06 inch

Container Height (h) 201.3±2.5 mm 7.93±0.10 inch

Overall Height (H) 206.3±2.5 mm 8.12±0.10 inch

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 322 255 230 209 174 149 112 89.5 65.6 47.8 38.1 27.81.67V 287 233 211 195 165 145 110 88.2 65.0 47.4 37.9 27.61.70V 269 220 202 187 160 141 108 87.1 64.5 47.1 37.7 27.51.75V 243 200 185 170 150 133 104 84.4 63.1 46.3 37.2 27.31.80V 208 177 163 153 136 121 97.8 80.2 60.6 44.8 36.2 26.81.85V 174 151 145 134 118 108 87.7 73.1 56.6 42.3 34.4 25.7

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 3134 2536 2341 2140 1840 1610 1229 1002 752 551 442 3241.67V 2906 2387 2197 2022 1773 1556 1209 990 746 548 440 3231.70V 2772 2318 2115 1959 1735 1520 1195 980 741 545 438 3221.75V 2520 2127 1965 1841 1627 1443 1161 956 728 537 433 3201.80V 2308 1921 1806 1706 1491 1343 1094 910 702 522 423 3151.85V 1847 1733 1595 1488 1333 1224 994 839 661 496 405 303

**Preliminary spec sheet Issued: 181217

Tel: +31(0)180-418-140 Tel: +886-2-2880-5600 Fax: +31(0)180-418-327 Fax: +866-2-2888-3300

Tel: +86-10-5820-5336, 5820-5338 Fax: +86-10-5820-3053 Fax: +86-755-8831-6075 Fax: +86-21-5046-1046

Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872) Fax: +1-817-244-4445

SHENZHEN OFFICE (CHINA) SHANGHAI OFFICE (CHINA) BEIJING OFFICE (CHINA)

Tel: +86-755-8831-6488, 8831-6775 Tel: +86-21-5046-1622, 5046-0833

BUSINESS HEADQUARTERS Tel: +886-2-2880-5600 Fax: +866-2-2888-3300

USA OFFICE EUROPE (EMEA) OFFICE TAIPEI OFFICE

Constant Current Discharge Characteristics Unit: A (25℃, 77℉)

Constant Power Discharge Characteristics Unit: W (25℃, 77℉)

Recognized under UL 1989,

and certified by ISO 9001, 14001.

Sales Offices

Dimensions

Short Circuit Current

Maximum Charge Current

Terminal types I2 thread lead alloy terminal to accept M6 bolt

Container Material

Internal Resistance Approx. 5.60 mΩ

Nominal Operating Temperature : 25℃(77℉)

Discharge : -15℃ ~ 50℃ (5℉~122℉)

Charge: -15℃ ~ 40℃ (5℉~104℉)

SpecificationNominal Voltage 12V (6 cells per unit)

2200W @5min-rate to 9.60V per PCS @25℃ (77℉)

Weight Approx. 16.50 Kg (36.37 lbs)

Maximum Discharge Current 400A (5sec)

Design for Standby Power Applications

XPL series

XPL2200 12V 2200W

Valve Regulated Lead Acid Battery

Page 2: XPL series XPL2200 12V 2200W - toshiba.com · 1.67v 368 296 271 247 212 183 138 110 80.4 57.1 44.8 31.8 1.70v 348 283 259 238 205 178 135 108 79.7 56.7 44.5 31.7 1.75v 315 258 237

Maintenance-Free Sealed Lead Acid Battery.

Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.

【Design Life】 【 Float Charging Voltage】

Up to 10 Years in Standby Service at 25℃ 13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)

Eurobat (20℃) : 10-12 years, Long Life 【Equalization Charging Voltage 】

【 Operating Temperature Range】 14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)

【 Self Discharge】

Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);

Fully recharging is required before usage, and charged sooner if stored

Storage: -15℃ ~ 40℃ (5℉~104℉) at higher temperature than 25℃ (77℉).

Design according with IEC 60896-21/22:2004

Nominal Capacity

1781A

22.5A

Terminal Breaking Torque 138.6 Kgf·cm / 120.3 Lbf·in / 13.58 N·m

Flame Retardant Polypropylene (UL 94-V0)

Length (L) 228.0±2.5 mm 8.98±0.10 inch

Width (W) 138.4±1.5 mm 5.45±0.06 inch

Container Height (h) 201.3±2.5 mm 7.93±0.10 inch

Overall Height (H) 206.3±2.5 mm 8.12±0.10 inch

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 403 326 293 267 224 192 142 113 81.4 57.7 45.2 32.01.67V 368 296 271 247 212 183 138 110 80.4 57.1 44.8 31.81.70V 348 283 259 238 205 178 135 108 79.7 56.7 44.5 31.71.75V 315 258 237 221 190 168 129 105 77.6 55.5 43.8 31.31.80V 277 231 216 198 173 154 121 98.7 74.1 53.4 42.4 30.51.85V 234 201 185 173 153 137 111 90.9 68.6 49.9 39.9 29.0

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 3948 3231 2934 2712 2317 2025 1546 1248 923 663 524 3771.67V 3665 3017 2779 2598 2220 1966 1516 1229 914 658 521 3751.70V 3524 2914 2703 2512 2165 1926 1495 1214 906 653 518 3731.75V 3287 2734 2550 2345 2055 1830 1444 1179 886 642 510 3691.80V 2950 2525 2314 2155 1917 1702 1372 1126 851 620 496 3611.85V 2610 2205 2064 1955 1714 1545 1270 1046 796 585 470 345

**Preliminary spec sheet Issued: 181217

Tel: +31(0)180-418-140 Tel: +886-2-2880-5600 Fax: +31(0)180-418-327 Fax: +866-2-2888-3300

Tel: +86-10-5820-5336, 5820-5338 Fax: +86-10-5820-3053 Fax: +86-755-8831-6075 Fax: +86-21-5046-1046

Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872) Fax: +1-817-244-4445

SHENZHEN OFFICE (CHINA) SHANGHAI OFFICE (CHINA) BEIJING OFFICE (CHINA)

Tel: +86-755-8831-6488, 8831-6775 Tel: +86-21-5046-1622, 5046-0833

BUSINESS HEADQUARTERS Tel: +886-2-2880-5600 Fax: +866-2-2888-3300

USA OFFICE EUROPE (EMEA) OFFICE TAIPEI OFFICE

Constant Current Discharge Characteristics Unit: A (25℃, 77℉)

Constant Power Discharge Characteristics Unit: W (25℃, 77℉)

Recognized under UL 1989,

and certified by ISO 9001, 14001.

Sales Offices

Dimensions

Short Circuit Current

Maximum Charge Current

Terminal types I2 thread lead alloy terminal to accept M6 bolt

Container Material

Internal Resistance Approx. 4.20 mΩ

Nominal Operating Temperature : 25℃(77℉)

Discharge : -15℃ ~ 50℃ (5℉~122℉)

Charge: -15℃ ~ 40℃ (5℉~104℉)

SpecificationNominal Voltage 12V (6 cells per unit)

2700W @5min-rate to 9.60V per PCS @25℃ (77℉)

Weight Approx. 18.30 Kg (40.33 lbs)

Maximum Discharge Current 400A (5sec)

XPL series

XPL2700 12V 2700W

Valve Regulated Lead Acid Battery

Design for Standby Power Applications

Page 3: XPL series XPL2200 12V 2200W - toshiba.com · 1.67v 368 296 271 247 212 183 138 110 80.4 57.1 44.8 31.8 1.70v 348 283 259 238 205 178 135 108 79.7 56.7 44.5 31.7 1.75v 315 258 237

Maintenance-Free Sealed Lead Acid Battery.

Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.

【Design Life】 【 Float Charging Voltage】

Up to 10 Years in Standby Service at 25℃ 13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)

Eurobat (20℃) : 10-12 years, Long Life 【Equalization Charging Voltage 】

【 Operating Temperature Range】 14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)

【 Self Discharge】

Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);

Fully recharging is required before usage, and charged sooner if stored

Storage: -15℃ ~ 40℃ (5℉~104℉) at higher temperature than 25℃ (77℉).

Design according with IEC 60896-21/22:2004

Nominal Capacity

--

32A

Terminal hardware Torque 138.6 Kgf·cm / 120.3 Lbf·in / 13.58 N·m

Flame Retardant Polypropylene (UL 94-V0)

Length (L) 261.0±2.5 mm 10.28±0.10 inch

Width (W) 168.5±2.0 mm 6.63±0.08 inch

Container Height (h) 210.5±2.5 mm 8.29±0.10 inch

Overall Height (H) 213.5±2.5 mm 8.41±0.10 inch

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V1.67V1.70V1.75V1.80V1.85V

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 4800 3862 3544 3304 2883 2539 1955 1573 1158 842 671 4881.67V 4475 3593 3348 3160 2752 2457 1912 1547 1148 836 667 4851.70V 4205 3464 3254 3074 2680 2406 1882 1528 1139 831 664 4841.75V 3725 3242 3080 2856 2535 2284 1810 1481 1116 817 655 4801.80V 3246 2996 2778 2612 2352 2130 1707 1407 1070 790 637 4701.85V 3032 2601 2475 2349 2116 1906 1555 1292 995 743 603 450

**Preliminary spec sheet Issued: 180213

Tel: +31(0)180-418-140 Tel: +886-2-2880-5600 Fax: +31(0)180-418-327 Fax: +866-2-2888-3300

Tel: +86-10-5820-5336, 5820-5338 Fax: +86-10-5820-3053 Fax: +86-755-8831-6075 Fax: +86-21-5046-1046

Fax: +1-817-244-4445

SHENZHEN OFFICE (CHINA) SHANGHAI OFFICE (CHINA) BEIJING OFFICE (CHINA)

Tel: +86-755-8831-6488, 8831-6775 Tel: +86-21-5046-1622, 5046-0833

Tel: +886-2-2880-5600 Fax: +866-2-2888-3300

USA OFFICE EUROPE (EMEA) OFFICE TAIPEI OFFICE Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872)

Constant Power Discharge Characteristics Unit: W (25℃, 77℉)

Recognized under UL 1989,

and certified by ISO 9001, 14001.

Sales Offices

Constant Current Discharge Characteristics Unit: A (25℃, 77℉)

Maximum Charge Current

Short Circuit Current

Terminal types

Container Material

BUSINESS HEADQUARTERS

Dimensions

I2 thread lead alloy terminal to accept M6 bolt

800A (5sec)

XPL series

XPL3500 12V 3500W

Valve Regulated Lead Acid Battery

Design for Standby Power Applications

G24

Nominal Operating Temperature : 25℃(77℉)

Internal Resistance Approx. 3.70 mΩ

Discharge : -15℃ ~ 50℃ (5℉~122℉)

Charge: -15℃ ~ 40℃ (5℉~104℉)

SpecificationNominal Voltage 12V (6 cells per unit)

3500W @5min-rate to 1.60V per PCS @25℃ (77℉)

Weight Approx. 25.70 Kg (56.64 lbs)

Maximum Discharge Current

Page 4: XPL series XPL2200 12V 2200W - toshiba.com · 1.67v 368 296 271 247 212 183 138 110 80.4 57.1 44.8 31.8 1.70v 348 283 259 238 205 178 135 108 79.7 56.7 44.5 31.7 1.75v 315 258 237

Maintenance-Free Sealed Lead Acid Battery.

Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.

【Design Life】 【 Float Charging Voltage】

Up to 10 Years in Standby Service at 25℃ 13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)

Eurobat (20℃) : 10-12 years, Long Life 【Equalization Charging Voltage 】

【 Operating Temperature Range】 14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)

【 Self Discharge】

Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);

Fully recharging is required before usage, and charged sooner if stored

Storage: -15℃ ~ 40℃ (5℉~104℉) at higher temperature than 25℃ (77℉).

Design according with IEC 60896-21/22:2004

Nominal Capacity

--

37A

Terminal hardware Torque 138.6 Kgf·cm / 120.3 Lbf·in / 13.58 N·m

Flame Retardant Polypropylene (UL 94-V0)

Length (L) 261.0±2.5 mm 10.28±0.10 inch

Width (W) 168.5±2.0 mm 6.63±0.08 inch

Container Height (h) 210.5±2.5 mm 8.29±0.10 inch

Overall Height (H) 213.5±2.5 mm 8.41±0.10 inch

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V1.67V1.70V1.75V1.80V1.85V

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 5495 4614 4217 3918 3406 2999 2282 1834 1348 968 766 5501.67V 5068 4277 3963 3738 3228 2882 2221 1797 1334 960 761 5481.70V 4873 4118 3841 3594 3133 2816 2181 1772 1323 954 757 5461.75V 4575 3842 3591 3328 2951 2655 2091 1713 1294 938 747 5411.80V 4009 3488 3231 3036 2739 2439 1969 1625 1240 906 725 5301.85V 3535 3020 2871 2739 2417 2185 1789 1491 1153 850 684 504

**Preliminary spec sheet Issued: 180213

Tel: +31(0)180-418-140 Tel: +886-2-2880-5600 Fax: +31(0)180-418-327 Fax: +866-2-2888-3300

Tel: +86-10-5820-5336, 5820-5338 Fax: +86-10-5820-3053

4200W @5min-rate to 1.60V per PCS @25℃ (77℉)

XPL series

XPL4200 12V 4200W

Valve Regulated Lead Acid Battery

Design for Standby Power Applications

Nominal Operating Temperature : 25℃(77℉)

Discharge : -15℃ ~ 50℃ (5℉~122℉)

Charge: -15℃ ~ 40℃ (5℉~104℉)

SpecificationNominal Voltage 12V (6 cells per unit)

Weight Approx. 28.20 Kg (62.15 lbs)

Maximum Discharge Current 800A (5sec)

Internal Resistance Approx. 3.20 mΩ

Short Circuit Current

Maximum Charge Current

Terminal types I2 thread lead alloy terminal to accept M6 bolt

Container Material

USA OFFICE EUROPE (EMEA) OFFICE TAIPEI OFFICE

Constant Current Discharge Characteristics Unit: A (25℃, 77℉)

Constant Power Discharge Characteristics Unit: W (25℃, 77℉)

Recognized under UL 1989,

and certified by ISO 9001, 14001.

Sales Offices

Dimensions

G24

Fax: +86-755-8831-6075 Fax: +86-21-5046-1046

Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872) Fax: +1-817-244-4445

SHENZHEN OFFICE (CHINA) SHANGHAI OFFICE (CHINA) BEIJING OFFICE (CHINA)

Tel: +86-755-8831-6488, 8831-6775 Tel: +86-21-5046-1622, 5046-0833

BUSINESS HEADQUARTERS Tel: +886-2-2880-5600 Fax: +866-2-2888-3300

Page 5: XPL series XPL2200 12V 2200W - toshiba.com · 1.67v 368 296 271 247 212 183 138 110 80.4 57.1 44.8 31.8 1.70v 348 283 259 238 205 178 135 108 79.7 56.7 44.5 31.7 1.75v 315 258 237

Maintenance-Free Sealed Lead Acid Battery.

Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.

【Design Life】 【 Float Charging Voltage】

Up to 10 Years in Standby Service at 25℃ 13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)

Eurobat (20℃) : 10-12 years, Long Life 【Equalization Charging Voltage 】

【 Operating Temperature Range】 14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)

【 Self Discharge】

Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);

Fully recharging is required before usage, and charged sooner if stored

Storage: -15℃ ~ 40℃ (5℉~104℉) at higher temperature than 25℃ (77℉).

Design according with IEC 60896-21/22:2004

Nominal Capacity

--

43A

Terminal hardware Torque 138.6 Kgf·cm / 120.3 Lbf·in / 13.58 N·m

Flame Retardant Polypropylene (UL 94-V0)

Length (L) 308.7±2.5 mm 12.15±0.10 inch

Width (W) 169.0±2.0 mm 6.65±0.08 inch

Container Height (h) 210.6±2.5 mm 8.29±0.10 inch

Overall Height (H) 213.6±2.5 mm 8.41±0.10 inch

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V1.67V1.70V1.75V1.80V1.85V

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 5941 5032 4768 4519 3933 3487 2717 2189 1613 1154 910 6511.67V 5489 4786 4549 4264 3717 3341 2633 2137 1593 1142 902 6471.70V 5266 4673 4395 4097 3606 3254 2580 2104 1578 1134 897 6451.75V 4839 4376 4065 3792 3398 3078 2465 2025 1535 1109 881 6371.80V 4602 3920 3665 3469 3133 2836 2315 1913 1463 1066 851 6201.85V 3873 3439 3281 3105 2787 2537 2090 1745 1353 995 800 588

**Preliminary spec sheet Issued: 180213

Tel: +31(0)180-418-140 Tel: +886-2-2880-5600 Fax: +31(0)180-418-327 Fax: +866-2-2888-3300

Tel: +86-10-5820-5336, 5820-5338 Fax: +86-10-5820-3053

4700W @5min-rate to 1.60V per PCS @25℃ (77℉)

XPL series

XPL4700 12V 4700W

Valve Regulated Lead Acid Battery

Design for Standby Power Applications

Nominal Operating Temperature : 25℃(77℉)

Discharge : -15℃ ~ 50℃ (5℉~122℉)

Charge: -15℃ ~ 40℃ (5℉~104℉)

SpecificationNominal Voltage 12V (6 cells per unit)

Weight Approx. 32.40 Kg (71.41 lbs)

Maximum Discharge Current 800A (5sec)

Internal Resistance Approx. 3.00 mΩ

Short Circuit Current

Maximum Charge Current

Terminal types I2 thread lead alloy terminal to accept M6 bolt

Container Material

USA OFFICE EUROPE (EMEA) OFFICE TAIPEI OFFICE

Constant Current Discharge Characteristics Unit: A (25℃, 77℉)

Constant Power Discharge Characteristics Unit: W (25℃, 77℉)

Recognized under UL 1989,

and certified by ISO 9001, 14001.

Sales Offices

Dimensions

G27

Fax: +86-755-8831-6075 Fax: +86-21-5046-1046

Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872) Fax: +1-817-244-4445

SHENZHEN OFFICE (CHINA) SHANGHAI OFFICE (CHINA) BEIJING OFFICE (CHINA)

Tel: +86-755-8831-6488, 8831-6775 Tel: +86-21-5046-1622, 5046-0833

BUSINESS HEADQUARTERS Tel: +886-2-2880-5600 Fax: +866-2-2888-3300

Page 6: XPL series XPL2200 12V 2200W - toshiba.com · 1.67v 368 296 271 247 212 183 138 110 80.4 57.1 44.8 31.8 1.70v 348 283 259 238 205 178 135 108 79.7 56.7 44.5 31.7 1.75v 315 258 237

Maintenance-Free Sealed Lead Acid Battery.

Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.

【Design Life】 【 Float Charging Voltage】

Up to 10 Years in Standby Service at 25℃ 13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)

Eurobat (20℃) : 10-12 years, Long Life 【Equalization Charging Voltage 】

【 Operating Temperature Range】 14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)

【 Self Discharge】

Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);

Fully recharging is required before usage, and charged sooner if stored

Storage: -15℃ ~ 40℃ (5℉~104℉) at higher temperature than 25℃ (77℉).

Design according with IEC 60896-21/22:2004

Nominal Capacity

--

50A

Terminal hardware Torque 138.6 (126) Kgf·cm / 120.3 (109.4) Lbf·in / 13.58 (12.35) N·m

Flame Retardant Polypropylene (UL 94-V0)

Length (L) 343.0±2.5 mm 13.50±0.10 inch

Width (W) 170.0±2.0 mm 6.69±0.08 inch

Container Height (h) 213.9±2.5 mm 8.42±0.10 inch

Overall Height (H) 216.9±2.5 mm 8.54±0.10 inch

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 780 620 564 509 428 367 272 214 153 108 84.4 59.51.67V 700 567 512 472 401 350 264 210 151 107 83.5 58.91.70V 661 536 490 454 386 340 259 206 150 106 82.9 58.61.75V 592 486 449 412 359 317 247 199 146 104 81.7 58.11.80V 514 434 397 369 324 288 231 187 139 100 79.3 57.11.85V 444 369 348 323 283 255 204 168 128 93.2 74.3 54.0

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 7739 6297 5777 5353 4610 4000 3086 2464 1794 1278 1005 7171.67V 7118 5911 5473 5057 4377 3845 3017 2420 1774 1267 998 7131.70V 6831 5714 5296 4906 4247 3753 2967 2389 1760 1259 993 7101.75V 6352 5357 4941 4605 3986 3565 2847 2311 1722 1238 980 7051.80V 5765 4877 4516 4169 3676 3334 2677 2191 1652 1198 953 6911.85V 5054 4256 3933 3688 3332 3056 2454 2022 1539 1126 902 660

**Preliminary spec sheet Issued: 180517

Tel: +31(0)180-418-140 Tel: +886-2-2880-5600 Fax: +31(0)180-418-327 Fax: +866-2-2888-3300

Tel: +86-10-5820-5336, 5820-5338 Fax: +86-10-5820-3053

Weight Approx. 36.10 Kg (79.56 lbs)

Maximum Discharge Current 800A (5sec)

Internal Resistance Approx. 2.30 mΩ

G31

5700W @5min-rate to 9.60V per PCS @25℃ (77℉)

Nominal Operating Temperature : 25℃(77℉)

Discharge : -15℃ ~ 50℃ (5℉~122℉)

Charge: -15℃ ~ 40℃ (5℉~104℉)

SpecificationNominal Voltage 12V (6 cells per unit)

XPL series

XPL5700 12V 5700W

Valve Regulated Lead Acid Battery

Design for Standby Power Applications

Short Circuit Current

Maximum Charge Current

Terminal types I2 thread lead alloy terminal to accept M6 bolt

Container Material

Constant Current Discharge Characteristics Unit: A (25℃, 77℉)

Constant Power Discharge Characteristics Unit: W (25℃, 77℉)

Recognized under UL 1989,

and certified by ISO 9001, 14001.

Sales Offices

Dimensions

BEIJING OFFICE (CHINA)

Tel: +86-755-8831-6488, 8831-6775 Tel: +86-21-5046-1622, 5046-0833

BUSINESS HEADQUARTERS Tel: +886-2-2880-5600 Fax: +866-2-2888-3300

USA OFFICE EUROPE (EMEA) OFFICE TAIPEI OFFICE

Fax: +86-755-8831-6075 Fax: +86-21-5046-1046

Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872) Fax: +1-817-244-4445

SHENZHEN OFFICE (CHINA) SHANGHAI OFFICE (CHINA)

Page 7: XPL series XPL2200 12V 2200W - toshiba.com · 1.67v 368 296 271 247 212 183 138 110 80.4 57.1 44.8 31.8 1.70v 348 283 259 238 205 178 135 108 79.7 56.7 44.5 31.7 1.75v 315 258 237

Maintenance-Free Sealed Lead Acid Battery.

Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.

【Design Life】 【 Float Charging Voltage】

Up to 10 Years in Standby Service at 25℃ 13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)

Eurobat (20℃) : 10-12 years, Long Life 【Equalization Charging Voltage 】

【 Operating Temperature Range】 14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)

【 Self Discharge】

Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);

Fully recharging is required before usage, and charged sooner if stored

Storage: -15℃ ~ 40℃ (5℉~104℉) at higher temperature than 25℃ (77℉).

Design according with IEC 60896-21/22:2004

Nominal Capacity

3722A

62A

Terminal hardware Torque 138.6 Kgf·cm / 120.3 Lbf·in / 13.58 N·m

Flame Retardant Polypropylene (UL 94-V0)

Length (L) 343.0±2.5 mm 13.50±0.10 inch

Width (W) 170.0±2.0 mm 6.69±0.08 inch

Container Height (h) 273.2±2.5 mm 10.76±0.10 inch

Overall Height (H) 275.7±2.5 mm 10.85±0.10 inch

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V1.67V1.70V1.75V1.80V1.85V

F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN1.60V 8440 7255 6774 6349 5650 5092 4039 3261 2422 1762 1392 10031.67V 7840 6754 6329 5959 5361 4882 3911 3179 2383 1740 1379 9971.70V 7552 6512 6094 5774 5196 4783 3829 3124 2353 1724 1369 9931.75V 6857 6011 5718 5408 4894 4459 3623 2984 2278 1681 1342 9811.80V 6077 5461 5155 4917 4482 4083 3322 2776 2163 1612 1295 9561.85V 5221 4792 4604 4343 3961 3639 2942 2505 2006 1507 1219 907

Please refer to the official site for the latest rating confirmation. URL: www.csb-battery.com**Preliminary spec sheet Issued: 180213

Tel: +31(0)180-418-140 Tel: +886-2-2880-5600 Fax: +31(0)180-418-327 Fax: +866-2-2888-3300

Tel: +86-10-5820-5336, 5820-5338 Fax: +86-10-5820-3053

Recognized under UL 1989,

and certified by ISO 9001, 14001.

Sales Offices

Short Circuit Current

Maximum Charge Current

Terminal types I2 thread lead alloy terminal to accept M6 bolt

Container Material

Fax: +86-755-8831-6075 Fax: +86-21-5046-1046 Tel: +86-755-8831-6488, 8831-6775 Tel: +86-21-5046-1622, 5046-0833

31T

Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872) Fax: +1-817-244-4445

SHENZHEN OFFICE (CHINA) SHANGHAI OFFICE (CHINA) BEIJING OFFICE (CHINA)

BUSINESS HEADQUARTERS Tel: +886-2-2880-5600 Fax: +866-2-2888-3300

USA OFFICE EUROPE (EMEA) OFFICE TAIPEI OFFICE

Constant Current Discharge Characteristics Unit: A (25℃, 77℉)

Constant Power Discharge Characteristics Unit: W (25℃, 77℉)

Dimensions

Weight Approx. 47.20 Kg (104.03 lbs)

Maximum Discharge Current 800A (5sec)

Internal Resistance Approx. 2.40 mΩ

6700W @5min-rate to 1.60V per PCS @25℃ (77℉)

XPL series

XPL6700 12V 6700W

Valve Regulated Lead Acid Battery

Design for Standby Power Applications

Nominal Operating Temperature : 25℃(77℉)

Discharge : -15℃ ~ 50℃ (5℉~122℉)

Charge: -15℃ ~ 40℃ (5℉~104℉)

SpecificationNominal Voltage 12V (6 cells per unit)