y2e2 – hvac sequence of operation (controls) · hvac systems at y2e2 cee 243 control basics...

40
Copyright 2011 HVAC Systems at Y2E2 CEE 243 Y2E2 HVAC sequence of operation (controls) James O’Donnell

Upload: phunghanh

Post on 22-Jul-2019

226 views

Category:

Documents


1 download

TRANSCRIPT

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Y2E2 – HVAC sequence of operation

(controls)

James O’Donnell

Copyright 2011

HVAC Systems at Y2E2

CEE 243

What we will learn today?

• Basics of controls

• Control sequences for each subsystem at

Y2E2

• Resources for Y2E2

– Mechanical Equipment pdf

2

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Control basics

• Typically components have a setpoint, i.e., operating functional objective,

• Under computer control, the HVAC system uses active components to maintain the setpoint.

• Active components can be regulated by the control system (e.g., damper 0 – 100% open)

• Rules “tell” control system how to reach setpoint.

• Control system has input sensors and output control signals

– control signals regulate the active components

3

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Simple control example – Active beam

4

constant

75 F

71 F

Assume system setpoint temp = 73 F

Occupied and unoccupied setpoint

Setpoint user adjustable by +/- 3 F

Deadband of +/- 2 F

User override lasts 2 hours

Point # 6370001

Description Space air temp

Setpoint –

Occupied

73

Setpoint –

Unoccupied

68

Deadband +- 2 F

Units O F

Zone Room #

System AHU-1, 2 or 3

User

adjustable?

+- 3 F

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Deadband control

5

0

20

40

60

80

100

120

0

100

200

300

400

500

600

700

800

900

1000

65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85

Va

lve

Po

sit

ion

pe

rce

nt

Air

flo

w C

FM

Temperature deg F

Air Flow

Cooling Valve

Heating Valve

DEAD

BAND

Setpoint

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Active beams

• Active components: Cold and hot water valves, air flow damper

• Temperature control– Occupied temperature setpoint is adjustable by the user +/- 3F

– Unoccupied setpoints cooling: 78F heating: 65F

– Control cold and/or hot water valve of active beam to achieve temperature setpoint

– Temperature deadband of +/- 2F

– User override button to extend occupied hours by 2 hours

• Air flow control– Air flow is constant (on during occupied hours (basement 24/7),

off during unoccupied hours)

– CAV boxes modulate flow to achieve constant air flow during occupied hours only, except during night setback and warmup(compensating for different air pressures)

6

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Space with radiators

7

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Baseboard radiators

• Active components: hot water control valve

• Temperature control– Occupied temperature setpoint is adjustable by

the user +/- 3F

– Unoccupied temperature setpoints heating: 65F

– Control hot water valve of baseboard heater to achieve temperature setpoint

– If outside air temperature is above 78F close valve at all times

– User override button to extend occupied hours by 2 hours

8

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Conference rooms

• Active beam control as in other rooms

• Active component: inline supply fan

• Additionally CO2 level control

– If CO2 concentration exceeds max CO2

setpoint, turn on inline supply fan

– Max CO2 setpoint is 500 ppm above outside

air CO2 concentration

9

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Laboratories

• Active components: damper, water coil valves

• Air flow control

– The greater of:• The required air changes (6 ac/hr)

• Proper amount needed for cooling

• Sufficient makeup air for fume hoods (supply ~ exhaust)

– For heating air flow is set to minimum

– For cooling air flow is set to maximum

• Temperature control

– +/- 2F deadband

10

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Radiant floor

11

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Radiant floor

• Active components: Pump and valve

• Off if outside air temperature > 78F

• Otherwise– Turn on pump

– To reach steady state:• Increase valve position by 10% (every 10 min) until

temperature setpoint of 71F is met

• Decrease valve position by 5% (every 10 min) until temperature setpoint of 71F is met

– After reaching steady state• Adjust valve position by 1% (every 10 min) only

• During unoccupied hours setpoint = 66F

12

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Fan Coil Units

13

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Fan coil units

• Active components: chilled water control valve

• On 24/7

• Temperature control:

– Modulate chilled water valve to achieve temperature setpoint if space temperature is above setpoint

– If two spaces are controlled by one unit, use higher temperature

14

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Main chilled water loop

Serves:

• Tempered water loop

• Cooling coils

(AHUs, FC, CVs,

VAVs)

• Server Rack

15

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Chilled water system

• Active components: Control valve and booster pump

• Normal operation: Valve is used to control differential pressure to setpoint (if not enough booster pump helps out)

• If water return temp < 58F (for > 5 min) reset down differential pressure setpoint

• If water return temp < 55F (for > 5 min), start pump and recirculate water– If water supply temp < 48F go back to normal

16

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Tempered chilled water loop

Serves:

• Active beams

17

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Tempered chilled water system

• Active components: Two pumps

• On/off speed control– Lead/lag operation (weekly)

– Pumps are controlled to meet differential pressure setpoint • lead pumps first

• If pressure difference to small lag pump starts in addition

• If both are running slow (< 25Hz), turn off lag pump

– Pumps should be off during unoccupied hours (expect overrides)

• Temperature control– Maintain supply water temperature at 60F by opening and closing

control valve

• Supply Temp Reset (to prevent condensation on active beams)– If outside dewpoint temperature > 58F

-> supply temperature setpoint = dewpoint temperature + 2F

18

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Main hot water loop

Serves:

• Tempered water loop

• Heating coils (AHU + CVs)

• Radiators19

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Hot water system

• Active components: Two pumps, heat exchanger valve

• On/Off speed control– Same as for tempered chilled water system

– If no hot water is needed close heat exchanger valve

• Temperature control– Maintain supply water temperature at 180F by

opening and closing value 1 (1/3 of flow) and valve 2 (2/3 of flow)

20

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Tempered hot water loop

Serves:

• Active beams

• Radiant slab

• Heating coils (VAVs)

21

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Tempered hot water system

• Active components: Two pumps, valve

• On/Off speed control

– Same as for hot water system

• Temperature control

– Maintain supply water temperature at 110F

by opening and closing value

22

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Air handling unit

23

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Air Handling Units (1)

• Active components: fans, heating and cooling coil water valve, heat recovery bypass valve, cooling coil bypass valve

• 24/7 because of labs in the basement

• Maintain total pressure setpoint by modulating fan speed

• Supply air to be maintained at 65F (max DewPoint 60F)

• Cooling, Heating, Dehumidification, Morning Warm-up

24

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Air Handling Units (2) - cooling

• Active components: heat recovery bypass damper, cooling coil bypass damper, cooling coil valve

• Heat recovery– If outside air temperature > exhaust air temperture -> heat

recovery bypass damper closed (heat recovery “on”) otherwise open

– Heat recovery bypass damper modulates to set supply air temperature to setpoint

• Cooling– If no heating and supply air temperature > setpoint

-> cooling coil bypass damper closed and cooling coil valve modulates to achieve setpoint

– If no heating and supply air temperature < setpoint-> first close valve then close bypass damper

25

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Air Handling Units (3) - heating

• Active components: heat recovery bypass damper, cooling coil bypass damper, cooling coil valve

• Heat recovery– If outside air temperature < heat recovery leaving temperature

& exhaust air temperature > heat recovery leaving temperature -> heat recovery bypass damper closed (heat recovery “on”) otherwise open

– Heat recovery bypass damper modulates to set supply air temperature to setpoint

• Heating– If no cooling and supply air temperature < setpoint

-> heating coil bypass damper closed and heating coil valve modulates to achieve setpoint

– If no cooling and supply air temperature > setpoint-> first close valve then close bypass damper

26

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Air Handling Units (4) - dehumidification

• If leaving air dewpoint temperature > 60 F

then achieve dewpoint setpoint in addition

to temperature setpoint with additional

heating to lower moisture content in air

27

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Air Handling Units (5) – Morning warmup

• Only if daytime temperature does not

exceed 68F

– 2-6 am air supply temperature setpoint is set

to 69F

– After 6am everything is set to normal

– Mardyke example

28

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Exhaust fans

• Functional Intent?

• Flow Rate 7500 cfm

• Possible Energy Conservation Measures

(ECM)?

29

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Mechanical ventilation

30

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Building pressurization control

• Basement:

– Labs: Negative pressure: 5-10% more

exhaust air than supply

– Offices: Positive pressure: 5-10% more

supply air than exhaust

• Above Grade levels:

– If static pressure rises above 0.03” w.c. atria

dampers open to keep pressure below 0.03”

31

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Natural ventilation

32

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Natural ventilation

• Active components: Operable windows, atria damper

• Initial range for natural ventilation outside air temperature 68 – 85F

• If outdoor temperature is within range & average space temperature > 70F -> open dampers– For each zone where temperature > 70F open operable windows

– If zone temperature < 70F for at least 5 min close windows again

– If all windows around one atrium are closed also close corresponding atrium damper

• Night purge (if daytime outside air temperature exceeds 75F)– During unoccupied hours open windows if

• Outside air temperature < 65F and space temperature > 65F

– Close windows if space temperature < 63F

33

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Representative offices in Y2E2

2 offices on the North side with radiant

heating and ceiling fans

34

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Representative offices in Y2E2

2 offices on the South side with active

beams (heating and cooling)

35

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Other Measurements

• Weather

• PV

• Electrical Sub-meters

36

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Electricity

37

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Reading Material

• Summary of Performance Analyses of a

Santa Clara County Facility by CEE 243

Student Groups

• LEED Report by Turner and Frankel

38

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Homework

• Compare patterns between different

years (2008,2009,2010)

• Classify pattern (red/yellow/green) re

assumed functional intent

39

Copyright 2011

HVAC Systems at Y2E2

CEE 243

Conclusions

• Basic Control overview for Y2E2.

• Reference data manual for more detail

• Questions?

40