YOUR REF: 3656EDA004 OUR REF: DA-2011-188/B
26 October 2016 Torres Hire Pty Ltd C/- Whitsunday Design & Drafting Pty Ltd 31 Gregory St MACKAY QLD 4740 Dear Sir/Madam CHANGE TO DEVELOPMENT APPROVAL Applicant’s Name: Torres Hire Pty Ltd Proposal: Change to Development Approval - Plan of Development -
General Industry Application Number: DA-2011-188/B Address: 24 Lester Hansen Street, SLADE POINT QLD 4740 Property Description: Lot 7 on CP895316
Your request for a Change of Condition, lodged on 6 September 2016 to amend DA-2011-188 approved on 15 September 2009, was considered by Council’s Manager Development Assessment under section 369 of the Sustainable Planning Act 2009. Acting under delegated authority on the 21 October 2016 your request was approved as follows: 1. Condition 1 has been amended as follows.
Plan of Development The approved General Industry - Extension development must be completed and maintained generally in accordance with the Plan of Development (identified in the Table below) and supporting documentation which forms part of this application, except as otherwise specified by any condition of this approval.
Job
Number Drawing Number
Title Rev Prepared by Date
11/3656 OP-01 Cover Sheet 0 Whitsunday Designs and Drafting Pty Ltd
22.09.2016
11/3656 OP-02 Site plan and BCA Analysis
0 Whitsunday Designs and Drafting Pty Ltd
22.09.2016
11/3656 OP-03 Overall Floor Plan 0 Whitsunday Designs and Drafting Pty Ltd
22.09.2016
11/3656 OP-04 Proposed Office Floor Plan
0 Whitsunday Designs and Drafting Pty Ltd
22.09.2016
11/3656 OP-05 Building Elevations 0 Whitsunday Designs and Drafting Pty Ltd
22.09.2016
This is a Mackay Regional Council digitally signed document
The works are in stages as follows: Stage 1 – Workshop, Wash bay extension and hardstand area Stage 2 – Office Extension
2. Condition 10 has been amended as follows.
Stormwater Quality Improvement Device
The proposed Stormwater Quality Improvement Device (Bioretention Basin with filter area of 121m2) shown in the WDD drawings TP07 to TP 11 must be amended as part of the Operational Works according to the following: a) Deleted b) The proposed couch grass in the bioretention basin must be replaced with plants
according Appendix A of WSUD Technical Design Guidelines
3. Condition 11 has been amended as follows.
Drainage Easement
The 5.0m proposed drainage easement shown on Drawing WDD OP-02 must in accordance with Council’s Engineering Design Guidelines and be included in the sealing of Survey Plan application
4. Condition 16 has been deleted. 5. Condition 17 has been amended as follows.
Uncovered Working Area
The uncovered working area including the driveway and carparking must be designed and constructed as part of the Operational Works. All uncovered working area must be sealed, linemarked and drained generally in accordance with WDD drawing OP-02, OP-03 and OP-04. The portion of the site (655.6m2) shown as hardstand on WDD Drawing OP-03 can be constructed as compacted gravel hardstand to provide an area to load and unload track vehicles only.
6. All other conditions remain unchanged. 7. The relevant period for this application remains unchanged as per the original
Decision Notice and will lapse on the 19 September 2019. If you require further information, please contact Darryl Bibay at [email protected]. Yours faithfully Brogan Jones Acting Principal Planner Enc. Appeal Provisions
This is a Mackay Regional Council digitally signed document
WHITSUNDAY DESIGN & DRAFTING PTY LTD
ABN 23 139 539 843Licence No: 1180150
31 Gregory Street Mackay Qld 4740Ph: 07 4953 1040Email: [email protected]. Date Revision By
PROJECT -
TITLE -
CHECKED BY -
FULL SIZE
DRAWN BY -
A3 SCALE - A1 SCALE
PROJECT NO. REVISION
ISSUE DATE
STATUS
DRAWING NO.
A1CLIENT- PROPOSED INDUSTRIAL BUILDING EXTENSIONAT 24 LESTER HANSEN STREET
COVER SHEET DL
RP
FOR CONSTRUCTION
11/3656 OP-01 0
22.09.2016
0 22.09.2016 FOR CONSTRUCTION
OPERATIONAL WORKS DRAWING LISTDRAWING NO. DRAWING NAME REVISION ISSUE DATE STATUS
OP-01 COVER SHEET 0 22.09.2016 FOR CONSTRUCTIONOP-02 SITE PLAN 0 22.09.2016 FOR CONSTRUCTIONOP-03 DEVELOPMENT CATCHMENT PLAN 0 22.09.2016 FOR CONSTRUCTIONOP-04 STORMWATER DRAINAGE PLAN 0 22.09.2016 FOR CONSTRUCTIONOP-05 BIO-FILTRATION BASIN LAYOUT 0 22.09.2016 FOR CONSTRUCTIONOP-06 BIO-FILTRATION BASIN - SECTIONS 0 22.09.2016 FOR CONSTRUCTIONOP-07 STORMWATER DRAINAGE DETAILS 0 22.09.2016 FOR CONSTRUCTION
OPERATIONAL WORKS DRAWINGSPROPOSED INDUSTRIAL BUILDING EXTENSION AT
24 LESTER HANSEN STREET, SLADE POINT
DL
This is a Mackay Regional Council digitally signed document
5.00
5.00
4.80
5.20
5.20
4.80
4.604.80
4.60
4.60
4.80
4.40
4.60
4.80
4.60
123.13889° 58' 30"
38.400180° 00' 50"
201°
40' 0
0"
6.760
92° 09' 35"123.915
270° 25' 00"121.480
359° 58' 30"8.500
1.5805° 23' 50"
359° 58' 30"30.675
3.084
13° 1
9' 00
"
PROPOSED INDUSTRIAL BUILDING EXTENSIONEXISTING INDUSTRIAL BUILDING PROPOSED WASHDOWN AREA
EXISTING OFFICE BUILDING
LEST
ER
HANS
EN
STRE
ET
EXISTING CONCRETE PAVEMENT
EXISTING TURF
EXISTING LANDSCAPING
EXISTING LANDSCAPING
EXISTING CONCRETE DRIVEWAY
PROPOSEDBIO-RETENTION
AREA
(EXISTING BUILDING) (EXISTING BUILDING)
EXISTING TURF
4 5 6 7 8 9 10 11 12 134 5 6 7 8 9 10 11 12 134
PROPOSED CONCRETE PAVEMENT
Proposed Industrial Building Setback32.595
14 15 16 17
54.995Proposed Industrial Building Extension
36.000 0.897Proposed Washdown Area
9.600 1.0000.300BIO RETENTION
11.100 0.300 9.399
Existing Office Setback11.505
Existing Office9.000 10.041
HEAVY RIGID VEHICLE TURNING PATH
PROVIDE 100mm WHITE LINE MARKING FOR CARPARKING(TYPICAL).
1
2 3
B
B
Was
hdow
n Setb
ack
0.597
1.0m PROPOSED TURFED SWALE
5.000
PROPOSED EASEMENT
B B
PP
PP 0.886
BIO
RET E
NTIO
N11
.100
PROPOSED GRAVEL
HARDSTAND
1.556 3.444
EXISTING STORMWATER PIPE
Powered by AutoTURN
Powered by AutoTURN
Powered by AutoTURN
Powered by AutoTURN
897wash bay
6000 3600
LEGEND
- EXISTING CONCRETE PAVEMENT
- EXISTING TUFED AREAS
- 1.8m HIGH EXISTING TIMBER PALING FENCE
- EXISTING SEWER MANHOLE
- EXISTING ELECTRICAL PILLAR
- EXISTING WATER METER
- EXISTING POWER POLE
- CONCRETE BOLLARDB
- BIO-RETENTION SYSTEM FH - PROPOSED ON-SITE FIRE HYDRANT
- EXISTING BUILDINGS
- PROPOSED BUILDINGS - FIRE WATER BOOSTER ASSEMBLYFB
- REINFORCED CONCRETE PAVEMENT
- EXISTING LANDCAPED AREAS
- EXISTING LANDCAPED AREASPP
- EXISTING OVERHEAD POWER LINES
WHITSUNDAY DESIGN & DRAFTING PTY LTD
ABN 23 139 539 843Licence No: 1180150
31 Gregory Street Mackay Qld 4740Ph: 07 4953 1040Email: [email protected]. Date Revision By
PROJECT -
TITLE -
CHECKED BY -
FULL SIZE
DRAWN BY -
A3 SCALE - A1 SCALE
PROJECT NO. REVISION
ISSUE DATE
STATUS
DRAWING NO.
A1CLIENT-
1 : 200
PROPOSED INDUSTRIAL BUILDING EXTENSIONAT 24 LESTER HANSEN STREET
SITE PLAN1 : 400
DL
RP
FOR CONSTRUCTION
11/3656 OP-02 0
22.09.2016
0 22.09.2016 FOR CONSTRUCTION
LOTPARISH OFCOUNTY OFLOCALITY -
PROPERTY DESCRIPTIONon
AREA -
7HOWARDCARLISLE
SLADE POINT
CP 895316
4462 m²
DL
This is a Mackay Regional Council digitally signed document
5.00
5.00
4.80
5.20
5.20
4.80
4.604.80
4.60
4.60
4.80
4.40
4.60
4.80
4.60
201°
40' 0
0"
6.760
LEST
ER
HANS
EN
STRE
ET
5.32 5.3
75.2
9
5.395.3
05.2
7
5.26
5.225.215.08
5.07
5.07
5.06
5.24
5.195.1
65.13
5.205.1
4
5.164.86
5.18
5.20
5.09
4.994.84
4.75
4.73
4.74
4.75 4.7
5
4.82 4.72
4.914.964.784.81
5.00
4.83
4.78
4.67 4.6
5
4.71 4.8
9
4.65
4.93
4.50
4.59
4.65
4.75
4.63
4.63
5.03
5.324.97
4.91
4.55
5.35
5.36
4.73
4.64
4.64
5.02
5.04
4.69
4.66
4.65
4.68
4.54
4.75
4.55
5.54
4.64
4.46
4.49
4.65
4.46
4.48
4.46
4.60
4.59
4.86
4.27
4.63
4.49
4.65
4.73
4.77
4.74
4.72
4.70
4.94
4.71
4.66
4.934.9
9
5.08
5.20
5.31
5.29
5.20
5.135.0
0
4.99
4.895.01
4.94
4.86
4.79
4.75
4.76
4.57 4.68 4.8
3
4.53
4.54
4.65
4.65
4.60
4.60 4.69
4.70
4.704.79
4.83 4.92
5.22
5.22
5.28
5.25
5.25
5.27
5.23
5.17
5.21
5.25
5.27
5.22
5.21
5.18
5.23
5.335.35
5.24
5.28 5.2
0 5.12
5.335.35
5.30 5.28
5.21 5.1
9
5.14 5.1
35.2
1
5.17
5.14
5.14 5.03
5.07
5.19
5.19
5.21 5.19
5.17
5.12
5.07
4.91
4.96
4.90
5.23
5.295.29
5.315.31
5.32 5.35
5.24 5.24
5.355.34
5.22 5.23
5.35
5.34 5.32
5.11
5.23 4.91
4.84
4.80
4.80
4.78
4.63
4.70 4.6
54.7
3
4.87
4.81
4.81
4.88
4.93
5.03
4.95
4.88
4.78
4.72
5.21
5.24
5.20 5.24
5.33
5.33
5.29
5.20
5.25
5.26
5.33
m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
4.35.77.6
76.0
DP DP DP DP
DPDPDP
DP
m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
3.95.16.8
68.0 m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
3.95.16.8
68.0 m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
3.95.16.8
68.0 m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
3.95.16.8
68.0
DPDP
m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
3.95.16.8
68.0 m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
3.95.16.8
68.0 m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
3.95.16.8
68.0 m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
3.95.16.8
68.0
m²l/sl/s
Q5 -Q100 -
PAVEMENT
6.110.7
119.0
m²l/sl/s
Q5 -Q100 -
PAVEMENT
29.752.2
580.0
m²l/sl/s
Q5 -Q100 -
LANDSCAPING
5.810.3
136.9EXISTING INDUSTRIAL BUILDING EXISTING OFFICE
BUILDINGm²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
21.127.837.1
371.0m²l/sl/sl/sQ100 -
Q5 -Q20 -
ROOF
7.710.213.6
136.0
m²l/sl/s
Q5 -Q100 -
PAVEMENT
42.274.2
824.0
EXISTING
m²l/sl/s
Q5 -Q100 -
LANDSCAPING
5.710.0
132.8
EXISTING
m²l/sl/s
Q5 -Q100 -
LANDSCAPING
4.47.7
102.0
EXISTING
5.10
EG EG EG EG
EG EG EG EG
EG
EXISITNG INVERT
INVERT
INVERT
COP-07
EDP
EDP EDP
EDP
m²l/sl/s
Q5 -Q100 -
PAVEMENT
38.868.2
757.9
m²l/sl/s
Q5 -Q100 -
PAVEMENT
33.659.0
655.6
m²l/sl/s
Q5 -Q100 -
LANDSCAPING
1.11.9
26.0
HARDSTAND
STORMWATER DRAINAGE DESIGN DETAILS5 min TIME OF CONCENTRATIONUNDERGROUND DRAINAGE - 5 YEAR STORM INTENSITY - 205mm/hSURFACE DRAINAGE - 100 YEAR STORM INTENSITY - 360mm/hEAVES GUTTERS - 20 YEAR STORM INTENSITY - 270mm/hBOX GUTTERS - 100 YEAR STORM INTENSITY - 360mm/hRUNOFF 100% - ROOF AREASRUNOFF 90% - PAVED AREASRUNOFF 75% - LANDSCAPED AREAS
LEGEND
- 90Ø PVC DOWNPIPEDP
- ROOF PITCHP-7.5°
- SURFACE FLOW PATH.SHAPE FINAL SURFACE TO SUIT.
- EXISTING SEWER MAIN
- 175 QUAD GUTTEREG
- EXISTING DOWNPIPEEDP
WHITSUNDAY DESIGN & DRAFTING PTY LTD
ABN 23 139 539 843Licence No: 1180150
31 Gregory Street Mackay Qld 4740Ph: 07 4953 1040Email: [email protected]. Date Revision By
PROJECT -
TITLE -
CHECKED BY -
FULL SIZE
DRAWN BY -
A3 SCALE - A1 SCALE
PROJECT NO. REVISION
ISSUE DATE
STATUS
DRAWING NO.
A1CLIENT-
1 : 200
PROPOSED INDUSTRIAL BUILDING EXTENSIONAT 24 LESTER HANSEN STREET
DEVELOPMENT CATCHMENT PLAN1 : 400
DL
RP
FOR CONSTRUCTION
11/3656 OP-03 0
22.09.2016
0 22.09.2016 FOR CONSTRUCTION
A1 SCALE:A3 SCALE:
1 : 200DEVELOPMENT CATCHMENT PLAN
1 : 400
This is a Mackay Regional Council digitally signed document
5.00
5.00
4.80
5.20
5.20
4.80
4.604.80
4.60
4.60
4.80
4.40
4.60
4.80
4.60
123.13889° 58' 30"
201°
40' 0
0"
6.760
92° 09' 35"123.915
LEST
ER
HANS
EN
STRE
ET
LOTPLAN
on525CI 3887
5.32 5.3
75.2
9
5.395.30
5.27
5.265.225.215.08
5.07
5.07
5.06
5.24
5.195.1
65.13
5.20
5.14
5.164.86
5.18
5.20
5.09
4.994.84
4.75
4.73
4.74
4.75 4.7
5
4.82 4.72
4.914.964.784.81
5.00
4.83
4.78
4.67 4.6
5
4.71 4.8
9
4.65
4.93
4.50
4.59
4.65
4.75
4.63
4.63
5.03
5.324.9
7
4.91
4.55
5.35
5.36
4.73
4.64
4.64
5.02
5.04
4.69
4.66
4.65
4.54
4.75
4.55
5.54
4.64
4.46
4.49
4.65
4.46
4.48
4.46
4.60
4.59
4.86
4.27
4.63
4.49
4.65
4.73
4.77
4.74
4.94
4.71
4.66
4.934.9
9
5.08
5.20
5.31
5.29
5.20
5.135.0
0
4.99
4.895.01
4.94
4.86
4.79
4.75
4.76
4.57 4.68 4.8
3
4.53
4.54
4.65
4.65
4.60
4.60 4.69
4.70
4.704.79
4.83 4.92
5.22
5.22
5.28
5.25
5.25
5.27
5.23
5.17
5.21
5.25
5.27
5.22
5.21
5.18
5.23
5.335.35
5.24
5.28 5.2
0 5.12
5.335.35
5.30 5.28
5.21 5.1
9
5.14 5.1
35.2
1
5.17
5.14
5.14 5.03
5.07
5.19
5.19
5.21 5.19
5.17
5.12
5.07
4.96
5.23
5.295.29
5.315.31
5.32 5.35
5.24 5.24
5.355.34
5.22 5.23
5.35
5.34 5.32
5.11
5.23 4.91
4.84
4.63
4.70
4.65
4.73
4.935.03
4.95
4.88
5.21
5.24
5.20 5.24
5.33
5.33
5.29
5.20
5.25
5.26
5.33
DP DP DP DP
DPDPDP
DP
DPDP
EXISTING INDUSTRIAL BUILDING EXISTING OFFICE BUILDING
5.10
FFL - 5.36
5.30
5.30
5.30
5.30
5.25p
5.25p
4.80
Ø2251 on 15054.4l/sIL- 4.47
OL- 4
.20
4.91 5.15k
5.00p
5.08k
4.93p
5.00k
4.85p
4.95k
4.80p
4.75p4.90k
5.40k
4.68
COP-07
EXISTING 600Ø RCP STORMWATER PIPE
EXISTING 3/900Ø RCP STORMWATER PIPE
EXISTING 2/900Ø RCP STORMWATER PIPE
STORMWATER DRAINAGE ALLOTMENT POINT FOR LOT 6SL - 4.47OL - 3.57
EXISTING 450Ø RCP STORMWATER PIPE
EXISTING STORMWATER GULLY PITSL - 4.54OL - 3.04
EXISTING 2/900Ø RCP STORMWATER PIPE
EXISTING STREET STORMWATER GRATESL - 4.50OL - 3.28
EXISTING STREET STORMWATER GRATESL - 4.57OL - 3.71
EXISTING STREET STORMWATER GRATESL - 4.85
EXISTING BUILDING STORMWATER DRAINAGE
EXISTING STORMWATER MANHOLESL - 4.51OL - 2.69
EXISTING BUILDING STORMWATER DRAINAGE
Ø300
146.1l/s
Ø3751 on 13146.1l/s
IL- 3.20OL- 3.04
EDP
EDP EDP
EDP
4.78p
LAY FLAT- 3.20
EXISTING PAVEMENT
OL- 4.30 Ø2251 on 13554.4l/s
4.90gGPT-1
IL- 4.304.81
4.50g
BIO
4.50gBIO
4.45p
4.45p
4.78g
GPT-1
4.65p
4.65k
WEIR
STORMWATER DRAINS
• INSTALL THE STORMWATER DRAINAGE SYSTEM TO COMPLY WITH AS 3500.3-2003.• PROVIDE STORMWATER DRAINS TO CONNECT DOWNPIPES, SURFACE DRAINS,
SUBSOIL DRAINS AND DRAINAGE PITS TO THE OUTLET POINT. (CONTRACTOR TO CONFIRM OUTLET LEVELS AND LOCATIONS BEFORE COMMENCING WORK)
• ALL UPVC UNDERGROUND STORMWATER PIPES SHALL BE CLASS '2'.• UPVC PIPES SHALL BE SOLVENT JOINTED. • AFTER LAYING AND JOINTING OF A PIPELINE HAS BEEN COMPLETED THE
CONTRACTOR SHALL ARRANGE FOR INSPECTION BY THE SUPERINTENDENT • TURN UP STORMWATER DRAINS WITH BENDS TO MEET THE DOWNPIPES, FINISHING
50mm ABOVE FINISHED GROUND OR PAVEMENT LEVEL. SEAL JOINTS BETWEEN DOWNPIPES AND DRAINS.
• BED PIPING ON A CONTINUOUS UNDERLAY OF SANDY LOAM MATERIAL, AT LEAST 75mm THICK AFTER COMPACTION. GRADE THE UNDERLAY EVENLY TO THE GRADIENT OF THE PIPELINE.
• PLACE THE SANDY LOAM MATERIAL IN THE PIPE SURROUND IN LAYERS < OR EQUAL TO 200mm LOOSE THICKNESS, AND COMPACT TO 95% OF THE STANDARD MAXIMUM DRY DENSITY OF THE MATERIAL USED WHEN DETERMINED IN ACCORDANCE WITH AS 1289.5.7.1-2006
• PROVIDE SUBSOIL DRAINS TO INTERCEPT GROUNDWATER SEEPAGE AND PREVENT WATER BUILD-UP BEHIND WALLS AND UNDER FLOORS AND PAVEMENTS. CONNECT SUBSOIL DRAINS TO THE STORMWATER DRAINAGE SYSTEM.
- FINISHED LEVEL - p-pavmentg-gratek - top of kerbf - finished surface
6.45k
LEGEND
- EXISTING SEWER MAIN
- INSPECTION OPENING TO SURFACEIOS
- 600SQ. EVERHARD STORMWATER PIT WITH 150 CONCRETE SURROUND (GALVANISED STEEL GRATE AND V-BASKET TRASH
SCREEN)
BIO
DP - 90Ø PVC DOWN PIPE
- 600SQ. CONCRETE STORMWATER PIT WITH GALVANISED STEEL GRATE AND V-BASKET TRASH SCREEN)
GPT-1
- NEW UNDERGROUND STORMWATER PIPES
6.59
- EXISTING SURFACE LEVEL
- CONCRETE BOLLARDB
- EXISTING UNDERGROUND STORMWATER PIPES
EDP - EXISTING DOWN PIPE
WHITSUNDAY DESIGN & DRAFTING PTY LTD
ABN 23 139 539 843Licence No: 1180150
31 Gregory Street Mackay Qld 4740Ph: 07 4953 1040Email: [email protected]. Date Revision By
PROJECT -
TITLE -
CHECKED BY -
FULL SIZE
DRAWN BY -
A3 SCALE - A1 SCALE
PROJECT NO. REVISION
ISSUE DATE
STATUS
DRAWING NO.
A1CLIENT-
1 : 200
PROPOSED INDUSTRIAL BUILDING EXTENSIONAT 24 LESTER HANSEN STREET
STORMWATER DRAINAGE PLAN1 : 400
DL
RP
FOR CONSTRUCTION
11/3656 OP-04 0
22.09.2016
0 22.09.2016 FOR CONSTRUCTION
A1 SCALE:A3 SCALE:
1 : 200STORMWATER DRAINAGE PLAN
1 : 400
This is a Mackay Regional Council digitally signed document
OL- 4
.20
4.90k
4.65k
WEIR
OL-
4.20
4.50g
BIO
Ø300
146.1l/s
4.75p
4.50g
BIO
AOP-06
4.20p
BED
BOP-06
EXISTING 450Ø STORMWATER PIPE
UNDERDRAIN PIPES -SLOTTED 100Ø RIDIG POLYETHYLENE PIPE -FALL 100
RIVER STONE & REEDS100 HIGH AT PIPE OUTLETSSIZE 50Ø min.-100Ø maxTO LANDSCAPING PLAN
600SQ. EVERHARD STORMWATER PIT, GALVANISED STEEL GRATE AND V-BASKET TRASH SCREEN COMPLETE WITH 280H x 150 CONCRETE SURROUND.
PROVIDE REMOVABLE SCREW CAPS FOR MAINTENANCE
TIMBER EDGE - 200x100 F17 UNSEASONED HWD. SET 150 INTO SURFACE
PROPERTY BOUNDARY
UNDE
R DR
AINS
FAL
L 100
mm
PR OPE RTY BOUNDARY
UNDERDRAIN PIPE -SLOTTED 150Ø RIDIG POLYETHYLENE PIPE -LAY FLAT
EXISTING 600Ø RCP STORMWATER PIPE
EXISTING 3/900Ø RCP STORMWATER PIPE
EXISTING 2/900Ø RCP STORMWATER PIPE
EXISTING STORMWATER MANHOLESL - 4.51OL - 2.69
Ø1501 on 125
21l/s
LAY FLAT- 3.20
4.90k
4.75p
4.90k
4.65p
4.90k
4.45p4.45p
1170
0
Ø3751 on 13146.1l/s
IL-3.2
0OL
- 3.04
Ø2251 on 13554.4l/s
IOS
FILTRATION DETAILS
GENERALALL FILTER MATERIAL SHALL BE TESTED AND A CERTIFICATE PROVIDED FOR CONDUCTIVITY AND STRUCTURE BY A GEOTECHNICAL ENGINEER.
FILTER LAYERTHE FILTER MEDIA SHOULD BE BASED ON NATURAL OR AMENDED NATURAL SOILS OR IT CAN BE ENTIRELY ENGINEERED; IN EITHER CASE, IT CAN BE OF SILICEOUS OR CALCAREOUS ORIGIN. THE MEDIA SHALL HAVE HIGH PERMEABILITY UNDER COMPACTION AND SHALL BE FREE OF RUBBISH, DELETERIOUS MATERIAL, TOXICANTS, DECLARED PLANTS, WEEDS AND SHOULD NOT BE HYDROPHOBIC. THE FILTER MEDIA SHOULD CONTAIN SOME ORGANIC MATTER FOR INCREASED WATER HOLDING CAPACITY BUT BE LOW IN NUTRIENT CONTENT.IN THE CASE OF NATURAL OR AMENDED NATURAL SOILS, THE MEDIA SHOULD BE LOAMY SAND.
THE HYDRAULIC CONDUCTIVITY OF POTENTIAL FILTER MEDIA SHOULD BE MEASURED USING THE ASTM F1815-06 METHOD FOR A TROPICAL ZONE WITH FILTRATION RATE RANGING BETWEEN 100 TO 300mm/hr.
PARTICLE SIZE DISTRIBUTION (PSD) IS OF SECONDARY IMPORTANCE COMPARED WITH HYDRAULIC CONDUCTIVITY. THE FOLLOWING COMPOSITION RANGE (PERCENTAGE W/W) PROVIDES A GUIDE FOR SELECTING AN APPROPRIATE MATERIAL:-
● CLAY SILT <3% (<0.05mm)● VERY FINE 5-30% (0.05 - 0.15mm)● FINE SAND 10-30% (0.15 - 0.25mm)● MEDIUM TO COARSE SAND 40-60% (0.25 - 1.00mm)● COARSE SAND 7-10% (1.00 - 2.00mm)
43-
15 85
15
85th
th
15 85
15
85
th
th
15
15
THE FILTER MEDIA SHOULD BE WELL-GRADED WITH ALL PARTICLE SIZE RANGES PRESENT FROM THE 0.075mm TO THE 4.75mm SIEVE (AS DEFINED BY AS1289.3.6.1 - 1995). THERE SHOULD BE NO GAP IN THE PARTICLE SIZE GRADING, AND THE COMPOSITION SHOULD NOT BE DOMINATED BY A SMALL PARTICLE SIZE RANGE. THIS IS IMPORTANT FOR PREVENTING STRUCTURAL COLLAPSE DUE TO PARTICLE MIGRATION.FILTER MEDIA MUST BE TESTED AND MEET THE FOLLOWING CRITERIA:-
● TOTAL NITROGEN (TN) CONTENT - <1000mg/kg● ORTHOPHOSPHATE (PO ) CONTENT- <80mg/kg● ORGANIC MATTER CONTENT - 3% (w/w)● pH - 5.5-7.5 (pH 1:5 IN WATER)● ELECTRICAL CONDUCTIVITY (EC) <1.2dS/m
FOR INSTALLATION THE FILTER MEDIA SHALL BE LAID IN 250mm LAYER AND BE LIGHTLY COMPACTED DURING INSTALLATION TO PREVENT MIGRATION OF FINE PARTICLES. A SINGLE PASS WITH A VIBRATING PLACE SHOULD BE USED TO COMPACT THE FILTER MEDIA. UNDER NO CIRCUMSTANCE SHALL THE MEDIA BE HEAVILY COMPACTED OR MULTIPLE-PASSES BE MADE.
TOP TRANSITION LAYERTHE TOP 100mm TRANSITION LAYER SHALL CONSIST OF FILTER MEDIA USED IN THE FILTER LAYER AMELIORATED WITH THE FOLLOWING ORGANIC MATTER, FERTILIZER AND TRACE ELEMENTS AS FOLLOWS:-
CONSTITUENT QUANTITY (kg/100m² FILTER AREA)
GRANULATED POULTRY MANURE FINES 50SUPERPHOSPHATE 2MAGNESIUM SULPHATE 3POTASSIUM SULPHATE 2TRACE ELEMENT MIX 1FERTILIZER NPK (16.4.14) 4
TRANSITION LAYERTHE TRANSITION LAYER PREVENTS FILTER MEDIA FROM WASHING INTO THE DRAINAGE LAYER. TRANSITION LAYER MATERIAL SHALL BE A CLEAN, WELL-GRADED SAND MATERIAL CONTAINING <2% FINES.TO AVOID MIGRATION OF THE FILTER MEDIA INTO THE TRANSITION LAYER, THE PARTICLE SIZE DISTRIBUTION OF THE SAND SHOULD BE ASSESSED TO ENSURE IT MEETS 'BRIDGING CRITERIA', THAT IS, THE SMALLEST 15% OF THE SAND PARTICLES BRIDGE WITH THE LARGEST 15% OF THE FILTER MEDIA PARTICLES.
D (TRANSITION LAYER) < 5 x D (FILTER MEDIA)
WHERE: D (TRANSITION LAYER) IS THE 15 PERCENTILE PARTICLE SIZE IN THE TRANSITION LAYER MATERIAL.(ie. 15% OF THE GRAVEL IS SMALLER THAN D mm), AND
D (FILTER MEDIA) IS THE 85 PERCENTILE PARTICLE SIZE IN THE FILTER MEDIA.
DRAINAGE LAYERTHE DRAINAGE LAYER COLLECTS TREATED WATER AT THE BOTTOM OF THE SYSTEM AND CONVEYS IT TO THE UNDER DRAIN PIPES. DRAINAGE LAYER MATERIAL IS TO BE CLEAN, FINE GRAVEL CONSISTING OF 2-5mm WASHED SCREENINGS. BRIDGING CRITERIA SHOULD BE APPLIED TO AVOID MIGRATION OF THE TRANSITION LAYER INTO THE DRAINAGE LAYER.
D (DRAINAGE LAYER) < 5 x D (TRANSITION LAYER)
WHERE: D (DRAINAGE LAYER) IS THE 15 PERCENTILE PARTICLE SIZE IN THE DRAINAGE LAYER MATERIAL.(ie. 15% OF THE GRAVEL IS SMALLER THAN D mm), AND
D (TRANSITION LAYER) IS THE 85 PERCENTILE PARTICLE SIZE IN THE TRANSITION LAYER MATERIAL.
UNDER DRAIN PIPESTHE PERFORATIONS IN THE UNDER DRAIN PIPES SHALL BE SMALL ENOUGH THAT THE DRAINAGE LAYER CANNOT FALL INTO THE PIPES. THE D (DRAINAGE LAYER) IS GREATER THAT THE PIPE PERFORATION DIAMETER.
GEO-TEXTILE FABRICSGEO-TEXTILE FABRICS ARE NOT RECOMMENDED FOR USE BETWEEN LAYERS IN THE BIO-FILTRATION SYSTEM DUE TO THE RISK OF CLOGGING. AN OPEN-WEAVE SHADE CLOTH SHALL BE PLACED BETWEEN THE TRANSITION LAYER AND THE DRAINAGE LAYER TO HELP REDUCE THE DOWNWARD MIGRATION OF SMALLER PARTICLES. THE BASE AND SIDES SHALL BE LINED WITH A GEO-TEXTILE FILTER FABRIC TO PREVENT CONTAMINATION OF THE FILTRATION SYSTEM.
WHITSUNDAY DESIGN & DRAFTING PTY LTD
ABN 23 139 539 843Licence No: 1180150
31 Gregory Street Mackay Qld 4740Ph: 07 4953 1040Email: [email protected]. Date Revision By
PROJECT -
TITLE -
CHECKED BY -
FULL SIZE
DRAWN BY -
A3 SCALE - A1 SCALE
PROJECT NO. REVISION
ISSUE DATE
STATUS
DRAWING NO.
A1CLIENT-
1 : 50
PROPOSED INDUSTRIAL BUILDING EXTENSIONAT 24 LESTER HANSEN STREET
BIO-FILTRATION BASIN LAYOUT1 : 100
DL
RP
FOR CONSTRUCTION
11/3656 OP-05 0
22.09.2016
0 22.09.2016 FOR CONSTRUCTION
A1 SCALE:A3 SCALE:
1 : 50BIO-RETENTION BASIN
1 : 100
DL
This is a Mackay Regional Council digitally signed document
Decision Notice Sustainable Planning Act
Sustainable Planning Act Appeals Chapter 7 Part 1 Planning and Environment Court:
465 Appeals about decisions relating to extensions for approvals
(1) For a development approval given for a development application, a person to whom a
notice is given under section 389, other than a notice for a decision under section 386(2), may appeal to the court against the decision in the notice.
(2) The appeal must be started within 20 business days after the day the notice of the
decision is given to the person. (3) Also, a person who has made a request under section 383 may appeal to the court
against a deemed refusal of the request. (4) An appeal under subsection (3) may be started at any time after the last day the
decision on the matter should have been made.
466 Appeals about decisions relating to permissible changes
(1) For a development approval given for a development application, the following persons may appeal to the court against a decision on a request to make a permissible change to the approval—
(a) if the responsible entity for making the change is the assessment manager for the
application— (i) the person who made the request; or (ii) an entity that gave a notice under section 373 or a pre-request response
notice about the request;
(b) if the responsible entity for making the change is a concurrence agency for the application—the person who made the request.
(2) The appeal must be started within 20 business days after the day the person is given
notice of the decision on the request under section 376.
(3) Also, a person who has made a request under section 369 may appeal to the court against a deemed refusal of the request.
(4) An appeal under subsection (3) may be started at any time after the last day the
decision on the matter should have been made.
467 Appeals about changing or cancelling conditions imposed by assessment manager or concurrence agency
(1) A person to whom a notice under section 378(9)(b) giving a decision to change or
cancel a condition of a development approval has been given may appeal to the court against the decision in the notice.
(2) The appeal must be started within 20 business days after the day the notice of the
decision is given to the person.
This is a Mackay Regional Council digitally signed document