zonex enclosures - nvent...an expanded offering of hinge- and screw-cover enclosures for hazardous...
TRANSCRIPT
zonexenclosuresEquipmEnt pROtECtiOn hazardous locations
2 ZOnE X EnCLOSuRE S
thE ZOnEX™ EnCLOSuRE famiLy dELivERS RELiabLE pROtECtiOn in a vERSatiLE pLatfORm.The newly expanded line of ZONEX™ ATEX-Certified* Enclosures includes the certifications, styles and sizes your application requires. ZONEX hinge-cover and screw-cover enclosures are designed for use in applications where “increased safety” protection (Ex e), is acceptable to safely house electrical components in Zone 1- and Zone 2-rated areas. These enclosures are not intended for use in explosion-proof or flame-proof (Ex d) applications.
Hinge-cover versions are ATEX and IECEX certified, and available in 16 standardsizes. The screw-cover versions provide also ATEX and IECEX certification and areavailable in five sizes. Additional certifications such as AEx and KOSHA will be available soon (AEx certified hinge-cover version is already available as non-standard model).• Hinge-coverversionsinstandardsizes
ranging from 300 x 300 x 150 mm to 900 x 600 x 210 mm
• Screw-coverversionsinstandardsizesranging from 102 x 102 x 76 mm to 254 x 254 x 127 mm
Enhanced customization options allow you to specify the exact enclosure solution you need. Options include: material changes, dimension changes, paint options, holes and cutouts, population of ATEX-certified terminal blocks and more. * For more information about ATEX-certification visit: http://ec.europa.eu/enterprise/sectors/mechanical/atex/index_en.htm
ZOnEX™ ENClOSurESAn expAnded offering of Hinge- And screw-cover enclosures for HAzArdous locAtions. Atex directive 94/9/ec And iecex certified for zone 1 zone 2 rAted AreAs.
ZOnEX Screw-Cover model
bonding provisions, screw-cover style 6-mm internal/external brass bonding provision
Easy-to-remove cover Type 316 stainless steel with capivated Type 316 stainless steel cover screws for corrosion resistance
Wall-mounting brackets, screw-cover style Welded-on, full-width top and bottom wall-mount brackets for easy installation
ZOnE X EnCLOSuRE S 3
Continuous gasket seal on the door and gland plate for protection against water and dust ingress
Wall-mounting brackets Heavy-duty 2,5-mm welded-on brackets, horizontal or vertical, for easy site installation
type 316 stainless steel 3mm double bit ¼-turn for easy access and closure
210-degree opening door that is easily removed by pulling clip style hinge pins
full-size gland plate 3-mm thick (12 gauge) flat bottom gland plate with bonding stud and continuous gasket seal
bonding provisions 10-mm brass internal/external bonding provisions
internal studs for panel or DIN rail mounting
ZOnEX hinge-Cover model
4 ZOnE X EnCLOSuRE S
CERtifiEd fOR yOuR appLiCatiOn REquiREmEntSZONEX enclosures deliver a robust solution for termination and junction enclosure applications in potentially hazardous locations, including:•Petroleumandchemicalprocessing•Watertreatmentprocessing•Pharmaceuticalprocessing•Grainprocessing
thERE aRE 2 WayS tO dEtERminE thE CORRECt SiZE ZOnEX EnCLOSuRE fOR pOpuLatEd tERminaL bLOCkS (see page 8):•Method1:MaximumTerminalBlockCount •Method2:MaximumDissipatedPower(watts) * NOTE - All selection methods must adhere to maximum dissipated power for selected
enclosure size.
mOdifiCatiOn and CuStOmiZatiOnHoffman excels at modifying and customizing ZONEX products to your specifications while maintaining ATEX and IECEX certifications. Contact your local Hoffman sales office or distributor for complete information. Hoffman offers:•Materialchanges:Type304stainlesssteel,aluminum,mildsteel•Gasketchanges:High-temperaturesiliconegasket•Holesandcutouts•Paint•DINrails•Terminalblockinstallationandmarking•Groundbars•Tagging•Accessoryinstallations•Zerotofourglandplates**Hinge-cover enclosures only
selection And specificAtion of A ZOnEX EnclosurE to meet your ApplicAtion requirements
Certification MarkingsATEX IECEX AEx / Ex
II 2 G D Ex e IIC T6 Gb (Ta -20 C to +40 C)
Ex tb IIIC T85 C Db IP 66Ex e IIC T6 Gb (Ta -20 C to +40 C)
Ex tb IIIC T85 C Db IP 66UL File No. E67546:
Class I, Zone I
II 2 G DEx e IIC T5 Gb (Ta -20 C to +55 C)
Ex tb IIIC T100 C Db IP 66Ex e IIC T5 Gb (Ta -20 C to +55 C)
Ex tb IIIC T100 C Db IP 66AEx e IIC Tamb -20 C to +60 C
Ex e IIC Tamb -20 C to +60 C
ZOnE X EnCLOSuRE S 5
fLammabLE/ COmbuStibLE SubStanCE
aiR/OXygEn
ignit
iOn SO
uRCE
atEX diRECtivE and CLaSSifiCatiOn SyStEmSince 2003, manufacturers across the European union (Eu) have been obliged to comply with strict new Eu directives governing safety in explosive atmospheres. Called ATEX (from the French ATmosphères EXplosives), ATEX Directive 94/9/EC has an impact not only on European manufacturers, but also on non-European makers of industrial equipment wishing to sell in Europe.
Two of the most common classification systems for hazardous locations are the Zone Classification system used by the European union (Eu) and the International Electrotechnical Commission (IEC), and the NEC Division Classification system.
Articles 505 and 506 of the NEC refer to zone classifications. refer to the Technical Information section of the Specifier’s Guideforspecificdefinitionsandadditionalinformation.
Hoffman’s ATEX enclosures are not intended for use in explosion-proof or flame-proof (Ex d) applications.
inCREaSEd SafEty “Ex e”It is assumed that the hazardous atmosphere penetrates to the enclosure interior and explosion is prevented by ensuring that either in normal operation or under fault conditions:•Therearenoarcsorsparks•Nocomponentsorpartstemperaturesexceedthe
temperature limit of the corresponding temperature class
nOtES:•ATEXandintrinsicallysafecertifiedterminalblockscanbe
installed in populated enclosures•IECEXpopulatedenclosuresrequireIECEXcertified
components specifically listed in Certification (see IECEX SIR 09.0100 for more detail)
•ContactyourlocalHoffmansalesofficeordistributorforcomplete information
All three elements of the fire triAngle must be present for ignition to occur.
Area ClassificationFlammable Substance Present Continuously
Flammable Substance Present Intermittently
Flammable Substance Present Abnormally
IEC / EU Zone 0 Zone 1 Zone 2
USNEC® 505 Zone 0 Zone 1 Zone 2
NEC® 500 Division 1 Division 2
CACEC Section 18 Zone 0 Zone 1 Zone 2
CEC Annex J Division 1 Division 2
IEC classification per IEC 60079-10EU classification per EN 60079-10US classification per ANSI/NF PA 70 National Electrical Code® (NEC®) Article 500 or Article 505CA classification per CSA C22.1 Canadian Electrical Code (CEC) Section 18 or Annex J
ATEX Marking Directive (94/9/EC)
II 2 G DEuropean Explosive
Atmosphere Symbol
Equipment Group
Equipment Category Gas Dust
Ex e II T6European Explosive
Atmosphere Protection Concept
Protection Method Gas Group Temperature Class
ZOnES
Safe areaZone 2 /22
Zone 1 / 21
Zone 0 / 20
Zone 0 / 20
Zone 0 / 20 Permanentlyorfrequentlyhazardousoverlongperiods
Zone 1 / 21 Occasionally hazardous
Zone 2 / 22 rarely or temporarily hazardous
Zones 20, 21 and 22 are dust
6 ZOnE X EnCLOSuRE S
SpECifiCatiOnS:•Type316stainlesssteel,320grainbrushedfinishonexteriorsurfaces•Welded-on,full-widthtopandbottomwall-mountbrackets
for easy installation•6-mminternal/externalbrassbondingprovision•Type316stainlesssteelcaptivatedcoverscrewsfor
corrosion resistance•One-piececontinuousgasketforprotectionagainstwater
and dust ingress•InternalweldnutsprovidedforpanelorDINrailinstallation•Mountingplateincluded
ZOnEX scrEw-covEr Atex-certified enclosures
SCREW-COVER ATEX (Standard Sizes)
Catalog Number Actual Dimensions - mm
A - Height B - Width C- Depth
EXE10210276SS6E 102 102 76
EXE152152102SS6E 152 152 102
EXE178178102SS6E 178 178 102
EXE216146127SS6E 216 146 127
EXE254254127SS6E 254 254 127
H2,
812
,7
W 2,8
H+2
5,4
W-22,6
3,2
H-1
2,7
H-1
2,7
(BO
DY
OPE
NIN
G)
W-12,7(BODY OPENING)
D2,0
16,0 D-23,8
Y
Y
M5
A
B
H
W8,6
8,6
H-3
6,4
W-50
Y-Y
ZOnE X EnCLOSuRE S 7
SpECifiCatiOnS:•Type316stainlesssteel,320grainbrushedfinishon
exterior surfaces•Type316stainlesssteel3mmdoublebit¼-turn
insert(s) for easy access and closure•210degreeopeningdoorthatiseasilyremovedby pulling clip style hinge pins•Heavy-duty2,5-mmwelded-onbrackets,horizontal or vertical, for easy site installation•3-mmthick(12gauge)full-sizebottomglandplate
with bonding stud•Fabricatedandformedentriesfor
gland plate screws provide quick and easy installation•Continuousgasketsealonthedoorand
gland plate for protection against water and dust ingress
•10-mmbrassinternal/external bonding provision
•Mountingplateincluded
ZOnEX hingE-covEr Atex-certified enclosures
Catalog NumberActual Dimensions - mm
A - Height B - Width C- DepthEXE300300150SS61E 300 300 150EXE300300210SS61E 300 300 210EXE400300150SS61E 400 300 150EXE400300210SS61E 400 300 210EXE400400150SS61E 400 400 150EXE400400210SS61E 400 400 210EXE500400150SS61E 500 400 150EXE500400210SS61E 500 400 210EXE500500210SS61E 500 500 210EXE600500210SS61E 600 500 210EXE600600210SS61E 600 600 210EXE600600300SS61E 600 600 300EXE750500210SS61E 750 500 210EXE750600210SS61E 750 600 210EXE750750300SS61E 750 750 300EXE900600210SS61E 900 600 210
EXE300300150SS61HE 300 300 150EXE300300210SS61HE 300 300 210EXE400300150SS61HE 400 300 150EXE400300210SS61HE 400 300 210EXE400400150SS61HE 400 400 150EXE400400210SS61HE 400 400 210EXE500400150SS61HE 500 400 150EXE500400210SS61HE 500 400 210EXE500500210SS61HE 500 500 210EXE600500210SS61HE 600 500 210EXE600600210SS61HE 600 600 210EXE600600300SS61HE 600 600 300EXE750500210SS61HE 750 500 210EXE750600210SS61HE 750 600 210EXE750750300SS61HE 750 750 300EXE900600210SS61HE 900 600 210
W
HH
-41,
6(B
OD
Y D
OO
R O
PEN
ING
)
20,8
20,8
W-41,6(BODY DOOR OPENING)
P
Q
19,4D2,5
28,9 D-49,8
Y
Y
M8 x 1,25
W-63,531,8W
A
B22,5
22,5
H+3
1,8
H
11,0
13,8
13,4
Y-Y
8 ZOnE X EnCLOSuRE S
dEtERminE thE CORRECt SiZE ZOnEX EnCLOSuRE fOR pOpuLatEd tERminaL bLOCk:
by maXimum tERminaL bLOCk COunt (known wire size/match terminal block size)
1. refer to power and terminal block matrix appropriate for selected model (screw-/hinge-cover)
2. Find a terminal block quantity less than or equal to required in the shaded areas associated with your chosen terminal block manufacturer
3. Select enclosure size4. use calculating power and amperage formula to verify
conformance to standard5. If maximum power is exceeded by terminal block count and
amperage, select an enclosure with higher power and re-calculate
by maXimum pOWER (watts)
1. refer to power and terminal block matrix appropriate for selected model (screw-/hinge-cover)
2. Find maximum power required in shaded areas associated with your chosen terminal block manufacturer
3. If terminal block quantity for maximum power is insufficient, continue down and across rows until requirement is met; this provides the smallest enclosure to meet maximum power and amperage needs
4. use calculating power and amperage formula to verify conformance to standard
5. If maximum power is exceeded by terminal block count and amperage, select an enclosure with higher power and re-calculate
SELECtiOn of zonEx EnclosurEsby terminAl block count & power
Terminal Wire Size, Voltage and Resistance (Rt) DataManufacturer Phoenix Weidmuller (SAK/WDU)
Model UK1.5 UK3 UK5 UK10 2.5 4 6 10Terminal Wire Size Range (mm2)
0.14 to 1.5
0.2 to 2.5
0.2 to 4.0
0.5 to 10.0
0.5 to 2.5
0.5 to 4.0
0.5 to 6.0
1.5 to 10.0
Terminal Voltage (Volts) 550 550 6 90 600 550 550 550 550
Terminal Resistance Rt (Ohm)
4.17x10-04
5.00x10-04
3.75x10-04
1.23x10-04
3.89x10-04
4.23x10-04
3.93x10-04
1.34x10-04
SpECifying EnCLOSuRES With tERminaL bLOCk pOpuLatiOn
•ATEX-andIECEX-certifiedterminalblocksfromPhoenixand Weidmuller are referenced in tables
•AnyATEXorIEXEXhazardouslocationcertifiedterminalblock may be selected and installed in ATEX-certified applications
•Onlythetablereferencedterminalblocksmaybespecified for IECEX populations and certification
•Combinationsofdifferentterminalblocksizesandquantities may be selected for population
•AllterminalblockinstallationapplicationsneedtousetheCALCULATINGPOWERandAMPERAGEformulaandassociated tables on page 10 to verify compliance with final intended amperage of application and power rating of selected enclosure
pn
CaLCuLating pOWER and ampERagE using combined terminal resistance factor (see page 10)Calculation of power/amperage/number of terminal blocks in accordance with EN 600079-7:2007, ANEX E, E.2
p = n x R x i2 or I = √[P/(NxR)]orN=P/(RxI2) Where: p is the total dissipated power (watts)
n is the total number of terminals i is the current (amps) R is the sum of terminal resistance (rt) and
wire resistance (rw)
R
MAXIMUM TERMINAL BLOCKSQuantity Offerings per Enclosure
MAXIMUM POWER Dissipation (Watts)
Phoenix Weidmuller (SAK/WDU)DIN Rail
Qty
T6 at Tamp
= +40 C
T5 at Tamp = +55 C
Actual Dimensions (mm)Catalog Number
UK1.5 UK3 UK5 UK10 2.5 4 6 10 Height Width Depth
9 7 6 4 6 6 5 4 1 3.8 W 3.8 W 102 102 76 EXE10210276SS6E
21 17 14 9 15 14 11 9 1 6.9 W 6.9 W 152 152 102 EXE152152102SS6E
27 22 18 11 19 17 14 11 1 6.9 W 6.9 W 178 178 102 EXE178178102SS6E
36 29 25 15 25 23 19 15 1 9.6 W 9.6 W 216 146 127 EXE216146127SS6E
45 37 32 19 32 29 24 19 19.6 W 9.6 W 254 254 127 EXE254254127SS6E
90 74 64 38 64 58 48 38 2
pOWER & tERminaL bLOCk quantity matRiXSCREW-COvER ZOnEX (StandaRd SiZES)
n p
ZOnE X EnCLOSuRE S 9
MAXIMUM TERMINAL BLOCKSQuantity Offerings per Enclosure
MAXIMUM POWER Dissipation (Watts)
Phoenix Weidmuller (SAK/WDU) DIN Rail Qty
T6 at Tamp = +40 C
T5 at Tamp = +55 C
Actual Dimensions (mm)Catalog Number
UK1.5 UK3 UK5 UK10 2.5 4 6 10 Height Width Depth
41 33 28 17 29 26 21 17 1
16.5 W 16.5 W 300 300
150 EXE300300150SS61E EXE300300150SS61HE82 66 56 34 57 52 43 34 2
123 99 84 51 86 78 64 51 3 210 EXE300300210SS61E EXE300300210SS61HE
65 53 44 27 46 42 34 27 1
18.5 W 18.5 W 400 300
150 EXE400300150SS61E EXE400300150SS61HE130 106 88 54 92 84 68 54 2
195 159 132 81 138 126 102 82 3 210 EXE400300210SS61E EXE400300210SS61HE
65 53 44 27 46 42 34 27 1
18.5 W 18.5 W 400 400
150 EXE400400150SS61E EXE400400150SS61HE130 106 88 60 92 84 68 54 2
195 158 133 81 138 126 102 81 3 210 EXE400400210SS61E EXE400400210SS61HE
90 72 61 37 63 58 47 38 1
23.5 W 23.5 W 500 400
150 EXE500400150SS61E EXE500400150SS61HE180 144 122 74 126 116 94 76 2
270 216 183 111 189 174 141 114 3 210 EXE500400210SS61E EXE500400210SS61HE
90 72 61 37 63 58 47 38 1
25.5 W 25.5 W 500 500 210 EXE500500210SS61E EXE500500210SS61HE
180 144 122 74 126 116 94 76 2
270 216 183 111 189 174 141 114 3
360 288 244 148 252 232 188 152 4
111 90 75 46 78 72 58 47 1
28 W 28 W 600 500 210 EXE600500210SS61E EXE600500210SS61HE
222 180 150 92 156 144 116 94 2
333 270 225 138 234 216 174 141 3
444 360 300 184 312 288 232 188 4
111 90 75 46 78 72 58 47 1
28 W 28 W 600 600
210 EXE600600210SS61E EXE600600210SS61HE222 180 150 92 156 144 116 94 2
333 270 225 138 234 216 174 141 3
444 360 300 184 312 288 232 188 4300 EXE600600300SS61E
EXE600600300SS61HE555 450 375 230 390 360 290 235 5
150 121 102 62 105 97 79 63 1
28 W 28 W 750 500 210 EXE750500210SS61E EXE750500210SS61HE
300 242 204 124 210 194 158 126 2
450 363 306 186 315 291 237 189 3
600 484 408 248 420 388 316 252 4
750 605 510 310 525 485 395 315 5
150 121 102 62 105 97 79 63 1
33 W 33 W 750
600 210 EXE750600210SS61E EXE750600210SS61HE300 242 204 124 210 194 158 126 2
450 363 306 186 315 291 237 189 3
600 484 408 248 420 388 316 252 4750 300 EXE750750300SS61E
EXE750750300SS61HE750 605 510 310 525 485 395 315 5
186 150 126 77 130 120 98 78 1
33 W 33 W 900 600 210 EXE900600210SS61E EXE900600210SS61HE
372 300 252 154 260 240 196 156 2
558 450 378 231 390 360 294 234 3
744 600 504 308 520 480 392 312 4
930 750 630 385 650 600 490 390 5
pOWER & tERminaL bLOCk quantity matRiXhingE-COvER ZOnEX (StandaRd SiZES)
pn
Color shaded areas are maximum physical quantity of terminal blocks that will fit enclosure, not necessarily the allowable quantity.Actual allowable quantity is determined by amperage and power allowed through provided mathematical formula.
* Maximum dissipated power based on screw type terminal blocks. Weidmuller 2.5 and smaller wire size limited to 15 amperes.
10 ZOnE X EnCLOSuRE S
COmbinEd tERminaL RESiStanCE faCtOR This factor is used to determine the number of terminals that can be accommodated within the enclosure without exceeding the enclosure maximum wattage rating. The combined terminal resistance factor (r) is the sum of the individual terminal resistances (rt) and the resistance of the cable core equal in length to the enclosure maximum diagonal (Rw).ThecoreresistancehasbeendefinedinthestandardBSEN 60228.•WattagetobeDissipated(p) = N x r x I²•TotalNumberofTerminals(n) •CombinedTerminalResistanceFactor(R) = (rt + rw) the sumofterminalresistance[Rt]andwireresistance[Rw]
•MaximumCurrent(amps)usedintheapplication=(i)
REXampLE:A customer wants to determine the number of WDu 2.5 terminals that could be used in an EXE300300150SS61E enclosure ratedat17.5watts(P)andat10amps(I).
SolvingforNintheaboveformulaN=P/(RxI2):n = 16.5 / (0.00345 x 102)n = 47
The maximum physical number of WDu 2.5 terminals that can be installed on a single rail is 29 and a total of 3 rails can be installed in the enclosure, therefore two rows of 23 terminal blocks could be accommodated in the enclosure.
COMBINED TERMINAL RESISTANCE FACTORPower ratings (Watts)
Phoenix Weidmuller (SAK/WDU)UK1.5 UK3 UK5 UK10 2.5 4 6 10
EXE10210276SS6E 3.8 W 0.00238 0.00171 0.00112 0.00042 0.00159 0.00117 0.00089 0.00043EXE152152102SS6E 6.9 W 0.00330 0.00227 0.00147 0.00056 0.00215 0.00152 0.00113 0.00057EXE178178102SS6E 6.9 W 0.00370 0.00251 0.00163 0.00062 0.00240 0.00167 0.00123 0.00063EXE216146127SS6E 9.6 W 0.00393 0.00265 0.00171 0.00065 0.00254 0.00176 0.00129 0.00066EXE254254127SS6E 9.6 W 0.00503 0.00332 0.00213 0.00082 0.00321 0.00218 0.00157 0.00083EXE300300150SS61E
EXE300300150SS61HE 16.5 W 0.00559 0.00360 0.00231 0.00090 0.00345 0.00217 0.00156 0.00096
EXE300300210SS61E EXE300300210SS61HE 16.5 W 0.00586 0.00376 0.00242 0.00094 0.00361 0.00227 0.00163 0.00100
EXE400300150SS61E EXE400300150SS61HE 18.5 W 0.00642 0.00410 0.00262 0.00102 0.00395 0.00248 0.00177 0.00108
EXE400300210SS61E EXE400300210SS61HE 18.5 W 0.00665 0.00424 0.00271 0.00106 0.00409 0.00257 0.00183 0.00111
EXE400400150SS61E EXE400400150SS61HE 18.5 W 0.00714 0.00454 0.00290 0.00113 0.00439 0.00275 0.00195 0.00119
EXE400400210SS61E EXE400400210SS61HE 18.5 W 0.00735 0.00466 0.00298 0.00116 0.00451 0.00283 0.00200 0.00122
EXE500400150SS61E EXE500400150SS61HE 23.5 W 0.00798 0.00504 0.00321 0.00126 0.00489 0.00306 0.00216 0.00131
EXE500400210SS61E EXE500400210SS61HE 23.5 W 0.00816 0.00515 0.00328 0.00128 0.00500 0.00313 0.00221 0.00134
EXE500500210SS61E EXE500500210SS61HE 25.5 W 0.00889 0.00559 0.00355 0.00139 0.00544 0.00341 0.00239 0.00145
EXE600500210SS61E EXE600500210SS61HE 28 W 0.00971 0.00608 0.00386 0.00152 0.00593 0.00372 0.00259 0.00157
EXE600600210SS61E EXE600600210SS61HE 28 W 0.01046 0.00653 0.00414 0.00163 0.00638 0.00400 0.00278 0.00169
EXE600600300SS61E EXE600600300SS61HE 28 W 0.01076 0.00671 0.00425 0.00167 0.00656 0.00411 0.00286 0.00173
EXE750500210SS61E EXE750500210SS61HE 28 W 0.01105 0.00688 0.00436 0.00172 0.00673 0.00422 0.00293 0.00178
EXE750600210SS61E EXE750600210SS61HE 33 W 0.01172 0.00728 0.00461 0.00182 0.00713 0.00447 0.00309 0.00187
EXE750750300SS61E EXE750750300SS61HE 33 W 0.01309 0.00810 0.00513 0.00202 0.00795 0.00498 0.00344 0.00208
EXE900600210SS61E EXE900600210SS61HE 33 W 0.01308 0.00810 0.00512 0.00202 0.00795 0.00498 0.00344 0.00208
COmbinEd tERminaL RESiStanCE faCtOR matRiXzONEX ENCLOSURES (Standard Sizes)
intEgRatOR paRtnER pROgRamIn response to the increasing demand for integration of increased safety ATEX/IECEX approved enclosures, Hoffman has developed a certified integrator program that allows approved integration companies to provide value-added enclosure solutions on belfalf of the Hoffman brand.
TheIntegratorPartnerProgramwill:• Allow enclosures to be populated with
terminal blocks• Modifyenclosureswithholes,cutouts
and customer tags• ProvidesATEX/IECEXcertificateforthe
assemblyTheIntegratorPartnerProgrammakesfull use of Hoffman’s industry-leading network of authorized distributors and their broad stock of enclosures to provide fast and efficient delivery.
ZOnE X EnCLOSuRE S 11
atEx-cErtifiEd aCCESSORiES
LOCk inSERtS (With kEy)
Lock inserts are field-installable. Stainless steel material and different key locking systems provides maximum protection for your equipment.
haZaRdOuS LOCatiOn WindOW kitSHazardous Location Window Kits are designed to be used on Increased Safety (Ex e) enclosures in ATEX or IECEx Zone 1 or 2 hazardous areas. These window kits are made with a robust heavy-gauge Type 316 stainless steel frame and a silicone gasket to ensure a dust-, oil-, and water-tight seal. Designed for use as viewing windows, these window kits are ideal for visibility of internal enclosure components. The window are easily installed by making a cutout in the enclosure and attaching the window and frame with included mounting hardware.
LaRgE-vOLumE atEX puRgE SyStEm type y, Z and Ex [pz]Designed to supply one or more enclosures with a protective gas supply, Hoffman’sEx[pz]purgesystemisdesignedandcertifiedaccordingtoEuropean requirements of ATEX Directive 94/9 EC and EN60079-2 for TypeEx[pz]applications.ATEX-certifiedEx[pz]purgesystemsreduce the classification in the protected enclosure from Zone 2 to non-hazardous, allowing the use and operation of general purpose equipment in the protected enclosure. used as a Type Y purge reduces classification from Div. 1 to Div. 2. Type Z purge reduces classification from Div. 2 to Non-Hazardous.
haZaRdOuS LOCatiOn hEatERDesigned for use in hazardous locations where electronic components require protection from condensation and corrosion, sudden temperature drops and low temperatures, Hoffman’s Hazardous location Heater offers maintenance-free, high-performance heating with a large convection surface, an extruded aluminum heat sink and 110-120 VAC operation.
haZaRdOuS LOCatiOn thERmOStatFor temperature control of heaters or low-temperature alarms in enclosures used in explosion-hazardous areas, Hoffman’s Hazardous location Thermostat features compact design and a robust thermostatic bimetallic sensor element for >100,000 cycle service life. The thermostat is usually connected directly and switched without the need for additional relays and offers high switching capacity with small hysteresis (switching difference).
haZaRdOuS LOCatiOn bREathER dRainSHazardous Location Breather Drains prevent moisture build-up within hazardous approved enclosures while maintaining enclosure UL Type rating. Drains are to be used when an enclosure is subject to fluctuations in temperature which can lead to the
formation of condensation and a subsequent moisture build-up. These drains allow air within an enclosure to breathe with the surrounding atmosphere, preventing condensation and any potential damage to electrical equipment.
Purge/pressurizationsystemscanbeusedforelectronics,electrical equipment, motors and switch gear in wall-mount to large enclosures, and also meet the demands of rack-mounted instrumentation, video displays, programmable controllers, computers, printers, recorders and measurement and calibration equipment. Available for 90 cubic feet maximum enclosurevolumeinverticalmount(VM)orhorizontalmount(HM)models.
induStRy StandaRdS (volume up to 90 cubic feet) 3003 WPSA type Y System Ul and fM Certified:ClassI,DivisionIGroup A,B,C,andD/Zone1,GroupsIIBandH2toDivision2/Zone2 type Z System Ul and fM Certified: Class1,Division2Group A,B,C,andD/Zone2,GroupsIIBandH2toNon-hazardousAteX CertifiedII3(3)GEx[pz]II,-29C≤Tamb.≤49C
MEXICO D.F.
MINNEAPOLIS TORONTO
SĀO PAULORIO DE JANEIRO
BETSCHDORF
HEMEL HEMPSTEAD
MOSCOW
WARSAW
DZIERZONIOW
LAINATE
SKARPNÄCK
STRAUBENHARDT
BANGALORE
DUBAI SHANGHAI
SHIN-YOKOHAMA
SINGAPORE
BOITUVA
QINGDAO
ISTANBUL
For morE InFormATIon AnD To ConTACT US, go To: WWW.pEntairprotEct.com
Bro-00179
EuropE
Straubenhardt, germany Tel: +49.7082.794.0
Betschdorf, france Tel: +33.3.88.90.64.90
Warsaw, Poland Tel: +48.22.209.98.35
Dzierzoniow, Poland Tel: +48.74.64.63.900
Hemel Hempstead, great Britain Tel: +44.1442.24.04.71
lainate, italy Tel: +39.02.932.714.1
Moscow, russia Tel: +7.495.926.18.85
North AmEricA
Minneapolis, Mn Tel: +1.763.421.2240
radford, VA Tel: +1.540.639.4440
Mexico, D.f. Tel: +52.55.5280.1449
toronto, Canada Tel: +1.416.289.2770
middlE EAst & iNdiA
Dubai, United Arabian emirates Tel: +971.4.37.81.700
Bangalore, india Tel: +91.80.6715.2001
istanbul, turkey Tel: +90.216.250.7374
AsiA
Shanghai, P.r. China Tel: +86.21.2412.1688
Singapore Tel: +65.6768.5800
Shin-Yokohama, Japan Tel: +81.45.476.0271
Seoul, Korea Tel: +82.2.2129.7755
Pentair,HoffmanandDesignwithConfidenceareownedbyPentairoritsglobalaffiliates.Allothertrademarksarethe property of their respective owners.
©2015Pentair.