Circuit breaker testing – New Approach
Thomas Renaudin
SEEEI conference
![Page 2: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/2.jpg)
Page 2© OMICRON
Circuit Breaker Testing
> Circuit Breakers – Design and standards
Tests on Circuit Breakers
CIBANO 500
![Page 3: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/3.jpg)
Page 3© OMICRON
Basically a circuit breaker is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Its basic function is to immediately discontinue electrical flow.
Definition of Circuit Breaker
Ideal switch:
closed open
R = 0 Ω R = ∞Ω
![Page 4: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/4.jpg)
Page 4© OMICRON
Purpose of Circuit Breakers in Power Systems
> Minimize losses in closed position
> Open and close on command
>Open or close a circuit to connect the power to/from the transmission line (O - break, C - make)
>Open a circuit for planned maintenance (O - break)
>Open a circuit at system fault to protect the system behind the circuit breaker (O break, O-C reclose, O-CO, auto-reclose)
>Isolate between poles, open contacts and earth
x
Busbar
Disconnector
Circuit Breaker
PowerTransformer
x Circuit Breaker
Network
![Page 5: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/5.jpg)
Page 5© OMICRON
Circuit Breaker Components
Source: ABB, [RUS07]
![Page 6: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/6.jpg)
Page 6© OMICRON
A: interrupter chamber
B: insulated support column
C: support structure
D: central cubical
E: wiring
F: operating mechanism
Source: Siemens
Circuit Breaker Components
![Page 7: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/7.jpg)
Page 7© OMICRON
Standards – ANSI
> C37.04-1999> Standard ratings defined
> C37.06-2000> Schedule of preferred ratings
> C37.09-1999> Type tests> Routine tests
> C37.081, C37.082, IEEE 693
![Page 8: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/8.jpg)
Page 8© OMICRON
Standards – IEC
> IEC 62271-100, 2001> Type, routine & field tests> Timing definitions> Guide for selection and
specification
> IEC 60694, 2001> Normal service
conditions> Schedule of preferred
ratings> Altitude correction
> IEC 60427, IEC 60815, IEC 60529, IEC 61166, IEC 61233
![Page 9: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/9.jpg)
Page 9© OMICRON
IEC - timing definition
![Page 10: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/10.jpg)
Page 10© OMICRON
Circuit Breaker Testing
Circuit Breakers – Design and standards> Tests on Circuit Breakers
CIBANO 500
![Page 11: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/11.jpg)
Page 11© OMICRON
What is usually needed to test breakers
Timing Analyzer
µΩ - Meter CB Supply
> Rewiring for each test> Individual µΩ-Measurement for each interrupter> Collect data for test report
![Page 12: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/12.jpg)
Page 12© OMICRON
1. Minimum pick-up test
2. Static resistance or contact resistance test (µOhm)
3. Timing of main and auxiliary contactsa. different operations (O, C, OC, CO, OCO, COCO, OCOCO,...)b. undervoltage testc. coil currents
4. Motor current
5. Contact travel (motion) of main contacts
6. Dynamic contact resistance (DRM)
Typical tests on circuit breakers
![Page 13: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/13.jpg)
Page 13© OMICRON
1. Minimum Pick-up Test
![Page 14: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/14.jpg)
Page 14© OMICRON
1. Minimum Pick-up Test
> Indicates the lowest voltage to operate the trip or close coil
> Start at a certain voltage level> Try to operate> If not working increase voltage and try again> Ramp the voltage pulse until minimum voltage is re
ached with which the circuit breaker switches> Everybody has a „selfmade“ solution for this test
![Page 15: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/15.jpg)
Page 15© OMICRON
2. Contact Resistance Test
Conventional Setup
![Page 16: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/16.jpg)
Page 16© OMICRON
2. Contact Resistance Test
> Test is performed with a µOhm-Meter> A lot of different test devices on the market (weight,
handling, output current and accuracy)> Inject a high current> Measurement of a small voltage in a noisy environ
ment> Use 4-wire technique to connect
![Page 17: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/17.jpg)
Page 17© OMICRON
3a. Timing Test
> Connect to all main contacts> Connect to trip & close coil> Voltage supply required
Time-consuming anderror-prone
Conventional Setup
![Page 18: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/18.jpg)
Page 18© OMICRON
3a. Timing Test - Measured Values
Open Time, Close Time, Contact Spread, Phase Spread, Trip-Free Time, Reclose Time
![Page 19: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/19.jpg)
Page 19© OMICRON
3b. Timing undervoltage condition> Coils are normally driven by station battery> What happens if battery condition is not the best> Perform a test with reduced supply voltage (e.g. 80
%)> Check times for under voltage> does it work anyhow> are there any delays compared to nominal voltage?
> Measure the overall times and compare to manufacturer values
![Page 20: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/20.jpg)
Page 20© OMICRON
3c. Coil Current> Important tool in circuit breaker analysis> Detect potential problems in actuating coils> Reveal information on power supply> Comparison is best method of analysis
![Page 21: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/21.jpg)
Page 21© OMICRON
4. Motor Current
> Connect source to charging motor or use current clamp
> Check charging times and charging currents
> Compare with previous measurements
![Page 22: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/22.jpg)
Page 22
5. Contact Travel
Page 22© OMICRON
Functional Breaker Model
![Page 23: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/23.jpg)
Page 23© OMICRON
5. Contact Travel - Travel Measurement to find out:
> Mechanical defects of the cinematic chain> Overall mechanical performance> Slow operation due to jammed mechanism> Deterioration of mechanical damping
> Contact wear> Arcing contact length (in combination with DRM)
![Page 24: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/24.jpg)
Page 24© OMICRON
6. Dynamic Resistance Measurement (DRM)
> Recording the contact resistance during breaker operation (resistance over time)
> Combination of contact resistance, timing and travel measurements
1.Inject high current
2.Start recording A & V
3.Operate Circuit Breaker
4.Calculate Resistance
![Page 25: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/25.jpg)
Page 25
6. Dynamic Resistance Measurement (DRM)
Use DRM to find out> Problems with contact fingers> Lubrication problems> The arcing contact length
Page 25© OMICRON
![Page 26: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/26.jpg)
Page 26
6. DRM Diagnosis: arcing contact length
Page 26© OMICRON
motion
dynamic resistance
coil current
arcing contact length
main contact
ms
![Page 27: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/27.jpg)
Page 27© OMICRON
Circuit Breaker Testing
Circuit Breakers – Design and standards
Tests on Circuit Breakers> CIBANO 500
![Page 28: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/28.jpg)
Page 28© OMICRON
Conventional Setup for Circuit Breaker Testing
> Rewiring between micro-ohm measurement and timing tests
> Lots of cables
> Time-consuming and error-prone
> Long test cables create inductive loops which catch interferences
> External supply or station battery required
Mirco-ohm measurement
Timing Tests
![Page 29: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/29.jpg)
Page 29© OMICRON
CIBANO 500 – 3-in-1 Test System> Timing analyzer> Possible operations: O, C, CO, OC, O-CO, CO-CO, O-CO-CO> Motion measurement is possible in parrallel
> Micro-ohm meter> Static AND dynamic contact resistance test
> Powerful coil and motor stabilized supply> Coil/motor current analysis> Undervoltage condition test> Minimum pick-up test> Tests are possible without station battery
![Page 30: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/30.jpg)
Page 30© OMICRON
CIBANO 500 – one system for all types of breakers
> Medium-voltage circuit breakers
> High-voltage circuit breakers (Live Tank)
> High-voltage circuit breakers (Dead Tank)
![Page 31: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/31.jpg)
Page 31© OMICRON
Unique connection concept
CIBANO 500 CB TN3
CB MC2
![Page 32: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/32.jpg)
Page 32© OMICRON
Modular concept for simplified testing – Main Contact Module CB MC2> 2 high-current outputs and 2 sensitive voltage
measurement channels
> Keeps high-current cables as short as possible> minimizing the weight of the necessary cables
> A digitized measuring signal is produced directly at the interrupter keeping analog cables as short as possible
> very low noise interference
> Only one connection cable to the main unit> fast set-up and reduced risk of wiring errors
> Both sides grounded test possible
![Page 33: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/33.jpg)
Page 33© OMICRON
Unique connection concept
![Page 34: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/34.jpg)
Page 34© OMICRON
Unique connection concept
![Page 35: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/35.jpg)
Page 35© OMICRON
Modular concept for simplified testing – Transducer Node CB TN3> Accessory for motion/contact travel test
> 3 analog and digital channels for data acquisition of linear or rotational motion sensors
> Interference-free digital transmission of results via one cable
![Page 36: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/36.jpg)
Page 36© OMICRON
Powerful software support
> Primary Test Manager software supports all tests
> One combined test report for all tests
![Page 37: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/37.jpg)
Page 37© OMICRON
Benefits of all-in-one OMICRON approach
> 3-in-1 system combines:> timing analyzer> micro-ohmmeter> powerful AC/DC supply
> One wiring for all test: all-in-one / all-in-once
> One system for medium- and high-voltage circuit breakers
> Immunity to interference due to short test cables
> One combined report for all tests
> Light-weight test system for on-site testing (20 kg / 44.1 lbs)
![Page 38: * Circuit breaker testing – New Approach Thomas Renaudin SEEEI conference](https://reader035.vdocument.in/reader035/viewer/2022062518/56649cf75503460f949c6bd2/html5/thumbnails/38.jpg)
Page 38© OMICRON