INSTRUCTIONS FOR (-)XRF-KDA1 MANUAL FRESH AIR DAMPER (-)XRX-AW02 MOTORIZED AND FRESH AIR DAMPER KIT WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING ADJUSTMENT OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN IMPROPER INSTALLATION, ADJUSTMENT; SERVICE OR MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Recognize this symbol as an indication of Important Safety Information! WARNING 6. Adjust damper slide to appropriate opening now. 7. Trap (C) filters between (C) front filter support and filter support on the (A) damper assembly while attaching to the (B) hood side with (3) screws provided. 8. Attach (D) rain hood (previously the top left panel) to the (B) hood side with (4) screws each side, (6) screws between rain hood and front filter support. 9. Attach (E) rain hood top to the same location as upper edge of (A) damper panel assembly with (6) screws that were removed in step 2. 10. Secure (E) rain hood top to rain hood and hood side with (8) screws provided. 11. Secure all remaining screws, making sure that all weather exposed screw holes use the screws. FRONT FILTER SUPPORT RAIN HOOD (PREVIOUSLY TOP LEFT PANEL) HOOD SIDES FILTER - PERMANENT (2) REQ'D RAIN HOOD TOP DAMPER PANEL ASSEMBLY NOTE: CIRCLED LETTERS EQUAL ORDER OF INSTALLATION TURN OFF ELECTRIC POWER TO THE UNIT BEFORE ATTEMPTING ANY MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL lNJURY OR DEATH. 1. Remove (4) screws from each side of the unit top cover. 2. Remove all screws from top left panel (retain screws and top left panel for later use). 3. Lift top cover high enough to replace top left panel with damper panel assembly. 4. Replace top left panel with (A) damper panel assembly. 5. Secure the (B) hood sides to the edges of the (A) damper panel assembly with (6) screws removed in step 2. DAMPER SLIDE FILTER SUPPORT A E C B B C D

Upload: others

Post on 17-Jun-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: rmioad13d.vp RXRF-KDA1 Manual Fresh Air Damper, RXRX-AW02

INSTRUCTIONS FOR(-)XRF-KDA1 MANUAL FRESH AIR DAMPER

(-)XRX-AW02 MOTORIZED ANDFRESH AIR DAMPER KIT

WARN ING

THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FORPROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONSTHOROUGHLY BEFORE ATTEMPTING ADJUSTMENT OR OPERATION. FAILURE TO FOLLOW THESEINSTRUCTIONS CAN RESULT IN IMPROPER INSTALLATION, ADJUSTMENT; SERVICE OR MAINTENANCE,POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

Recognize this symbol as an indication of Important Safety Information!

WARN ING

6. Adjust damper slide to appropriate opening now.

7. Trap (C) filters between (C) front filter support and filter support on the (A) damper assembly while attaching to the (B) hood side with (3) screws provided.

8. Attach (D) rain hood (previously the top left panel) tothe (B) hood side with (4) screws each side, (6) screwsbetween rain hood and front filter support.

9. Attach (E) rain hood top to the same location as upperedge of (A) damper panel assembly with (6) screwsthat were removed in step 2.

10. Secure (E) rain hood top to rain hood and hood sidewith (8) screws provided.

11. Secure all remaining screws, making sure that allweather exposed screw holes use the screws.

FRONT FILTER SUPPORT

RAIN HOOD(PREVIOUSLY TOP LEFT PANEL)

HOOD SIDES

FILTER - PERMANENT(2) REQ'D

RAIN HOOD TOP

DAMPER PANEL ASSEMBLY

NOTE:

— CIRCLED LETTERS EQUALORDER OF INSTALLATION

TURN OFF ELECTRIC POWER TO THE UNIT BEFOREATTEMPTING ANY MAINTENANCE. FAILURE TO DOSO CAN CAUSE ELECTRICAL SHOCK RESULTING INPERSONAL lNJURY OR DEATH.

1. Remove (4) screws from each side of the unit topcover.

2. Remove all screws from top left panel (retain screwsand top left panel for later use).

3. Lift top cover high enough to replace top left panel withdamper panel assembly.

4. Replace top left panel with (A) damper panelassembly.

5. Secure the (B) hood sides to the edges of the (A)damper panel assembly with (6) screws removed instep 2.

DAMPER SLIDE

FILTER SUPPORT

A

E

C

B

B

C

D

Page 2: rmioad13d.vp RXRF-KDA1 Manual Fresh Air Damper, RXRX-AW02

IF UNIT HAS AN EX IST ING MAN UAL FRESH AIR DAMPER Refer to page 1. Reverse assembly procedure untildamper panel assembly is removed. Assemble motorizeddamper assembly (see (F) below). Then reassemble freshair damper using motorized damper assembly.

IF UNIT HAS NO EX IST ING MAN UAL FRESH AIR DAMPER 1. Assemble motorized damper panel assembly by

removing the damper slide from damper panelassembly, then attaching the (F) motorized damper tothe opposite side. Use (6) of the screws from thedamper slide to attach the motorized damper.

2. Remove (4) screws from top cover sides.

3. Remove all screws from top left panel (retain screwsand top left panel for later use).

MO TOR IZED DAMPER

FRONT FILTER SUPPORT

FILTER - PERMANENT (2) REQ'D

RAIN HOOD TOP

MOTORIZED DAMPERPANEL ASSEMBLY

4. Lift top cover and remove top left panel. Plug powercord for motorized damper into polarized wire harnessconnector.

5. Apply power to unit and set minimum damper positionwith adjustment wheel on damper motor.

6. Secure the (B) hood sides to the edges of the (A)motorized damper panel assembly with (6) screwsremoved in step 3.

7. Trap (C) filters between (C) front filter support and filter support on the (A) damper assembly while attaching to the (B) hood side with (3) screws provided.

8. Attach (D) rain hood (previously the top left panel) tothe (B) hood side with (4) screws each side, (6) screwsbetween rain hood and front filter support.

9. Attach (E) rain hood top to the same location as upperedge of (A) damper panel assembly with (6) screwsthat were removed in step 3.

10. Secure (E) rain hood top to rain hood and hood sidewith (8) screws provided.

11. Secure all remaining screws, making sure that allweather exposed screw holes use the screws.

DAMPER PANEL AS SEM BLY

MOTORIZED DAMPER PANEL ASSEMBLY

DAMPERSLIDE

(DISCARD)

HOOD SIDES

HOOD SIDES

TOP COVER(REF.)

NOTE:

— CIRCLED LETTER EQUALORDER OF INSTALLATION

A

E

C

B

B

C

D

RAIN HOOD(PREVIOUSLY TOP LEFT PANEL)

A

F

Page 3: rmioad13d.vp RXRF-KDA1 Manual Fresh Air Damper, RXRX-AW02

TO AD JUST DAMPER MIN I MUM PO SI TION 1. Remove return air cover.

2. Apply power to unit.

3. Supply fan must be on.

4. Turn potentiometer wheel on damper motor to adjustdamper minimum position,

5. After successfully adjusting damper position, replacereturn air cover.

FOR HOR I ZON TAL AIR FLOW IN STAL LA TIONS 1. Installer must provide opening in return air duct with

removable cover for access to minimum positionadjustment on motorized damper.

2. Remove cover on return air duct.

3. Apply power to unit.

4. Supply fan must be on.

5. Turn potentiometer wheel on damper motor to adjustdamper minimum position.

6. After successfully adjusting damper position, replacecover on return air duct.

DAMPER MOTOR

RETURN AIRCOVER

12"

8"

DRIP RAIL

REMOVABLE COVER

WITH UNIT POWER ON,TURN WHEEL ON DAMPER MOTOR TO ADJUSTMINIMUM POSITION

RMIOAD13DSUPERSEDES 04-06-09JUNE 4, 2009

Page 4: rmioad13d.vp RXRF-KDA1 Manual Fresh Air Damper, RXRX-AW02

0-35% Mo tor ized Out side Air(-)XRX-AW02

Notes:1. Unit wir ing shown as ref er ence only. Check unit wir ing for ac tual unit wir ing.

CONNECTOR & CONTACT CONFIGURATIONPL7 (303917) CAP - (303902) SOCKET

WIRE COLOR CODE

BLK Black BLU BlueBRN Brown GRY GrayORG Orange RED RedVIO Violet WHT WhiteYEL Yellow

COMPONENT CODE

EconomizerM8405A Damper Actuator 24vPL6 Male A/C Unit PlugPL7 Female A/C Unit PlugPL20 Female Damper PlugPL21 Male Smoke Plug

Re vi sion Change Date

HARNESS ENDS AT PL6 & PL7

Date: March 19, 2009

Supercedes:

Drawn by: MGL

Unit #: 60-287-13D

Di a gram#: 6028713DW

Ap proved by: