04 sundyne presentation fscontrol system

Upload: joseellargo

Post on 04-Jun-2018

257 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    1/27

    CONTROL SYSTEMS

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    2/27

    INTRODUCTION

    General, pump curve - System curve

    Parallel operation

    Series operation

    Compressor control

    Pump control bulletin

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    3/27

    GENERAL DISCUSSION

    Are recurring problems a responsibility of maintenance?

    Controls/procedures may result in equipment failure

    May need coordination with process group

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    4/27

    CURVE SHAPES

    120

    100

    80

    60

    40

    00 20 40 60 80 100 120 140 160

    Flow (Percent)

    Head

    (Percent)

    Full EmissionConcentric Bowl & ETADouble Log Spiral

    Z Series

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    5/27

    TOTAL SYSTEM HEAD

    Capacity, Q

    Head, H

    System static head

    System friction head

    System head

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    6/27

    IMPACT OF VALVE THROTTLING

    Capacity, Q

    Head, H

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    7/27

    OPERATING SYSTEM

    Capacity, Q

    Head, H

    Q2 Q1

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    8/27

    BY-PASS REQUIRED?

    Capacity, Q

    Head, H

    Bypass Flow

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    9/27

    INTERSECTION OF PUMP AND SYSTEMCURVES

    Capacity, Q

    Head, H

    Under-sized pump

    Properly sized pump

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    10/27

    IMPACT OF WEAR

    Over a period of time, system and pump characteristics getdeteriorated

    After 15 years, friction losses in pipe are 60% more important!

    To be taken in account in the choice of the pump

    Minor loss for pump performances

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    11/27

    MINIMUM FLOW

    2 Types of Minimum flow phenomena:

    At start-up

    During normal operation

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    12/27

    MINIMUM FLOWat start-up

    Start-up shock wave

    Water Hammering

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    13/27

    MINIMUM FLOWduring operation

    Minimum Continuous stable flow

    Minimum Continuous thermal flow

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    14/27

    MINIMUM FLOWFlow surging

    May happen if a air/gas pocket is located in the downstream line

    Can be seen as a simple spring-mass system

    Need a excitation to happen

    Can be reduced / solved by having a flow control valve close from thepump discharge

    Predominent for compressors

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    15/27

    MINIMUM FLOWSurging reduction

    Control valve within 3m of discharge

    Flexible lines only after control valve

    A straight pipe of at least 10 times diameter length on the discharge

    Choose correct size of valve

    Install low flow by pass

    Eliminate air and gasses trapped

    Operate at higher flow

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    16/27

    MINIMUM FLOWMinimum flow control

    S FS

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    17/27

    MINIMUM FLOWPhenomenon

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    18/27

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    19/27

    MAXIMUM FLOWPhenomenon

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    20/27

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    21/27

    CONTROLLING

    120

    100

    80

    60

    40

    00 20 40 60 80 100 120 140 160

    Flow (Percent)

    Head

    (Perc

    ent)

    Full EmissionConcentric Bowl & ETADouble Log SpiralZ Series

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    22/27

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    23/27

    PARALLEL OPERATION

    Always use discharge check valve.

    Need differential to open check valve

    Low gravity fluid may vaporize - Pump deadheaded.

    Unstable operation results in equipment damage

    Always use bypass control valve.

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    24/27

    PARALLEL OPERATION WITH FLOW

    CONTROLLED BYPASS ON EACH PUMP

    FLOW SENSOR

    CONTROLLER

    BLOCK

    CHECK

    BYPASS

    CONTROL

    VALVE

    CONTROLLER

    FLOW SENSOR

    BLOCK

    CHECK

    BYPASSCONTROL

    VALVE

    THROTTLE

    CONTROL

    VALVE

    A

    B

    STARTUP SEQUENCE

    1. SET EACH BYPASS FORMIN. ALLOWABLE FLOW

    2. CLOSE PROCESS FLOW

    CONTROL VALVE3. START PRE-LUBE PUMPS

    IF APPLICABLE4. START A AND STABILIZE

    START B AND STABILIZE5. SET DESIRED PROCESS

    FLOW RATE

    PARALLEL OPERATION

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    25/27

    SERIES OPERATION

    Capacity, Q

    Head, H

    PUMP A OR B

    PUMP A AND B

    SYSTEM HEAD CURVE

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    26/27

    SERIES OPERATION

    Requires extra measure of care (for second unitespecially)

    Pre-lube normally advisable on 2nd unit.

    Tandem seal & suitable buffer probably required.

    Flange rating to be reviewed

    Thurst bearing capacity to be increased

  • 8/13/2019 04 Sundyne Presentation Fscontrol System

    27/27

    STARTUP SEQUENCE1. SET BYPASS FOR MIN. ALLOWABLE FLOW2. CLOSE PROCESS FLOW CONTROL VALVE3. START PRE-LUBE PUMPS IF APPLICABLE

    4. START 1ST UNIT AND STABILIZE5. START 2ND UNIT AND STABILIZE6. SET DESIRED PROCESS FLOW RATE

    BYPASS FLOW

    CONTROL

    SENSOR CHECK

    CHECKCONTROLLER

    PROCESS FLOW

    CONTROL VALVE

    SERIES OPERATION - PREFERRED