05 - pcs924 stub differential relay
DESCRIPTION
PCS924 Stub Differential RelayTRANSCRIPT
-
1 Introduction
PCS-924 Stub Differential Relay 1-a Date: 2011-08-02
1 Introduction
Table of Contents
1.1 Application ....................................................................................................... 1-1
1.2 Function ........................................................................................................... 1-1
1.3 Features ........................................................................................................... 1-3
List of Figures
Figure 1.1-1 Functional diagram of PCS-924 ............................................................................ 1-1
-
1 Introduction
PCS-924 Stub Differential Relay 1-b Date: 2011-08-02
-
1 Introduction
PCS-924 Stub Differential Relay 1-1 Date: 2011-08-02
1.1 Application
PCS-924 is a fully numerical stub differential relay which is mainly designed for protecting T zone
of one and a half breakers arrangement. It is developed based on UAPC (Unified Advanced
Platform for Protection and Control) platform.
The protection function of PCS-924 comprises of current differential protection, phase overcurrent
protection and feeder line end fault protection.
Busbar No.1
Line
52
52
52
Line
Busbar No.2
*
*
*
ICB2
ICB1
ILine
50P87S 50FLE
PCS-924
Figure 1.1-1 Functional diagram of PCS-924
1.2 Function
1. Protection Functions
Current differential protection (87S)
Phase overcurrent protection (50P)
Feeder line end fault protection (50FLE)
2. Logic
User programmable logic
3. Additional function
CT circuit supervision (CTS)
Self diagnostic
-
1 Introduction
PCS-924 Stub Differential Relay 1-2 Date: 2011-08-02
DC power supply supervision
Current drift auto regulation
Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events and 1024 device logs.
Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Clock synchronization
PPS (RS-485)
IRIG-B (RS-485)
PPM (DIN)
SNTP (PTP)
IEEE1588
SNTP (BC)
PPS (DIN)
4. Monitoring
Number of circuit breaker operation (single-phase tripping, three-phase tripping and
reclosing)
Frequency
5. Communication
2 RS-485 communication rear ports conform to IEC 60870-5-103 protocol or DNP3.0 protocol
1 RS-485 communication rear ports for clock synchronization
Up to 4 Ethernet ports (depend on the chosen type of plug-in MON module), IEC 61850, or
IEC 60870-5-103 over TCP/IP
Up to 2 Ethernet ports via optic fiber (ST interface or SC interface, depend on the chosen type
of plug-in MON module)
GOOSE communication function (optional plug-in module)
6. User Interface
Friendly HMI interface with LCD and 9-button keypad on the front panel.
1 front multiplex RJ45 port for testing and setting
1 RS-232 or RS-485 rear ports for printer
Language switchover English + selected language
-
1 Introduction
PCS-924 Stub Differential Relay 1-3 Date: 2011-08-02
Auxiliary software - PCSPC
1.3 Features
The intelligent device integrated with protection, control and monitor provides powerful
protection function, flexible protection configuration, user programmable logic and
configurable binary input and binary output, which can meet with various application
requirements.
High-performance hardware platform and modularized design, MCU (management control
unit) + DSP (digital signal processor). MCU manages general fault detector element and DSP
manages protection and metering. Their data acquisition system is completely independent in
electronic circuit. DC power supply of output relay is controlled by the operation of fault
detector element operates, this prevents maloperation due to error from ADC or damage of
any apparatus.
Multiple setting groups with password protection
Powerful PC tool software can fulfill protection function configuration, modify setting and
waveform analysis.
-
1 Introduction
PCS-924 Stub Differential Relay 1-4 Date: 2011-08-02
-
2 Technical Data
PCS-924 Stub Differential Relay 2-a Date: 2013-06-19
2 Technical Data
Table of Contents
2.1 Electrical Specifications ................................................................................. 2-1
2.1.1 AC Current Input .................................................................................................................. 2-1
2.1.2 AC Voltage Input .................................................................................................................. 2-1
2.1.3 Power Supply ....................................................................................................................... 2-1
2.1.4 Binary Input .......................................................................................................................... 2-1
2.1.5 Binary Output ....................................................................................................................... 2-2
2.2 Mechanical Specifications.............................................................................. 2-2
2.3 Ambient Temperature and Humidity Range .................................................. 2-2
2.4 Communication Port ....................................................................................... 2-3
2.4.1 EIA-485 Port ........................................................................................................................ 2-3
2.4.2 Ethernet Port ........................................................................................................................ 2-3
2.4.3 Optical Fibre Port ................................................................................................................. 2-3
2.4.4 Print Port .............................................................................................................................. 2-4
2.4.5 Clock Synchronization Port ................................................................................................. 2-4
2.5 Type Tests ........................................................................................................ 2-4
2.5.1 Environmental Tests............................................................................................................. 2-4
2.5.2 Mechanical Tests ................................................................................................................. 2-4
2.5.3 Electrical Tests ..................................................................................................................... 2-4
2.5.4 Electromagnetic Compatibility ............................................................................................. 2-4
2.6 Certifications ................................................................................................... 2-5
2.7 Protective Functions ....................................................................................... 2-6
2.7.1 Current Differential Protection ............................................................................................. 2-6
2.7.2 Phase Overcurrent Protection ............................................................................................. 2-6
2.7.3 Feeder Line End Fault Protection ........................................................................................ 2-6
-
2 Technical Data
PCS-924 Stub Differential Relay 2-b Date: 2013-06-19
-
2 Technical Data
PCS-924 Stub Differential Relay 2-1 Date: 2013-06-19
2.1 Electrical Specifications
2.1.1 AC Current Input
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 505Hz, 605Hz
Rated Current (In) 1A 5A
Linear to 0.05In~40In
Thermal withstand
-continuously
-for 10s
-for 1s
-for half a cycle
4In
30In
100In
250In
Burden < 0.15VA/phase @In < 0.25VA/phase @In
Accuracy 0.5%In
2.1.2 AC Voltage Input
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 505Hz, 605Hz
Rated Voltage (Un) 100V~130V
Linear to 1V~170V
Thermal withstand
- continuously
-10s
-1s
200V
260V
300V
Burden at rated < 0.25VA/phase @Un
Accuracy 0.5%Un
2.1.3 Power Supply
Standard IEC 60255-11:2008
Rated Voltage 110Vdc/125Vdc, 220Vdc/250Vdc
Operating Range 80%~120% of rated voltage
Permissible AC ripple voltage 15% of the nominal auxiliary voltage
Burden
Quiescent condition
Operating condition
-
2 Technical Data
PCS-924 Stub Differential Relay 2-2 Date: 2013-06-19
Maximum permissible voltage 120% of rated voltage
Withstand voltage
-continously 2000Vac, 2800Vdc
Response time for logic input
-
2 Technical Data
PCS-924 Stub Differential Relay 2-3 Date: 2013-06-19
Permissible humidity 5%-95%, without condensation
Pollution degree
Altitude
-
2 Technical Data
PCS-924 Stub Differential Relay 2-4 Date: 2013-06-19
2.4.3.3 For Synchronization Port
Characteristic Glass optical fiber
Connector type ST
Fibre type Multi mode
Wave length 820nm
Minimum receiving power Min. -25.0dBm
Margin Min +3.0dB
2.4.4 Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON 300K printer
Safety level Isolation to ELV level
2.4.5 Clock Synchronization Port
Type RS-485
Transmission distance 100M@500VDC
2.5.4 Electromagnetic Compatibility
1MHz burst disturbance test IEC 60255-22-1:2007
-
2 Technical Data
PCS-924 Stub Differential Relay 2-5 Date: 2013-06-19
Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Electrostatic discharge test
IEC60255-22-2:2008 class IV
For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests
IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80~1000MHz
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Fast transient disturbance tests
IEC 60255-22-4:2008
Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Surge immunity test
IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
Conducted RF Electromagnetic
Disturbance
IEC 60255-22-6:2001
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Power Frequency Magnetic Field
Immunity
IEC 61000-4-8:2001
class V, 100A/m for 1min, 1000A/m for 3s
Pulse Magnetic Field Immunity IEC 61000-4-9:2001
class V, 6.4/16s, 1000A/m for 3s
Damped oscillatory magnetic field
immunity
IEC 61000-4-10:2001
class V, 100kHz & 1MHz100A/m
Auxiliary power supply performance
- Voltage dips
-Voltage short interruptions
IEC60255-11: 2008
Up to 500ms for dips to 40% of rated voltage without reset
100ms for interruption without rebooting
2.6 Certifications
ISO9001:2008
ISO14001:2004
OHSAS18001:2007
ISO10012:2003
-
2 Technical Data
PCS-924 Stub Differential Relay 2-6 Date: 2013-06-19
CMMI L5
EMC: 2004/108/EC, EN50263:1999
Products safety(PS): 2006/95/EC, EN61010-1:2001
2.7 Protective Functions
Note!
The meanings of symbols mentioned in the following sections are given here.
In -- rated secondary current of CT
Un -- rated secondary phase-to-ground voltage of VT
Unn -- rated secondary phase-to-ground voltage of VT
2.7.1 Current Differential Protection
Setting range 0.100In~1.000In
Accuracy 2.5% of setting or 0.02In whichever is greater
2.7.2 Phase Overcurrent Protection
Setting range 0.100In~20.000In
Accuracy 2.5% of setting or 0.01Un, whichever is greater
Time delay 0.01~10.00s
Accuracy 1% of Setting+30ms (at 1.2 times voltage setting)
2.7.3 Feeder Line End Fault Protection
Setting range 0.100In~20.000In
Accuracy 2.5% of setting or 0.01Un, whichever is greater
Time delay 0.01~10.00s
Accuracy 1% of Setting+30ms (at 1.2 times voltage setting)
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-a Date: 2011-08-02
3 Operation Theory
Table of Contents
3.1 Fault Detector (FD) .......................................................................................... 3-1
3.1.1 Application............................................................................................................................ 3-1
3.1.2 Fault Detector in Fault Detector DSP .................................................................................. 3-1
3.1.3 Protection Fault Detector in Protection Calculation DSP .................................................... 3-2
3.1.4 Function Block Diagram ...................................................................................................... 3-3
3.1.5 I/O Signal ............................................................................................................................. 3-3
3.2 Current Differential Protection ....................................................................... 3-4
3.2.1 Function Description ............................................................................................................ 3-4
3.2.2 Protection Principle .............................................................................................................. 3-4
3.2.3 Function Block Diagram ...................................................................................................... 3-6
3.2.4 I/O Signal ............................................................................................................................. 3-6
3.2.5 Logic .................................................................................................................................... 3-7
3.2.6 Settings ................................................................................................................................ 3-9
3.3 Feeder Line End Fault Protection .................................................................. 3-9
3.3.1 Application............................................................................................................................ 3-9
3.3.2 Protection Principle .............................................................................................................. 3-9
3.3.3 Function Block Diagram .................................................................................................... 3-10
3.3.4 I/O Signal ........................................................................................................................... 3-10
3.3.5 Logic .................................................................................................................................. 3-10
3.3.6 Settings ............................................................................................................................... 3-11
3.4 Phase overcurrent protection ....................................................................... 3-11
3.4.1 Protection Principle ............................................................................................................. 3-11
3.4.2 Function Block Diagram .................................................................................................... 3-12
3.4.3 I/O Signal ........................................................................................................................... 3-12
3.4.4 Logic .................................................................................................................................. 3-12
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-b Date: 2011-08-02
3.4.5 Settings .............................................................................................................................. 3-13
3.5 Trip Logic ....................................................................................................... 3-13
3.5.1 Application.......................................................................................................................... 3-13
3.5.2 Function Description .......................................................................................................... 3-13
3.5.3 Logic .................................................................................................................................. 3-14
3.5.4 I/O Signal ........................................................................................................................... 3-14
3.5.5 Settings .............................................................................................................................. 3-15
List of Figures
Figure 3.1-1 Flow chart of protection program ........................................................................ 3-3
Figure 3.2-1 3-terminal application ............................................................................................ 3-4
Figure 3.2-2 Logic of 3-terminal current differential protection ............................................. 3-7
Figure 3.2-3 Logic of 2-terminal current differential protection ............................................. 3-8
Figure 3.3-1 Logic of feeder line end fault protection ........................................................... 3-11
Figure 3.4-1 Logic of phase overcurrent protection .............................................................. 3-13
Figure 3.5-1 Simplified tripping logic ...................................................................................... 3-14
List of Tables
Table 3.1-1 Input signal ............................................................................................................... 3-3
Table 3.1-2 Output signal ............................................................................................................ 3-3
Table 3.2-1 Input signals ............................................................................................................. 3-6
Table 3.2-2 Output signals .......................................................................................................... 3-6
Table 3.2-3 Current differential protection settings ................................................................. 3-9
Table 3.3-1 Input signals ........................................................................................................... 3-10
Table 3.3-2 Output signals ........................................................................................................ 3-10
Table 3.3-3 Feeder line end fault protection settings ............................................................ 3-11
Table 3.4-1 Input signals ........................................................................................................... 3-12
Table 3.4-2 Output signals ........................................................................................................ 3-12
Table 3.4-3 Current differential protection settings ............................................................... 3-13
Table 3.5-1 Input signal ............................................................................................................. 3-14
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-c Date: 2011-08-02
Table 3.5-2 Output signal .......................................................................................................... 3-14
Table 3.5-3 Setting description ................................................................................................ 3-15
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-d Date: 2011-08-02
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-1 Date: 2011-08-02
3.1 Fault Detector (FD)
3.1.1 Application
The device has plug-in DSP modules with fault detector DSP and protection DSP for fault detector
and protection calculation respectively. Protection DSP with protection fault detector element is
responsible for calculation of protection elements, and fault detector DSP is responsible to
determine fault appearance on the protected power system. Fault detector in fault detector DSP
picks up to provide positive supply to output relays. The output relays can only operate when both
the fault detector in fault detector DSP and a protection element operate simultaneously.
Otherwise, the output relays would not operate. An alarm message will be issued with blocking
outputs if a protection element operates while the fault detector does not operate.
3.1.2 Fault Detector in Fault Detector DSP
Main part of FD is differential current fault detector element and two breakers sum current fault
detector element. They are continuously calculating the analog input signals.
The FD pickup condition in this relay includes:
1. Pickup condition 1: differential current is greater than the setting value
2. Pickup condition 2: two breakers sum current is greater than the setting value
If any of the above conditions is complied, the FD will operate to activate the output circuit
providing with DC power supply to the output relays.
3.1.2.1 Fault Detector Based on Differential Current (pickup condition 1)
The criterion is:
I3Dmax > [87S.I_Biased] Equation 3.1-1
Where:
= A, B or C
I3Dmax = Max( Line_CB2_CB1_ III ), the maximum value of phase differential current of phase
A, phase B and phase C, please refer to Figure 3.2-1 about CB1I , CB2I and LineI .
[87S.I_Biased]: current setting of current differential protection.
If operating condition is met, differential current element will pickup and trigger FD to provide DC
power supply for output relays, the FD operation signal will maintain 7s after differential current
element drops off.
3.1.2.2 Fault Detector Based on Two Breakers Sum Current (pickup condition 2)
The criterion:
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-2 Date: 2011-08-02
Max( CB2_CB1_ II ) > [50P.I_Set] Equation 3.1-2
Where:
= A, B or C
CB1I , CB2I : secondary current of two circuit breakers.
[50P.I_Set]: current setting of phase overcurrent protection
If above condition is met and phase overcurrent protection is enabled, two breakers sum current
element will pickup and trigger FD to provide DC power supply for output relays, the FD operation
signal will maintain 7s after two breakers sum current element drops off.
3.1.3 Protection Fault Detector in Protection Calculation DSP
The protection device is running either of the two programs: one is Regular program for normal
state, and the other is Fault calculation program after protection fault detector picks up.
Under the normal state, the protection device will perform the following tasks:
1. Calculate analog quantity
2. Read binary input
3. Hardware self-check
4. Disconnector position supervision
5. Analog quantity input supervision
Once the protection fault detector element in protection calculation DSP picks up, the protection
device will switch to fault calculation program, for example the calculation of phase overcurrent
protection, and to determine logic. If the fault is within the protected zone, the protection device will
send tripping command.
The protection program flow chart is shown as Figure 3.1-1.
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-3 Date: 2011-08-02
Pickup?
Regular program Fault calculation program
No Yes
Main program
Sampling program
Figure 3.1-1 Flow chart of protection program
The protection FD pickup conditions are the same as the FD in fault detector DSP as shown below.
The operation criteria for the conditions are also the same as that in fault detector DSP. Please
refer to section 3.1.2 for details.
1. Pickup condition 1: differential current is greater than the setting value
2. Pickup condition 2: two breakers sum current is greater than the setting value
When any pickup condition mentioned above is met, the protection device will go to fault
calculation state.
3.1.4 Function Block Diagram
FD
PkpI3P1
Diff.Pkp
OC.Pkp
I3P2
I3P3
3.1.5 I/O Signal
Table 3.1-1 Input signal
No. Input Signal Description Configurable
1 I3P1 Three-phase current input of CT1
2 I3P2 Three-phase current input of CT2
3 I3P3 Three-phase current input of CT3
Table 3.1-2 Output signal
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-4 Date: 2011-08-02
No. Output Signal Description Configurable
1 FD.Pkp The device picks up
2 FD.Diff.Pkp Differential current fault detector element operates.
3 FD.OC.Pkp Two breakers sum current fault detector element operates.
3.2 Current Differential Protection
3.2.1 Function Description
Generally, differential current is composed of 3-terminal current (current of two breakers and
current of the feeder line, shown as Figure 3.2-1), only when normally closed auxiliary contact of
feeder line disconnector is energized (feeder line disconnector is open), differential current is
composed of 2-terminal current (currents of two breakers).
3.2.2 Protection Principle
3.2.2.1 3-terminal Current Differential Protection
Three groups of current are inputted to the device (3 current circuits per group), as shown in
Figure 3.2-1. CB1_I and CB2_I are secondary phase currents of two circuit breakers, Line_I
are secondary phase currents of the line ( = A, B or C).
Line
52
52
52
Line
*
*
*
PC
S-9
24
02
01
~0
20
60
20
7~
02
12
02
13
~0
21
8
CT
gro
up
1C
T g
rou
p 2
CT
gro
up
3
CT1
CT2
CT3
CB1
CB2
CB3
ICB2
ICB1
ILine
Figure 3.2-1 3-terminal application
When current differential protection is enabled, 3-terminal current differential protection is valid if
normally closed auxiliary contact of feeder line disconnector is open (feeder line disconnector is
closed).
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-5 Date: 2011-08-02
The criterion:
I3D > [87S.I_Biased] Equation 3.2-1
I3D > [87S.Slope]I3R Equation 3.2-2
Where:
I3D: 3-terminal differential current (I3D = Line_CB2_CB1_ III )
I3R: 3-terminal restraint current (I3R = Line_CB2_CB1_ III )
[87S.I_Biased]: current setting of current differential protection
[87S.Slope]: percentage restraint coefficient of current differential protection
When I3D>1.3In, tripping output will operate once current differential protection operates (In:
secondary rated current of CT).
When I3D [87S.I_Biased] Equation 3.2-3
I2D > [87S.Slope]I2R Equation 3.2-4
Where:
I2D: 2-terminal differential current (I2D = CB2_CB1_ II ).
I2R: 2-terminal restraint current (I2R = CB2_CB1_ II ).
[87S.I_Biased]: current setting of current differential protection.
[87S.Slope]: percentage restraint coefficient of current differential protection.
When I2D>1.3In, tripping output will operate once current differential protection operates (In:
secondary rated current of CT).
When I2D
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-6 Date: 2011-08-02
protection operates.
Both local circuit breakers are tripped (CB1 and CB2) but transfer tripping is not initiated after
2-terminal current differential protection operates.
3.2.2.3 Differential Current Alarm
If any of the phase differential current is greater than the setting [87S.I_Alm] for 5s, this device will
issue the alarm signal [87S.Alm_Diff]. If the alarmed phase differential current is reverted to
normal, the alarm signal [87S.Alm_Diff] will be restored automatically after 5s.
3.2.3 Function Block Diagram
87S
I3P1 87S.Op
87S.En1
87S.En2
87S.Blk
I3P2
I3P3
89b_DS
87S.Op_2Terminals
87S.St
87S.Op_3Terminals
87S.Valid_89b_DS
87S.Alm_89b_DS
87S.Alm_Diff
3.2.4 I/O Signal
Table 3.2-1 Input signals
No. Input Signal Description Configurable
1 I3P1 Three-phase current input of CT1
2 I3P2 Three-phase current input of CT2
3 I3P3 Three-phase current input of CT3
4 89b_DS Normally closed auxiliary contact of feeder line disconnector
5 87S.En1 Current differential protection enabling input 1, it can be binary
inputs or logic links. Yes
6 87S.En2 Current differential protection enabling input 2, it can be binary
inputs or logic link. Yes
7 87S.Blk
Current differential protection blocking input, such as function
blocking binary input.
When the input is 1, current differential protection is reset and
time delay is cleared.
Yes
Table 3.2-2 Output signals
No. Output Signal Description Configurable
1 87S.Op Current differential protection operates.
2 87S.St Current differential protection picks up.
3 87S.Op_2Terminals Current differential protection with two terminals operates. Yes
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-7 Date: 2011-08-02
No. Output Signal Description Configurable
4 87S.Op_3Terminals Current differential protection with three terminals operates. Yes
5 87S.Valid_89b_DS Disconnector position is valid.
6 87S.Alm_89b_DS Disconnector position is abnormal.
7 87S.Alm_Diff Differential current is abnormal.
3.2.5 Logic
Logic diagram of 3-terminal current differential protection and 2-terminal current differential
protection are shown in following two figures.
&
&
&
&
&
&
&
&
&
20ms 0
>=1
20ms 0
>=1
20ms 0
>=1
&
87S.Op
>=1
BI BI_89b_DS
SIG [87S.En1]
SIG [87S.En2]
SIG [87S.Blk]
&
EN [87S.En]
SET I3DB>[87S.I_Biased]
SET I3DC>[87S.I_Biased]
SET I3DA>[87S.Slope]I3RA
SET I3DB>[87S.Slope]I3RB
SET I3DC>[87S.Slope]I3RC
SIG I3DA>1.3In
SIG I3DC>1.3In
SIG I3DB>1.3In
SET I3DA>[87S.I_Biased]
Figure 3.2-2 Logic of 3-terminal current differential protection
Where:
I3DA: differential current of phase A for 3-terminal current differential protection
I3DB: differential current of phase B for 3-terminal current differential protection
I3DC: differential current of phase C for 3-terminal current differential protection
I3RA: restraint current of phase A for 3-terminal current differential protection
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-8 Date: 2011-08-02
I3RB: restraint current of phase B for 3-terminal current differential protection
I3RC: restraint current of phase C for 3-terminal current differential protection
&
&
&
&
&
&
&
&
&
20ms 0
>=1
20ms 0
>=1
20ms 0
>=1
&
87S.Op
>=1
BI BI_89b_DS
SIG [87S.En1]
SIG [87S.En2]
SIG [87S.Blk]
&
EN [87S.En]
SET I2DB>[87S.I_Biased]
SET I2DC>[87S.I_Biased]
SET I2DA>[87S.Slope]I2RA
SET I2DB>[87S.Slope]I2RB
SET I2DC>[87S.Slope]I2RC
SIG I2DA>1.3In
SIG I2DC>1.3In
SIG I2DB>1.3In
SET I2DA>[87S.I_Biased]
Figure 3.2-3 Logic of 2-terminal current differential protection
Where:
I2DA: differential current of phase A for 2-terminal current differential protection
I2DB: differential current of phase B for 2-terminal current differential protection
I2DC: differential current of phase C for 2-terminal current differential protection
I2RA: restraint current of phase A for 2-terminal current differential protection
I2RB: restraint current of phase B for 2-terminal current differential protection
I2RC: restraint current of phase C for 2-terminal current differential protection
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-9 Date: 2011-08-02
3.2.6 Settings
Table 3.2-3 Current differential protection settings
No. Name Range Step Unit Remark
1 87S.I_Biased (0.050~30.000)In 0.001 A Current setting of current differential
protection
2 87S.I_Alm (0.050~30.000)In 0.001 A Current setting of current differential CT
alarm element
3 87S.Slope 0.3~1.0 0.001 Slope of current differential protection
4 87S.En 0 or 1 1
Enabling or disabling current differential
protection;
0: disable; 1: enable
5 87S.En_CTS_Blk 0 or 1 1
Enabling or disabling CTS blocking
current protection function;
0: disable; 1: enable
3.3 Feeder Line End Fault Protection
3.3.1 Application
Two stages of feeder line end fault protection is available for the device. If feeder line end fault
protection is enabled, feeder line end fault protection is in service when normally closed auxiliary
contact of feeder line disconnector is closed. (feeder line disconnector is open)
3.3.2 Protection Principle
The criterion:
ILine_max > [50FLE1.I_Set] or [50FLE2.I_Set] Equation 3.3-1
I3Dmax > [87S.I_Biased] Equation 3.3-2
Where:
ILine_max=Max(ILine_A, ILine_B, ILine_C), ILine_A, ILine_B and ILine_C are secondary phase current of the line.
[50FLE1.I_Set], [50FLE2.I_Set]: current setting of stage 1 and stage 2 of feeder line end fault
protection
I3Dmax=Max( Line_CB2_CB1_ III ), the maximum value of phase differential current of phase A,
phase B and phase C, please refer to Figure 3.2-1 about CB1I , CB2I and LineI .
[87S.I_Biased]: current setting of current differential protection.
In order to prevent the device from undesired trip due to error in normally closed auxiliary contact
of feeder line disconnector, feeder line end fault protection is controlled by differential current
element.
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-10 Date: 2011-08-02
Provided that differential current element of feeder line end fault protection operates, if
ILine_max >[50FLE1.I_Set], stage 1 of feeder line end fault protection will operate to initiate transfer
trip after the time delay of [50FLE1.t_Op], if ILine_max >[50FLE2.I_Set], stage 2 of feeder line end
fault protection will operate to initiate transfer trip after the time delay of [50FLE2.t_Op].
3.3.3 Function Block Diagram
50FLEx
50FLEx.StI3P3
50FLEx.Op
50FLEx.En1
50FLEx.En2
50FLEx.Blk
BI_89b_DS
3.3.4 I/O Signal
Table 3.3-1 Input signals
No. Input Signal Description Configurable
1 I3P3 Three-phase current input of CT3
2 BI_89b_DS normally closed auxiliary contact of feeder line disconnector
3 50FLEx.En1 Stage x of feeder line end fault protection enabling input 1, it can
be binary inputs or logic links. Yes
4 50FLEx.En2 Stage x of feeder line end fault protection enabling input 2, it can
be binary inputs or logic link. Yes
5 50FLEx.Blk
Stage x of feeder line end fault protection blocking input, such as
function blocking binary input.
When the input is 1, feeder line end fault protection is reset and
time delay is cleared.
Yes
Table 3.3-2 Output signals
No. Output Signal Description Configurable
1 50FLEx.St Operation signal of stage x of feeder line end fault protection
2 50FLEx.Op Pickup signal of stage x of feeder line end fault protection
3.3.5 Logic
Logic diagram of feeder line end fault protection is shown in the following figure.
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-11 Date: 2011-08-02
SIG [50FLEx.En1]
SIG [50FLEx.En2]
SIG [50FLEx.Blk]
&
EN [50FLEx.En]
SET ILine_max>[50FLEx.I_Set] &
50FLEx.St
50FLEx.t_Op 0ms 50FLEx.Op
BI BI_89b_DS
SET I3Dmax>[87S.I_Biased]
Figure 3.3-1 Logic of feeder line end fault protection
Where:
x=1 or 2
3.3.6 Settings
Table 3.3-3 Feeder line end fault protection settings
No. Name Range Step Unit Remark
1 50FLE1.I_Set (0.050~30.000)In 0.001 A Current setting of stage 1 of feeder
line end fault protection
2 50FLE1.t_Op 0.000~20.000 0.001 s Time delay of stage 1 of feeder line
end fault protection
3 50FLE1.En 0 or 1
Enabling or disabling stage 1 of
feeder line end fault protection
0: disable
1: enable
4 50FLE2.I_Set (0.050~30.000)In 0.001 A Current setting of stage 2 of feeder
line end fault protection
5 50FLE2.t_Op 0.000~20.000 0.001 s Time delay of stage 2 of feeder line
end fault protection
6 50FLE2.En 0 or 1
Enabling or disabling stage 2 of
feeder line end fault protection
0: disable
1: enable
3.4 Phase overcurrent protection
3.4.1 Protection Principle
Phase overcurrent protection is based on the sum current of two circuit breakers, the criterion is:
Max( CB2_CB1_ II )>[50P.I_Set] Equation 3.4-1
CB1I , CB2I : secondary current of two circuit breakers.
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-12 Date: 2011-08-02
= A, B or C
[50P.I_Set]: current setting of phase overcurrent protection.
Both local circuit breakers (CB1 and CB2) will be tripped if phase overcurrent protection operates.
3.4.2 Function Block Diagram
50P
50P.StI3P1
50P.Op50P.En1
50P.En2
50P.Blk
I3P2
3.4.3 I/O Signal
Table 3.4-1 Input signals
No. Input Signal Description Configurable
1 I3P1 Three-phase current input of CT1
2 I3P2 Three-phase current input of CT2
3 50P.En1 Phase overcurrent protection enabling input 1, it can be binary
inputs or logic links. Yes
4 50P.En2 Phase overcurrent protection enabling input 2, it can be binary
inputs or logic link. Yes
5 50P.Blk
Phase overcurrent protection blocking input, such as function
blocking binary input.
When the input is 1, phase overcurrent protection is reset and
time delay is cleared.
Yes
Table 3.4-2 Output signals
No. Output Signal Description Configurable
1 50P.Op Operation signal of phase overcurrent protection
2 50P.St Pickup signal of phase overcurrent protection
3.4.4 Logic
Logic diagram of phase overcurrent protection is shown in following figure.
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-13 Date: 2011-08-02
SIG [50P.En1]
SIG [50P.En2]
SIG [50P.Blk]
&
EN [50P.En]
SET Max( )>[50P.I_Set] CB2_CB1_ II
50P.t_Op 0ms
&
50P.Op
50P.St
Figure 3.4-1 Logic of phase overcurrent protection
3.4.5 Settings
Table 3.4-3 Current differential protection settings
No. Name Range Step Unit Remark
1 50P.I_Set (0.050~30.000)In 0.001 A current setting of phase overcurrent
element
2 50P.t_Op 0.000~20.000 0.001 s time delay of phase overcurrent
element
3 50P.En 0 or 1 enable phase overcurrent element
3.5 Trip Logic
3.5.1 Application
For any enabled protection tripping elements, their operation signal will convert to appropriate
tripping signals through trip logics and then trigger output contacts by configuration.
3.5.2 Function Description
This module gathers signals from protection tripping elements and then converts the operation
signal from protection tripping elements to appropriate tripping signals.
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-14 Date: 2011-08-02
3.5.3 Logic
SIG Max(I3P3)>0.06I2n
SIG 87S.Op_3Terminals
TT
&
t_Dwell_TT 0
SIG FD.Pkp
&
>=1
SIG 50FLE1.Op
SIG 50FLE2.Op
>=1
0 t_Dwell_TT&
SIG Max(I3P1+I3P2)>0.06I2n
SIG 87S.Op_3Terminals
Trp
&
t_Dwell_Trp 0
SIG FD.Pkp
&
>=1
SIG 87S.Op_2Terminals
SIG 50P.Op
>=1
0 t_Dwell_Trp&
Figure 3.5-1 Simplified tripping logic
1. [t_Dwell_Trp] is the shortest period of tripping contact operation. The tripping contact shall be
reset under conditions of no current and or protection tripping element reset.
3.5.4 I/O Signal
Table 3.5-1 Input signal
Name Description
I3P1 Three-phase current input of CT1
I3P2 Three-phase current input of CT2
I3P3 Three-phase current input of CT3
87S.Op_3Terminals 3-terminal current differential protection operates.
87S.Op_2Terminals 2-terminal current differential protection operates.
50FLE1.Op Operation signal of stage 1 of feeder line end fault protection
50FLE2.Op Operation signal of stage 2 of feeder line end fault protection
50P.Op Operation signal of phase overcurrent protection
Table 3.5-2 Output signal
Name Description
Trp Tripping local two circuit breakers
TT Initiating transfer tripping
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-15 Date: 2011-08-02
3.5.5 Settings
Table 3.5-3 Setting description
No. Name Range Step Unit Remark
1 t_Dwell_Trp 0.000~1000.000 0.001 s the dwell time of tripping command, empirical
value is 0.04
2 t_Dwell_TT 0.000~1000.000 0.001 s the dwell time of transfer tripping command
-
3 Operation Theory
PCS-924 Stub Differential Relay 3-16 Date: 2011-08-02
-
4 Supervision
PCS-924 Stub Differential Relay 4-a Date: 2011-08-02
4 Supervision
Table of Contents
4.1 General Description ........................................................................................ 4-1
4.2 Supervision Alarms ......................................................................................... 4-1
4.3 Relay Self-supervision .................................................................................... 4-4
4.3.1 Relay Hardware Monitoring ................................................................................................. 4-4
4.3.2 Fault Detector Monitoring .................................................................................................... 4-4
4.3.3 Check Tripping Output Circuit.............................................................................................. 4-4
4.3.4 Check Setting ...................................................................................................................... 4-4
4.4 AC Input Monitoring ........................................................................................ 4-4
4.4.1 Current Drift Monitoring and Auto-adjustment ..................................................................... 4-4
4.4.2 Sampling Monitoring ............................................................................................................ 4-4
4.5 Secondary Circuit Monitoring ........................................................................ 4-5
4.5.1 Opto-coupler Power Supervision ......................................................................................... 4-5
Table of Tables
Table 4.2-1 Alarm description and handling suggestion ........................................................ 4-1
-
4 Supervision
PCS-924 Stub Differential Relay 4-b Date: 2011-08-02
-
4 Supervision
PCS-924 Stub Differential Relay 4-1 Date: 2011-08-02
4.1 General Description
Protection system is in quiescent state under normal conditions, and it is required to respond
promptly for faults occurred on power system. When equipment is in energizing process before the
LED HEALTHY is on, the equipment need to be checked to ensure no abnormality. Therefore,
the automatic supervision function, which checks the health of the protection system when startup
and during normal operation, plays an important role.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a defect is detected during initialization when DC power supply is provided to the
equipment, the equipment will be blocked with indication and alarm of relay out of service. It is
suggested a trial recovery of the equipment by re-energization. Please contact supplier if the
equipment is still failure.
When a failure is detected by the automatic supervision, it is followed by a LCD message, LED
indication and alarm contact outputs. The failure alarm is also recorded in event recording report
and can be printed If required.
4.2 Supervision Alarms
Hardware circuit and operation status of the equipment are self-supervised continuously. If any
abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.
A minor abnormality may block a certain number of protections functions while the other functions
can still work. However, if severe hardware failure or abnormality are detected, all protection
functions will be blocked and the LED HEALTHY will be extinguished and blocking output
contacts BO_FAIL will be given. The protective device then can not work normally and
maintenance is required to eliminate the failure. All the alarm signals and the corresponding
handling suggestions are listed below.
Note!
If the protective device is blocked or alarm signal is sent during operation, please do find
out its reason with the help of self-diagnostic record. If the reason can not be found at site,
please notify the factory NR. Please Do not simply press button TARGET RESET on the
protection panel or re-energize on the protective device.
Table 4.2-1 Alarm description and handling suggestion
No. Item Alarm description Handing suggestion
1 Fail_Device The device fails.
The signal is issued with other specific alarm
signals, and please refer to the handeling
suggestion other specific alarm signals.
2 Alm_Device The device is abnormal. The signal is issued with other specific alarm
-
4 Supervision
PCS-924 Stub Differential Relay 4-2 Date: 2011-08-02
signals, and please refer to the handeling
suggestion other specific alarm signals.
3 Alm_CommTest The device is in the
communication test mode.
No special treatment is needed, and disable
the communication test function after the
completion of the test.
4 Alm_Setting_OvRange Set value of any setting is out
of scope.
Please reset setting values according to the
range described in the instruction manual,
then re-power or reboot the equipment and
the alarm message will disappear and the
equipment will restore to normal operation
state.
5 Alm_BoardConfig
Mismatch between the
configuration of plug-in
modules and the designing
drawing of an applied-specific
project.
1. Go to the menu InformationBorad
Info, check the abnormality information.
2. For the abnormality board, if the board
is not used, then remove, and if the board is
used, then check whether the board is
installed properly and work normally.
3. After the abnormality is removed,
re-power or reboot the device and the device
will restore to normal operation state.
6 Bxx.Fail_TrpOut
Driving circuits of binary
output relays of BO plug-in
module in slot xx are
damaged.
Please re-insert the corresponding binary
output module and re-power the equipment
after the completion of insertion, and the
device will restore to normal operation state.
7 Fail_SettingSurv
Setting surveillance between
DSP module and MON
module is abnormal.
Please inform the manufacture or the agent
for repair.
8 Fail_Memory Error is found during
checking memory data.
Please inform the manufacture or the agent
for repair.
9 Fail_Settings Error is found during
checking settings.
1. Check CT ratio settings of each side of
transformer to be set in proper range, and if
need, please reset those settings and reboot
or re-power the device.
2. Check overexcitation settings to be set
reasonable, and if need, please reset those
settings and reboot or re-power the device.
3. After above two steps, abnormality may
disappear. Otherwise, a hardware failue
probably ocurrs and please inform the
manufacture or the agent.
10 Fail_DSP DSP chip is damaged.
Chips are damaged and please inform the
manufacture or the agent replacing the
module.
11 Bxx.Alm_OptoDC The power supply of BI 1. check whether the binary input module
-
4 Supervision
PCS-924 Stub Differential Relay 4-3 Date: 2011-08-02
plug-in module in slot xx is
abnormal.
is connected to the power supply.
2. check whether the voltage of power
supply is in the required range.
3. After the voltage for binary input module
restores to normal range, the ALARM LED
will be extinguished and the corresponding
alarm message will disappear and the device
will restore to normal operation state.
12 Fail_Config Software configuation is
incorrect.
Please inform configuration engineers to
check and confirm visualization functions of
the device
13 Fail_Sample AC current samplings are
abnormal.
1. Please make the device out of service.
2. Then check if the analog input modules
and wiring connectors connected to those
modules are installed at the position.
3. Re-power the device and the device will
restore to normal operation state.
14 Alm_PersistFD Fault detector element
operates for longer than 10s.
Please check secondary values and
protection settings. If settings are not set
reasonable to make fault detectors pick up,
please reset settings, and then the alarm
message will disappear and the device will
restore to normal operation state.
15 CTS.Alm CT circuit of corresponding
circuit breaker fails.
Please check the corresponding CT
secondary circuit. After the abnormality is
eliminated, ALARM LED will go off
automatically and device returns to normal
operation state.
16 Fail_SV_QF The quality factor of sample
values is abnormal.
Thess alarms may be issued for electric
transformer applied projects. If alarms are
issued, please check working state of
merging units and the connection between
merging units and the protection device.
17 Alm_Maintenance The device is in maintenance
state.
After maintenance is finished, please
de-energized the binary input
[BI_Maintenance] and then the alarm will
disappear and the device restore to normal
operation state.
18 Alm_TimeSync Time synchronization
abnormality alarm.
1. check whether the selected clock
synchronization mode matches the clock
synchronization source;
2. check whether the wiring connection
between the equipment and the clock
-
4 Supervision
PCS-924 Stub Differential Relay 4-4 Date: 2011-08-02
synchronization source is correct
3. check whether the setting for selecting
clock synchronization (i.e. [Opt_TimeSync])
is set correctly. If there is no clock
synchronization, please set the setting
[Opt_TimeSync] as No TimeSync.
4. After the abnormality is removed, the
ALARM LED will be extinguished and the
corresponding alarm message will disappear
and the device will restore to normal
operation state.
4.3 Relay Self-supervision
4.3.1 Relay Hardware Monitoring
All chips on DSP module are monitored to ensure whether they are damaged or having errors. If
any one of them is detected damaged or having error, the alarm signal [Fail_DSP] is issued with
device being blocked.
4.3.2 Fault Detector Monitoring
When any fault detector picks up for over 10s, an alarm will be issued [Alm_PersistFD] without
protective device blocked.
4.3.3 Check Tripping Output Circuit
Chips controlling the output relays in the output circuit are continually monitored. If any error or
damage is detected in these chips, alarm [Bxx.Fail_TrpOut] will be given and the device will be
blocked.
4.3.4 Check Setting
This relay has 10 setting groups, only one setting group could be activiated (is active) at a time.
The settings of active setting group are checked to ensure they are reasonable. If settings are
checked to be unreasonable or out of setting scopes, a corresponding alarm signal will be issued,
and protective device is also blocked.
4.4 AC Input Monitoring
4.4.1 Current Drift Monitoring and Auto-adjustment
Zero point of current may drift due to variation of temperature or other environment factors. The
equipment continually traces the drift and adjust it to normal value automatically.
4.4.2 Sampling Monitoring
AC current samplings of protection DSP and fault detector DSP are monitored and if the samples
of protection DSP and fault detector DSP are detected to be wrong or inconsistent between them,
-
4 Supervision
PCS-924 Stub Differential Relay 4-5 Date: 2011-08-02
the alarm signal [Fail_Sample] will be issued and the device will be blocked.
4.5 Secondary Circuit Monitoring
4.5.1 Opto-coupler Power Supervision
Positive power supply of opto-coupler is continually monitored. If an error or damage has occurred,
an alarm [Bxx.Alm_OptoDC] will be issued.
-
4 Supervision
PCS-924 Stub Differential Relay 4-6 Date: 2011-08-02
-
5 Measurement and Recording
PCS-924 Stub Differential Relay 5-a Date: 2011-08-02
5 Measurement and Recording
Table of Contents
5.1 Measurement ................................................................................................... 5-1
5.2 Recording ........................................................................................................ 5-1
5.2.1 General Description ............................................................................................................. 5-1
5.2.2 Event Recording .................................................................................................................. 5-2
5.2.3 Disturbance Recording ........................................................................................................ 5-2
5.2.4 Present Recording ............................................................................................................... 5-3
-
5 Measurement and Recording
PCS-924 Stub Differential Relay 5-b Date: 2011-08-02
-
5 Measurement and Recording
PCS-924 Stub Differential Relay 5-1 Date: 2011-08-02
5.1 Measurement
PCS-924 performs continuous measurement of the analogue input quantities. The relay samples
24 points per cycle and calculates the RMS value in each interval and updated the LCD display in
every 0.5s. The measurement data can be displayed on the LCD of the relay front panel or on the
local/remote PC via software tool. Navigate the menu to view the sampling value through LCD
screen.
1. RMS Values
Access path: Press key to enter main menu firstly. Select the item Measurements and press
key ENT to enter, and then select submenu Measurements1. Press key ENT to display
corresponding measurement values as below on the LCD.
Measured directly
Magnitude of phase current of CT1 (Ia1, Ib1, Ic1)
Magnitude of phase current of CT2 (Ia2, Ib2, Ic2)
Magnitude of phase current of CT3 (Ia3, Ib3, Ic3)
Calculated by DSP
Differential current (Id_a, Id_b, Id_c)
Phase Angle
Phase angle of (Ia1-Ib1), (Ib1-Ic1), (Ic1-Ia1)
Phase angle of (Ia2-Ib2), (Ib2-Ic2), (Ic2-Ia2)
Phase angle of (Ia3-Ib3), (Ib3-Ic3), (Ic3-Ia3)
Phase angle of (Ia1-Ia2), (Ib1-Ib2), (Ic1-Ic2)
Phase angle of (Ia1-Ia3), (Ib1-Ib3), (Ic1-Ic3)
Phase angle of (Ia2-Ia3), (Ib2-Ib3), (Ic2-Ic3)
5.2 Recording
5.2.1 General Description
PCS-924 provides the following recording functions:
1. Event recording
2. Disturbance recording
3. Present recording
All the recording information except waveform can be viewed on local LCD or by printing.
Waveform could only be printed or extracted with PCS-PC software tool and a waveform analysis
software.
-
5 Measurement and Recording
PCS-924 Stub Differential Relay 5-2 Date: 2011-08-02
5.2.2 Event Recording
5.2.2.1 General Description
The device can store the latest 1024 disturbance records, 1024 binary events, 1024 supervision
events and 1024 device logs. All the records are stored in non-volatile memory, and when the
available space is exhausted, the oldest record is automatically overwritten by the latest one.
5.2.2.2 Disturbance Records
When any protection element operates or drops off, such as fault detector, distance protection etc.,
they will be logged in event records.
5.2.2.3 Supervision Events
The device is under automatic supervision all the time. If there are any failure or abnormal
condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event
records.
5.2.2.4 Binary Events
When there is a binary input is energized or de-energized, i.e., its state has changed from 0 to 1
or from 1 to 0, it will be logged in event records.
5.2.2.5 Device Logs
If an operator implements some operations on the device, such as reboot protective device,
modify setting, etc., they will be logged in event records.
5.2.3 Disturbance Recording
5.2.3.1 Application
Disturbance records can be used to have a better understanding of the behavior of the power
network and related primary and secondary equipment during and after a disturbance. Analysis of
the recorded data provides valuable information that can be used to improve existing equipment.
This information can also be used when planning for and designing new installations.
5.2.3.2 Design
A disturbance record consists of fault record and fault waveform. A disturbance record is initiated
by fault detector element.
The disturbance record has two types:
1. Fault detector element picks up without operation of protective element.
2. Fault detector element picks up with operation of protective elements.
5.2.3.3 Capacity and Information of Disturbance Records
The device can store up to 64 disturbance records with waveform in non-volatile memory. It is
based on first in first out queue that the oldest disturbance record will be overwritten by the latest
one.
-
5 Measurement and Recording
PCS-924 Stub Differential Relay 5-3 Date: 2011-08-02
For each disturbance record, the following items are included:
1. Sequence number
Each operation will be recorded with a sequence number in the record and displayed on LCD
screen.
2. Date and time of fault occurrence
The time resolution is 1ms using the relay internal clock synchronized via clock synchronized
device if connected. The date and time is recorded when a system fault is detected.
3. Relative operating time
An operating time (not including the operating time of output relays) is recorded in the record.
4. Faulty phase
5. Protection elements
5.2.3.4 Capacity and Information of Fault Waveform
MON module can store 64 pieces of fault waveform oscillogram in non-volatile memory. If a new
fault occurs when 64 fault waveform have been stored, the oldest will be overwritten by the latest
one.
Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, differential current, alarm elements, and binary inputs and etc.
Each time recording includes 10-cycle pre-fault waveform, and 250 cycles at least and 500 cycles
at most can be recorded.
5.2.4 Present Recording
Present recording is a waveform triggered manually on on the devices LCD or remotely through
PCS-PC software. Recording content of present recording is same to that of disturbance
recording.
Each time recording includes 10-cycle waveform before triggering, and 250 cycles at most can be
recorded.
-
5 Measurement and Recording
PCS-924 Stub Differential Relay 5-4 Date: 2011-08-02
-
6 Hardware
PCS-924 Stub Differential Relay 6-a Date: 2011-08-02
6 Hardware
Table of Contents
6.1 General Description ........................................................................................ 6-1
6.2 Typical Wiring .................................................................................................. 6-4
6.2.1 Conventional CT/VT (For reference only) ........................................................................... 6-4
6.2.2 ECT/EVT (For reference only) ............................................................................................. 6-6
6.3 Plug-in Module Description ............................................................................ 6-8
6.3.1 PWR Plug-in Module (Power Supply) ................................................................................. 6-8
6.3.2 MON Plug-in Module (Management) ................................................................................. 6-10
6.3.3 AI Plug-in Module (Analog Input) ....................................................................................... 6-13
6.3.4 DSP Plug-in Module (Fault Detector and Protection Calculation) .................................... 6-15
6.3.5 NET-DSP Plug-in Module (GOOSE and SV) .................................................................... 6-16
6.3.6 BI Plug-in Module (Binary Input)........................................................................................ 6-16
6.3.7 BO Plug-in Module (Binary Output) ................................................................................... 6-20
6.3.8 HMI Module........................................................................................................................ 6-22
List of Figures
Figure 6.1-1 Rear view of fixed module position ..................................................................... 6-1
Figure 6.1-2 Hardware diagram .................................................................................................. 6-2
Figure 6.1-3 Front view of PCS-924 ........................................................................................... 6-3
Figure 6.1-4 Typical rear view of PCS-924 ................................................................................ 6-4
Figure 6.2-1 Typical wiring of PCS-924 (conventional CT/VT) ................................................ 6-5
Figure 6.2-2 Typical wiring of PCS-924 (ECT/EVT) .................................................................. 6-7
Figure 6.3-1 View of PWR plug-in module ................................................................................ 6-9
Figure 6.3-2 Output contacts of PWR plug-in module ............................................................. 6-9
Figure 6.3-3 View of MON plug-in module .............................................................................. 6-11
Figure 6.3-4 Connection of communication terminal ............................................................ 6-13
-
6 Hardware
PCS-924 Stub Differential Relay 6-b Date: 2011-08-02
Figure 6.3-5 View of AI plug-in module ................................................................................... 6-14
Figure 6.3-6 View of DSP plug-in module ............................................................................... 6-15
Figure 6.3-7 View of NET-DSP plug-in module ....................................................................... 6-16
Figure 6.3-8 View of BI plug-in module (NR1503) .................................................................. 6-17
Figure 6.3-9 View of BI plug-in module (NR1504) .................................................................. 6-17
Figure 6.3-10 View of BO plug-in module (NR1521A) ............................................................ 6-21
Figure 6.3-11 View of BO plug-in module (NR1521C) ............................................................ 6-21
Table of Tables
Table 6.3-1 Terminal definition and description ....................................................................... 6-9
Table 6.3-2 Terminal definition of AI module .......................................................................... 6-14
-
6 Hardware
PCS-924 Stub Differential Relay 6-1 Date: 2011-08-02
6.1 General Description
PCS-924 adopts 64-bit microchip processor CPU produced by FREESCALE as control core for
logic calculation and management function, meanwhile, adopts high-speed digital signal processor
DSP for all the protection calculation. 24 points are sampled in every cycle and parallel processing
of sampled data can be realized in each sampling interval to ensure ultrahigh reliability and safety
of protection equipment.
PCS-924 is comprised of intelligent plug-in modules, except that few particular plug-in modules
position cannot be changed in the whole device (gray plug-in modules as shown in Figure 6.1-1),
other plug-in modules like AI (analog input) and IO (binary input and binary output) can be flexibly
configured in the remaining slot positions.
MO
N m
od
ule
DS
P m
od
ule
PW
R m
od
ule
01 04 05 06 07 00
AI
mo
du
le
BI
mo
du
le
BO
mo
du
leSlot No.
02 03 08 09 10 11 12 13 14 15
BI
mo
du
le
BO
mo
du
le
BO
mo
du
le
BO
mo
du
le
Figure 6.1-1 Rear view of fixed module position
PCS-924 has 16 slots, PWR module, MON module and DSP module are assigned at fixed slots.
Besides 3 fixed modules are shown in above figure, there are 13 slots can be flexibly configured.
AI plug-in module, BI plug-in module and BO plug-in module can be configured at position
between slot B02, B03 and B06~B15. It should be pay attention that AI plug-in module will occupy
two slots.
This device is developed on the basis of our latest software and hardware platform, and the new
platform major characteristics are of high reliability, networking and great capability in
anti-interference great capability in anti-interference. See Figure 6.1-2 for hardware diagram.
-
6 Hardware
PCS-924 Stub Differential Relay 6-2 Date: 2011-08-02
Conventional CT/VT
Exte
rnal
Bin
ary
Input
Outp
ut R
ela
y
+E
Pickup
Relay
Protection
Calculation
DSP
A/D
LCD
Fault
Detector
DSP
A/D
CPU
ECVT
ECVT
Power
SupplyUaux
Keypad
LED
Clock SYN
PRINT
RJ45
ETHERNET
Figure 6.1-2 Hardware diagram
The working process of the device is as shown in above figure: current and voltage from
conventional CT/VT are converted into small voltage signal and sent to DSP module after filtered
and A/D conversion for protection calculation and fault detector respectively (ECVT signal is sent
to the relay without small signal and A/D convertion). When DSP module completes all the
protection calculation, the result will be recorded in 64-bit CPU on MON module. DSP module
carries out fault detector, protection logic calculation, tripping output, and MON module perfomes
SOE (sequence of event) record, waveform recording, printing, communication between
protection and SAS and communication between HMI and CPU. When fault detector detects a
fault and picks up, positive power supply for output relay is provided.
The items can be flexibly configured depending on the situations like sampling method of device
(conventional CT/VT and ECT/EVT), the mode of binary output (conventional binary output and
GOOSE binary output), and whether it needs independent binary output for pole discrepancy
protection. The configurations for PCS-900 series based on microcomputer are classified into
standard and optional modules.
Table 6.1-1 PCS-924 module configuration
No. ID Module description Remark
1 NR1101/NR1102 Management module (MON module) Standard
2 NR1401 Analog input module (AI module ) Standard
3 NR1161 Protection calculation and fault detector module (DSP module) Standard
4 NR1503/NR1504 Binary input module (BI module) Standard
5 NR1521 Binary output module (BO module) Standard
6 NR1301 Power supply module (PWR module) Standard
7 NR1136 GOOSE and SV from merging unit by IEC61850-9-2 (NET-DSP Option
-
6 Hardware
PCS-924 Stub Differential Relay 6-3 Date: 2011-08-02
No. ID Module description Remark
module)
8 Human machine interface module (HMI module) Standard
MON module provides functions like management function, event record, setting
management etc.
AI module converts AC current and voltage from current transformers and voltage
transformers respectively to small voltage.
DSP module performs filtering, sampling, protection calculation and fault detector calculation.
BI module provides binary inputs, the binary inputs are opto-couplers of rating
24V/110V/125V/220V/250V (configurable).
BO module provides output contacts for tripp[ing, and signal output contact for annunciation
signal, remote signal, fault and disturbance signal, operation abnormal signal etc.
PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of
the device.
HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user
as human-machine interface.
NET-DSP module receives and sends GOOSE messages, sampled values (SV) from
merging unit by IEC61850-9-2 protocol.
PCS-924 series is made of a 4U height 19 chassis for flush mounting. Components mounted on
its front include a 320240 dot matrix LCD, a 9 button keypad, 20 LED indicators and a multiplex
RJ45 port. A monolithic micro controller is installed in the equipment for these functions.
Following figures show front and rear views of PCS-924 respectively.
ENT
ES
CG
RP
PCS-9241
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
HEALTHY
ALARM STUB DIFFERENTIAL RELAY
Figure 6.1-3 Front view of PCS-924
20 LED indicators are, from top to bottom, operation (HEALTHY), self-supervision (ALARM),
others are configurable.
For the 9-button keypad, ENT is enter, GRP is group number and ESC is escape.
-
6 Hardware
PCS-924 Stub Differential Relay 6-4 Date: 2011-08-02
NR1102 NR1401
DANGER
NR1161
1
2
NR1504 NR1521 NR1521 NR1521 NR1521 NR1301
11
1
9
3
10
8
7
6
4
5
2
12
BO_COM1
BO_ALM
OPTO+
BO_FAIL
BO_ALM
BO_COM2
OPTO-
PWR+
PWR-
GND
BO_FAIL
5V ALM
BO_ALM BO_FAIL
OK
NR1504
Figure 6.1-4 Typical rear view of PCS-924
6.2 Typical Wiring
6.2.1 Conventional CT/VT (For reference only)
MO
N m
od
ule
DS
P m
od
ule
PW
R m
od
ule
01 04 05 06 07 00
AI
mo
du
le
BI
mo
du
le
BO
mo
du
le
Slot No.02 03 08 09 10 11 12 13 14 15
NR1301
BO
mo
du
le
BO
mo
du
le
NR1521ANR1504NR1102 NR1401 NR1161 NR1521C NR1521B
The following typical wiring is given based on above hardware configuration
-
6 Hardware
PCS-924 Stub Differential Relay 6-5 Date: 2011-08-02
Ia
Ib
Ic
0201
0202
0203
0204
0205
0206
Cu
rren
t of C
T1
0225
0010
0011
0001
0002
0003
BO_FAIL
BO_ALM
0004
0005
0006
BO_FAIL
BO_ALM
0007
0008
0012
Power
Supply
PWR+
PWR-
OPTO+
OPTO-
External DC power
supply
Power supply for
opto-coupler (24V)
COM
COM
Multiplex
RJ45 (Front)Grounding
Bus
0801
0802
0807
0809
0814
0821
0808
0816
0815
+
+
+
+
+
+
Not used
Not used
Power supply supervision
BI_01
BI_06
BI_07
BI_12
BI_13
BI_18
0822-
PT
INT
ER
0101
0102
0103
0105
0106
0107SGND
RTS
TXD
SYN+
SYN-
SGND
Clo
ck S
YN
PR
INT
0104
0101
0102
0103
485-1A
485-1B
SGND
CO
M
0104
1101
1102
1103
1104
1105
1106
1121
1122
1201
1202
1203
1204
1205
1206
1221
1222
1301
1302
1303
1304
1305
1306
1317
1318
1319
1320
1321
1322
BO_01
BO_02
BO_03
BO_11
BO_01
BO_02
BO_03
BO_11
BO_01
BO_02
BO_03
BO_09
BO_10
BO_11
Co
ntro
lled
by fa
ult d
ete
cto
r
ele
me
nt
Sig
na
l Bin
ary
Ou
tpu
t (op
tion
)
Firs
t 9 c
on
tacts
co
ntro
lled
by fa
ult d
ete
cto
r
ele
me
nt a
nd
last 2
co
nta
cts
with
ou
t co
ntro
lled
by
fau
lt de
tecto
r ele
me
nt (o
ptio
n)
*BI p
lug
-in m
od
ule
ca
n b
e in
de
pe
nd
en
t co
mm
on
term
ina
l
To
the
scre
en
of o
the
r co
axia
l
ca
ble
with
sin
gle
po
int e
arth
ing
Ia
Ib
Ic
0207
0208
0209
0210
0211
0212
Cu
rren
t of C
T2
Ia
Ib
Ic
0213
0214
0215
0216
0217
0218C
urre
nt o
f CT
3
Figure 6.2-1 Typical wiring of PCS-924 (conventional CT/VT)
-
6 Hardware
PCS-924 Stub Differential Relay 6-6 Date: 2011-08-02
01
NR1301
PWR
09080705040302 001312
NR1102
BOBIMON
NR1521NR1504
PCS-924 (conventional CT/VT and conventional binary output)
NET-
DSP
NR1136
PCS-924 (conventional CT/VT and GOOSE binary output)
NR1521
BO
NR1521
BO
06 10 11 14 15
NR1521
BO
Slot No.
Module ID
01
NR1301
PWR
09080705040302 001312
NR1102
BIAI DSPMON
NR1504NR1161NR1401
06 10 11 14 15Slot No.
Module ID
BI
NR1504
AI
NR1401
DSP
NR1161
6.2.2 ECT/EVT (For reference only)
MO
N m
od
ule
DS
P m
od
ule
PW
R m
od
ule
01 04 05 06 07 00
AI
mo
du
le
BI
mo
du
le
BO
mo
du
le
Slot No.02 03 08 09 10 11 12 13 14 15
NR1301
BO
mo
du
le
BO
mo
du
le
NR1521ANR1503NR1102 NR1401 NR1161 NR1521C NR1521B
The following typical wiring is given based on above hardware configuration.
-
6 Hardware
PCS-924 Stub Differential Relay 6-7 Date: 2011-08-02
SV from
ECT/EVT
RX
0225
0010
0011
0001
0002
0003
BO_FAIL
BO_ALM
0004
0005
0006
BO_FAIL
BO_ALM
0007
0008
0012
Power
Supply
PWR+
PWR-
OPTO+
OPTO-
External DC power
supply
Power supply for
opto-coupler (24V)
COM
COM
Multiplex
RJ45 (Front)
Grounding
Bus
0801
0802
+BI_01
-
PT
INT
ER
0101
0102
0103
0105
0106
0107SGND
RTS
TXD
SYN+
SYN-
SGND
Clo
ck S
YN
PR
INT
0104
0101
0102
0103
485-1A
485-1B
SGND
CO
M
0104
1101
1102
1103
1104
1105
1106
1121
1122
1201
1202
1203
1204
1205
1206
1221
1222
BO_01
BO_02
BO_03
BO_11
BO_01
BO_02
BO_03
BO_11
Co
ntro
lled
by fa
ult d
ete
cto
r
ele
me
nt
Sig
na
l Bin
ary
Ou
tpu
t (op
tion
)
0803
0804
+BI_02
-
0805
0806
+BI_03
-
0821
0822
+BI_11
-
Phase A
Phase B
Phase C
MU
TX
FO
inte
rface
for S
V c
ha
nn
el
Up
to 8
(LC
Typ
e)
IRIG-B
*BI p
lug
-in m
od
ule
ca
n b
e c
om
mo
n n
eg
ativ
e
term
ina
l
To
the
scre
en
of o
the
r co
axia
l
ca
ble
with
sin
gle
po
int e
arth
ing
Figure 6.2-2 Typical wiring of PCS-924 (ECT/EVT)
PCS-924 ECT/EVT, GOOSE binary output and binary output
01
NR1301
PWR
09080705040302 001312
NR1102
DSP BIMON
06 10 11 14 15Slot No.
Module ID
NET-
DSP
NR1136 NR1504NR1161
PCS-924 ECT/EVT, conventional binary output and binary output
01
NR1301
PWR
09080705040302 001312
NR1102
DSP BOBIMON BO BO
06 10 11 14 15Slot No.
Module ID
NET-
DSP
NR1136 NR1521NR1504NR1161 NR1521 NR1521 NR1521
BOBI
NR1504
In the protection system adopting electronic current and voltage transformer (ECT/EVT), the
merging unit will merge the sample data from ECT/EVT, and then send it to the device through
-
6 Hardware
PCS-924 Stub Differential Relay 6-8 Date: 2011-08-02
multi-mode optical fibre. DSP module receives the data from merging unit through the optical-fi