05 - pcs924 stub differential relay

182

Click here to load reader

Upload: toing

Post on 04-Sep-2015

285 views

Category:

Documents


14 download

DESCRIPTION

PCS924 Stub Differential Relay

TRANSCRIPT

  • 1 Introduction

    PCS-924 Stub Differential Relay 1-a Date: 2011-08-02

    1 Introduction

    Table of Contents

    1.1 Application ....................................................................................................... 1-1

    1.2 Function ........................................................................................................... 1-1

    1.3 Features ........................................................................................................... 1-3

    List of Figures

    Figure 1.1-1 Functional diagram of PCS-924 ............................................................................ 1-1

  • 1 Introduction

    PCS-924 Stub Differential Relay 1-b Date: 2011-08-02

  • 1 Introduction

    PCS-924 Stub Differential Relay 1-1 Date: 2011-08-02

    1.1 Application

    PCS-924 is a fully numerical stub differential relay which is mainly designed for protecting T zone

    of one and a half breakers arrangement. It is developed based on UAPC (Unified Advanced

    Platform for Protection and Control) platform.

    The protection function of PCS-924 comprises of current differential protection, phase overcurrent

    protection and feeder line end fault protection.

    Busbar No.1

    Line

    52

    52

    52

    Line

    Busbar No.2

    *

    *

    *

    ICB2

    ICB1

    ILine

    50P87S 50FLE

    PCS-924

    Figure 1.1-1 Functional diagram of PCS-924

    1.2 Function

    1. Protection Functions

    Current differential protection (87S)

    Phase overcurrent protection (50P)

    Feeder line end fault protection (50FLE)

    2. Logic

    User programmable logic

    3. Additional function

    CT circuit supervision (CTS)

    Self diagnostic

  • 1 Introduction

    PCS-924 Stub Differential Relay 1-2 Date: 2011-08-02

    DC power supply supervision

    Current drift auto regulation

    Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision

    events and 1024 device logs.

    Disturbance recorder including 64 disturbance records with waveforms (The file format of

    disturbance recorder is compatible with international COMTRADE file.)

    Clock synchronization

    PPS (RS-485)

    IRIG-B (RS-485)

    PPM (DIN)

    SNTP (PTP)

    IEEE1588

    SNTP (BC)

    PPS (DIN)

    4. Monitoring

    Number of circuit breaker operation (single-phase tripping, three-phase tripping and

    reclosing)

    Frequency

    5. Communication

    2 RS-485 communication rear ports conform to IEC 60870-5-103 protocol or DNP3.0 protocol

    1 RS-485 communication rear ports for clock synchronization

    Up to 4 Ethernet ports (depend on the chosen type of plug-in MON module), IEC 61850, or

    IEC 60870-5-103 over TCP/IP

    Up to 2 Ethernet ports via optic fiber (ST interface or SC interface, depend on the chosen type

    of plug-in MON module)

    GOOSE communication function (optional plug-in module)

    6. User Interface

    Friendly HMI interface with LCD and 9-button keypad on the front panel.

    1 front multiplex RJ45 port for testing and setting

    1 RS-232 or RS-485 rear ports for printer

    Language switchover English + selected language

  • 1 Introduction

    PCS-924 Stub Differential Relay 1-3 Date: 2011-08-02

    Auxiliary software - PCSPC

    1.3 Features

    The intelligent device integrated with protection, control and monitor provides powerful

    protection function, flexible protection configuration, user programmable logic and

    configurable binary input and binary output, which can meet with various application

    requirements.

    High-performance hardware platform and modularized design, MCU (management control

    unit) + DSP (digital signal processor). MCU manages general fault detector element and DSP

    manages protection and metering. Their data acquisition system is completely independent in

    electronic circuit. DC power supply of output relay is controlled by the operation of fault

    detector element operates, this prevents maloperation due to error from ADC or damage of

    any apparatus.

    Multiple setting groups with password protection

    Powerful PC tool software can fulfill protection function configuration, modify setting and

    waveform analysis.

  • 1 Introduction

    PCS-924 Stub Differential Relay 1-4 Date: 2011-08-02

  • 2 Technical Data

    PCS-924 Stub Differential Relay 2-a Date: 2013-06-19

    2 Technical Data

    Table of Contents

    2.1 Electrical Specifications ................................................................................. 2-1

    2.1.1 AC Current Input .................................................................................................................. 2-1

    2.1.2 AC Voltage Input .................................................................................................................. 2-1

    2.1.3 Power Supply ....................................................................................................................... 2-1

    2.1.4 Binary Input .......................................................................................................................... 2-1

    2.1.5 Binary Output ....................................................................................................................... 2-2

    2.2 Mechanical Specifications.............................................................................. 2-2

    2.3 Ambient Temperature and Humidity Range .................................................. 2-2

    2.4 Communication Port ....................................................................................... 2-3

    2.4.1 EIA-485 Port ........................................................................................................................ 2-3

    2.4.2 Ethernet Port ........................................................................................................................ 2-3

    2.4.3 Optical Fibre Port ................................................................................................................. 2-3

    2.4.4 Print Port .............................................................................................................................. 2-4

    2.4.5 Clock Synchronization Port ................................................................................................. 2-4

    2.5 Type Tests ........................................................................................................ 2-4

    2.5.1 Environmental Tests............................................................................................................. 2-4

    2.5.2 Mechanical Tests ................................................................................................................. 2-4

    2.5.3 Electrical Tests ..................................................................................................................... 2-4

    2.5.4 Electromagnetic Compatibility ............................................................................................. 2-4

    2.6 Certifications ................................................................................................... 2-5

    2.7 Protective Functions ....................................................................................... 2-6

    2.7.1 Current Differential Protection ............................................................................................. 2-6

    2.7.2 Phase Overcurrent Protection ............................................................................................. 2-6

    2.7.3 Feeder Line End Fault Protection ........................................................................................ 2-6

  • 2 Technical Data

    PCS-924 Stub Differential Relay 2-b Date: 2013-06-19

  • 2 Technical Data

    PCS-924 Stub Differential Relay 2-1 Date: 2013-06-19

    2.1 Electrical Specifications

    2.1.1 AC Current Input

    Standard IEC 60255-27:2005

    Phase rotation ABC

    Nominal frequency (fn) 505Hz, 605Hz

    Rated Current (In) 1A 5A

    Linear to 0.05In~40In

    Thermal withstand

    -continuously

    -for 10s

    -for 1s

    -for half a cycle

    4In

    30In

    100In

    250In

    Burden < 0.15VA/phase @In < 0.25VA/phase @In

    Accuracy 0.5%In

    2.1.2 AC Voltage Input

    Standard IEC 60255-6, IEC60288

    Phase rotation ABC

    Nominal frequency (fn) 505Hz, 605Hz

    Rated Voltage (Un) 100V~130V

    Linear to 1V~170V

    Thermal withstand

    - continuously

    -10s

    -1s

    200V

    260V

    300V

    Burden at rated < 0.25VA/phase @Un

    Accuracy 0.5%Un

    2.1.3 Power Supply

    Standard IEC 60255-11:2008

    Rated Voltage 110Vdc/125Vdc, 220Vdc/250Vdc

    Operating Range 80%~120% of rated voltage

    Permissible AC ripple voltage 15% of the nominal auxiliary voltage

    Burden

    Quiescent condition

    Operating condition

  • 2 Technical Data

    PCS-924 Stub Differential Relay 2-2 Date: 2013-06-19

    Maximum permissible voltage 120% of rated voltage

    Withstand voltage

    -continously 2000Vac, 2800Vdc

    Response time for logic input

  • 2 Technical Data

    PCS-924 Stub Differential Relay 2-3 Date: 2013-06-19

    Permissible humidity 5%-95%, without condensation

    Pollution degree

    Altitude

  • 2 Technical Data

    PCS-924 Stub Differential Relay 2-4 Date: 2013-06-19

    2.4.3.3 For Synchronization Port

    Characteristic Glass optical fiber

    Connector type ST

    Fibre type Multi mode

    Wave length 820nm

    Minimum receiving power Min. -25.0dBm

    Margin Min +3.0dB

    2.4.4 Print Port

    Type RS-232

    Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

    Printer type EPSON 300K printer

    Safety level Isolation to ELV level

    2.4.5 Clock Synchronization Port

    Type RS-485

    Transmission distance 100M@500VDC

    2.5.4 Electromagnetic Compatibility

    1MHz burst disturbance test IEC 60255-22-1:2007

  • 2 Technical Data

    PCS-924 Stub Differential Relay 2-5 Date: 2013-06-19

    Common mode: class III 2.5kV

    Differential mode: class III 1.0kV

    Electrostatic discharge test

    IEC60255-22-2:2008 class IV

    For contact discharge: 8kV

    For air discharge: 15kV

    Radio frequency interference tests

    IEC 60255-22-3:2007 class III

    Frequency sweep

    Radiated amplitude-modulated

    10V/m (rms), f=80~1000MHz

    Spot frequency

    Radiated amplitude-modulated

    10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

    Radiated pulse-modulated

    10V/m (rms), f=900MHz

    Fast transient disturbance tests

    IEC 60255-22-4:2008

    Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns

    Communication terminals: class IV, 2kV, 5kHz, 5/50ns

    Surge immunity test

    IEC 60255-22-5:2008

    Power supply, AC input, I/O port: class IV, 1.2/50us

    Common mode: 4kV

    Differential mode: 2kV

    Conducted RF Electromagnetic

    Disturbance

    IEC 60255-22-6:2001

    Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150

    kHz~80MHz

    Power Frequency Magnetic Field

    Immunity

    IEC 61000-4-8:2001

    class V, 100A/m for 1min, 1000A/m for 3s

    Pulse Magnetic Field Immunity IEC 61000-4-9:2001

    class V, 6.4/16s, 1000A/m for 3s

    Damped oscillatory magnetic field

    immunity

    IEC 61000-4-10:2001

    class V, 100kHz & 1MHz100A/m

    Auxiliary power supply performance

    - Voltage dips

    -Voltage short interruptions

    IEC60255-11: 2008

    Up to 500ms for dips to 40% of rated voltage without reset

    100ms for interruption without rebooting

    2.6 Certifications

    ISO9001:2008

    ISO14001:2004

    OHSAS18001:2007

    ISO10012:2003

  • 2 Technical Data

    PCS-924 Stub Differential Relay 2-6 Date: 2013-06-19

    CMMI L5

    EMC: 2004/108/EC, EN50263:1999

    Products safety(PS): 2006/95/EC, EN61010-1:2001

    2.7 Protective Functions

    Note!

    The meanings of symbols mentioned in the following sections are given here.

    In -- rated secondary current of CT

    Un -- rated secondary phase-to-ground voltage of VT

    Unn -- rated secondary phase-to-ground voltage of VT

    2.7.1 Current Differential Protection

    Setting range 0.100In~1.000In

    Accuracy 2.5% of setting or 0.02In whichever is greater

    2.7.2 Phase Overcurrent Protection

    Setting range 0.100In~20.000In

    Accuracy 2.5% of setting or 0.01Un, whichever is greater

    Time delay 0.01~10.00s

    Accuracy 1% of Setting+30ms (at 1.2 times voltage setting)

    2.7.3 Feeder Line End Fault Protection

    Setting range 0.100In~20.000In

    Accuracy 2.5% of setting or 0.01Un, whichever is greater

    Time delay 0.01~10.00s

    Accuracy 1% of Setting+30ms (at 1.2 times voltage setting)

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-a Date: 2011-08-02

    3 Operation Theory

    Table of Contents

    3.1 Fault Detector (FD) .......................................................................................... 3-1

    3.1.1 Application............................................................................................................................ 3-1

    3.1.2 Fault Detector in Fault Detector DSP .................................................................................. 3-1

    3.1.3 Protection Fault Detector in Protection Calculation DSP .................................................... 3-2

    3.1.4 Function Block Diagram ...................................................................................................... 3-3

    3.1.5 I/O Signal ............................................................................................................................. 3-3

    3.2 Current Differential Protection ....................................................................... 3-4

    3.2.1 Function Description ............................................................................................................ 3-4

    3.2.2 Protection Principle .............................................................................................................. 3-4

    3.2.3 Function Block Diagram ...................................................................................................... 3-6

    3.2.4 I/O Signal ............................................................................................................................. 3-6

    3.2.5 Logic .................................................................................................................................... 3-7

    3.2.6 Settings ................................................................................................................................ 3-9

    3.3 Feeder Line End Fault Protection .................................................................. 3-9

    3.3.1 Application............................................................................................................................ 3-9

    3.3.2 Protection Principle .............................................................................................................. 3-9

    3.3.3 Function Block Diagram .................................................................................................... 3-10

    3.3.4 I/O Signal ........................................................................................................................... 3-10

    3.3.5 Logic .................................................................................................................................. 3-10

    3.3.6 Settings ............................................................................................................................... 3-11

    3.4 Phase overcurrent protection ....................................................................... 3-11

    3.4.1 Protection Principle ............................................................................................................. 3-11

    3.4.2 Function Block Diagram .................................................................................................... 3-12

    3.4.3 I/O Signal ........................................................................................................................... 3-12

    3.4.4 Logic .................................................................................................................................. 3-12

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-b Date: 2011-08-02

    3.4.5 Settings .............................................................................................................................. 3-13

    3.5 Trip Logic ....................................................................................................... 3-13

    3.5.1 Application.......................................................................................................................... 3-13

    3.5.2 Function Description .......................................................................................................... 3-13

    3.5.3 Logic .................................................................................................................................. 3-14

    3.5.4 I/O Signal ........................................................................................................................... 3-14

    3.5.5 Settings .............................................................................................................................. 3-15

    List of Figures

    Figure 3.1-1 Flow chart of protection program ........................................................................ 3-3

    Figure 3.2-1 3-terminal application ............................................................................................ 3-4

    Figure 3.2-2 Logic of 3-terminal current differential protection ............................................. 3-7

    Figure 3.2-3 Logic of 2-terminal current differential protection ............................................. 3-8

    Figure 3.3-1 Logic of feeder line end fault protection ........................................................... 3-11

    Figure 3.4-1 Logic of phase overcurrent protection .............................................................. 3-13

    Figure 3.5-1 Simplified tripping logic ...................................................................................... 3-14

    List of Tables

    Table 3.1-1 Input signal ............................................................................................................... 3-3

    Table 3.1-2 Output signal ............................................................................................................ 3-3

    Table 3.2-1 Input signals ............................................................................................................. 3-6

    Table 3.2-2 Output signals .......................................................................................................... 3-6

    Table 3.2-3 Current differential protection settings ................................................................. 3-9

    Table 3.3-1 Input signals ........................................................................................................... 3-10

    Table 3.3-2 Output signals ........................................................................................................ 3-10

    Table 3.3-3 Feeder line end fault protection settings ............................................................ 3-11

    Table 3.4-1 Input signals ........................................................................................................... 3-12

    Table 3.4-2 Output signals ........................................................................................................ 3-12

    Table 3.4-3 Current differential protection settings ............................................................... 3-13

    Table 3.5-1 Input signal ............................................................................................................. 3-14

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-c Date: 2011-08-02

    Table 3.5-2 Output signal .......................................................................................................... 3-14

    Table 3.5-3 Setting description ................................................................................................ 3-15

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-d Date: 2011-08-02

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-1 Date: 2011-08-02

    3.1 Fault Detector (FD)

    3.1.1 Application

    The device has plug-in DSP modules with fault detector DSP and protection DSP for fault detector

    and protection calculation respectively. Protection DSP with protection fault detector element is

    responsible for calculation of protection elements, and fault detector DSP is responsible to

    determine fault appearance on the protected power system. Fault detector in fault detector DSP

    picks up to provide positive supply to output relays. The output relays can only operate when both

    the fault detector in fault detector DSP and a protection element operate simultaneously.

    Otherwise, the output relays would not operate. An alarm message will be issued with blocking

    outputs if a protection element operates while the fault detector does not operate.

    3.1.2 Fault Detector in Fault Detector DSP

    Main part of FD is differential current fault detector element and two breakers sum current fault

    detector element. They are continuously calculating the analog input signals.

    The FD pickup condition in this relay includes:

    1. Pickup condition 1: differential current is greater than the setting value

    2. Pickup condition 2: two breakers sum current is greater than the setting value

    If any of the above conditions is complied, the FD will operate to activate the output circuit

    providing with DC power supply to the output relays.

    3.1.2.1 Fault Detector Based on Differential Current (pickup condition 1)

    The criterion is:

    I3Dmax > [87S.I_Biased] Equation 3.1-1

    Where:

    = A, B or C

    I3Dmax = Max( Line_CB2_CB1_ III ), the maximum value of phase differential current of phase

    A, phase B and phase C, please refer to Figure 3.2-1 about CB1I , CB2I and LineI .

    [87S.I_Biased]: current setting of current differential protection.

    If operating condition is met, differential current element will pickup and trigger FD to provide DC

    power supply for output relays, the FD operation signal will maintain 7s after differential current

    element drops off.

    3.1.2.2 Fault Detector Based on Two Breakers Sum Current (pickup condition 2)

    The criterion:

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-2 Date: 2011-08-02

    Max( CB2_CB1_ II ) > [50P.I_Set] Equation 3.1-2

    Where:

    = A, B or C

    CB1I , CB2I : secondary current of two circuit breakers.

    [50P.I_Set]: current setting of phase overcurrent protection

    If above condition is met and phase overcurrent protection is enabled, two breakers sum current

    element will pickup and trigger FD to provide DC power supply for output relays, the FD operation

    signal will maintain 7s after two breakers sum current element drops off.

    3.1.3 Protection Fault Detector in Protection Calculation DSP

    The protection device is running either of the two programs: one is Regular program for normal

    state, and the other is Fault calculation program after protection fault detector picks up.

    Under the normal state, the protection device will perform the following tasks:

    1. Calculate analog quantity

    2. Read binary input

    3. Hardware self-check

    4. Disconnector position supervision

    5. Analog quantity input supervision

    Once the protection fault detector element in protection calculation DSP picks up, the protection

    device will switch to fault calculation program, for example the calculation of phase overcurrent

    protection, and to determine logic. If the fault is within the protected zone, the protection device will

    send tripping command.

    The protection program flow chart is shown as Figure 3.1-1.

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-3 Date: 2011-08-02

    Pickup?

    Regular program Fault calculation program

    No Yes

    Main program

    Sampling program

    Figure 3.1-1 Flow chart of protection program

    The protection FD pickup conditions are the same as the FD in fault detector DSP as shown below.

    The operation criteria for the conditions are also the same as that in fault detector DSP. Please

    refer to section 3.1.2 for details.

    1. Pickup condition 1: differential current is greater than the setting value

    2. Pickup condition 2: two breakers sum current is greater than the setting value

    When any pickup condition mentioned above is met, the protection device will go to fault

    calculation state.

    3.1.4 Function Block Diagram

    FD

    PkpI3P1

    Diff.Pkp

    OC.Pkp

    I3P2

    I3P3

    3.1.5 I/O Signal

    Table 3.1-1 Input signal

    No. Input Signal Description Configurable

    1 I3P1 Three-phase current input of CT1

    2 I3P2 Three-phase current input of CT2

    3 I3P3 Three-phase current input of CT3

    Table 3.1-2 Output signal

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-4 Date: 2011-08-02

    No. Output Signal Description Configurable

    1 FD.Pkp The device picks up

    2 FD.Diff.Pkp Differential current fault detector element operates.

    3 FD.OC.Pkp Two breakers sum current fault detector element operates.

    3.2 Current Differential Protection

    3.2.1 Function Description

    Generally, differential current is composed of 3-terminal current (current of two breakers and

    current of the feeder line, shown as Figure 3.2-1), only when normally closed auxiliary contact of

    feeder line disconnector is energized (feeder line disconnector is open), differential current is

    composed of 2-terminal current (currents of two breakers).

    3.2.2 Protection Principle

    3.2.2.1 3-terminal Current Differential Protection

    Three groups of current are inputted to the device (3 current circuits per group), as shown in

    Figure 3.2-1. CB1_I and CB2_I are secondary phase currents of two circuit breakers, Line_I

    are secondary phase currents of the line ( = A, B or C).

    Line

    52

    52

    52

    Line

    *

    *

    *

    PC

    S-9

    24

    02

    01

    ~0

    20

    60

    20

    7~

    02

    12

    02

    13

    ~0

    21

    8

    CT

    gro

    up

    1C

    T g

    rou

    p 2

    CT

    gro

    up

    3

    CT1

    CT2

    CT3

    CB1

    CB2

    CB3

    ICB2

    ICB1

    ILine

    Figure 3.2-1 3-terminal application

    When current differential protection is enabled, 3-terminal current differential protection is valid if

    normally closed auxiliary contact of feeder line disconnector is open (feeder line disconnector is

    closed).

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-5 Date: 2011-08-02

    The criterion:

    I3D > [87S.I_Biased] Equation 3.2-1

    I3D > [87S.Slope]I3R Equation 3.2-2

    Where:

    I3D: 3-terminal differential current (I3D = Line_CB2_CB1_ III )

    I3R: 3-terminal restraint current (I3R = Line_CB2_CB1_ III )

    [87S.I_Biased]: current setting of current differential protection

    [87S.Slope]: percentage restraint coefficient of current differential protection

    When I3D>1.3In, tripping output will operate once current differential protection operates (In:

    secondary rated current of CT).

    When I3D [87S.I_Biased] Equation 3.2-3

    I2D > [87S.Slope]I2R Equation 3.2-4

    Where:

    I2D: 2-terminal differential current (I2D = CB2_CB1_ II ).

    I2R: 2-terminal restraint current (I2R = CB2_CB1_ II ).

    [87S.I_Biased]: current setting of current differential protection.

    [87S.Slope]: percentage restraint coefficient of current differential protection.

    When I2D>1.3In, tripping output will operate once current differential protection operates (In:

    secondary rated current of CT).

    When I2D

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-6 Date: 2011-08-02

    protection operates.

    Both local circuit breakers are tripped (CB1 and CB2) but transfer tripping is not initiated after

    2-terminal current differential protection operates.

    3.2.2.3 Differential Current Alarm

    If any of the phase differential current is greater than the setting [87S.I_Alm] for 5s, this device will

    issue the alarm signal [87S.Alm_Diff]. If the alarmed phase differential current is reverted to

    normal, the alarm signal [87S.Alm_Diff] will be restored automatically after 5s.

    3.2.3 Function Block Diagram

    87S

    I3P1 87S.Op

    87S.En1

    87S.En2

    87S.Blk

    I3P2

    I3P3

    89b_DS

    87S.Op_2Terminals

    87S.St

    87S.Op_3Terminals

    87S.Valid_89b_DS

    87S.Alm_89b_DS

    87S.Alm_Diff

    3.2.4 I/O Signal

    Table 3.2-1 Input signals

    No. Input Signal Description Configurable

    1 I3P1 Three-phase current input of CT1

    2 I3P2 Three-phase current input of CT2

    3 I3P3 Three-phase current input of CT3

    4 89b_DS Normally closed auxiliary contact of feeder line disconnector

    5 87S.En1 Current differential protection enabling input 1, it can be binary

    inputs or logic links. Yes

    6 87S.En2 Current differential protection enabling input 2, it can be binary

    inputs or logic link. Yes

    7 87S.Blk

    Current differential protection blocking input, such as function

    blocking binary input.

    When the input is 1, current differential protection is reset and

    time delay is cleared.

    Yes

    Table 3.2-2 Output signals

    No. Output Signal Description Configurable

    1 87S.Op Current differential protection operates.

    2 87S.St Current differential protection picks up.

    3 87S.Op_2Terminals Current differential protection with two terminals operates. Yes

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-7 Date: 2011-08-02

    No. Output Signal Description Configurable

    4 87S.Op_3Terminals Current differential protection with three terminals operates. Yes

    5 87S.Valid_89b_DS Disconnector position is valid.

    6 87S.Alm_89b_DS Disconnector position is abnormal.

    7 87S.Alm_Diff Differential current is abnormal.

    3.2.5 Logic

    Logic diagram of 3-terminal current differential protection and 2-terminal current differential

    protection are shown in following two figures.

    &

    &

    &

    &

    &

    &

    &

    &

    &

    20ms 0

    >=1

    20ms 0

    >=1

    20ms 0

    >=1

    &

    87S.Op

    >=1

    BI BI_89b_DS

    SIG [87S.En1]

    SIG [87S.En2]

    SIG [87S.Blk]

    &

    EN [87S.En]

    SET I3DB>[87S.I_Biased]

    SET I3DC>[87S.I_Biased]

    SET I3DA>[87S.Slope]I3RA

    SET I3DB>[87S.Slope]I3RB

    SET I3DC>[87S.Slope]I3RC

    SIG I3DA>1.3In

    SIG I3DC>1.3In

    SIG I3DB>1.3In

    SET I3DA>[87S.I_Biased]

    Figure 3.2-2 Logic of 3-terminal current differential protection

    Where:

    I3DA: differential current of phase A for 3-terminal current differential protection

    I3DB: differential current of phase B for 3-terminal current differential protection

    I3DC: differential current of phase C for 3-terminal current differential protection

    I3RA: restraint current of phase A for 3-terminal current differential protection

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-8 Date: 2011-08-02

    I3RB: restraint current of phase B for 3-terminal current differential protection

    I3RC: restraint current of phase C for 3-terminal current differential protection

    &

    &

    &

    &

    &

    &

    &

    &

    &

    20ms 0

    >=1

    20ms 0

    >=1

    20ms 0

    >=1

    &

    87S.Op

    >=1

    BI BI_89b_DS

    SIG [87S.En1]

    SIG [87S.En2]

    SIG [87S.Blk]

    &

    EN [87S.En]

    SET I2DB>[87S.I_Biased]

    SET I2DC>[87S.I_Biased]

    SET I2DA>[87S.Slope]I2RA

    SET I2DB>[87S.Slope]I2RB

    SET I2DC>[87S.Slope]I2RC

    SIG I2DA>1.3In

    SIG I2DC>1.3In

    SIG I2DB>1.3In

    SET I2DA>[87S.I_Biased]

    Figure 3.2-3 Logic of 2-terminal current differential protection

    Where:

    I2DA: differential current of phase A for 2-terminal current differential protection

    I2DB: differential current of phase B for 2-terminal current differential protection

    I2DC: differential current of phase C for 2-terminal current differential protection

    I2RA: restraint current of phase A for 2-terminal current differential protection

    I2RB: restraint current of phase B for 2-terminal current differential protection

    I2RC: restraint current of phase C for 2-terminal current differential protection

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-9 Date: 2011-08-02

    3.2.6 Settings

    Table 3.2-3 Current differential protection settings

    No. Name Range Step Unit Remark

    1 87S.I_Biased (0.050~30.000)In 0.001 A Current setting of current differential

    protection

    2 87S.I_Alm (0.050~30.000)In 0.001 A Current setting of current differential CT

    alarm element

    3 87S.Slope 0.3~1.0 0.001 Slope of current differential protection

    4 87S.En 0 or 1 1

    Enabling or disabling current differential

    protection;

    0: disable; 1: enable

    5 87S.En_CTS_Blk 0 or 1 1

    Enabling or disabling CTS blocking

    current protection function;

    0: disable; 1: enable

    3.3 Feeder Line End Fault Protection

    3.3.1 Application

    Two stages of feeder line end fault protection is available for the device. If feeder line end fault

    protection is enabled, feeder line end fault protection is in service when normally closed auxiliary

    contact of feeder line disconnector is closed. (feeder line disconnector is open)

    3.3.2 Protection Principle

    The criterion:

    ILine_max > [50FLE1.I_Set] or [50FLE2.I_Set] Equation 3.3-1

    I3Dmax > [87S.I_Biased] Equation 3.3-2

    Where:

    ILine_max=Max(ILine_A, ILine_B, ILine_C), ILine_A, ILine_B and ILine_C are secondary phase current of the line.

    [50FLE1.I_Set], [50FLE2.I_Set]: current setting of stage 1 and stage 2 of feeder line end fault

    protection

    I3Dmax=Max( Line_CB2_CB1_ III ), the maximum value of phase differential current of phase A,

    phase B and phase C, please refer to Figure 3.2-1 about CB1I , CB2I and LineI .

    [87S.I_Biased]: current setting of current differential protection.

    In order to prevent the device from undesired trip due to error in normally closed auxiliary contact

    of feeder line disconnector, feeder line end fault protection is controlled by differential current

    element.

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-10 Date: 2011-08-02

    Provided that differential current element of feeder line end fault protection operates, if

    ILine_max >[50FLE1.I_Set], stage 1 of feeder line end fault protection will operate to initiate transfer

    trip after the time delay of [50FLE1.t_Op], if ILine_max >[50FLE2.I_Set], stage 2 of feeder line end

    fault protection will operate to initiate transfer trip after the time delay of [50FLE2.t_Op].

    3.3.3 Function Block Diagram

    50FLEx

    50FLEx.StI3P3

    50FLEx.Op

    50FLEx.En1

    50FLEx.En2

    50FLEx.Blk

    BI_89b_DS

    3.3.4 I/O Signal

    Table 3.3-1 Input signals

    No. Input Signal Description Configurable

    1 I3P3 Three-phase current input of CT3

    2 BI_89b_DS normally closed auxiliary contact of feeder line disconnector

    3 50FLEx.En1 Stage x of feeder line end fault protection enabling input 1, it can

    be binary inputs or logic links. Yes

    4 50FLEx.En2 Stage x of feeder line end fault protection enabling input 2, it can

    be binary inputs or logic link. Yes

    5 50FLEx.Blk

    Stage x of feeder line end fault protection blocking input, such as

    function blocking binary input.

    When the input is 1, feeder line end fault protection is reset and

    time delay is cleared.

    Yes

    Table 3.3-2 Output signals

    No. Output Signal Description Configurable

    1 50FLEx.St Operation signal of stage x of feeder line end fault protection

    2 50FLEx.Op Pickup signal of stage x of feeder line end fault protection

    3.3.5 Logic

    Logic diagram of feeder line end fault protection is shown in the following figure.

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-11 Date: 2011-08-02

    SIG [50FLEx.En1]

    SIG [50FLEx.En2]

    SIG [50FLEx.Blk]

    &

    EN [50FLEx.En]

    SET ILine_max>[50FLEx.I_Set] &

    50FLEx.St

    50FLEx.t_Op 0ms 50FLEx.Op

    BI BI_89b_DS

    SET I3Dmax>[87S.I_Biased]

    Figure 3.3-1 Logic of feeder line end fault protection

    Where:

    x=1 or 2

    3.3.6 Settings

    Table 3.3-3 Feeder line end fault protection settings

    No. Name Range Step Unit Remark

    1 50FLE1.I_Set (0.050~30.000)In 0.001 A Current setting of stage 1 of feeder

    line end fault protection

    2 50FLE1.t_Op 0.000~20.000 0.001 s Time delay of stage 1 of feeder line

    end fault protection

    3 50FLE1.En 0 or 1

    Enabling or disabling stage 1 of

    feeder line end fault protection

    0: disable

    1: enable

    4 50FLE2.I_Set (0.050~30.000)In 0.001 A Current setting of stage 2 of feeder

    line end fault protection

    5 50FLE2.t_Op 0.000~20.000 0.001 s Time delay of stage 2 of feeder line

    end fault protection

    6 50FLE2.En 0 or 1

    Enabling or disabling stage 2 of

    feeder line end fault protection

    0: disable

    1: enable

    3.4 Phase overcurrent protection

    3.4.1 Protection Principle

    Phase overcurrent protection is based on the sum current of two circuit breakers, the criterion is:

    Max( CB2_CB1_ II )>[50P.I_Set] Equation 3.4-1

    CB1I , CB2I : secondary current of two circuit breakers.

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-12 Date: 2011-08-02

    = A, B or C

    [50P.I_Set]: current setting of phase overcurrent protection.

    Both local circuit breakers (CB1 and CB2) will be tripped if phase overcurrent protection operates.

    3.4.2 Function Block Diagram

    50P

    50P.StI3P1

    50P.Op50P.En1

    50P.En2

    50P.Blk

    I3P2

    3.4.3 I/O Signal

    Table 3.4-1 Input signals

    No. Input Signal Description Configurable

    1 I3P1 Three-phase current input of CT1

    2 I3P2 Three-phase current input of CT2

    3 50P.En1 Phase overcurrent protection enabling input 1, it can be binary

    inputs or logic links. Yes

    4 50P.En2 Phase overcurrent protection enabling input 2, it can be binary

    inputs or logic link. Yes

    5 50P.Blk

    Phase overcurrent protection blocking input, such as function

    blocking binary input.

    When the input is 1, phase overcurrent protection is reset and

    time delay is cleared.

    Yes

    Table 3.4-2 Output signals

    No. Output Signal Description Configurable

    1 50P.Op Operation signal of phase overcurrent protection

    2 50P.St Pickup signal of phase overcurrent protection

    3.4.4 Logic

    Logic diagram of phase overcurrent protection is shown in following figure.

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-13 Date: 2011-08-02

    SIG [50P.En1]

    SIG [50P.En2]

    SIG [50P.Blk]

    &

    EN [50P.En]

    SET Max( )>[50P.I_Set] CB2_CB1_ II

    50P.t_Op 0ms

    &

    50P.Op

    50P.St

    Figure 3.4-1 Logic of phase overcurrent protection

    3.4.5 Settings

    Table 3.4-3 Current differential protection settings

    No. Name Range Step Unit Remark

    1 50P.I_Set (0.050~30.000)In 0.001 A current setting of phase overcurrent

    element

    2 50P.t_Op 0.000~20.000 0.001 s time delay of phase overcurrent

    element

    3 50P.En 0 or 1 enable phase overcurrent element

    3.5 Trip Logic

    3.5.1 Application

    For any enabled protection tripping elements, their operation signal will convert to appropriate

    tripping signals through trip logics and then trigger output contacts by configuration.

    3.5.2 Function Description

    This module gathers signals from protection tripping elements and then converts the operation

    signal from protection tripping elements to appropriate tripping signals.

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-14 Date: 2011-08-02

    3.5.3 Logic

    SIG Max(I3P3)>0.06I2n

    SIG 87S.Op_3Terminals

    TT

    &

    t_Dwell_TT 0

    SIG FD.Pkp

    &

    >=1

    SIG 50FLE1.Op

    SIG 50FLE2.Op

    >=1

    0 t_Dwell_TT&

    SIG Max(I3P1+I3P2)>0.06I2n

    SIG 87S.Op_3Terminals

    Trp

    &

    t_Dwell_Trp 0

    SIG FD.Pkp

    &

    >=1

    SIG 87S.Op_2Terminals

    SIG 50P.Op

    >=1

    0 t_Dwell_Trp&

    Figure 3.5-1 Simplified tripping logic

    1. [t_Dwell_Trp] is the shortest period of tripping contact operation. The tripping contact shall be

    reset under conditions of no current and or protection tripping element reset.

    3.5.4 I/O Signal

    Table 3.5-1 Input signal

    Name Description

    I3P1 Three-phase current input of CT1

    I3P2 Three-phase current input of CT2

    I3P3 Three-phase current input of CT3

    87S.Op_3Terminals 3-terminal current differential protection operates.

    87S.Op_2Terminals 2-terminal current differential protection operates.

    50FLE1.Op Operation signal of stage 1 of feeder line end fault protection

    50FLE2.Op Operation signal of stage 2 of feeder line end fault protection

    50P.Op Operation signal of phase overcurrent protection

    Table 3.5-2 Output signal

    Name Description

    Trp Tripping local two circuit breakers

    TT Initiating transfer tripping

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-15 Date: 2011-08-02

    3.5.5 Settings

    Table 3.5-3 Setting description

    No. Name Range Step Unit Remark

    1 t_Dwell_Trp 0.000~1000.000 0.001 s the dwell time of tripping command, empirical

    value is 0.04

    2 t_Dwell_TT 0.000~1000.000 0.001 s the dwell time of transfer tripping command

  • 3 Operation Theory

    PCS-924 Stub Differential Relay 3-16 Date: 2011-08-02

  • 4 Supervision

    PCS-924 Stub Differential Relay 4-a Date: 2011-08-02

    4 Supervision

    Table of Contents

    4.1 General Description ........................................................................................ 4-1

    4.2 Supervision Alarms ......................................................................................... 4-1

    4.3 Relay Self-supervision .................................................................................... 4-4

    4.3.1 Relay Hardware Monitoring ................................................................................................. 4-4

    4.3.2 Fault Detector Monitoring .................................................................................................... 4-4

    4.3.3 Check Tripping Output Circuit.............................................................................................. 4-4

    4.3.4 Check Setting ...................................................................................................................... 4-4

    4.4 AC Input Monitoring ........................................................................................ 4-4

    4.4.1 Current Drift Monitoring and Auto-adjustment ..................................................................... 4-4

    4.4.2 Sampling Monitoring ............................................................................................................ 4-4

    4.5 Secondary Circuit Monitoring ........................................................................ 4-5

    4.5.1 Opto-coupler Power Supervision ......................................................................................... 4-5

    Table of Tables

    Table 4.2-1 Alarm description and handling suggestion ........................................................ 4-1

  • 4 Supervision

    PCS-924 Stub Differential Relay 4-b Date: 2011-08-02

  • 4 Supervision

    PCS-924 Stub Differential Relay 4-1 Date: 2011-08-02

    4.1 General Description

    Protection system is in quiescent state under normal conditions, and it is required to respond

    promptly for faults occurred on power system. When equipment is in energizing process before the

    LED HEALTHY is on, the equipment need to be checked to ensure no abnormality. Therefore,

    the automatic supervision function, which checks the health of the protection system when startup

    and during normal operation, plays an important role.

    The numerical relay based on the microprocessor operations is suitable for implementing this

    automatic supervision function of the protection system.

    In case a defect is detected during initialization when DC power supply is provided to the

    equipment, the equipment will be blocked with indication and alarm of relay out of service. It is

    suggested a trial recovery of the equipment by re-energization. Please contact supplier if the

    equipment is still failure.

    When a failure is detected by the automatic supervision, it is followed by a LCD message, LED

    indication and alarm contact outputs. The failure alarm is also recorded in event recording report

    and can be printed If required.

    4.2 Supervision Alarms

    Hardware circuit and operation status of the equipment are self-supervised continuously. If any

    abnormal condition is detected, information or report will be displayed and a corresponding alarm

    will be issued.

    A minor abnormality may block a certain number of protections functions while the other functions

    can still work. However, if severe hardware failure or abnormality are detected, all protection

    functions will be blocked and the LED HEALTHY will be extinguished and blocking output

    contacts BO_FAIL will be given. The protective device then can not work normally and

    maintenance is required to eliminate the failure. All the alarm signals and the corresponding

    handling suggestions are listed below.

    Note!

    If the protective device is blocked or alarm signal is sent during operation, please do find

    out its reason with the help of self-diagnostic record. If the reason can not be found at site,

    please notify the factory NR. Please Do not simply press button TARGET RESET on the

    protection panel or re-energize on the protective device.

    Table 4.2-1 Alarm description and handling suggestion

    No. Item Alarm description Handing suggestion

    1 Fail_Device The device fails.

    The signal is issued with other specific alarm

    signals, and please refer to the handeling

    suggestion other specific alarm signals.

    2 Alm_Device The device is abnormal. The signal is issued with other specific alarm

  • 4 Supervision

    PCS-924 Stub Differential Relay 4-2 Date: 2011-08-02

    signals, and please refer to the handeling

    suggestion other specific alarm signals.

    3 Alm_CommTest The device is in the

    communication test mode.

    No special treatment is needed, and disable

    the communication test function after the

    completion of the test.

    4 Alm_Setting_OvRange Set value of any setting is out

    of scope.

    Please reset setting values according to the

    range described in the instruction manual,

    then re-power or reboot the equipment and

    the alarm message will disappear and the

    equipment will restore to normal operation

    state.

    5 Alm_BoardConfig

    Mismatch between the

    configuration of plug-in

    modules and the designing

    drawing of an applied-specific

    project.

    1. Go to the menu InformationBorad

    Info, check the abnormality information.

    2. For the abnormality board, if the board

    is not used, then remove, and if the board is

    used, then check whether the board is

    installed properly and work normally.

    3. After the abnormality is removed,

    re-power or reboot the device and the device

    will restore to normal operation state.

    6 Bxx.Fail_TrpOut

    Driving circuits of binary

    output relays of BO plug-in

    module in slot xx are

    damaged.

    Please re-insert the corresponding binary

    output module and re-power the equipment

    after the completion of insertion, and the

    device will restore to normal operation state.

    7 Fail_SettingSurv

    Setting surveillance between

    DSP module and MON

    module is abnormal.

    Please inform the manufacture or the agent

    for repair.

    8 Fail_Memory Error is found during

    checking memory data.

    Please inform the manufacture or the agent

    for repair.

    9 Fail_Settings Error is found during

    checking settings.

    1. Check CT ratio settings of each side of

    transformer to be set in proper range, and if

    need, please reset those settings and reboot

    or re-power the device.

    2. Check overexcitation settings to be set

    reasonable, and if need, please reset those

    settings and reboot or re-power the device.

    3. After above two steps, abnormality may

    disappear. Otherwise, a hardware failue

    probably ocurrs and please inform the

    manufacture or the agent.

    10 Fail_DSP DSP chip is damaged.

    Chips are damaged and please inform the

    manufacture or the agent replacing the

    module.

    11 Bxx.Alm_OptoDC The power supply of BI 1. check whether the binary input module

  • 4 Supervision

    PCS-924 Stub Differential Relay 4-3 Date: 2011-08-02

    plug-in module in slot xx is

    abnormal.

    is connected to the power supply.

    2. check whether the voltage of power

    supply is in the required range.

    3. After the voltage for binary input module

    restores to normal range, the ALARM LED

    will be extinguished and the corresponding

    alarm message will disappear and the device

    will restore to normal operation state.

    12 Fail_Config Software configuation is

    incorrect.

    Please inform configuration engineers to

    check and confirm visualization functions of

    the device

    13 Fail_Sample AC current samplings are

    abnormal.

    1. Please make the device out of service.

    2. Then check if the analog input modules

    and wiring connectors connected to those

    modules are installed at the position.

    3. Re-power the device and the device will

    restore to normal operation state.

    14 Alm_PersistFD Fault detector element

    operates for longer than 10s.

    Please check secondary values and

    protection settings. If settings are not set

    reasonable to make fault detectors pick up,

    please reset settings, and then the alarm

    message will disappear and the device will

    restore to normal operation state.

    15 CTS.Alm CT circuit of corresponding

    circuit breaker fails.

    Please check the corresponding CT

    secondary circuit. After the abnormality is

    eliminated, ALARM LED will go off

    automatically and device returns to normal

    operation state.

    16 Fail_SV_QF The quality factor of sample

    values is abnormal.

    Thess alarms may be issued for electric

    transformer applied projects. If alarms are

    issued, please check working state of

    merging units and the connection between

    merging units and the protection device.

    17 Alm_Maintenance The device is in maintenance

    state.

    After maintenance is finished, please

    de-energized the binary input

    [BI_Maintenance] and then the alarm will

    disappear and the device restore to normal

    operation state.

    18 Alm_TimeSync Time synchronization

    abnormality alarm.

    1. check whether the selected clock

    synchronization mode matches the clock

    synchronization source;

    2. check whether the wiring connection

    between the equipment and the clock

  • 4 Supervision

    PCS-924 Stub Differential Relay 4-4 Date: 2011-08-02

    synchronization source is correct

    3. check whether the setting for selecting

    clock synchronization (i.e. [Opt_TimeSync])

    is set correctly. If there is no clock

    synchronization, please set the setting

    [Opt_TimeSync] as No TimeSync.

    4. After the abnormality is removed, the

    ALARM LED will be extinguished and the

    corresponding alarm message will disappear

    and the device will restore to normal

    operation state.

    4.3 Relay Self-supervision

    4.3.1 Relay Hardware Monitoring

    All chips on DSP module are monitored to ensure whether they are damaged or having errors. If

    any one of them is detected damaged or having error, the alarm signal [Fail_DSP] is issued with

    device being blocked.

    4.3.2 Fault Detector Monitoring

    When any fault detector picks up for over 10s, an alarm will be issued [Alm_PersistFD] without

    protective device blocked.

    4.3.3 Check Tripping Output Circuit

    Chips controlling the output relays in the output circuit are continually monitored. If any error or

    damage is detected in these chips, alarm [Bxx.Fail_TrpOut] will be given and the device will be

    blocked.

    4.3.4 Check Setting

    This relay has 10 setting groups, only one setting group could be activiated (is active) at a time.

    The settings of active setting group are checked to ensure they are reasonable. If settings are

    checked to be unreasonable or out of setting scopes, a corresponding alarm signal will be issued,

    and protective device is also blocked.

    4.4 AC Input Monitoring

    4.4.1 Current Drift Monitoring and Auto-adjustment

    Zero point of current may drift due to variation of temperature or other environment factors. The

    equipment continually traces the drift and adjust it to normal value automatically.

    4.4.2 Sampling Monitoring

    AC current samplings of protection DSP and fault detector DSP are monitored and if the samples

    of protection DSP and fault detector DSP are detected to be wrong or inconsistent between them,

  • 4 Supervision

    PCS-924 Stub Differential Relay 4-5 Date: 2011-08-02

    the alarm signal [Fail_Sample] will be issued and the device will be blocked.

    4.5 Secondary Circuit Monitoring

    4.5.1 Opto-coupler Power Supervision

    Positive power supply of opto-coupler is continually monitored. If an error or damage has occurred,

    an alarm [Bxx.Alm_OptoDC] will be issued.

  • 4 Supervision

    PCS-924 Stub Differential Relay 4-6 Date: 2011-08-02

  • 5 Measurement and Recording

    PCS-924 Stub Differential Relay 5-a Date: 2011-08-02

    5 Measurement and Recording

    Table of Contents

    5.1 Measurement ................................................................................................... 5-1

    5.2 Recording ........................................................................................................ 5-1

    5.2.1 General Description ............................................................................................................. 5-1

    5.2.2 Event Recording .................................................................................................................. 5-2

    5.2.3 Disturbance Recording ........................................................................................................ 5-2

    5.2.4 Present Recording ............................................................................................................... 5-3

  • 5 Measurement and Recording

    PCS-924 Stub Differential Relay 5-b Date: 2011-08-02

  • 5 Measurement and Recording

    PCS-924 Stub Differential Relay 5-1 Date: 2011-08-02

    5.1 Measurement

    PCS-924 performs continuous measurement of the analogue input quantities. The relay samples

    24 points per cycle and calculates the RMS value in each interval and updated the LCD display in

    every 0.5s. The measurement data can be displayed on the LCD of the relay front panel or on the

    local/remote PC via software tool. Navigate the menu to view the sampling value through LCD

    screen.

    1. RMS Values

    Access path: Press key to enter main menu firstly. Select the item Measurements and press

    key ENT to enter, and then select submenu Measurements1. Press key ENT to display

    corresponding measurement values as below on the LCD.

    Measured directly

    Magnitude of phase current of CT1 (Ia1, Ib1, Ic1)

    Magnitude of phase current of CT2 (Ia2, Ib2, Ic2)

    Magnitude of phase current of CT3 (Ia3, Ib3, Ic3)

    Calculated by DSP

    Differential current (Id_a, Id_b, Id_c)

    Phase Angle

    Phase angle of (Ia1-Ib1), (Ib1-Ic1), (Ic1-Ia1)

    Phase angle of (Ia2-Ib2), (Ib2-Ic2), (Ic2-Ia2)

    Phase angle of (Ia3-Ib3), (Ib3-Ic3), (Ic3-Ia3)

    Phase angle of (Ia1-Ia2), (Ib1-Ib2), (Ic1-Ic2)

    Phase angle of (Ia1-Ia3), (Ib1-Ib3), (Ic1-Ic3)

    Phase angle of (Ia2-Ia3), (Ib2-Ib3), (Ic2-Ic3)

    5.2 Recording

    5.2.1 General Description

    PCS-924 provides the following recording functions:

    1. Event recording

    2. Disturbance recording

    3. Present recording

    All the recording information except waveform can be viewed on local LCD or by printing.

    Waveform could only be printed or extracted with PCS-PC software tool and a waveform analysis

    software.

  • 5 Measurement and Recording

    PCS-924 Stub Differential Relay 5-2 Date: 2011-08-02

    5.2.2 Event Recording

    5.2.2.1 General Description

    The device can store the latest 1024 disturbance records, 1024 binary events, 1024 supervision

    events and 1024 device logs. All the records are stored in non-volatile memory, and when the

    available space is exhausted, the oldest record is automatically overwritten by the latest one.

    5.2.2.2 Disturbance Records

    When any protection element operates or drops off, such as fault detector, distance protection etc.,

    they will be logged in event records.

    5.2.2.3 Supervision Events

    The device is under automatic supervision all the time. If there are any failure or abnormal

    condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event

    records.

    5.2.2.4 Binary Events

    When there is a binary input is energized or de-energized, i.e., its state has changed from 0 to 1

    or from 1 to 0, it will be logged in event records.

    5.2.2.5 Device Logs

    If an operator implements some operations on the device, such as reboot protective device,

    modify setting, etc., they will be logged in event records.

    5.2.3 Disturbance Recording

    5.2.3.1 Application

    Disturbance records can be used to have a better understanding of the behavior of the power

    network and related primary and secondary equipment during and after a disturbance. Analysis of

    the recorded data provides valuable information that can be used to improve existing equipment.

    This information can also be used when planning for and designing new installations.

    5.2.3.2 Design

    A disturbance record consists of fault record and fault waveform. A disturbance record is initiated

    by fault detector element.

    The disturbance record has two types:

    1. Fault detector element picks up without operation of protective element.

    2. Fault detector element picks up with operation of protective elements.

    5.2.3.3 Capacity and Information of Disturbance Records

    The device can store up to 64 disturbance records with waveform in non-volatile memory. It is

    based on first in first out queue that the oldest disturbance record will be overwritten by the latest

    one.

  • 5 Measurement and Recording

    PCS-924 Stub Differential Relay 5-3 Date: 2011-08-02

    For each disturbance record, the following items are included:

    1. Sequence number

    Each operation will be recorded with a sequence number in the record and displayed on LCD

    screen.

    2. Date and time of fault occurrence

    The time resolution is 1ms using the relay internal clock synchronized via clock synchronized

    device if connected. The date and time is recorded when a system fault is detected.

    3. Relative operating time

    An operating time (not including the operating time of output relays) is recorded in the record.

    4. Faulty phase

    5. Protection elements

    5.2.3.4 Capacity and Information of Fault Waveform

    MON module can store 64 pieces of fault waveform oscillogram in non-volatile memory. If a new

    fault occurs when 64 fault waveform have been stored, the oldest will be overwritten by the latest

    one.

    Each fault record consists of all analog and digital quantities related to protection, such as original

    current and voltage, differential current, alarm elements, and binary inputs and etc.

    Each time recording includes 10-cycle pre-fault waveform, and 250 cycles at least and 500 cycles

    at most can be recorded.

    5.2.4 Present Recording

    Present recording is a waveform triggered manually on on the devices LCD or remotely through

    PCS-PC software. Recording content of present recording is same to that of disturbance

    recording.

    Each time recording includes 10-cycle waveform before triggering, and 250 cycles at most can be

    recorded.

  • 5 Measurement and Recording

    PCS-924 Stub Differential Relay 5-4 Date: 2011-08-02

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-a Date: 2011-08-02

    6 Hardware

    Table of Contents

    6.1 General Description ........................................................................................ 6-1

    6.2 Typical Wiring .................................................................................................. 6-4

    6.2.1 Conventional CT/VT (For reference only) ........................................................................... 6-4

    6.2.2 ECT/EVT (For reference only) ............................................................................................. 6-6

    6.3 Plug-in Module Description ............................................................................ 6-8

    6.3.1 PWR Plug-in Module (Power Supply) ................................................................................. 6-8

    6.3.2 MON Plug-in Module (Management) ................................................................................. 6-10

    6.3.3 AI Plug-in Module (Analog Input) ....................................................................................... 6-13

    6.3.4 DSP Plug-in Module (Fault Detector and Protection Calculation) .................................... 6-15

    6.3.5 NET-DSP Plug-in Module (GOOSE and SV) .................................................................... 6-16

    6.3.6 BI Plug-in Module (Binary Input)........................................................................................ 6-16

    6.3.7 BO Plug-in Module (Binary Output) ................................................................................... 6-20

    6.3.8 HMI Module........................................................................................................................ 6-22

    List of Figures

    Figure 6.1-1 Rear view of fixed module position ..................................................................... 6-1

    Figure 6.1-2 Hardware diagram .................................................................................................. 6-2

    Figure 6.1-3 Front view of PCS-924 ........................................................................................... 6-3

    Figure 6.1-4 Typical rear view of PCS-924 ................................................................................ 6-4

    Figure 6.2-1 Typical wiring of PCS-924 (conventional CT/VT) ................................................ 6-5

    Figure 6.2-2 Typical wiring of PCS-924 (ECT/EVT) .................................................................. 6-7

    Figure 6.3-1 View of PWR plug-in module ................................................................................ 6-9

    Figure 6.3-2 Output contacts of PWR plug-in module ............................................................. 6-9

    Figure 6.3-3 View of MON plug-in module .............................................................................. 6-11

    Figure 6.3-4 Connection of communication terminal ............................................................ 6-13

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-b Date: 2011-08-02

    Figure 6.3-5 View of AI plug-in module ................................................................................... 6-14

    Figure 6.3-6 View of DSP plug-in module ............................................................................... 6-15

    Figure 6.3-7 View of NET-DSP plug-in module ....................................................................... 6-16

    Figure 6.3-8 View of BI plug-in module (NR1503) .................................................................. 6-17

    Figure 6.3-9 View of BI plug-in module (NR1504) .................................................................. 6-17

    Figure 6.3-10 View of BO plug-in module (NR1521A) ............................................................ 6-21

    Figure 6.3-11 View of BO plug-in module (NR1521C) ............................................................ 6-21

    Table of Tables

    Table 6.3-1 Terminal definition and description ....................................................................... 6-9

    Table 6.3-2 Terminal definition of AI module .......................................................................... 6-14

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-1 Date: 2011-08-02

    6.1 General Description

    PCS-924 adopts 64-bit microchip processor CPU produced by FREESCALE as control core for

    logic calculation and management function, meanwhile, adopts high-speed digital signal processor

    DSP for all the protection calculation. 24 points are sampled in every cycle and parallel processing

    of sampled data can be realized in each sampling interval to ensure ultrahigh reliability and safety

    of protection equipment.

    PCS-924 is comprised of intelligent plug-in modules, except that few particular plug-in modules

    position cannot be changed in the whole device (gray plug-in modules as shown in Figure 6.1-1),

    other plug-in modules like AI (analog input) and IO (binary input and binary output) can be flexibly

    configured in the remaining slot positions.

    MO

    N m

    od

    ule

    DS

    P m

    od

    ule

    PW

    R m

    od

    ule

    01 04 05 06 07 00

    AI

    mo

    du

    le

    BI

    mo

    du

    le

    BO

    mo

    du

    leSlot No.

    02 03 08 09 10 11 12 13 14 15

    BI

    mo

    du

    le

    BO

    mo

    du

    le

    BO

    mo

    du

    le

    BO

    mo

    du

    le

    Figure 6.1-1 Rear view of fixed module position

    PCS-924 has 16 slots, PWR module, MON module and DSP module are assigned at fixed slots.

    Besides 3 fixed modules are shown in above figure, there are 13 slots can be flexibly configured.

    AI plug-in module, BI plug-in module and BO plug-in module can be configured at position

    between slot B02, B03 and B06~B15. It should be pay attention that AI plug-in module will occupy

    two slots.

    This device is developed on the basis of our latest software and hardware platform, and the new

    platform major characteristics are of high reliability, networking and great capability in

    anti-interference great capability in anti-interference. See Figure 6.1-2 for hardware diagram.

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-2 Date: 2011-08-02

    Conventional CT/VT

    Exte

    rnal

    Bin

    ary

    Input

    Outp

    ut R

    ela

    y

    +E

    Pickup

    Relay

    Protection

    Calculation

    DSP

    A/D

    LCD

    Fault

    Detector

    DSP

    A/D

    CPU

    ECVT

    ECVT

    Power

    SupplyUaux

    Keypad

    LED

    Clock SYN

    PRINT

    RJ45

    ETHERNET

    Figure 6.1-2 Hardware diagram

    The working process of the device is as shown in above figure: current and voltage from

    conventional CT/VT are converted into small voltage signal and sent to DSP module after filtered

    and A/D conversion for protection calculation and fault detector respectively (ECVT signal is sent

    to the relay without small signal and A/D convertion). When DSP module completes all the

    protection calculation, the result will be recorded in 64-bit CPU on MON module. DSP module

    carries out fault detector, protection logic calculation, tripping output, and MON module perfomes

    SOE (sequence of event) record, waveform recording, printing, communication between

    protection and SAS and communication between HMI and CPU. When fault detector detects a

    fault and picks up, positive power supply for output relay is provided.

    The items can be flexibly configured depending on the situations like sampling method of device

    (conventional CT/VT and ECT/EVT), the mode of binary output (conventional binary output and

    GOOSE binary output), and whether it needs independent binary output for pole discrepancy

    protection. The configurations for PCS-900 series based on microcomputer are classified into

    standard and optional modules.

    Table 6.1-1 PCS-924 module configuration

    No. ID Module description Remark

    1 NR1101/NR1102 Management module (MON module) Standard

    2 NR1401 Analog input module (AI module ) Standard

    3 NR1161 Protection calculation and fault detector module (DSP module) Standard

    4 NR1503/NR1504 Binary input module (BI module) Standard

    5 NR1521 Binary output module (BO module) Standard

    6 NR1301 Power supply module (PWR module) Standard

    7 NR1136 GOOSE and SV from merging unit by IEC61850-9-2 (NET-DSP Option

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-3 Date: 2011-08-02

    No. ID Module description Remark

    module)

    8 Human machine interface module (HMI module) Standard

    MON module provides functions like management function, event record, setting

    management etc.

    AI module converts AC current and voltage from current transformers and voltage

    transformers respectively to small voltage.

    DSP module performs filtering, sampling, protection calculation and fault detector calculation.

    BI module provides binary inputs, the binary inputs are opto-couplers of rating

    24V/110V/125V/220V/250V (configurable).

    BO module provides output contacts for tripp[ing, and signal output contact for annunciation

    signal, remote signal, fault and disturbance signal, operation abnormal signal etc.

    PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of

    the device.

    HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user

    as human-machine interface.

    NET-DSP module receives and sends GOOSE messages, sampled values (SV) from

    merging unit by IEC61850-9-2 protocol.

    PCS-924 series is made of a 4U height 19 chassis for flush mounting. Components mounted on

    its front include a 320240 dot matrix LCD, a 9 button keypad, 20 LED indicators and a multiplex

    RJ45 port. A monolithic micro controller is installed in the equipment for these functions.

    Following figures show front and rear views of PCS-924 respectively.

    ENT

    ES

    CG

    RP

    PCS-9241

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    HEALTHY

    ALARM STUB DIFFERENTIAL RELAY

    Figure 6.1-3 Front view of PCS-924

    20 LED indicators are, from top to bottom, operation (HEALTHY), self-supervision (ALARM),

    others are configurable.

    For the 9-button keypad, ENT is enter, GRP is group number and ESC is escape.

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-4 Date: 2011-08-02

    NR1102 NR1401

    DANGER

    NR1161

    1

    2

    NR1504 NR1521 NR1521 NR1521 NR1521 NR1301

    11

    1

    9

    3

    10

    8

    7

    6

    4

    5

    2

    12

    BO_COM1

    BO_ALM

    OPTO+

    BO_FAIL

    BO_ALM

    BO_COM2

    OPTO-

    PWR+

    PWR-

    GND

    BO_FAIL

    5V ALM

    BO_ALM BO_FAIL

    OK

    NR1504

    Figure 6.1-4 Typical rear view of PCS-924

    6.2 Typical Wiring

    6.2.1 Conventional CT/VT (For reference only)

    MO

    N m

    od

    ule

    DS

    P m

    od

    ule

    PW

    R m

    od

    ule

    01 04 05 06 07 00

    AI

    mo

    du

    le

    BI

    mo

    du

    le

    BO

    mo

    du

    le

    Slot No.02 03 08 09 10 11 12 13 14 15

    NR1301

    BO

    mo

    du

    le

    BO

    mo

    du

    le

    NR1521ANR1504NR1102 NR1401 NR1161 NR1521C NR1521B

    The following typical wiring is given based on above hardware configuration

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-5 Date: 2011-08-02

    Ia

    Ib

    Ic

    0201

    0202

    0203

    0204

    0205

    0206

    Cu

    rren

    t of C

    T1

    0225

    0010

    0011

    0001

    0002

    0003

    BO_FAIL

    BO_ALM

    0004

    0005

    0006

    BO_FAIL

    BO_ALM

    0007

    0008

    0012

    Power

    Supply

    PWR+

    PWR-

    OPTO+

    OPTO-

    External DC power

    supply

    Power supply for

    opto-coupler (24V)

    COM

    COM

    Multiplex

    RJ45 (Front)Grounding

    Bus

    0801

    0802

    0807

    0809

    0814

    0821

    0808

    0816

    0815

    +

    +

    +

    +

    +

    +

    Not used

    Not used

    Power supply supervision

    BI_01

    BI_06

    BI_07

    BI_12

    BI_13

    BI_18

    0822-

    PT

    INT

    ER

    0101

    0102

    0103

    0105

    0106

    0107SGND

    RTS

    TXD

    SYN+

    SYN-

    SGND

    Clo

    ck S

    YN

    PR

    INT

    0104

    0101

    0102

    0103

    485-1A

    485-1B

    SGND

    CO

    M

    0104

    1101

    1102

    1103

    1104

    1105

    1106

    1121

    1122

    1201

    1202

    1203

    1204

    1205

    1206

    1221

    1222

    1301

    1302

    1303

    1304

    1305

    1306

    1317

    1318

    1319

    1320

    1321

    1322

    BO_01

    BO_02

    BO_03

    BO_11

    BO_01

    BO_02

    BO_03

    BO_11

    BO_01

    BO_02

    BO_03

    BO_09

    BO_10

    BO_11

    Co

    ntro

    lled

    by fa

    ult d

    ete

    cto

    r

    ele

    me

    nt

    Sig

    na

    l Bin

    ary

    Ou

    tpu

    t (op

    tion

    )

    Firs

    t 9 c

    on

    tacts

    co

    ntro

    lled

    by fa

    ult d

    ete

    cto

    r

    ele

    me

    nt a

    nd

    last 2

    co

    nta

    cts

    with

    ou

    t co

    ntro

    lled

    by

    fau

    lt de

    tecto

    r ele

    me

    nt (o

    ptio

    n)

    *BI p

    lug

    -in m

    od

    ule

    ca

    n b

    e in

    de

    pe

    nd

    en

    t co

    mm

    on

    term

    ina

    l

    To

    the

    scre

    en

    of o

    the

    r co

    axia

    l

    ca

    ble

    with

    sin

    gle

    po

    int e

    arth

    ing

    Ia

    Ib

    Ic

    0207

    0208

    0209

    0210

    0211

    0212

    Cu

    rren

    t of C

    T2

    Ia

    Ib

    Ic

    0213

    0214

    0215

    0216

    0217

    0218C

    urre

    nt o

    f CT

    3

    Figure 6.2-1 Typical wiring of PCS-924 (conventional CT/VT)

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-6 Date: 2011-08-02

    01

    NR1301

    PWR

    09080705040302 001312

    NR1102

    BOBIMON

    NR1521NR1504

    PCS-924 (conventional CT/VT and conventional binary output)

    NET-

    DSP

    NR1136

    PCS-924 (conventional CT/VT and GOOSE binary output)

    NR1521

    BO

    NR1521

    BO

    06 10 11 14 15

    NR1521

    BO

    Slot No.

    Module ID

    01

    NR1301

    PWR

    09080705040302 001312

    NR1102

    BIAI DSPMON

    NR1504NR1161NR1401

    06 10 11 14 15Slot No.

    Module ID

    BI

    NR1504

    AI

    NR1401

    DSP

    NR1161

    6.2.2 ECT/EVT (For reference only)

    MO

    N m

    od

    ule

    DS

    P m

    od

    ule

    PW

    R m

    od

    ule

    01 04 05 06 07 00

    AI

    mo

    du

    le

    BI

    mo

    du

    le

    BO

    mo

    du

    le

    Slot No.02 03 08 09 10 11 12 13 14 15

    NR1301

    BO

    mo

    du

    le

    BO

    mo

    du

    le

    NR1521ANR1503NR1102 NR1401 NR1161 NR1521C NR1521B

    The following typical wiring is given based on above hardware configuration.

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-7 Date: 2011-08-02

    SV from

    ECT/EVT

    RX

    0225

    0010

    0011

    0001

    0002

    0003

    BO_FAIL

    BO_ALM

    0004

    0005

    0006

    BO_FAIL

    BO_ALM

    0007

    0008

    0012

    Power

    Supply

    PWR+

    PWR-

    OPTO+

    OPTO-

    External DC power

    supply

    Power supply for

    opto-coupler (24V)

    COM

    COM

    Multiplex

    RJ45 (Front)

    Grounding

    Bus

    0801

    0802

    +BI_01

    -

    PT

    INT

    ER

    0101

    0102

    0103

    0105

    0106

    0107SGND

    RTS

    TXD

    SYN+

    SYN-

    SGND

    Clo

    ck S

    YN

    PR

    INT

    0104

    0101

    0102

    0103

    485-1A

    485-1B

    SGND

    CO

    M

    0104

    1101

    1102

    1103

    1104

    1105

    1106

    1121

    1122

    1201

    1202

    1203

    1204

    1205

    1206

    1221

    1222

    BO_01

    BO_02

    BO_03

    BO_11

    BO_01

    BO_02

    BO_03

    BO_11

    Co

    ntro

    lled

    by fa

    ult d

    ete

    cto

    r

    ele

    me

    nt

    Sig

    na

    l Bin

    ary

    Ou

    tpu

    t (op

    tion

    )

    0803

    0804

    +BI_02

    -

    0805

    0806

    +BI_03

    -

    0821

    0822

    +BI_11

    -

    Phase A

    Phase B

    Phase C

    MU

    TX

    FO

    inte

    rface

    for S

    V c

    ha

    nn

    el

    Up

    to 8

    (LC

    Typ

    e)

    IRIG-B

    *BI p

    lug

    -in m

    od

    ule

    ca

    n b

    e c

    om

    mo

    n n

    eg

    ativ

    e

    term

    ina

    l

    To

    the

    scre

    en

    of o

    the

    r co

    axia

    l

    ca

    ble

    with

    sin

    gle

    po

    int e

    arth

    ing

    Figure 6.2-2 Typical wiring of PCS-924 (ECT/EVT)

    PCS-924 ECT/EVT, GOOSE binary output and binary output

    01

    NR1301

    PWR

    09080705040302 001312

    NR1102

    DSP BIMON

    06 10 11 14 15Slot No.

    Module ID

    NET-

    DSP

    NR1136 NR1504NR1161

    PCS-924 ECT/EVT, conventional binary output and binary output

    01

    NR1301

    PWR

    09080705040302 001312

    NR1102

    DSP BOBIMON BO BO

    06 10 11 14 15Slot No.

    Module ID

    NET-

    DSP

    NR1136 NR1521NR1504NR1161 NR1521 NR1521 NR1521

    BOBI

    NR1504

    In the protection system adopting electronic current and voltage transformer (ECT/EVT), the

    merging unit will merge the sample data from ECT/EVT, and then send it to the device through

  • 6 Hardware

    PCS-924 Stub Differential Relay 6-8 Date: 2011-08-02

    multi-mode optical fibre. DSP module receives the data from merging unit through the optical-fi