06-08 november'15_fault notifications
DESCRIPTION
sadasdasdasdasdasdasdasdasdasTRANSCRIPT
-
Fault NotificationsDate: 8-Nov-15
Santa Rita
FN No. Code Designation Fault Measures Repair note Sub status Priority Assigned toMechanical
2319 00USX FOAM PREP STA Please rectify Within 1 Week
C&I
2320 20MBP33CF101 GAS FLOW IND SENSOR Under investigation Immediate LLAGAS RA
Electrical2321 10UBA63 U10 460/230V AC PCC Busted flourescent light for replacement Within 1 Week
2318 20BZL03GW021 LIGHTING PANEL For bulb replacement Within 1 Week
2317 40SAC63AH081 For checking Within 2 days
San Lorezo
FN No. Code Designation Fault Measures Repair note Sub status Priority Assigned toMechanical
962 50PAB31AA301 CONDR DP I-V For rectification Next opportune outage TEY HM
C&I
964 01GMB10CL001 OIL SEP WTR LVL For checking Under investigation Within 2 days
963 50MBN12CF001 FLOW TRMTR U/STR PMP1 For checking Under investigation Within 1 Week PANUNCILLON MP
965 50MBQ10CP001 PRES IGN GAS TNK For checking Under investigation Within 1 Week ALAMANO RB
961 60MBN60CP512 PG LEAKG PMP2 DIS Gauge pointer is damage / not in place. For replacement. Under investigation Within 1 Week ADELANTAR JH
959 60PGB40AA002 CCW SYST FIL VLV Torque open fault during opening of the valve. For checking. Under investigation Within 1 Week ALAMANO RB
Electrical
960 60BAA02 H2 VENT CUBICLE For checking. Immediate
Note: Items in Red are critical items.
Date: 7-Nov-15
Santa Rita
FN No. Code Designation Fault Measures Repair note Sub status Priority Assigned toMechanical
2313 00PUS03AP001 SWF PMP A Oil leak at pump DE side. For rectification Immediate TEY HM
2314 40LBF10AP002 MAIN PMP 2 For checking Immediate CRUZ ALEX G DE LA
Electrical
2316 00BZL11GP001 For replacement. Within 1 Week
2315 00EKT FUEL GAS HEATING SYST For checking Immediate
00USX control room wrong door lock installation, door cannot be lock from outside.
Pilot Gas Flow < Min alarm active, actual pilot flow is 0.71kg/sec at base load operation.
Please check/adjustNote: C&I informed.
Busted 2 pieces flourescent lamp at LCM area.
40UBA63/64 AIR CON UNIT 1
Air con no cooling effect, valid also to 40SAC64AH083
50PAB31AA301 upstream flange is leaking (continuous droplets)
"01GMB00CL081 Separator Oil Tank Level High" alarm is active at ASD but actual level is
low.
"FO U/STR INJ PMP 1 TOO HIGH" alarm is coming and going. 50MBN12CF001 >Min
signal faulty.
Ignition Gas Pressure Low alarm active at ASD but at the local pressure is 12 bar
60BAA02GH001A H2 VENTILATION FAULT alarm active at ASD.
Unusual sound at HP bypass pump 2 during running.
NOR/EMERG LITG PNL-00UYE
Busted lamp at post 00BZL11GP001 near sliding gate at Gate 1
Air con at 00EKTcontrol room no cooling effect.
-
San Lorenzo
FN No. Code Designation Fault Measures Repair note Sub status Priority Assigned toMechanical
955 50LBA10AA001 HP MAIN STM S/O-V For checking/investigation & repair Scheduled Within 1 Week CRUZ ALEX G DE LA
958 50LBB40AA601 HRH STM SAMP I-V Damaged insulation & cladding. For repair Immediate CRUZ ALEX G DE LA
957 50LBF10AA151 HP RED STN CTRL-V For re-installation. Immediate CRUZ ALEX G DE LA
C&I
956 50HAD50CL001 IP DRM LEVEL 1 For checking of impulse line Under monitoring Immediate MACALALAD MC
953 50MBN23AA501 FO PREM UNLOADING V For rectification. Work completed Immediate MACALALAD MC
954 50QUB32AA010 HP MS SAMP SOL-V Please check and rectify Under investigation Within 2 weeks PEREZ SM
Note: Items in Red are critical items.
Date: 6-Nov-15
Santa Rita
FN No. Code Designation Fault Measures Repair note Sub status Priority Assigned toMechanical
2311 00SCA11AT002 OIL SEP/RCVR Duplicate FN Within 1 Week TEY HM
Mechanical
2310 40CYE FIRE & GAS DETECTION For checking. Under investigation Within 1 Week CORTUNA WP
2309 40CYZ01CB010 40 GD-10 with 2% indication at mimic panel. For calibration checking. Under investigation Within 1 Week CORTUNA WP
Mechanical
2308 40MAW20CT002A TEMP SEAL STM For checking Within 1 Week BAUTISTA JE
Note: Items in Red are critical items.
San Lorenzo
FN No. Code Designation Fault Measures Repair note Sub status Priority Assigned toMechanical
952 50MB GAS TURBINE For retightening. Immediate LACSAMANA EA
Crack weld joint upstream pipe connection of main steam valve, experience after unit
shutdown on 7 Nov @ 0620H.
>>During investigation, cracked also noticed at the valve downstrean welding connection.
Picture attached.
Pipe support move from its original position located upstream of HP bypass valve
50LBF10AA151.
IP drum level 2 of 3 fault, check at the ES and found CL001 @ 432mm, CL002 @ 338 &
CL003 @ 570 mm level.venting of impulse lines of CL001 and CL002 was done, CL003 has a correct
reading. for monitoring . (mike) 7Nov15
Excessive air leak at breather of solenoid valve.
5/2 way valve was replaced, no more leak on the breather. (mike/rolly/tawin) 7 Nov15
Valve cannot be reset/opened even if the water sample temperature is way below limit
of 50 deg C.
Oil leak observed from 00SCA11AT002, set air compressor to last priority.
(Leak at outlet oil sep receiver conn. fittings of braided hose). See attached photo.
for oil filter replacement -- Onieduplicate FN, see FN 1902/2015 with WO
7026, status 5 -- Onie 11/06/2015)
Trouble in 2-7 UBA 63-64 SUB-STRUCTURE, Input Device Not Responding and 2-35 HEAT
DET. ULA,Input Device Not Responding active at MXL panel.
GAS DET GT EXH AIR DUCT TURB SIDE LEFT
40MAW20CT002A Temperature Seal Steam Channel Fault active at ASD.
Gas leak observed on premix gas burner fittings on burner 22.
-
950 50MBP33AA401 PG DRN VLV 1 To be rectified. Immediate LACSAMANA EA
948 50PCB11AP001 SCW BOOSTER PUMP Replace the faulty vent valve. Reviewed Within 1 Week USON SL
Mechanical
946 01GCK80CQ001 AN OUT COND REC Please check and calibrate the transmitter. Under investigation Within 1 Week CORTUNA WP
951 50MBM13CR101 FLAME MON 1 Flame Monitoring 1 too erratic during start up. For checking. Under investigation Immediate BARRION RM
949 50MBP40AA501 TNK VENT VLV To be checked. Work completed Immediate ALAMANO RB
947 50MBU36AA151 EMULSION WTR CTRL-V for replecement Work completed Within 1 Week QUESADA NK
835 60PCB10CP001 SCW FLTR DP Low DP reading at the CCR. To be checked. In progress Within 2 days CORTUNA WPMechanical
945 50MBM12GT013 IGNTR For checking. Immediate MENDOZA MJ
Note: Items in Red are critical items.
Valve stuck up. Failed to open and close command as found during C&I
troubleshooting.
[50 - Equipment Fault] 50PCB11AP001 pump casing vent valve is passing.
replaced with new spare valve w/locking device. done. FN can be closed `11/06/2015 -- Oel
Anion exchanger outlet water conductivity transmitter is giving incorrect value/reading of
1.584 uS/cm compared to portable conductivity meter of 0.06 uS/cm. Suspected transmitter is out of calibration.Reoccouring
fault.
Tank vent valve SENS FLT due to 50MBP40CG501H feedback open not
achieved.The proximity switch was damaged/broken. Replacement done and function
test. FN can be closed. 6Nov15
The valve position indication in the flight recorder was found fluctuating. This is an
indication of defective baluff position transmitter.
No sparks on burner igniter # 13 as reported by Electrical Dept. during ignition test.
Sheet1