1EENG 224
Chapter 11AC Power Analysis
Huseyin BilgekulEeng224 Circuit Theory II
Department of Electrical and Electronic Engineering Eastern Mediterranean University
Chapter Objectives: Know the difference between instantaneous power and average
power Learn the AC version of maximum power transfer theorem Learn about the concepts of effective or Rms value Learn about the complex power, apparent power and power
factor Understand the principle of conservation of AC power Learn about power factor correction
2EENG 224
Power Factor Correction The design of any power transmission system is very sensitive to the magnitude of the
current in the lines as determined by the applied loads.
Increased currents result in increased power losses (by a squared factor since P = I2R) in the transmission lines due to the resistance of the lines.
Heavier currents also require larger conductors, increasing the amount of copper needed for the system, and they require increased generating capacities by the utility company.
Since the line voltage of a transmission system is fixed, the apparent power is directly related to the current level.
In turn, the smaller the net apparent power, the smaller the current drawn from the supply. Minimum current is therefore drawn from a supply when S = P and QT = 0.
The process of introducing reactive elements to bring the power factor closer to unity is called power-factor correction. Since most loads are inductive, the process normally involves introducing elements with capacitive terminal characteristics having the sole purpose of improving the power factor.
3EENG 224
Power Factor Correction
Original Inductive Load Inductive Load with improved power factor correction
Effect of capacitor on total current Power triangle of power factor correction
Increasing the power factor without altering the voltage or current to the load is called Power Factor Correction
4EENG 224
Power Factor Correction
Qc = Q1 – Q2
= P (tan θ1 - tan θ2)
= ωCVrms2
P = S1 cos θ1 Q2 = P tan θ2
c 1 22 2rms rms
Q P (tan θ tan θ )C
ωV ω V
Q1 = S1 sin θ1 = P tan θ1
Increasing the power factor without altering the voltage or current to the load is called Power Factor Correction.
5EENG 224
Power Factor Correction The process of increasing the power factor without altering the voltage or current to the original load is called power factor correction.
Power factor correction is necessary for economic reasons.
1 2
1 1 1 1 1 1 2 2
Real power stays same
cos sin tan ta
n
P P P
P S Q S P Q P
1 2 1 2(tan tan )CQ Q Q P
1 22 2
(tan tan )C
rms rms
Q PC
V V
2rms
L
VL
Q
• The capacitance value needed to change the pf angle from 1 to 2 .
• Similarly the inductance value needed to change the pf angle from 1 to 2 for a capacitive load.
6EENG 224
Power Factor
Correction
7EENG 224
Power Factor
Correction
8EENG 224
Power Factor Correction
9EENG 224
Practice Problem 11.15: Find the value of the capacitance needed to correct a load of 140 kVAR at 0.85 lagging pf to unity pf. The load is supplied by a 110 Volt (rms), 60 Hz line.
10EENG 224
Wattmeter is the instrument for measuring the average power. Two coils are used, the high impedance Voltage coil and the low impedance Current coil. Wattmeter measures the average power given by:
ApplicationsPower Measurement
Wattmeter Wattmeter connected to the load
12 cos( ) cos( )m m v i Rms Rms v iP V I V I
11EENG 224
12EENG 224
13EENG 224
Problem 11-74