1.1 introduction - shodhgangashodhganga.inflibnet.ac.in/bitstream/10603/19842/8/08_chapter 1.pdf ·...
TRANSCRIPT
1
CHAPTER-I
INTRODUCTION
1.1 INTRODUCTION
The increasing demand for electricity and the growing energy
demand in metropolitan cities have made it necessary to extend the
existing high voltage network right up to the consumer. During the
last two decades for reliable power supply and economic advantages
[1], Gas Insulated Substation (GIS) have found a broad range of
application in power systems, because of their high reliability, easy
maintenance, small space requirement etc. In our country, a good
number of GIS units have been in operation and a large number of
units are under various stages of installations. GIS is based on the
principal of operation of complete enclosure of all energized or live
parts in a metallic encapsulation, which shields them from the
external environment. Compressed Sulphur Hexafluoride (SF6) gas,
which has excellent electrical properties, is employed on the insulating
medium between the encapsulation and the energized part. GIS have
a grounded outer sheath enclosing the high voltage conductor.
Gas Insulated Substation comprises the following components-
circuit breakers, isolator, disconnector switch, earthing switch,
current transformers, voltage transformers, Busbars and connectors,
power transformers, surge arrestors, cable termination, Gas supplying
and Gas monitor equipment, Density meters and Local meters.
2
It can be observed from the literature that GIS sub-station posses the
following advantageous features [2-5]
� GIS station occupies only about 10% of the space required by
conventional air insulated substation.
� GIS can be installed either underground or indoors and in
heavily populated areas.
� GIS are also conveniently used in coastal areas and industrial
and urban locations where space and pollution are the main
considerations.
� These substations are generally located closer to the load
centres there by reducing the losses in transmission and
distribution network.
� GIS systems are immune at atmospheric condition and
pollution, the outages get reduced and coupled with their
measured reliability, and the overall maintenance costs are
minimized.
� High service reliability due to non-exposure of high voltage parts
to atmospheric influences.
Disadvantages of GIS
Although GIS has been in operation for several years, a lot of
problems encountered in practice need full understanding. Some of
the problems being studied are:
3
� Switching operation generate Very Fast Transient over Voltages
(VFTO).
� Prolonged arcing may produce corrective/toxic by-products.
� Partial discharges within the enclosures can cause break
downs.
� Metallic particle contamination.
� Transient electric field and transient magnetic fields.
� Field non-uniformities reduce withstanding levels of GIS.
In general, spacers are used to isolate different sections.
Spacers are either cone (or) disc shaped of large majority of spacers
are using alumina filled epoxy. Epoxy support spacers in GIS have
been highly reliable. Spacer insulation is the single most critical
component for the dielectric performance of GIS units. In modern GIS
design, internal stresses below 4kV/mm (rms) are used. The
requirements on GIS insulators are many and they must be able to
[6-8].
� Withstand the high internal and surface electric fields, typically
up to 4.0kV/mm (rms) for continuous operation.
� Withstand forces during transportation.
� Withstand short circuit forces.
� They must be made of a non-tracking material, so that no
conducting tracks occur during testing.
� Must be relatively insensitive to surface contamination.
4
If it is a gas tight insulator, it must withstand a test pressure of
3.25 times the maximum working pressure and should be leak tight
so that not more than 0.5% of gas is lost per year. In a GIS, the
insulating media employed are the SF6 gas and the solid insulating
supports. The behavior of the insulating system depends on the basic
properties of the gas and the surface and volume properties of the
solid insulators. Spacers acquire charge from corona sources,
ionization in the gas and discharges from metallic particles.
Discharges from metallic particles and spacers together give the
lowest breakdown voltage. In recent years, there has been an
emphasis on the long term reliability of the epoxy spacers.
Moving particles give rise to both partial discharges and acoustic
signals. Particles can attach to spacer surface and can cause flashover
of the spacer. Forced services outages caused by spacer problems are
mainly due to excessive operating stresses.
The main types of defects that occur in GIS are free particles
and protrusions on electrode surfaces in the gas medium, surface
contamination by gas impurities and defects within the bulk of the
solid material. The above defects when present, give rise to local field
enhancements, which cause flashovers. If the field enhancements are
small, then there will only be streamer corona without any leader
development leading to breakdown. These corona discharges
chemically react with solid insulating spacers and modify their
5
properties. When the applied voltage is further increased, the steamer
corona transforms into a leader discharge and the leader growth will
then be influenced by the space charges due to corona stabilization
under the application of slowly rising a.c or switching impulse
voltages. Breakdown occurs after the time that is necessary for the
leader propagation and voltage collapse. The time will be longer under
the application of steeply rising impulses (rise times lower than a few
microseconds) leading to higher breakdown voltages. Therefore, there
is a minimum voltage at which breakdown occurs under the
application of such fast rising impulses.
The defects in the SF6 gas used in the GIS include free floating
particles [9, 10] and metallic protrusions on electrode surfaces.
These particles can give rise to partial discharges in the vicinity of the
high voltage conductors. Free metallic particles on the electrodes get
charged and can traverse the complete gap in the case of a.c voltage
and the extent of this motion depends on the size of the particles,
their weight and the magnitude of the a.c field. During the motion of
the particles, charge exchange occurs by sparking before they hit the
surface.
The main defects include particles and flashover tracks on the
insulation surfaces as well as surface contamination while cracks and
voids within the bulk of the insulation can also cause problems.
Metallic and other particles can be sticking to the insulator surface,
6
and they behave like protrusions on the electrode surfaces. The
breakdown voltage when particles are present will depend on the
tangential field on insulator surface, the field enhancement due to the
particles themselves, and the surface charges caused by earlier partial
discharges. These particles are considered to adhere to the insulator
surface at critical areas where they get charged by partial discharges
and move into low stress areas until the partial discharges extinguish.
These partial discharges give rise to surface tracks and reduce the
insulator surface resistance. Due to partial discharges or flashovers
during testing, the solid insulating material will be carbonized due to
the high temperature of the spark resulting in conducting track. A
track can be formed by the energy of single flashover or by successive
flashovers at same location.
These tracks from leakage paths eroding the insulator surface
over a period of time. Gaseous impurities and SF6 products also
contaminate insulator surface. Air, N2 and lower compounds of SF6 up
to 10% were found to have only a minimum effect on the dielectric
properties of SF6 gas. During the operation of GIS, SF6 decomposition
products are formed and the spacer should have adequate resistance
to these decomposition products. All GIS units in service use cast
epoxy spacers. In order to avoid the interface problem, where voids or
small gas gaps can initiate volume puncture or surface flashover, the
spacers are either cast directly on to the conductor or on to metal
inserts[11,12], or have the interface well shielded. Decomposition
7
products of SF6 gas due to the partial discharges [13] and
disconnector switching are also observed to have no significant effect
but the main contaminant that effects the dielectric integrity is the
moisture in the gas. Moisture can be condensed on the insulator
surface and at the ambient temperature it can cause dew formation
on the insulator surface. A dew point of -5˚C is considered safe to
ensure that no harmful condensation of moisture in liquid form gets
deposited on the insulator surface.
Within the GIS, non-uniform fields are always present due to
the presence of dust, floating metallic particles, fixed particles in the
form of electrode surface roughness, condensation of moisture on the
insulator surfaces, etc.
The insulation strength of compressed SF6 is greatly decreased
by contamination in the form of conducting particles. Electrical
insulation performance of GIS systems is adversely affected by
metallic particle contamination. The accumulated field experience
indicates that sources for such contamination are mechanical
abrasions, movement of conductors under load cycling and vibrations
during shipment and service [14]. These particles may be free to move
in the electrical field or may be fixed to the conductors thus
enhancing local surface fields. In a horizontal co-axial system with the
particles resting on the inside surface of the enclosure the motion of
such particle is random in nature. The dynamics of wire particles in a
8
horizontal co-axial system are studied because they approximately
correspond to the type of particles encountered in practice.
Another important source of field non-uniformity within the GIS
is sharp points or mechanical edges. These defects are often of minor
importance under normal power frequency voltages. However, steep
fronted impulse voltages such as lightning, impulse or very fast
transients can significantly decrease the di-electric strength of GIS
assembly in the presence of these particles. Good design and the
adoption of quality assurance methods at all levels will enable the GIS
manufacture to limit the quantity and size of any residual particles in
a modern GIS to insignificant levels. Although the likelihood of particle
effects in GIS is very small, it still does exists, which is why research
is in progress to develop diagnostic and analytical methods for
detecting and localizing them.
When the shape of the spacer is changed from an annular disc
to a conical disc keeping the thickness at the base constant, the field
around the insulator also changes. The field on the spacer surface
increases when the angle of inclination reduces while the maximum
stress occurs on the surface of the inner conductor covered by the
insulator. A shielding electrode having a suitable shape is used to
avoid this field concentration on the conductor. However, the field
concentration was observed to be zero when an annular disc insulator
is used.
9
In recent years, from the view points of the environment friendly
and efficient power transmission, electric power equipment tends to be
compact and be operated under higher voltage. In a gaseous
insulation system, a solid insulator plays an important role for
mechanical support for holding insulation clearance between high
voltage and low voltage electrodes. In the insulation design of a gas-
solid composite insulation system which is typically included in GIS
and a Gas Insulated Transmission Line (GIL), etc., the insulation
technique in the gas-solid interface heavily becomes important as well
as the insulation both in gas gap and inside the spacer. In the
insulation of a gas-solid interface, various factors of significance are
contamination particles, voids, cracks, E-field intensification at triple
junction and charging on the spacer surface, as well as the electric
field distribution on the spacer surface with a perfectly pure condition.
For these reasons, the spacer insulation in the practical gas insulated
switchgears, are made improved by various techniques, for examples,
controlling the spacer shape, additional shielding electrodes for
relaxation of E-field, and the introduction of thin layer made of a low
conductivity material on the spacer surface. In addition, a lower
permittivity is being applied to the spacer. However, these techniques
lead to the complicated structure of the spacer which limits the
flexibility of the spacer design and increases the manufacturing cost.
In order to overcome the limitations, it is necessary to propose a new
10
concept on the spacers by keeping their simple structure and
configurations.
With a new concept for spacer insulation an application of a
Functionally Graded Material (FGM) which has been developed
originally for the structural material under thermal or mechanical
severe stress in special environment. In electrical applications for us,
the FGM spacer has spatial distribution of dielectric permittivity and
can make the E-field distribution in and around the spacer more
suitable, thus achieving the efficient E-field control by keeping the
simple configuration of the spacer.
1.2 LITERATURE SURVEY
Ibrahim A. Metwally [15] in his research reported that, from the
last two decades, the evolutionary development of GIS has resulted in
higher integration of a number of new technologies to enhance
performance and reliability by reducing defects, having more compact
designs, and reducing maintenance intervals and costs. Incremental
improvements are continuing in interrupter technology, such as self-
extinguishing features at Medium Voltage (MV) and resistance
interruption at Extra and Ultra-High Voltages (EHV and UHV). In
addition, SF6 gas technology for circuit breakers, zinc oxide (ZnO) for
arresters, radio communication for condition monitoring, and a choice
of porcelain or polymer composite for the full range of equipment are
also some of the technologies integrated or innovated by GIS
11
manufacturers in recent years. Recently, ac GIS ratings have reached
up to 1,100kV rated voltage and 50kA (rms) rated short-circuit
breaking current. In addition, 1,200kV ac GIS are going to be visible
very soon. Moreover, 500 kV dc GIS for dc transmission systems have
become available [16].
Epoxy or cast resin solid insulators are used as spacers in GIS.
They represent the weakest points in GIS systems as the electric field
on their surfaces is higher than that in the gas space [17]. Generally,
the higher the operating voltage of GIS, the higher is the failure rate
due to the higher electric field strength. In particular by means of
monitoring and diagnostic systems as about 61% of the Failures could
have been detected PD in compressed SF6 GIS arise from protrusions,
free conducting particles[18], floating components, and bulk
insulation defects (voids). These defects represent about 53% of the
total main failure causes in GIS. Some techniques are used for the
mitigation and control of particle contaminations in GIS are particle
traps, dielectric coating of the electrodes, the use of SF6 gas mixtures,
and the use of FGM as solid spacer with optimizing its profile. The
ultra-high frequency and acoustic emission techniques can be used
for GIS PD monitoring system, dramatic reduction in failure rates can
be achieved when using such systems.
G. Schoffner et al [19] discussed that Gas Insulated
Transmission Lines (GIL) area means of bulk electric power
12
transmission at extra high voltage consists of tubular aluminum
conductors encased in a metallic tube that is filled with a mixture of
SF6 and Nitrogen gases for electrical insulation. Since the first
installation of GIL in 1975, second generation GIL has been developed
that is more economically viable and its design optimized both for
installation and operation. Where GIL is installed in combination with
Gas Insulated Switchgear (GIS), compact solutions can be delivered in
order to supply large amounts of electric power to meet the high
demand of large cities and industry [20]. These new possibilities can
mitigate power flow problems, reduce the risk of failure of electrical
transmission systems and enable the installation of optimum
solutions regarding technical, economical and environmental aspects.
The requirements to installations for high voltage power transmission
and distribution have changed. HIS and GIL as innovative products
offer new possibilities to cope with these new requirements.
Depending on each situation, by a coordinated application of the
different techniques of GIS, HIS, AIS, OHL and GIL the optimum
solution will be provided regarding technical, economical and
environmental aspects [21].
D.I.Yang et al explains that the insulator [22] made in epoxy
resin was widely used in SF6 GCB (Gas Circuit Breaker) and Gas
Insulated Switchgear because it’s electrical and mechanical property
are efficiency. Especially, spacer that was used for supporting the
conductor and gas division in GCB and GIS is regarded as of the
13
important component affected on the lifetime of the power apparatus.
The authors report that two different results obtained in the
development of several type spacers for GIS [23]. Firstly, for the three-
phase spacer of 362kV GIS, they presented the optimal design that
was obtained by electric field analysis and mechanical stress analysis
using commercial program.
N. Giao Trinh et al [24] showed that in Electrostatic-field
optimization of the profile of the gas dielectric interface was studied as
a means of improving the dielectric performance of epoxy spacers. An
optimum disc shaped spacer is defined with a dielectric cone angle of
750, assuming a dielectric constant of the epoxy resin of 5 or higher.
The dielectric performance of the optimum disc shaped spacer is
found to be limited, however, to about 85% of that of the conductor
system without spacer. A new composite-shaped spacer was developed
which combines the advantage of the long leakage distance of a cone
shaped profile with that of the quasi-uniform field distribution of a
disc shaped profile. Tests indicate that a dielectric performance
comparable to that of a conductor system without spacer [25] is
possible with the new composite-shaped spacer. From this profile
optimization study on epoxy spacers for use in compressed
SF6insulated cables, the following conclusions are made [26].
� For simple cone-shaped interfaces, a range of optimal angles
could be defined as a function of the relative dielectric constant
14
εr of epoxy. For practical values of εr, 5 and higher, the optimal
di-electric cone angle ranges from 650 to 800.
� Metal inserts embedded in the epoxy can have a beneficial effect
when located near the metal-epoxy-SF6 junction, since they
artificially reduce the local field intensity at these junctions.
� The best ac performance obtained with the optimum disc-
shaped spacer is about 85% of the intrinsic disc dielectric
performance of the test conductor without spacer at the
nominal operating gas pressure of 0.4 MPa.
J.M. Braun [27] stated that the Bulk failure by electrical treeing
of the solid dielectric in Gas Insulated Switchgear is relatively, the
general deterioration process in a void can be described as follows, “A
high field at the void location and the low dielectric strength of the
contents of voids result in partial discharges in the cavity”. This leads
over time to erosion and enlargement of the cavity and generation of
electrical "tree" channels which eventually bridge the insulation and
cause failure. Partial discharges in epoxy insulation occur when a
combination of a sufficiently high electric field stress and a discharge-
initiating free electron is present in a void. The process depends,
among other parameters, on the gas content within the void [28]. In
modeling partial discharge characteristics within spacers and
decomposition and pressure of gases are found inside the voids are of
prime concern. The gases that could be found are obviously residues
15
of the epoxy curing process and include entrapped air, curing
byproducts, as well as thermal decomposition byproducts.
R. M. Radwan [29] et al describes that the effect of the spacer's
dimensions and its relative permittivity on the total electric field
distribution. These effects will be also outlined for a practical spacer's
shape. The field behavior near the triple Junction has been explained
[30].
� For the spacer's shape, the spacer's thickness has a
considerable effect on the maximum field value on its surface.
The optimum value of this thickness is 0.5p.u.
� The relative permittivity of the spacer's material has a
considerable effect on the field distribution especially around
and near the high voltage and low vo1tage electrodes.
� For a practical spacer's shape, the maximum electric field on
the convex side is about 20% higher than that on the concave
side and they occur at Rx=1.5 and 1.65 p.u. respectively.
� The electric field distribution near the triple junction has a
peculiar behavior. Theoretically, it becomes infinity or zero
depending on the spacer's relative permittivity and the spacer's
inclination angle "�" or in other words the spacer's thickness
"zs.".
J. Jia [31] et al resulted that In GIS, particles near spacer in
GIS tend to cause apparatus faults by leading flashover breakdown
16
along spacer surface. Metal inserted spacer as a method is designed in
purpose to prevent particles from lifting and adhering to spacer. The
author’s showed that, the influence of metal inserted spacer on
particle motion in non-uniform electrical field under DC voltage is
calculated for three type spacers. The results show that metal inserted
spacer has good performance in preventing particle from lifting and
adhering to spacer for disk and ribbed spacer [32]. Also, metal
inserted electrode shows a different influence range on particle motion
for different spacers. The results can be used to analysis AC condition
[33-34] considering the root-mean-square value of voltage.
K. Itaka [35] et al discussed that the Problems concerning local
electric field intensification on a cone-type spacer which is fitted
between flanges in SF6-gas-insulated apparatuses were investigated.
Conventional structures, in which flat surfaces of the spacer come in
contact with rounded corners of the flange, sometimes cause
flashovers at considerably low voltages because of local field
intensification [36]. In the improved structure proposed by the
authors, surface shape of the spacer and contact position are slightly
changed in order to avoid local field intensification. Field calculations
and experiments verified that the improved structure is effective for
actual use. Problems concerning local field intensification on a cone-
type spacer fitted between flanges in SF6-gas insulated apparatus
were investigated. The results are summarized as follows:
17
� The conventional structure sometimes caused flashover at quite
low voltages because of local field intensification.
� It was made clear quantitatively that the above characteristic is
caused since the spacer makes contact with the flange at the
interface between rounded surface and flat surface which has
increased electric stress, and since the small gas gap near the
spacer-flange interface becomes like a wedge.
� An improved structure was designed avoiding these problems.
� The effectiveness of the proposed structure is made clear by
field calculations and experiments. Since these results can be
applied for the design of not only cone-type spacers but also
disc-type spacers, they are significant for the insulation design
of practical gas-insulated apparatuses.
N. Giao Trinhn [37] et al studied that the spacer and a
composite-profile cone, were evaluated in a coaxial conductor 2.5 X 7
cm in diameter under the influence on the V-t characteristics [38] of
the conductor when subjected to repeated applications of impulse
voltages of constant wave shape and increasing magnitude. The
results show that an insulating spacer can reduce the critical
withstand voltage and yield smaller dispersion in the breakdown
voltages. These effects can be minimized by adopting a design that
favors breakdown in the gas rather than along the spacer interface
[39]. The following conclusions are made.
18
� The presence of a spacer results in a reduced withstand voltage
of the conductor, a shorter delay time to breakdown and less
dispersion of the breakdown data.
� The influence is more pronounced under negative polarity and
at higher gas pressures.
� Proper design of the spacer, aimed at preventing breakdowns
developing along the interface, can minimize the effects on the
V-t characteristic of the conductor.
� The influence of the spacer is also more pronounced in a 50%
SF6 - 50% N2 mixture than in pure SF6.
� Insulating spacers were observed to cause a temporary
reduction in the withstand capability of the cable, associated
with electrostatic charging of the insulators.
V.V-Akimov [40] et al stated that DC electric strength of pure
SF6 gaps is almost the same as that for AC ones. However, DC
electrical strength of real insulation systems including support epoxy
spacers is apparently lower than that with AC. One of the major
causes of such phenomena relates with the difference between AC and
DC spacer electric field formation mechanisms. There are free electric
charge accumulation processes on the spacer surface during long-
term DC voltage application [41]. This may lead to substantial
distortion of an initial (capacitive) field distribution near the spacer
surface and as a result to decrease in flashover voltage. In this
19
connection, the design criteria developed for AC spacers are not
enough valid for their using with DC insulation.
0. Farish [42] et al discussed that in compressed-Gas-insulated
equipment, the weakest point in the system is often at the interface
between the gas and the solid spacers used to support the conductors.
The low dielectric strength is attributed to the effects of surface
charges, or to ionization at high-field sites such as the gas electrode-
spacer "triple junction", there have been some studies of surface
charge development under dc stress relatively little is known about
the way charge builds up on a surface and how the surface charge
influences the breakdown process under impulse conditions [43]. In
the present work a study was made of impulse flashover of model
spacers under conditions where:
� Surface charge was allowed to accumulate as a result of
repeated impulse stressing.
� A fault was simulated by introducing an annular gas gap at the
triple junction
� The spacer surface was recharged with a line charge or uniform
charge distribution
� Metal inserts were used to shield the triple junction and move
the high-field site to the mid-gap region.
An important feature of the study was that, in all cases, the
surface charge density was measured before and after each impulse-
20
voltage application, the equipment was designed so that the complete
surface of the spacer, including both triple-junction regions, could be
scanned by a charge probe. For a plain spacer, the response to
impulse stress is determined by conditions at the impulse junction.
For defects of a few tens of microns, discharge activity begins at about
70% of the limiting field strength but the breakdown level is only
slightly affected, with large defects at the cathode triple junction the
onset level is considerably reduced and charge can be deposited over
most of the spacer surface [44]. If charge is allowed to accumulate the
impulse strength can be reduced by as much as 30%. When controlled
charging methods are used to create regions of high charge density
the strength can be as low as 50% of the gas-only value, even for
pressures of 1 bar, with the greatest reduction occurring for
deposition of hetero charge. Inserts can provide effective shielding of
the triple junction. However, they introduce a normal field component
which can attract surface charges. This may be detrimental in a
system in which charges are produced as a result of micro discharge
activity in the gas.
K. Tekletsadik [45] et al discussed about the Breakdown or
flashover arcs in Gas Insulated Systems (GIS) that produce a magnetic
force which influences the path of the arc and has a decisive effect on
the spacer-surface damage experienced during flashovers. A mild-steel
flange and aluminum disc piece were made to hold the test epoxy-
resin spacer and to have an access to take arc photographs in an
21
open-to-air configuration at the open end of the GIS [46-48], with
special spacer-electrode arrangements to study the arc lift off and
push onto the surface during flashover on both sides of the spacer.
The principle of arc dynamics is discussed, along with, experimental
arrangements, results obtained from arc photographs and the effects
of the arc path on spacer-surface damage.
Breakdown and flashover arcs in GIS produce a magnetic force
which influences the motion of the arc. The arc dynamics are found to
have a decisive effect on the spacer-surface damage experienced
during flashovers. A flashover arc can be pushed onto the surface of
the spacer or lifted off the surface depending on which side of the
spacer surface failed. An arc path which is pushed onto the surface
causes more severe surface damage. It should be noted by designers
that there is, in many cases, a strong probability that the current flow
will come from one side of the spacer, and in these cases the spacer
geometry can be modified to allow the magnetic-field effect to lift the
arc away from the surface of the spacer.
Shigemitsu Okabe[49] et al stated that The insulation strength
decreased the most when the lighting impulse voltage was applied to
internal insulation of the spacer, In the experiment in which
alternating current voltage is applied for a long period of time, it was
found that there is no decline in the insulation properties even after
the voltage is applied for the equivalent of 30 years when the electric
22
field intensity is 12kVrms/mm or less although the combination with
the multiple lightning impulse application may bring about damages
to the spacer insulation. The degradation mechanism caused by
generation of micro-pits was also understood through simultaneous
microscopic observation of the surface and of the interface between
the electrode and epoxy.
In order to contribute to high reliability and rational Insulation
design of Gas Insulated Switchgear, V-N characteristics [50] (the
dielectric breakdown voltage vs. number of repetitions of voltage
application characteristics) regarding the internal insulation and
creeping insulation of the epoxy spacer, the main insulating element
of GIS, were obtained against the lightning impulse voltage and the
switching impulse voltage. Further, effects of long-time ac voltage
application on spacer degradation were examined and the following
results were obtained.
� Regarding “V-N characteristics (internal insulation, creeping
insulation)”The gradient “n” of V-N characteristics of the
epoxy spacer internal insulation. The proportional decrease
of dielectric strength was largest when the lightning impulse
was applied to the epoxy spacer internal insulation.
� Micro discharge traces were observed both on an embedded
electrode surface and resin surface on the interface in a
spacer to which impulse voltages were applied repeatedly or
ac voltage was applied for a long time. The generation of the
23
micro-discharge-traces was influenced by the roughness of
the electrode surface and flaking on the electrode interface.
Spacer insulation degradation caused by impulse and ac
voltage application is assumed to lead to erosion due to the
spread of discharge traces when the electric field is
intensified at the micro protrusions and the small areas of
flaking on their tips.
T. Nitta et al [51] observed that various factors controlling the
flashover of solid insulators in pressurized SF6, are reviewed and their
influences in gas insulated systems are discussed from a practical
point of view. Flashover voltage of clean insulator surface is under the
influence of the insulator-metal contact as well as the macroscopic
electric field distortion due to the high dielectric permittivity of solid
insulator. Conducting particles or even fine metal powder can reduce
the flashover voltage. Their effects are strongly dependent on the
position they are located, the size of the insulator and gas pressure.
Humidity of SF6, gas should be strictly governed in SF6, gas insulated
apparatuses, and since the condensation of water can decrease
flashover voltage considerably. Decomposition products of SF6, due to
the arcing in switchgears are deleterious to epoxy insulators [52]
particularly when silica is used as their filler. The decomposition
products decrease the leakage resistance on the insulation surface.
The field strength near positive electrode is enhanced by the
electrolytic effect in the surface conduction layer. In some extreme
24
condition, it initiates tracking on the insulator surface. Some of the
important factors influencing the flash over characteristics on the
surface of solid insulators in compressed SF6 [53].
R. M. Radwan [54] et al stated that the Solid insulating spacers
are one of the critical components affecting reliable performance of
Gas Insulated Systems. The breakdown strength of GIS is strongly
influenced by the roughness of the spacer's surface and defects
produced from improper manufacturing. Also, GIS are likely to be
contaminated with non-conducting and conducting particles,
produced during mechanical abrasion or arcing occurring during
operation of the isolating switches and circuit breakers. The presence
of a conducting particle in a GIS can strongly influence the dielectric
performance of the system. This depends on the type, location and
density of the particles. Studies reported on scaled models and on an
actual spacer with a particle fixed on its surface have revealed drastic
reduction in the system breakdown voltages. Therefore the knowledge
of the electric field intensity around the spacer's defects and
conducting particles on its surface contributes towards better
understanding of its surface flashover phenomenon [55]. The Finite
Element Method has been employed to compute the electric field at
the dielectric interface. It is an efficient technique for solving field
problems. The following conclusions are drawn:
25
� The electric field on the spacer's surfaces is strongly affected by
the presence of surface defects. It may increase to almost 150 %
or 185%from its value without protrusion or depression
respectively.
� There is no noticeable effect of changing the defect’s position on
the electric field intensification; the Defect Field Factor (DFF) is
almost constant at 1.5 and 1.85 for protrusion and depression
respectively.
� The electric field on the spacer's surfaces is also strongly
affected by the presence of conducting particles. It increases at
the particle location on the spacer's surface. It reaches almost
1.3 its normal value for a particle of 2 mm.
� The Particle Field Factor (PFF) is almost constant at 1.15,
wherever the particle is located, for a particle of 1 mm.
� The electric field at the spacer's surface decreases, at the
particle location, with the increase of the vertical elevated
distance of the flying particle, and it is almost negligible when
the particle elevated distance "hp" is 5 times the particle's
diameter.
� For an adhered particle, the electric field reaches almost 3.6 its
normal value for a particle of 2 mm. Also the PFF is almost
constant at 3.6, wherever the particle is located for a particle of
2mm.
26
Hideo Fujinami [56] et al discussed that the Mechanism and
effect of the dc charge accumulation on the surface of solid insulating
support (spacer) have been studied in compressed SF6 gas, using
various cylindrical model spacers [57-59]. The distribution of surface
charge has a close relation with the normal component (gas side) En of
electric field on the spacer surface. The maximum charge density can
be estimated from the condition of En = 0. When voltage is applied in
a polarity opposite to pre-stressed dc, surface charge increases the
maximum field strength in the arrangement, thus resulting in the
reduction of the insulating ability. It is possible to estimate the lowest
flashover voltage due to surface charge only from numerical field
calculations [60]. An anti-charging spacer shaped along electric lines
of force has been proposed and studied. Mechanism and effect of the
dc charge accumulation have been studied in compressed SF6 gas,
using various cylindrical model spacers.
The main conclusions are as follows.
� The surface charge distribution on a spacer has a close relation
with the normal component (gas side) En of the electrical field on
the surface, and is also influenced by the surface roughness.
� Possible causes of surface charge are (a) micro discharge or field
emission from surface projections, (b) motion of dust particles,
and (c) natural ionization of SF6 gas in a prolonged time range.
Charge carriers drift through the gas along electric lines of force
27
up to the maximum charge density on the spacer surface given
by the condition of En = 0.
� Numerically calculated results of maximum charge density
showed good agreement with the experimental values.
� The flashover voltage of a spacer with surface charge can be
estimated by composing the two fields due to the surface charge
and due to the applied voltage without charge. It is possible to
estimate the lowest flashover value that is in the safest side,
only from numerical field calculations.
� An anti-charging spacer profile which has no normal field
component on the surface was proposed and verified
experimentally.
T. Nitta [61] et al stated that a technique to design, fabricate
and test dc gas-insulated switchgear has been developed to apply the
advantages of compressed gas insulation to metal-enclosed HVDC
equipment [62]. Charge accumulation on solid insulators is one of the
fundamental problems which have to be solved in establishing the
design stress for HVDC equipment. The present theory is a review of
the studies which have been performed in the development of a +125
kV HVDC gas-insulated converter station and +500 kV HVDC-GIS.
The properties and mechanisms of surface charging, the optimum
design of the spacer and its breakdown characteristics are
summarized. Problems associated with capacitive probe measurement
of surface charge and a practical solution to obtain the charge
28
distribution on the spacer, are presented. Charge accumulation on
spacers in HVDC gas insulation has been studied as one of two
critical factors in designing the insulators applicable to 550 kV HVDC-
GIS. From the results, the following conclusions have been drawn [63-
65].
� The analytical computation method to evaluate charge
distribution on a conical spacer from the capacitive Outputs has
been developed. At present the method is the only way to
transform the probe measurements into charge densities on the
spacer surface.
� In an industrially clean system, the charge carriers are
transported from the surface of the conductor and the sheath to
the surface of the spacer through the gas phase.
� Negative charges due to field emission from micro protrusions
and/or micro dust attached to the highly stressed parts of the
conductor and the sheath is the source of charged carriers.
� We should design the physical configuration of the spacer and
the electrodes for DC-GIS in such a way that the surface of the
spacer intersects the electric field lines in acute angle as
possible. We should take care to avoid the local enhancement of
the electric stress on the conductor and sheath. This practice is
different from avoiding the sharp edges which have influenced
the insulation design of AC-GIS.
29
� The conical and post spacers which are selected as the optimum
design for HVDC-GIS exhibit satisfactory results even at dc
polarity reversal.
M.M. Morcos [66] et al observed that the use of compressed gas
as the insulating medium has made it possible to use compact
equipment compared to that with air insulation. However, the
compact construction increases the operating field intensity. Sulphur
hexafluoride (SF6,) gas insulation is extremely sensitive to local
increases in electric field, which results from protrusion on electrode,
triple junction (the region where the electrode, insulator and SF6, gas
meet) in compressed gas, the presence of conducting particles in gas
insulation, and the shape of spacers supporting the conductor inside
its grounded casing. The influence of a metallic particle attached to
the spacer is particularly significant in the decrease of the dielectric
strength of the SF6, [67] insulated system. Therefore, for development
of highly reliable compact gas-insulated systems, it is vital to reduce
the effect of metallic particles. The flashover withstand of a gas spacer
interface is a limiting factor in the design and operation of a SF6, gas
insulated system. The surface flashover shows a strong sensitivity to
the metallic particle contamination [68] of the spacer surface. The
particle may cause a flashover at a small fraction of the clean gas gap
breakdown voltage. The particles initiate spacer flashover at low
voltage values, not only for AC and DC voltages, but also for impulse
and oscillating impulse voltages. Therefore, it is reasonable when
30
commissioning a SF6 gas-insulated system to carry out tests with a
voltage wave form for which the particle-contaminated insulation is
more sensitive and/or to use diagnostic measurements in order to
detect the presence of particles.
H.Maekawa [69] al presented that the detecting of Partial
Discharge (PD) in gas insulated switchgear is one of important
monitoring terms. Authors studied the behavior of surge due to PD in
gas insulated switchgear. PD can be detected by catching the
electromagnetic wave radiating from the insulated spacer between
enclosures, because coaxial between central conductor and enclosure
is not completely in insulating spacer part. Antenna can be caught the
electromagnetic wave by catching the several waves from different
propagating paths. In the same time, PD location [70] in GIS can be
estimated. In this system, they have developed and applied to actual
500kV GIS and well performed. In the study, obtained results are
summarized as follows.
� PD in GIS can be detecting by catching the electromagnetic
waves with detecting antenna placed by insulated spacer.
� By finding the arrival timing of signals obtained by each
antenna and calculating the time domain differences among
them, the location of PD can be estimated easily.
D.A. Mansour [71] et al showed that the high reliability, less
maintenance and compact size of Gas Insulated Switchgears have
31
made them the primary choice for many utilities. However, sometimes
insulation defects inside GIS can be a serious threat to safe operation
of GIS and can lead to costly disruption of supply. As insulation
failure usually starts with partial discharge (PD) activity, author’s
investigates the differences in PD characteristics [72] in SF6 gas
among different types of defects. The defect types considered in this
study are particles in a gas gap; particles adhered on a spacer surface
and spacer/electrode detachment. Different experiments were made
for sequential PD measurements [73] using the system of PD-Current
Pulse Waveform Analysis [74] (PD-CPWA). The PD phase
characteristics, PD pulse number and PD current were analyzed for
the different defect types. Also the ratio of voltage increment to phase
increment at the next PD pulse appearance (∆u/∆φ pattern) was
obtained and compared for each defect type. Experimental results
shows that correct identification of defects can be achieved based on
considered PD characteristics. Partial discharge characteristics were
measured and analyzed with a wideband (4 GHz, 20 GS/s) measuring
instrument to identify the type of different defect types inside GIS.
Different electrode setups were built for simulating possible defect
types in GIS. Three types of defects were examined for
spacer/electrode detachment, particles in a gas gap and particles
adhered on a spacer surface.
Naoki Hayakawa [75] et al stated that A metallic particle
appeared in a gas insulated switchgear sometimes adheres on a solid
32
spacer surface. If the adhered metallic particle is exposed to a surge
high voltage, a breakdown (BD) may be induced. Therefore, it is
eagerly demanded to diagnose its risk correctly under the service
voltage by partial discharge (PD) measurement. In his research,
particle-initiated surface PD characteristics were systematically
studied in 0.4 MPa SF6 gas by changing the sizes of particles. PD
inception voltage [76], temporal change of PD current and the PD
pulse number were analyzed in detail. Furthermore, comparing with
PD characteristics of particles in a gas gap, the influence of the solid
insulator on the PD characteristics was clarified. It was found out that
PD characteristics greatly changed with time owing to electric charges
deposited on a spacer surface. PD characteristics of various metallic
particles on the epoxy plate were measured and analyzed using the
ultra-high speed measurement system. Temporal change of PD
characteristics and dependence of PD characteristics on the particle
size is analyzed. The following results are obtained.
� The electric field strength near the metallic particle tip was
intensified extremely when a metallic particle was fixed on the
epoxy plate. And PDIV decreased by about 20 ~ 30%.
� PD didn’t appear in several cycles after the voltage application
even if the applied voltage was much higher than PDIV.
Temporal change of PD characteristics was extremely large
immediately after the voltage application.
33
� PD current increased with the particle diameter. PD pulse
number depended on the particle diameter and time.
Immediately after the voltage application, the PD pulse number
decreased with metallic particle diameter. However, after several
minutes, the PD pulse number started to increase with the
particle diameter.
� Complex PD characteristics of different sizes of particles were
qualitatively explained with the surface charges accumulated on
the epoxy plate near the particle tip.
Hirotaka Muto [77] et al studied that as a mean of diagnosing
partial discharge (PD) signals propagate inside a Gas Insulated
Switchgear, a study for the leakage of electromagnetic waves [78-79]
(EM-waves) emitted from the insulating spacer was implemented. The
EM-waves leaking out from the solid insulator have the resonance
frequencies [80] depend on the spacing between adjacent bolts in the
direction of the flange circumference, because the leakage portion is
the equivalent of a slot antenna. In the present work using an
electromagnetic analysis model which has a simulated spacer on a
concentrically-shaped GIS tank, the output characteristics of the EM-
waves that leaked out from the slit ere analyzed under various
conditions such as the spacing between adjacent bolts the width of
the spacer, the dielectric constant of the spacer and the form of the
flange. Also the actual measurement by the experimental equipment
used to simulate the model was implemented for comparison with the
34
analytical results. Consequently, the optimal specifications of the
sensor and the measurement method used to achieve highly-sensitive
detection for practical use are summarized and proposed as well as
evaluating the effectiveness of the electromagnetic analysis model are
adopted.
Katsumi Kato [81] et al describes that the applicability of the
FGM spacer to gas insulated power equipment. In the FGM spacer,
they gave the spatial distribution of dielectric permittivity to control
the E- field distribution inside and outside the spacer. Firstly, E-field
simulation results when applying the FGM by a finite element method
are presented, in which they show that effective reduction of the
maximum field strength by applying the FGM. Next, a fabrication
technique of the FGM spacer sample with not only step-by-step but
also continuous changes of permittivity [82] is presented by use of
centrifugal force.
Finally, authors proposed the application of FGM as a spacer
material for gas insulated switchgears. The application effectiveness
was verified by numerical simulation and experimental results and
they made continuously changed distribution of permittivity and
controlled it by applying the centrifugal force [83]. They optimized the
fabrication condition for the permittivity distribution and these
fabrication techniques are expected to be extended to future electric
power equipment.
35
Masahiro Hanai [84], et al describes that for the size reduction
and the enhancing reliability of electric power equipment, the electric
field stress around insulators should be considered enough. For the
relaxation of field stress, the application of FGM with spatial
distribution of dielectric permittivity can be an effective solution.
Investigating the applicability of FGM for reducing the electric field
stress on the electrode [85] surface with contact to solid dielectrics,
this was one of the important factors dominating a long-term
reliability of the insulating spacer.
At last they implemented the application of FGM for reducing
the electric field stress on the electrode surface in contact with solid
insulators, which was one of the important factors dominating a long
term insulating property [86] of the solid spacer. The FGM application
effect was verified by numerical simulation of electric field and life
time estimation. They made U-shape permittivity distribution [87] and
controlled it by applying the centrifugal force, their application
duration, author’s made various types of the Y-shape permittivity
distribution. These fabrication techniques [88] are expected to be
extended to the actual application of FGM to the electric power
equipment and estimated a long-term insulation performance for the
fabricated FGM sample and found the significant effect for life time
extension by the application of FGM. Finally, authors verified that
high performance of electrical insulation of solid spacer could be
obtained by a permittivity graded FGM application.
36
Heung-Jin Ju,[89], et al investigated for use as an insulator in
high voltage applications. The FGM was able to relax the electric field
concentration around a high voltage electrode and along gas-insulator
surface. The FGM, spacer the permittivity of which was gradually
changed, exhibited a considerable reduction in the maximum electric
field when compared to a conventional spacer with a uniform
permittivity. It is difficult to apply a gradual permittivity variation in
the FGM spacer to real product processing due to its complicated
shape. Thus, in this work, the electrode shape in gas insulated
switchgear was changed in order to increase the possibility of real
FGM insulator. Consequently, the insulation capability of the
switchgear with the optimally designed FGM spacer [90] can be
efficiently improved.
They implemented to improve the insulation capability
capability of switchgears, an elliptical FGM spacer was proposed. The
electrode shape was modified and optimization of the FGM spacer
configuration was performed. By modifying the electrode shape, the
maximum electric field intensity was slightly reduced [91] and the
electrode structure was simplified. The maximum electric field was
also efficiently reduced through the application of the FGM spacer.
Consequently, the optimal designed elliptical FGM spacer model was
more efficient than the uniform permittivity spacer model in improving
the insulation performance.
37
Hitoshi Okubo [92], et al proposed a new concept for solid
insulation, an application of FGM. By controlling the distribution of
dielectric permittivity inside solid insulators [93], one can achieve the
efficient field control with keeping simple configuration of solid
insulators. In this paper, authors described a computer-aided
optimization technique for the FGM solid insulators. By controlling
the filler particle concentration in the matrix, an optimized field
distribution is obtained.
Authors verified the compact design of gas insulated
equipment, they proposed the application of FGM to the solid spacer.
Firstly, they proposed a computer-aided optimization technique for the
FGM solid insulators. In the optimization process, permittivity
distribution of the FGM solid insulator is sequentially modified for
minimizing the electric field stress in and around FGM solid
insulators. Consequently, they successfully developed the
optimization techniques on permittivity distribution in FGM solid
insulators. Next, in order to verify the optimization efficiency, they
carried out the optimized distributions of permittivity in the cone
spacer calculation model. Finally, they could confirm the significant
effect of FGM application for gas/solid composite insulation system
[94].
Hitoshi Okubo [95], et al describes that the electrical
insulation designs of GIS spacer, they need to control electric field
38
distribution around solid spacer, especially around the triple junction.
For this purpose, they proposed the application of FGM [96], which
has spatial distribution of dielectric permittivity, to the spacer of SF6
GIS. In this, they discussed applicability of FGM with numerical
simulation and fabrication conditions. They firstly investigate the field
control effect of the FGM spacer with a conical shape, by FEM.
Secondly; they fabricated FGM spacer with continuously graded
distribution of permittivity by applying the centrifugal force. As for the
filler material to control permittivity, they selected TiO2 rutile crystal
particle. In order to obtain the optimum permittivity distribution, the
centrifugal forces, their application duration, the diameter distribution
filler particles, volume ratio of filler versus resins and so on were
controlled.
They implemented the compact design of electric power
equipment, author’s proposed the application of FGM to the solid
spacer. As one of the estimations of the applicability to the GIS
spacer, they introduced conical spacer models. Furthermore, in order
to fabricate effective FGM spacer, they made continuously graded
distribution of permittivity and controlled it by applying the
centrifugal force. Finally, they optimized the fabrication condition and
obtained the permittivity gradient from 4.0 to 9.0 by using TiO2
particle filler. These techniques of permittivity distributions are
expected to be applied to future electric power equipment.
39
Summary: The following aspects have been observed from the
Literature cited above,
� GIS have been used as an improvement for several problems,
such as space saving of substations, reliability and safety
installation, maintenance costs and environmental
disturbances.
� The SF6 having many advantages like non-toxic, superior
cooling characteristics, greater dielectric strength and arc-
quenching properties.
� The conventional spacer sometimes caused flashover at quite
low voltages because of local field intensification.
� Conventional spacer having the weakest point in GIS system as
the electric field on their surface is higher than that in the gas
space.
� The failure of the conventional spacer have been detected PD in
compressed SF6 GIS arise from protrusions, free conducting
particles, floating particles and bulk insulation defects(voids).
� GIS systems used cast filled epoxy resins spacers that are cast
in metallic moulds under vaccum and cured under carefully
temperature conditions and this is to ensure that the casting is
free from voids and cracks, and to ensure good adhesion to the
conductor or metal sleeve on which the spacers are cast.
40
� The conductors used in GIS are made of alluminium alloy or
high conducting copper on the other hand, materials used for
enclosure are mild steel, stainless steel or alluminium alloys.
� GIS has to withstand different types of voltage stresses that
occurs in the network such as continous power frequency
voltages, temporary over voltages and transient over voltages.
� In a GIS, the insulating media employed are the SF6 Gas and
the solid insulating support. The behavior of the insulating
system depends on the basic properties of the gas and surface
and the volume properties of the solid insulators.
� The insulation of Gas-solid interface have to consider various
factors like contamination particles, voids, cracks, E-Field
Intensification at triple junction and charging on the spacer
surface.
� The spacer insulation in Gas insulated switchgear are made
improved by various techniques. For example, controlling the
spacer shape additional shielding electrodes for relaxation of E-
Field and the introduction of the thin layer made of a low
conductivity material on the spacer surface. In addition a lower
permittivity material is being applied to the spacer.
� This techniques leads to be complicated structure of the spacer
which limits the flexibility of the spacer design and increases
the manufacturing cost.
41
� A new concept of spacer insulation, an application of a
Functionally Graded Material (FGM) which is developed for the
structural material under thermally or mechanically severe
stress in special environment.
� The application of FGM spacer has spatial distribution of
Dieletric permittivity inside. By the control of the distribution of
dielectric permittivity, it can make the E-Field distribution in
and around the spacer more suitable.
1.3 STATEMENT OF THE PROBLEM
The present and future trend in electric power equipment tends
to be compact and be operated under high voltage. The modular
design of GIS offers a high degree of flexibility to meet layout
requirements of both substation as well as power station switchgear,
making efficient use of available space. GIS technology has reached a
stage of application where wide ranges of GIS equipment up to highest
voltage of 800kV are available with many unique features. In a
gaseous insulation system, a solid insulator (spacers) plays an
important role for mechanical support for holding insulation clearance
between High Voltage (HV) and Low Voltage Electrodes (LV). In the
insulation design of a gas-solid composite insulation system which
typically include in Gas Insulated Switchgears (GIS) and a Gas
Insulated Transmission Line (GIL), etc., the insulation technique in
the gas-solid interface becomes important as well as the insulation
42
both in gas gap and inside the spacer. In the insulation of gas-solid
interface, various factors like, contamination particles, voids, cracks,
E-field intensification at triple junction and charging on the spacer
surface have to be considered. For these reasons, the spacer
insulation in the practical gas insulated switchgears are made
improved by various techniques, for examples, controlling the spacer
shape, additional shielding electrodes for relaxation of E-field, and the
introduction of thin layer made of a low conductivity material on the
spacer surface. In addition, a lower permittivity is being applied to the
spacer. However, these techniques lead to a complicated structure of
the spacer which limits the flexibility of the spacer design and
increases the manufacturing cost. In order to overcome the
limitations, it is necessary to propose a new concept for spacer’s
design which maintains simple structure and configurations, with the
use of FGM application to the solid spacer, the properties of the
insulator can be changed to get the required relative permittivity at
specific location. FGM insulator is proposed for which the permittivity
of the spacer is sequentially modified for minimizing the electric field
stress in and around the FGM insulators.
Mainly, the various types of insulator shapes have been
applied for single phase and three phase systems and the electric
fields contours along the surface of insulator spacers are
obtained for conventional and FGM. The results obtained from the
numerical simulation of various insulator shapes of conventional and
43
FGM have been compared and analyzed. From those results it is
understood that the applicability of the FGM to the solid dielectrics is
for improvement of the electric field stresses.
1.4 MODELLING TECHNIQUE
In the proposed work, in order to determine (estimate) the
critical electric field values, first numerical simulations have been
carried out for various insulator shapes for both single and three
phase GIS systems. The E-field around the surface of insulator along
X-axis and Y-axis has been obtained for various shapes of insulating
spacers. Next, to reduce the critical filed on surface of conductor in
both single phase and three phase GIS systems by using FGM. The
modelling of each material has been discussed in detail. In order to
estimate these stresses for single phase GIS, the dimentions are
considered like outer diameter of the enclosure is 241mm and
thickness is 6.4mm. The outer Diameter of the conductor is 89mm
and thickness is 0.7mm and the materials used for conductor and
enclosure is Aluminum Alloy and for Insulator is Epoxy resin and Gas
is SF6.
For three phase GIS models, the dimentions are considered like
the each phase conductor diameter of the conductor is 89mm, the
diameter of the enclosure is 508mm, the thickness of the enclosure is
6.4mm and the thickness of the conductor is 12.7mm. The materials
used for different geometries are, for conductor and enclosure material
44
it is Aluminum Alloy, for insulator material it is Epoxy resin, and the
Gas used is SF6
The results obtained from the numerical simulation of various
insulator shapes of conventional and functionally graded material
spacers have been compared and analyzed with Finite Element
Method (FEM). From those results the applicability of the FGM to the
solid dielectrics for improvement of the electric stress and the long
term insulation performance in electric power equipment is verified.
1.4.1 Functionally Graded Material (FGM)
The term Functionally Graded Material (FGM) refers to solid
objects or parts that usually consist of multiple materials or
embedded components, that is, they are materially heterogeneous.
The term “heterogeneous object” is defined for those objects with
and/or multiple material objects with clear material domains.
A FGM consists of a material whose properties change from one
surface to another according to a smooth continuous function based
on the position throughout the thickness of the material. Electric
power equipments tend to be compact and then operated under higher
electric field stress. Especially, in gas insulated power equipments
such as GIS, solid insulators play a critical role for electrical
insulation. To improve the insulation performance of solid insulators,
it is needed to control the electric field distribution around the solid
insulators. With a new concept on solid insulators with keeping their
45
simple structure and configuration, the application of FGM with
permittivity distribution to solid spacers for GIS, and made the
fundamental investigation of FGM.
In GIS/GIL designs often use gas tight spacers to separate
different bus compartments. It is preferable to limit the bulk field to
below 4kV/mm (rms). Most spacers are cast, filled epoxy resin
systems. Resins are usually bisphenol A, cycloaliphatic or hydantoin.
Fillers like silica and quartz have been used and are necessary for
good thermal and tracking properties and minimal shrinkage during
casting. The epoxy formulations are, however, proprietary.
Silica/quartz fillers are subject to corrosion damage when SF6 arcing
by-products are present. In the FGM solid insulators, spatial
distributions of relative permittivity are given for the control of the
electric field distribution in and around the solid insulators.
Conventional materials have constant relative permittivity distribution
on the contrary, FGM materials have continuously graded relative
permittivity distribution by the arrangement of filler particles. As a
filler, Al2O3, SiO2 or TiO2 particles are applied with several 10 µm ~
sub µm diameter. In order to relax the stress concentration, the
application of FGM is expected to be effective by giving the suitable
relative permittivity (εr) distribution inside the insulators.
46
1.5 ORGANISATION OF THESIS:
CHAPTER I Presents introduction to Gas Insulated Substations and
the various factors like contamination particles, voids, cracks, E-field
intensification at triple junction and charging on the spacer surface in
GIS are discussed. Since, the spacer insulation in the particle gas
insulated switchgears, are made improved by various techniques for
examples, controlling the spacer shape, additional shielding electrodes
for relaxation of E-field, and the introduction of thin layer made of low
conductivity material on the spacer surface. This chapter verifies the
effects of FGM on the improvement performance by numerical
simulation.
CHAPTER II Presents the statement of problem, introduces the
concept of FGM, main contribution of the thesis and Organization of
the thesis.
CHAPTER III Presents the application FGM and also different
Geometry’s applied for single phase bus duct, the obtained electric
field stress for different insulators along the surface of spacers are
compared and analysed for conventional and FGM spacer is
presented.
CHAPTER IV Presents different Geometry’s applied for three phase
bus duct the obtained electric field stress for different insulators along
the surface of spacers are compared and analysed for conventional
and FGM spacer is presented.
47
.CHAPTER V Presents the conclusions of the proposed research work.
The future scope of this work is also discussed.
1.6 SUMMARY
The statement of the problem formulation has been done and
the contributions of the proposed research work have been given in
detailed. Moreover, the organization of the thesis has been given in
this chapter.