12 - hvac design brief
TRANSCRIPT
-
7/29/2019 12 - HVAC Design Brief
1/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects1 Entask Consultancy Services (P) Ltd.
COMMERCIAL COMPLEX @ SARJAPUR ROAD, BANGALORE
HVAC DESIGN BRIEF
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
2/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects2 Entask Consultancy Services (P) Ltd.
INDEX OF CONTENTS
SL.NO. DESCRIPTION PAGE NUMBER
5.0 HVAC
5.1 GENERAL 3
5.2 SCOPE OF HVAC WORKS 4 - 5
5.3 DESIGN CRITERIA AND DESCRIPTION 6
5.4 CODES AND STANDARDS 7 9
5.5 HVAC DESIGN CONDITIONS 10
5.6 PROJECTED HVAC REQUIREMENT 11
5.7 EQUIPMENT DETAILS 12 25
5.8 SCHEMATIC DIAGRAMS 26
5.9 ELECTRICAL LOAD LIST 27
5.10 HEAT LOAD CALCULATION LIST 28 - 29
5.1 GENERAL
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
3/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects3 Entask Consultancy Services (P) Ltd.
THIS DOCUMENT BRIEFS ON THE HVAC SYSTEM ADOPTED FOR COMMERCIAL COMPLEX @ SARJAPUR
ROAD, BANGALORE.
COMMERCIAL COMPLEX is a Commercial Complex Development of built up area of approx. 7.67 lakh
Sq.ft. with three Office blocks, Parking, other common areas and utilities. It is proposed to design
the total infrastructure facility for the schedule of areas.
The schedule of areas is as follows.
SL.NO.
DESCRIPTIONAPPROX.
AREA (Sq. ft)PURPOSE
1 LOWER BASEMENT 287,995.0 Car Parking & STP
2 LOWER BASEMENT 187,995.0 Car Parking
3 UPPER BASEMENT87,995.0 Car Parking
4 GROUND FLOOR 1,10,407.0 Offices, Toilets, Electrical Rooms & Lobby
5 FIRST FLOOR43,710.0 Offices, Toilets, Electrical Rooms & Lobby
6 SECOND FLOOR43,710.0 Offices, Toilets, Electrical Rooms & Lobby
7 THIRD FLOOR43,710.0 Offices, Toilets, Electrical Rooms & Lobby
8 FOURTH FLOOR43,710.0 Offices, Toilets, Electrical Rooms & Lobby
9 FIFTH FLOOR43,710.0 Offices, Toilets, Electrical Rooms & Lobby
10
SIXTH FLOOR 43,710.0 Offices, Toilets, Electrical Rooms & Lobby
11 SEVENTH FLOOR43,710.0 Offices, Toilets, Electrical Rooms & Lobby
12 EIGHTH FLOOR43,710.0 Offices, Toilets, Electrical Rooms & Lobby
13 ROOF43,399.0 HVAC Plant area & Open Terrace
TOTAL AREA7,67,471.0
NOTE: ABOVE TABULATION SUBJECT TO CHANGE BASED ON REVISION OF ARCHITECT DRAWINGS
PROJECT DESIGN BRIEF
COMMERCIAL COMPLEX is a Commercial Complex Development of overall carpet area for air
conditioning works out to be 2.93 lakhs Sq. ft. excluding toilets and common areas like staircases
etc.
5.2 SCOPE OF HVAC DESIGN & WORKS
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
4/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects4 Entask Consultancy Services (P) Ltd.
SCOPE OF HVAC DESIGN
Chilled water central plant design consisting of Hybrid combination of Chillers, Pumpingsystem, Hydronic Pressure maintaining equipments, Chemical dosing system, Condenser cktfor Heat rejection by Cooling towers and to generate Chilled water which can deliver thedesired Airside Temperature of 23+/- 1 DEG C. on the Low side.
Chilled water & Condenser water pumping design with use of Variable frequency drive forSecondary chilled water pumps.
Chilled water, Condenser water & Condensate drain piping network with routing.
Space allocation of AHU and CSU Units for all the Floors showing Scheme Drawing of allusable spaces like OFFICE blocks and etc.
Common area Air Conditioning scheme.
Appropriate Fresh air distribution of to the Office AHUs to maintain Indoor Air quality.
BTU Metering and Tenant Billing system Design for enabling billing for End users based onactual consumptions.
Forced Ventilation system design for Toilets - 16 ACPH and for Sewage Treatment Plant.
Ductless Ventilation system for Basement floors CAR parking @ 04 ACPH for Normal mode,08 ACPH for Pollution mode and 30 ACPH for Fire Modes.
Air Pressurization system for escape routes in the Basement levels - Staircase and Lobby.
IBMS system integration of all HVAC Equipments and Control elements.
SCOPE OF HVAC WORKS
The central Heating, Ventilation and Air-Conditioning (HVAC) system shall comprise of following:
a) HIGH SIDE EQUIPMENTDesign of the equipment based on the data furnished in the document.
Procurement of materials within the battery limits as per the schedule given by Owner /
Project Managers.
Manufacturing as per standards & details furnished in the specifications.
Assembly.
Testing in Shop before delivery.
Inspection.
Insurance up to handing over.
Packing & Forwarding.
Transportation.
Installation at Site as per the schedule given by Owner/ PROJECT MANAGERS.
Submission of method statements for execution.
Commissioning in the presence of specialized agency (manufacturers representative).
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
5/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects5 Entask Consultancy Services (P) Ltd.
Performance Guarantee run.
Handing over.
b) LOW SIDE WORKS
Design of the equipment based on the data furnished in the document.
Procurement of materials within the battery limits as per the schedule given by Owner /
Project Managers.
Manufacturing as per specifications mentioned in the document.
Assembly at Site.
Commissioning.
Testing of all equipment as per the list attached in the document.
Performance Guarantee run.
Handing over.
Supply of various equipment as per the relevant Specification & Drawings, unloading, receiving,inspection, storing, transportation to work site, handling, assembling, cleaning, mechanicalerection, assisting main contractor in associated civil works which are required for ac system,Installation, alignment, testing and commissioning and handing over in working condition of allitems covered in the BOQ.
5.3 DESIGN CRITERIA & DESCRIPTION
FRESH AIR
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
6/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects6 Entask Consultancy Services (P) Ltd.
AS PER ASHRAE 62 N
Ideal air conditioning equipment should sanities cool, heat, humidify/dehumidify, evenlydistribution air through the area and all; cost effectively.
The world focus has shifted from the environment to Invironment. This is a new terminology,
being used increasingly to focus on the Indoor Air Quality (IAQ) and its effect on human health.While the outdoor environment continues to be of concern, the indoor environment is receivingincreased attention as more information has become available on the presence and effect of indoorcontaminants.
ASHRAE 62-1989 IAQ STANDARD:"VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY"
From the above chart it clearly states that 20 cfm / person is the desired rate of fresh air to
maintain good INDOOR AIR QUALITY (IAQ).
DESIGN ASSUMPTIONS
OCCUPANCY - 80 sqft / person on built up area i.e. as perArchitects area summary sheet
FRESH AIR - 20 cfm / person
LIGHTING LOAD - 1.5 watts /sqft
EQUIPMENT LOAD - 225 watts / Computer set
GLAZING - Double Glazing
STP WATERREQUIRED FOR WATERCOOLED CHILLERS - 30 KLD of Make-up water
5.4 CODES & STANDARDS
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
7/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects7 Entask Consultancy Services (P) Ltd.
Basically Air-conditioning system design shall be done as per latest ASHRAE Standards. Also otherapplicable Standards which shall be considered as guidelines are mentioned as under:-
AMERICAN SOCIETY FOR HEATING, AIR CONDITIONING & REFRIGERATION ENGINEERS(ASHRAE)
FRESH AIR AS PER ASHRAE STANDARDS IS WHERE EVER APPLICABLE SMACNA STANDARDS FOR SHEET METAL DUCTING UL STANDARDS FOR FIRE DAMPERS NBC STANDARDS WHERE EVER APPLICABLE ECBC STANDARDS
The installation shall conform in all respects to ASHRPROJECT MANAGERS / Indian Standard Code ofPractice for Air conditioning Installation, tender specifications and drawings.
In case of discrepancy among specifications, drawings and other documents, the specifications take
precedence over all other documents. In case of discrepancy between specification, drawings etc.,& Codes & Standards, the tenderer shall assume the more stringent of the two.
CODES & STANDARDS
Air Conditioning Equipment
IS 659 Safety Code for air conditioning
IS 660 Safety Code for mechanical refrigeration
IS 3615 Glossary of terms used in refrigeration & air conditioning
IS 5111 Testing of refrigeration compressors
IS 7896 Data for outside design conditions for air conditioning
IS 10617 Hermetic Compressors (Part-I, II & III)
IS 11338 Thermostats for use in refrigeration, air conditioners etc.SP 7 National Building Code (Group 4)
IS 3615 Glossary of terms used in refrigeration and air conditioning
IS 7896 Outside design data condition for AC design is for summer months
Noise & Vibration
IS 2264 Preferred frequencies for acoustical measurements.
IS 3483 Code of practice for noise reduction
IS 3932 Sound level meter for general purpose use.
IS 9736 Glossary of terms applicable to acoustics in buildings.
IS 9901 Measurement of sound insulation in buildings & building elements
IS 9876 Guide to the measurement of air borne acoustical noise &
evaluation of its effects on man.IS 10423 Personal sound exposure meter.
IS 11446 Measurement of air borne noise emitted by compressors unitsintended for outdoor use.
IS 12710 Glossary of terms used in acoustic emission testing.
IS 4758 Methods of measurement of noise emitted by machines
IS 14280 Mechanical vibration balancing shaft and fitment keyconvention
IS 12065 Permissible limits of noise level for rotating electrical machines.
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
8/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects8 Entask Consultancy Services (P) Ltd.
Pipe & Fittings
IS 638 Gaskets
IS 1239 Mild steel tubes & fittings
IS 5822 Code of practice laying of electrically welded steel pipes forwater supply.
Pump & Valves
IS 778 Copper alloy gate, globe & check valves for water workspurposes.
IS 4854 Glossary of terms for valves and their parts.
IS 5312 Swing check type non return valves.
IS 8092 Code for inspection of surface quality of steel castings for valves,fittings & other piping components.
IS 12969 Method of test for quality characteristic of valves.
IS 13095 Butterfly valves for general purposes.
Refrigerant Gas & Lubricants
IS 1447 Method of sampling and test for lubricants.
IS 4578 Lubricating oils for refrigeration machinery
IS 10609 Refrigerants
Number
DesignationSheet Metal Works
IS 277 Galvanized Steel sheet
IS 513 Cold rolled low carbon steel sheets.
Thermal Insulation
IS 334 Glossary of terms relating to bitumen & tar
IS 3069 Glossary of terms, symbols & units relating to thermal insulationmaterials
IS 3144 Mineral wool thermal insulation Methods of tests
IS 3346 Method of determination of thermal conductivity of thermalinsulation materials
IS 4671 Expanded polystyrene for thermal insulation purposes
International Standards
SMACNA HVAC Systems Duct Design
SMACNA HVAC Air duct leakage test manual
SMACNA HVAC duct construction standards Metal & flexible
SMACNA Rectangular duct construction
SMACNA Round duct construction
SMACNA Energy conservation guidelines.
SMACNA Energy recovery equipment and systems, air to air
ANSI-UL-555-1985 Fire dampers
ANSI Scheme for identification of piping system
SMACNA HVAC Systems Testing, adjusting & balancing
CTI Acceptance test code for water cooling towers, mechanical draft,natural draft, fan assistant type evaluation of results and thermaltesting of wet and dry cooling towers as per CTI-ATC-105- 1990
CTI Code of measurement of sound from cooling towers as per CTI-ATC-128
ANSI / AMCA Laboratory methods for testing fans for rating as per ANSI / AMCA210
UL Fire dampers as per ANSI-UL-555
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
9/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects9 Entask Consultancy Services (P) Ltd.
ASME Scheme for identification of piping system as per ANSI / ASME A-13.1
Drawings, Specifications and deviations
The drawings and specifications lay down minimum standards of equipment and workmanship.Should the tenderer wish to depart from the provisions of the specifications and drawings either on
account of manufacturing practice or for any other reasons, he should clearly draw attention in histender to the proposed points of departures and submit such complete information, Drawings andspecifications will enable the merits of the deviations to be fully appreciated. In the absence ofany such deviation list, it will be deemed that the tenderer is fully satisfied with the intents of thespecifications and the drawings and their compliance with the statutory provisions and local codes.All deviations or departures not brought out to the notice shall be disregarded.
Units of Measurement
HVAC design documents will generally use inch-Pound (IP) Units. In those instances where both SIand IP units are listed, the IP units take precedence of cooling and heating load calculations andequipment specification. The following listing indicates common application of Units ofMeasurement for HVAC Design Documents.
DUCTWORK SIZE : Millimetres OR Inches
PIPE SIZE : Millimetres OR Inches
AREA : Square feet OR Square meters
VELOCITY : Feet per minute OR Meter per Second
TEMPERATURE : Degrees F OR Degrees C
FAN/DUCT PRESSURE : Pascals (Pa) OR Inches of W.C.
PUMP PRESSURE : Meters OR Feet of Liquid - Water
AIR FLOW RATE : Cubic Feet/Minute - CFM OR Litres/Second - LPSLIQUID FLOW RATE : Gallons/Minute - GPM OR Litres/Second - LPS
5.5 HVAC DESIGN CONDITIONS
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
10/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects10 Entask Consultancy Services (P) Ltd.
INSIDE & OUTSIDE CONDITIONS:
LOCATION:
SITE LOCATION - BANGALORE
GEOGRAPHICAL LOCATION - 12.58 DEG N
ALTITUDE - 921 M ABOVE MEAN SEA LEVEL
The outside and inside conditions for the desired facility shall be designed based on below
mentioned parameters:
INSIDE CONDITIONS:
OFFICE BLOCKS
1) Dry Bulb Temperature - 23 +/- 1 DEG C.
2)Relative Humidity - Less than 60%
The air conditioning system for the Commercial Complex facility shall be designed to cater for the
Comfort cooling application only.
OUTDOOR DESIGN CONDITION:
SUMMER DRY bulb temp 35.6 DEG C WET bulb temp 25.6 DEG C RH-45 %
MONSOON DRY bulb temp 27.8 DEG C WET bulb temp 25.6 DEG C RH -82 %
WINTER DRY bulb temp 14.4 DEG C WET bulb temp 12.2 DEG C RH -78 %
5.6 PROJECTED HVAC REQUIREMENT IN TR
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
11/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects11 Entask Consultancy Services (P) Ltd.
Sl.No.Floor
Reference
Description of
Application
Carpet Area
AC (sq ft)Occupancy
TR as per
HeatloadCFM Fresh Air
Block-A - Office 10,092.9 126 52.86 24,997 2,523
Block-B - Office 9,716.3 121 49.80 23,394 2,429
Block-C - Office 16,043.2 201 81.13 37,952 4,011
Block-A - Office 9,027.6 113 49.48 23,709 2,257
Block-B - Office 8,823.2 110 43.68 20,292 2,206
Block-C - Office 16,043.2 201 82.83 38,999 4,011
Block-A - Office 10,867.6 136 55.61 26,110 2,717
Block-B - Office 8,855.5 111 43.79 20,334 2,214
Block-C - Office 16,710.3 209 85.06 39,870 4,178
Block-A - Office 10,867.6 136 55.61 26,110 2,717
Block-B - Office 8,855.5 111 43.79 20,334 2,214
Block-C - Office 16,710.3 209 85.06 39,870 4,178
Block-A - Office 10,867.6 136 55.61 26,110 2,717
Block-B - Office 8,855.5 111 43.79 20,334 2,214
Block-C - Office 16,710.3 209 85.06 39,870 4,178
Block-A - Office 10,867.6 136 55.61 26,110 2,717
Block-B - Office 8,855.5 111 43.79 20,334 2,214
Block-C - Office 16,710.3 209 85.06 39,870 4,178
Block-A - Office 10,867.6 136 55.61 26,110 2,717
Block-B - Office 8,855.5 111 43.79 20,334 2,214
Block-C - Office 16,710.3 209 85.06 39,870 4,178
Block-A - Office 10,867.6 136 55.61 26,110 2,717
Block-B - Office 8,855.5 111 43.79 20,334 2,214
Block-C - Office 16,710.3 209 85.06 39,870 4,178
9 Eighth Floor Block-A - Office 5,433.8 68 25.01 11,332 1,358
293,780.6 3,672.26 1,491.52 698,561 73,445Grand Total
Sixth Floor7
Seventh Floor8
Third Floor
5 Fourth Floor
Fifth Floor6
SUMMARY OF AC TONNAGE LOADS
PURVANKARA COMMERCIAL COMPLEX PROJECT, SARJAPUR ROAD, BANGALORE
Ground Floor
First Floor
Second Floor
1
2
3
4
The overall AC load estimate works out to be about 1492.0 TRand by applying the diversity, it isproposed to install 1300.0TRof air conditioning plant.
A centralized air conditioning system is proposed with a hybrid combination ofAIR COOLED SCREWCHILLERSof 300TR x 3nos. + 200TR x 2nos. WATER COOLED SCREW CHILLERS with Chilled &Condenser water Pumping system, Hydronic Pressure maintaining equipments, Chemical dosingsystem and Condenser ckt for Heat rejection by Cooling towers.
5.7 EQUIPMENT DETAILS
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
12/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects12 Entask Consultancy Services (P) Ltd.
HVAC SYSTEM PROPOSED
Based on the data furnished in the Design Basis, the air conditioning area for the Building works outabout 2,93,780Sq.ft. excluding toilets and common areas like staircases etc. As such, the capacityof the air conditioning plant required works out to around 1492.0TR. Applying the diversity factorof 0.87, it is proposed to install 1300.0TRof air conditioning plant. A centralized air conditioning
system is planned with a hybrid combination ofAIR COOLED SCREW CHILLERSof 300TR x 3nos. +200TR x 2nos. WATER COOLED SCREW CHILLERS with Chilled & Condenser water Pumpingsystem, Hydronic Pressure maintaining equipments, Chemical dosing system and Condenser cktfor Heat rejection by Cooling towers.
v The chilled water plant consisting of Water cooled chillers system shall utilize treated watergenerated from the STP for make up water requirement.
v The pumping system shall comprise of Primary, Secondary and Condenser water pumps.v Secondary pumping system shall be with Variable speed pumps with VFD application to
save energy during diversified load.
vThe chilled water generated shall be metered by means ofBTU METERS.
v The overall make up water required for Water cooled plant of400TRcapacities is around30 KLD which is fed from the treated STP water.
v The chiller plant shall be placed in the Terrace of the building. The Water cooled chillersand pumping system shall be housed inside a closed roof.
v The reason for a combination ofchillers is as per the loading pattern and difference in DB(Dry bulb) and WB (WET bulb) is very marginal, Hence chillers without VFD are envisaged.
SYSTEM DESCRIPTION
The overall load is generated by Centralized chilled water plant which is housed in the Terrace ofthe building. The chilled water generated shall be distributed to each floor by means of variablespeed pumping system.
The centralized chilled water generation plant consists of the following equipments:
CHILLERS
On-going performance verification of chiller capacity and power input is by means of certifiedcomputerized selection output to assure the owner of specified performance in accordance with thelatest version of ARI Standard 550/590 and EUROVENT STANDARDS.
All chillers that fall within the scope of the certification program have an ARI certification label atno cost to the owner. Equipment covered by the ARI certification program include all water-cooled
centrifugal and screw water chilling packages rated up to 2000 tons (7,000kW) for 60 hertz serviceat ARI standard rating conditions, hermetic or open drive, with electric driven motor not exceeding5000 volts, and Cooling water (not glycol). For 50 hertz application the capacity range covered is200 to 1,000 tons (700 to 3500 kW).
Published certified ratings verified through testing by ARI include:
v Capacity, tons (kW)v Power, kW/ton (COP)v Pressure drops, ft. of water (kPa)
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
13/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects13 Entask Consultancy Services (P) Ltd.
v Integrated Part Load Value (IPLV) or Non-Standard Part Load Value (NPLV)As part of the ARI certification program, ARI has computer selection program used to select and ratechillers. The certified computer program version number and issue date for all manufacturers islisted in the ARI Directory of Certified Applied Air-Conditioning Products available on www.ari.org.ARI Standard 550/590-98 for Centrifugal or Screw Water - Chilling Packages and associated manualsdefine certification and testing procedures and tolerances of all units that fall within the
application rating conditions.
DESIGN PARAMETERS FOR CHILLER SELECTION
The standard rating conditions are:
Leaving chilled water temperature ...........................44FEvaporator waterside field fouling allowance ............0.0001Chilled water flow rate ............................................2.4 gpm/tonEntering condenser water temperature .....................85FCondenser waterside field fouling allowance.............0.00025 (for Water cooled chillers)Condenser water flow rate .....................................3.0 gpm/ton (for Water cooled chillers)
Air cooled screw chiller
Air cooled screw chillers, which are largely used in the comfort cooling industry, the chillerpackage shall consist of compressor-motor units, condenser coils, condenser fans, chiller, receiver,refrigerant piping & fittings, refrigerant feeding devices, valves, strainer, liquid moisture indicator,suction line insulation, first charge of oil & gas, starter panel & Micro-processor panel etc., all thecomponents being mounted on welded steel base frame; the base frame, structural profiles &panels made of galvanized sheet steel (GSS) shall be protected with primary coating & finished
with acrylic paint. The Chillers shall be suitable for outdoor installation; in other words, noweather protection of any kind by way of wall or roof is contemplated. The starter panel shall besuitable for outdoor application & shall confirm IP - 55 grade of protection. The panel shallincorporate main disconnect switches & fuses for individual motors, contactors, over load relays,single phase preventers, under/ over voltage trip, on/off push buttons, auto manual switches tofacilitate automatic operation through DDC System or for manual operation to facility forremote starting & stopping of chiller packages, auxiliary contactors, etc. if any required.
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
14/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects14 Entask Consultancy Services (P) Ltd.
Water cooled screw chiller
Water cooled screw chillers, which are also largely used in the comfort cooling industry, the unitshall be completely factory assembled and wired in a single package complete with screwcompressor(s), cooler, condenser, starting control, safety and operating controls, refrigerant piping& fittings, refrigerant feeding devices, valves, strainer, liquid moisture indicator, suction lineinsulation, first charge of oil & gas, starter panel & Micro-processor panel etc,. The unit shall beconstructed from heavy gauge galvanized steel and steel "C" channel with built-in skid and lifting
holes.
EvaporatorEvaporator shall be direct expansion, shell and tube type. The shell is fabricated from seamlesscarbon steel pipe, with finned copper tubes and tube sheets of heavy gauge carbon steel. Thec o o l e r s h a l l b e i n s u l a t e d w i t h c l o s e d c e l l f o a m e d r u b b e r i n s u l a t i o n .
CondensersCondensers shall be shell and tube type and the condensers shall have removable heads on bothends for tube cleaning and servicing. The condensers shall be leak tested at working pressure andinclude relief valves and purge valves.
CompressorThe overall compressor design shall include a suction cooled motor, integral lubrication systemutilizing compressor pressure differential and semi-hermetic design. The casing is to be constructedfrom a high strength iron casting. An electric crankcase oil heater shall be provided to maintain theproper oil temperature when the system is not in operation.
COOLING TOWER SYSTEM
INDUCED DRAFT CROSS FLOW TYPE COOLING TOWERS WITH LOW NOISE AND CTI APPROVED
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
15/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects15 Entask Consultancy Services (P) Ltd.
DESIGN CRITERIA
Cooling tower thermal performance shall be certified by the Cooling Tower Institute in accordancewith CTI Certification Standards STD-201label at no cost to the owner.
The cooling towers shall be of Cross flow, Induced-draft vertical discharge type, in rectangularsingle or multi-cell configuration complete with Motor, Fan, Hand rails, Ladder and other
accessories etc. and designed with high efficiency drift eliminators to meet current environmentalstandards and guidelines for microbial control. It should be possible to hook up to BMS. Thedistribution system shall be gravity-feed type fitted with removable target nozzle to ensure equalwater distribution over the fills. Drift eliminators shall be efficient enough to effectively limit driftloss to no more than 0.005% of the designed flow rate.
Storage capacity that needs to be planned for make up water should be at least one dayconsumption.
PUMPING SYSTEM
Pump
The chilled water generated by the chiller plant shall be pumped to the respective floor AHUs unitsand load cells by means of secondary pumping system.The Chilled Water Pump Sets shall be back-pull out design fitted with variable frequency drive (VFD)for Secondary system. The pump shall be complete with ribbed cast iron casing, double shroudedsingle entry radial flow bronze impeller, mechanical seal, bearing bracket incorporating 2 nos.roller bearings, shaft, longer coupling, coupling guard, flanged connections for discharge andsuction, purge /air vent/test cocks, etc
Regulatory requirements of Pumps
Conform to Health/Life Safety Code for Public Schools Conform to International Mechanical Code Conform to BOCA National Building Code Conform to BOCA National Fire Protection Code Conform to State of Illinois Plumbing Code Conform to National Electric Code NFPA 70 Conform to Illinois Accessibility Code Conform to applicable ANSI/HI standards Products: Listed and classified by Underwriters Laboratories, Inc. as suitable for the
purpose specified and indicated.
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
16/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects16 Entask Consultancy Services (P) Ltd.
DESIGN REQUIREMENTS
The power ratings of the pump motor shall be larger of the following:
The maximum power required by the pump from zero discharge to zero head. 110% of the power required at the duty point.
Pumps of a particular category shall be identical and shall be suitable for parallel operation withequal load division. Components of identical pumps shall be interchangeable.
Pump Logic Controller (should be fully compatible to hook up to BMS / Chiller Plant ManagementSystem)
The technologic pump logic controller assembly shall be listed by and bear the label ofUnderwriters Laboratory, Inc. (UL)
The Equipment should be able to hook up to chiller plant management system (BMS) viasoftware integration either in ASHRAE Backnet / RTU Modbus Protocol. Necessaryhardware / software for integration should be part of scope.
The controller shall be specifically designed for variable speed pumping applications. The controller shall function to proven program that safeguards against damaging
hydraulic conditions including:
Pump flow surgesHuntingEnd of curveSystem over pressure
The pump logic controller shall be capable of receiving up to two discrete analog inputsfrom zone sensor / transmitter as indicated on the plans. It will then select he analoguesignal that has deviated the greatest amount from its set point. This selected signal willused as the command feedback input for a hydraulic stabilization function to minimizehunting. Each input signal shall be capable of maintaining a different set point value.Controller shall be capable of controlling up to three pumps in parallel.
The pump logic controller shall be capable of accepting an additional analog input for aflow sensor. This input shall serve as the criteria for the end of curve protectionalgorithm.
The pump logic controller shall be self-prompting. All messages shall be displayed inplain English. The operator interface shall have the following features:
a) Multi-fault memory and recall last 10 faults and related operational data.b) Red fault light, yellow warning light and Green power on light.c) Soft-touch membrane keypad switches.
The pump logic controller shall be of a high end type i.e., all the parameters availableon the logic control panel should be able to monitor / controlled from the remotelocation and should housed in a NEMA 1 Enclosure.
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
17/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects17 Entask Consultancy Services (P) Ltd.
The display shall have four lines, with 20 characters on three lines and eight large characters on oneline. Actual pump information shall be displayed indicating pump status.
VARIABLE FREQUENCY DRIVE ENABLED SECONDARY PUMPS have been adopted for PROPOSEDCOMMERCIAL COMPLEX FOR RAMKY.
Secondary pumping would enable Substantial energy savings due to partial load profile during offpeak hours.
Adjustable Frequency Drive
The adjustable frequency drives shall be pulse width modulation (PWM) type,microprocessor controlled design.
VFD Shall is Danfoss VLT 6000 Series / ABB ACH 550 Series only. The AFD, including all factory-installed options, be tested to UL standard 508. The AFD
also meets C-UL and is CE marked and builds to ISO 9001 standards.
The AFD shall be housed in a NEMA 1 enclosure. AFF with plastic enclosure shall not beacceptable.
The AFD shall employ an advanced sine wave approximation and voltage vector control toallow operation at rated motor shaft output speed with no derating. This voltage vector
control shall minimize harmonics to the motor to increase motor efficiency and life.
Power factor shall be near unity regardless of speed or load.
The VFD shall have balanced DC link reactors to minimize power line harmonics. VFDswithout a DC link reactor shall provide a 3 % impedance line reactor.
Input and output power circuit switching can be done without interlocks or damage to theVFD.
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
18/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects18 Entask Consultancy Services (P) Ltd.
BASEMENT DUCTLESS VENTILATION SYSTEM
Car Park Ventilation System for Upper Basement, Lower Basement 1 and 2
Height(m)
Area(m
2)
Volume(m
3)
Upper Basement 3.9 6,783 26,454
Lower Basement 1 3.1 6,894 21,372
Lower Basement 2 2.9 7,283 21,120
Car park details
The car parking comprises of three Basement Floor cars parking with entrance & exit openings.
The fresh air coming from the ramps of the Lower Ground level to the Upper Basement is sufficient.
Incase of Lower Basement 1 and 2 the fresh air from the ramps are not sufficient and hence supplyair fans are required for lower basements 1 and lower basement 2.
The Car Park system if designed for 04 for Normal mode, 08 ACPH for Pollution mode and 30 ACPHfor Emergency mode.
Upper Basement (Air Changes per Hour - ACPH):
Normal Mode : 4 (ACPH) X 26,454 / 1.7 = 62,250 CFMPollution mode : 8 (ACPH) x 26,454 / 1.7 = 1,24,500 CFMFire mode : 30 (ACPH) x 26,454 / 1.7 = 4,66,830 CFM
Lower Basement 1 (Air Changes Per Hour - ACPH):
Normal Mode : 4 (ACPH) X 21,372 / 1.7 = 50,285 CFMPollution mode : 8 (ACPH) x 21,372 / 1.7 = 1,00,570 CFMFire mode : 30 (ACPH) x 21,372 / 1.7 = 3,77,145 CFM
Lower Basement 2 (Air Changes Per Hour - ACPH):
Normal Mode : 4 (ACPH) X 21,120 / 1.7 = 49,700 CFMPollution mode : 8 (ACPH) x 21,120 / 1.7 = 99,400 CFMFire mode : 30 (ACPH) x 21,120 / 1.7 = 3,72,720 CFM
Since the car park is envisaged to have a common extract shaft, we have considered the following.
Extract Fan Selections for Upper Basement, Lower Basement 1 and 2:
We have taken a DIVERSITY FACTOR that fire will happen in Single basement only. Hence, thesystem is designed for Emergency mode in the Largest Basements i.e. 30 ACPH (1st Basement) -4,66,830 CFM which also ensures 8 ACPH during Normal mode in all 3 basements.
No. of Extract shaft : 4 No.No. of Fans in each shaft : 3 NosTotal No. of Extract Fans : 4 x 3 = 12 Nos.Capacity of each Extract fan : 4,66,830 / 12 = 39,000 CFM @ 25 mm WC.
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
19/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects19 Entask Consultancy Services (P) Ltd.
Each Extract Fan Shaft Size : 6 X 2 Metres.For Lower Basement 1:
No. of Supply shaft : 2 Nos.No. of Supply Fans / Shaft : 2 Nos.Total No. of Supply Fans : 2 x 2 = 4 NosCapacity of Supply fan : 20,000 CFM 25 mm WC.
Supply Fan Shaft Cut Out Size : 3.25 X 2 Metres.
For Lower Basement 2:
No. of Supply shaft : 2 Nos.No. of Supply Fans / Shaft : 2 Nos.Total No. of Supply Fans : 2 x 2 = 4 NosCapacity of Supply fan : 20,000 CFM 25 mm WC.Supply Fan Shaft Cut Out Size : 3.25 X 2 Metres.
Jet Fan and Extract Fan System Description:
PPM LevelACPH Jet Fan
Total No. of Extract Fans 12 Nos.
0-25 ppm 4 Off 4 Fans will operate
25 ppm 8 Low Speed 8 Fans will operate
Emergency Mode 30 High Speed All 12 Fans will operate
0-25 ppm: When the CO level in the car park is between 0-25 ppm the Jet Fan are in the Off mode,4 Nos. of Extract fans will be running to achieve 4 ACPH in all 3 Basements.
> 25 ppm: When the CO level in the car park is greater than 25 ppm the Jet Fans will be operatedat Low speed and 8 Nos. of extract fans will be running to achieve 8 ACPH in all 3 Basements.
Emergency mode: During the emergency mode the Jet Fans will be operated at full speed,12 Nos. of extract fans will be running to achieve 30 ACPH in the Basement where smoke is to beremoved quickly.
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
20/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects20 Entask Consultancy Services (P) Ltd.
Extract Fan Selections for Parking Upper Basement, Lower Basement 1 and 2:
Note: The Extract Fans are designed for 300 Degree C for one hour
BEFORE CFD ANALYSIS AFTER CFD ANALYSIS AND JETFANPOSITIONING
Our Ref: TAP/CP/B/2007/ 098 Dt: 06 / 10 / 2007
Units Specifications
Qty. Nos 12
Duty Volume CFM 39,000
Static Pressure mmWC 25
Selected Model HT 125 JM / 40 /6 / 9 / 25
Blower Type Axial Fan
Fan Diameter mm 1250
No of Blades 9
Fan Casing Long
Absorbed Shaft Power KW 10.74
Shaft RPM RPM 960
Recommended High Temperature Motor Single Speed KW 15 KW / 6pole
Sound Level @ 3 Metres Dba 76
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
21/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects21 Entask Consultancy Services (P) Ltd.
Supply Fan Selections Lower Basement 1:
Note: the Supply fans are designed for 50 Degree C
Units SpecificationsQty. Nos 2
Duty Volume CFM 20,000
Static Pressure mmWC 25
Selected Model 100JM / 40 / 6 / 9 / 32
Blower Type Axial Fan
Fan Diameter mm 1000
No of Blades 9
Fan Casing Long
Absorbed Shaft Power KW 5.61
Shaft RPM RPM 960
Recommended Motor Single Speed KW 7.5 KW / 6 Pole
Sound Level @ 3 Metres Dba 71
Sound Level after Silencer Dba 60
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
22/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects22 Entask Consultancy Services (P) Ltd.
Supply Fan Selections Lower Basement 2:
Units SpecificationsQty. Nos 2
Duty Volume CFM 20,000
Static Pressure mmWC 25
Selected Model 100JM / 40 / 6 / 9 / 32
Blower Type Axial Fan
Fan Diameter mm 1000
No of Blades 9
Fan Casing Long
Absorbed Shaft Power KW 5.61
Shaft RPM RPM 960
Recommended Motor Single Speed KW 7.5 KW / 6 Pole
Sound Level @ 3 Metres Dba 71
Sound Level after Silencer Dba 60
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
23/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects23 Entask Consultancy Services (P) Ltd.
SPECIFICATIONS FOR JET FANS
Technical Data / Technical specifications of the JET THRUST FAN UNIT offered
Qty required : Upper Basement+Lower Basement 1+Lower Basement 2 =23+23+24 = 70 Nos.
Jet fans are with silencers & mounting assembly
JETFAN
Sound level is measured at 1.5-meter distance in reference value in parking areas
Note: The jet fans are designed for 300 Degree C for one hour
Overall system description:
The vehicle entrance & exit ramps shall be utilized as the main source of fresh air into the carpark for First Basement.
It is proposed the extract points are located as shown on the marked drawing enclosed to you inseparate mail. The location of these extract points have been chosen to ensure the bestdistribution of the inlet airflow as possible and suitability for a system comprising of Jet Fanunits as per the geometry of the Car Parking Area.
No. Description Unit Technical details
1 Nozzle Dia Mm 350 mm
2 Air Flow M3/sec 0.9/1.8 m3/sec @ 4 / 2 Pole
3 Capacity of Fan Cfm 1905 / 3810 Cfm
4 Tip Velocity m/s 16
5 Phase Ph 3
6 Voltage V 420
7 Frequency Hz 50
8 Revolution RPM 1420 /2840RPM
9 Ampere A 0.63 / 2.38 @ 4 / 2 Pole
10 Sound Level dB (A) 53 / 65 @ 4 / 2 Pole
11 Weight Kg 80
12 Power Consumption KW 0.1 KW / 1.0 KW @ 4 / 2 Pole
13 Rated Motor Power Kw 0.14 KW / 1.1 KW @ 4 / 2 Pole
14 Depth of Unit Mm 455 mm
15 Thrust Nm 8/32
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
24/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects24 Entask Consultancy Services (P) Ltd.
Extract grilles would be located at high level. In case of main power failure the Extract Fans shall be provided with alternate source of power. All of the fans will be controlled via PLC based control panel separately for each Basement. The
logic shall be arrived separately for pollution mode and emergency mode separately. Aninterlink will need to be provided to allow communication between panels and also the BMS.
For the Pollution mode it is proposed that the extract fans in all Basements Floor are operatedto provide 8 ACPH. It is suggested that a Carbon Monoxide (CO) detection system is provided tocontrol the background ventilation rate depending on car park usage and detected levels of CO.Details of a suitable detection head for this application can be provided if required. The type ofdetector that would be recommended is an analogue type detector with a 4-20mA signal. Thiswill allow for detection of varying levels of CO, typically in the ranges 0-30, 30-50, >50 PPMwhere the frequency of supply to the main fans can be adjusted accordingly via the main controlpanel.
Jet Fan units would be installed at ceiling level and positioned accordingly within the car park toprovide the best distribution of the inlet air flow as possible.
The final installed locations of the Jet fans and mode of operation of these fans would bedetermined at the time of the detailed design in which techniques of Computational FluidDynamics (CFD) will be used to model the air movement with the car park. A more detaileddescription of the CFD to be carried out can be provided upon request.
Control equipment:
(8+8+8) 24 Nos. for basement floor On / off type carbon monoxide (CO) detection. With COdetection in place the ventilation system would run on demand during peak periods when there ishighest car park activity. The benefit of this over the conventional approach is ventilating all thetime at 6 ACPH will be seen in reduced operating costs and noise levels.
Incoming electrical supply
Dual Incomer
CO GAS DETECTOR
KEY ELEMENTS OF DESIGN IN VIEW TO ACHIVE ENERGY SAVINGS:
System with combination of Air cooled and Water cooled screw chillers. Chillers with R-134a Eco-friendly Refrigerant gas. Variable speed Pumping to save energy during diversified loads of Offices. Use of IBMS system to run the system efficiently by close monitoring and trends.
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
25/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
Architects25 Entask Consultancy Services (P) Ltd.
ENERGY CONSERVATION AND ENVIRONMENTAL CONCERN
WITH THE INCREASE IN DEMAND OF ENERGY CONSUMPTION, I.E ELECTRICITY, THEAVAILABILTY OF POWER BECOMES A MAJOR CONCERN.
SINCE THE CONSUMPTION OF POWER IS DIRECTLY RELATED TO GENERATION USING FOSSILFUELS, IT
S EVIDENT THAT IT IS HARMFUL TO THE ENVIRONMENT. HENCE THE DESIGN ADOPTED FOR THIS COMMERCIAL COMPLEX IS IN VIEW OF NOT ONLY
ATTAINING MAXIMUM DEMAND POWER FOR HVAC TO BE ECONOMISED, BUT ALSO TO HAVE
ENERGY EFFICIENT SYSTEM.
APPROVED MAKES OF MATERIALS
AIR / WATER COOLED CHILLERS
COOLING TOWERS
AHUS / CSUS / FCUS TFAS
PRIMARY & CONDENSER WATERPUMPS
SECONDARY PUMPS
CLOSED LOOP EXPANSION TANK
AIR SEPERATOR / AUTO AIRVENT
MS PIPE
BUTTERFLY VALVES
PRESSURE INDEPENDENT BALANCINGCUM CONTROL VALVES
Y STRAINER / SUCTION GUIDE
NON RETURN VALVE
PPRESSURE GAUGE & THERMOMETER
RPUF INSULATION
INLINE FANS
GI SHEET
GRILLES & DIFFUSERS / VCD / FIREDAMPER
CLOSED CELL NITRILE RUBBERINSULATION
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22 -
7/29/2019 12 - HVAC Design Brief
26/26
Project: Commercial Complex @ Bangalore HVAC Design Brief
5.8 SCHEMATIC DIAGRAMS
HEAT LOAD SUMMARY
The overall AC load estimate works out to be about 1492.0 TRand by applying the diversity, it isproposed to install 1300.0TRof air conditioning plant.
http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22http://www.pdfcomplete.com/cms/hppl/tabid/108/Default.aspx?r=q8b3uige22