The American University in Cairo
NFPA 45
FIRE PROTECTION FOR LABORATORIES USING
CHEMICALS
![Page 2: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/2.jpg)
Purpose of the Standard
• This standard provides basic requirements for the protection of life and property in laboratory work where hazardous chemicals are handled through prevention and controls of fires and explosions.
• To protect personnel from the effects of toxic, corrosive, or otherwise hazardous chemicals to which they may exposed as a result of fire or explosion.
![Page 3: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/3.jpg)
Definitions
• Educational Occupancies:• Building used for the gathering of 6 or more persons for
the purposes of instruction, such as schools, universities, colleges, and academies.
• Laboratory Unit:• An enclosed space used for experiments or tests. It may
contain one or more separate laboratory work areas.A laboratory unit is classified as A, B, or C according to the quantities of flammable and combustible liquids.
![Page 4: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/4.jpg)
Definitions
• Laboratory Work Area:• A room or space for testing, analysis, research, instruction,
or similar activities that involve the use of chemicals. This work area may or may not be enclosed.
• Hazardous Chemicals:• A chemical with one or more of the following hazard
ratings as defined in NFPA 704, Standard system for the identification of fire hazards of materials. Health-2,3, or 4; Flammability 3 or 4; Reactivity 2, 3, or 4.
![Page 5: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/5.jpg)
Laboratory Unit Fire Hazard Classification
Excl. quant. In cabinets and cans
Excl. quant. In cabinets and cans
Incl.. quant. In cabinets and cans
Incl.. quant. In cabinets and cans
Lab. Unit Class
Flam. Or Comb. Class
Unsprink Sprink. Unsprink Sprink.
Class A High Hazard
I
I, II, and IIIA
300 gal.
400 gal.
600 gal.
800 gal
600 gal.
800 gal.
1200 gal.
1600 gal.
Class B Interm. Hazard
I
I, II, and IIIA
150 gal
200 gal.
300 gal.
400 gal.
300 gal.
400 gal.
600 gal.
800 gal.
Class C Low Hazard
I
I, II, and IIIA
75 gal.
100 gal.
150 gal.
200 gal.
150 gal.
200 gal.
300 gal.
400 gal.
![Page 6: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/6.jpg)
Explosion Hazard Classification
• A laboratory work area shall be considered to contain an explosion hazard if:
• 1- Storage of materials with a reactivity hazard rating of 4.
• 2- Use or formation of materials with reactivity hazard rating of 4.
• 3- Highly exothermic reactions such as polymerizations, oxidations, nitrations, peroxidation, hydrogenation, or organo-metalic reactions.
![Page 7: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/7.jpg)
Construction Notes
• Laboratories will be classified (NFPA 101) as : Business – Health Care, Industrial
• Compartmentation of each laboratory unit is achieved by providing: (One-hour rated separation from adjacent labs or other areas. – Self-closing fire doors with at least ¾ hour rating.
• Two or more exits must be provided for labs of 200 feet area or more.
![Page 8: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/8.jpg)
Continue
• Doors to corridors from laboratories must swing in the direction of exit.
• When central supply of flammable, combustible or oxidizing gases is provided, shut-off valves in accessible locations must be provided, in addition to those at the points of supply and use.
![Page 9: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/9.jpg)
Continue
• Controls for air, gas, and other utilities must be color coded and labeled.
• GFCI on electrical outlets within 6 feet of all sinks.
![Page 10: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/10.jpg)
Laboratory Unit Layout
![Page 11: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/11.jpg)
Fire Protection
• Portable fire extinguishers
• Fire alarm systems
• Evacuation and emergency plans.
• Automatic extinguishing systems (sprinkler system).
• Inside standpipe and hose systems.
![Page 12: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/12.jpg)
Lab Ventilating Systems
• Haz. Chemicals shall not be recirculated.• Location of fresh air intakes – avoid
drawing of hazardous chemicals from labs.• Negative pressure in the labs relative to the
corridors or adjacent non-labs areas.• Location of air supply diffusion devices to
avoid air current (hoods, exhaust system, and fire detection or ext. systems)
![Page 13: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/13.jpg)
Continue
• Min. 6 air change per hour – fume hoods.
• Open use of hazardous chemicals – 10 or more air change per hour.
• Exhaust ducts – negative pressure.
• Hoods air velocity : 80 – 100 fpm
• Local exhaust systems (elephant trunks or snorkels.
![Page 14: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/14.jpg)
Continue
• Exhaust ducts to outside the building – roofs 10 feet above roof level.
• Lab hoods shall be located in areas of minimum air turbulence.
• Lab hoods shall not be located adjacent to a single means of access to an exit or high traffic areas.
![Page 15: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/15.jpg)
Chemical Storage & Disposal
• Hazardous chemicals – minimum necessary• Segregation of incompatible materials.• Dating of the first opening – 6 months
testing and evaluation and disposal.• Class I transference – bonding and
grounding.• Classification of chemical wastes.• No disposal of chemical wastes to the sink.
![Page 16: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/16.jpg)
Maximum Allowable Container Capacity
Flammable Liquids
Flammable Liquids
Flammable Liquids
Combustible Liquids
Combustible Liquids
Container Types
IA IB IC II IIIA
Glass
Metal
Safety Cans
Metal Drums
1 pt
1 gal
2 gal
N/A
1 pt
5 gal
5 gal
5 gal.
1 gal
5 gal
5 gal
5 gal
1 gal
5 gal
5 gal
60 gal
5 gal
5 gal
5 gal
60 gal
![Page 17: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/17.jpg)
Compressed and Liquefied Gases
• Manual shutoff valves at each point of supply and each point of use.
• Permanent piping shall be identified with the name of material.
• Cylinders of gases having health hazard rating of 3 or 4 shall be kept in ventilated hood or other continuously mech. Ventilated enclosure.
![Page 18: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/18.jpg)
Maximum quantity and size limitations for comp. Gas
cylindersFlamm.
Gases and/or oxygen
Flamm. Gases and/or
oxygen
Liquefied flamm. gases
Liquefied flamm. gases
Gases with health
hazards ratings of 3
or 4
Sprinklered Space
Unsprinkl. Space
Sprinklered Space
Unsprinkl. Space
Max. # of cyl. Per 500
ft² or less
Max. Cylnder Size
(inches)
6
10 X 50
3
10 X 50
3
9 X 30
2
9 X 30
3
4 X 15
![Page 19: 14164403-NFPA-45](https://reader036.vdocument.in/reader036/viewer/2022082701/552e52b15503466f768b4969/html5/thumbnails/19.jpg)
Lab Operations and Apparatus
• Automatic shutdown – unattended lab operations.
• Refrigerators or freezers for flam. Substances: Class I, Division 1 locations inside the ref.
• Outside the ref. : Class I, Division 2.• Over-temp shutoff switches for electrically
heated equipment.