Notified Body No: 0833 0249 Title: Reddiplex Acoustic Seals Air Leakage Tests in Accordance with BS 476: Part 31, Section 31.1: 1983, on a Single-Acting, Single-Leaf Doorset WF Report No: 167811/A Prepared for: Reddiplex Limited The Furlong Droitwich Worcestershire WR9 0RJ. Date: 4 th December 2007

Upload: others

Post on 18-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

Notified Body No:

0833

0249

Title:

Reddiplex Acoustic Seals Air Leakage Tests in Accordance with BS 476: Part 31, Section 31.1: 1983, on a Single-Acting, Single-Leaf Doorset

WF Report No:

167811/A

Prepared for:

Reddiplex Limited The Furlong Droitwich Worcestershire WR9 0RJ. Date:

4th December 2007

Page 2: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 2 of 18

Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset

when fitted with a range of smoke seals within the door frame jambs and head, and subjected to a test utilising the test method detailed within BS 476: Part 31, Section 31.1: 1983.

Approved Document B (Fire Safety) of the Building Regulations requires doorsets shall “have a leakage rate not exceeding 3 m3/m/hr (head and jambs only) when tested at 25 Pa under BS 476 Fire tests on building materials and structures, Section 31.1 Methods for measuring smoke penetration through doorsets and shutter assemblies, Method of measurement under ambient temperature conditions”

In the absence of other criteria, this guidance has been adopted in reporting the results of this test. The leakage rates at other pressures are also included in this report.

The doorset was subjected to 100,000 opening and closing cycles as required by CERTIFIRE TS 21.

Test Sponsor Reddiplex Limited, The Furlong, Droitwich, Worcestershire, WR9 0RJ.

Summary of Tested Specimen

The specimen doorset had overall nominal dimensions of 2080 mm high by 1007 mm wide and incorporated a door leaf of overall dimensions 2040 mm high by 936 mm wide by 44 mm thick. The doorset was fixed within a plywood faced, timber stud partition, to form the test construction such that it opened away from the test rig.

The test series comprised two different seals. For the first test the door frame was fitted with a smoke seal referenced ‘Acoustic Corner Seal R9946’. The second test comprised a ‘Acoustic Twin Fin R9945’ seal. Each seal was continuous around the entire doorset perimeter (head and jambs). The doorset was rendered unlatched.

Full details of the exact manner of installation are included in the Schedule of Components.

Leakage Rate at +25 Pa (m3/m/h)

Leakage Rate at -25 Pa (m3/m/h)

Test Results:

Before Cycling 0.93 0.93

Acoustic Corner Seal

R9946 After Cycling 0.12 0.12

Before Cycling 0.05 0.06

Acoustic Twin Fin

R9945 After Cycling 0.04 0.09

Date of Test 5th, 12th and 17th October 2007

This report may only be reproduced in full. Extracts or abridgements of reports shall not be published without permission of Bodycote warringtonfire.

Page 3: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 3 of 18

Signatories

Responsible Officer N. Howard* Testing Officer

Approved S. Hankey* Operations Manager

* For and on behalf of Bodycote warringtonfire. Report Issued Date : 4th December 2007

This copy has been produced from a .pdf format electronic file that has been provided by Bodycote warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or abridgements of reports must not be published without permission of Bodycote warringtonfire. The original signed paper version of this report is the sole authentic version. Only original paper versions of this report bear authentic signatures of the responsible Bodycote warringtonfire staff.

Page 4: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 4 of 18

CONTENTS PAGE NO.

SUMMARY.................................................................................................................................. 2 SIGNATORIES............................................................................................................................ 3 TEST PROCEDURE...................................................................................................................... 5 TEST SPECIMEN ........................................................................................................................ 6 SCHEDULE OF COMPONENTS .................................................................................................... 9 DOORSET CLEARANCE GAPS ................................................................................................... 11 TEST DATA AND INFORMATION.............................................................................................. 12 LEAKAGE DATA........................................................................................................................ 13 PERFORMANCE CRITERION .................................................................................................... 17 ONGOING IMPLICATIONS....................................................................................................... 17 CONCLUSIONS ........................................................................................................................ 18

Page 5: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 5 of 18

Test Procedure Introduction Guidance with respect to the performance of fire doors required to resist the

passage of smoke at ambient temperature conditions is given in Approved Document B (Fire Safety) of the Building Regulations.

Certain aspects of some test specifications are open to different interpretations. The Fire Test Study Group has identified a number of such areas and has agreed Resolutions which define common agreement of interpretations between fire test laboratories which are members of the Group. Where such Resolutions are applicable to this test they have been followed.

Instruction to test

The tests were conducted on the 5th, 12th and 17th October 2007 on behalf of Reddiplex Limited.

Test Specimen Construction

A comprehensive description of the test construction is given in the Schedule of Components. The description is based on a detailed survey of the specimen and information supplied by the sponsor of the test.

Installation The specimen seals were supplied by the test sponsor on the day of test. Bodycote warringtonfire was not involved in any selection or sampling procedures of the specimens or any of the components.

A representative of Bodycote warringtonfire installed the doorset within the partition on the 4th October 2007.

Preparation The tests were conducted in accordance with the procedures specified in BS 476: Part 31: Section 31.1: 1983.

Prior to the evaluation the gaps between the leaf and the frame were measured and the values recorded. The door gaps were then sealed and the differential pressures were applied. The leakage rates measured were recorded as the base rig leakage. The door gaps were then unsealed and the leakage measured at the same differential pressures. The above procedure was then repeated with the airflow in the opposite direction.

The doorset was then subjected to 100,000 opening and closing cycles as defined with CERTIFIRE TS21, the above tests were then repeated to determine the effects on the leakage performance.

Page 6: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 6 of 18

Test Specimen Figure 1- General Elevation of Test Specimen

GENERAL ELEVATION OF OUTER FACE

6

936 LEAF

1007 FRAME

2080

FRAM

E

2040

LEA

F

230

765

280

765

HIN

GES

HORIZONTAL SECTION

44PLYWOOD PARTITION INNER FACE

OUTER FACE

1

2

3

Do not scale. All dimensions are in mm

Page 7: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 7 of 18

Figure 2 – Details of Acoustic Corner Seal 9946

TAPE

1

4595

12

12

12

3.3

0.5

1.7

TAPE

24

3

44

ACOUSTIC CORNER SEAL 9946

Do not scale. All dimensions are in mm

Page 8: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 8 of 18

Figure 3 – Details of Acoustic Twin Fin Seal 9945

TAPE

1

4595

12 25

3

44

12.2

5

50°

ACOUSTIC TWIN FIN SEAL 9945

Do not scale. All dimensions are in mm

Page 9: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 9 of 18

Schedule of Components (Refer to Figures 1 to 3) (All values are nominal unless stated otherwise) (All other details are as stated by the sponsor) Item

Description

1. Door frame Material : Timber, softwood (supplied & fitted by Warringtonfire) Density : 500 kg/m3 nominal Average moisture content : 12 % (measured with a Protimeter moisture meter) Overall size : 45 mm x 95 mm, with 12 mm deep rebate Jambs to head jointing method : Mortice & tennon and screwed Fixing i. method : Countersunk head steel screws ii. size : 100 mm long x 4.9 mm (No.10) diameter screws iii. frequency : 6 no. screws along hinged jambs (2 no. at 180 mm

centres about each hinge position), and 4 no. screws along closing jamb

2. Door leaf Manufacturer : Noberne Doors Limited (supplied & fitted by

Warringtonfire) Reference : Series 2, solid core flush door Door leaf thickness : 44 mm Construction i. general : Construction details of the door leaf are known and are

retained in our confidential file relating to this investigation

ii. stiles and rails : Softwood timber iii. core : Flaxboard iv. faces : Medium density fibreboard v. lippings : Hardwood to vertical edges 3. Hinges Manufacturer : Royde & Tucker Ltd Reference : H 102-fr-BZP Primary material : Bright zinc plated steel Size i. knuckle : 104 mm long by 13.7 mm diameter ii. blades : 100 mm long by 35 mm wide by 3 mm thick Fixings i. type : Countersunk head wood screws ii. material : Steel iii. sizes : 29 mm long by 5.1 mm diameter iv. number off per blade : 5 off v. maximum distance of fixing screws from face of door leaf

:

32 mm

Bedding material : None

Page 10: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 10 of 18

4. Jamb and head seal Manufacturer : Reddiplex Limited Product name : Acoustic Corner Seal Product code : 9946 Dimensions : 12 mm x 12 mm Method of installation : Supplied with a self-adhesive backing Material description (s) : Rigid, with flexible sealing fins Position of seal : Fitted to the planted stop and doorframe 5. Jamb and head seal Manufacturer : Reddiplex Limited Product name : Acoustic Twin Fin Seal Product code : 9945 Dimensions : 12 mm base with angled flipper Method of installation : Supplied with a self-adhesive backing Material description (s) : Rigid, with flexible sealing fins Position of seal : Fitted to the planted stop, C/D mode 6. Overhead Door Closer Manufacturer : Dorma Door Controls Reference : TS83 Fixing method : Surface mounted to unexposed face of doorset using

screws provided with closer unit.

Page 11: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 11 of 18

Doorset Clearance Gaps

1 2 3

14

4

13

5

12

6

11

7

10 9 8

Gap Dimension in mm at Positions 1 2 3 4 5 6 7 8* 9* 10* 11 12 13 14

2.5 2.5 2.4 2.2 2.1 3.3 2.8 4.4 4.3 5.4 2.4 2.0 2.3 2.3 Mean 2.4 Maximum 3.3 Minimum 2.0

* Dimension not included in calculations

Page 12: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 12 of 18

Test Data and Information General The following data, which was recorded during the tests, is included in the report:

• Table of the net leakage through the specimen at specified pressure differentials.

• Graph of the net leakages through the specimen at specified pressure differentials.

The ambient air temperature in the vicinity of the test construction at the start of the test was 17°C with no variation during the test.

Leakage Calculation

The readings were corrected for each leakage measurement to a reference temperature of 20°C and standard atmospheric pressure (1 atmosphere equals 101325 Pa) utilising the following formula:

Q = Qa x (Pa + p) x 293.15 x (1 - 0.3795) x Mw x __Es__

101325 (Ta + 273.15) 100 Pa + p Where Q = Adjusted rate of air flow (m3/h)

Qa = Measured rate of airflow (m3/h) p = Pressure increase (Pa) Pa = Barometric Pressure (Pa) Ta = Air temperature (°C) Mw = Relative Humidity (%) Es = Saturated water vapour pressure (Pa)

Page 13: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 13 of 18

Leakage Data Net Leakages at Specified Pressure Differentials

Prior to Cycling - Acoustic Corner Seal R9946

Pa m3/m/h -100 1.01 -70 1.00 -50 0.72 -30 0.78 -25 0.93 -20 0.53 -10 0.49 -5 0.57 0 0.00 5 0.33 10 0.68 20 0.60 25 0.93 30 0.93 50 0.96 70 1.29 100 1.44

0.00

0.20

0.40

0.60

0.80

1.00

1.20

1.40

1.60

1.80

2.00

-100 -80 -60 -40 -20 0 20 40 60 80 100

Pressure (Pa)

Air

Lea

kage

(m

3/m

/h)

Page 14: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 14 of 18

Net Leakages at Specified Pressure Differentials

After 100,000 Cycles – Acoustic Corner Seal R9946

Pa m3/m/h -100 0.15 -70 0.14 -50 0.11 -30 0.11 -25 0.12 -20 0.09 -10 0.05 -5 0.05 0 0.00 5 0.06 10 0.09 20 0.08 25 0.12 30 0.13 50 0.14 70 * 100 *

* Leakage not recorded due to door leaf opening under positive pressure

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

-100 -80 -60 -40 -20 0 20 40 60 80 100Pressure (Pa)

Air

Lea

kage

(m

3/m

/h)

Page 15: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 15 of 18

Net Leakages at Specified Pressure Differentials Prior to Cycling – Acoustic Twin Fin Seal R9945

Pa m3/m/h -100 0.07 -70 0.05 -50 0.05 -30 0.05 -25 0.06 -20 0.03 -10 0.03 -5 0.02 0 0.00 5 0.04 10 0.04 20 0.02 25 0.05 30 0.04 50 0.05 70 0.06 100 *

* Leakage not recorded due to door leaf opening under positive pressure

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

-100 -80 -60 -40 -20 0 20 40 60 80 100Pressure (Pa)

Air

Lea

kage

(m

3/m

/h)

Page 16: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 16 of 18

Net Leakages at Specified Pressure Differentials

After 100,000 Cycles – Acoustic Twin Fin Seal R9945

Pa m3/m/h -100 0.09 -70 0.06 -50 0.07 -30 0.07 -25 0.09 -20 0.01 -10 0.02 -5 0.03 0 0.00 5 0.02 10 0.02 20 0.03 25 0.04 30 0.08 50 0.07 70 0.10 100 0.12

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

-100 -80 -60 -40 -20 0 20 40 60 80 100

Pressure (Pa)

Air

Lea

kage

(m

3/m

/h)

Page 17: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 17 of 18

Performance Criterion Guidance with respect to the performance of fire doors required to resist the

passage of smoke at ambient temperature conditions is given in Approved Document B (Fire Safety) of the Building Regulations which requires doorsets shall “have a leakage rate not exceeding 3 m3/m/hr (head and jambs only) when tested at 25 Pa under BS 476 Fire tests on building materials and structures, Section 31.1 Methods for measuring smoke penetration through doorsets and shutter assemblies, Method of measurement under ambient temperature conditions”

In the absence of other criteria, this guidance has been adopted in reporting the results of this test, which are detailed below. The leakage rates at other pressures are also included in this report.

Ongoing Implications Limitations The results relate only to the behaviour of the specimen under the particular

conditions of test.

The test results relate only to the specimen tested. Application of the results to specimens of different dimensions or incorporating different components should be the subject of a design appraisal.

The dimensions of the gaps between the leaf and frame were measured and are detailed earlier in this report. The results of these tests are, therefore, limited to doorsets where the gap dimensions are similar to, but do not exceed those detailed in this report.

Review The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons it is recommended that the relevance of test reports over five years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report.

Page 18: 167811 Test 3 and 4 BS Report FR · WF Report No. 167811/A Page 2 of 18 Summary Objective To evaluate the performance of a specimen of a single-acting, single-leaf, doorset when fitted

WF Report No. 167811/A Page 18 of 18

Conclusions Evaluation against objective

A specimen of a single-acting, single-leaf doorset fitted with a ‘Acoustic Corner Seal R9946’ and subsequently a ‘Acoustic Twin Fin R9945’ smoke seal has been subjected to a test in accordance with BS 476: Part 31, Section 31.1: 1983. In addition, the doorset was subjected to 100,000 opening and closing cycles as required by CERTIFIRE TS 21.

The performance of the specimens was assessed against the criteria detailed within the Standard and the following results obtained:

Leakage Rate at +25 Pa (m3/m/h)

Leakage Rate at -25 Pa (m3/m/h)

Test Results:

Before Cycling 0.93 0.93

Acoustic Corner Seal

R9946 After Cycling 0.12 0.12

Before Cycling 0.05 0.06

Acoustic Twin Fin

R9945 After Cycling 0.04 0.09