  • 7/21/2019 1KHD626826ge System Test Report ETL600

    1/13

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd

    Rev. ind:

    Type des. Part no.

    Prep. A. Bemsel / PSNEX 2005-11-12 Doc.kind No. of p.

    Appr. H. Benninger / PSND 2007-05-21

    Resp.dept. PSNEX

    Title System Test Report ETL600 13+

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B1

    FILE: 1KHD626826ge System Test Report ETL600.doc; TEMPLATE: TECHN_DOC_STAND_P.dot R0; SKELETON: ; SAVEDATE: 5/21/2007 5:32:00 PM

    SYSTEM TEST REPORT

    Powerline Carrier Equipment: Series ETL600

    Project : ..

    ABB Order N : ..

    Station : ..

    Link : ..

    Equipment N : ..

    Frequency : TX = kHz RX = kHz

    Direction : ..

    System Test Report contains

    ETL600 System Test Report Pages B1 to B13

    HMI600 Printout of Configuration Pages .............

    HMI600 Printout of Status Pages .............

    The tuning of the equipment is in accordance with the following instructions:

    Programming and Testing of ETL600 1KHW001493-EN

    Compatibility Requirements for ETL600 1KHW001490-ENTuning of ETL600 Rx RF Filter P4RX 1KHW001491-ENTuning of ETL600 Tx RF Filter E5TX 1KHW001492-ENInput Voltage Change B5LC 1KHL015788-ENAPLC Channel Equalization for ETL600 1KHW001494-ENFirmware Download for ETL600 1KHW001496-ENTechnical Data ETL600 1KHW001498-EN

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    2/13

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B2

    SAFETY INSTRUCTIONS

    Please refer to chapter 2 of Instruction Manual 1KHW001489.

    Designations and abbreviations used:

    Refer to 1KHW001493-EN Programming and Testing of ETL600

    REVISION

    Rev.ind.

    Page (p.)Chapter (c.)

    Description DateDept./Init.

    a Complete document Exctracted from document 1KHW001993-EN, Rev. A. 2005-11-21,PTUKX1/AB

    b c. Safety instructions Text modified

    c. Designations andabbreviations

    Added

    Complete document Added fields for revision index referring to the contents of the test report

    Complete table of tests Changed text size to 9

    Steps B.5.2 and B.5.3 Added. => Previous steps B.5.2 to B.5.4 renumbered to B.5.4 to B.5.6

    Steps B.5.1 and B.6.1 Added lines for the bandwidth 4 kHzc. Customer acceptance(last page)

    Modified

    2006-02-17,PTUKT/Be

    c Section B7 Inserted.Previous sections B7 B14 renumbered to B8 B15 2006-04-26,PTUKT/Be

    Step B10.4 (earlier B9.4) Replaced T22 by T71

    Step B4 Checkbox added

    d Steps B12, B13 Changed acceptance limits 2006-06-30,PSND/Be

    e p. 1, p. 13p. 1

    Updated department designationsInserted line for link designation

    2006-09-19,PSND/Be

    f Steps B14, B15 Tests of G.703.1 and LAN ports added

    (

    previous sections B14, B15 renumbered to B16, B17).Replaced entry fields for telephony levels by checkboxes

    2007-02-01,

    PSND/Be

    g Steps B11.3, B11.5 Corrected default levels 2007-05-21,PSND/Be

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    3/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B3

    Test

    No. Test procedur e Test point

    Permissible

    value Units

    Test

    result

    B.1 General

    B.1.1 Visual checks

    Correct wiring of protective earth P7LA, P7LC PE wired [ ]

    Correct wiring of power supply P7LA, P7LC polarity ok [ ]

    Equipment connected to adequatevoltage source

    [ ]

    B.2 Check power supply B5LA/B5LCUpper Lower

    B.2.1 Battery supply 48V DC B5LA (BAT-0V) -46 to 56 V DC [ ] [ ] D

    B.2.2 Mains supply 230V AC B5LC (UR-0V) -46 to 52 V DC [ ] [ ] D

    B.2.3 Mains supply 115V AC B5LC (UR-0V) -46 to 52 V DC [ ] [ ] D

    B.2.4 Ripple on 48V DC B5LA (BAT-0V) < 1 V rms [ ] [ ] D

    B.2.5 Ripple on UR (Mains) B5LC (UR-0V) < 1 V rms [ ] [ ] D

    B.3 Connect to the equipment, downloadconfiguration and prepare for tuning &testing

    Connect to the equipment Check communicationbetween PC and P4LT

    [ ]

    Download configuration Download successful [ ]

    Activate the Tuning & testing dialog box Prepare Tuning & testing [ ]

    B.4 Change conf iguration, if necessary [ ]

    B.5 Transmitter

    B.5.1 Programming of Tx RF filt erRefer to Tuning of ETL600 Tx RF FilterE5TX 1KHW001492-EN Upper* Lower

    Bandwidth = 4 kHz E5TX Refer [ ] [ ] D

    Bandwidth = 8 kHz E5TX to [ ] [ ] D

    Bandwidth = 16 kHz E5TX document [ ] [ ] D

    Bandwidth = 32 kHz E5TX 1KHW001492 [ ] [ ] D

    Center frequency E5TX fTx=________ kHz

    B.5.2 Settings for RF hybrid P3LE

    Jumpers set according to dialog box'Tune Tx RF filter'

    P3LE T3Ax, T3Bx,T4Ax, T4Bx

    [ ]

    B.5.3 Settings for combiner P3LG, ifpresent

    Jumpers set according to dialog box'Tune Tx RF filter'

    P3LG TAx, TBx, JRx [ ]

    Upper und Lower stands for upper rack / lower rack and applies to 80 W equipment ETL680 only.

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    4/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B4

    Test

    No. Test procedure Test point

    Permissible

    value Units

    Test

    result

    B.5.4 Tune Tx RF fil terUpper* Lower

    Dialog box 'Tune Tx RF filter' E5TX Refer to doc.1KHW001492

    [ ] [ ] D

    B.5.5 Adjust Tx RF level

    Dialog box: Adjust Tx RF level

    Click Start/Set

    RF hybrid (X200) or RF line(X175)

    value indicatedin dialog box

    [ ]

    B.5.6 Adjust Tx alarm level

    Dialog box: Adjust Tx alarm level

    Click Activate Tx alarm level, set jumperCH and turn potentiometer R116 onP1LA till LED on it lights

    LED to be ON [ ]

    Tx alarm indication: RF hybrid & - in case of80W - combiner

    LED to be ON [ ]

    State of HW alarm relay afterprogrammed delay.

    Pins 2-3 of V9OT cable Closed [ ]

    Turn potentiometer R116 on P1LA tillLED on it goes off.

    LED to be OFF [ ]

    Tx alarm indication RF hybrid & - in case of80W - combiner

    LED to be OFF [ ]

    State of HW alarm relay afterprogrammed delay.

    Click OK.

    Pins 2-3 of V9OT cable Open [ ]

    B.6 Receiver

    B.6.1 Programming of Rx RF filt erRefer to Tuning of ETL600 Rx RF FilterP4RX 1KHW001491-EN

    Bandwidth = 4 kHz P4RX Refer [ ]

    Bandwidth = 8 kHz P4RX to [ ]

    Bandwidth = 16 kHz P4RX document [ ]

    Bandwidth = 32 kHz P4RX 1KHW001491 [ ]

    Center frequency P4RX fRx=________ kHz

    B.6.2 Tune Rx RF fil ter P4RX, if present

    Dialog box 'Tune Rx RF filter' P4RX, P3LL, P4LM Refer to doc.1KHW001491

    [ ]

    B.6.3 Adjust Rx RF level

    Dialog box: Tuning & testing

    Dialog box: Adjust Rx RF level Dialog box Valueindicatedin dialog box.

    dBu [ ]

    Follow the instructions in the dialog box

    B.6.4 Tune RF hybr id P3LE

    Tuned Default Dialog box: Tune RF hybrid Dialog box Tuned / default

    setting[ ] [ ] D

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    5/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B5

    Test

    No. Test procedur e Test point

    Permissible

    value Units

    Test

    result

    B.6.5 Link alarm indication

    Activate link alarm by interrupting RFconnection.

    Link alarm LED on P4LT LED to be ON [ ]

    State of Link alarm relay afterprogrammed delay.

    Terminals 5-6 at V9OTexternal cable

    Closed [ ]

    Deactivate link alarm by restoring thelink.

    Link alarm LED on P4LT LED to be OFF [ ]

    State of link alarm relay afterprogrammed delay.

    Terminals 5-6 at V9OTexternal cable

    Open [ ]

    B.7 Equalization

    B.7.1 Measure frequency responseCh 1 Ch 2 Ch 3

    In menu Equipment / Commissioning and

    maintenance / Frequency response /APLC channel 1, APLC channel 2 orAPLC channel 3

    HMI600 [ ] [ ] [ ]

    B.7.2 Select Equal izerCh 1 Ch 2 Ch 3

    In menu Equipment / Commissioning andmaintenance / Select equalizer / APLCchannel 1, APLC channel 2 orAPLC channel 3

    HMI600 [ ] [ ] [ ]

    B.8 Testing of R1BC, if present

    Activate alarms as programmed on

    R1BC.

    Corresponding N/C contacts

    on R1BC.

    Closed [ ]

    Deactivate alarms as programmed onR1BC.

    Corresponding N/C contactson R1BC.

    Open [ ]

    B.9 Configure Real Time Clock (RTC)

    B.9.1 Setting real time clock

    Menu: Equipment, Commissioning andmaintenance, Eventrecorder, Set clock

    Download date / time to RTC Dialog box Actual time anddate

    [ ]

    B.9.2 Testing external real time clocksynchronization (if available)

    Menu: Equipment, Commissioning andmaintenance, Eventrecorder, Set clock

    Download date/time to RTC Dialog box Wrong time

    Upload date/time from RTC Dialog box Correct time [ ]

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    6/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B6

    Test

    No. Test procedur e Test point

    Permissible

    value Units

    Test

    result

    B.10 Testing of NSD600 / G4AI, ifpresent

    B.10.1 Inputs

    N11 N22N28N34N54N65 N71Input 1 IN1Activate Input 1

    Check LED IN1

    Terminal,(T/1) (T.../2)

    LED IN1

    U1, seeSystem settings

    ON

    V DC[ ] [ ] [ ] [ ] [ ] [ ] [ ]

    N11 N22N28N34N54N65 N71Input 2 IN2Activate Input 2

    Check LED IN2

    Terminal,(T/3) (T.../4)

    LED IN2

    U2, seeSystem settings

    ON

    V DC[ ] [ ] [ ] [ ] [ ] [ ] [ ]

    N11 N22N28N34N54N65 N71Input 3 IN3Activate Input 3

    Check LED IN3

    Terminal,(T/5) (T.../6)

    LED IN3

    U3, seeSystem settings

    ON

    V DC[ ] [ ] [ ] [ ] [ ] [ ] [ ]

    N11 N22N28N34N54N65 N71Input 4 IN4

    Activate Input 4Check LED IN4

    Terminal,

    (T/7) (T.../8)LED IN4

    U4, see

    System settingsON

    V DC [ ] [ ] [ ] [ ] [ ] [ ] [ ]

    B.10.2 Outputs

    N11 N22N28N34N54N65 N71Enforce action for OUT1.Check Output 1, OUT1:

    Check LED OUT1

    Terminal,(T/9) (T.../10)

    LED OUT1

    Closed

    ON[ ] [ ] [ ] [ ] [ ] [ ] [ ]

    N11 N22N28N34N54N65 N71Enforce action for OUT2.Check Output 2, OUT2:

    Check LED OUT2

    Terminal,(T/11) (T.../12)

    LED OUT2

    Closed

    ON[ ] [ ] [ ] [ ] [ ] [ ] [ ]

    N11 N22N28N34N54N65 N71Enforce action for OUT3.Check Output 3, OUT3:

    Check LED OUT3

    Terminal,(T/13) (T.../14)

    LED OUT3

    Closed

    ON[ ] [ ] [ ] [ ] [ ] [ ] [ ]

    N11 N22N28N34N54N65 N71Enforce action for OUT4.Check Output 4, OUT4:

    Check LED OUT4

    Terminal,(T/15) (T.../16)

    LED OUT4

    Closed

    ON[ ] [ ] [ ] [ ] [ ] [ ] [ ]

    N11 N22N28N34N54N65 N71Enforce action for relay 1REL1 close/open

    Check LED REL1

    Terminal,(T/17) (T.../18)

    LED REL1

    Refer G4AIprogramming

    ON[ ] [ ] [ ] [ ] [ ] [ ] [ ]

    N11 N22N28N34N54N65 N71Enforce action for relay 2REL2 close/open

    Check LED REL2

    Terminal,(T/19) (T.../20)

    LED REL2

    Refer G4AIprogramming

    ON[ ] [ ] [ ] [ ] [ ] [ ] [ ]

    B.10.3 NSD600 loop test TPE1 TPE2Check Actual transmissiontime TLink

    Menu: Equipment,Commissioning andmaintenance, NSD600 sendloop test

    HMI600 < 1.3*T0 ms _______ _______

    B.10.4 Command transmissiontime

    Command A

    Tx command A

    Rx command A

    Terminal:

    (T71/1) (T71/2) [ ](T/...) (T.../) [ ]

    (T71/9) (T71/10) [ ]

    (T/...) (T.../) [ ]

    Refer HMI600

    Mean value

    T0 ms

    TPE1

    ________

    TPE2

    ________

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    7/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B7

    Test

    No. Test procedure Test point

    Permissible

    value Units

    Test

    result

    Command B

    Tx command B

    Rx command B

    Terminal:

    (T71/3) (T71/4) [ ](T/...) (T.../) [ ]

    (T71/11) (T71/12) [ ](T/...) (T.../) [ ]

    Refer HMI600

    Mean value

    T0 ms

    TPE1

    ________

    TPE2

    ________

    Command C

    Tx command C

    Rx command C

    Terminal:

    (T71/5) (T71/6) [ ](T/...) (T.../) [ ]

    (T71/13) (T71/14) [ ]

    (T/...) (T.../) [ ]

    Refer HMI600

    Mean value

    T0 ms

    TPE1

    ________

    TPE2

    ________

    Command D

    Tx command D

    Rx command D

    Terminal:

    (T71/7) (T71/8) [ ](T/...) (T.../) [ ]

    (T71/15) (T71/16) [ ]

    (T/...) (T.../) [ ]

    Refer HMI600

    Mean value

    T0 ms

    TPE1

    ________

    TPE2

    ________

    B.10.5 Reset counters

    Menu: Equipment,Commissioning andmaintenance, Eventrecorder,Reset counter, OK:

    HMI600 All counters = 0 [ ]

    B.11 Testing of O4LE

    B.11.1 Service Phone. Mark if configured: N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Pick up the phones and talk. Service phone, at frontpanel Remote servicephone rings, buzzerdrones, talk ispossible

    N11[ ]

    N22[ ]

    N54[ ]

    B.11.2 Hot line direct phone Mark if configured: N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Pick up the phone, wait, pickup remote phone

    Direct phone Remote directphone rings untilphone is picked up.

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Measure Output level.

    Feed 800 Hz with configuredinput level of remotesubscriber (Def.: 0.0 dBm).

    Feed into rem. equ. at

    terminal, telephony 0a-0bMeasure at terminal,telephony 0a-0b

    Configured Output

    level 1 dB(Def.: -7.0 dBm)

    dBm

    (600 )

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    B.11.3 Remote subscriber. Atremote equ. is Pax 2-Wire

    Mark if configured: N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Test Ringer: Feed ringingvoltage (25 VAC, 25 Hz, R =

    2.2 k) into remote PAX 2-Wire

    Feed into rem. equ. atterminal, telephony 8a-8b

    Subscriber mustring

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Measure Output level.

    Feed 800 Hz with configuredinput level of remotePAX.(Def.: 0.0 dBm)

    Feed into rem. equ. at

    terminal, telephony 8a-8bMeasure at terminal,telephony 0a-0b

    Configured Output

    level 1 dB(Def.: -7.0 dBm)

    dBm

    (600 )

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    8/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B8

    Test

    No. Test procedur e Test point

    Permissible

    value Units

    Test

    result

    B.11.4 Remote subscriber. Atremote equ. is Pax 4-wire

    Mark if configured: N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Test Ringer:

    Activate M-WIRE of remotePax 4-wire.

    Activate at Remote equ.at terminal, telephony 4a-4b

    Subscriber mustring

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Measure Output level.

    Feed 800 Hz with configuredinput level of remotePAX.(Def.: -3.5 dBm)

    Feed into rem. equ. atterminal, telephony 1a-1b

    Measure at terminal,telephony 0a-0b

    Configured Outputlevel 1 dB(Def.: -7.0 dBm)

    dBm

    (600 )N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    B.11.5 Pax 2-wire Mark if configured: N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Measure Output level.Feed 800 Hz with configuredinput level of remotesubscriber.(Def.: 0.0 dBm)

    Feed into rem. equ. atterminal, telephony 0a-0b

    Measure at terminal,telephony 8a-8b

    Configured Outputlevel 1 dB(Def.: -7.0 dBm)

    dBm(600 ) N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    PAX-BLOCKING normal Measure at terminal,telephony 6a-6b, 6b-7a

    6a-6b is open,6b-7a is closed

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    PAX-BLOCKING blocked

    Switch off remote equ., waitabout 30 sec.

    Measure at terminal,telephony 6a-6b, 6b-7a

    6a-6b is open,6b-7a is closed

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    B.11.6 Pax 4-wire. At remote equ. is

    Pax 4-wire

    Mark if configured: N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Test E-Wire:

    Close and open at Remoteequ. at terminal, telephony4a-4b

    Terminal, telephony3a-3b

    E-Wire must toggle N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Measure Output level.

    Feed 800 Hz with configuredinput level of remote PAX(Def.: -3.5 dBm).

    (Activate at terminal, telephony4a-4b on both equ.)

    Feed into rem. equ. atterminal, telephony 1a-1b

    Measure at terminal,telephony 2a-2b

    Configured Outputlevel 1 dB(Def.: -3.5 dBm)

    dBm

    (600 )N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    PAX-BLOCKING normal Measure at terminal,telephony 6a-6b, 6b-7a 6a-6b is open,6b-7a is closed N11[ ]N22[ ]

    N54[ ]

    PAX-BLOCKING blocked

    Switch off remote equ., waitabout 30 sec.

    Measure at terminal,telephony 6a-6b, 6b-7a

    6a-6b is open,6b-7a is closed

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    9/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B9

    Test

    No. Test procedure Test point

    Permissible

    value Units

    Test

    result

    B.11.7 Pax 4-wire. At remote equ. isRemote subscriber

    Mark if configured: N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Test E-Wire:

    Toggle hook of phone.(Close and open at Remoteequ. at terminal, telephony0a-0b)

    Terminal, telephony3a-3b

    E-Wire must toggle N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Measure Output level.

    Feed 800 Hz with configuredinput level of remotesubscriber.(Def.: 0.0 dBm)

    Feed into rem. equ. atterminal, telephony 0a-0b

    Measure at terminal,telephony 2a-2b

    Configured Outputlevel 1 dB(Def.: -3.5 dBm)

    dBm

    (600 )N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    PAX-BLOCKING normal Measure at terminal,telephony 6a-6b, 6b-7a

    6a-6b is open6b-7a is closed

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    PAX-BLOCKING blocked

    Switch off remote equ., waitabout 30 sec.

    Measure at terminal,telephony 6a-6b, 6b-7a

    6a-6b is open6b-7a is closed

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    B.11.8 Pax 4/2-wire Mark if configured: N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Test E-Wire:Close and open at Remoteequ. at terminal, telephony4a-4b

    Terminal, telephony3a-3b

    E-Wire must toggle N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Measure Output level of AF1.

    Feed 800 Hz with configuredinput level of remote PAX(Def.: -3.5 dBm).

    Activate at terminal, telephony4a-4b on both equ..

    Feed into rem. equ. at

    terminal, telephony 1a-1bMeasure at terminal,telephony 2a-2b

    Configured Output

    level 1 dB(Def.: -3.5 dBm)

    dBm

    (600 )

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Measure Output level ofPAX2W.

    Feed 800 Hz with configuredinput level of remote PAX(Def.: -3.5 dBm).

    (Activate at terminal, telephony4a-4b on both equ.)

    Feed into rem. equ. atterminal, telephony 1a-1b

    Measure at terminal,telephony 8a-8b

    Configured Outputlevel 1 dB(Def.: -7.0 dBm)

    dBm

    (600 )N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Test Local/Transit:Measure Output level at AF1.Feed 800 Hz with configuredinput level of remote PAX2W(Def.: -0.0 dBm).

    Activate at terminal, telephony5a-4b of remote equ..(Activate at terminal, telephony4a-4b on both equ.)

    Feed into rem. equ. atterminal, telephony 8a-8b

    Measure at terminal,telephony 8a-8b

    Configured Outputlevel 1.5 dB(Def.: -7.0 dBm)

    dBm(600 )

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    PAX-BLOCKING normal Measure at terminal,telephony 6a-6b, 6b-7a

    6a-6b is open6b-7a is closed

    N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    PAX-BLOCKING blockedSwitch off remote equ., waitabout 30 sec.

    Measure at terminal,

    telephony 6a-6b, 6b-7a

    6a-6b is open

    6b-7a is closed N11[ ]

    N22[ ]

    N54[ ]

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    10/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B10

    Test

    No. Test procedur e Test point

    Permissible

    value Units

    Test

    result

    B.11.9 Transit mode for E&M wire Mark if configured: N11

    [ ]

    N22

    [ ]

    N54

    [ ]

    Test E-Wire:Close and open at Remoteequ. at terminal, telephony4a-4b

    Terminal, telephony3a-3b E-Wire must toggle N11[ ]

    N22[ ]

    N54[ ]

    B.11.10 Testing the teleoperationports

    N11 N22 N34 N54 N65B.11.11 Teleoperation AF1, if notused for telephony

    Mark if configured:

    [ ] [ ] [ ] [ ] [ ]

    Fed input level, [dBm],@ 800 Hz at AF1-IN of remote.

    Expected Outputlevel at AF1-OUT

    Measured Output level atAF1-OUT

    N11: ___________1

    N22: ___________1

    N34: ___________1

    N54: ___________1

    N65: ___________1

    Feed into rem. equ. atterminal, telephony 1a-1b

    Measure at terminal,telephony 2a-2b

    ext. Boost not active.

    N11: _______1

    N22: _______1

    N34: _______1

    N54: _______1

    N65: _______1

    dBm

    (600 )N11: ___________

    N22: ___________

    N34: ___________

    N54: ___________

    N65: ___________

    N11 N22 N34 N54 N65B.11.12 Teleoperation AF2 Mark if configured:

    [ ] [ ] [ ] [ ] [ ]

    Fed input level, [dBm],@ 800 Hz at AF2-IN of remote.

    Expected Outputlevel at AF2-OUT

    Measured Output level atAF2-OUT

    N11: ___________1

    N22: ___________1

    N34: ___________1

    N54: ___________1

    N65: ___________1

    Feed into rem. equ. atterminal, teleop. 3a-3b

    Measure at terminal,teleop. 4a-4b

    ext. Boost not active.

    N11: _______1

    N22: _______1

    N34: _______1

    N54: _______1

    N65: _______1

    dBm

    (600 )N11: ___________

    N22: ___________

    N34: ___________

    N54: ___________

    N65: ___________

    N11 N22 N34 N54 N65B.11.13 Teleoperation AF3 Mark if configured:

    [ ] [ ] [ ] [ ] [ ]

    Fed input level, [dBm],

    @ 800 Hz at AF3-IN of remote.

    Expected Output

    level at AF3-OUT

    Measured Output level at

    AF3-OUT

    N11: ___________1

    N22: ___________1

    N34: ___________1

    N54: ___________1

    N65: ___________1

    Feed into rem. equ. atterminal, teleop. 5a-5b

    Measure at terminal,teleop. 6a-6b

    ext. Boost not active.

    N11: _______1

    N22: _______1

    N34: _______1

    N54: _______1

    N65: _______1

    dBm

    (600 )N11: ___________

    N22: ___________

    N34: ___________

    N54: ___________

    N65: ___________

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    11/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B11

    Test

    No. Test procedure Test point

    Permissible

    value Units

    Test

    result

    N11 N22 N34 N54 N65B.11.14 Teleoperation AF4 Mark if configured:

    [ ] [ ] [ ] [ ] [ ]

    Fed input level, [dBm],@ 800 Hz at AF4-IN of remote.

    Expected Outputlevel at AF4-OUT

    Measured Output level atAF4-OUT

    N11: ___________

    N22: ___________

    N34: ___________

    N54: ___________

    N65: ___________

    Feed into rem. equ. atterminal, teleop. 7a-7b

    Measure at terminal,teleop. 8a-8b

    ext. Boost not active.

    N11: _______1

    N22: _______1

    N34: _______1

    N54: _______1

    N65: _______1

    dBm

    (600 )N11: ___________

    N22: ___________

    N34: ___________

    N54: ___________

    N65: ___________

    N11 N22 N54B.11.15 Teleoperation AF4 used forext. teleprotection

    Mark if configured:

    [ ] [ ] [ ]

    Test EXT-BOOST: Activate at remote equ. atterminal, teleop. 9a-9b

    Fed input level, [dBm],@ 800 Hz at AF4-IN

    Feed into rem. equ. atterminal, teleop. 7a-7b

    Expected Outputlevel at AF4-OUT

    Measured Output level atAF4-OUT

    N11: ___________

    N22: ___________

    N54: ___________

    Measure at terminal,teleop. 8a-8b

    N11: _______1

    N22: _______1

    N54: _______1

    dBm

    (600 )N11: ___________

    N22: ___________

    N54: ___________

    B.12 Testing of V.11 port s

    B.12.1 V.11 Port 1 Front plate P4LT/P4LU

    BER test V.11 PORT 1 BER 10-6

    during ____ sec[ ]

    B.12.2 V.11 Port 2 Front plate P4LT/P4LU

    BER test V.11 PORT 2 BER 10-6

    during ____ sec[ ]

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    12/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B12

    Test

    No. Test procedur e Test point

    Permissible

    value Units

    Test

    result

    B.13 Testing of V.24 port s

    B.13.1 V.24 Port 1 Front plate P4LT/P4LU

    BER test V.24 PORT 1 BER 10-6

    during ____ sec[ ]

    B.13.2 V.24 Port 2 Front plate P4LT/P4LU

    BER test V.24 PORT 2 BER 10-6

    during ____ sec[ ]

    B.13.3 V.24 Port 3 Front plate P4LT/P4LU

    BER test V.24 PORT 3 BER 10-6

    during ____ sec[ ]

    B.13.4 V.24 Port 4 Front plate P4LT/P4LUBER test V.24 PORT 4 BER 10

    -6

    during ____ sec[ ]

    B.13.5 V.24 Port 5 Front plate P4LT/P4LU

    BER test V.24 PORT 5 BER 10-6

    during ____ sec[ ]

    B.13.6 V.24 Port 6 Front plate P4LT/P4LU

    BER test V.24 PORT 6 BER 10-6

    during ____ sec[ ]

    B.14 Testing of G.703.1 port

    B.14.1 G.703.1 Port Front plate P4LT/P4LU

    BER test G.703.1 PORT BER 10-6

    during ____ sec[ ]

    B.15 Testing of LAN port

    B.15.1 LAN Port Front plate P4LT/P4LU

    Test of throughput LAN PORT Throughput

    during _____ sec _____ __________________

    Percentage of errored frames LAN PORT% errored frames

    during _____ sec % _________

    B.16 Documentation

    Make a printout of equipmentconfiguration and status data.

    [ ]

    Save the '*.et6' file on diskwith Serial No. of ETL codedin the file name,

    e.g. HE400327B0.ET6

    [ ]

    B.17 Manual reset [ ]

  • 7/21/2019 1KHD626826ge System Test Report ETL600

    13/13

    Rev. ind.

    System Test Report ETL600 Equipment HE

    Doc. no. Lang. Rev. ind. Page

    ABB Switzerland Ltd 1KHD626826 en G B13

    CUSTOMER ACCEPTANCE

    The acceptance form is completed by ABB and the customer representative once all equipment testsdetailed in this document have been performed successfully. Customer acceptance form is part of thetest report.

    Testfield ABB Switzerland Ltd

    Department PSNEX

    Date:

    Test Engineer: _____________________________

    Supervisor: _____________________________

    FAT Witnessed

    Date: _____________________________

    Engineer: _____________________________

    ... _____________________________

    .. Date: ..... _____________________________

    .. Date: ..... _____________________________

    .. Date: ..... _____________________________

    .. Date: ..... _____________________________

    .. Date: ..... _____________________________