1mrk511302-uen - en communication protocol manual iec 61850 edition 1 670 series 2.0 iec2

370
Relion ® Protection and Control 670 series 2.0 IEC IEC 61850 Edition 1 Communication Protocol Manual

Upload: insan-aziz

Post on 11-Jul-2016

26 views

Category:

Documents


6 download

DESCRIPTION

IEC61850

TRANSCRIPT

  • Relion Protection and Control

    670 series 2.0 IECIEC 61850 Edition 1 CommunicationProtocol Manual

  • Document ID: 1MRK 511 302-UENIssued: May 2014

    Revision: -Product version: 2.0

    Copyright 2014 ABB. All rights reserved

  • CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.The software and hardware described in this document is furnished under a licenseand may be used or disclosed only in accordance with the terms of such license.This product includes software developed by the OpenSSL Project for use in theOpenSSL Toolkit. (http://www.openssl.org/)This product includes cryptographic software written/developed by: Eric Young([email protected]) and Tim Hudson ([email protected]).TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

  • DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of theperson or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.

  • ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standard EN 60255-26 for the EMC directive, andwith the product standards EN 60255-1 and EN 60255-27 for the low voltagedirective. The product is designed in accordance with the international standards ofthe IEC 60255 series.

  • Table of contents

    Section 1 Introduction.......................................................................9This manual........................................................................................9Intended audience..............................................................................9Product documentation.....................................................................10

    Product documentation set..........................................................10Document revision history...........................................................11Related documents......................................................................12

    Document symbols and conventions................................................13Symbols.......................................................................................13Document conventions................................................................14Functions included in 670 series IEDs........................................15IEC61850 edition 1 / edition 2 mapping.......................................23

    Section 2 Introduction to IEC 61850...............................................31Related documentation to IEC 61850..........................................32

    Section 3 Substation Configuration description Language(SCL)..............................................................................35The substation section......................................................................36The communication section..............................................................36The IED section................................................................................37Tool concept.....................................................................................40Engineering concept in IEC 61850-6................................................41

    Section 4 Communication profile....................................................43Section 5 Supported services.........................................................45Section 6 Data sets and control blocks..........................................49

    Data sets..........................................................................................49Report control block (URCB/BRCB).................................................50GOOSE Control Blocks (GoCB).......................................................53

    Section 7 Logical node data model................................................57Common data objects in each logical node......................................57Logical nodes for automatic control..................................................59

    Automatic tap changer control ATCC..........................................59Automatic voltage control for tapchanger, parallelcontrol TR8ATCC ..................................................................68Tap changer control and supervision, 6 binary inputsTCMYLTC and TCLYLTC ....................................................82

    Table of contents

    670 series 2.0 IEC 1Communication Protocol Manual

  • Logical nodes for control..................................................................85Bay control CBAY........................................................................85

    Bay control QCBAY................................................................85Logical node for interlocking SCILO ...........................................87Switch controller CSWI................................................................88

    Switch controller SCSWI........................................................88Bay reserve function QCRSV......................................................90

    Logical nodes for conversion functions............................................92Integer to Boolean converter FCVB.............................................92

    Integer to Boolean 16 conversion with logic noderepresentation ITBGAPC........................................................92

    Boolean to integer converter FCVI..............................................94Boolean 16 to Integer conversion with logic noderepresentation BTIGAPC........................................................94

    Logical nodes for protection functions..............................................94Differential protection PDIF.........................................................94

    Transformer differential protection, two windingT2WPDIF ...............................................................................94Transformer differential protection, three windingT3WPDIF ...............................................................................98Low impedance restricted earth fault protectionREFPDIF .............................................................................102Generator differential protection GENPDIF .........................1031Ph High impedance differential protection HZPDIF ...........106Busbar differential protection, 2 zones, three phaseBCZTPDIF ...........................................................................107Busbar differential protection, 2 zones, single phaseBCZSPDIF ...........................................................................108Line differential protection, 3 CT sets, 23 line endsL3CPDIF ..............................................................................108Line differential protection, 6 CT sets, 35 line endsL6CPDIF ..............................................................................111Line differential protection 3 CT sets, with inzonetransformers, 23 line ends LT3CPDIF .................................114Line differential protection 6 CT sets, with inzonetransformers, 35 line ends LT6CPDIF .................................117

    Additional security logic for differential protection RGFC..........120Additional security logic for differential protectionLDRGFC ..............................................................................120

    Distance protection PDIS..........................................................122Phase selection with load encroachment, quadrilateralcharacteristic FDPSPDIS.....................................................122Faulty phase identification with load encroachmentFMPSPDIS...........................................................................125Loss of excitation LEXPDIS.................................................126

    Table of contents

    2 670 series 2.0 IECCommunication Protocol Manual

  • Distance protection zone, quadrilateral characteristicZMQPDIS.............................................................................128Distance protection zone, quadrilateral characteristicZMQAPDIS...........................................................................129Distance measuring zone, quadrilateral characteristicfor series compensated lines ZMCPDIS..............................130Distance measuring zone, quadrilateral characteristicfor series compensated lines ZMCAPDIS............................131Full-scheme distance protection, mho characteristicZMHPDIS.............................................................................133Fullscheme distance protection, quadrilateral for earthfaults ZMMPDIS...................................................................134Fullscheme distance protection, quadrilateral for earthfaults ZMMAPDIS.................................................................135Distance protection zone, quadrilateral characteristic,separate settings ZMRAPDIS..............................................136Distance protection zone, quadrilateral characteristic,separate settings ZMRPDIS.................................................137High speed distance protection ZMFPDIS...........................139Phase selection, quadrilateral characteristic withsettable angle FRPSPDIS....................................................145High speed distance protection for series compensatedlines ZMFCPDIS...................................................................148Underimpedance protection for generators andtransformers ZGVPDIS........................................................154

    Directional overpower PDOP.....................................................157Directional over-power protection GOPPDOP.....................157

    Directional underpower PDUP...................................................158Rate of change of frequency PFRC...........................................160

    Rate-of-change frequency protection SAPFRC ..................160Frequency time accumulation protection QFVR........................161

    Frequency time accumulation protection FTAQFVR............161Instantaneous overcurrent PIOC...............................................162

    Instantaneous phase overcurrent protection 3-phaseoutput PHPIOC ....................................................................162Instantaneous residual overcurrent protection EFPIOC ......163

    Local acceleration logic PLAL...................................................163Local acceleration logic ZCLCPLAL.....................................163

    Protection scheme PSCH..........................................................164Scheme communication logic with delta based blockingscheme signal transmit ZCPSCH.........................................164Current reversal and WEI logic for distance protection 3-phase ZCRWPSCH..............................................................166Scheme communication logic for residual overcurrentprotection ECPSCH..............................................................167

    Table of contents

    670 series 2.0 IEC 3Communication Protocol Manual

  • Current reversal and weak-end infeed logic for residualovercurrent protection ECRWPSCH....................................169Protection scheme [Line diff logic] LDLPSCH .....................170Power swing logic PSLPSCH...............................................172Phase segregated Scheme communication logic fordistance protection ZC1PPSCH...........................................173Current reversal and weak-end infeed logic for phasesegregated communication ZC1WPSCH.............................175

    Sensitive directional earth fault PSDE.......................................176Sensitive directional residual overcurrent and powerprotection SDEPSDE ..........................................................176

    Switch onto fault logic PSOF.....................................................179Automatic switch onto fault logic, voltage and currentbased ZCVPSOF .................................................................179

    Time over current PTOC...........................................................179Four step residual overcurrent protection, (Zerosequence or negative sequence directionality)EF4PTOC ............................................................................179Four step phase overcurrent protection 3-phase outputOC4PTOC ...........................................................................184Stub protection STBPTOC ..................................................189Broken conductor check BRCPTOC ...................................190Negative-sequence time overcurrent protection formachines NS2PTOC ...........................................................191Three phase overcurrent LCP3PTOC..................................193Negative sequence overcurrent protection LCNSPTOC......194Zero sequence overcurrent protection LCZSPTOC.............195Four step directional negative phase sequenceovercurrent protection NS4PTOC........................................196Four step phase overcurrent protection OC4PTOC.............201Four step single phase overcurrent protectionPH4SPTOC..........................................................................205Four step residual overcurrent protection EF4PTOC...........209Sudden change in current variation SCCVPTOC.................214

    Overfrequency PTOF................................................................214Overfrequency protection SAPTOF .....................................214

    Overvoltage PTOV....................................................................215Negative sequence overvoltage protection LCNSPTOV......215Zero sequence overvoltage protection LCZSPTOV.............216Two step overvoltage protection OV2PTOV .......................217Two step residual overvoltage protection ROV2PTOV .......220Voltage differential protection VDCPTOV............................222

    Protection trip conditioning PTRC.............................................223Carrier receive logic LCCRPTRC.........................................223Tripping logic common 3-phase output SMPPTRC..............224

    Table of contents

    4 670 series 2.0 IECCommunication Protocol Manual

  • Thermal overload PTTR............................................................225Thermal overload protection, one time constant, CelsiusLCPTTR...............................................................................225Thermal overload protection, one time constant,Fahrenheit LFPTTR..............................................................227Thermal overload protection, two time constantsTRPTTR ..............................................................................228Rotor overload protection GRPTTR.....................................230Stator overload protection GSPTTR.....................................232

    Three phase undercurrent PTUC..............................................233Three phase undercurrent LCP3PTUC................................233

    Undervoltage PTUV...................................................................234Two step undervoltage protection UV2PTUV ......................234Loss of voltage check LOVPTUV ........................................237

    Underfrequency PTUF...............................................................237Underfrequency protection SAPTUF ...................................237

    Volts per Hz PVPH....................................................................239Overexcitation protection OEXPVPH ..................................239

    Multipurpose analog protection GAPC......................................240Accidental energizing protection for synchronousgenerator AEGPVOC...........................................................240Status of primary switching object for Busbar ProtectionZone Selection BDCGAPC ..................................................241Capacitor bank protection CBPGAPC..................................242Compensated over- and undervoltage protectionCOUVGAPC.........................................................................249General currrent and voltage protection CVGAPC...............251Low active power and power factor protectionLAPPGAPC..........................................................................259Mho Impedance supervision logic ZSMGAPC.....................261Radial feeder protection PAPGAPC.....................................262

    Out-of-step protection PPAM.....................................................264Out-of-step protection OOSPPAM.......................................264PoleSlip/Out-of-step protection PSPPPAM..........................265

    Earth fault protection PHIZ........................................................267ROTIPHIZ (64R)...................................................................267100% Stator earth fault protection, 3rd harmonic basedSTEFPHIZ............................................................................268100% stator earth fault protection, injection basedSTTIPHIZ.............................................................................271

    Voltage-restrained time overcurrent PVOC...............................272Voltage-restrained time overcurrent protectionVRPVOC..............................................................................272

    System logical nodes......................................................................274Generic security application component....................................274

    Table of contents

    670 series 2.0 IEC 5Communication Protocol Manual

  • Generic security application component AGSAL.................274Physical device information LPHD............................................276Logical node zero LLNO............................................................276Dual ethernet port link status PRPSTATUS..............................277

    Logical nodes for protection related functions................................278Breaker failure RBRF................................................................278

    Breaker failure protection 3-phase activation and outputCCRBRF .............................................................................278Breaker failure protection, single phase versionCCSRBRF............................................................................279

    Differential supervision RDIF.....................................................280Current circuit supervision CCSSPVC.................................280

    Disturbance recorder RDRE......................................................281Disturbance report DRPRDRE.............................................281

    Fault locator RFLO....................................................................282Fault locator LMBRFLO........................................................282

    Secondary system supervision SPVC.......................................283Fuse failure supervision SDDRFUF.....................................283Fuse failure supervision based on voltage differenceVDSPVC...............................................................................284

    Pole discordance protection RPLD ...........................................285Pole discordance protection CCPDSC.................................285

    Power swing detection RPSB....................................................286Power swing detection ZMRPSB ........................................286

    Autoreclosing RREC..................................................................287Autorecloser for 1 phase, 2 phase and/or 3 phaseoperation SMBRREC ..........................................................287

    Synchronising RSYN.................................................................292Synchrocheck, energizing check, and synchronizingSESRSYN............................................................................292

    Logical nodes for generic references.............................................297Generic process I/O GGIO........................................................297

    Logic rotating switch for function selection and LHMIpresentation SLGAPC..........................................................297Selector mini switch VSGAPC..............................................299Generic communication function for Double Pointindication DPGAPC..............................................................301Single point generic control 8 signals SPC8GAPC..............301Event counter with limit supervision L4UFCNT....................304IEC61850 generic communication I/O functionsSPGGIO...............................................................................306IEC61850 generic communication I/O functions 16inputs SP16GGIO.................................................................307Generic communication function for Measured ValueMVGAPC..............................................................................308

    Table of contents

    6 670 series 2.0 IECCommunication Protocol Manual

  • Pulse-counter logic PCFCNT...............................................310Trip matrix logic TMAGAPC.................................................311Elapsed time integrator with limit transgression andoverflow supervision TEIGGIO.............................................312

    Logical nodes for metering and measurement...............................313Metering MMTR.........................................................................313

    Function for energy calculation and demand handlingETPMMTR............................................................................313

    Non phase related measurement MMXN..................................317Measurements CVMMXN.....................................................317

    Measurement MMXU.................................................................321Phase current measurement CMMXU.................................321Phase-phase voltage measurement VMMXU......................323Phase-neutral voltage measurement VNMMXU..................324

    Sequence and imbalance MSQI................................................326Current sequence component measurement CMSQI..........326Voltage sequence measurement VMSQI.............................328

    Logical nodes for sensors and monitoring......................................330Circuit breaker monitoring SCBR..............................................330

    Breaker monitoring SSCBR..................................................330Insulation medium supervision (gas) SIMG...............................335

    Gas medium supervision SSIMG.........................................335Insulation medium supervision (liquid) SIML.............................336

    Liquid medium supervision SSIML.......................................336Logical nodes for switchgear..........................................................338

    Circuit breaker XCBR................................................................338Circuit breaker SXCBR.........................................................338

    Switch XSWI..............................................................................340Circuit switch SXSWI............................................................340

    Logical nodes for power transformers............................................343Tap changer YLTC....................................................................343

    Tap changer control and supervision, 6 binary inputsTCMYLTC and TCLYLTC ..................................................343Tap changer control and supervision, 32 binary inputsTCLYLTC.............................................................................346

    Section 8 GOOSE receive blocks................................................349Interlock receive - INTLKRCV........................................................349

    Horizontal communication via GOOSE for interlockingGOOSEINTLKRCV....................................................................349

    Binary Receive - BINRCV ..............................................................350Goose binary receive GOOSEBINRCV.....................................350

    VCTR Receive - VCTRRCV...........................................................351

    Table of contents

    670 series 2.0 IEC 7Communication Protocol Manual

  • Voltage control receiving block for GOOSEGOOSEVCTRRCV....................................................................351

    Double point Receive (DP) - DPRCV ............................................352GOOSE function block to receive a double point valueGOOSEDPRCV.........................................................................352

    Integer Receive - INTRCV..............................................................353GOOSE function block to receive an integer valueGOOSEINTRCV........................................................................353

    Measured Value Receive - MVRCV...............................................353GOOSE function block to receive a measurand valueGOOSEMVRCV........................................................................353

    Single Point Receive (SP) - SPRCV...............................................353GOOSE function block to receive a single point valueGOOSESPRCV.........................................................................353

    Section 9 Glossary.......................................................................355Glossary.........................................................................................355

    Table of contents

    8 670 series 2.0 IECCommunication Protocol Manual

  • Section 1 Introduction

    1.1 This manualThe communication protocol manual describes the communication protocolssupported by the IED. The manual concentrates on the vendor-specificimplementations.

    1.2 Intended audienceThis manual addresses the communication system engineer or system integratorresponsible for pre-engineering and engineering for communication setup in asubstation from an IED perspective.The system engineer or system integrator must have a basic knowledge ofcommunication in protection and control systems and thorough knowledge of thespecific communication protocol.

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 9Communication Protocol Manual

  • 1.3 Product documentation1.3.1 Product documentation set

    IEC07000220-4-en.vsd

    Plann

    ing &

    purch

    ase

    Engin

    eerin

    g

    Instal

    ling

    Comm

    ission

    ing

    Opera

    tion

    Maint

    enan

    ce

    Deco

    mmiss

    ioning

    Deins

    tallin

    g & di

    spos

    al

    Application manualOperation manual

    Installation manualEngineering manual

    Communication protocol manualCyber security deployment guideline

    Technical manual

    Commissioning manual

    IEC07000220 V4 EN

    Figure 1: The intended use of manuals throughout the product lifecycleThe engineering manual contains instructions on how to engineer the IEDs usingthe various tools available within the PCM600 software. The manual providesinstructions on how to set up a PCM600 project and insert IEDs to the projectstructure. The manual also recommends a sequence for the engineering ofprotection and control functions, LHMI functions as well as communicationengineering for IEC 60870-5-103, IEC 61850 and DNP3.The installation manual contains instructions on how to install the IED. Themanual provides procedures for mechanical and electrical installation. The chaptersare organized in the chronological order in which the IED should be installed.The commissioning manual contains instructions on how to commission the IED.The manual can also be used by system engineers and maintenance personnel forassistance during the testing phase. The manual provides procedures for thechecking of external circuitry and energizing the IED, parameter setting and

    Section 1 1MRK 511 302-UEN -Introduction

    10 670 series 2.0 IECCommunication Protocol Manual

  • configuration as well as verifying settings by secondary injection. The manualdescribes the process of testing an IED in a substation which is not in service. Thechapters are organized in the chronological order in which the IED should becommissioned. The relevant procedures may be followed also during the serviceand maintenance activities.The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for the monitoring,controlling and setting of the IED. The manual also describes how to identifydisturbances and how to view calculated and measured power grid data todetermine the cause of a fault.The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also provide assistancefor calculating settings.The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data, sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.The communication protocol manual describes the communication protocolssupported by the IED. The manual concentrates on the vendor-specificimplementations.The point list manual describes the outlook and properties of the data pointsspecific to the IED. The manual should be used in conjunction with thecorresponding communication protocol manual.The cyber security deployment guideline describes the process for handling cybersecurity when communicating with the IED. Certification, Authorization with rolebased access control, and product engineering for cyber security related events aredescribed and sorted by function. The guideline can be used as a technicalreference during the engineering phase, installation and commissioning phase, andduring normal service.

    1.3.2 Document revision historyDocument revision/date History-/May 2014 First release

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 11Communication Protocol Manual

  • 1.3.3 Related documentsDocuments related to REB670 Identify numberApplication manual 1MRK 505 302-UENCommissioning manual 1MRK 505 304-UENProduct guide 1MRK 505 305-BENTechnical manual 1MRK 505 303-UENType test certificate 1MRK 505 305-TEN

    Documents related to REC670 Identify numberApplication manual 1MRK 511 310-UENCommissioning manual 1MRK 511 312-UENProduct guide 1MRK 511 313-BENTechnical manual 1MRK 511 311-UENType test certificate 1MRK 511 313-TEN

    Documents related to RED670 Identify numberApplication manual 1MRK 505 307-UENCommissioning manual 1MRK 505 309-UENProduct guide 1MRK 505 310-BENTechnical manual 1MRK 505 308-UENType test certificate 1MRK 505 310-TEN

    Documents related to REG670 Identify numberApplication manual 1MRK 502 051-UENCommissioning manual 1MRK 502 053-UENProduct guide 1MRK 502 054-BENTechnical manual 1MRK 502 052-UENType test certificate 1MRK 502 054-TEN

    Documents related to REL670 Identify numberApplication manual 1MRK 506 338-UENCommissioning manual 1MRK 506 340-UENProduct guide 1MRK 506 341-BENTechnical manual 1MRK 506 339-UENType test certificate 1MRK 506 341-TEN

    Section 1 1MRK 511 302-UEN -Introduction

    12 670 series 2.0 IECCommunication Protocol Manual

  • Documents related to RET670 Identify numberApplication manual 1MRK 504 138-UENCommissioning manual 1MRK 504 140-UENProduct guide 1MRK 504 141-BENTechnical manual 1MRK 504 139-UENType test certificate 1MRK 504 141-TEN

    670 series manuals Identify numberOperation manual 1MRK 500 118-UENEngineering manual 1MRK 511 308-UENInstallation manual 1MRK 514 019-UENCommunication protocol manual, IEC60870-5-103

    1MRK 511 304-UEN

    Communication protocol manual, IEC 61850Edition 1

    1MRK 511 302-UEN

    Communication protocol manual, IEC 61850Edition 2

    1MRK 511 303-UEN

    Communication protocol manual, LON 1MRK 511 305-UENCommunication protocol manual, SPA 1MRK 511 306-UENAccessories guide 1MRK 514 012-BENCyber security deployment guideline 1MRK 511 309-UENConnection and Installation components 1MRK 513 003-BENTest system, COMBITEST 1MRK 512 001-BEN

    1.4 Document symbols and conventions1.4.1 Symbols

    The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presenceof a hazard which could result in corruption of software or damageto equipment or property.

    The information icon alerts the reader of important facts andconditions.

    The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 13Communication Protocol Manual

  • Although warning hazards are related to personal injury, it is necessary tounderstand that under certain operational conditions, operation of damagedequipment may result in degraded process performance leading to personal injuryor death. It is important that the user fully complies with all warning andcautionary notices.

    1.4.2 Document conventions Abbreviations and acronyms in this manual are spelled out in the glossary. The

    glossary also contains definitions of important terms. Push button navigation in the LHMI menu structure is presented by using the

    push button icons.For example, to navigate between the options, use and .

    HMI menu paths are presented in bold.For example, select Main menu/Settings.

    LHMI messages are shown in Courier font.For example, to save the changes in non-volatile memory, select Yes andpress .

    Parameter names are shown in italics.For example, the function can be enabled and disabled with the Operation setting.

    Each function block symbol shows the available input/output signal. the character ^ in front of an input/output signal name indicates that the

    signal name may be customized using the PCM600 software. the character * after an input/output signal name indicates that the signal

    must be connected to another function block in the applicationconfiguration to achieve a valid application configuration.

    Logic diagrams describe the signal logic inside the function block and arebordered by dashed lines. Signals in frames with a shaded area on their right hand side represent

    setting parameter signals that are only settable via the PST or LHMI. If an internal signal path cannot be drawn with a continuous line, the

    suffix -int is added to the signal name to indicate where the signal startsand continues.

    Signal paths that extend beyond the logic diagram and continue inanother diagram have the suffix -cont.

    Section 1 1MRK 511 302-UEN -Introduction

    14 670 series 2.0 IECCommunication Protocol Manual

  • 1.4.3 Functions included in 670 series IEDsTable 1: Main protection functionsIEC 61850 or functionname

    ANSI Description

    Differential protectionBBP3PH4B 87B Busbar differential protection, 2 zones, three phase/4 bays

    Package including functions BUTPTRC_B1-BUTPTRC_B4, BCZTPDIF, BZNTPDIF_A,BZNTPDIF_B, BZITGGIO, BUTSM4

    BBP3PH8B 87B Busbar differential protection, 2 zones, three phase/8 baysPackage including functions BUTPTRC_B1-BUTPTRC_B8, BCZTPDIF, BZNTPDIF_A,BZNTPDIF_B, BZITGGIO, BUTSM8

    BBP1PH12B 87B Busbar differential protection, 2 zones, single phase/12 baysPackage including functions BUSPTRC_B1-BUSPTRC_B12, BCZSPDIF, BZNSPDIF_A,BZNSPDIF_B, BZISGGIO, BUSSM12

    BBP1PH24B 87B Busbar differential protection, 2 zones, single phase/24 baysPackage including functions BUSPTRC_B1-BUSPTRC_B24, BCZSPDIF, BZNSPDIF_A,BZNSPDIF_B, BZISGGIO, BUSSM24

    BDCGAPC 87B Status of primary switching object for busbar protection zone selectionT2WPDIF 87T Transformer differential protection, two windingT3WPDIF 87T Transformer differential protection, three windingHZPDIF 87 1Ph High impedance differential protectionGENPDIF 87G Generator differential protectionREFPDIF 87N Restricted earth fault protection, low impedanceL3CPDIF 87L Line differential protection, 3 CT sets, 23 line endsL6CPDIF 87L Line differential protection, 6 CT sets, 35 line endsLT3CPDIF 87LT Line differential protection 3 CT sets, with inzone transformers, 23 line endsLT6CPDIF 87LT Line differential protection 6 CT sets, with inzone transformers, 35 line endsLDLPSCH 87L Line differential coordination functionLDRGFC 11REL Additional security logic for differential protectionImpedance protectionZMQAPDIS, ZMQPDIS 21 Distance protection zone, quadrilateral characteristicZDRDIR 21D Directional impedance quadrilateralZMCPDIS, ZMCAPDIS 21 Distance measuring zone, quadrilateral characteristic for series compensated linesZDSRDIR 21D Directional impedance quadrilateral, including series compensationFDPSPDIS 21 Phase selection, quadrilateral characteristic with fixed angleZMHPDIS 21 Full-scheme distance protection, mho characteristicZMMPDIS, ZMMAPDIS 21 Fullscheme distance protection, quadrilateral for earth faultsZDMRDIR 21D Directional impedance element for mho characteristicZDARDIR Additional distance protection directional function for earth faultsZSMGAPC Mho Impedance supervision logicFMPSPDIS 21 Faulty phase identification with load enchroachmentZMRPDIS, ZMRAPDIS 21 Distance protection zone, quadrilateral characteristic, separate settingsFRPSPDIS 21 Phase selection, quadrilateral characteristic with settable angle

    Table continues on next page

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 15Communication Protocol Manual

  • IEC 61850 or functionname

    ANSI Description

    ZMFPDIS 21 High speed distance protectionZMFCPDIS 21 High speed distance protection for series compensated linesZMCAPDIS Additional distance measuring zone, quadrilateral characteristicZMRPSB 68 Power swing detectionPSLPSCH Power swing logicPSPPPAM 78 Pole slip/out-of-step protectionOOSPPAM 78 Out-of-step protectionZCVPSOF Automatic switch onto fault logic, voltage and current basedLEXPDIS 40 Loss of excitationPPLPHIZ Phase preference logicROTIPHIZ 64R Sensitive rotor earth fault protection, injection basedSTTIPHIZ 64S 100% stator earth fault protection, injection basedZGVPDIS 21 Underimpedance protection for generators and transformers

    Table 2: Backup protection functionsIEC 61850 or functionname

    ANSI Description

    Current protectionPHPIOC 50 Instantaneous phase overcurrent protectionOC4PTOC 51_67 Four step phase overcurrent protectionPH4SPTOC 51 Four step single phase overcurrent protectionEFPIOC 50N Instantaneous residual overcurrent protectionEF4PTOC 51N_67

    NFour step residual overcurrent protection

    NS4PTOC 46I2 Four step directional negative phase sequence overcurrent protectionSDEPSDE 67N Sensitive directional residual over current and power protectionLCPTTR 26 Thermal overload protection, one time constant, CelsiusLFPTTR 26 Thermal overload protection, one time constant, FahrenheitTRPTTR 49 Thermal overload protection, two time constantsCCRBRF 50BF Breaker failure protectionCCSRBRF 50BF Breaker failure protection, single phase versionSTBPTOC 50STB Stub protectionCCPDSC 52PD Pole discordance protectionGUPPDUP 37 Directional underpower protectionGOPPDOP 32 Directional overpower protectionBRCPTOC 46 Broken conductor checkCBPGAPC Capacitor bank protectionNS2PTOC 46I2 Negative sequence time overcurrent protection for machinesAEGPVOC 50AE Accidental energizing protection for synchronous generator

    Table continues on next page

    Section 1 1MRK 511 302-UEN -Introduction

    16 670 series 2.0 IECCommunication Protocol Manual

  • IEC 61850 or functionname

    ANSI Description

    VRPVOC 51V Voltage restrained overcurrent protectionGSPTTR 49S Stator overload protectionGRPTTR 49R Rotor overload protectionVoltage protectionUV2PTUV 27 Two step undervoltage protectionOV2PTOV 59 Two step overvoltage protectionROV2PTOV 59N Two step residual overvoltage protectionOEXPVPH 24 Overexcitation protectionVDCPTOV 60 Voltage differential protectionSTEFPHIZ 59THD 100% Stator earth fault protection, 3rd harmonic basedLOVPTUV 27 Loss of voltage checkPAPGAPC 27 Radial feeder protectionFrequency protectionSAPTUF 81 Underfrequency protectionSAPTOF 81 Overfrequency protectionSAPFRC 81 Rate-of-change frequency protectionFTAQFVR 81A Frequency time accumulation protectionMultipurpose protectionCVGAPC General current and voltage protection

    Table 3: Control and monitoring functionsIEC 61850 or functionname

    ANSI Description

    ControlSESRSYN 25 Synchrocheck, energizing check, and synchronizingSMBRREC 79 AutorecloserTR1ATCC 90 Automatic voltage control for tap changer, single controlTR8ATCC 90 Automatic voltage control for tap changer, parallel controlTCMYLTC 84 Tap changer control and supervision, 6 binary inputsTCLYLTC 84 Tap changer control and supervision, 32 binary inputsSLGAPC Logic Rotating Switch for function selection and LHMI presentationVSGAPC Selector mini switchDPGAPC Generic communication function for Double Point indicationSPC8GAPC Single Point Generic Control 8 signalsAUTOBITS AutomationBits, command function for DNP3.0SINGLECMD Single command, 16 signals

    Command function block for LON and SPAVCTRSEND Horizontal communication via GOOSE for VCTRGOOSEVCTRRCV Horizontal communication via GOOSE for VCTR

    Table continues on next page

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 17Communication Protocol Manual

  • IEC 61850 or functionname

    ANSI Description

    I103CMD Function commands for IEC60870-5-103I103GENCMD Function commands generic for IEC60870-5-103I103POSCMD IED commands with position and select for IEC60870-5-103I103IEDCMD IED commands for IEC60870-5-103I103USRCMD Function commands user defined for IEC60870-5-103Apparatus control and interlockingSCILO 3 Logical node for interlockingBB_ES 3 Interlocking for busbar earthing switchA1A2_BS 3 Interlocking for bus-section breakerA1A2_DC 3 Interlocking for bus-section disconnectorABC_BC 3 Interlocking for bus-coupler bayBH_CONN 3 Interlocking for 1 1/2 breaker diameterBH_LINE_A 3 Interlocking for 1 1/2 breaker diameterBH_LINE_B 3 Interlocking for 1 1/2 breaker diameterDB_BUS_A 3 Interlocking for double CB bayDB_BUS_B 3 Interlocking for double CB bayDB_LINE 3 Interlocking for double CB bayABC_LINE 3 Interlocking for line bayAB_TRAFO 3 Interlocking for transformer baySCSWI Switch controllerSXCBR Circuit breakerSXSWI Switch controllerRESIN1 Reservation input 1RESIN2 Reservation input 2POS_EVAL Evaluation of position indicationQCRSV Bay reservationQCBAY Apparatus control

    Function for handling the status of Local/Remote switchLOCREM Handling of LRswitch positionsLOCREMCTRL LHMI control of PSTO

    Function for handling Internal Local/Remote switchSecondary system supervisionCCSSPVC 87 Current circuit supervisionFUFSPVC Fuse failure supervisionVDSPVC 60 Fuse failure supervision based on voltage differenceLogicSMPPTRC 94 Tripping logicTMAGAPC Trip matrix logicALMCALH Logic for group alarmWRNCALH Logic for group warning

    Table continues on next page

    Section 1 1MRK 511 302-UEN -Introduction

    18 670 series 2.0 IECCommunication Protocol Manual

  • IEC 61850 or functionname

    ANSI Description

    INDCALH Logic for group indicationAND Configurable logic blocks, ANDOR Configurable logic blocks, ORINV Configurable logic blocks, inverterPULSETIMER Configurable logic blocks, PULSETIMERGATE Configurable logic blocks, controllable gateTIMERSET Configurable logic blocks, timerXOR Configurable logic blocks, exclusive ORLLD Configurable logic blocks, LLDSRMEMORY Configurable logic blocks, set-reset memoryRSMEMORY Configurable logic blocks, reset-set memoryANDQT Configurable logic blocks Q/T, ANDQTORQT Configurable logic blocks Q/T, ORQTINVERTERQT Configurable logic blocks Q/T, INVERTERQTXORQT Configurable logic blocks Q/T, XORQTSRMEMORYQT Configurable logic Q/T, set-reset with memoryRSMEMORYQT Configurable logic Q/T, reset-set with memoryTIMERSETQT Configurable logic Q/T, settable timerPULSETIMERQT Configurable logic Q/T, pulse timerINVALIDQT Configurable logic Q/T, INVALIDQTINDCOMBSPQT Configurable logic Q/T, single-indication signal combiningINDEXTSPQT Configurable logic Q/T, single-indication signal extractorFXDSIGN Fixed signal function blockB16I Boolean 16 to Integer conversionBTIGAPC Boolean 16 to Integer conversion with Logic Node representationIB16 Integer to Boolean 16 conversionITBGAPC Integer to Boolean 16 conversion with Logic Node representationTIGAPC Delay on timer with input signal integrationTEIGAPC Elapsed time integrator with limit transgression and overflow supervisionMonitoringCVMMXN, CMMXU,VMMXU, CMSQIVMSQI, VNMMXU

    Measurements

    AISVBAS Function block for service value presentation of secondary analog inputsSSIMG 63 Gas medium supervisionSSIML 71 Liquid medium supervisionSSCBR Circuit breaker condition monitoringEVENT Event function

    Function for event reporting for LON and SPATable continues on next page

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 19Communication Protocol Manual

  • IEC 61850 or functionname

    ANSI Description

    DRPRDRE, A1RADR-A4RADR, B1RBDR-B6RBDR

    Disturbance report

    SPGAPC Generic communication function for Single Point indicationSP16GAPC Generic communication function for Single Point indication 16 inputsMVGAPC Generic communication function for Measured ValueBINSTATREP Logical signal status reportRANGE_XP Measured value expander blockLMBRFLO Fault locatorI103MEAS Measurands for IEC60870-5-103I103MEASUSR Measurands user defined signals for IEC60870-5-103I103AR Function status auto-recloser for IEC60870-5-103I103EF Function status earth-fault for IEC60870-5-103I103FLTPROT Function status fault protection for IEC60870-5-103I103IED IED status for IEC60870-5-103I103SUPERV Supervison status for IEC60870-5-103I103USRDEF Status for user defiend signals for IEC60870-5-103L4UFCNT Event counter with limit supervisionMeteringPCFCNT Pulse-counter logicETPMMTR Function for energy calculation and demand handlingSystem protection and controlSMAIHPAC Multipurpose filter

    Table 4: Station communication functionsIEC 61850 or functionname

    ANSI Description

    Station communicationSPA SPA communication protocolADE LON communciation protocolPROTOCOL Operation selection between SPA and IEC60870-5-103 for SLMCHSERRS485 DNP3.0 for TCP/IP and EIA-485 communication protocolDNPFREC DNP3.0 fault records for TCP/IP and EIA-485 communication protocolIEC61850-8-1 Parameter setting function for IEC61850GOOSEINTLKRCV Horizontal communication via GOOSE for interlockingGOOSEBINRCV Goose binary receiveGOOSEDPRCV GOOSE function block to receive a double point valueGOOSEINTRCV GOOSE function block to receive an integer valueGOOSEMVRCV GOOSE function block to receive a measurand value

    Table continues on next page

    Section 1 1MRK 511 302-UEN -Introduction

    20 670 series 2.0 IECCommunication Protocol Manual

  • IEC 61850 or functionname

    ANSI Description

    GOOSESPRCV GOOSE function block to receive a single point valueGOOSEVCTRCONF GOOSE VCTR configuration for send and receiveVCTRSEND Horizontal communication via GOOSE for VCTRGOOSEVCTRRCV Horizontal communication via GOOSE for VCTRMULTICMDRCV,MULTICMDSND

    Multiple command and transmit

    FRONT, LANABI,LANAB, LANCDI,LANCD

    Ethernet configuration of links

    MU1_4I_4U MU2_4I_4UMU3_4I_4U MU4_4I_4UMU5_4I_4U MU6_4I_4U

    Process bus communication IEC61850-9-2

    PRP Duo driver configurationScheme communicationZCPSCH 85 Scheme communication logic for distance or overcurrent protectionZC1PPSCH 85 Phase segregated Scheme communication logic for distance protectionZCRWPSCH 85 Current reversal and weak-end infeed logic for distance protectionZC1WPSCH 85 Current reversal and weak-end infeed logic for phase segregated communicationZCLCPSCH Local acceleration logicECPSCH 85 Scheme communication logic for residual overcurrent protectionECRWPSCH 85 Current reversal and weak-end infeed logic for residual overcurrent protectionDirect transfer tripLAPPGAPC 37_55 Low active power and power factor protectionCOUVGAPC 59_27 Compensated over- and undervoltage protectionSCCVPTOC 51 Sudden change in current variationLCCRPTRC 94 Carrier receive logicLCNSPTOV 47 Negative sequence overvoltage protectionLCZSPTOV 59N Zero sequence overvoltage protectionLCNSPTOC 46 Negative sequence overcurrent protectionLCZSPTOC 51N Zero sequence overcurrent protectionLCP3PTOC 51 Three phase overcurrentLCP3PTUC 37 Three phase undercurrent

    Table 5: Basic IED functionsIEC 61850 or functionname

    Description

    INTERRSIG Self supervision with internal event listSELFSUPEVLST Self supervision with internal event listTIMESYNCHGEN Time synchronization module

    Table continues on next page

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 21Communication Protocol Manual

  • IEC 61850 or functionname

    Description

    SYNCHBIN,SYNCHCAN,SYNCHCMPPS,SYNCHLON,SYNCHPPH,SYNCHPPS,SYNCHSNTP,SYNCHSPA,SYNCHCMPPS

    Time synchronization

    TIMEZONE Time synchronizationDSTBEGIN,DSTENABLE, DSTEND

    GPS time synchronization module

    IRIG-B Time synchronizationSETGRPS Number of setting groupsACTVGRP Parameter setting groupsTESTMODE Test mode functionalityCHNGLCK Change lock functionSMBI Signal matrix for binary inputsSMBO Signal matrix for binary outputsSMMI Signal matrix for mA inputsSMAI1 - SMAI20 Signal matrix for analog inputs3PHSUM Summation block 3 phaseATHSTAT Authority statusATHCHCK Authority checkAUTHMAN Authority managementFTPACCS FTP access with passwordSPACOMMMAP SPA communication mappingSPATD Date and time via SPA protocolDOSFRNT Denial of service, frame rate control for front portDOSLANAB Denial of service, frame rate control for OEM port ABDOSLANCD Denial of service, frame rate control for OEM port CDDOSSCKT Denial of service, socket flow controlGBASVAL Global base values for settingsPRIMVAL Primary system valuesALTMS Time master supervisionALTIM Time managementALTRK Service trackingACTIVLOG Activity logging parametersFSTACCS Field service tool access via SPA protocol over ethernet communicationPCMACCS IED Configuration ProtocolSECALARM Component for mapping security events on protocols such as DNP3 and IEC103DNPGEN DNP3.0 communication general protocol

    Table continues on next page

    Section 1 1MRK 511 302-UEN -Introduction

    22 670 series 2.0 IECCommunication Protocol Manual

  • IEC 61850 or functionname

    Description

    DNPGENTCP DNP3.0 communication general TCP protocolCHSEROPT DNP3.0 for TCP/IP and EIA-485 communication protocolMSTSER DNP3.0 for serial communication protocolOPTICAL103 IEC60870-5-103 Optical serial communicationRS485103 IEC60870-5-103 serial communication for RS485IEC61850-8-1 Parameter setting function for IEC61850HORZCOMM Network variables via LONLONSPA SPA communication protocolLEDGEN General LED indication part for LHMI

    1.4.4 IEC61850 edition 1 / edition 2 mappingTable 6: IEC61850 edition 1 / edition 2 mappingFunction block name Edition 1 logical nodes Edition 2 logical nodesAEGPVOC AEGGAPC AEGPVOCAGSAL SECLLN0

    AGSALAGSAL

    ALMCALH ALMCALHALTIM ALTIMALTMS ALTMSALTRK ALTRKBCZSPDIF BCZSPDIF BCZSPDIFBCZTPDIF BCZTPDIF BCZTPDIFBDCGAPC SWSGGIO BDCGAPCBRCPTOC BRCPTOC BRCPTOCBTIGAPC B16IFCVI BTIGAPCBUSPTRC_B1 BBSPLLN0

    BUSPTRCLLN0BUSPTRC

    BUSPTRC_B2 BUSPTRC BUSPTRCBUSPTRC_B3 BUSPTRC BUSPTRCBUSPTRC_B4 BUSPTRC BUSPTRCBUSPTRC_B5 BUSPTRC BUSPTRCBUSPTRC_B6 BUSPTRC BUSPTRCBUSPTRC_B7 BUSPTRC BUSPTRCBUSPTRC_B8 BUSPTRC BUSPTRCBUSPTRC_B9 BUSPTRC BUSPTRCBUSPTRC_B10 BUSPTRC BUSPTRCBUSPTRC_B11 BUSPTRC BUSPTRCBUSPTRC_B12 BUSPTRC BUSPTRC

    Table continues on next page

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 23Communication Protocol Manual

  • Function block name Edition 1 logical nodes Edition 2 logical nodesBUSPTRC_B13 BUSPTRC BUSPTRCBUSPTRC_B14 BUSPTRC BUSPTRCBUSPTRC_B15 BUSPTRC BUSPTRCBUSPTRC_B16 BUSPTRC BUSPTRCBUSPTRC_B17 BUSPTRC BUSPTRCBUSPTRC_B18 BUSPTRC BUSPTRCBUSPTRC_B19 BUSPTRC BUSPTRCBUSPTRC_B20 BUSPTRC BUSPTRCBUSPTRC_B21 BUSPTRC BUSPTRCBUSPTRC_B22 BUSPTRC BUSPTRCBUSPTRC_B23 BUSPTRC BUSPTRCBUSPTRC_B24 BUSPTRC BUSPTRCBUTPTRC_B1 BBTPLLN0

    BUTPTRCLLN0BUTPTRC

    BUTPTRC_B2 BUTPTRC BUTPTRCBUTPTRC_B3 BUTPTRC BUTPTRCBUTPTRC_B4 BUTPTRC BUTPTRCBUTPTRC_B5 BUTPTRC BUTPTRCBUTPTRC_B6 BUTPTRC BUTPTRCBUTPTRC_B7 BUTPTRC BUTPTRCBUTPTRC_B8 BUTPTRC BUTPTRCBZNSPDIF_A BZNSPDIF BZNSGAPC

    BZNSPDIFBZNSPDIF_B BZNSPDIF BZNSGAPC

    BZNSPDIFBZNTPDIF_A BZNTPDIF BZNTGAPC

    BZNTPDIFBZNTPDIF_B BZNTPDIF BZNTGAPC

    BZNTPDIFCBPGAPC CBPLLN0

    CBPMMXUCBPPTRCHOLPTOVHPH1PTOVPH3PTOCPH3PTUCRP3PDOP

    LLN0CBPPTRCHOLPTOVHPH1PTOVPH3PTOCPH3PTUCRP3PDOP

    CCPDSC CCRPLD CCPDSCCCRBRF CCRBRF CCRBRFCCSRBRF CCSRBRF CCSRBRFCCSSPVC CCSRDIF CCSSPVCCMMXU CMMXU CMMXUCMSQI CMSQI CMSQI

    Table continues on next page

    Section 1 1MRK 511 302-UEN -Introduction

    24 670 series 2.0 IECCommunication Protocol Manual

  • Function block name Edition 1 logical nodes Edition 2 logical nodesCOUVGAPC COUVLLN0

    COUVPTOVCOUVPTUV

    LLN0COUVPTOVCOUVPTUV

    CVGAPC GF2LLN0GF2MMXNGF2PHARGF2PTOVGF2PTUCGF2PTUVGF2PVOCPH1PTRC

    LLN0GF2MMXNGF2PHARGF2PTOVGF2PTUCGF2PTUVGF2PVOCPH1PTRC

    CVMMXN CVMMXN CVMMXNDPGAPC DPGGIO DPGAPCDRPRDRE DRPRDRE DRPRDREECPSCH ECPSCH ECPSCHECRWPSCH ECRWPSCH ECRWPSCHEF4PTOC EF4LLN0

    EF4PTRCEF4RDIRGEN4PHARPH1PTOC

    LLN0EF4PTRCEF4RDIRGEN4PHARPH1PTOC

    EFPIOC EFPIOC EFPIOCETPMMTR ETPMMTR ETPMMTRFDPSPDIS FDPSPDIS FDPSPDISFMPSPDIS FMPSPDIS FMPSPDISFRPSPDIS FPSRPDIS FPSRPDISFTAQFVR FTAQFVR FTAQFVRFUFSPVC SDDRFUF FUFSPVCGENPDIF GENPDIF LLN0

    GENGAPCGENPDIFGENPHARGENPTRC

    GOPPDOP GOPPDOP LLN0GOPPDOPPH1PTRC

    GRPTTR GRPTTR LLN0GRPTTRGRPTUC

    GSPTTR GSPTTR GSPTTRGUPPDUP GUPPDUP LLN0

    GUPPDUPPH1PTRC

    HZPDIF HZPDIF HZPDIFINDCALCH INDCALHITBGAPC IB16FCVB ITBGAPC

    Table continues on next page

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 25Communication Protocol Manual

  • Function block name Edition 1 logical nodes Edition 2 logical nodesL3CPDIF L3CPDIF LLN0

    L3CGAPCL3CPDIFL3CPHARL3CPTRC

    L4UFCNT L4UFCNT L4UFCNTL6CPDIF L6CPDIF LLN0

    L6CGAPCL6CPDIFL6CPHARL6CPTRC

    LAPPGAPC LAPPLLN0LAPPPDUPLAPPPUPF

    LLN0LAPPPDUPLAPPPUPF

    LCCRPTRC LCCRPTRC LCCRPTRCLCNSPTOC LCNSPTOC LCNSPTOCLCNSPTOV LCNSPTOV LCNSPTOVLCP3PTOC LCP3PTOC LCP3PTOCLCP3PTUC LCP3PTUC LCP3PTUCLCPTTR LCPTTR LCPTTRLCZSPTOC LCZSPTOC LCZSPTOCLCZSPTOV LCZSPTOV LCZSPTOVLD0LLN0 LLN0 LLN0LDLPSCH LDLPDIF LDLPSCHLDRGFC STSGGIO LDRGFCLEXPDIS LEXPDIS LLN0

    LEXPDISLEXPTRC

    LFPTTR LFPTTR LFPTTRLMBRFLO LMBRFLO LMBRFLOLOVPTUV LOVPTUV LOVPTUVLPHD LPHD LPHDLT3CPDIF LT3CPDIF LLN0

    LT3CGAPCLT3CPDIFLT3CPHARLT3CPTRC

    LT6CPDIF LT6CPDIF LLN0LT6CGAPCLT6CPDIFLT6CPHARLT6CPTRC

    MVGAPC MVGGIO MVGAPCNS2PTOC NS2LLN0

    NS2PTOCNS2PTRC

    LLN0NS2PTOCNS2PTRC

    Table continues on next page

    Section 1 1MRK 511 302-UEN -Introduction

    26 670 series 2.0 IECCommunication Protocol Manual

  • Function block name Edition 1 logical nodes Edition 2 logical nodesNS4PTOC EF4LLN0

    EF4PTRCEF4RDIRGEN4PHARPH1PTOC

    LLN0EF4PTRCEF4RDIRPH1PTOC

    OC4PTOC OC4LLN0GEN4PHARPH3PTOCPH3PTRC

    LLN0GEN4PHARPH3PTOCPH3PTRC

    OEXPVPH OEXPVPH OEXPVPHOOSPPAM OOSPPAM LLN0

    OOSPPAMOOSPTRC

    OV2PTOV GEN2LLN0OV2PTOVPH1PTRC

    LLN0OV2PTOVPH1PTRC

    PAPGAPC PAPGAPC PAPGAPCPCFCNT PCGGIO PCFCNTPH4SPTOC OCNDLLN0

    GEN4PHARPH1BPTOCPH1PTRC

    LLN0GEN4PHARPH1BPTOCPH1PTRC

    PHPIOC PHPIOC PHPIOCPRPSTATUS RCHLCCH RCHLCCH

    SCHLCCHPSLPSCH ZMRPSL PSLPSCHPSPPPAM PSPPPAM LLN0

    PSPPPAMPSPPTRC

    QCBAY QCBAY LLN0QCRSV QCRSV QCRSVREFPDIF REFPDIF REFPDIFROTIPHIZ ROTIPHIZ LLN0

    ROTIPHIZROTIPTRC

    ROV2PTOV GEN2LLN0PH1PTRCROV2PTOV

    LLN0PH1PTRCROV2PTOV

    SAPFRC SAPFRC SAPFRCSAPTOF SAPTOF SAPTOFSAPTUF SAPTUF SAPTUFSCCVPTOC SCCVPTOC SCCVPTOCSCILO SCILO SCILOSCSWI SCSWI SCSWISDEPSDE SDEPSDE LLN0

    SDEPSDESDEPTOCSDEPTOVSDEPTRC

    Table continues on next page

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 27Communication Protocol Manual

  • Function block name Edition 1 logical nodes Edition 2 logical nodesSESRSYN RSY1LLN0

    AUT1RSYNMAN1RSYNSYNRSYN

    LLN0AUT1RSYNMAN1RSYNSYNRSYN

    SINGLELCCH SCHLCCHSLGAPC SLGGIO SLGAPCSMBRREC SMBRREC SMBRRECSMPPTRC SMPPTRC SMPPTRCSP16GAPC SP16GGIO SP16GAPCSPC8GAPC SPC8GGIO SPC8GAPCSPGAPC SPGGIO SPGAPCSSCBR SSCBR SSCBRSSIMG SSIMG SSIMGSSIML SSIML SSIMLSTBPTOC STBPTOC STBPTOCSTEFPHIZ STEFPHIZ STEFPHIZSTTIPHIZ STTIPHIZ STTIPHIZSXCBR SXCBR SXCBRSXSWI SXSWI SXSWIT2WPDIF T2WPDIF LLN0

    T2WGAPCT2WPDIFT2WPHART2WPTRC

    T3WPDIF T3WPDIF LLN0T3WGAPCT3WPDIFT3WPHART3WPTRC

    TCLYLTC TCLYLTC TCLYLTCTCMYLTC TCMYLTC TCMYLTCTEIGAPC TEIGGIO TEIGAPCTMAGAPC TMAGGIO TMAGAPCTR1ATCC TR1ATCC TR1ATCCTR8ATCC TR8ATCC TR8ATCCTRPTTR TRPTTR TRPTTRUV2PTUV GEN2LLN0

    PH1PTRCUV2PTUV

    LLN0PH1PTRCUV2PTUV

    VDCPTOV VDCPTOV VDCPTOVVDSPVC VDRFUF VDSPVCVMMXU VMMXU VMMXUVMSQI VMSQI VMSQIVNMMXU VNMMXU VNMMXU

    Table continues on next page

    Section 1 1MRK 511 302-UEN -Introduction

    28 670 series 2.0 IECCommunication Protocol Manual

  • Function block name Edition 1 logical nodes Edition 2 logical nodesVRPVOC VRLLN0

    PH1PTRCPH1PTUVVRPVOC

    LLN0PH1PTRCPH1PTUVVRPVOC

    VSGAPC VSGGIO VSGAPCWRNCALH WRNCALHZC1PPSCH ZPCPSCH ZPCPSCHZC1WPSCH ZPCWPSCH ZPCWPSCHZCLCPSCH ZCLCPLAL LLN0

    ZCLCPSCHZCPSCH ZCPSCH ZCPSCHZCRWPSCH ZCRWPSCH ZCRWPSCHZCVPSOF ZCVPSOF ZCVPSOFZGVPDIS ZGVLLN0

    PH1PTRCZGVPDISZGVPTUV

    LLN0PH1PTRCZGVPDISZGVPTUV

    ZMCAPDIS ZMCAPDIS ZMCAPDISZMCPDIS ZMCPDIS ZMCPDISZMFCPDIS ZMFCLLN0

    PSFPDISZMFPDIS

    LLN0PSFPDISZMFPDIS

    ZMFPDIS ZMFLLN0PSFPDISZMFPDIS

    LLN0PSFPDISZMFPDIS

    ZMHPDIS ZMHPDIS ZMHPDISZMMAPDIS ZMMAPDIS ZMMAPDISZMMPDIS ZMMPDIS ZMMPDISZMQAPDIS ZMQAPDIS ZMQAPDISZMQPDIS ZMQPDIS ZMQPDISZMRAPDIS ZMRAPDIS ZMRAPDISZMRPDIS ZMRPDIS ZMRPDISZMRPSB ZMRPSB ZMRPSBZSMGAPC ZSMGAPC ZSMGAPC

    1MRK 511 302-UEN - Section 1Introduction

    670 series 2.0 IEC 29Communication Protocol Manual

  • 30

  • Section 2 Introduction to IEC 61850

    The general scope of the IEC 61850 protocol standard is designed to support thecommunication of all functions being performed in the substation. Its main goal isinteroperability; this is the ability for IEDs from one or different manufacturers toexchange information and use the information for their own functions. Moreover,the standard allows a free allocation of these functions and accepts any systemphilosophy, from a distributed architecture (for example, decentralised substationautomation) to a centralised configuration (for example, RTU based).The standard separates the functionality represented by the data model and therelated communication services from the communication implementation (stack).The data model of the standard is an object-oriented one, grouping the data into thesmallest possible sets referring to the smallest possible functions to beimplemented independently. These smallest possible data groups or functions arenamed logical nodes. The logical nodes and all data and attributes contained arenamed according to a standardised semantic, which is mandatory.This manual describes how the IEC61850 standard is in the 670 series IEDs.References and brief descriptions of the standard are also included. It is assumedthat the reader has basic knowledge of the IEC 61850 standard.The following parts of the IEC61850 standard are of importance as they relate tothis manual: Station Configuration description Language (SCL) is described in IEC

    61850-6. The SCL is an XML based definition of how to describe the parts ofa substation. This part of the standard also includes the roles of different toolsas well as the engineering concepts.

    Communication profile (IEC 61850 stack) is described in IEC 61850-8-1. Thispart of the standard includes a number of possible communication profiles, andhow the services defined in IEC 61850-7-2 are mapped to the communicationprofile.

    Communication services are described in IEC 61850-7-2. This part dealsmainly with the communication facilities from client and server point of view.It includes the different possibilities of communication functionality.

    Logical node data model. This is described in IEC 61850-7-3 and IEC61850-7-4.

    Conformance tests and the basis for conformance documents are handled inIEC 61850-10.

    Detailed information regarding the IEC61850 implementation of the IED 670 isdescribed inside the conformance documents.

    1MRK 511 302-UEN - Section 2Introduction to IEC 61850

    670 series 2.0 IEC 31Communication Protocol Manual

  • MICS, Modeling Information Conformance Statement, contains thedeclaration of the used logical node types.

    PICS, Protocol Information Conformance Statement, contains the details andwhat is supported regarding protocol facilities.

    PIXIT, Protocol Extra Information, contains additional information on how theIEC 61850 is implemented and used.

    TICS, Tissue Information Conformance Statement, contains the supportedTissues, which are handled in the Tissues process as defined by UCA, UtilityCommunication Architecture forum. The Tissues handling is found in http://www.tissue.iec61850.com.

    The conformance documents are unique for each product release and refer to eachother; the identities included in the related documents refer to a specific version ofthe 670 series.The communication profile in IEC 61850 uses the MMS standard, which usesEthernet and TCP/IP to handle the information transport within the substation.The data modelling uses the concept of logical nodes to identify the publishedinformation for communication. The standard defines a set of logical nodes, eachrepresenting a communication view of a process function with a number of dataobjects. For example, a transformer differential - or line differential protection,because the standard defines only a differential protection. Therefore, it is possibleto adapt the logical node, which is defined in the standard, as a logical node class.The standard defines methods to describe the actually used logical node as a logicalnode type which is then based upon the logical node class. This allows all partnersto interpret the logical node type information because the description is completelygiven in the standard. The type description of all logical nodes is part of the DataType Template (DTT) section in the SCL description file of a station or the IED.Besides the information about the configuration of the communication facilities,this manual contains the full description of all logical nodes available in the 670series IED. The information about the logical nodes and their data objects may beused to identify which signals are available for the functions as described in thetechnical manual. The link to the technical manual is done in the logical nodetables by listing the signal name as given in the function block, or as seen inPCM600 or the LHMI.

    2.1.1 Related documentation to IEC 61850Use the latest revision of the documents listed, unless stated otherwise.

    Section 2 1MRK 511 302-UEN -Introduction to IEC 61850

    32 670 series 2.0 IECCommunication Protocol Manual

  • Document ID TitleIEC 61850-5First edition 2003-07Ref. number: IEC 61850-5:2003(E)

    Communication networks and systems insubstations -Part 5:Communication requirements for functions anddevices models

    IEC 61850-6First edition 2004-03Ref. number: IEC 61850-6: 2004(E)

    Communication networks and systems insubstations -Part 6:Configuration description language forcommunication in electrical substations related toIEDs

    IEC 61850-7-1First edition 2003-07Ref. number: IEC 61850-7-1: 2003(E)

    Communication networks and systems insubstations -Part 7-1:Basic communication structure for substationsand feeder equipment -Principles and models

    IEC 61850-7-2First edition 2003-05Ref. number: IEC 61850-7-2: 2003(E)

    Communication networks and systems insubstations -Part 7-2:Basic communication structure for substationsand feeder equipment -Abstract communication service interface (ACSI)

    IEC 61850-7-3First edition 2003-05Ref. number: IEC 61850-7-3: 2003(E)

    Communication networks and systems insubstations -Part 7-3:Basic communication structure for substationsand feeder equipment -Common data classes

    IEC 61850-7-4First edition 2003-05Ref. number: IEC 61850-7-4: 2003(E)

    Communication networks and systems insubstations -Part 7-4:Basic communication structure for substationsand feeder equipment -Compatible logical node classes and data classes

    IEC 61850-8-1First edition 2004-05Ref. number: IEC 61850-8-1: 2004(E)

    Communication networks and systems insubstations -Part 8-1:Specific Communication Service Mapping(SCSM) - Mappings to MMS (ISO 9506-1 andISO 9506-2) and to ISO/IEC 8802-3

    IEC 61850-10First edition 2005-05Ref. number: IEC 61850-10: 2005(E)

    Communication networks and systems insubstations -Part 10:Conformance testing

    IEC 61850 MICS1MRG014230

    670 series version 2.0 Ed1 - MICS:Modelling implementation conformance statement

    IEC 61850 PICS1MRG014288

    670 series version 2.0 Ed1 - PICS:Protocol implementation conformance statement

    IEC 61850 PIXIT1MRG014232

    670 series version 2.0 Ed1 - PIXIT:Protocol implementation extra information

    IEC 61850 TICS1MRG014233

    670 series version 2.0 Ed1 - TICS:Tissue implementation conformance statement

    1MRK 511 302-UEN - Section 2Introduction to IEC 61850

    670 series 2.0 IEC 33Communication Protocol Manual

  • 34

  • Section 3 Substation Configuration descriptionLanguage (SCL)

    Three different types of SCL files - SCD, CID, and ICD, can be exported fromPCM 600.The SCL language is based on XML. However, detailed knowledge of the XMLcontents is not needed.The SCL XML file (ICD/SCD/CID) contains five sections, which are specified inIEC 618506 clause 9. Header Substation section describes the functional structure and its relation to primary

    devices. Communication section describes the connection between the IED access

    points to the respective subnetwork. and includes also the properties(addresses) of the access points.

    IED section contains a description of the supported communication services,the access point(s) and the IEDs logical devices, logical nodes and their attributes.

    Data type template section contains a declaration of all types used in the SCLfile, logical nodes type, DO types, attributes and enums.

    The system structure is defined by the organization of the plant structure inPCM600. The signal engineering and the signal routing are IET600 tasks. The IEDneeds to be configured with PCM600 before the system is configured with IET600.The IED section contains the logical node types included in the respective IEDconfiguration and the data sets and the control blocks configured by IET600. Thedata sets and the control blocks are logically defined as part of the logical nodes(see IEC 6185072 clause 9). IET600 also needs a correctly configuredcommunication section for GOOSE engineering.The data type templates section provides the correct content description of eachlogical node type to all tools and users (clients) of the information. Each IED andvendor may have their own logical node type definitions included in the data typetemplate section together with all other logical node types based on the standard.

    1MRK 511 302-UEN - Section 3Substation Configuration description Language (SCL)

    670 series 2.0 IEC 35Communication Protocol Manual

  • IEC08000178.vsd

    IED Name AccessPoint Address GSEIED Name AccessPoint Address GSE

    Services

    AuthenticationLDevice

    DAI

    DOType

    DAType

    EnumType

    SubstationVoltageLevel

    BayLNode

    IED LD LNIED LD LN

    CommunucationSubnetwork

    Connected AP

    IEDAccessPoint

    Server

    GOOSE Control

    LN0 LNDataSet DOI

    DataTypeTemplates

    Report Control

    Inputs

    DOI

    SettingControl

    LNodeType

    DOType

    DAType

    EnumType

    DO

    DA

    IED

    SDO

    BDA

    Stati

    onCo

    mmun

    IEC08000178 V1 EN

    Figure 2: IEC 61850: Principle structure of the SCL XML fileThe arrows show the link between the different sections given when an IED isintegrated in the substation structure and/or in the communication structure. Allneeded logical nodes of an IED are linked to the substation section by the SC tool.A reference to GOOSE Control Blocks (GoCB) is included in the communicationsection when GoCB is configured.

    3.1 The substation sectionThe substation description in IEC 61850-6 clause 9 describes the arrangement ofthe primary equipment. In addition, it also includes a list of the applied logicalnodes and the relation of those logical nodes to the primary equipment.

    3.2 The communication sectionThe organization of the physical IEDs to the communication network isindependent of the substation structure. The IEC 61850 standard defines the

    Section 3 1MRK 511 302-UEN -Substation Configuration description Language (SCL)

    36 670 series 2.0 IECCommunication Protocol Manual

  • communication network with no relation to an existing media or protocol. Themapping to an existing media and protocol is specified in IEC 6185081.The IEC 61850 standard describes in part 72 the ACSI in a media and protocolindependent form. Part 81 specifies the mapping of this ACSI to the existingMMS.The communication section describes how information is routed between the IEDsand contains the following parts: Subnetworks IEDs connected to different subnetworks Access points per IED to subnetworks Address IP address of LAN network (is exceptionally part of the address elements) Link to GoCB message in transmission direction (extended during signal

    engineering and routing)

    en06000101.vsd

    IED(server)

    - Access Point (AP)- Address- GSE; GoCBs

    Communication

    AP

    IED(server)

    - Access Point (AP)- Address- GSE; GoCBs

    Communication

    IED(server)

    - Access Point (AP)- Address- GSE; GoCBs

    Communication

    AP

    IED(client)

    - Access Point (AP)- Address- GSE; GoCBs

    Communication

    IED(client)

    - Access Point (AP)- Address- GSE; GoCBs

    Communication

    Subnetwork

    IEC06000101 V1 EN

    Figure 3: IEC 618506: Communication networkAdditional information about the server is part of the IED.

    3.3 The IED sectionThe IED section describes the complete IED as it is needed for IEC 61850communication and signal engineering. The data type template part of an IED maybe seen as part of the IED, even when separated in its own section. The IED's ICD

    1MRK 511 302-UEN - Section 3Substation Configuration description Language (SCL)

    670 series 2.0 IEC 37Communication Protocol Manual

  • files include the description of the logical nodes, their data type templates and theused or supported services. The structure of the IED section follows the definitionsmade in the IEC 61850 standard.Two basic IED types are used in system configuration. Station level IEDs

    are located on the station level and are identified as client IEDs when they reador write information from or to the bay IEDs. This functionality is representedby logical nodes of group Information (I). These are the logical nodes (LN)= ITCI, IHMI and ITMI. Client IEDs are the receiver of information inmonitoring direction and sender of commands (control). These logical nodeshave no data objects. They are only used to link the report control blocks(BRCBs) from the server IEDs. They have to read their information about thesignals and the signal configuration from the bay IEDs. This is possible bychecking all control blocks for a link to it as a client.

    Bay level IEDsare located on the bay level and are identified as server IEDs when they reador write information vertically. When GOOSE messages are received, the baylevel IED also has the client role.

    Section 3 1MRK 511 302-UEN -Substation Configuration description Language (SCL)

    38 670 series 2.0 IECCommunication Protocol Manual

  • en06000104.vsd

    AP

    Subnetwork

    Control

    IED

    CVMMXU1

    SB1.LD0

    Server

    LPHDSXCBR1SCSWI1SXSWI1SCSWI2SXSWI2SCSWI3SXSWI3SCSWI4SXSWI4SCSWI5

    LLN0

    Mod

    CBOpCapOrigin

    Data

    DataAttribute

    BehHealth

    NamePltctlValPos

    LocOpCntBlkOpnBlkCls

    stValqt

    LogicalNode

    ctlModel

    IEC06000104 V2 EN

    Figure 4: Organization of LDs, LNs, DOs and DAs in an IED

    A server represents the communication interface to the subnetwork (Ethernet). One or more logical device(s) (LD) are connected to a server. A set of logical nodes belong to a LD. The LN LLN0 is a special logical node per LD and contains for example the

    data sets, the various control blocks, inputs (from GOOSE messages). In IED670 series, the data sets and the control blocks shall be located to LD0.

    The LN LPHD is a special logical node per LD and contains data objects thatdescribe the status of the physical device (the IED)

    Each logical node represents a function and contains a number of data objects(DO)

    Each DO includes a number of data attributes (DA)

    The data objects represent information signals that may be routed to station levelIEDs or to other bay IEDs that are communicating via GOOSE. The signalengineering task is to select the requested signals (DOs) and link them to the clientIEDs as receiver. When using a dataset for MMS, the requested signals are DOsbut when creating a dataset for GOOSE messaging, DAs are used.

    1MRK 511 302-UEN - Section 3Substation Configuration description Language (SCL)

    670 series 2.0 IEC 39Communication Protocol Manual

  • The number of data objects and data attributes per DO is defined by the used LNtype in the IED. The content of logical node types and DO types are defined in theDTT. This also means that the definitions in the DTT section have to be uniquewithin an SCD file.

    3.4 Tool conceptThe IEC 61850-6 defines a number of roles for tools. In the Relion series,PCM600 is defined as the IED tool, and IET600 is defined as the systemengineering tool.The sections in SCL contain properties that are to be configured by these tools.There is no relation between one section and one specific tool. The task of the IEDtool is to configure all properties for the IED, while the system tool has the task todefine the place of the IED in the system and its communication dependencies. Forexample, the plant structure in PCM600 results in the subsystem section in SCLregarding the subsystem structure down to the IED level. The PCM600 alsoconfigures the IED section as a result of the IED configuration. In PCM600, theconfiguration properties for SCL are handled automatically as a result of theconfiguration, except for the receiving of GOOSE information that has adependency with the system tool.IEC 61850 engineering with PCM600, PCM600 IEC61850 Configuration tool andIET600PCM600: When an IED is instantiated, its place in the plant structure creates the

    corresponding structure in the substation section in SCL. The communicationfacilities is also created in the communication section.

    The functionality of the IED is configured by using ACT in PCM600. For eachfunction, the corresponding logical device and logical node(s) is created in theIED section together with its type definition in data type template section

    The above forms the IED capabilities from a communication perspective andwill then be included in the file exported from PCM600 as SCD, ICD or CID file

    PCM600: IEC61850 Configuration tool Included in PCM600 is the new IEC61850 Configuration tool which allows

    the user to define data sets and control blocks for both Client Server andGOOSE communication.

    The IEC61850 Configuration tool gives the user the possibility to make theIEC61850 engineering without export / import step.

    It does NOT however allow the User to define the substation part.

    Section 3 1MRK 511 302-UEN -Substation Configuration description Language (SCL)

    40 670 series 2.0 IECCommunication Protocol Manual

  • IET600: Open a SCD file or import/merge a SCD, ICD or CID file for the particular

    IED(s). For each IED, the user defines the datasets, the control blocks for reporting

    (this means unbufffered/buffered reporting and GOOSE) and the properties foreach report control block.

    Data sets (DS) are generated automatically in PCM600. Reportcontrol blocks (RCBs) are not generated automatically inPCM600.

    If client definitions (like client. ICD) are required in the system configuration,they are merged into IET600 and connected to the unbuffered/buffered reportcontrol blocks.

    Logical nodes, which are not related to the conducting equipment, must beincluded in the bay level in the substation section.

    The resulting SCD file is exported from IET600.

    PCM600:Define the inputs for the client in IET600 and cross-reference the signals in SMT.Import the SCD file to PCM600 to receive GOOSE data. For each IED that shallreceive GOOSE information, the received data is connected to the applicationsusing SMT in PCM600.

    If input signals are not defined for clients in IET600, they will notbe visible in SMT. Inputs (GOOSE clients) can also be defined inPCM600.

    3.5 Engineering concept in IEC 61850-6 Top-down approach means that the system engineering tool has ICD files

    available for each IED to be included in the system configuration. The ICDfiles may be of the template type and represent a pre-configured IED.

    Bottom-up approach means that the configurations are produced by the IEDtool, and that are exported as CID files (or SCD file) to be imported into thesystem tools.

    1MRK 511 302-UEN - Section 3Substation Configuration description Language (SCL)

    670 series 2.0 IEC 41Communication Protocol Manual

  • .IED A IED B IED Z

    Client A Client B

    IEDtool

    Systemtool

    IEC09000151-1-en.vsdIEC09000151 V1 EN

    Figure 5: Relation between system and IED toolsRegardless of the engineering approach, the idea is that the IED tool provides theCID or ICD file for each IED. These ICD/CID files are then imported into thesystem tool and merged into a SCD file, representing the complete substation or apart of the substation, like one for each voltage level.

    Section 3 1MRK 511 302-UEN -Substation Configuration description Language (SCL)

    42 670 series 2.0 IECCommunication Protocol Manual

  • Section 4 Communication profile

    The IEC 61850 standard is conceptually written to be independent of an existingcommunication media and message transmission concept. Out of this, a specificcommunication profile is decided and has been commonly used. The profile contains: Ethernet as the media TCP/IP ISO session and presentation layer MMS (Manufacturing Message Specification (ISO 9506-1 and ISO 9506-2)

    The IEC 61850 standard describes its requested services in ACSI, which iscontained in part 7-2 of the standard. The mapping to the MMS for all aspects ofservices and Ethernet usage is specified in part 8-1 of IEC 61850.Each device manufacturer, which is a partner of an IEC 61850 basedcommunication network, has to take these two specifications and adapt theirrespective product to the requirements and definitions given in the standard. Tomake this profile visible to all other partners, so they can check what they canexpect and what they have to support, the PICS document is defined. The PICScontains in a table based form the possibility of a product or product family.

    IED (server)(61850 services; part 7-2)

    Communication(MMS services; part 8-1)

    - Access Point (AP) / Address- GSE

    IEC08000179.vsd

    AP

    IED (client)(61850 services; part 7-2)

    Subnetwork

    IED (server)(61850 services part; 7-2)

    Communication(MMS services; part 8-1)

    Communication(MMS services; part 8-1)

    - Access Point (AP) / Address- GSE

    - Access Point (AP) / Address- GSE

    IEC08000179 V1 EN

    Figure 6: IEC 61850 Protocol: related standards for communication

    1MRK 511 302-UEN - Section 4Communication profile

    670 series 2.0 IEC 43Communication Protocol Manual

  • SV GOOSE TimeSync(SNTP) MMS Protocol Suite GSSE

    TCP/IPT-Profile

    ISO COT-Profile

    ISO/IEC 8802-2 LLC

    GSSET-ProfileUDP/IP

    ISO/IEC 8802-3 Ethertype

    SampledValues(Multicast)

    GenericObjectOrientedSubstationEvent

    TimeSync

    CoreACSIServices

    GenericSubstationStatusEvent

    ISO/IEC 8802-3IEC09000153-1-en.vsd

    IEC09000153 V1 EN

    Figure 7: Overview of functionality and profiles according to IEC 61850-8-1Out of this content, the implementation in the 670 series supports: GOOSE TimeSync using SNTP The peer-to-peer/vertical communication using MMS protocol suite with the T-

    profile TCP/IP Sampled values according to 9-2LE

    For each of the above, the resulting underlying protocols as stated in Figure 7.See the PICS and PIXIT for more information.

    Section 4 1MRK 511 302-UEN -Communication profile

    44 670 series 2.0 IECCommunication Protocol Manual

  • Section 5 Supported services

    IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describeshow the services are applied in the communication. The conformance documentscontain the description of the supported services in the IED.Services that are not mentioned in this chapter or in the conformance document arenot supported by the IED 670.Data setDefine data sets by the SCD description.Create data sets under LD0/LLN0.

    For more information on data sets, see ABB 670 series version 2.0Ed1 - PIXIT 1MRG014232

    SubstitutionSubstitution is supported for the respective DATA, according to IEC 61850-7-4,that have the substitution attributes defined.Setting group control blockThere is only one setting group control block, which is located in LD0/LLN0(Logical Device/Logical Node 0).Change or edit of setting values as well as reading of setting values is neithersupported nor visible in IEC 61850.

    Note that the actual number of used setting groups is defined by theparameter MaxNoSetGRP in the function SETGRPS, which isconfigured in PST in PCM600. But six setting groups is themaximum and it cannot be exceeded.

    Report control blockFor properties about report control blocks, see PIXIT.UnBuffered reporting as well as Buffered reporting is supported.Generic object oriented substation event (GOOSE)The structured GOOSE is supported. This means that the data sets can be definedwith FCDA as well as explicit attributes.

    1MRK 511 302-UEN - Section 5Supported services

    670 series 2.0 IEC 45Communication Protocol Manual

  • The supported data types to be published and received over GOOSE are binaryvalues, double point values, integer values and measured values, together with theirquality. One signal is available inside the application to validate the reception of aGOOSE message. Invalid means that the correct GOOSE message is not receivedprior 2*TAL(Time Allowed to Live).

    GOOSE with TAL= 0 ms is treated as GOOSE with TAL = 100 msand accepted.

    Note that the data sets that are used or referred to by GOOSEcontrol blocks can only include a data attribute once. In otherwords, there may not be the same data attribute in more than onedata set.

    When publishing a measured value, the user must take care of which measuredvalue data attributes are added to a data set. If the measured value is event-handled(like in the case of MMXU functions), then one can add that value directly to thedata set. If the value is not event-handled, (like in the case of Synchrocheckfunction), it is recommended to connect the value desired to be published to aMVGAPC function block (in ACT) and then use the measured value given by theMVGAPC.Example of functions that have event-handled measured values (can be addeddirectly to the data set). CVMMXN - Measurements CMMXU - Phase current measurement VMMXU - Phase-phase voltage measurement CMSQI - Current sequence component measurement VMSQI - Voltage sequence measurement VNMMXU - Phase-neutral voltage measurement MVGAPC - IEC 61850 generic communication I/ O functions

    Generic function blocks are provided to make available to the 61850 bus signalsthat are not defined inside any of the available function blocks. Example of suchfunctions include: SPGAPC - IEC 61850 generic communication I/ O functions DPGAPC - IEC 61850 generic communication I/ O functions MVGAPC - IEC 61850 generic communication I/ O functions

    ControlOf the different control sequences, the direct-with-normal-security and SBO-with-enhanced security are supported (defined by the ctlModel parameter, IEC61850-7-2).

    Section 5 1MRK 511 302-UEN -Supported services

    46 670 series 2.0 IECCommunication Protocol Manual

  • Check bits; interlock check and synchrocheck check, are only valid for LN typesbased upon CSWI class.Verification of Originator Category is supported, see also PIXIT.

    1MRK 511 302-UEN - Section 5Supported services

    670 series 2.0 IEC 47Communication Protocol Manual

  • 48

  • Section 6 Data sets and control blocks

    6.1 Data setsIEC 61850 has defined data sets and report control blocks to transmit signals formonitoring purposes. Data sets are also used for GOOSE messages in horizontalcommunication among IEDs. The project defines the data objects or single dataattributes that should be collected in a data set. The following figure shows a dataset where all position information of the apparatuses of a bay are put into one dataset.PCM600 will generate default data sets, based on the current ACT configuration.The default data sets can be modified or removed in the engineering tools. NoRCBs are created automatically by PCM600. However, the pre-configured IEDsare delivered with RCBs for all default the data sets.

    en06000106.vsd

    LD0/SXCBR1.Pos FC=STLD0/SXSWI1.Pos FC=STLD0/SXSWI2.Pos FC=STLD0/SXSWI3.Pos FC=STLD0/SXSWI4.Pos FC=ST

    LD0/LLN0.AppPos

    DATA-SET

    CVMMXU1

    LD0

    LPHDSXCBR1SCSWI1SXSWI1SCSWI2SXSWI2SCSWI3SXSWI3SCSWI4SXSWI4SCSWI5

    LLN0

    Origin

    stValqt

    Pos

    Pos

    Pos

    Pos

    Pos

    IEC06000106 V2 EN

    Figure 8: IEC 6185072: Example of a data set for MMSGeneral rules for data set configuration:

    1MRK 511 302-UEN - Section 6Data sets and control blocks

    670 series 2.0 IEC 49Communication Protocol Manual

  • All data objects or their data attributes can be selected for a data set. Only those data attributes of a data object can/