2000 kva transformer - body leakage of 24 a

21
http://cr4.globalspec.com/thread/84286 Farhan Javed Active Contributor Join Date: Jan 2012 Posts: 16 2000 KVA Transformer !od" #ea$a%e of 2& A 0&'10'201( 1:1& A) *i ever"one+ ,e have a 2000 KVA D"n11 Transformer at our site and it is earther from t-o earth .its one for neutra/ and for bod" ,e have recent/" observed that there is a /ea$a%e of 2& A from transformer bod" ust -ant to $no- -hether it is norma/ or not3 )oreover+ cou/d it have an" effect on 4/ectronic Protection 5e/a" insta//ed on the u.stream of transformer *T Pane/7 as -e are often findin% our )ain VC! of *T .ane/ tri..ed sho-in% 488 durin% transformer e9citation startu.7 ,e are usin% iemens; < J602 .rotection re/a" An" su%%estion'comment -ou/d be a..reciated 5e%ards Farhan Javed Comments rated to be =ood Ans-ers: These comments received enou%h .ositive ratin%s to ma$e them >%ood ans-ers> ?1 >Re: 2000 KVA Transformer - Body Leakage of 24 A> b" Tornado on 0&'10'201( 2:&@ A) score 27 ?2 >Re: 2000 KVA Transformer - Body Leakage of 24 A> b" P, /ac$ on 0&'10'201( (:( A) score (7 ? >Re: 2000 KVA Transformer - Body Leakage of 24 A> b" /eve/es on 0&'10'201( 11:( P) score (7 ?20 >Re: 2000 KVA Transformer - Body Leakage of 24 A> b" eu%ene(&& on 0&'12'201( 2:1& A) score 27 Comments rated to be >a/most> =ood Ans-ers:

Upload: abdulyunus-amir

Post on 07-Oct-2015

219 views

Category:

Documents


0 download

DESCRIPTION

2000 KVA Transformer - Body Leakage of 24 A

TRANSCRIPT

http://cr4.globalspec.com/thread/84286Farhan JavedActive Contributor

Join Date: Jan 2012Posts: 162000 KVA Transformer - Body Leakage of 24 A04/10/20131:14 AM

Hi everyone,We have a 2000 KVA Dyn-11 Transformer at our site and it is earther from two earth pits one for neutral and for body. We have recently observed that there is a leakage of 24 A from transformer body. I just want to know whether it is normal or not?Moreover, could it have any effect on Electronic Protection Relay installed on the upstream of transformer (HT Panel) as we are often finding our Main VCB of HT panel tripped showing IE>> during transformer excitation (start-up). We are using Siemens' 7SJ602 protection relay. Any suggestion/comment would be appreciated.RegardsFarhan Javed

Comments rated to be Good Answers:These comments received enough positive ratings to make them "good answers". #1"Re: 2000 KVA Transformer - Body Leakage of 24 A" by Tornadoon 04/10/2013 2:45 AM (score 2) #2"Re: 2000 KVA Transformer - Body Leakage of 24 A" by PWSlackon 04/10/2013 3:38 AM (score 3) #8"Re: 2000 KVA Transformer - Body Leakage of 24 A" by leveleson 04/10/2013 11:38 PM (score 3) #20"Re: 2000 KVA Transformer - Body Leakage of 24 A" by eugene344on 04/12/2013 2:14 AM (score 2)Comments rated to be "almost" Good Answers:Check out these comments that don't yet have enough votes to be "official" good answers and, if you agree with them, rate them! #7"Re: 2000 KVA Transformer - Body Leakage of 24 A" by eugene344on 04/10/2013 10:39 PM (score 1)2TornadoGuru

Join Date: May 2009Location: Ketchikan, AK, USAPosts: 16134Good Answers: 644#1Re: 2000 KVA Transformer - Body Leakage of 24 A04/10/20132:45 AM

The phase-to-ground voltage is probably at least 220 for this transformer. If so, 24A x 220V 5.3KW (and maybe more). That's a lot of energy leakage, and certainly not normal. If you are lucky, it may be something as simple as a loose wire strand, or insulation damage somewhere. In any event, prompt investigation and correction are essential. Good luck in tracking this down quickly and safely.__________________In vino veritas; in cervisia carmen; in aqua E. coli.

Register to ReplyGood Answer (Score 2)

Go to Next Good Answer3PWSlackGuru

Join Date: Jan 2007Location: In the bothy, 7 chains down the line from Dodman's Lane level crossing, in the nation formerly known as Great Britain. Kettle's on.Posts: 22999Good Answers: 594#2Re: 2000 KVA Transformer - Body Leakage of 24 A04/10/20133:38 AM

Look for connections and crosses between the neutral conductor and the ground/earth conductor atalldistribution boxes downstream, and eliminate them. This is an important safety issue, so do it before someone disconnects one of those conductors thinking all is well, and gets an armful of volts for the trouble. Do it today/now/immediately/without delay either.__________________"Did you get my e-mail?" - "The biggest problem in communication is the illusion that it has taken place" - George Bernard Shaw, 1856

Register to ReplyGood Answer (Score 3)

Go to Next Good AnswerJCasePower-User

Join Date: Jul 2007Location: USAPosts: 197Good Answers: 7#15In reply to #2Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/20137:39 AM

I agree with PW.To answer the OP question (again). NO! It is not at all normal! Get working to fix it right now! Follow PW's guidance, as it is good.

Register to Reply

sainath sastryMember

Join Date: Feb 2013Posts: 7#3Re: 2000 KVA Transformer - Body Leakage of 24 A04/10/20139:28 AM

certainly it is more current. make independent neutral earthing with 50X6 mm GI flat, at the same time with Body also. transformer earthing should not connect with grid earthing, check tap operations, may be relay triping on instantaneous current. check settings, commonly megger values, you may found something if you open inspection top cover...like opened winding, etc, carbonised oil.

Register to Reply

electricalexpert65Guru

Join Date: Oct 2009Posts: 2015Good Answers: 164#4Re: 2000 KVA Transformer - Body Leakage of 24 A04/10/20139:29 AM

24A earth leakage current is very dangerous. Indicates some insulation deterioration. Pl. investigate & rectify immediately.

Register to Reply

North of 60Guru

Join Date: Mar 2007Location: Iqaluit, NU. CanadaPosts: 1372Good Answers: 89#5Re: 2000 KVA Transformer - Body Leakage of 24 A04/10/20139:41 AM

Are you saying that the grounding conductor that connects the metal tank/case of this transformer to your earth pit sees a current flow of 24 amps? If so, have you tried to measure the voltage across the circuit between the tank and the earth pit?What happens to this current flow when you unload the transformer? Open its downstream breaker and see what the current flow is.Does the transformer have powered cooling fans mounted on it? If so... check them very carefully.__________________Joe Contractor to Electrical Inspector, "What do you mean you are going to make me follow the code?".

Register to Reply

cuba_peteGuru

Join Date: Dec 2010Posts: 1765Good Answers: 40#6Re: 2000 KVA Transformer - Body Leakage of 24 A04/10/201311:04 AM

From transformer body to where...to neutral, to earth, phase (heaven forbid)?What is the reference?

Register to Reply

eugene344Active Contributor

Join Date: Jun 2011Posts: 24Good Answers: 4#7Re: 2000 KVA Transformer - Body Leakage of 24 A04/10/201310:39 PM

1. PWSLACK has given some guidance on the 24A leakage current. However if the current persists when the LV side is disconnected, you may have a HV fault and this needs to be resolved quickly. With the transformer isolated from supply (HV and LV) check insulation resistance HV to Tank, LV to Tank and HV to LV. Check the arrangement of the HV system neutral earthing.2. The tripping on energising is possibly due to inrush current. ((I>> is usually instantaneous and thus will operate if the inrush is greater than the setting) This can be up to 6 times full load current, and may not be balanced. Review the protection settings to ensure that instantaneous (I>>) settings take account of inrush current.

Register to ReplyScore 1 for Good Answer

No more "Almost" Good Answers.3levelesGuru

Join Date: Jan 2008Posts: 1756Good Answers: 59#8Re: 2000 KVA Transformer - Body Leakage of 24 A04/10/201311:38 PM

Let me put my cynical fly into the ointment, so to speak.Is thatmeasuredcurrent ohmic or capacitive?What is theharmonic content, as measured with an oscilloscope?I do not believe for a moment, that a 5 kWatts real leak can occur,without loud and obvious signs.On the other hand, say, a 100kHz capacitive coupling can do thatcomfortably. And you will not be any wiser, until actually measuringit. So, get on with it!

Register to ReplyGood Answer (Score 3)

Go to Next Good AnswerIQGuru

Join Date: Feb 2013Posts: 615Good Answers: 12#9Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/20132:55 AM

Is it from the transformer or from your MV cables, (earth leakage and cirrcualting earth faults)? Did you disconnect the cables and measure the amps?Also, it is time people defined their voltage ratrher than telling us HT. 11, 22, 33, 66kV, is NOT HT. If you place the correct information here, people can assist you better. i.e voltage, cable type, etc. Cheers.

Register to ReplyScore 1 for Off Topic

electricalexpert65Guru

Join Date: Oct 2009Posts: 2015Good Answers: 164#10In reply to #9Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/20133:25 AM

I am surprised! What are you talking? If 11, 22, 33, 66kV are NOT HT, then what are they? Are they LT?Reference is drawn to IEC 60038, wherein it is mentioned that LV is less than 1kV, HV Range 'A' is above 1kV but less than or equal to 245kV and HV Range 'B' is above 245kV.And, just in case you don't know, LV is Low Voltage & HV is High Voltage.Pl. do not post incorrect statements.

Register to ReplyScore 1 for Off Topic

tcmtechGuru

Join Date: Jun 2009Location: South of Minot North DakotaPosts: 5644Good Answers: 519#11In reply to #10Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/20133:36 AM

He never claimed he was High IQ. Just IQ.__________________"I'm not really and optimist. It just an unpleasant side effect of my medication" tcmtech.

Register to ReplyScore 1 for Off Topic

HiTekRedNekGuru

Join Date: Oct 2006Location: N44564001S44555812E15314192W15302699Posts: 2234Good Answers: 100#12In reply to #10Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/20135:42 AM

As in real estate,location is everything.In power transmission, above 35Kv is considered High Voltage.The IEC defines High Voltage as above 1000Volts for AC and above 1500 volts for DC.The NEC defines it as any voltage above 600 volts AC,and British Standard has it's variance from these definitions also.__________________"I no longer need to run as a presidential candiadate for the socialist party.The Democratic party has adopted our platform."Norman Thomas,1944

Register to ReplyScore 1 for Off Topic

IQGuru

Join Date: Feb 2013Posts: 615Good Answers: 12#13In reply to #10Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/20135:44 AM

Rather than show ignorance here, IEC 60038 is for Standard Voltages. It does not state what is MV, HV or EHV. So dipstick, for your education it works as such.1kv to 132kV Distribution voltage. which covers MV and HV. 11kV is MV, 132kV - 400kV is HV, 500kV and above is EHV and super EHV. 1MV is operational in China. Know you voltages.Electronic Protection Relay installed on the upstream of transformer (HT Panel)As quoted, HT panel?Rather state a voltage then folks know and can help.God help you on a transmission line or sub station. But to answer the lads concern, itcouldbe coming from the Tfx or morelikelythe cable and if this was oil filled cables, there is an earth issue on a cable. If this is XLPE cable it can be the termination, the cable screen, the cable core holed and the semi con leaking into the screen. It could even be a joint breaking down, if there is a joint in the cable. The far side earth protection should have tripped, if the cable is faulted to that side. If it is closer to the near side breaker the fault will not be seen by the relays. And this depends on earthing of the cables. So in your jest, you should perhaps keep quite as there are people who don't waste time with 17th edition as it has no value in 132kV systems. Wipe the shit from your eyes and learn for a change. And I guarantee this is a MV cable fault and very close the to the termination. It just makes it easier when one knows a voltage, rather than assumed terminology. But then if this is NOT your field, then tolerating fools and horses is hard work for us F'wits.Read Note 3, page 10, IEC 60038 Ed 6.2, 2002-07.

Register to Reply

electricalexpert65Guru

Join Date: Oct 2009Posts: 2015Good Answers: 164#17In reply to #13Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/201310:29 AM

Voltage levels have been defined and classified by various National and International Standards as also by certain electric power utility companies. The following are the definitions given in various Indian & International Standards for AC Voltages.******India:As per the Indian Electricity Rules, 1956, vide Rule 2(av), the following are the limits:Low Voltage: Not exceeding 250VMedium Voltage: Not exceeding 650VHigh Voltage: Not exceeding 33000VExtra High Voltage: Exceeding 33000V******But, in IS 13234 - 1992, which is the "Guide for short-circuit current calculation in Three-phase A.C. Systems" - it is mentioned vide Table I that:Low Voltage: 100V to 1000VMedium Voltage: > 1kV to 35kVHigh Voltage: > 35kV to 230kVAs can be seen from the above, there is no harmony between the IS and the IE Rules in this issue.******France:Vide a publication dated 14thNovember 1998, the French Regulations define three voltage levels as below:Low Voltage: < 1kVHigh Voltage A (HTA): > 1kV but 50kV******CENELEC(The European Electrotechnical Standardisation Committee): Vide a publication dated 27thJuly 1992, the CENELEC recognises the following voltage levels:Low Voltage: < 1kVMedium Voltage: > 1kV but 35kV******IEC (International Electrotechnical Commission):In IEC 60071, the following ranges are defined:Low Voltage: < 1kVHighVoltage RangeI: > 1kV but 245kVThe acronyms EHV (Extra High Voltage) and UHV (Ultra High Voltage), though are being used elaborately in India, have never been officially defined in any of the above three standards.USA:i) Vide IEEE Std. 241-1990 (IEEE Recommended Practice for Electric Power Systems in Commercial Buildings), Clause 3.1.1.2,Low Voltage: A class of nominal system voltages 1000V or lessMedium Voltage: A class of nominal system voltages greater than 1000V and less than 100000VHigh Voltage: A class of nominal system voltages equal to or greater than 100000V or less than 230000V******ii) Vide ANSI C84.1-1989 (Voltage ratings for electric power systems and equipment),Low Voltage: 120V to 600VMedium Voltage: 2400V to 69000VHigh Voltage: 115000V to 230000V******iii) Vide ANSI C92.2-1987 (Power Systems - Alternating Current Electrical Systems and Equipment Operating at Voltages above 230kV Nominal - Preferred Voltage Ratings)Extra High Voltage: 345000V to 785000VUltra High Voltage: 1100000V******Note: IEEE - Institution of Electrical and Electronic EngineersANSI - American National Standards Institute******As can be seen from the above, there is no clear cut demarcation for classification of various voltage levels in AC Electric Power Transmission and Distribution. Also, there is no single standard across the globe, with various countries defining various limits for these voltages. And, as in the case of India and USA, even within one country, two standards do not match, when it comes to these limitations. It is wished that the electrical community across the globe meets and takes a decision soon to bring harmony across the countries of the world in standardizing the limits for various voltage classifications.

Register to ReplyScore 1 for Off Topic

Farhan JavedActive Contributor

Join Date: Jan 2012Posts: 16#14Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/20137:35 AM

Thanks everyone for your suggestions and sarcasm!!First of all Trandformer incoming voltage is 11 KV we conducted all the test of transformer like HV to LV Meggar, HV Meggar, LV Meggar, Cable Meggar, TTR, horn conditions and everything is fine.We observed that the leakage is from our downstream network and is being observed at transfromer body as both LT and Transofrmer share a common earth.We removed entire plant load and then tried to reset the VCB but it tripped again!!Transformer vendor has suggested that our protection CTs "5P20" might be entering into saturation region and since we have set 0.0 sec delay on IE>> fault, VCB is being tripped instantly...Interestingly after performing all transformer tests when we reset the VCB it did not tripped and since yesterday it is working fine!!!Regards,Farhan Javed

Register to Reply

PWSlackGuru

Join Date: Jan 2007Location: In the bothy, 7 chains down the line from Dodman's Lane level crossing, in the nation formerly known as Great Britain. Kettle's on.Posts: 22999Good Answers: 594#16In reply to #14Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/20139:06 AM

Did the 24A leak go away at the same time, though?__________________"Did you get my e-mail?" - "The biggest problem in communication is the illusion that it has taken place" - George Bernard Shaw, 1856

Register to Reply

juan J. IsdrayCommentator

Join Date: Jan 2013Posts: 70#19In reply to #14Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/20134:15 PM

Ok Farhan, everyone here has express their best opinion but far away from site, now take your notebook and choice the better of each one because you are touching the problem.Reference to the voltage designation, please check standard ANSI-84 1 -2006 despite voltage designation now is not your top priority.Good luckBye

Register to Reply

2eugene344Active Contributor

Join Date: Jun 2011Posts: 24Good Answers: 4#20In reply to #14Re: 2000 KVA Transformer - Body Leakage of 24 A04/12/20132:14 AM

If LV and HT earths are common, and there is no problem on HV side, the current is probably LV neutral current which is finding parallel paths through neutral to earth connections. Check if the LV neutral is connected to earth at the transformer and another place.As for the HV VCB tripping. What is the CT ratio? Since the transformer is 2000kVA (primary current 104amps), the CT primary is at least 100A. 5p20 will take 2000A before saturating. This is not likely to be the reason for the VCB tripping on Ie>>.Inrush current could be as high as 600A. However this level of current will not always happen as it depends on the point in the cycle that the closing occurs. Sometimes the VCB will not trip, and other times it will.What is the current setting for the Ie>> function? You could put a short time delay (e.g. 0.2 seconds) or increase the current setting if it is too low. The Ie> function with appropriate time setting should pick up low level earth faults

Register to ReplyGood Answer (Score 2)

No more Good Answers.Go to first "Almost" Good AnswerlevelesGuru

Join Date: Jan 2008Posts: 1756Good Answers: 59#18Re: 2000 KVA Transformer - Body Leakage of 24 A04/11/201312:10 PM

I find this thread an exercise in human obtuseness.There is a 24Amps leak somewhere, supposedly.There is no measurement presented, but somebody's say so.Well, I do not believe so.An approximately 5kWatts leakage is loud, cannot be hidden.I asked for some measurements with independent instrumentation, like oscilloscope. The fellow comes back with Meggering parts. By the way, it is Megger, not meggar. Who cares?A relay trips for a reason, that is for sure. That is not sure at all, what the reason is. The relay not tripping for a day for unknown reasons is not an achievement in my book.Actual measurements, anyone. As in verifying, if the 24Amps is real in the first place, and its nature, if it exist at all?!?

Register to Reply

nightshadeAssociate

Join Date: Nov 2011Posts: 48#21In reply to #18Re: 2000 KVA Transformer - Body Leakage of 24 A08/11/20148:54 AM

Hi,Leveles thank you for pointing out the tests. I have taken over maintenance of this particular transformer after my predeccesor Farhan. I conducted the tests. Below are the results;1) Unloaded LT, leakage current on earth : 16A2) Unloaded LT, voltage on transformer body to earth busbar : 0V3) Unloaded LT, voltage on neutral to earth : 0V4) Unloaded LT, leakage current frequency : 150 Hz5) Unloaded LT, leakage current THD : 250%6) Unloaded LT, power quadrant 1, net power 0W, PF 1.00, tan 0.00With LT on load the above values remain same except the frequency changes to 50Hz (our system freq).We do not have an oscilloscope on site, the THD values were noted from a power analyser we use (PEL 100). An interesting observation here is that while the transformer neutral is earthed seperately, the transformer body earth is common with the plant distribution ( body earth connection made to a bus bar where multiple equipment and feeders have been earthed including a generator neutral connection). I do not believe that the leakage is resulting from damage to transformer or some neutral to phase cross over. I do not believe the current is ohmic (though the 1.0 PF seemed disturbing). What are your thoughts?

Register to Reply

HiTekRedNekGuru

Join Date: Oct 2006Location: N44564001S44555812E15314192W15302699Posts: 2234Good Answers: 100#22In reply to #21Re: 2000 KVA Transformer - Body Leakage of 24 A08/11/201410:39 AM

A few questions need answering to satisfy my curiosity,and eliminate some variables that may be obvious to some, but ambiguous to other:Re: The generator you mentioned:Is it running while conducting the tests you mentioned?Do you have a lot of Switch-mode power supplies in the plant;computers,UPS's etc?The fact that the current is a 3rd harmonic indicates such devices on premises that are supplied by another source.Even though the individual currents may be small, due to the nature of 3rd harmonics,the currents are additive.I suspect this may be the source of the current.__________________"I no longer need to run as a presidential candiadate for the socialist party.The Democratic party has adopted our platform."Norman Thomas,1944

Register to Reply

nightshadeAssociate

Join Date: Nov 2011Posts: 48#23In reply to #22Re: 2000 KVA Transformer - Body Leakage of 24 A08/11/201411:56 PM

HiTek the answers to your queries are given below;1) Is the generator running while test was conducted : Yes, Transformer primary was also available, LT was unloaded. Load was on generator.2) Yes there are significant SMPs installed at our plant. UPSes, computers and DC power supplies.3) Why would you say that the current is 3rd harmonic dominanat. Beacuse of the frequency of 150Hz?

Register to Reply

HiTekRedNekGuru

Join Date: Oct 2006Location: N44564001S44555812E15314192W15302699Posts: 2234Good Answers: 100#24In reply to #23Re: 2000 KVA Transformer - Body Leakage of 24 A08/12/20141:08 AM

Yes,the 150hz frequency is the reason,presuming your system is 50hz.Instead of going into possible remedies here, I can direct you to a good source to help resolve your issues.Link:http://www.hammondpowersolutions.com/files/HPS_article_Harmonics_PhaseShifting.pdf__________________"I no longer need to run as a presidential candiadate for the socialist party.The Democratic party has adopted our platform."Norman Thomas,1944

Register to Reply

Register to Reply24 commentsBack to top

Interested in this topic? By joining CR4 you can "subscribe" tothis discussion and receive notification when new comments are added.Join CR4, The Engineer's Place for News and Discussion!Comments rated to be Good Answers:These comments received enough positive ratings to make them "good answers". #1"Re: 2000 KVA Transformer - Body Leakage of 24 A" by Tornadoon 04/10/2013 2:45 AM (score 2) #2"Re: 2000 KVA Transformer - Body Leakage of 24 A" by PWSlackon 04/10/2013 3:38 AM (score 3) #8"Re: 2000 KVA Transformer - Body Leakage of 24 A" by leveleson 04/10/2013 11:38 PM (score 3) #20"Re: 2000 KVA Transformer - Body Leakage of 24 A" by eugene344on 04/12/2013 2:14 AM (score 2)Comments rated to be "almost" Good Answers:Check out these comments that don't yet have enough votes to be "official" good answers and, if you agree with them, rate them! #7"Re: 2000 KVA Transformer - Body Leakage of 24 A" by eugene344on 04/10/2013 10:39 PM (score 1)Copy to ClipboardUsers who posted comments:cuba_pete(1);electricalexpert65(3);eugene344(2);Farhan Javed(1);HiTekRedNek(3);IQ(2);JCase(1);juan J. Isdray(1);leveles(2);nightshade(2);North of 60(1);PWSlack(2);sainath sastry(1);tcmtech(1);Tornado(1)

Previous in Forum:Capacitor Discharge StandardNext in Forum:11kV Generator