LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707 www.lvscontrols.com APPLICATION FEATURES MOUNTING Project: Model No.: Comments: The Model LUT-ATS-D is a single zone, silent emergency transfer control with universal dimming capability. It can be used with 2 and 3-wire line voltage dimming systems, as well as 0-10V, DALI, and Lutron EcoSystem. The LUT-ATS-D allows emergency lighting to be switched and dimmed with the normal lighting. In the event of a utility power interruption, the LUT-ATS-D will automatically transfer designated emergency fixtures from the dimming control to the emergency power source and bring them to full brightness, regardless of whether the dimming system is in operation or turned off. Applications of the LUT-ATS-D include designated dimmable emergency LUT-ATS-D in public places such as auditoriums, restaurants, conference rooms, theaters, and classrooms. Voltage Surge Protection Line Voltage Dimming Includes field-selectable Automatic Testing & Fire Alarm Interface options Triple Interlock (electrical, mechanical, and time delay) maximizes safety and reliability of LUT-ATS-D , by eliminating arcing and the potential for phase to phase shorts between separate power sources during transfer. 5 YEAR WARRANTY 0-10V Dimming Utility & Emergency Power Indicator LED’s Slim, aractive universal mount enclosure allows flush, surface, panel, and box mounting. Integral front mounted test switch Oversized 50A rated relay contacts allow high inrush loads to be used safely and reliably. Tested at over 5000 cycles. Works with both inverter and generator systems, normally-on and normally-off type. U L ® UL1008 LISTED C US LED COMPATIBILE LUT-ATS-D Branch Circuit Emergency Lighting Transfer Switch for 2, 3, and 4-Wire Dimmable Loads

Upload: nguyenkiet

Post on 07-Jul-2019

244 views

Category:

Documents


0 download

TRANSCRIPT

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com

APPLICATION

FEATURES

MOUNTING

Project:

Model No.:

Comments:

The Model LUT-ATS-D is a single zone, silent emergency transfer control with universal dimming capability. It can be used with 2 and 3-wire line voltage dimming systems, as well as 0-10V, DALI, and Lutron EcoSystem.

The LUT-ATS-D allows emergency lighting to be switched and dimmed with the normal lighting. In the event of a utility power interruption, the LUT-ATS-D will automatically transfer designated emergency fixtures from the dimming control to the emergency power source and bring them to full brightness, regardless of whether the dimming system is in operation or turned off.

Applications of the LUT-ATS-D include designated dimmable emergency LUT-ATS-D in public places such as auditoriums, restaurants, conference rooms, theaters, and classrooms.

Voltage Surge Protection

Line Voltage Dimming

Includes field-selectable Automatic Testing & Fire Alarm Interface optionsTriple Interlock (electrical, mechanical, and time delay) maximizes safety and reliability of LUT-ATS-D , by eliminating arcing and the potential for phase to phase shorts between separate power sources during transfer.

5YEAR

WARRANTY

0-10V Dimming

Utility & Emergency Power Indicator LED’s

Slim, attractive universal mount enclosure allows flush, surface, panel, and box mounting.

Integral front mounted test switch

Oversized 50A rated relay contacts allow high inrush loads to be used safely and reliably. Tested at over 5000 cycles.

Works with both inverter and generator systems, normally-on and normally-off type.

UL®UL1008 LISTEDC US

LED COMPATIBILE

LUT-ATS-DBranch Circuit Emergency Lighting Transfer Switch for 2, 3, and 4-Wire Dimmable Loads

SPECIFICATIONS

ORDERING INFORMATION ADDITIONAL RESOURCES

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com20170816_LUT005_Spec

SINGLE LINE DRAWING

WIRING DIAGRAM

LUT-ATS-D Installation InstructionsTheory of Operation & FAQAlternative Wiring Diagrams

Terms & Conditions/Warranty Information Fire Alarm Tie-In/Override www.lvscontrols.com/assets/UL924FAI.pdf

EMERGENCY HOT

#2

NORMAL PANEL

EMERGENCYPOWER

TEST SWITCH

UTILITYPOWER

20A#10

Normal Lights (optional)

EMERGENCY PANEL OR INVERTER

20ANORMAL HOT

NORMAL NEUTRALEMERGENCY NEUTRAL #4

#3

Emergency Light

Note: Emergency Light is also called N/E Light or Normal/Emergency

Light by many specifiers

#12

#13

#11

#1

#7 #9

#5 #6

#8

DESIGNATEDEMERGENCY

LIGHTS

NORMALLIGHTS

UL 1008Transfer SwitchOr Equivalent

NormalUtility Power

Emergency Power Source

(Neutral Not Shown)

LUT-ATS-D

NORMALPANEL

NormalUtility Power

EMERGENCYPANEL OR INVERTER

$

LUT-ATS-D

D

Note: dimmer may be a stand-alone dimmer, multi-zone dimmer (such as Grafik Eye), or central dimming panel. One is required

LUT-ATS-D per dimming zone with emergency lighting.

LUT-ATS-D

Note: Typical 2-Wire Dimming shown. Please see

Installation Instructions for 3-wire and 0-10V Wiring Diagrams.

Fire Alarm Jumper(see additional

resources)

MODEL NO.

SENSING INPUT

LOAD RATING

BALLAST LOAD RATING

INCANDESCENT LOAD

WARRANTY

LUT-ATS-D

120V-277V

120V - 277V (16A)

16A Magnetic/16A Electronic

1920W (120V) / 4432W (277V)

5 Year Replacement Warranty

ELECTRICAL

MOUNTING

RATING

SHIPPING WEIGHT/ COLOR

TEMPERATURE

FLUSH MOUNTED SIZE

BODY SIZE

4-11/16” Back-up Box, no plaster ring required

UL94V-0

18 oz. / White

32ºF - 140ºF (0ºC - 60ºC)

6” x 6” x 0.5”

4” x 4” x 2.3”

MECHANICAL