2.2 | valid addresses for sdiresource.boschsecurity.us/documents/b901_inguide_installation... · i...

2
1 | Overview 3.4 | Wire to the SDI control panel Callout ― Description 1 ― Bosch control panel (GV3 shown) 2 ― Terminal wiring 3 ― B901 Access Control Module 4 ― Interconnect cable (P/N: F01U79745) (included) Figure 3.3: SDI wiring from control panel to B901 2.2 | Valid addresses for SDI Valid B901 addresses are dependant on the number of modules allowed and the desired failure mode (Fail Safe, Fail Secure) by a particular control panel. SDI2 RESET ZONEX T AMPER SDI2 PWR+/R A/Y B/G C OM/B PWR+/R A/Y B/G C OM/B 24 25 26 27 28 29 23 26 W ARNI N G! Multi-Ba t t e r y installation r e q ui r e s Dual Ba t t e r y r n es I r i r r Ba t t e r y R e r t y ea r t one or t t t e r i e Ba t t e r y R e r t y ea r t one or t t t e r i e Ba t t e r y R e r t y ea r t one or t t t e r i e 3 2 SDI2 RESET ZONEX T AMPER SDI2 PWR+/R A/Y B/G C OM/B PWR+/R A/Y B/G C OM/B 24 25 26 27 28 29 23 26 W ARNI N G! Multi-Ba t t e r y installation r e q ui r e s Dual Ba t t e r y r n es I r i r r Ba t t e r y R e r t y ea r t one or t t t e r i e Ba t t e r y R e r t y ea r t one or t t t e r i e Ba t t e r y R e r t y ea r t one or t t t e r i e 3 4 1 1 B G Y R Callout ― Description 1 ― Bosch control panel (B9512G shown) 2 ― Terminal wiring 3 ― B901 Access Control Module 4 ― Interconnect cable (P/N: F01U79745) (included) Figure 3.2: SDI2 wiring from control panel to B901 R Y G B R Y G B R Y G B Commercial Protected-Premises Control Panel D9412GV3 Control Panel is UL Listed For Central Station, Remote Station, Local, Auxiliary, Proprietary, and Household Fire Alarm, and VOLTAGE RANGES Open 3.7 - 5.0 VDC Short 0.0 - 1.3 VDC Normal 2.0 - 3.0 VDC Reset Pin Disable all except Battery Charging and Programming PERIPHERAL DEVICE CONNECTIONS RED POWER + YELLOW DATA BUS A GREEN DATA BUS B BLACK COMMON ZONEX OUT 1 ZONEX IN 1 NFPA Style 4.0 Signaling Line Circuits D9412GV3 26 25 ZONEX POWER + 24 ZONEX COMMON 23 SDI Connector ZONEX OUT 2 ZONEX IN 2 Battery: Replace every 3 to 5 years with one or two Model D126 or D1218 12 V Lead Acid Batteries. Operation Monitor LED Pulses when Normal Flickers when Ringing Point 8, S3 Option 25 Point 4 16 Point 5 Point 6 17 19 Point 7 Point 8 21 20 22 Minimum system reuirements or Classiication in accordance with ANSISIACP-01-2007: UL Listed and Classiied control unit Model D9412GV3, D7412GV3, or D7212GV3 UL Listed and Classiied keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW WARNING To prevent risk o electric shock, disconnect AC power and telephone lines beore servicing. 18 15 Not suitable or remote st ation protected premises services where separate transmission circuits Commercial Protected-Premises Control Panel D9412GV3 Control Panel is UL Listed For Central Station, Remote Station, Local, Auxiliary, Proprietary, and Household Fire Alarm, and VOLTAGE RANGES Open 3.7 - 5.0 VDC Short 0.0 - 1.3 VDC Normal 2.0 - 3.0 VDC Reset Pin Disable all except Battery Charging and Programming PERIPHERAL DEVICE CONNECTIONS RED POWER + YELLOW DATA BUS A GREEN DATA BUS B BLACK COMMON ZONEX OUT 1 ZONEX IN 1 NFPA Style 4.0 Signaling Line Circuits D9412GV3 26 25 ZONEX POWER + 24 ZONEX COMMON 23 SDI Connector ZONEX OUT 2 ZONEX IN 2 Battery: Replace every 3 to 5 years with one or two Model D126 or D1218 12 V Lead Acid Batteries. Operation Monitor LED Pulses when Normal Flickers when Ringing Point 8, S3 Option 25 Point 4 16 Point 5 Point 6 17 19 Point 7 Point 8 21 20 22 Minimum system reuirements or Classiication in accordance with ANSISIACP-01-2007: UL Listed and Classiied control unit Model D9412GV3, D7412GV3, or D7212GV3 UL Listed and Classiied keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW WARNING To prevent risk o electric shock, disconnect AC power and telephone lines beore servicing. 18 15 Not suitable or remote st ation protected premises services where separate transmission circuits 1 1 3 3 2 4 3 | Installation After you set the address switch for the proper address, install the module in the enclosure, and then wire it to the control panel. CAUTION! Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage. 3.1 | Mount the module in the enclosure Mount the module into the enclosure’s 3-hole mounting pattern using the supplied mounting screws and mounting bracket. Refer to Figure 3.1. Figure 3.1: Mounting the module in the enclosure Callout ― Description 1 ― Module with mounting bracket installed 2 ― Enclosure 3 ― Mounting screws (3) 4 2 PWR A B COM B 3 1 B RELAY C EARTH G R OUND C OMMON 10 9 8 7 W ARNI N G! Multi-B a t t e r y in s t all a tion r e q ui r e s Model D122 or D122L Dual B a t t e r y Ha r n e s s. I m p r oper in s t all a tion can be a f i r e haza r d . W equipment. any output must be supervised. The s y s t cont r D A C, O T , N This e q Ala r W servicing. OUTPUT B (2) OUTPUT C (3) R Callout ― Description 1 ― Control panel COM terminal (B9512G shown) 2 ― 12 VDC regulated power-limited power supply (B520 shown) 3 ― Terminal wiring (PWR and COM terminal wiring) 4 ― B901 Access Control Module Figure 3.5: Wiring the card reader to the B901 3.6 | Wire to 12VDC power supply (optional) Refer to Figure 3.5 to wire additional power to a regulated power- limited power supply for fire protective signaling units and commercial/ residential burglar units. Control panel Valid B901 addresses Designation B9512G/B9512G-E/ B8512G/B8512G-E D9412GV4/D7412GV4 D9412GV3/D7412GV3 D9412GV2/D7412GV2, D9000 81 - 88 Devices 1 - 8 Fail Safe mode = door unlocked 91-98 Devices 1 - 8 Fail Se- cure = door locked 3.5 | Wire to the card reader Use the terminals labeled LED, DATA1, DATA0, 5.2V or 12V, COM, and T+ when wiring the module to a card reader. Refer to Figure 3.4. 3.2 | Mount the access card reader Refer to your access card reader installation instructions for proper installation and maintenance procedures related to your supported card reader. 2.1 | Valid addresses for SDI2 Valid B901 addresses are dependant on the number of modules allowed by a particular control panel. Control panel Valid B901 addresses Designation B9512G/B9512G-E 01 - 32 Devices 1 - 32 B8512G/B8512G-E 01 - 08 Devices 1 - 8 3.3 | Wire to the SDI2 control panel When you wire the module to a control panel, use the control panel terminals labeled R, Y, G, B (PWR, A, B, COM). Connect them to the module terminals labeled R, Y, G, B (PWR, A, B, COM). Use either terminal strip wiring or interconnect wiring connector to the control panel. Do not use both. Refer to Figures 3.2 - 3.3. W Br G B P T+ COM ZN+ RTE COM REX 12V 5.2V 2 1 3 DATA DATA BUZZ LED 0 1 R Callout ― Description 1 ― Card reader (ARD-AYK12 shown) 2 ― Terminal wiring 3 ― B901 Access Control Module Figure 3.4: Wiring the card reader to the B901 DOOR NC C N0 PWR A B COM 1 5 2 3 DOOR NC C N0 PWR A B COM 1 5 2 4 3 Callout ― Description 1 ― Door 2 ― B901 door lock relay terminal 3 ― B901 terminal 4 ― AUX PWR terminal (12 VDC) (B520 shown) 5 ― Door strike (12 VDC) Figure 3.6: Wiring the door strike to the B901 Compatible Credential Formats 37 bit HID H10304 (With Site Code) 37 bit HID H10302 (No Site Code) 26 bit HID H10301 EM-EM4200 (3-byte or 5-byte) Control panel Valid B901 addresses Designation B6512 01 - 04 Devices 1 - 4 2 | Address settings Two address switches determine the address for the B901 Access Control Module. The control panel uses the address for communications. The address also determines the output numbers. Use a slotted screwdriver to set the two address switches. NOTICE! The module reads the address switch setting only during power up. If you change the switches after you apply power to the module, you must cycle the power to the module in order for the new setting to be enabled. Set the address switches per the control panel configuration. If multiple B901 modules reside on the same system, each B901 module must have a unique address. Figure 2.1 shows the address switch settings for address 01. Figure 2.1: Address switches NOTICE! Use only Access Control listed power supplies for powering door strikes. NOTICE! B901 tamper generates an SDI - “Missing Door” or an SDI2 - “Module Tamper” message (if Enclosure Tamper parameter is set to Yes). 3.7 | Wire to the door strike A relay provides a dry contact single pull double throw output. Some strikes require a closed circuit to unlock the door, while others require an open circuit to unlock the door. Common (C). For 12/24 VDC strikes, provide input power here from the power supply. Refer to Figure 3.6. Normally closed (NC). For door strikes that require an interruption of power to open. Connect the positive side of the door strike to the NC terminal. Refer to Figure 3.6. Normally open (NO). For door strikes that require power to open. Connect the positive side of the door strike to the NO terminal. Refer to Figure 3.6. The B901 Access Control module is a fully supervised SDI2/SDI device that allows access control integration for compatible control panels. Each module can store up to 2000 user tokens (on SDI2), each with a different access level for each door. Authority for access is controlled by the user’s authority level, the time of day, the state of the door, and the armed state to the module. READER T+ COM ZN+ RTE COM REX 12V 5.2V DATA0 DATA1 BUZZER LED NC C N0 PWR A B COM 2 3 4 5 RELAY 1 6 7 8 Figure 1.1: Access control module Callout ― Description 1 ― Terminal connector 2 ― Interconnect wiring connectors 3 ― Address switch 4 ― Reader LED 5 ― Heartbeat LED (blue) 6 ― Reader and door terminals 7 ― Relay terminals 8 ― Relay LED

Upload: tranxuyen

Post on 30-Oct-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

1 | Overview

3.4 | Wire to the SDI control panel

Callout ― Description1 ― Bosch control panel (GV3 shown)2 ― Terminal wiring3 ― B901 Access Control Module4 ― Interconnect cable (P/N: F01U79745) (included)

Figure 3.3: SDI wiring from control panel to B901

2.2 | Valid addresses for SDIValid B901 addresses are dependant on the number of modules allowed and the desired failure mode (Fail Safe, Fail Secure) by a particular control panel.

SD

I2

RESETZONEX TAMPER

SDI2

PWR+/R

A/Y

B/G

COM/B

PWR+/R

A/Y

B/G

COM/B

24

25

26

27

28

29

23

26

WARNING!Multi-Battery installation requires

Dual Battery rnesI r

ir r

Battery Rer t year t

one or t

tterie

Battery Rer t year t

one or t

tterie

Battery Rer t year t

one or t

tterie

32

SD

I2

RESETZONEX TAMPER

SDI2

PWR+/R

A/Y

B/G

COM/B

PWR+/R

A/Y

B/G

COM/B

24

25

26

27

28

29

23

26

WARNING!Multi-Battery installation requires

Dual Battery rnes I r

ir r

Battery Rer t year t

one or t

tterie

Battery Rer t year t

one or t

tterie

Battery Rer t year t

one or t

tterie

3

4

1 1

BG

YR

Callout ― Description1 ― Bosch control panel (B9512G shown)2 ― Terminal wiring3 ― B901 Access Control Module4 ― Interconnect cable (P/N: F01U79745) (included)

Figure 3.2: SDI2 wiring from control panel to B901

R

Y

G

B

R

Y

G

B

RYGB

Commercial Protected-Premises Control Panel

D9412GV3 Control Panel is UL Listed For Central Station, Remote Station, Local, Auxiliary, Proprietary, and Household Fire Alarm, and

VOLTAGE RANGESOpen� 3.7 - 5.0 VDC Short 0.0 - 1.3 VDCNormal� 2.0 - 3.0 VDC

Reset PinDisable all except Battery

Charging and Programming

PERIPHERAL DEVICE CONNECTIONS

RED POWER +

YELLOW DATA BUS A

GREEN DATA BUS B

BLACK COMMON

ZONEX OUT 1

ZONEX IN 1

NFPAStyle 4.0SignalingLineCircuits

D9412GV3

26

25

ZONEX POWER + 24

ZONEX COMMON 23

SDI Connector

ZONEX OUT 2

ZONEX IN 2

Battery: Replace every 3 to5 years with one or two Model �D126 or D1218 12 V Lead Acid �Batteries.

Operation Monitor LED Pulses when Normal Flickers when RingingGREEN

Point 8, S3 Option

25

Point 4

16

Point 5 Point 6

17 19

Point 7 Point 8

2120 22

Minimum system re�uirements �or Classi�ication in accordance with ANSI�SIA CP-01-2007:UL Listed and Classi�ied control unit Model D9412GV3, D7412GV3, or D7212GV3�UL Listed and Classi�ied keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW�

WARNING�To prevent risk o� electric shock, disconnect AC power and telephone lines be�ore servicing. �

1815

Not suitable �or remote station protected premises services where separate transmission circuits

Commercial Protected-Premises Control Panel

D9412GV3 Control Panel is UL Listed For Central Station, Remote Station, Local, Auxiliary, Proprietary, and Household Fire Alarm, and

VOLTAGE RANGESOpen� 3.7 - 5.0 VDC Short 0.0 - 1.3 VDCNormal� 2.0 - 3.0 VDC

Reset PinDisable all except Battery

Charging and Programming

PERIPHERAL DEVICE CONNECTIONS

RED POWER +

YELLOW DATA BUS A

GREEN DATA BUS B

BLACK COMMON

ZONEX OUT 1

ZONEX IN 1

NFPAStyle 4.0SignalingLineCircuits

D9412GV3

26

25

ZONEX POWER + 24

ZONEX COMMON 23

SDI Connector

ZONEX OUT 2

ZONEX IN 2

Battery: Replace every 3 to5 years with one or two Model �D126 or D1218 12 V Lead Acid �Batteries.

Operation Monitor LED Pulses when Normal Flickers when RingingGREEN

Point 8, S3 Option

25

Point 4

16

Point 5 Point 6

17 19

Point 7 Point 8

2120 22

Minimum system re�uirements �or Classi�ication in accordance with ANSI�SIA CP-01-2007:UL Listed and Classi�ied control unit Model D9412GV3, D7412GV3, or D7212GV3�UL Listed and Classi�ied keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW�

WARNING�To prevent risk o� electric shock, disconnect AC power and telephone lines be�ore servicing. �

1815

Not suitable �or remote station protected premises services where separate transmission circuits

1 1

3

3

2

4

3 | InstallationAfter you set the address switch for the proper address, install the module in the enclosure, and then wire it to the control panel.

CAUTION!Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.

3.1 | Mount the module in the enclosureMount the module into the enclosure’s 3-hole mounting pattern using the supplied mounting screws and mounting bracket. Refer to Figure 3.1.

Figure 3.1: Mounting the module in the enclosure

Callout ― Description1 ― Module with mounting bracket installed2 ― Enclosure3 ― Mounting screws (3)

4

2

PWR A B COM

B

31

B

RELAY C

EARTH GROUND

COMMON

10

9

8

7

WARNING! Multi-Battery installation requiresModel D122 or D122L Dual Battery Harness. Improper installation can be a fire hazard.

W

equipment.

any output must be supervised.

The systcontrDAC, OT, NThis eqAlar

W

servicing.

OUTPUTB (2)

OUTPUTC (3)

R

Callout ― Description1 ― Control panel COM terminal (B9512G shown)

2 ― 12 VDC regulated power-limited power supply (B520 shown)

3 ― Terminal wiring (PWR and COM terminal wiring)

4 ― B901 Access Control Module

Figure 3.5: Wiring the card reader to the B901

3.6 | Wire to 12VDC power supply (optional)Refer to Figure 3.5 to wire additional power to a regulated power-limited power supply for fire protective signaling units and commercial/residential burglar units.

Control panel Valid B901 addresses

Designation

B9512G/B9512G-E/B8512G/B8512G-ED9412GV4/D7412GV4D9412GV3/D7412GV3D9412GV2/D7412GV2,D9000

81 - 88 Devices 1 - 8Fail Safe mode = door unlocked

91-98 Devices 1 - 8 Fail Se-cure = door locked

3.5 | Wire to the card readerUse the terminals labeled LED, DATA1, DATA0, 5.2V or 12V, COM, and T+ when wiring the module to a card reader. Refer to Figure 3.4.

3.2 | Mount the access card readerRefer to your access card reader installation instructions for proper installation and maintenance procedures related to your supported card reader.

2.1 | Valid addresses for SDI2Valid B901 addresses are dependant on the number of modules allowed by a particular control panel.

Control panel Valid B901 addresses

Designation

B9512G/B9512G-E 01 - 32 Devices 1 - 32

B8512G/B8512G-E 01 - 08 Devices 1 - 8

3.3 | Wire to the SDI2 control panelWhen you wire the module to a control panel, use the control panel terminals labeled R, Y, G, B (PWR, A, B, COM). Connect them to the module terminals labeled R, Y, G, B (PWR, A, B, COM). Use either terminal strip wiring or interconnect wiring connector to the control panel. Do not use both. Refer to Figures 3.2 - 3.3.

W

Br

G

B

P

T+ COM

ZN+ RTE

COM

REX 12V 5.2V

21 3

DATA

DATA

BUZZ LED

0 1

R

Callout ― Description1 ― Card reader (ARD-AYK12 shown)2 ― Terminal wiring3 ― B901 Access Control Module

Figure 3.4: Wiring the card reader to the B901

DOOR

NC

C N

0

PWR A B COM

1

5

2

3

DOOR

NC

C N

0

PWR A B COM

1

5

2

4

3

Callout ― Description1 ― Door2 ― B901 door lock relay terminal3 ― B901 terminal4 ― AUX PWR terminal (12 VDC) (B520 shown)5 ― Door strike (12 VDC)

Figure 3.6: Wiring the door strike to the B901

Compatible Credential Formats37 bit HID H10304 (With Site Code)37 bit HID H10302 (No Site Code)26 bit HID H10301 EM-EM4200 (3-byte or 5-byte)

Control panel Valid B901 addresses

Designation

B6512 01 - 04 Devices 1 - 4

2 | Address settingsTwo address switches determine the address for the B901 Access Control Module. The control panel uses the address for communications. The address also determines the output numbers. Use a slotted screwdriver to set the two address switches.

NOTICE!The module reads the address switch setting only during power up. If you change the switches after you apply power to the module, you must cycle the power to the module in order for the new setting to be enabled.

Set the address switches per the control panel configuration. If multiple B901 modules reside on the same system, each B901 module must have a unique address. Figure 2.1 shows the address switch settings for address 01.

Figure 2.1: Address switches

NOTICE!Use only Access Control listed power supplies for powering door strikes.

NOTICE!B901 tamper generates an SDI - “Missing Door” or an SDI2 - “Module Tamper” message (if Enclosure Tamper parameter is set to Yes).

3.7 | Wire to the door strikeA relay provides a dry contact single pull double throw output. Some strikes require a closed circuit to unlock the door, while others require an open circuit to unlock the door.• Common (C). For 12/24 VDC strikes, provide input power here

from the power supply. Refer to Figure 3.6.• Normally closed (NC). For door strikes that require an interruption

of power to open. Connect the positive side of the door strike to the NC terminal. Refer to Figure 3.6.

• Normally open (NO). For door strikes that require power to open. Connect the positive side of the door strike to the NO terminal. Refer to Figure 3.6.

The B901 Access Control module is a fully supervised SDI2/SDI device that allows access control integration for compatible control panels. Each module can store up to 2000 user tokens (on SDI2), each with a different access level for each door. Authority for access is controlled by the user’s authority level, the time of day, the state of the door, and the armed state to the module.

READERT+ COM ZN+ RTE COM REX 12V 5.2V DATA0 DATA1 BUZZER LEDNC C N0

PW

R A B

CO

M

2 3

45

RELAY

1

67

8

Figure 1.1: Access control module

Callout ― Description1 ― Terminal connector2 ― Interconnect wiring connectors3 ― Address switch4 ― Reader LED5 ― Heartbeat LED (blue)6 ― Reader and door terminals7 ― Relay terminals8 ― Relay LED

Bosch Security Systems, Inc.130 Perinton ParkwayFairport, NY 14450USAwww.boschsecurity.com

© 2017 Bosch Security Systems, Inc. F.01U.300.416 | 10 | 2017.01

Bosch Sicherheitssysteme GmbHRobert-Bosch-Ring 585630 GrasbrunnGermany

CopyrightThis document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.

TrademarksAll hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.Bosch Security Systems, Inc. product manufacturing datesUse the serial number located on the product label and refer to theBosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.

8 | SpecificationsDimensions 2.9 in x 5.0 in x 0.6 in (73.5 mm x 127 mm x 15.25

mm)Voltage (input) 12 VDC nominalCurrent Standby: 110 mA + reader current

Alarm: 110 mA + reader currentAlarm output Form C relay (NC, COM, NO) at 12/24 V @ 2.0 AOperatingtemperature

0°C to +50°C (+32°F to +122°F)

Relative humidity 5% to 93% at +32°C (+90°F) non-condensingTerminal wire size 18 AWG to 22 AWG (1.02 mm to 0.65 mm)SDI2/SDI wiring to B901 + Reader with external power supply

Maximum distance - wire size (unshielded wire only): 1000 ft (305 m) - 22 AWG (0.65 mm), 2500 ft (762 m) - 18 AWG (1.02 mm)

SDI2/SDI wiring to B901 + Reader from control panel

175 ft (53 m) - 22 AWG (0.65 mm), 450 ft (137 m) - 18 AWG (1.02 mm)

Wiring distance from B901 to Reader

200 ft (61 m) - 22 AWG (0.65 mm), 500 ft (152 m) - 18 AWG (1.02 mm) Reader dependant

Bosch compatiblecontrol panels

B9512G/B9512G-E/B8512G/B8512G-E/B6512/D9412GV4/D7412GV4/D9412GV3/D7412GV3/D9412GV2/D7412GV2/D9412G/D7412G (Refer to the control panel installation document for the number of supported devices.)

Bosch compatiblereaders andaccessories

ARD-AYH12 EM Prox Wall MountARD-AYJ12 EM Prox MullionARD-AYK12 EM Prox Mini MullionARD-AYQ12 EM Prox Wall Mount Vandal ResistantARD-AYCE65B EM Prox or PIN MullionARD-R10 HID iClass Mini MullionARD-R40 HID iClass Wall MountD8223 HID Prox Wall MountD8224 HID Prox MullionD8224-SP HID Prox Switch Plate MountD8225 HID Prox Mini MullionD8229 PIN Reader

Bosch compatiblecredentials

ACA-ATR13 EM Tokens*ACD-ATR11ISO EM Cards*ACD-ATR14CS EM Clamshell CardsACD-IC2K26-50 iClass Cards**ACT-IC2K26-10 iClass Tokens**D8236-10 HID Prox Cards***D8236KF-10 HID Prox Tokens***

* EM cards work with EM readers, ** iClass cards work with iClass readers,*** Prox cards work with Prox readers

Approved For Level CommentDestructive Attack ILine Security IV IP or cellular with encryptionLine Security II IP or cellular without encryptionLine Security I B430/PSTNEndurance IVSend by Power IV

7 | CertificationsRegion CertificationUSA UL 294 - Access Control System Units

UL 365 - Police Station Connected Burglar Alarm Units and SystemsUL 609 - Local Burglar Alarm Units and SystemsUL 864 - Control Units and Accessories for Fire Alarm SystemsUL 985 - Household Fire Warning System UnitsUL 1023 - Household Burglar-Alarm System UnitsUL 1076 - Proprietary Burglar Alarm Units and SystemsUL 1610 - Central Station Burglar Alarm UnitsCSFM - California Office of The State Fire Marshal

FCC Part 15 Class BCA Canada CAN/ULC S303 - Local Burglar Alarm Units and Systems

CAN/ULC S304 - Signal Receiving Centre and Premise Alarm Control UnitsULC-ORD C1023 - Household Burglar Alarm System UnitsULC-ORD C1076 - Proprietary Burglar Alarm Units and SystemsULC 2016701-S1871E - Fire Alarm and Security SubassembliesICES-003 - Information Technology Equipment (ITE)

When the tamper switch is activated, the heartbeat LED stays OFF for 3 sec before indicating the firmware version. The LED pulses the major, minor, and micro digits of the firmware version, with a 1 sec pause after each digit.

In the following example, the version 1.4.3 shows as LED flashes:[3 sec pause] *___****___*** [3 sec pause, then normal operation].

To show the firmware version using an LED flash pattern: - If the optional tamper switch is installed: With the enclosure door open, activate the tamper switch (push and release the switch).- If the optional tamper switch is NOT installed: Momentarily short the T+ terminal.Refer to Figure 6.1 for an example of flash patterns.

6 | Show the firmware version

Figure 6.1: Firmware LED flash patterns

5 | LED descriptionsThe module includes one blue Heartbeat LED, and one Reader LED. The Heartbeat LED indicates that the module has power as well as a module’s current state. The Reader LED indicates data transmission. Refer to Table 5.1.

Flash Pattern FunctionFlashes once every 1 sec

Normal state: Indicates normal operation state. (blue)

ON Steady LED trouble state: Module is not powered (for OFF Steady only), or some other trouble condition prohibits the module from communicating with the control panel.OFF Steady

Flashes rapidly Card data is executing (yellow)

OFF Steady No card data is being received

Table 5.1: LED descriptions

4 | Configuration

3.8 | Wire to door contact

ZN+ RTE

COM

REX

21

Callout ― Description1 ― RTE device

2 ― B901 Access Control Module

Figure 3.7: Wiring the door contact

ZN+ RTE

COM

REX

3

1

2

Callout ― Description1 ― Door Contact

2 ― 1k EOL

3 ― B901 Access Control Module

Figure 3.8: Wiring the RTE

NOTICE!Firmware reprogramming on the B901 is not supported if connected via the SDI bus. Updating the firmware is achieved via the SDI2 connection only.

Wire the door contact.

3.8.1 | Request to Enter (RTE)Wire the Request to Enter (RTE) device. The strike is activated, and the door point is shunted when RTE is momentarily shorted to COM. The Shunt only option shunts the point when this input is momentarily shorted. To activate the shunt but not the strike, program RTE Shunt Only? as [YES].

3.8.2 | Request to Exit (REX)

After you wire the module, power up the system and configure the B901 using Remote Programming Software (RPS) to assign the module to an assigned area. Whenever possible, be consistent when numbering doors, areas, and keypads. For example, assign Door 1 to Area 1 and keypad 1. Test for proper operation.

Figure 3.9: Wiring the REX

ZN+ RTE

COM

REX

1

2

Callout ― Description1 ― REX device

2 ― B901 Access Control Module

Wire the Request to Exit (REX) device.

The strike is activated, and the door point is shunted when REX is momentarily shorted to COM. The Shunt only option shunts the point when this input is momentarily shorted. To activate the shunt but not the strike, program REX Shunt Only? as [YES].

NOTICE!Do not use a Request to Exit device (REX) for emergency exit applications. NFPA 101 requires that a UL Listed panic device be used to provide direct power from the standby power source. Check with your local Authority Having Jurisdiction (AHJ) prior to installing your system.

en Installation Guide

Access Control Interface ModuleB901