29.00 vaults, general 29.01 vault access, ladder, sump

32
FIXED LADDER FOR VAULTS ALL ALUMINUM 10' X 15' AND 10' X 21' TRAFFIC RATED PRECAST VAULTS (STEEL DETAILS) 10' X 15' AND 10' X 21' TRAFFIC RATED PRECAST VAULTS (CONCRETE DETAILS) TRANSFORMER TRANSCLOSURE CABINETS TYPICAL TRANSCLOSURE INSTALLATION FERRORESONANCE PREVENTION FLOATING WYE - DELTA CUSTOMER SUPPLIED OUTDOOR ABOVE GROUND VAULT FLOATING WYE - DELTA VAULT LAYOUT (1500 KVA MAX) GROUNDING FOR GROUNDED WYE - GROUNDED WYE BANK WITH DEAD TOP LARGE TWO TRANSFORMER VAULT 5000 KVA MAX VAULT SECONDARY BUS FUSE CABINET, WALL MOUNTED TYPE, 200 AMPERE - THREE-PHASE (FMO) VACUUM SWITCH GROUNDING - FAULT INDICATORS AND REMOTE OPERATORS KEARNEY VACUUM SWITCHES SUBMERSIBLE, VAULT TYPE AUTOMATIC TRANSFER SCHEMES VAULT AUTO TRANSFER SCHEME TRANSFORMERS (VAULT OR TRANSCLOSURE INSTALLATION) 29.05-01 29.05-03 29.06-01 29.06-03 29.01-05 29.03-11 29.03-13 29.03-15 29.04-09 29.02-03 29.02-05 29.03-01 29.03-03 29.03-05 29.03-07 29.03-09 SECTION 29 - NETWORK, VAULTS AND TRANSCLOSURES TABLE OF CONTENTS ELKINS 11/17/10 CECCONI GUINN LOADBREAK THREE-WAY JUNCTION - WALL MOUNTED 29.08-01 0 3 2 1 APPR. REVISED BY CK'D THREE-PHASE VAULT TRANSFORMERS DIMENSIONS 29.09-03 VAULT TRANSFORMER SECONDARY BUSHING SUPPORT 29.09-05 COOPER - CURRENT LIMITING SUBMERSIBLE FUSE DIMENSIONS (REPLACEMENT) COOPER - CURRENT LIMITING SUBMERSIBLE FUSE DIMENSIONS (REPLACEMENT) 29.04-12B 29.04-12A THREE-PHASE VAULT TRANSFORMERS 29.09-01 G&W - CURRENT LIMITING SUBMERSIBLE FUSE - APPLICATIONS (FMO) G&W - CURRENT LIMITING SUBMERSIBLE FUSE DIMENSIONS (FMO) 29.04-12D 29.04-12C GENERAL REQUIRMENTS FOR VAULT ROOMS GENERAL REQUIRMENTS FOR VAULT ROOMS 29.00-01A 29.00-01B GENERAL REQUIRMENTS FOR VAULT ROOMS 29.00-01C ELKINS 2/22/11 CECCONI BURLISON FOR MAINTENANCE ONLY DRAWINGS THE FOR MAINTENANCE ONLY DRAWINGS LISTED BELOW ARE NOT CONTAINED IN THE PRINTED SPEC BOOK, BUT ARE AVAILABLE ONLINE 29.09 VAULT TRANSFORMERS 29.08 VAULT AND ENCLOSURE PRIMARY JUNCTIONS 29.06 SOURCE TRANSFER SCHEMES 29.05 VAULT SWITCHES 29.04 VAULT AND ENCLOSURE FUSING 29.03 TRANSCLOSURES AND VAULT LAYOUTS 29.01 VAULT ACCESS, LADDER, SUMP PUMP AND CONTROL 29.00 VAULTS, GENERAL 29.02 MANUFACTURED VAULTS ADCOCK 10/25/12 KATIGBAK GUINN VAULT LIGHTING KITS (FMO) 29.01-01 ELECTRICAL SCHEMATIC FOR VAULT 29.01-09 OIL MINDER SYSTEM 29.01-11 STANCOR OIL MINDER SYSTEM CONTROLLER 29.01-13 ADCOCK 9/4/14 KATIGBAK GUINN 29.00-00A DEF DEP X DEM DEC

Upload: others

Post on 04-Nov-2021

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

FIXED LADDER FOR VAULTS ALL ALUMINUM

10' X 15' AND 10' X 21' TRAFFIC RATED PRECAST VAULTS (STEEL DETAILS)10' X 15' AND 10' X 21' TRAFFIC RATED PRECAST VAULTS (CONCRETE DETAILS)

TRANSFORMER TRANSCLOSURE CABINETSTYPICAL TRANSCLOSURE INSTALLATIONFERRORESONANCE PREVENTIONFLOATING WYE - DELTA CUSTOMER SUPPLIED OUTDOOR ABOVE GROUND VAULTFLOATING WYE - DELTA VAULT LAYOUT (1500 KVA MAX)GROUNDING FOR GROUNDED WYE - GROUNDED WYE BANK WITH DEAD TOP

LARGE TWO TRANSFORMER VAULT 5000 KVA MAXVAULT SECONDARY BUS

FUSE CABINET, WALL MOUNTED TYPE, 200 AMPERE - THREE-PHASE (FMO)

VACUUM SWITCH GROUNDING - FAULT INDICATORS AND REMOTE OPERATORSKEARNEY VACUUM SWITCHES SUBMERSIBLE, VAULT TYPE

AUTOMATIC TRANSFER SCHEMESVAULT AUTO TRANSFER SCHEME

TRANSFORMERS (VAULT OR TRANSCLOSURE INSTALLATION)

29.05-0129.05-03

29.06-0129.06-03

29.01-05

29.03-1129.03-1329.03-15

29.04-09

29.02-0329.02-05

29.03-0129.03-0329.03-0529.03-0729.03-09

SECTION 29 - NETWORK, VAULTSAND TRANSCLOSURESTABLE OF CONTENTSELKINS11/17/10 CECCONI GUINN

LOADBREAK THREE-WAY JUNCTION - WALL MOUNTED 29.08-01

0

3

2

1

APPR.REVISED BY CK'D

THREE-PHASE VAULT TRANSFORMERS DIMENSIONS 29.09-03VAULT TRANSFORMER SECONDARY BUSHING SUPPORT 29.09-05

COOPER - CURRENT LIMITING SUBMERSIBLE FUSE DIMENSIONS (REPLACEMENT)COOPER - CURRENT LIMITING SUBMERSIBLE FUSE DIMENSIONS (REPLACEMENT)

29.04-12B29.04-12A

THREE-PHASE VAULT TRANSFORMERS 29.09-01

G&W - CURRENT LIMITING SUBMERSIBLE FUSE - APPLICATIONS (FMO)G&W - CURRENT LIMITING SUBMERSIBLE FUSE DIMENSIONS (FMO)

29.04-12D29.04-12C

GENERAL REQUIRMENTS FOR VAULT ROOMSGENERAL REQUIRMENTS FOR VAULT ROOMS

29.00-01A29.00-01B

GENERAL REQUIRMENTS FOR VAULT ROOMS 29.00-01C

ELKINS2/22/11 CECCONI BURLISON

FOR MAINTENANCE ONLY DRAWINGS

THE FOR MAINTENANCE ONLY DRAWINGS LISTED BELOW ARE NOT CONTAINED

IN THE PRINTED SPEC BOOK, BUT ARE AVAILABLE ONLINE

29.09 VAULT TRANSFORMERS

29.08 VAULT AND ENCLOSURE PRIMARY JUNCTIONS

29.06 SOURCE TRANSFER SCHEMES

29.05 VAULT SWITCHES

29.04 VAULT AND ENCLOSURE FUSING

29.03 TRANSCLOSURES AND VAULT LAYOUTS

29.01 VAULT ACCESS, LADDER, SUMP PUMP AND CONTROL

29.00 VAULTS, GENERAL

29.02 MANUFACTURED VAULTS

ADCOCK10/25/12 KATIGBAK GUINN

VAULT LIGHTING KITS (FMO) 29.01-01

ELECTRICAL SCHEMATIC FOR VAULT 29.01-09OIL MINDER SYSTEM 29.01-11STANCOR OIL MINDER SYSTEM CONTROLLER 29.01-13

ADCOCK9/4/14 KATIGBAK GUINN

29.00-00A

DEFDEP

X

DEMDEC

Page 2: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

A TRANSFORMER VAULT IS AN ENCLOSED COMPARTMENT WITHIN A BUILDING OR BELOW GROUND LEVEL ESPECIALLY DESIGNED FOR THE TYPE TRANSFORMERS SPECIFIED BY THE COMPANY.

A TRANSFORMER ENCLOSURE IS A SPECIAL COMPARTMENT SUITABLE FOR INSTALLING COMPANY'S STANDARDTRANSFORMERS. SUCH ENCLOSURE MAY UTILIZE THE CUSTOMER'S BUILDING WALL(S) AS ONE OR MORE SIDESOF THE ENCLOSURE.

ALL ENCLOSURES MUST HAVE A REMOVABLE COVER APPROVED BY THE ENGINEER EXCEPT THOSE LOCATED INISOLATED OR PROTECTED AREAS WHERE, IN THE WRITTEN OPINION OF THE ENGINEER, THERE IS NO REASONABLY FORESEEABLE DANGER OF ACCESS BY MINORS, WORKMEN AND OTHER MEMBERS OF THE PUBLIC.

ONLY AUTHORIZED COMPANY PERSONNEL SHALL HAVE ACCESS TO TRANSFORMER VAULTS OR ENCLOSURESAND ALL ENTRY DOORS SHALL BE KEPT LOCKED UNLESS ATTENDED.

DWG.

29.00-01A11/9/10 GUINN GUINN ELKINS

GENERAL REQUIREMENTS FOR VAULT ROOMS R

0

3

2

1

APPR.REVISED BY CK'D

FERRORESONANCE

FERRORESONANCE IS POSSIBLE WITH UNDERGROUND CABLES AND SINGLE-PHASE SWITCHES FEEDING A DELTAPRIMARY TRANSFORMER BANK OR A FLOATING-WYE TO DELTA TRANSFORMER BANK. THE PREFERRED METHODTO PREVENT THE POSSIBILITY OF FERRORESONANCE IN VAULTS IS TO USE A GANGED SWITCH TO ENERGIZE ORDE-ENERGIZE THE TRANSFORMER BANK. IF THE BANK IS A FLOATING-WYE TO DELTA TRANSFORMER BANK AND ONLY SINGLE-PHASE SWITCHING IS AVAILABLE, FERRORESONANCE CAN BE PREVENTED BY TEMPORARILY

FERRORESONANCE PREVENTION.GROUNDING THE NEUTRAL BEFORE ENERGIZING THE BANK. SEE DWG. 29.03-05 FOR MORE INFORMATION ON

GENERAL

TRANSFORMERS

IT IS THE CUSTOMER'S RESPONSIBILITY TO PROVIDE A TRANSFORMER LOCATION OUTSIDE OF THE BUILDING THAT ALLOWS US TO USE OUR STANDARD MINERAL OIL FILLED TRANSFORMERS AND STANDARD FUSING METHODS. IF THIS IS NOT POSSIBLE, PROGRESS ENERGY WILL INSTALL TRANSFORMERS, SWITCHES ANDFUSES INSIDE A BUILDING IN A CUSTOMER SUPPLIED VAULT THAT IS IN COMPLIANCE WITH NEC ARTICLE 450.THIS ARTICLE STATES THAT UNDER CERTAIN CONDITIONS, MINERAL OIL TRANSFORMERS CAN BE INSTALLEDINSIDE BUILDINGS. HOWEVER, TO AVOID CONFUSION AND TO KEEP PROGRESS ENERGY FROM HAVING TO MONITOR CONTINUED COMPLIANCE WITH THESE CONDITIONS, ALL VAULTS WITHIN A BUILDING WILL BE EQUIPPED WITH TRANSFORMERS USING A LESS FLAMMABLE DIELECTRIC. IN ADDITION THE TRANSFORMER(S) WILL BE FUSED WITH CURRENT LIMITING FUSES. AS MENTIONED IN THE FUSE SECTION ABOVE. THIS CURRENTLIMITING FUSE (CL) REDUCES THE FAULT CURRENT AVAILABLE WITHIN THE TRANSFORMER TANK. THE LESSFLAMMABLE DIELECTRIC, COOPER "FR3", RAISES THE FIRE POINT OF THE TRANSFORMER DIELECTRIC TO ABOVE300° C. THIS COMBINATION GREATLY REDUCES THE CHANCE OF CATASTROPHIC FAILURE DURING A PRIMARY

FAULT IN THE TRANSFORMER.

SPECIAL THREE-PHASE VAULT TRANSFORMERS ARE AVAILABLE. THESE TRANSFORMERS ARE STAINLESS STEEL UNITS AND ARE FILLED WITH LESS-FLAMMABLE FLUID. THEY ARE ALSO FULLY RATED FOR OPERATION IN A 50°C

FOR VAULT TRANSFORMER BANKS CONSISTING OF BANKED SINGLE-PHASE UNITS, STANDARD SINGLE-PHASEDOUBLE BUSHING TRANSFORMERS CAN BE USED PROVIDING THEY ARE MODIFIED. USE A STANDARD STAINLESS STEEL UNIT WHEN AVAILABLE. THESE UNITS SHOULD BE DRAINED AND FLUSHED OF THE EXISTING MINERAL OILAND FILLED WITH A LESS-FLAMMABLE FLUID SUCH AS FR3. ARRANGEMENTS SHOULD BE MADE WITH THETRANSFORMER SHOP TO HAVE THIS DONE. THE TRANSFORMERS SHOULD ALSO BE CONVERTED FROM LIVEBUSHINGS TO BUSHING WELLS IN THE TRANSFORMER SHOP. THE TRANSFORMERS SHOULD BE DERATED FOROPERATION IN THE HIGHER AMBIENT TEMPERATURE CONDITIONS BY 1.5% FOR EACH 1°C ABOVE A 30°C

AMBIENT.

FUSES

FOR AVAILABLE FUSES. FULL RANGE CURRENT LIMITING FUSES ARE ALSO AVAILABLE FOR FUSING

AMBIENT ENVIRONMENT.

TRANSFORMERS IN VAULTS WHEN THE FUSE IS OUTSIDE THE VAULT. CONTACT DISTRIBUTION STANDARDS FORADDITIONAL INFORMATION.

TRANSFORMER LOCATION

FULL RANGE CURRENT LIMITING SUBMERSIBLE FUSES ARE AVAILABLE FOR USE IN VAULTS. SEE SECTION 29.04

Page 3: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.00-01B

GENERAL REQUIREMENTS FOR VAULT ROOMS R

0

3

2

1

APPR.REVISED BY CK'D

11/9/10 GUINN GUINN ELKINS

DESIGN

VAULT SPECIFICATIONS AND REQUIREMENTS SHALL BE PROVIDED TO THE CUSTOMER BY PROGRESS ENERGYENGINEERING REPRESENTATIVE. CUSTOMER MUST FURNISH DETAILED DRAWINGS FOR REVIEW AND APPROVAL

THE ROOM'S INSIDE DIMENSIONS ARE TO BE A MINIMUM OF 20' LENGTH X 14' WIDTH X 10' HEIGHT. THELENGTH WILL BE REQUIRED TO BE MORE THAN 20' IF MORE THAN ONE TRANSFORMER IS REQUIRED.

ONLY EQUIPMENT OWNED BY PROGRESS ENERGY WILL BE ALLOWED INSIDE THE VAULT ROOM.

VAULT ROOM MUST MEET ALL THE REQUIREMENTS OF NEC 450 SECTION III, TRANSFORMER VAULTS, INCLUDINGTHE CONSTRUCTION OF WALLS, ROOFS AND FLOORS, DOORWAYS, VENTILATION, DRAINAGE, ETC.

THE VAULT ROOM MUST REMAIN READILY ACCESSIBLE TO PROGRESS ENERGY OR PROGRESS ENERGYCONTRACTOR LINE AND SERVICE VEHICLES AT ALL TIMES.

THE AREA IN FRONT OF THE ENTRANCE FOR A GROUND LEVEL VAULT MUST BE LEVEL PAVEMENT OR CONCRETEIN ORDER TO ALLOW EQUIPMENT TO BE EASILY ROLLED UP TO THE DOOR. THERE SHALL NO OBSTRUCTIONS TO

ROOM SHALL BE ILLUMINATED WITH LIGHT FIXTURES APPROVED BY PROGRESS ENERGY AND AT LOCATIONSSPECIFIED BY PROGRESS ENERGY. THE LIGHT SWITCH LOCATION SHALL BE AS SPECIFIED BY PROGRESSENERGY. THE LIGHTING SHALL BE INSTALLED PER NEC REQUIREMENTS AND SERVED BY CUSTOMER'S

ACCEPTANCE PRIOR TO PROGRESS ENERGY INSTALLING FACILITIES

PROGRESS ENERGY ENGINEERING AND LINE AND SERVICE ARE TO HAVE A FINAL INSPECTION FOR COMPLIANCEPRIOR TO FINAL ACCEPTANCE.

PROGRESS ENERGY LINE AND SERVICE WILL REQUIRE A MINIMUM OF THREE WEEKS TO COMPLETE THEEQUIPMENT INSTALLATION AFTER FINAL ACCEPTANCE BY PROGRESS ENERGY.

VAULT IS TO BE CLEANED OF DIRT, MUD, AND DEBRIS PRIOR TO PROGRESS ENERGY ACCEPTANCE.

METERING

CUSTOMER TO PROVIDE A METERING ROOM FOR ALL ELECTRICAL METERS. CUSTOMER IS TO PROVIDE ACCESS TO THE METER ROOM FOR PROGRESS ENERGY OR PROGRESS ENERGY CONTRACTOR PERSONNEL FORMAINTENANCE OR METER READING. ALL METERS ARE TO BE INSTALLED PER PROGRESS ENERGY AND NECSPECIFICATIONS AND MUST BE CLEAR OF OBSTRUCTIONS WITH SAFE ACCESS FOR MAINTENANCE OR METERREADING. SITE SPECIFIC METERING ISSUES TO BE DETERMINED BY PROGRESS ENERGY ENGINEER ANDCUSTOMER ENGINEER.

WALLS

WALLS TO BE CONSTRUCTED OF SOLID MASONRY AND IN SUCH A WAY THAT CLIMBING IS NOT POSSIBLE. ALLWALLS MUST MEET APPLICABLE BUILDING AND FIRE CODES.

WALLS SHALL BE CAPABLE OF WITHSTANDING A RADIAL FORCE EQUAL OR GREATER THAN THE STRENGTH OF THE PULLING EYES.

THE HEIGHT OF THE INTERIOR SHALL BE A MINIMUM OF 12 FEET FROM THE FLOOR TO THE BOTTOM OF THECEILING SUPPORT BEAMS.

CUSTOMER IS TO PROVIDE CONDUIT KNOCKOUT-TYPE OPENINGS OR PVC SLEEVES IN THE ROOM'S FLOOR TOPROVIDE ACCESS FOR PROGRESS ENERGY CABLES ENTRANCES. ALL CABLE ENTRANCES SHALL BE COORDINATEDWITH THE PROGRESS ENERGY ENGINEER.

PULLING EYES

THERE ARE TO BE A MINIMUM OF THREE PULLING EYES IN THE BACK WALLS EQUALLY SPACED ALONG THE WALLS.THERE ARE TO BE A MINIMUM OF TWO PULLING EYES IN THE END WALLS EQUALLY SPACED ALONG THE WALLS.THE PULLING EYES ARE TO BE INSTALLED APPROXIMATELY 6" - 18" ABOVE THE FLOOR. THE PULLING EYES SHALLHAVE A MINIMUM TENSILE STRENGTH OF 15,000 POUNDS. THE CUSTOMER WILL SUPPLY THE WALL MOUNTING HARDWARE TO SECURE THE PULLING EYES IN PLACE.

PRIOR TO CONSTRUCTION.

THE ENTRANCE OF A GROUND LEVEL VAULT AND NO OVERHANGS ABOVE A BELOW GROUND VAULT.

ELECTRICAL PANEL. IF AN EMERGENCY GENERATOR PANEL EXISTS, THE LIGHTS SHALL BE SERVED BY THEEMERGENCY PANEL.

Page 4: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.00-01C

GENERAL REQUIREMENTS FOR VAULT ROOMS R

0

3

2

1

APPR.REVISED BY CK'D

11/9/10 GUINN GUINN ELKINS

CONDUIT FOR PRIMARY SECONDARY AND METERING CONDUCTORS

THE NUMBER AND SIZE OF PRIMARY, SECONDARY AND METERING CONDUITS INTO THE VAULT AND THEIR EXACTLOCATION SHALL BE NEGOTIATED WITH CUSTOMER AND AGREED UPON WITH COMPANY ENGINEER.

FLOORS

FLOOR TO BE CONCRETE WITH SUFFICIENT STRUCTURAL STRENGTH TO SUPPORT A MINIMUM EQUIPMENTWEIGHT OF 16000 POUNDS DISTRIBUTED OVER A FOOTPRINT OF 69" X 40".

THE FLOORS MUST HAVE A 4" PVC CONDUIT SLEEVE IN EACH CORNER OF THE VAULT TO ALLOW PROGRESSENERGY TO INSTALL GROUND RODS. THE SLEEVES MUST EXTEND THROUGH THE FLOOR TO THE GROUND BELOW.THE SLEEVES ARE TO BE LOCATED APPROXIMATELY 12" FROM THE WALLS.

THE FLOOR, AT ANY ENTRANCE, MUST HAVE A SILL THAT IS A MINIMUM HEIGHT OF 4 INCHES TO ENSURE ANYOIL SPILL IS CONTAINED WITHIN VAULT ROOM.

DOOR

THE DOOR, WHEN INSTALLED, MUST HAVE A MINIMUM HORIZONTAL OPENING OF 8 FOOT AND MEET ANYAPPLICABLE NEC, BUILDING, OR FIRE CODES.

THE DOOR MUST BE ACCESSIBLE BY PROGRESS ENERGY PERSONNEL ONLY.

THE DOOR MUST NOT OPEN INTO THE VAULT ROOM.

THE DOOR'S HEIGHT ABOVE THE SILL SHALL BE A MINIMUM OF 8'.

CUSTOMER'S ELECTRICAL CONDUCTORS

CUSTOMER IS TO PROVIDE ELECTRICAL CABLES IN THE VAULT. ENTRANCE LOCATIONS ARE TO BE APPROVED BYTHE PROGRESS ENERGY ENGINEERING REPRESENTATIVE PRIOR TO CONSTRUCTION. RIGID BUS DUCT IS

ALL CIRCUITS, PHASE CABLES, AND NEUTRAL CABLES SHALL BE CLEARLY MARKED TO MEET THE REQUIREMENTSOF THE NEC.

POINT OF DELIVERY

THE POINT OF DELIVERY WILL BE WHERE THE CUSTOMER'S CONDUCTORS OR BUS CONNECT TO THE PROGRESSENERGY SECONDARY CONDUCTORS.

GROUNDING

CUSTOMER SHALL PROVIDE SUFFICIENT GROUNDING CONNECTION AVAILABLE TO COMPANY FOR GROUNDINGCOMPANY EQUIPMENT. THIS SHALL BE CONDUIT SLEEVE(S) FOR INSTALLING GROUND RODS TO EARTH BELOW,OR A COPPER CONNECTION TO BUILDING STEEL. COPPER CONNECTION PROVIDED BY CUSTOMER TO BUILDINGSTEEL SHALL BE A MINIMUM #3/0 COPPER. IF BUILDING STEEL IS USED, THE AUTHORITY HAVING JURISDICTION (ELECTRICAL INSPECTOR) SHALL INSPECT AND APPROVE THE METHOD OF CONNECTION.

SECONDARY CONDUCTORS

THE MAXIMUM ALLOWED NUMBER OF CONDUCTORS SHALL BE 14, SIZE 750 KCMIL CU OR AL MAXIMUM. SMALLERSIZES ARE ACCEPTABLE AS LONG AS THE NUMBER IS 14 OR LESS.

ACCEPTABLE AND IF PROVIDED, PROGRESS ENERGY WILL MAKE SECONDARY CONNECTION FROM THE SUPPLYTRANSFORMER TO THE RIGID BUS DUCT AND THE POINT OF CONNECTION SHALL BE THE POINT OF DELIVERY.

ENTRY DOORS SHALL HAVE A STURDY HASP SUITABLE FOR COMPANY'S STANDARD LOCK OR LOCK TUMBLERS

LOCK TUMBLERS SHALL BE READILY OPENED FROM THE INSIDE WITHOUT A KEY.

COMPANY'S STANDARD "DANGER HIGH VOLTAGE" SIGN SHALL BE AFFIXED TO THE OUTSIDE OF ALL ENTRYDOORS OF TRANSFORMER VAULTS INSIDE OF BUILDINGS AND OF TRANSFORMER ENCLOSURES. THIS SIGN

WITHIN THE DOOR TO ACCOMMODATE COMPANY'S STANDARD KEY. SELF-LOCKING DOORS AND DOORS WITH

SHOULD BE SECURELY AFFIXED AND MAINTAINED AT A PLACE EASILY SEEN.

Page 5: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.01-0510/21/10 DANNA GUINN ELKINS

FIXED LADDER FOR VAULTS

ALL ALUMINUMRR

0

3

2

1

APPR.REVISED BY CK'D

MOUNTING HEIGHTTHE LADDER TO ADJUST THE

LEADANCHORS

1/2" DIA. SSBOLT, WASHERAND NUT

24" X 30" MINIMUM ACCESS DOOROPENING WITH LADDER TOP IN PLACE

ACCESS DOOR CLOSED WITHTOP SECTION OF LADDER STORED

MOUNT LADDER AFTER THE ACCESSDOOR PANEL HAS BEEN SET

NOTES:

1. THIS IS A NON-STOCK STANDARD ITEM FOR NEW OR EXISTING VAULTS.

2. ALLOW 8 WEEKS FOR DELIVERY.

THE LADDER IS SHOWN IN A TYPICAL PRECAST VAULT.SPECIFY THE EXACT LENGTH NEEDED WHEN ORDERING.

3. GROUND LADDER TO VAULT GROUNDING GRID.

CN 54051800

VAULTPRECAST

APPROX 12'

10" TYP.

24-1/8"

17"

(BY OTHERS)(BY OTHERS)

17"

24-1/8"

10" TYP.

APPROX 12'PRECASTVAULT

CU LDRVLTCCN 54051800

SPECIFY THE EXACT LENGTH NEEDED WHEN ORDERING.THE LADDER IS SHOWN IN A TYPICAL PRECAST VAULT.

2. ALLOW 8 WEEKS FOR DELIVERY.

1. THIS IS A NON-STOCK STANDARD ITEM FOR NEW OR EXISTING VAULTS.

NOTES:

DOOR PANEL HAS BEEN SETMOUNT LADDER AFTER THE ACCESS

TOP SECTION OF LADDER STOREDACCESS DOOR CLOSED WITH

OPENING WITH LADDER TOP IN PLACE24" X 30" MINIMUM ACCESS DOOR

AND NUTBOLT, WASHER1/2" DIA. SS

ANCHORSLEAD

SIDE VIEW

FRONT VIEW

TOPSECTION

SECTIONBOTTOM

MOUNT THE FIXED SECTION OF THE LADDER 13" BELOW THE TOP OF THE ACCESS PANEL

CUT FROM THE BOTTOM OF

BRACKETSWALL MOUNT

OPENINGCLEARS THE DOORSO THE TOP SECTIONMOUNT BRACKETS ADJUST THE WALL

13"

STREET LEVELSIDEWALK OR

15/16"

10"

4. ENGINEER MUST SPECIFY HATCH TYPE ON ACCESS DOOR WITH RECESS LOCK BOX.

Page 6: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

SENSOR

NOTES:

1. GROUND ALL METAL PARTS (SUMP, LIGHTS, AND PANEL).

SUMP

CONTROLLER; SEE

ELECTRICAL SCHEMATIC FOR VAULT0

3

2

1

APPR.REVISED BY CK'D

FOR DETAILDWG. 29.01-13

CONNECT TO 120 VOLT

WHITE WIRE TO SYSTEM NEUTRAL

TO FUSE HOLDERBLACK WIRE

VAULT GROUNDGREEN WIRE TO

SOURCE ONLY

LOAD SIDE

CN 11130101, FUSE HOLDER

CN 21143102 30 AMP FUSE

29.01-09

DEF

X

DEPDEMDEC

7/14/14 GUINN GUINN ADCOCK

Page 7: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

7/14/14 GUINN GUINN ADCOCK

OIL MINDER SYSTEM0

3

2

1

APPR.REVISED BY CK'D

1/2 HP PUMP

CN 54052006

NOTES:

1. USE PUMP WITH STANCOR OIL MINDER CONTROLLER. SEE

FLOAT OFF LEVEL4 1/4" FROM BASEPLATE

PROBE TIP 2 1/2"FROM BASEPLATE

2. OIL-MINDER PROBE TIP MUST BE BELOW FLOAT OFF LEVEL. ADJUST FLOAT ACCORDINGLY.

TO OIL MINDER CONTROLLER

CU SUMPPUMPC

29.01-11

DEFDEP

X

DEMDEC

3. INSTALL PUMP CONTROL AS HIGH ON THE VAULT WALL AS THE LIQUID LEVEL CABLES WILL ALLOW.

4. USE CAROLINAS STOCK 2" SCH 40 PVC FOR DISCHARGE PIPE. IF THE SUMP IS SMALL ENOUGH THAT HEADWATER DRAINING BACK INTO SUMP AFTER THE PUMP CUTS OFF CAUSES THE PUMP TO CYCLE, INSTALL A 2" TO3" ADAPTER AND A 3" ONE WAY FLUSH VALVE IN THE DISCHARGE PIPE. THIS SHOULD BE PURCHASED FROM A

5. IF HEAD IS GREATER THAN 20 FEET, A LARGER PUMP WILL BE NECESSARY. CONTACT DISTRIBUTIONS STANDARDS.

8. PUMP CONTROL IS WATER TIGHT BUT NOT SUBMERSIBLE.

LOCAL PLUMBING SUPPLY OUTLET.

6. CABLES FOR OIL SENSOR AND PUMP SWITCH COME WITH THE CONTROL. 20 FEET OF CABLE COMES WITH PUMP.3 WIRE SOURCE VOLTAGE CABLE MUST BE SUPPLIED. 3#10 IS ADEQUATE.

7. MINIMUM BASIN DIAMETER IS 24 INCHES.

CAPACITY TABLE FOR STANDARD 1/2 H.P. PUMP

HEAD IN FEET

GALLONS PER MINUTE (GPM)

10'

122

15'

90

20'

50

SHUT-OFF

26'

Page 8: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

STANCOR OIL MINDER SYSTEM CONTROLLER7/14/14 GUINN GUINN ADCOCK0

3

2

1

APPR.REVISED BY CK'D

OIL MINDER CONTROL BOXCU CNTRLSPUMPC

POWER

OIL FAULT

HIGH LEVEL

OVERLOAD

PUMP RUN

115 VAC

L1 N P1(N) P2(L)

RMS RELAY10 AMPS @ 240 VAC

F4F3F2F1OIL

PROBE

ONFLOAT

HIGH ALARMFLOAT

SETTINGS

OVERLOADAMPS

SENSOR

1 10

75

3

5 15

1310

7

STANCOR515 FAN HILL RD.

MONROE, CT 06468www.stancorpumps.comOIL MINDER II CONTROL

PATENTS: 2,752,188; 4,715,785; 6,203,281MADE IN USA

BLK

WHT GR

POWERSUPPLY

GR

WHT BLK

BLK

WHT

WHT

POWER POWER PROBE FLOATTO

PUMP

10 FT. PIGTAILINCLUDED

RESET

SILENCE

CN 54041404

29.01-13

DEFDEP

X

DEMDEC

Page 9: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

HIGH HEELGRATINGAPPROX.

PER PANELCLEAR OPENING

OPENINGCLEAR PER PANEL

APPROX.GRATINGSTANDARD

1800 IN.2SOLID CONCRETEPANEL WEIGHT 2380 LBS.

BRICK PAVER PANELMUST BE FILLED AT JOBSITETO MATCHSIDEWALK

THE CROSS BRACES ARE ONLYUSED IF THE VAULT IS LOCATEDIN THE STREET OR IS SUBJECTEDTO CONTINUOUS TRAFFIC.

THE VAULTS ARE HS20-44TRAFFIC RATED (THIS IS STREET RATED)

IF THE VAULT TOP NEEDS TO BE RAISED FOR PAVING

2. REMOVE THE TOP PANELS AND THE SUPPORT STEEL AND PUT SHIMS IN THE BEAM POCKETS THE SAME THICKNESS AS THE COLLAR IN STEP 1.

3. WELD SHIMS TO THE END ANGLETHE SAME THICKNESS AS THECOLLAR IN STEP 1.

4. REPLACE THE SUPPORT STEEL AND THE PANELS.

THE CROSS BRACES CAN BE LEFTOFF IF THE VAULT IS ONLY SUBJECTEDTO INCIDENTAL TRAFFIC (SIDEWALK INSTALLATIONS)

BEAM POCKETSEE NOTE 2

SEE NOTE 1

SEE NOTE 2

15' VAULT SHOWN21' VAULT HAS 2 MORE PANELS

SEENOTE 5

SEE NOTE 6

SEENOTE 7

SEENOTE 8

SEENOTE 9

1. WELD A COLLAR SHIM AROUND THE TOP TO THE EDGE ANGLE.

THE VAULTS ARE NON-STOCKSTANDARD ALLOW 6 MONTHSDELIVERY TIME

ALL TOP PANELSARE INTERCHANGEABLEBETWEEN THE 15'AND THE 21' VAULTS.

1/2 GRATING PANEL (SPEC HIGHHEEL OR STANDARD GRATING HALFPANEL) 2 ACCESS PANELS CAN BEINSTALLED BACK TO BACK IF ONEDOOR IS NEEDED FOR REMOTEOPERATORS, SPECIFY ON THE ORDERDRAWING.

GRATING (LIFTING DEVICE FOR HIGH HEEL GRATE TO BE LEFT IN THE VAULT).

TO THE EDGE ANGLE.

DWG.

29.02-03

STAINLESS STEEL SLAM LOCK W/ REMOVABLE KEY

STAINLESS STEEL COMPRESSION SPRING ASSIST

STAINLESS STEEL HINGES AND ATTACHING HARDWARE

AUTO-LOCK STAINLESS STEEL HOLD OPEN ARMS WITH

ACCESS DOOR PANEL FEATURES:

DOUBLE LEAF CONSTRUCTION H-20 LOAD RATING .

1/4" THICK

RELEASE HANDLES

ACCESS DOOR DETAIL

PLAN VIEW STEEL DETAILS

RECESSED LOCKING BOX.

(SEE NOTES 1 THROUGH 4)

SEE ACCESSDOOR DETAIL

RECESSED

WORK THIS DRAWING WITH DWG. 29.02-05

10. FOR VAULT LADDER DETAILS SEE DWG. 29.01-05.

NOTES:

DIAMOND PAT. AL.COVER PLATE

PADLOCKBOX

2880 IN. 2

5. CN 54051305 ACCESS PANEL WITH

6. CN 54051206 SPECIFY HIGH HEEL

7. CN 54051206 SPECIFY STANDARD GRATING

8. CN 54052105 SOLID CONCRETE PANEL

9. CN 54052204 BRICK PAVER PANEL

54"

3" 24"

30"

3"

6/17/10 DANNA GUINN ELKINS

10' X 15' AND 10' X 21'

TRAFFIC RATED PRECAST VAULTS (STEEL DETAILS)

ALL VAULT ORDERS MUST BE ACCOMPANIEDBY AN ORDER DRAWING. TO SPECIFY TOPPANELS, CONDUIT PANELS, SUMP LOCATION,ETC. CONTACT DISTRIBUTION STANDARDSFOR ORDER ASSISTANCE.

R

0

3

2

1

APPR.REVISED BY CK'D

SLAM LOCK

LIFTING HANDLE

STAINLESS STEEL

Page 10: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

MIN. FROM WALL

SEE NOTE 1

JOINT LINE

15' 1-1/2" (FOR 15' VAULT)

SEE NOTE 3

ID SUMP24"x24"x24"

6'-0"

8"

SUMP GRATE

12"

12" MIN.

NOTE 2

SEE NOTE 2

SEE

8"

8"

CN 54051602

CN 54051701

21'-2" (FOR 21' VAULT)

KNOCKOUTS

10" - 21' VAULT8" - 15' VAULT

SEE NOTE 4

DIMENSIONEDFROM THIS

LOCATIONPANEL

KNOCKOUT12-1/2"

3X6 MAX.2X2 MIN.ALL 6"

6"

1. ALL 4 CORNERS OF VAULT HAVE PIPE INSERTS FOR THE INSTALLATION OF GROUND RODS. ATTACH #2 BC GROUNDING RING AROUND THE VAULT ABOVE THE FLOOR. ATTACH THE GROUND RING TO THE 4 GROUND ROD LOCATIONS AND ATTACH THE #2 BC TO THE WALL WITH NEUTRAL SPOOLS AND TIE WIRE.

2. SPECIFY SUMP AND SUMP PUMP DISCHARGE PIPE LOCATION ON THE ORDER DRAWING.

4. CONDUIT PANEL LOCATIONS AND SIZE SHOULD BE SPECIFIED ON THE ORDER DRAWING. PANEL LOCATIONSWILL BE MEASURED AS SHOWN ABOVE. THE KNOCKOUT IS 30" FROM THE TOP OF THE VAULT WALL OR 30"BELOW THE JOINT LINE. MINIMUM 12" FROM ANY WALL TO THE START OF A CONDUIT PANEL. THE PANELSCAN ONLY BE 3 VERTICAL BY 6 HORIZONTAL (MAXIMUM). PANELS MAY BE AS SMALL AS 2 VERTICAL BY 2 HORIZONTAL.

5. VAULTS ARE SOMETIMES MANUFACTURED WITH SLOPE TO MATCH THE SLOPE OF FINISHED GRADE. THECONTRACTOR SHOULD MEASURE THE VAULT PRIOR TO INSTALLATION, AND PROPERLY LEVEL THE EXCAVATEDAREA. THIS WILL ELIMINATE THE NEED TO RE-EXCAVATE FOR THE PURPOSE OF LEVELING AFTER THE VAULTHAS BEEN SET.

WORK THIS DRAWING WITH DWG. 29.02-03.

3. SEE DWGS. 29.01-09, 29.01-11 AND 29.01-13 FOR SUMP PUMP.

NOTES:

10'-0"

NOTE 4SEE

(BOTH 15' AND21' VAULTS)VLT15X10CVEHC

VLT21X10CVEHC

APPROX. 10'-6"

30"

30"

6"

30"

9/1/10 DANNA GUINN ELKINS

10' X 15' AND 10' X 21'TRAFFIC RATED PRECAST VAULTS

(CONCRETE DETAILS)0

3

2

1

APPR.REVISED BY CK'D

SIDE VIEW END VIEW

6'-0"

9/4/14 GUINN GUINN ADCOCK

29.02-05

DEFDEP

X

DEMDEC

Page 11: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

ISN'T AVAILABLE FROM THREE-PHASE, PAD-MOUNTED TRANSFORMERS.8. THESE ENCLOSURES WITH OVERHEAD TYPE TRANSFORMERS SHALL ONLY BE INSTALLED TO PROVIDE THREE-PHASE SERVICE THAT

7. FOR 2 OR 3 CABINETS, USE THE ABOVE TABLE DIMENSIONS, CATALOG AND ASSEMBLY NUMBERS.

L2

200" X 66" X 91" (L3 X D X H)

133" X 66" X 91" (L3 X D X H)

164" X 54" X 81" (L2 X D X H)

109" X 54" X 81" (L2 X D X H)

CONVENTIONAL TF. SIZES WITH BUSHING WELLS (kVA)ENCLOSURE SIZES

WIDE (IN.)BAY(S)

L3

3. USE OVERHEAD TYPE TRANSFORMERS WITH BUSHING WELLS. (TRANSFORMERS HAVE TO BE REQUESTED AND REWORKED FROM THE

1. THESE ENCLOSURES ARE APPROVED FOR PURCHASE, NON-STOCK AND SHOULD BE SPECIAL ORDERED.

NOTES:

H

D

SIDE VIEWFRONT VIEW

TOP VIEW - TOPS REMOVED

DWG.

29.03-01

TRANSFORMER SHOP).

9. USE DEEP DRIVEN GROUNDS. DWG. 29.03-03 SHOULD BE USED AS AN EXAMPLE ON GROUNDING.

6. SEE SECTION 34 FOR PRIMARY METERING ENCLOSURES. THE ABOVE CABINET SHOULD NOT BE USED FOR PRIMARY METERING.

5. REFER TO DWG. 27.06-05 FOR LOCATION OF OIL-FILLED PAD-MOUNTED TRANSFORMERS.

4. FOR TRANSFORMER ENCLOSURE PADS, SEE DWGS. 24.02-01A & 24.02-01B.

2. FOR OVERHEAD TRANSFORMER DIMENSIONS SEE DWG. 06.00-12.

CN 22277206 TR200X66X91SCCONCRETE PAD PADTRA208X74CC

CONCRETE PAD PADTRA141X74CCCN 22277107 TR133X66X91SC

CN 22277008 TR109X54X81SCCONCRETE PAD PADTRA117X62CC

CN 22277305 TR164X54X81SCCONCRETE PAD PADTRA172X62CC

3

2

66

54

54

66

250 333 50050 75 100 167

COMPATIBLE UNITS, CATALOG NUMBERS & DIMENSIONS

10/21/10 DANNA GUINN ELKINS

TRANSFORMER TRANSCLOSURE CABINETS0

3

2

1

APPR.REVISED BY CK'D

8/27/12 SIMMONS BURLISON ELKINS

6/13/13 SIMMONS GUINN ADCOCK

12/16/13 SIMMONS GUINN ADCOCK

Page 12: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

X4

X2

X3

X1

H1

H2

H2

H1

14.4

KV

X1

X3

X2

H2

H1 X1

X3

X2

X4

X4

NBØ

METER

IF THE BANK IS ENERGIZED ONE PHASE AT A TIME THE FLOATING WYE MUST BE TEMPORARILY GROUNDED.

THE BANK SHOWN IS CONNECTED FLOATING WYE - DELTA.

THE FLOATING NEUTRAL IS BROUGHT TO A FEED THRUBUSHING.

TO GROUND THE NEUTRAL:

ATTACH THE YELLOW GROUNDING ELBOW TO THETRANSCLOSURE GROUND LOOP.

REMOVE THE DEAD-END RECEPTACLE FROM THE FEED THRU BUSHING.

INSTALL THE YELLOW GROUNDING ELBOW ON THE FEEDTHRU BUSHING.

THE BANK CAN NOW BE ENERGIZED ONE PHASE AT A TIMEWITHOUT PRODUCING DAMAGING FERRORESONANCE OVERVOLTAGES.

AFTER THE BANK IS ENERGIZED, THE TEMPORARY GROUNDMUST BE REMOVED BY REVERSING THE ABOVE PROCEDURE BEFORE LEAVING THE BANK IN SERVICE.

1. RUN THE SECONDARY THROUGH THE CT'S AND THEN CONNECT TO THE TRANSFORMER TERMINALS. THE CT'S CAN NOT BE

2. RUN A #4 COPPER GROUNDING LOOP AROUND THE BOTTOM OF THE TRANSCLOSURE AND GROUND THE CABINET AT EACH BAY.

3. THIS IS A "TYPICAL" INSTALLATION. SEE REFERENCE SPEC.

4. THE GROUNDING FEED THRU CAN BE MOUNTED ANYWHERE IN THE TRANSCLOSURE AS LONG AS IT IS OPERABLE WITHA HOT STICK AND GOOD CLEARANCE IS MAINTAINED BETWEEN THE MOUNTING HARDWARE AND ANY EXPOSED SECONDARY

NOTES:

YELLOW GROUNDING ELBOW

FEED THRU BUSHING PARKING STAND

5. SUPPORT PRIMARY AND SECONDARY CABLES WITH CABLE TIES AND CABLE PROTECTORS AS NECESSARY.

6. A TRANSCLOSURE SHOULD BE USED FOR THREE-PHASEFOUR-WIRE 240/120 VOLT OR THREE-PHASE THREE-WIRE240 VOLT SERVICE ONLY. SEE STANDARD PRACTICES

INSTALLED OVER THE SECONDARY BUSHINGS TO METERA DELTA SECONDARY.

DWG.

29.03-03

HOT PARTS. SEE DWG. 26.04-06.

DWG. 06.10-06 II.

6/17/10 DANNA GUINN ELKINS

TYPICAL TRANSCLOSURE INSTALLATION

SECTION 06.

SEE DWG. 29.03-11. ONE DEEP DRIVEN GROUND ROD CONSISTINGOF 4 -5' RODS ASSEMBLED ON TOP OF ONE ANOTHER SHALL BEINSTALLED AND CONNECTED TO THE #4 GROUNDING LOOP.

AVAILABLE FROM DISTRIBUTIONTOOLS AND TEST EQUIPMENT

0

3

2

1

APPR.REVISED BY CK'D

6/13/13 SIMMONS GUINN ADCOCK

Page 13: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.03-05

ENERGIZE

1. OPEN SWITCH2. CLOSE CUTOUTS3. CLOSE SWITCH

DE-ENERGIZE

1. OPEN SWITCH 2. OPEN CUTOUTS

PRIMARY

FLOATINGNEUTRAL

FEEDTHROUGH PARKING STAND

23 KV PRIMARY14.4 KV TRANSFORMERS

12 KV PRIMARY7.2 KV TRANSFORMERS

ENERGIZE

1. ALL 3 CUTOUTS OPEN

2. REMOVE DEAD END RECEPTACLE FROM THE FEED THROUGH PARKING STAND

3. INSTALL THE YELLOW GROUNDING ELBOW ON THE FEEDTHROUGH PARKING STAND

4. CLOSE IN ALL 3 CUTOUTS

5. CHECK SECONDARY VOLTAGE

6. REMOVE GROUNDING ELBOW

7. INSTALL DEAD END RECEPTACLE ON FEED THROUGH PARKING STAND

THE GROUNDING ELBOW MUSTBE REMOVED WHEN NOT WORKINGON THE BANK

PRIMARY SECONDARY

DE-ENERGIZE

1. REMOVE DEAD END RECEPTACLE FROM THE FEEDTHROUGH PARKING STAND

2. INSTALL THE YELLOW GROUNDING ELBOW ON THE FEEDTHROUGH PARKING STAND

3. OPEN THE CUTOUTS

YELLOW GROUNDINGELBOW

DEAD ENDRECEPTACLE

DELTA BANKS SOURCED BY AN UNDERGROUND CIRCUIT SHOULD HAVE A GANGED THREE-PHASE SWITCH TO ENERGIZE ANDDE-ENERGIZE THE BANK. THIS CAN BE DONE BY USING A GANG OPERATED PMH OR VAULT SWITCH. FUSING FOR THE BANK CAN BEON THE DIP POLE OR AT THE TRANSFORMER LOCATION.

FLOATING WYE-DELTA BANKS SOURCED BY AN UNDERGROUND CIRCUIT SHOULD BE ENERGIZED BY A GANG OPERATED SWITCH OR BYTEMPORARILY GROUNDING THE FLOATING NEUTRAL WHILE THE BANK IS ENERGIZED FROM A SINGLE-PHASE SOURCE SUCH AS FUSEDCUTOUTS OR SINGLE-PHASE DISCONNECTS. TEMPORARY GROUNDING SHOULD BE DONE BY BRINGING THE FLOATING NEUTRAL TO THEFRONT OF THE TRANSCLOSURE OR VAULT.

10/4/10 DANNA GUINN ELKINS

FERRORESONANCE PREVENTION R

0

3

2

1

APPR.REVISED BY CK'D

Page 14: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

H1

H2

H2

H1X1

X3

X2

X4

X4

X2

X3

X1 H1

H2

X4

X2

X3

X1

FLOATINGNEUTRAL

TO ENERGIZE:

1. ALL 3 CUTOUTS OPEN2. REMOVE DEAD END RECEPTACLE

FROM THE FEED THRU PARKING STAND

3. INSTALL THE YELLOW GROUNDINGELBOW ON THE FEEDTHROUGH PARKING STAND

4. CLOSE IN ALL 3 CUTOUTS 5. CHECK SECONDARY VOLTAGE

6. REMOVE GROUNDING ELBOW7. INSTALL DEAD END RECEPTACLE

ON FEED THRU PARKING STAND

THE GROUNDING ELBOW MUST BE REMOVED WHEN NOT WORKING ON THE BANK

PRIMARY SECONDARY

TO DE-ENERGIZE:

1. REMOVE DEAD END RECEPTACLE FROM THE FEED THRU PARKING STAND

2. INSTALL THE YELLOW GROUNDING ELBOW ON THE FEED THRU PARKING STAND

3. OPEN THE CUTOUTS

TO PREVENT FERRORESONANCE WHILE ENERGIZING THIS BANK THROUGH UNDERGROUND

IN METER ENCLOSURE

GROUND RODS INEACH CORNER

#4 BARE COPPERGROUND LOOP AROUND THE PERIMETER OF THE VAULT

#4 BC EQUIPMENT GROUNDS

METER ENCLOSURE

THIS CONFIGURATION WILL ACCEPT UP TO 8 CUSTOMER CONDUCTORS PER PHASE.

PULLING EYE

FEED-THRU PARKING STAND

YELLOW GROUNDINGELBOW

ATTACH THE #4 GROUND LOOPWITH NEUTRAL SPOOLS

POSITION THE FEED THRU PARKING STAND TO ALLOW THE GROUNDING ELBOW TO BEBE INSTALLED AND REMOVED FROM OUTSIDE THE VAULT WITH A SHOTGUN STICK.

CN 21100508FLEXIBLE BRAIDEDCONNECTOR STRAPS

JUMPERS BY PROGRESS

PLASTIC COVERS FORCONNECTORSEXPOSED TORAIN

NEUTRAL

CUSTOMER'SCONDUCTORS

FOR TEMPORARILY GROUNDED NEUTRAL

PRIMARY - THE FLOATING NEUTRAL MUST BE TEMPORARILY GROUNDED AS SHOWN IN THIS DRAWING OR A THREE-PHASE GANG OPERATEDSWITCH MUST BE INSTALLED.

DWG.

29.03-07

ELBOW ARRESTERFEED-THRU &

2 TOTAL

CONSULT ENGINEERING MANUAL VAULT SECTION FOR DETAILS

9/9/10 DANNA GUINN ELKINS

FLOATING WYE - DELTA CUSTOMER SUPPLIED

OUTDOOR ABOVE GROUND VAULT

ENERGY

R

0

3

2

1

APPR.REVISED BY CK'D

Page 15: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.03-09

H1

H2

H2

H1

14.4

KV

X1

X3

X2

X4

X4

X2

X3

X1

14.4

KV

H1

H2

N

X4

X2

X3

X1

14.4

KV

FLOATINGNEUTRAL

PRIMARY SECONDARY

15' I.D.

GROUND RODS INEACH CORNER

#4 BARE COPPERGROUND LOOP AROUND THE PERIMETER OF THE VAULT

#4 BC EQUIPMENT GROUNDS

TOTAL 2CN 21100508FLEXIBLE BRAIDEDCONNECTOR STRAPS

JUMPERS BY PROGRESS

PLASTIC COVERS

STAINLESS STEEL TRANSFORMERS IF THE VAULT IS BELOW GROUND

PRIMARY LOOP

SUMP

REMOTE OPERATORCABLES

LADDER

REMOTE OPERATORHANDLES

SET TRANSFORMERS ON TIMBERS

GROUND LADDER AND OPERATORHANDLES TO THE VAULT GROUNDING GRID

TYPICAL

SWITCHVACUUM

20' I.D.

9/20/10 GUINN GUINN ELKINS

FLOATING WYE - DELTA

VAULT LAYOUT (1500 KVA MAX)

ENERGY

R

0

3

2

1

APPR.REVISED BY CK'D

MOUNT CL FUSES VERTICALLYWITH SOURCE SIDE ON TOP

29.04-12B.SEE DWGS. 29.04-12A AND

(SEE NOTE 1)

NOTES:

1. INSTALL 4-5' RODS IN ONE CORNER AND 1-5' RODIN THE OTHER THREE CORNERS.

#4 BC

Page 16: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

APP

RO

X 1

2"

8"

SEM

I-CO

ND

UCTIN

G

INSU

LATIO

N S

HIE

LD

BARE 1

/0CO

ND

UCTO

R

2"

AQ

UA-S

EAL

#4 B

C

#4 B

C T

RAN

SFO

RM

ER

GRO

UN

DIN

G L

OO

P

2/0

BC V

AU

LT G

RO

UN

DIN

G L

OO

P

#4 B

C

#4 B

C

SQ

UEEZE C

NTO

#4 B

CTW

O T

IMES

ALU

MIN

UM

TO

BE O

VER T

HE

CO

PPER

#4 B

C

NO

TES:

1.

START W

ITH

A 2

6"

PIECE O

F 1/0

JACKETED

PRIM

ARY C

ABLE

.

2.

REM

OVE T

HE O

UTER I

NSU

LATIN

G J

ACKET A

ND

TH

E C

ON

CEN

TRIC

NEU

TRAL

FOR T

HE E

NTIR

E L

EN

GTH

OF

TH

E C

ABLE

.O

F TH

E C

ABLE

.

4.

INSTALL

TH

E C

ABLE

IN

TO

TH

E E

LBO

W A

ND

IN

STALL

TH

E M

ALE

CO

NTACT.

5.

CU

T B

ACK 8

" O

F SEM

I-CO

N A

ND

IN

SU

LATIO

N F

RO

M T

HE O

TH

ER E

ND

OF

TH

E C

ABLE

LEAVIN

G 8

" O

F EXPO

SED

1/0

SO

LID

ALU

MIN

UM

.

6.

AQ

UA-S

EAL

AN

D T

APE

BETW

EEN

TH

E S

EM

I-CO

N A

ND

BARE C

ON

DU

CTO

R

7.

INSTALL

TH

E S

TATIC

WIR

E T

O T

HE E

LBO

W A

ND

ARO

UN

D T

HE S

EM

I-CO

N T

O T

HE A

QU

A-S

EAL

AN

D T

HEN

TO

TH

E G

RO

UN

DLO

OP.

GRO

UN

DIN

G L

OO

P#

4 B

C T

RAN

SFO

RM

ER

H1

H2

X1

X

2

H1

H2

X1

X

2

H1

H2

X1

X

2SS

SS

SS

#4 B

C

AN

D T

APE

#4 B

CSEE

NO

TE 8

#4 B

C T

RAN

SCLO

SU

RE G

RO

UN

D

H2

DWG.

29.03-11

8.

SQ

UEEZE T

HE #

4 B

C T

O T

HE 1

/0 A

LUM

INU

M 2

TIM

ES.

IF T

HE A

LUM

INU

M 1

/0 C

ON

DU

CTO

R I

S S

UBJE

CTED

TO

SALT

CO

NTAM

INAN

TS,

AQ

UA S

EAL

AN

D T

APE

TH

E C

ON

NECTIO

NS.

9.

TH

E H

2 B

USH

ING

MAY B

E L

EFT

AS A

CERAM

IC B

USH

ING

AN

D N

OT C

ON

VERTED

TO

A B

USH

ING

WELL

. TH

IS S

HO

ULD

BE

CO

ORD

INATED

WIT

H T

HE T

RAN

SFO

RM

ER S

HO

P.

3.

CU

T B

ACK T

HE I

NSU

LATIO

N A

ND

TH

E S

EM

I-CO

N S

HIE

LD P

ER

DW

G.

26.0

4-0

2B

AN

D I

NSTALL

TH

E C

ON

DU

CTO

R C

ON

TACT.

6/17/10 DANNA GUINN ELKINS

GROUNDING FOR GROUNDED WYE - GROUNDED WYE BANK WITH DEAD TOP TRANSFORMERS(VAULT OR TRANSCLOSURE INSTALLATION)0

3

2

1

APPR.REVISED BY CK'D

10.

VAU

LTS R

EQ

UIR

E O

NE D

EEP

DRIV

EN

GRO

UN

D R

OD

CO

NSIS

TIN

G O

F 4 -

5' RO

DS I

N O

NE C

ORN

ER O

F TH

E V

AU

LT A

ND

1 -

5' RO

D I

N E

ACH

OF

TH

E O

TH

ER C

ORN

ERS.

TRAN

SCLO

SU

RES R

EQ

UIR

E O

NE D

EEP

DRIV

EN

GRO

UN

D R

OD

CO

NSIS

TIN

G O

F 4 -

5'

RO

DS A

SSEM

BLE

D O

N T

OP

OF

ON

E A

NO

TH

ER.

GRO

UN

D R

OD

(S)

SH

ALL

BE C

ON

NECTED

TO

TH

E G

RO

UN

D L

OO

P.

SEE N

OTE 1

0

6/13/13 SIMMONS GUINN ADCOCK

Page 17: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.03-13

2500

2500

4-WAYSWITCH

SUMP

REMOTE OPERATORHANDLES AT THE VAULT ENTRANCE

SET VAULT TYPETRANSFORMERS ON TIMBERS

CL FUSES

SEE VAULT DESIGN GUIDE TRANSFORMER SECTION FOR INFORMATION ONFUSING AND SPLIT BUS

#4 BC GROUND LOOP

SECTIONALGROUND RODS

SECONDARYBUSHING LAYOUT

FRONT VIEW OF THE SECONDARY LAYOUT ON 3Ø TRANSFORMERS

TOP VIEW OF THE SECONDARY TERMINALS

20'

N

CTCT

BACK TO BACK 8-HOLECONNECTORS WITHPLASTISOL COVERS

1. THE METER PT'S CANBE MOUNTED IN THE VAULT OR THE VOLTAGECIRCUIT CAN BE BROUGHTOUT OF THE VAULT. THEPT'S CAN BE INSTALLED IN A T1 CABINET MOUNTED NEXT TO THE METER ENCLOSURE.

2. THE INSTALLATION SHOWN IS A SPLIT BUSON THE COMPANY SIDE AND ON THE CUSTOMER'S

3. MOUNT CL FUSESVERTICALLY WITH SOURCESIDE ON TOP. SEE

4. RUN #4 COPPER VAULT GROUND AROUNDTHE VAULT AND ATTACHTO GROUND RODS IN EACH CORNER.

5. EACH PIECE OF EQUIPMENT IS TO BELOOP GROUNDED TO THEVAULT GROUND LOOPPER INDIVIDUAL EQUIPMENTSPEC DWG.

6. THE INSTALLATION SHOWN ASSUMES THE VAULT WILL NOT FLOODTO THE LEVEL OF THE SECONDARY BUSHINGSON THE TRANSFORMERS.IF THIS IS NOT TRUE,CONTACT DISTRIBUTION STANDARDS FOR SPECIALSUBMERSIBLE SECONDARYCONNECTORS.

7. THE TRANSFORMERS SHOWN HAVE INTERNAL EXPULSION FUSES TO PREVENT THE FAILED COILS FROM BEING RE-ENERGIZED. THETRANSFORMERS MUSTSTILL HAVE SOME TYPEOF PRIMARY FUSING ASSHOWN.

8. THE TRANSFORMERS HAVE TAPS AND A WYE-DELTA SWITCH.

9. IF THE TRANSFORMERSARE PARALLED, ON THEPRIMARY, INSTALL 3-WAY200 AMP JUNCTIONSTO FEED THE INDIVIDUALTRANSFORMERS FROMONE FUSED SOURCE.

NOTES:

5.5" WINDOW CT'S SHOWN

IF THE VAULT FLOORWILL BE WET

30'

6/17/10 DANNA GUINN ELKINS

LARGE TWO TRANSFORMER VAULT

5000 KVA MAX.

SIDE.

R

SIDE

0

3

2

1

APPR.REVISED BY CK'D

CL FUSESSEE NOTE 3

SEE NOTE 3

AND 29.04-12B.DWGS. 29.04-12A

Page 18: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.03-15

MAIN VAULT SERVICEENTRANCE CABLES

PROGRESS ENERGY SECONDARY TOUNLOAD THE

PROGRESS ENERGY SECONDARY ORSEPARATELY METERED BUILDINGSERVICE ENTRANCE CIRCUIT(S)

5000 AMP SUBSTATION CT ASSEMBLY ON CROSSARM RACK

PLASTICCOVERSTYPICAL TOP VIEW

1. SOMETIMES IT WILL BE NECESSARY TO SERVE SECONDARY OR ADDITIONAL SMALL METERED SERVICES FROM A TRANSFORMER FEEDING THE MAIN LARGE SERVICE IN A VAULT. IF THESE SMALL LOADS CANNOT BECONNECTED TO THE TRANSFORMER SECONDARY BUSHINGS WHILE LEAVING ROOM FOR THE CT, THETRANSFORMER CAN BE UNLOADED INTO A BUS THAT WILL ALLOW THE SMALL SERVICES TO BE TAPPED UPBEFORE THE MAIN LARGE SERVICE LOAD CURRENT PASSES THROUGH THE CT'S TO THE CUSTOMER'S SERVICE

VAULT SECONDARY BUS R

0

3

2

1

APPR.REVISED BY CK'D

6/17/10 GUINNDANNA ELKINS

NOTES:

ENTRANCE CABLES.

1 CTA65000C

BOLT, HX, 1/2-13X2", ALUMINUM

BILL OF MATERIALS

CATALOG

22110100

BOLT, HX, CAP, 1/2-13X3/4, GLV

BOLT, HX, 1/2-13X1-1/2", ALUMINUMBOLT, HX, 1/2-13X10", GLV, A307BOLT, HX, 3/8-16X1", GLV, A307

HX, 1/2-13X3-1/2, GLV, A307BOLT, HX, 1/2-13X1-1/2,GLV, A307BAR, 3/8X4"X9", AL, 4-HOLE3/8X4"X14", AL, 4-HOLE NEMA

ASSEMBLY, MTG, 5000A, 600V CURRENT XFMRINSULATOR, POST, STN, 7.5KV

DESCRIPTION

22011209308369023083680310031706100322093002030910030104100328031001640010016509

1

8

QTY

4

48

4

22

2221

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

1

TRANSFORMER

Page 19: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.04-12A11/9/10 HOFFMAN GUINN ELKINS

COOPER - CURRENT LIMITING

SUBMERSIBLE FUSE DIMENSIONS (REPLACEMENT)REVISED CK'DBY APPR.

1

0

3

2

30.97"

27.77"

19.77"

20.95"

34.63"

USE UNIVERSAL BRACKET

9220207259FUSEVLTEMF15C

MOUNTING OPTIONSOPTIONA MIN.A MAX.B MIN.B MAX.C MIN.C MAX.

LENGTH (IN)22.7725.9125.9729.6129.6733.10

A MIN.

A MAX.

B MIN.

B MAX.

C MIN.

C MAX.

20°

6.27"

3.18"

2.56"

PLAN VIEW

FRONT VIEW

PLAN VIEW

NOTES:

2. LABEL EACH FUSE AMP SIZE USING 1-5/8" LABELING STICKER KIT ON CENTER OF FUSE BODY.

3. USE STANDARD 9/16" GROUND LUG WITH BRACKET WITH #2 CU GROUND.

4. SEE DWG. 29.04-12B FOR FUSE SPECIFICATIONS AND COMPATIBLE UNITS.

5.409"

10.56"

6.83"

1. COOPER FUSES SHOULD BE USED FOR ALL NEW INSTALLS. REQUIRES NEW UNIVERSAL BRACKET LISTED ON

THIS DRAWING.

8/1/11 HOFFMAN BURLISON ELKINS

Page 20: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.04-12B7/13/10 HOFFMAN GUINN ELKINS

COOPER - CURRENT LIMITING

SUBMERSIBLE FUSE DIMENSIONS (REPLACEMENT)REVISED CK'DBY APPR.

1

0

3

2

NOTES:

SINGLE-PHASE 13.2 KVKVA HV LV FUSE (AMPS) CATALOG NUMBER COMPATIBLE UNIT100 14.4 240/120 10 9220207260 F10EMF15C167 14.4 240/120 20 9220207261 F20EMF15C

THREE-PHASE 22.86 KVKVA HV LV FUSE (AMPS) CATALOG NUMBER COMPATIBLE UNIT300 14/24Y/14 208Y/120 10500 14/24Y/14 208Y/120 20750 14/24Y/14 208Y/120 301000 14/24Y/14 208Y/120 40300 14/24Y/14 480Y/277 10500 14/24Y/14 480Y/277 20750 14/24Y/14 480Y/277 301000 14/24Y/14 480Y/277 401500 14/24Y/14 480Y/277 502500 14/24Y/14 480Y/277 803000 14/24Y/14 480Y/277 100

922020726292202072789220207260922020726192202072629220207278922020727992202072819220207282

F30EMF15CF40EMF15CF10EMF15CF20EMF15CF30EMF15CF40EMF15CF50EMF15CF80EMF15CF100EMF15C

THREE-PHASE 12.47 KVKVA HV LV FUSE (AMPS) CATALOG NUMBER COMPATIBLE UNIT300 14/24Y/14 208Y/120 20500 14/24Y/14 208Y/120 30750 14/24Y/14 208Y/120 501000 14/24Y/14 208Y/120 65300 14/24Y/14 480Y/277 20500 14/24Y/14 480Y/277 30750 14/24Y/14 480Y/277 501000 14/24Y/14 480Y/277 651500 14/24Y/14 480Y/277 1002500 14/24Y/14 480Y/277 125

9220207261922020726292202072799220207280922020726192202072629220207279922020728092202072829220207283

F20EMF15CF30EMF15CF50EMF15CF65EMF15CF20EMF15CF30EMF15CF50EMF15CF65EMF15CF100EMF15CF125EMF15C

1. SEE DWG. 29.04-12A FOR FUSE DIMENSIONS AND DETAILS.

9220207260 F10EMF15C9220207261 F20EMF15C

8/11/11 HOFFMAN BURLISON ELKINS

Page 21: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

ATTACH THE #2 BCTO THE SWITCH GROUNDING TABSWITH BRONZE LUGS

3 REMOTE OPERATOR CABLES ON 3-WAY SWITCH

TOP VIEW OF A 3-WAY VACUUM SWITCH

2. 3-WAY SWITCH IS SHOWN. GROUND 2-WAY AND 4-WAY SWITCHES THE SAME.

3. SPECIAL BRACKETS TO MOUNT REMOTE OPERATORS ARE SHIPPED WITH THE 3-WAY SWITCH. THESE SHOULD BE USED IN PLACE OF THE

4. EACH SWITCH POSITION REQUIRES A SEPARATE REMOTE OPERATOR.

2 BC VAULT GROUNDING LOOP

.

SEE NOTE 5

SEE NOTE 5 SEE NOTE 4

BRACKETS SHIPPED WITH THE REMOTE OPERATORS ON THE 3-WAY SWITCH ONLY.

SEE NOTE 3

EACH CABLE LENGTH 20'OTHER LENGTHSARE SPECIAL ORDER 30', 40', 50'

CONCENTRIC NEUTRAL ATTACHED TO THEGROUNDING RING

7" MIN

FIXED HANDLE REMOTE OPERATOR

CU OPERFIXVACC

CN 11241106

WARNING: REMOTE

OPERATORS ARE

NOT INSULATED

FROM THE

VACUUM SWITCH

REMOTE CABLE TO THESWITCH

2" X 3" WALLMOUNT ANGLE

8-1/2"

OPEN POSITION

PUSH TOCLOSE

IF THE VACUUM SWITCH CANNOT BE POSITIONED TOOPERATE FROM OUTSIDE THEVAULT OR MANHOLE WITH ASTICK, REMOTE OPERATORS SHOULD BE USED AND THEHANDLES MOUNTED AT THE VAULT OR MANHOLE ENTRANCETO ALLOW FOR SWITCHING FROM OUTSIDE THE VAULT ORMANHOLE.

FAULT INDICATOR READOUTSSHOULD BE MOUNTED NEAR THE CORRESPONDING REMOTEHANDLE AND LABELED TO ASSIST IN TROUBLESHOOTINGFAULTED CIRCUITS.

TRAIN AND SECURE REMOTE CABLES TO NOT EXCEED 7"MINIMUM BENDING RADIUS. COIL EXCESS CABLE.

GROUND REMOTE HANDLE

MOUNTING ANGLE WITH

CIRCLE THE TOPOF THE VACUUMSWITCH WITH#2 BC

#2 BC TO THE

VAULT GROUNDING GRID.

5-1/2" 8"

4-1/4"

CABLE ADJUSTINGNUTS

WITH SWITCHCLOSED

RUN BOTH #2 BC GROUND WIRES DOWN THE SIDE OF THE VACUUM SWITCH AND CONNECT THEMSEPARATELY TOTHE VAULT GROUNDING LOOP

REMOTE OPERATOR INSTALLATION ON THE VACUUM SWITCH

ADJUST TO

AFTER REMOVING THE MANUAL HANDLE AND HASPLOOSELY ATTACH THE MOUNTING POST "1" TO THETHREADED BOSSES "2" ON THE SWITCH. USE THETHREADED STUD "3".

LOOSELY ATTACH CABLE AND TOP BAR ASSEMBLY"4" WITH THE BOLTS AND WASHERS PROVIDED TOTHE MOUNTING POSTS.

REMOVE THE DETENT PIN "5" FROM THE BRASSCOUPLING "6" ON THE END OF THE CABLE.

MAKE SURE THE NEOPRENE BELLOWS "7" IS INPOSITION ON THE SWITCH OPERATING SHAFT.

POSITION THE BRASS COUPLING OVER THEOPERATOR SHAFT AND ATTACH WITH THEDETENT PIN. THEN TIGHTEN THE MOUNTINGPOST AND TOP BAR BOLTS.

ADJUST THE CABLE USING THE ADJUSTING NUTS "8" AS SHOWN.

"1"

"2"

"3"

"4"

"5"

"6"

"7"

"8"

SEE NOTE 3

ALLOW 20" CLEARANCEFROM THE TOP OF THE SWITCH WHEN USING REMOTE OPERATORS

DWG.

29.05-01

2"

6. USE SINGLE-PHASE FAULT INDICATORS IF TAP FEEDS FUSES OR A TRANSFORMER BANK (SEE SECTION 23).

5. USE THREE-PHASE FAULT INDICATORS ON SOURCE AND FEED CIRCUITS (SEE SECTION 23).

8/25/10 GUINN GUINN ELKINS

VACUUM SWITCH GROUNDING - FAULT INDICATORS

AND REMOTE OPERATORSR

0

3

2

1

APPR.REVISED BY CK'D

NOTES:

1. CHECK GAS PRESSURE BEFORE INSTALLING. DO NOT INSTALL IF GAS PRESSURE IS LOW.

Page 22: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

ONE LINE DIAGRAM ONE LINE DIAGRAM

350 LBS 450 LBS

MANUAL SWITCHOPERATOR 8-1/2"

3"

CLOSE

OPEN

27" 34-1/2"

MANUAL SWITCH OPERATORS

NOTES:

2. VACUUM SWITCHES ARE SUBMERSIBLE AND CAN BE USED IN VAULTS OR MANHOLES. IF THE LOCATION ISSUBJECT TO FLOODING, SECURE THE SWITCH TO PREVENT FLOATING. VACUUM SWITCHES CAN BE MOUNTEDON WALLS OR UPSIDE DOWN.

3. VACUUM SWITCHES HAVE 600 AMP BUSHINGS (WITH REMOVABLE STUDS) TO ACCEPT 600 AMP ELBOWS AND

4. AN EXTERNAL OPERATING SHAFT IS USED TO PERFORM THE SWITCHING FUNCTION; PUSH TO CLOSE, PULL TOOPEN. A LOCKING HASP IS PROVIDED TO PADLOCK THE OPERATING HANDLE IN THE OPEN

5. CABLE TRAINING AND TERMINATION SHOULD BE CAREFULLY PLANNED. SUPPORT THE CABLES 3' TO 4' FROM THE ELBOW TERMINATIONS.

6. THE VACUUM BOTTLES ARE INSULATED WITH NONFLAMMABLE, HEAVIER THAN AIR, SF6 GAS. THE GAS

CN 11243300CN 11243201

CN 11243102

ONE LINE DIAGRAM

25"

ALL FEET ARE REMOVABLE

9/16" HOLESON 28-5/8"MOUNTING CIRCLE

9/16" HOLESON 23-5/8"MOUNTING CIRCLE

9/16" HOLESON 35-7/8"MOUNTING CIRCLE

22"

SF6 FILL VALVE

GAUGE TOCHECK GASPRESSURE

GROUNDLUGSSEE DWG.

PRESSURE SHOULD BE CHECKED DURING VAULT INSPECTIONS AND SCHEDULED MAINTENANCE. THE PRESSURE SHOULD BE BETWEEN 6 PSI AND 14 PSI. THIS SHOULD BE RECORDED AND COMPARED WITH LATER READINGS. IF THERE IS MORE THAN A 2 PSI DROP THE SWITCH SHOULD BE MONITORED CLOSELY FOR FURTHER DROP. IF THE PRESSURE IS BELOW 4 PSI (FOR NO APPARENT REASON) THE SWITCH SHOULD

TO CHECK THE GAS PRESSURE ONOLDER SWITCHESWITHOUT GAUGESUSE A GOODTIRE GAUGE

SEE NOTE 6

TOP VIEW

FRONT VIEW

SEE NOTE 4

600 AMP BUSHINGSSEE NOTE 3

BE RECHARGED. (CONTACT MATERIAL RECOVERY FOR THE CHARGING KIT) IF SWITCH HAS AGAIN LOST PRESSURE WITHIN 6 MONTHS OF RECHARGING. THE SWITCH SHOULD THEN BE REPLACED. IF THE PRESSUREGAUGE ON THE SWITCH SHOWS LOW PRESSURE, DOUBLE CHECK WITH A TIRE GAUGE BEFORE TAKINGACTION. MATERIAL RECOVERY HAS A DIGITAL PRESSURE GAUGE AVAILABLE FOR LOAN. ALWAYS PUT THE

DWG.

29.05-03

TO REDUCE TO 200 AMP. SEE DWG. 26.03-09. HOWEVER, VACUUM SWITCHES CAN BE ORDERED WITH 200 AMP

OR CLOSED SWITCHED POSITION. SEE DWG. 29.05-01 FOR REMOTE OPERATORS.

8/25/10 GUINN GUINN ELKINS

CAP BACK ON THE VALVE STEM.

KEARNEY VACUUM SWITCHES

SUBMERSIBLE, VAULT TYPE

29.05-01

R

7. ASSIGN EACH SWITCH HANDLE A NUMBER. LABEL AT VACPAC AND AT REMOTE OPERATOR LOCATION. WHENMORE THAN ONE VACPAC IS INSTALLED IN VAULT, USE NEW NUMBER FOR EACH SWITCH.

EXAMPLE: TWO THREE WAY - USE NUMBERS 1, 2, 3, 4, 5 & 6.

0

3

2

1

APPR.REVISED BY CK'D

BUSHINGS IF SUFFICIENT LEAD TIME IS AVAILABLE.

600A CU VSVP2WAY60025C

600A CU VSVP3WAY60025C 600A CU VSVP4WAY60025C

200A CU VSVP3WAY20025CCN 9220168597 (SEE NOTE 3)

4-WAY 2-600A, 2-200ACU VSVAC4W662225C

CN 9220173810 (SEE NOTE 3)

1. CHECK GAS PRESSURE BEFORE INSTALLING. INSTALL IF GAS PRESSURE IS LOW.

Page 23: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.06-01

SOME OF THE TERMS USED WITH TRANSFER SCHEMES ARE LISTED BELOW WITH AN EXPLANATION:

TRANSFER TIMER:

AN ADJUSTABLE TIMER, FROM 2-60 SECONDS, THAT ALLOWS THE ENGINEER TO DELAY THE TRANSFER FROMTHE PREFERRED TO THE ALTERNATE SOURCE. THIS CAN BE SET TO COORDINATE WITH ANY OF THE FEEDERBREAKER OR RECLOSER DELAYED OPERATIONS ALLOWING THE TRANSFER TO TAKE PLACE FOLLOWING A QUICKTRIP THAT DID NOT CLEAR THE CIRCUIT OR ALLOWING PREFERRED SOURCE FEEDER BREAKER OR RECLOSER

AUTO-MAN RESTORE SWITCH:

IF SET IN AUTO, THE LOAD WILL BE RETURNED TO THE RE-ENERGIZED PREFERRED SOURCE. IF SET IN MAN, THELOAD WILL REMAIN ON THE ALTERNATE SOURCE EVEN AFTER THE PREFERRED SOURCE IS RE-ENERGIZED. INTHE MAN POSITION, SERVICE PERSONNEL WILL MANUALLY HAVE TO SWITCH BACK TO THE PREFERRED SOURCE.

RESTORE TIMER:

AN ADJUSTABLE TIMER, FROM 5-180 SECONDS, THAT ALLOWS THE ENGINEER TO DELAY THE AUTOMATICTRANSFER BACK TO THE RE-ENERGIZED PREFERRED SOURCE.

NOTE: THE TRANSFER BACK TO THE PREFERRED SOURCE OCCURS ONLY IF THE RESTORE SWITCH IS SET IN THEAUTO POSITION.

CLOSE-OPEN TRANSITION SWITCH:

THIS DETERMINES WHETHER THE PREFERRED AND ALTERNATE SOURCE WILL BE PARALLELED DURING THE AUTORESTORE SEQUENCE. IF SET TO CLOSE, FOLLOWING THE TIMING OUT OF THE RESTORE TIMER, THE PREFERREDSOURCE WILL CLOSE BEFORE THE ALTERNATE SOURCE OPENS. THIS PARALLELS THE TWO SOURCES FOR ONLY6 CYCLES WHICH IN MOST CASES IS NOT LONG ENOUGH TO AFFECT LOAD FLOWS OR ALLOW REGULATORS TOTHE VOLTAGE CHANGES. THIS ALLOWS THE RESTORATION TO THE PREFERRED SOURCE WITHOUT THE CUSTOMER EXPERIENCING WHAT LOOKS LIKE A QUICK TRIP OPERATION. IF SET TO OPEN, FOLLOWING THETIMING OUT OF THE RESTORE TIMER, THE ALTERNATE SOURCE WILL OPEN AND THEN 6 CYCLES LATER, THE PREFERRED SOURCE WILL CLOSE. THE CUSTOMER WILL EXPERIENCE A MOMENTARY DURING THIS OPERATION.

FAULT-BLOCK:

FAULT BLOCK PREVENTS A FAULTED CIRCUIT FROM BEING TRANSFERRED TO THE ALTERNATE SOURCE BYSENSING OVERCURRENTS ON THE LOAD SIDE FAULT DETECTORS. THIS LATCHES THE NORMAL TRANSFERSCHEME OUT AND ONLY ALLOWS THE PREFERRED SOURCE TO OPEN WITHOUT THE ALTERNATE SOURCE CLOSING. THE INDICATOR IN THE CONTROL CABINET WILL BE LIT WHEN SERVICE PERSONNEL ARRIVE AND

BLOWN FUSES ARE REPLACED AND THE FAULT BLOCK BUTTON IS PUSHED, THE SYSTEM WILL AUTOMATICALLYTIME OUT AND RESET TO NORMAL. IF THE FAULT BLOCK LATCHES DUE TO INRUSH CURRENT BUT THERE IS NOLOSS OF VOLTAGE, A TIMER WILL RESET THE FAULT BLOCK AND THE SYSTEM WILL RETURN TO NORMAL WITH NO TRANSFER OCCURRING. WITH FUSES LOCATED ON THE LOAD TAP, FAULTS WILL BE CLEARED BY THE FUSESAND EVEN THOUGH THE FAULT BLOCK DETECTORS WILL LATCH THE FAULT, NO UNDER-VOLTAGE WILL OCCUR AT THE SENSORS AT THE PREFERRED SOURCE ELBOWS AND THE INRUSH RESTRAINT TIMER WILL CANCEL

FOR PAD-MOUNTED TRANSFERS, THERE ARE SEVERAL PACKAGES AVAILABLE THAT (LIKE THE SUBMERSIBLE

DISTRIBUTION STANDARDS FOR ASSISTANCE IN DESIGN AND ORDER INFORMATION.VERSION SHOWN ON DWG. 29.06-03) CAN BE TAILORED FOR SPECIAL APPLICATIONS AS NEEDED. CONTACT

TO LOCKOUT BEFORE TRANSFERRING TO THE ALTERNATE SOURCE.

6/17/10 DANNA GUINN ELKINS

AUTOMATIC TRANSFER SCHEMES R

0

3

2

1

APPR.REVISED BY CK'D

BOTH PREFERRED AND ALTERNATE SWITCH POSITIONS WILL BE OPEN. AFTER THE TROUBLE IS CLEARED, THE

THE FAULT BLOCK AND NOTHING WILL OCCUR.

Page 24: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.06-03

FOR THREE-PHASE SENSING, USETHREE POTENTIAL TRANSFORMERS

VACUUM SWITCHCN 11243201

3-WAY JUNCTIONOR FEEDTHROUGH

PREFERRED SOURCE ALTERNATE SOURCE

FUSES, CT'S OR 200 AMP FAULT DETECTORSFOR FAULT BLOCK

PT FOR VOLTAGE SENSINGOF ONE PHASE AND CONTROLPOWER FOR THE OPPOSITE SOURCE TRANSFER OPERATOR

VAULT TRANSFORMERBANK

SUBMERSIBLECONTROL CABINET

REMOTE CABLE OPERATOR

REMOTE PUSH BUTTONSTO TEST TRANSFER FROM OUTSIDE THE VAULT

TRANSFER SEQUENCE

NORMALLY CLOSEDTRANSFER OPERATOR

NORMALLY OPENTRANSFER OPERATOR

FAULT OCCURS UPSTREAM OF THE 200 AMP FAULT DETECTORS CAUSING A FEEDER LOCKOUT OR SINGLEPHASING DUE TO A BLOWN FUSE ON THE PREFERRED SOURCE.

CONTROL TIMES OUT AND OPENS THE PREFERRED SWITCH OPERATOR AND CLOSES THE ALTERNATE SOURCE SWITCH OPERATOR.

AFTER THREE-PHASE PREFERRED SOURCE IS RESTORED THE RESTORE TIMER OPENS THE ALTERNATE SWITCH POSITION AND CLOSES THE PREFERRED SWITCH POSITIONRETURNING THE SYSTEM TO NORMAL.

THE CONTROLS HAVE AN OPEN OR CLOSE TRANSITION RESTORE SWITCH TO ALLOW THE RETURN TO THE PREFERRED SOURCE WITHOUT THE CUSTOMER EXPERIENCING A MOMENTARY. THIS PARALLELS THE PREFERRED AND ALTERNATE FEED FOR ABOUT 10 CYCLES.

THE VAULT ENTRANCE

ALTERNATEPT LEADS

PREFERREDPT LEADS

FAULT SENSINGLEADS

TRANSFERCABLE

PREFERRED

ALTERNATE

CABLETRANSFER

LOAD

FAULTED LOAD CIRCUIT DOWNSTREAM OF THE FAULT SENSORS

BANK FAULTS AND BLOWS DIP POLE FUSE(S)

FAULT BLOCK IS LATCHED FROM CURRENT FLOW THROUGH THE SENSORS ON THE LOAD CIRCUIT UPSTREAM OF THE TRANSFORMER BANK.

TRANSFER TIMES OUT AND PREFERRED SWITCH POSITION OPENS.

ALTERNATE FEED DOES NOT CLOSE DUE TO FAULT BLOCK.

SERVICE PERSONAL OPENS LOAD TAP WITH REMOTE HANDLE.

BANK TROUBLE IS CLEARED UP.

RESET FAULT BLOCK INSIDE THE CONTROL CABINET

DIP POLE IS RE-FUSED

RESTORE TRANSFER TIMER WILL CLOSE PREFERRED SOURCE.

LOAD TAP IS CLOSED BY REMOTE OPERATOR HANDLE.

BUSHING

FOR DELTA BANKS, USE A PHASE SEQUENCE RELAY FOR VOLTAGE SENSING.

ABOVEGROUND OR

CN 11241106 AT

6/17/10 DANNA GUINN ELKINS

VAULT AUTO

TRANSFER SCHEMER

0

3

2

1

APPR.REVISED BY CK'D

Page 25: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

23"

10-3/8"

WALL

UNIVERSALMOUNTINGBRACKET

BACKJUNCTION

PLATE

GROUNDING LUGWALL

4"MIN.

MOUNTING ANGLEWALL

TO GROUND

STEP 1

LOOSELY ATTACH UNIVERSAL MOUNTINGBRACKETS TO JUNCTION BACK PLATE ANDPLACE ASSEMBLY AGAINST WALL. ADJUSTBRACKETS FOR PROPER ALIGNMENT ANDMARK THEIR LOCATION ON WALL.

DETACH UNIVERSAL MOUNTING BRACKETS

STEP 2

FROM JUNCTION BACK PLATE. MOUNTBRACKETS ON WALL ACCORDING TO MARKSMADE IN STEP 1.

STEP 3

WITH UNIVERSAL MOUNTING BRACKETSSECURE, FASTEN BACK PLATE (WITHJUNCTION ATTACHED) TO MOUNTINGBRACKETS, MAKING SURE PARKING STANDSARE IN UPRIGHT POSITION.

ADJUST MOUNTING ANGLE TO DESIRED

STEP 4

POSITION.

SYSTEM GROUND USING #4 BC.

STEP 5

TIGHTEN ALL BOLTS SECURELY TO ASSURE NO MOVEMENT DURING OPERATION. GROUND JUNCTION BRACKET TO

REMOVE PROTECTIVE CAPS, CLEAN AND LUBRICATE JUNCTION BUSHING INTERFACE WITH SILICONE GREASE

LOADMAKE OPERATING PROCEDURE.

DWG.

29.08-01

SEE DWGS. 25.01-03A, 25.01-03BFOR PAD-MOUNTED APPLICATIONS

FOR 600 AMP DEADBREAK APPLICATIONSUSE CN 11185402

6/17/10 DANNA GUINN ELKINS

LOADBREAK THREE-WAY JUNCTION -

WALL MOUNTEDR

25.01-10A, 25.01-10B AND 25.01-11.

PROVIDED OR CN 30520803. MATE THREE LOADBREAK ELBOWS TO JUNCTION BUSHINGS FOLLOWING APPLICABLE

NOTES:

1. IF ELBOW IS CLOSED INTO A FAULT, REPLACE ELBOW AND JUNCTION.

0

3

2

1

APPR.REVISED BY CK'D

CN 11186301CU FDTHR253WWMTC

Page 26: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.09-01

THREE-PHASE VAULT TRANSFORMERS R

REVISED CK'DBY APPR.

1

0

3

2

CATALOG NUMBER

THREE-PHASE VAULT TRANSFORMERS

KVA

500750

1296302112963047

HV

14/24Y/1414/24Y/14

LV

208Y/120208Y/120

COMPATIBLE UNIT

TU500V314DYBCTU750V314DYBC

12963013

12963070

12963096

12963062

12963039

12963088

12963100

NO LONGER PURCHASED*

*

10005007501000150025003000

14/24Y/1414/24Y/1414/24Y/1414/24Y/1414/24Y/1414/24Y/1414/24Y/14

208Y/120480Y/277480Y/277480Y/277480Y/277480Y/277480Y/277

TU1000V314DYBCTU500V314DYFCTU750V314DYFCTU1000V314DYFCTU1500V314DYFCTU2500V314DYFCTU3000V314DYFC

NOTES:

1. TRANSFORMERS ARE DESIGNED FOR THE ENCLOSED ROOM VAULT ENVIRONMENT. SPECIAL FEATURESINCLUDE 304L STAINLESS STEEL TANK, DELTA-WYE SWITCH, TAP CHANGER, INTERNAL CARTRIDGEEXPULSION FUSE, LOW-FLAMMABLE OIL, JACKING AND ROLLING PROVISIONS AND A TOP OILTHERMOMETER.

2. UNITS ARE RATED 55°C RISE AND DESIGNED FOR OPERATION IN ENCLOSED LOCATIONS AT AMBIENT

TEMPERATURES OF UP TO 50°C.

3. UNITS SHOULD BE INSTALLED WITH AN EXTERNAL FULL-RANGE CURRENT LIMITING FUSE FOR PROTECTION.

4. THE 3000 KVA UNIT (NO LONGER PURCHASED) IS A STANDARD 65°C RISE UNIT RATED FOR 30° AMBIENT.

PER IEEE STD. C57.91, THIS UNIT SHOULD BE DE-RATED 1.5% FOR EACH DEGREE CELCIUS ABOVE 30°C

AMBIENT. IN A 50°C AMBIENT ENVIRONMENT, ITS RATING WOULD BE ONLY 2100 KVA.

5. WHILE SOME SPARES ARE STOCKED IN GARNER, ALL UNITS SHOULD BE CONSIDERED AS SPECIAL-ORDERNON-STOCK.

6. SEE DWG 29.09-03 FOR OUTLINE DRAWING AND DIMENSIONS.

7. SEE DWG 29.09-05 FOR SECONDARY BUSHING COVER DETAIL.

SEE SECTION 29.04.

6/17/10 DANNA GUINN ELKINS

Page 27: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.09-036/17/10 DANNA GUINN ELKINS

THREE-PHASE VAULT TRANSFORMERS

DIMENSIONS

10 10

8.3 8.3 5.5

9.5 6.5 6.5 6.5

6.5

T

X

X

X

X

13

11

1

7

11

15

8 6

HHHH

2

KVA

DIMENSIONS IN INCHES

M P T(MAX)H

(MAX)W

(MAX)D

64

71

71

71

77

70

83

83

83

83

66

66

66

66

66

34

46

51

51

51

9

9

11.9

11.9

11.9

31

42

46

46

46

500

1500

2500

1000

750

1. FILL PLUG2. TAP CHANGER3. DELTA/WYE SWITCH4. TANK GROUNDS5. DRAIN VALVE AND SAMPLER6. LIQUID LEVEL GAUGE7. THERMOMETER8. PRESSURE/VACUUM REGULATOR AND GAUGE9. SCHRADER VALVE

10. HANDHOLES PER SPECIFICATION11. NAMEPLATE12. LIFTING LUGS13. KVA RATING PLATE14. NON-PCB DETAIL15. BOLTS FOR SECONDARY COVER16. FULLY INSULATED HV NEUTRAL

R

12

12

12

12D

H

W

M

P

4 4

5

14

9

16

3

0

1

2

3

0321

0

3

2

1

APPR.REVISED BY CK'D

WEIGHT

(LBS.)

5270

7500

10,250

10,370

16,250

Page 28: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.09-0510/4/10 GUINN GUINN ELKINS

VAULT TRANSFORMER

SECONDARY BUSHING SUPPORTR

0

3

2

1

APPR.REVISED BY CK'D

NOTES:

1. MAXIMUM OF 14-750 KCMIL CU OR AL CONDUCTORS FOR THIS INSTALLATION USING 2-8 HOLE TERMINALBLOCKS AND USING THE END 2 HOLES FOR BUSHING SUPPORT.

INSTALL 78" FIBERGLASS GUY STRAININ LAST TWO HOLES TO SUPPORTSECONDARY BUSHINGS. CUT ENDS OFFINSULATOR TO INSERT INTO BLOCK

VAULT FLOOR

SET SCREW BLOCK CONNECTORS

MAY BE INSTALLED BACK-TO-BACKON SAME TERMINAL.

SEE DWG. 27.06-12 (TYPICAL)

CONNECTOR. SEE DWG. 02.04-18.

10/25/12 GUINN GUINN ADCOCK

Page 29: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

ON

OFF

15' CORD

GREEN WIRE TOVAULT GROUND

WHITE WIRE TO SYSTEM NEUTRAL

BLACK WIRE TO FUSE

CONNECT TO 120 VOLTSOURCE ONLY

LOAD SIDE

1. INSTALL LIGHT SWITCH AND PLUG AT THE VAULT ENTRANCE.

2. PLUG IS TO ALLOW LIGHTING CIRCUIT TO BE ENERGIZED FROM A GENERATOR DURING VAULT SOURCE

3. THE SWITCH AND FIXTURE ARE WATERTIGHT BUT NOT SUBMERSIBLE.

4. THE PACKAGE TO ADD AN ADDITIONAL LIGHT IS CONNECTED TO THE FIRST LIGHT FIXTURE. AS MANY AS TEN

5. CABLE CLAMPS AND LEAD INSERTS ARE INCLUDED IN THE PACKAGE. USE 1/2" BIT FOR INSERTS AND 1/4" SS

SEAL END OF THECABLE INSULATION

CUT 25' CORD

CONNECT BLACK TO THE SWITCH AND NUT WHITE TO WHITEAND GREEN TO GREEN

TO CONNECT ADDITIONAL LIGHTS REMOVE ONE OF SCREW CAPS IN THE EXISTING FIXTURE AND INSTALL THE WATERTIGHT CONNECTOR AND WIRE NUT MATCHING

15' CORD

6. USE 150 WATT BULB MAXIMUM.

NOTES:

OUTAGES.

ADDITIONAL LIGHTS CAN BE ADDED TO THE ORIGINAL PACKAGE.

OR BRONZE BOLTS IN THE INSERTS.

ARE NOT INCLUDED IN COMPATIBLE UNITNOTE: FUSE HOLDER AND 30 AMP FUSE

DWG.

29.01-01

AS NEEDED

CU LGTVLTKITC

CU LGTVLTADDCCN 13082607

CN 13082706

CN 11130101 FUSE HOLDER - FUSESEC30CCN 21143102 30 AMP FUSE

VAULT LIGHTING KITS (FMO)

WIRE COLORS

0

3

2

1

APPR.REVISED BY CK'D

7. CUSTOMER TO SUPPLY VAULT LIGHTING IN NEW VAULT INSTALLATIONS. DRAWING IS FOR MAINTENANCE ONLY.

HOLDER

7/9/13 KATIGBAK GUINN ADCOCK

Page 30: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

CL 2'-8"

3'-8"

5"

12" 12"

TOP VIEW

4'-7"

32"

11" 21"

SOURCE SIDE

FCABNT23VLTRTC

11/16" DIA.

CABINETCN 14413504

HOLES

FUSEHOLDERCN 11129905FHLDRMRK3SMLZ4C

LOAD SIDE

#4 BCGROUND

NOTES:

1. FUSE CABINET IS RAIN TIGHT AND WHEN REQUIRED MAY BE USED IN ALL ABOVE OR BELOW GROUND VAULTS.

2. USE 200 AMPERE LOADBREAK ELBOWS FOR PRIMARY CABLE TERMINATIONS.

12"12"

2"

4'-0"

HASP FOR PADLOCKING

3. FUSE CABINETS ARE SHIPPED WITH FUSEHOLDER MOUNTINGS BUT WITHOUT FUSEHOLDERS AND FUSES. TYPE SML-4Z FUSEHOLDERS ARE REQUIRED. THESE FUSEHOLDERS ARE LOADBREAK, AND GIVE A VISIBLE INDICATION OF A BLOWN FUSE.

4. THE ABOVE FUSES ARE AVAILABLE AT THE GENERAL WAREHOUSE. OTHERS ARE AVAILABLE BY SPECIAL ORDER.

5. FUSE CABINET HAS AN INTERNAL SAFETY BARRIER BETWEEN THE DOOR AND THE FUSEHOLDERS THAT MUST BE REMOVED FOR ACCESS TO THE FUSEHOLDERS. THE FUSEHOLDERS CAN BE SEEN THROUGH THE CLEAR SAFETY BARRIER.

6. FUSE CABINET IS TO BE GROUNDED WITH #4 BC GROUND WIRE.

7. THE MINIMUM MOUNTING HEIGHT TO THE BOTTOM OF THE FUSE CABINET IS 3'.

8. WEIGHT: APPROXIMATELY 400 LBS.

DWG.

29.04-09

11"

21141809

21141908

21142005

21142104

21142203

21142302

21142401

21142500125E

100E

60E

65E

50E

40E

25E

15E

FSM4100ES23KC

FSM4125ES23KC

FSM465ES23KC

FSM480ES23KC

FSM415ES23KC

FSM425ES23KC

FSM440ES23KC

FSM440ES23KC

CNFUSES COMP. UNIT

FRONT VIEW SIDE VIEW

6/17/10 HOFFMAN GUINN ELKINS

FUSE CABINET, WALL MOUNTED TYPE,

200 AMPERE, THREE-PHASE (FMO)R

0

3

2

1

APPR.REVISED BY CK'D

Page 31: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

B

H

G

1/2" - 13 GROUNDING NUT

E D

C

A

F

I

DWG.

29.04-12C6/17/10 HOFFMAN GUINN ELKINS

G&W - CURRENT LIMITING SUBMERSIBLE FUSE DIMENSIONS (FMO)

REVISED CK'DBY APPR.

1

0

3

2R

1.6"

.56"

FRONT VIEW

TOP VIEW

SIDE VIEW

ROTATINGPARKINGSTANDS

LOAD SIDEIS ENGRAVED

#304 STAINLESS STEEL MOUNTING BRACKET.REMOVABLE STRAPS ALLOW FUSE REPLACEMENTWHILE BRACKET IS MOUNTED TO WALL

MECHANICALLY REINFORCED, EPOXY INSULATION WITHEXTERNAL SEMICON

200A BUSHING WELLW/ REMOVABLE STUD

NOTES: 1. SEE DWG. 29.04-12D FOR APPLICATIONS.

(INCHES)"H" DIM

4.1

4.1

(INCHES)"B" DIM

6.3

7.450-100 29.0

CURRENT RATING

25.93-40

(AMPS)"A" DIM

(INCHES)

15.912.0 6.55.4 5.5

(INCHES)"E" DIM

5.3

(INCHES)"C" DIM

12.0 4.3

"D" DIM(INCHES)

5.5

(INCHES)"F" DIM

13.0

"G" DIM(INCHES) (INCHES)

"I" DIM

3.2

4.3

LOAD

SID

E

Page 32: 29.00 VAULTS, GENERAL 29.01 VAULT ACCESS, LADDER, SUMP

DWG.

29.04-12D6/17/10 HOFFMAN GUINN ELKINS

G&W - CURRENT LIMITING SUBMERSIBLE FUSE -

APPLICATIONS (FMO)REVISED CK'DBY APPR.

1

0

3

2R

2. FUSES ARE FULL RANGE CURRENT LIMITING.

3. LOAD SIDE IS ENGRAVED.

5. NO DERATING OF THE FUSE IS REQUIRED.

6. FUSE CAN BE MOUNTED HORIZONTAL OR VERTICAL.

4. SEE DWG. 29.04-12C FOR DIMENSIONS.

3000

1500

2500

1000

500

750

1000

500

750

TRANSFORMER OR BANKHV LV

14/24Y/14

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

208Y/120

208Y/120

208Y/12014/24Y/14

14/24Y/14

14/24Y/14

14/24Y/14

14/24Y/14

14/24Y/14

14/24Y/14

14/24Y/14125 AMPS

100 AMPS

125 AMPS

80 AMPS

40 AMPS

65 AMPS

80 AMPS

40 AMPS

65 AMPS

CN 85

CN 4555

CN 85

CN 84

CN 151331

CN 151333

CN 84

CN 151331

CN 151333

FUSE/CAT. NO.

FSUB40ES25KC

COMP. UNIT

FSUB65ES25KC

FSUB80ES25KC

FSUB40ES25KC

FSUB65ES25KC

FSUB80ES25KC

FSUB100ES25KC

FSUB125ES25KC

FSUB125ES25KC

12KV

65 AMPS

100 AMPS

40 AMPS

18 AMPS

30 AMPS

40 AMPS

18 AMPS

30 AMPS

CN 151333

CN 4555

CN 151331

CN 10239

CN 151330

CN 151331

CN 10239

CN 151330

FUSE/CAT. NO.

FSUB18ES25KC

COMP. UNIT

FSUB30ES25KC

FSUB40ES25KC

FSUB18ES25KC

FSUB30ES25KC

FSUB40ES25KC

FSUB65ES25KC

FSUB100ES25KC

23KV

100 AMPSCN 4555

FSUB100ES25KC

BRACKET FOR FUSES 50 TO 125 AMPS: CN 10236BRACKET FOR FUSES TO 40 AMPS: CN 10238

TOTAL 3Ø KVA OF

300 14/24Y/24 208Y/12025 AMPS

CN 151329FSUB25ES25KC

12 AMPSCN 00074

FSUB12ES25KC

300 14/24Y/24 480Y/27725 AMPS

CN 151329FSUB25ES25KC

12 AMPSCN 00074

FSUB12ES25KC

NOTES:

1. THESE FUSES TO BE USED FOR MAINTENANCE REPLACEMENTS. SEE DWGS. 29.04-12A AND 29.04-12B FORFOR NEW INSTALLATIONS.