3 reactive services

Upload: arvind

Post on 30-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 3 Reactive Services

    1/12

    PJM 2005

    Reactive Service Working GroupMay 20, 2005

    Reactive Service Compensation

  • 8/9/2019 3 Reactive Services

    2/12

    2005 PJMwww.pjm.com 2

    Reactive Power Background

    Reactive power component of electric power supports system voltages thatmust be managed for system reliability.

    System voltages must be controlled at all key points of the power networkwithin acceptable limits. This control is accomplished by the supply or by the

    consumption of reactive power at these points.

    Large amount of the reactive power that is produced is consumed by powergrid infrastructure to support the transmission of power over long distances.

    The transmission of reactive power over long distances is not efficientbecause reactive power losses in transmission lines and transformersincrease dramatically as demand and power flows increase.

    The high transportation loss characteristic and the fact that voltage magnitude

    tolerances are narrow at all points on the power grid essentially require thatreactive power supply be more distributed across the network.

  • 8/9/2019 3 Reactive Services

    3/12

    2005 PJMwww.pjm.com 3

    Types of Reactive Power Supply

    Static Reactive Power Produced by equipment that cannot quickly change reactive power output level

    Reactive power output level drops when system voltage level drops

    Provided by bulk system capacitors and distribution system capacitors Under normal operating conditions, most reactive requirements should be

    supplied by capacitors located on transmission and distribution system.

    Dynamic Reactive Power

    Produced by equipment that can quickly change reactive power output level Reactive power output level can increase when system voltage level drops

    Provided by generators, static var compensators and synchronous condensers

    Under normal operating conditions, dynamic reactive power supplies shouldoperate with substantial reactive power reserves in order to quickly providereactive power to the system during power system disturbances.

  • 8/9/2019 3 Reactive Services

    4/12

    2005 PJMwww.pjm.com 4

    Reactive Power Demand

    Includes customer load requirements and reactive losses that occur ontransmission system and distribution system components as power istransmitted from generator to load.

    Distribution System Reactive power does not travel far therefore reactive supply must be

    located near the location of the reactive demand (via distribution systemcapacitors)

    designed/operated to minimize reactive support from transmissionsystem Transmission System

    High voltage lines produce reactive power at low power transfer levelsand consume reactive power at high power transfer levels.

    Bulk power system static capacitors needed at key locations to providevoltage support for power transfers.

    For contingency events, power flows instantly increase on remaining linesrapidly increasing reactive power consumption

    Dynamic reactive support and voltage control needed to maintain propervoltage profile during system disturbances.

  • 8/9/2019 3 Reactive Services

    5/12

  • 8/9/2019 3 Reactive Services

    6/12

    2005 PJMwww.pjm.com 6

    Principles for Reactive Power Compensation (cont.)

    Standards for key interconnection points (generator to transmissionand transmission to distribution).

    Capacity type compensation structure coupled with variable

    component dependent on performance compliance. Reactive capability of all generators provides some reliability benefit

    (marginal value today could be critically important in future)

    Efficient load power factor to minimize transmission system supportof the distribution system

    Common set of load power factor standards across the PJM market.

    Appropriate performance compliance measurements andperformance incentives for meeting load power factor standards

  • 8/9/2019 3 Reactive Services

    7/12

    2005 PJMwww.pjm.com 7

    Recommendations

    Develop common standard, method for measuring compliancewith the standard and incentive for meeting or exceeding thestandard for :

    generator reactive capability and voltage control load power factor efficiency

    Ensure consistent compensation for similar reactive supply types

    Be cautious with moving forward with a needs test

  • 8/9/2019 3 Reactive Services

    8/12

    2005 PJMwww.pjm.com 8

    Generator Reactive Standards/Compensation

    Standards reactive capability requirement of .9 lag to .95 lead

    must operate with AVR in service at all times

    Compensation generator compensation should be commensurate with actual

    reactive capability

    reactive allocation factor of (1 - PF2

    ) should be adjusted by actualpower factor to prorate original FERC approved costs. actual power factor obtained from periodic reactive capability tests

    generator AVR status should become a required SCADA point

    regularly monitor generator response to operator requests forreactive and automatic response to contingency events

  • 8/9/2019 3 Reactive Services

    9/12

    2005 PJMwww.pjm.com 9

    Generator Reactive Standards/Compensation (cont.)

    Compensation (cont) incorporate AVR availability rate and actual operational response

    into compensation structure

    repeated unsatisfactory performance should disqualify generatorfrom reactive compensation

    Other Issues

    Fixed $/MVAR-year rate for capability versus FERC-approved rate Should existing contracts continue or fall into new rate structure?

    How to apply power factor adjustments to black-box settled units

  • 8/9/2019 3 Reactive Services

    10/12

    2005 PJMwww.pjm.com 10

    Load Power Factor Standards

    Reactive power consumption is an equally important component ofmaintaining an adequate voltage profile not just a supply matter

    Standards

    develop a standard power factor requirement for the interconnection point

    between transmission and distribution systems develop method of measuring compliance with the standard

    Compensation

    Compliance measure could be used to adjust reactive service payments

    generator compensation should be commensurate with actual reactivecapability

    Enforcement of standards can start with PJM holding zonal customers to

    standard Sub-zonal customers held accountable through interconnection agreements

    with EDC

  • 8/9/2019 3 Reactive Services

    11/12

    2005 PJMwww.pjm.com 11

    Needs Test?

    PJM recommends caution in this area since the reactivecapability of all generators provide some reliability benefit

    Reactive sources are long-lived assets and system reactive

    needs change over time reactive supply of marginal value today may be of critical

    importance in the future

    A granular needs test designed to avoid compensating forreactive supply that is redundant must try to anticipate a dauntingarray of possible system states each of which may result in a

    different conclusion

  • 8/9/2019 3 Reactive Services

    12/12

    2005 PJMwww.pjm.com 12

    Consistent Compensation for Similar Supply Types

    Schedule 2 provides compensation for generators

    Not clear if synchronous generators and newer technologies likeSVC are covered in Schedule 2

    Explore one single and consistent compensation approach for all

    types or at least similar types of reactive power sources