Page 1: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Brief Introduction for Automated Relay Testing(Relay type DUOBIAS-M)

Kamin DaveManager – Sales & Applications

South Asia & Middle East

DOBLE ENGINEERING COMPANY

Page 2: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Protection Relay Testing:

Testing of Differential Protection Relay type DUOBIAS-M

Page 3: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: DUOBIAS-M

Two/Three Winding Differential Protection relaysInbuilt IDMTL & Inst. O/C function for backup ProtectionLow Impedance Restricted Earth Fault ProtectionAutomatic calculation for TAP values based on CTRSettings for Transformer & CT vector group compensations 2nd Harmonic content setting during inrush period due to point on wave switching

DFT (Independent or Cross Blocking)

Page 4: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: DUOBIAS-MMAKE : REYROLLEMODEL : DUOBIAS-MRelay Settings:Differential Element:

MVA = 20VWDG1 = 110KVVWDG2 = 11KVTRCON = DYn11.CTCON = YYID> = 0.2Bias Slope Limit = 4.0PUID>> = 8.0PUm1 = 20% (0.2pu)(2f0) / I(f0) = 20.0%

Page 5: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: DUOBIAS-MMAKE : REYROLLEMODEL : DUOBIAS-MLocation : 220KV Kavoor SS, KPTCLRelay Settings:Differential Element:

CTR1 = 200CTR2 = 1200W1 = 1.9057W2 = 1.14345In = 1AStar winding is earthed

Page 6: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: DUOBIAS-MFLC on TR Primary side:

IFLC = (20*1000) / (1.7325*110)= 104.94 Ampere

FLC on TR Secondary side:IFLC = (20*1000) / (1.7325*11)

= 1049.45 AmpereCF1 = (1*104.94) / (200*1) = 0.699W1 = (1 / CF1) = (1/0.699) = 1.9057CF2 = (1*1049.45) / (1200*1) = 0.874W2 = (1/CF2) = (1/0.874) = 1.14345

Page 7: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Setting: REYDISP

Diff Settings

Page 8: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Setting: REYDISP

CT Ratio for WDG1 & WDG2

Page 9: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Characteristic: Dual Slope

Page 10: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Characteristic on Settings:

m1=20%m2

Page 11: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Test Equipment

• Make : DOBLE

• Model : F6150

Software

• F6TesT Version 2.19-1064

Page 12: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

IA

IB

IC

I1

I2

I3

DUOBIAS

Test Circuit:

Source Configurations:Six current sources

Winding 1 currents

Winding 2 currents

Page 13: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup test for Winding1

• Pickup test for winding2

• Slope Characteristic test

• 2nd Harmonic test

Tests conducted:

Page 14: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Winding1 Pickup Test

Use “RAMP” Module

Page 15: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test:Pickup Test for Winding1 (WDG1):-Ipickup = (ID)*CF1

= (0.2)*0.524= 0.11A

Pickup Test for Winding2 (WDG2):-Ipickup = (ID)*CF2

= (0.2)*0.944 = 0.17A

Page 16: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

How to Create Test Plan in Software???

Page 17: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on Mouse & Click on “Append”to Create new location in location level

Page 18: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on Mouse & Click on “Append”to Create new relay in Relay level

Page 19: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on Mouse & Click on “Append”to add New Testplan in Testplan level

Page 20: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on Mouse & Click on “Append”to add New Testplan in Testplan level

Page 21: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Test Type”& select “Ramp” module

Page 22: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Double click on“Test name” & createNew test definition

Page 23: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Pulldown arrow &Select “6 Currents (Right bank)”

Page 24: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Yes”

Page 25: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Now, it is showing6 Current sources for test

Page 26: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test: WDG1

Expected value = 0.1A Actual Test value = 0.11A

WDG1 current sources

Select Trigger “Open to Close”

Pickup value

Page 27: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test: WDG1

Save & Close module”

Page 28: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Winding2 Pickup Test

Use “RAMP” Module

Page 29: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on Mouse & Click on “Append”to add New Testplan in Testplan level

Page 30: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Test Type”& select “Ramp” module

Page 31: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Double click on“Test name” & createNew test definition

Page 32: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Pulldown arrow &Select “6 Currents (Right bank)”

Page 33: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Pulldown arrow &Select “6 Currents (Right bank)”

Page 34: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Yes”

Page 35: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Now, it is showing6 Current sources for test

Page 36: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test: WDG2

Expected value = 0.17A Actual Test value = 0.18A

WDG2 current sources

Select Trigger “Open to Close”

Pickup value

Page 37: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test

Use “DiffChar” Module

Page 38: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test:

Page 39: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test:Vector Compensation

Page 40: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test:

Page 41: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test:Vector Compensation

Page 42: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test:

YDY0 YD1

Relay

0o

0o

+30o

0o

YD11 Vector Compensation

Page 43: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

How to create testplan???

Page 44: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Add” button

Select “Differential” Function, enter “Function name”And Click on “Next” button

Page 45: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “Bias Formula” from list

Bias current Formula:Ibias = (IP+IS) / 2

Page 46: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter YDY0 & YD1 R

Amplitude Compensation

DYn11

YDY0 YD1

Page 47: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Modify” button

Page 48: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Slope SLP1 = 20% & SLP2 based on relay setting

SLP1=20%

SLP2

How to AdjustSlope?

Enter Pickup value

Page 49: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Bias current (Ibias) formula from list

Bias current Formula:Ibias = (IP+IS) / 2

Click on “Close” buttonAfter setting Slope curve

Page 50: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Append” button to Create new test module

Page 51: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “DiffChar” module

Page 52: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select relay settings from list

Page 53: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Test elements

Page 54: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Max test current 15A

Page 55: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger “Open to Close”

Page 56: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select test points for test & click on Add Point to List

Page 57: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Blue line showsExpected curve

White line showsActual results on Selected points

Test results

Page 58: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Export report in PDF, MS Word, Text format

Page 59: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Second Harmonics Test

Use “DATC 6.38” Module

Page 60: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

%2nd Harmonics aremore during TREnergization

Page 61: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

IA

IB

IC

I1

I2

I3

DUOBIAS

2nd Harmonic Test : Test Method

50Hz +100HzCombine signal

Page 62: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

How to Set Harmonics in“DATC 6.38” Module??

Page 63: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Harmonic

Select 2nd Harmonic

Enter 2nd HarmonicContent 18% inAll three phases

Page 64: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Time Configuration

Page 65: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select contact status“O C”

Page 66: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter trip time value

Page 67: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Oscillogram

Page 68: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

18% 2nd Harmonics in all three phases

Click on “Start Transient” button

Page 69: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Harmonic Analysis barShows % of 2nd Harmonicis 18%

Harmonic Analysis barShows FundamentalCurrent is 100%

Page 70: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

2nd Harmonic Test : Trip/Block

Relay issued Trip commandBecause injected valueOf 2nd harmonicContent is less thanSet value

Page 71: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Harmonic

Select 2nd Harmonic

Enter 2nd HarmonicContent 22% inAll three phases

Page 72: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Oscillogram

Page 73: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

2nd Harmonic Test : Trip/Block

22% 2nd Harmonics in all three phases

Start Transient

Page 74: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

2nd Harmonic Test : Trip/Block

Relay Issued Trip command when 2nd Harmonic components(18%) Less than set value (20%)

Relay blocked trip command when 2nd Harmonic components(22%) more than set value (20%)

Page 75: 33.DUOBIAS-M Relay Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

DOBLE ENGINEERING COMPANY305-SAKAR, O.P. ROADNR. ABS TOWERVADODARA-390 015INDIA. Tel:- +91 265 655 77 15EMAIL ID:- [email protected]:- www.doble.com