Lot 5 – 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017.
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
24 June 2017 The Bathla Group 17 Gilba Road Girraween NSW 2145 Dear Mr Bijan Afsar
RE: BUILDIG CODE OF AUSTRALIA REPORT
PROPERTY: LOT 5 - 1086 RICHMOND ROAD MARSDEN PARK NSW Please find enclosed our BCA 2016 of Australia Report in relation to the proposed residential flat buildings at the above property. Should you require further information in relation to the above, please do not hesitate to contact the undersigned. Regards,
Greg Evans Director Accredited Certifier BPB 1870 360 Certification
360 Certification M: 0422 688 491
[email protected] Mosman NSW 2088
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 1 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
BCA 2016 CODE REPORT
LOT 5 – 1086 RICHMOND ROAD MARSDEN PARK
Date: 24 JUNE 2017
Our Re: C2017057
TABLE OF CONTENTS
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 3 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
CONTENTS Page No.
1.0 – EXECUTIVE SUMMARY ............................................................ 3
1.1 DESIGN CONSIDERATIONS ....................................................................... 3
2.0 – PROPERTY DESCRIPTION ....................................................... 4
2.1 – BUILDING LOCATION ........................................................................... 4
2.2 – BASIS OF ASSESSMENT ......................................................................... 4
2.3 – REPORT PURPOSE ............................................................................... 5
2.4 – REPORT METHODOLOGY........................................................................ 5
2.5 – EXCLUSIONS ...................................................................................... 5
2.6 – BUILDING DESCRIPTION ....................................................................... 6
3.0 - BCA 2016 OF AUSTRALIA ASSESSMENT ................................. 7
3.1 – STRUCTURAL & FIRE RESISTANCE (SECTION B & C OF NCC) ......................... 7
3.2 – ACCESS & EGRESS (SECTION D, NCC) .................................................. 13
3.3 – SERVICES AND EQUIPMENT (SECTION E, NCC) ........................................ 19
3.4 – HEALTH & AMENITY (PART F, NCC) ..................................................... 23
3.6 – ENERGY EFFICIENCY. (PART J, NCC) ..................................................... 26
4.0 – FIRE SAFETY AND OTHER MEASURES .................................. 30
5.0 – CONCLUSION ........................................................................ 31
6.0 – REFERENCES & PLANS .......................................................... 32
© Mosman Certifiers Pty Ltd. All rights reserved. 360 Certification (Mosman Certifiers Pty Ltd) has prepared this document for the sole use of the Client and for a specific purpose, each as expressly stated in the document. No other party should rely on this document without the prior written consent of 360 Certification. 360 Certification undertakes no duty, nor accepts any responsibility, to any third party who may rely upon or use this document. This document has been prepared based on the Client’s description of its requirements and 360 Certification’s experience, having regard to assumptions that 360 Certification can reasonably be expected to make in accordance with sound professional principles. 360 Certification accepts no liability for information provided by the Client and other third parties used to prepare this document or as the basis of the analysis. Subject to the above conditions, this document may be transmitted, reproduced or disseminated only in its entirety. Document History
Revision Date Prepared & Approved
DRAFT 24 June 2017 Greg Evans, Accredited Certifier BPB 1870, 360 Certification
Revision 1 Greg Evans, Accredited Certifier BPB 1870, 360 Certification
1.0 – EXECUTIVE SUMMARY
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 3 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
1.0 – Executive Summary This BCA 2016 Report has been prepared to assess the proposed plans appurtenant to the Development Application that is to be submitted to Blacktown Council for a new residential flat building with 76 apartments and basement carparking for 130 vehicles. The assessment of the documentation has revealed that the building is primarily capable of complying with the Deemed-to-Satisfy [herein ‘DTS’] provisions of the BCA 2016 Code 2016 (Volume 1, Class 2-9 Buildings) [herein ‘BCA 2016’], and where necessary the Performance Requirements, without modification that require a development consent to be modified.
1.1 Design Considerations
No.
Recommendation
DTS Clause
1 The proponent has indicated that they intend to reduce the FRL’s of the Class 7b parts to 120 minutes, via a performance solution based on fire engineering analysis.
Clause 3 of Spec. C1.1, C2.8, C2.9,
C2.10
2 The total floor area and volume of the Class 7a & 7b parts is more than the maximum 5,000m2 permitted - approximately 5300m2. The proponent has indicated that they intend to address the slightly enlarged fire compartment via a performance solution based on fire engineering analysis.
C2.2
3 The spandrels are capable of complying provided the horizontal spandrels extend past either side of the opening by 450mm.
C2.6
5 The public corridors are greater than 40 metres in length and therefore must be smoke separated in accordance with Clause 2 of Specification C2.5. Currently the corridor between grid line B & F is not smoke separated like the corridor between grid line G and N. Additional smoke separation to be show on the plans.
C2.14
6 The exit travel distances within the basement do not comply with this clause, as:
- occupants have 45m to a point of choice instead of 20m; and, - 45m to one of the exits instead of 40m.
A third exit from the basement towards grid line N would resolve this matter. If a third stair is not proposed the proponent has indicated that they intend to address this via a performance solution based on fire engineering principles.
C2.14
7 The exit travel distances on the roof does not comply with this clause, as: - occupants have 22m to a point of choice instead of 20m between grid line J & L;
and, The proponent has indicated that they intend to address this via a performance solution based on fire engineering principles.
D1.4
8 The direct distance between alternative exits within the basement is 60m as required. However, if measured from first exit door to the point of choice to the second exit door, the distance increases to approximately 62m. Also, the distance between the alternative exits on the roof is greater than the maximum 45m and is approximately 60m. The proponent has indicated that they intend to address this via a performance solution based on fire engineering principles.
D1.5
9 The fire isolated stair at grid line N must have a doorway leading to outside, and the living room window of UG15 protected on the inside as required by D1.7(c) and as per C3.4
D1.7
10 The exit doors swing in the direction of egress as required, except the two sets of double doors from the ground floor hallways and the garbage exit door.
D2.20
11 Direct access must also be provided to the sprinkler valve set at basement level one between grid line I-J, which requires a minor layout change to this area.
E1.5
2.0 – PROPERTY DESCRIPTION
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 4 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
2.0 – Property Description
2.1 – Building Location
The site is currently located on Lot 51, Deposited Plan No. 1196583. This building is to be located on proposed Lot 5, 1086 Richmond Road, Marsden Park NSW. Existing farmland and farm type buildings currently adjoins subject property. Site plan: 1086 Richmond Road Marsden Park NSW © NSW Government.
2.2 – Basis of Assessment
This BCA 2016 Report has been prepared based of the following:-
I. The Deemed-to-Satisfy and the Performance Requirements of BCA 2016 including NSW Variations and relevant Australian Standards;
II. Plans prepared by the Bathla Group, dated May 2017;
III. The Environmental Planning & Assessment Act 1979;
IV. Disability (Access to Premises — Buildings) Standards 2010;
2.0 – PROPERTY DESCRIPTION
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 5 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
2.3 – Report purpose
This BCA 2016 Report has been prepared to assess the proposed plans appurtenant to the Development Application that is to be submitted to Blacktown Council for a new residential flat building with 76 apartments and basement carparking for 130 vehicles. The BCA 2016 Report will: a) compare the proposed building against the Deemed-to-Satisfy provisions of
BCA 2016 including NSW Variations and relevant Australian Standards;
b) Identify DTS breaches that can be altered to comply with the DTS provisions of BCA 2016;
c) Identify DTS breaches and relevant performance requirements to be considered for Performance Solutions by the fire engineering and other consultants.
2.4 – Report methodology
This BCA 2016 report initially relies upon the plans of the proposed building, and a review of the structure against Deemed-to-Satisfy provisions of BCA 2016 and adopted Australian Standards. Consideration can be given to the Performance Requirements of BCA 2016 where appropriate. Where relevant the assessment can include the following categories – ▪ Structural; ▪ Fire resistance and compartmentation; ▪ Occupant Access/Egress; ▪ Fire Safety/Protection Services ▪ Health & Amenity; ▪ Energy Efficiency. Where compliance is not achieved with the relevant Deemed-to-Satisfy provisions, recommendations will be made to comply with the DTS or the relevant performance requirements.
2.5 – Exclusions
The report is limited to the proposed buildings and excludes the existing structures. This report does not imply, nor make reference to structural design or operating capability or design of any electrical, fire, hydraulic or mechanical services. Furthermore, limited reference is made to the Disability (Access to Premises — Buildings) Standards 2010 and the Disability Discrimination Act 1992 (Cth).
2.0 – PROPERTY DESCRIPTION
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 6 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
2.6 – Building Description
Building Residential flat building.
Use/Classifications
Storey Description Classification(s)
Basement Carpark 7a and 7b
Ground Floor Carpark 7a and 7b
First Floor RFB 2
Second Floor RFB 2
Third floor RFB 2
Roof Floor RFB 2
Note: The basement storage is more than 10% of the floor area of the storey. The storage is
Class 7b, which requires higher FRL’s.
Rise in Storeys The proposed building has a rise in storeys of five as per Clause C1.2.
Note: The lift lobby on the roof causes that level to be a storey.
Storeys contained The proposed building will contain seven storeys.
Floor Area The total floor area and volume of the Class 7a & 7b parts is more than
the maximum 5,000m2 permitted - approximately 5,300m2.
Volume The volume of the Class 7a and 7b part is less than the maximum permitted
for type A Construction of 30,000m3.
Effective Height The building will have an effective height of approximately 12.00 m.
Car parking Spaces 130 on the basement level.
Type of Construction The proposed building requires Type ‘A’ Construction.
Primary FRL’s Class 2 – 90 minutes;
Class 7a – 120 minutes; Class 7b – 240 minutes.
Fire Compartments The carpark on basement 1 & 2 is one fire compartment. Ground, Level 1,
level 2, level 3 and roof are effectively separate fire compartments. The
apartments are fire separated – not separate fire compartments.
HBCF Insurance HBCFI is NOT applicable as the building has a rise in storeys of five (as
defined by the Home Building Regulation 2014, being levels: ground, level
1, level 2, level 3 and the roof level. As such, the building is considered a multi-storey building under clause 54 of the Home Building Regulation 2014). The basements have been excluded as they are wholly beneath the
ground and therefore not counted in the rise in storeys.
Zoning R3 - Medium Density Residential:
RE1 - Public Recreation: Local Open Space
SP2 - Infrastructure: Classified Road
SP2 - Infrastructure: Local Road
Flood Prone No
Acid Sulphate Soils No
Heritage No
Conservation Area No
Bushfire Prone Land Yes. Far western corner is located within buffer zone.
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 7 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
3.0 - BCA 2016 of Australia Assessment
3.1 – Structural & Fire Resistance (Section B & C of NCC)
Clause Description Clause Requirements/Comments Compliance
Yes/No Part B Structural Provisions B1.0 Deemed-to-satisfy provisions Part applicable. Note only.
B1.1 Resistance to actions. Subject to geotechnical and structural
engineering.
Yes
B1.2 Determination of individual
actions.
Subject to geotechnical and structural
engineering.
Yes
B1.3 ***** Blank clause. N/A
B1.4 Determination of structural resistance of materials and
forms of construction.
Subject to geotechnical and structural engineering.
Yes
B1.5 Structural software. Note only. Note only.
B1.6 Construction of buildings in flood
hazard areas.
Property not identified as flood prone. N/A
Clause Description Clause Requirements/Comments Compliance Yes/No
Part C1 Fire Resistance and Stability C1.0 DtS Provisions. Applicable performance requirements
for building solutions. Note only
C1.1 Type of construction required. Type ‘A’ construction required to
comply with Clause 2 and 3 of Specification C1.1.
The majority of building elements
must be non-combustible, including: external walls, lifts and fire resisting
internal walls.
Internal load bearing walls must be of
concrete, masonry or fire protected timber.
The roof does not require an FRL, but must be non-combustible.
The buildings’ required FRL’s.
Class 2 – 90 minutes;
Class 7a – 120 minutes; Class 7b – 240 minutes.
The proponent has indicated that they
intend to reduce the FRL’s of the Class 7b parts to 120 minutes, via a
performance solution based on fire
engineering analysis. REFER TO DESIGN CONSIDERATIONS
Yes,
subject to fire engineering
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 8 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
C1.2 Calculation of rise in storeys. The proposed building has a rise in storeys of five, as per Clause C1.2 of BCA 2016. The building contains seven
storeys including the basement.
Yes
C1.3 Buildings of multiple
classifications.
The building contains Class 2, 7a and
7b parts. For this clause only, the
building is identified as a five storey Class 2 building which requires Type
‘A’, construction. Note: The basement storage is more than 10% of the floor area of the storey. As such, the storage is Class 7b, which requires higher FRL’s.
Yes
C1.4 Mixed type of construction. The building is not subject to mixed types of construction.
N/A
C1.5 Two storey Class 2, 3 or 9c buildings.
Not applicable as the Class 2 has a rise in storeys of five.
N/A
C1.6 Class 4 parts of buildings. No Class 4 parts. N/A
C1.7 Open spectator stands and
indoor sports stadiums.
Not applicable N/A
C1.8 Lightweight fire rated
construction.
If proposed, lightweight fire rated
construction is to comply with this clause and manufactures
specifications.
Yes
C1.9 ***** Blank clause. N/A
C1.10 Fire hazard properties NSW Variations NSW C1.10(a)(v) NSW C1.10(b) NSW C1.10(c)(xiii).
The fire hazard properties of floor linings, floor coverings, wall
linings, ceiling linings and air-handling ductwork, are capable of complying
with this clause.
As the Class 2 part of the building will
not be sprinklered, the floor linings are to achieve a critical radiant flux not less than 2.0 and a smoke development rate of not less than 750
percent minutes.
Wall and ceiling linings are assumed to
be plasterboard and will comply with this clause.
Yes
C1.11 Performance of external walls in
fire.
Not applicable as the building not
proposed to be constructed with concrete panels.
N/A
C1.12 Non-combustible materials Noted. Note only
C1.13 Fire-protected timber: Concession
Not proposed to comply with requirements for fire protective
timber.
N/A
Part C2 Compartmentation and Separation
C2.0 DtS Provisions. Applicable performance requirements for building solutions.
Note only
C2.1 Application of Part. Applicable Yes or No Applicable
C2.2 General floor area and volume
limitations.
The total floor area and volume of the
Class 7a & 7b parts is more than the
Yes,
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 9 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
maximum 5,000m2 permitted -
approximately 5300m2. The proponent has indicated that they intend to
address the slightly enlarged fire compartment via a performance solution based on fire engineering analysis. REFER TO DESIGN CONSIDERATIONS The volume of the carpark is less than
the maximum 30,000m3 permitted.
The area and volume limitations do not apply to the Class 2 parts.
Subject to fire
engineering
C2.3 Large isolated buildings. Not a large isolated building. N/A
C2.4 Requirements for open space
and vehicular access.
Not a large isolated building.
N/A
C2.5 Class 9a and 9c buildings. NSW Variations NSW C2.5(b).
Not a Class 9a or 9c building. N/A
C2.6 Vertical separation of openings in external walls.
Spandrel protection is required.
All spandrels must achieve an FRL of 60/60/60or 90/90/90 if load bearing.
Vertical spandrels must be: (A) is not less than 900 mm in height; and
(B) extends not less than 600 mm above the upper surface of the intervening floor; and
(C) is of non-combustible material having an FRL of not less than 60/60/60; or Horizontal spandrels must be:
a slab or other horizontal construction that— (A) projects outwards from the external face of the wall not less than 1100 mm; and (B) extends along the wall not less than 450 mm beyond the openings concerned; and (C) is non-combustible and has an FRL of not less than 60/60/60
In this instance the spandrels are capable of complying provided the
horizontal spandrels extend past either
side of the opening by 450mm. REFER TO DESIGN CONSIDERATIONS
Yes
C2.7 Separation by fire walls. At present no fire walls, as defined by the BCA, proposed or required.
N/A
C2.8 Separation of classifications in the same storey.
The basement storage is more than 10% of the floor area of the storey. As
Yes,
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 10 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
such, the basement levels must have
an FRL of 240 minutes or the Class 7b parts must be fire separated from the
Class 7a parts.
As this fire separation is not practical or cost effective, the proponent has
indicated that they intend to reduce
the FRL’s of the Class 7b parts to 120 minutes, via a performance solution
based on fire engineering analysis. REFER TO DESIGN CONSIDERATIONS
The ground floor, first floor, second
floor, third floor and the roof only
have a classification of 2. As such this clause does not apply to those parts.
subject to fire
engineering
C2.9 Separation of classifications in
the different storey.
The basement storage is more than
10% of the floor area of the storey. As such, the basement levels must have
an FRL of 240 minutes or the Class 7b parts must be fire separated from the
Class 7a parts.
Assuming the basement levels FRL’s
are reduced to 120 minutes, via a performance solution based on fire
engineering analysis, the ground floor slab must have an FRL of 120
minutes, being the higher FRL
between the Class 7a/7b and 2 parts. REFER TO DESIGN CONSIDERATIONS
Yes,
subject to fire engineering
C2.10 Separation of lift shafts. Assuming the basement levels FRL’s are reduced to 120 minutes, via a
performance solution based on fire
engineering analysis, the lift is to be fire isolated with construction
achieving an FRL of 120 minutes on the basement levels and 90 minutes
on the Class 2 parts. Doorways to the
lift are to have an FRL of --/60/--. REFER TO DESIGN CONSIDERATIONS
Yes, subject to fire
engineering
C2.11 Stairways and lifts in one shaft. The lift and stairs are within separate fire isolated shafts as required.
Yes
C2.12 Separation of equipment. The following equipment must be fire
separated from the building: - (i) lift motors and lift control panels; or
(ii) emergency generators used to sustain emergency equipment operating in the emergency mode; or (iii) central smoke control plant; or (iv) boilers; or
(v) a battery or batteries installed in the building that have a voltage
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 11 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
exceeding 24 volts and a capacity exceeding 10 ampere hours. (vi) on-site fire pumps must comply with the requirements of AS 2419.1 Where required, fire separating construction must achieve an FRL of
120/120/120 with doorways achieving
an FRL of --/120/30.
At present the hydrant pump room on ground floor and MSB, are fire
separated as required.
C2.13 Electricity supply system. The proposed fire pumps and main electrical distribution board serving the
pump or FIP are to be fire separated with fire rated construction achieving
an FRL of 120/120/120 with doorways
achieving an FRL of --/120/30.
The emergency switchgear must be separated from non-emergency
switchgear as per Clause C2.13(d).
Yes
C2.14 Public corridors in Class 2 and Class 3 buildings.
The public corridors are greater than 40 metres in length and therefore
must be smoke separated in accordance with Clause 2 of
Specification C2.5.
Currently the corridor between grid
line B & F is not smoke separated like the corridor between grid line G and
N. Additional smoke separation to be
show on the plans. REFER TO DESIGN CONSIDERATIONS
Yes subject to minor change.
Part C3 Protection of Openings C3.0 DtS Provisions. Applicable performance requirements
for building solutions. Note only
C3.1 Application of part. Applicable Yes or No. Note only
C3.2 Protection of openings in external walls.
No windows require protection as per Clause C3.2.
N/A
C3.3 Separation of external walls and
associated openings in different fire compartments.
No external walls in different fire
compartments are exposed to each other. As such, clause not applicable.
N/A
C3.4 Acceptable methods of
protection.
See Clause 3.2 above. N/A
C3.5 Doorways in fire walls. No fire walls. As such, not applicable. N/A
C3.6 Sliding fire doors. No sliding fire doors. N/A
C3.7 Protection of doorways in horizontal exits.
No horizontal exits. N/A
C3.8 Openings in fire isolated exits. Doorways to the fire isolated stairs are
to have self-closing fire doors achieving an FRL of --/60/30.
Yes
C3.9 Service penetrations in fire
isolated exits.
Fire isolated stairs must not be
penetrated with any plumbing or
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 12 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
electrical services, except fire services,
including exit signs, emergency lighting and hydrants.
C3.10 Openings in fire isolated lift shafts.
The doorways to the lift shaft must be protected by –/60/– fire doors that—
(i) comply with AS 1735.11; and
(ii) are set to remain closed except when discharging or receiving
passengers, goods or vehicles.
Yes
C3.11 Bounding construction: Class 2, 3, 4 & 9b buildings NSW Variation NSW C3.11(d).
The doorways to the residential sole occupancy units, must be self-closing
fire door sets, achieving an FRL of --/60/30 as the building
requires Type A construction.
Yes
C3.12 Openings in floors and ceilings for services.
Openings in the ground, first floors, and enclosed roof parts are required
to be protected as they require an FRL with respect to integrity and
insulation.
Yes
C3.13 Openings in shafts. In a building of Type A construction, an opening in a wall providing access to a
ventilating, pipe, garbage or other service shaft must be protected by—
(a) if it is in a sanitary compartment — a door or panel which, together with
its frame, is noncombustible or has an
FRL of not less than –/30/30; or
(b) a self-closing –/60/30 fire door or
hopper; or
(c) an access panel having an FRL of
not less than –/60/30; or
(d) if the shaft is a garbage shaft — a
door or hopper of non-combustible construction.
Yes
C3.14 ***** Blank clause. N/A
C3.15 Openings for service installations Where an electrical, electronic,
plumbing, mechanical ventilation, air-conditioning or other service
penetrates a building element (other than an external wall or roof) that is
required to have an FRL with respect
to integrity or insulation or a resistance to the incipient spread of fire, that installation must be fire stopped as per this clause.
Yes
C3.16 Construction joints. Construction joints to be fire stopped
as per this clause.
Yes
C3.17 Columns protected with
lightweight construction to
achieve an FRL.
Columns proposed to be protected
with lightweight fire rated construction
to comply with this clause.
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 13 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
3.2 – Access & Egress (Section D, NCC)
Clause Description Clause Requirements/Comments Compliance Yes/No
Part D1 Provisions for Escape D1.0 DtS Provisions Applicable performance requirements
for building solutions. Note only.
D1.1 Application of Part Part applicable Note only.
D1.2 Number of exits required NSW Variation NSW D1.2(d)(vii).
The basements have two exits as required.
The Class 2 parts require at least one
exit as per this clause.
[Note: Additional exits are required for exit travel distance].
Yes
D1.3 When fire-isolated stairways and ramps are required.
Stair Description Fire Isolated
Y/N
1 Stair 1 serving the basements at grid line C.
Yes, as the stair connects two basement levels.
2 Stair 2 serving the basements at grid line J.
Yes, as the stair connects two basement levels.
3 Stair serving first, second, third and roof levels at grid line C.
Yes, as the stair connects four storeys and bypasses a fifth.
4 Stair serving ground, first, second, third, and roof at grid line E.
Yes, as the stair connects four storeys.
5 Stair serving first, second, third and roof levels at grid line J.
Yes, as the stair connects four storeys and bypasses a fifth.
6 Stair serving first, second, third levels at grid line N.
Yes, as the stair connects four storeys.
Yes
D1.4 Exit travel distances The exit travel distances within the basement do not comply with this
clause, as: - occupants have 45m to a point
of choice instead of 20m; and,
- 45m to one of the exits instead of 40m.
A third exit from the basement
towards grid line N would resolve this matter. If a third stair is not proposed
the proponent has indicated that they
intend to address this via a performance solution based on fire
engineering principles. REFER TO DESIGN CONSIDERATIONS
Yes, subject to fire
engineering
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 14 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
The exit travel distances within the Class 2 parts on the ground and first
floor are 6m from an exit or from a point from which travel in different
directions to 2 exits is available as per Clause D1.4(a)(i)(A).
The exit travel distances on the roof does not comply with this clause, as:
- occupants have 22m to a point of choice instead of 20m
between grid line J & L; and,
The proponent has indicated that they intend to address this via a
performance solution based on fire engineering principles. REFER TO DESIGN CONSIDERATIONS
D1.5 Distance between alternative exits
The direct distance between alternative exits within the basement is
60m as required. However, if measured from first exit door to the
point of choice to the second exit door,
the distance increases to approximately 62m.
The proponent has indicated that they
intend to address this via a performance solution based on fire
engineering principles. REFER TO DESIGN CONSIDERATIONS
The distance between alternative exits on the ground and first floor complies
with this clause as they are more than 9m apart and less than 45m apart as
required.
The distance between the alternative
exits on the roof is greater than the maximum 45m and is approximately
60m.
The proponent has indicated that they
intend to address this via a performance solution based on fire
engineering principles. REFER TO DESIGN CONSIDERATIONS
Yes, subject to fire
engineering
D1.6 Dimensions of exits and paths of
travel NSW Variations NSW D1.6(f)(vii) NSW D1.6(i)
The dimensions of exits and paths of
travel to exits generally complies with this clause and is subject to detailed
design at construction certificate
stage.
Yes
D1.7 Travel via fire-isolated exits. Excluding fire isolated stair at grid line
N, the discharge of the fire isolated
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 15 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
stairs complies with this clause.
The fire isolated stair at grid line N must have a doorway leading to
outside, and the living room window of UG15 protected on the inside as
required by D1.7(c) and as per C3.4. REFER TO DESIGN CONSIDERATIONS
D1.8 External stairways or ramps in
lieu of fire-isolated exits
No external stair in lieu of a fire
isolated stair required or proposed.
N/A
D1.9 Travel by non-fire-isolated
stairways or ramps.
No non-fire isolated stairs, as all fire
isolated.
N/A
D1.10 Discharge from exits NSW Variation NSW D1.10(f).
The discharge of the exits complies with this clause. Details are required at
construction certificate stage to ensure
that compliance with this clause, D1.7(c), and D2.12.
Yes
D1.11 Horizontal exits. No horizontal exits are provided / required.
N/A
D1.12 Non-required stairways, ramps
or escalators.
No non-required stairways, ramps or
escalators.
N/A
D1.13
Number of persons accommodated. NSW Variation NSW Table D1.13.
The building is likely to approximately less than 160 occupants.
Yes
D1.14 Measurement of distances Note only. Note only.
D1.15 Method of measurement Note only. Note only.
D1.16 Plant rooms and lift machine rooms: Concession.
The plant rooms and lift rooms are entitled to comply with the
concessions for egress using ladders
complying with this part.
Yes
D1.17 Access to lift pits The lift pits will be less than 3m in
depth and therefore access to the lift
pit will be via the lowest landing doors.
Yes
Part D2 Construction of Exits D2.0 DtS Provisions. Applicable performance requirements
for building solutions. Note only.
D2.1 Application of part NSW Variation NSW D1.2(c).
Part applies.
Note only.
D2.2 Fire-isolated stairways and ramps.
The fire isolated stairs must be constructed with non-combustible
materials, so that if there is local
failure it will not cause structural damage to, or impair the fire-
resistance of, the shaft.
Yes
D2.3 Non-fire-isolated stairways and
ramps.
No non-fire isolated stairs. N/A
D2.4 Separation of rising and descending stair flights.
No rising and descending stair flights provided the basement stairs at grid
line C and J are separated from the
stairs serving the level 1, 2, 3 and the roof.
Yes
D2.5 Open access ramps and balconies.
No open access ramps or balconies used to comply with the requirements
of Table E2.2a.
N/A
D2.6 Smoke lobbies. No smoke lobbies utilised. N/A
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 16 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
D2.7 Installations in exits and paths
of travel.
Electrical distribution boards that are
located within a path of travel to an exit must be contained within non-
combustible construction (metal cabinet) and smoke sealed.
Yes
D2.8 Enclosure of space under stairs
and ramps.
No cupboards beneath the non-fire
isolated stairs proposed.
N/A
D2.9 Width of stairways. Stairways greater than 2m in width
only count for 2m of exit width.
Note only.
D2.10 Pedestrian ramps. No internal pedestrian ramps serving as exits.
N/A
D2.11 Fire-isolated passageways. The fire isolated passageway on the
ground floors are assumed to be load bearing and therefore must be
concrete or masonry.
Yes
D2.12 Roof as open space. The roof is not utilised as open space for the purpose of this clause.
N/A
D2.13 Goings and risers. NSW Variation NSW 2.13(a)(ix), (x), xi
The goings and the risers are capable of complying with this clause.
Yes
D2.14 Landings. The proposed landings are capable of complying with this clause and are
subject to detailed design at construction certificate stage.
Yes
D2.15 Thresholds. NSW Variation NSW D2.15(d)(e).
The proposed thresholds are capable
of complying with this clause and are subject to detailed design at
construction certificate stage.
Yes
D2.16 Balustrades or other barriers. NSW Variation D2.16(g)(iv) & (v).
The proposed balustrades capable of complying with this clause and are
subject to detailed design at construction certificate stage.
Yes
D2.17 Handrails. Hand rails will be required to all stairs
and they are capable of complying with this clause.
Yes
D2.18 Fixed platforms, walkways’
stairways and ladders.
No fixed platforms, walkways and
ladders proposed or required.
N/A
D2.19 Doorways and doors. NSW Variation NSW D2.19(b)(v).
No revolving, sliding or tilt up doors
proposed in an exit or in the path of
travel to an exit.
Nonetheless, should an automatic sliding door be proposed, it must be
able to be opened manually under a force of not more than 110 N if there
is a malfunction or failure of the power
source; and if it leads directly to a road or open space it must open
automatically if there is a power failure to the door or on the activation of a
fire or smoke alarm anywhere in the
fire compartment served by the door.
Yes
D2.20 Swinging doors. The exit doors swing in the direction of
egress as required, except the two sets of double doors from the ground
Yes, subject to
minor change
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 17 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
floor hallways and the garbage exit
door. REFER TO DESIGN CONSIDERATIONS
D2.21 Operation of latch. NSW Variation NSWD2.21(c)& (d).
Excluding the internal doors of the residential units, door hardware must
be a single hand downward action on
a single device which is located between 900 mm and 1.1 m from the
floor and if serving an area required to be accessible by Part D3—
(A) be such that the hand of a person who
cannot grip will not slip from the
handle during the operation of the latch; and
(B) have a clearance between the handle
and the back plate or door face at the
centre grip section of the handle of not less than 35 mm and not more than 45
mm.
Yes
D2.22 Re-entry from fire-isolated exits. Building not >25m in effective height. N/A
D2.23 Signs on doors. The doorways opening into the fire
isolated stairs and the smoke doors in the hallways must have the following
signage:
“FIRE SAFETY DOOR DO NOT
OBSTRUCT DO NOT KEEP OPEN”;
The doorways leading from the fire
isolated stairs that open to outside must have signage that states:
“FIRE SAFETY DOOR DO NOT
OBSTRUCT”;
Yes
D2.24 Protection of openable windows.
Class 2, 3, 4 or 9b building.
http://www.legislation.nsw.gov.
au/#/view/act/2015/50/part6/div3/sec118
The bedroom windows on the first
floors that have a sill height of less than 1.7 metres and do not open to a
balcony, require protection as per this
clause.
BCA 2016 applies to bedroom windows only, 2m above the ground
with a sill less than 1.7m in height. They MUST be fixed into that position
or have the screen that can withstand
250 Newtons (25kg).
Section 118 of the Strata Schemes
Management Act 2015 requires ALL windows accessible from an
apartment, 2m above the ground
with a sill less than 1.7m in height.
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 18 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
They MUST have the child lock, but do
not have to be fixed, or have the screen that can withstand 250
Newtons (25kg).
D2.25 Timber stairways: Concession No applicable as no timber stairs
proposed within the fire isolated
stairway.
N/A
NSW
D2.101
Doors in path of travel in an
entertainment venue.
Not an ‘entertainment venue’, as
defined by the EP & A Regs. 2000.
N/A
Part D3 Access for People with Disabilities
D3.0 DtS Provisions. Applicable performance requirements for building solutions.
Note only.
D3.1 General building access
requirements.
Disabled access is a requirement of
BCA 2016 and Federal legislation.
In this instance, disabled access must be provided from the principal
pedestrian entry to the: - accessible car parking places
on basement levels;
- waste bins on ground level; - entry doors of the residential
units on all levels; - External common spaces
including the roof.
The building appears capable of
complying with this clause subject to detailed design.
Yes
D3.2 Access to buildings. An accessway is provided from the
boundary of the property, to the principal pedestrian entrances.
Yes
D3.3 Parts of buildings to be
accessible.
Accessible hand rails, tactiles, nosing’s,
will be required to all non-fire isolated stairs to 1428.1-2009.
Yes
D3.4 Exemptions. Disabled access need not be provided
to service areas / metres rooms etc. - Gas metre room;
- Water metre room; - Electricity metre room;
- Fire hydrant pump room.
Yes
D3.5 Accessible car parking. Two accessible car parking space are required and provided. The space must
comply with AS/NZS 2890.6.
Vertical clearance of not less than
2500mm must be provided above each dedicated space and adjacent shared
area, when measured in accordance with AS 2890.1: 1993 Clause 5.3. (AS
2890.6: 2009 Clause 2.4) (Figure 4).
Yes
D3.6 Signage. Braille and tactile signage complying with Specification D3.6 must: -
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 19 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
(ii) identify each door required by E4.5 to be provided with an exit sign and state— (A) "Exit"; and (B) "Level" ; and either (aa) the floor level number; or (bb) a floor level descriptor; or (cc) a combination of (aa) and (bb).
In addition to the above, where a
pedestrian entrance is not accessible, directional signage incorporating the
international symbol of access, in accordance with AS 1428.1 must be
provided to direct a person to the location of the nearest accessible
pedestrian entrance.
D3.7 Hearing augmentation. Hearing augmentation not required. N/A
D3.8 Tactile indicators. If non fire isolated stairs proposed, and form part of the accessible path,
they must have tactiles in accordance with sections 1 and 2 of AS/NZS
1428.4.1.
Yes
D3.9 Wheelchair seating in Class 9b assembly buildings.
No fixed seating proposed as part of the development.
N/A
D3.10 Swimming Pools. No pools proposed. N/A
D3.11 Ramps. The accessible ramps must comply with AS 1428.1-2009 and must not
have a vertical rise of more than 3m.
Yes
D3.12 Glazing on an accessway. On an accessway, where there is no chair rail, handrail or transom, all
frameless or fully glazed doors, sidelights and any glazing capable of
being mistaken for a doorway or
opening, must be clearly marked in accordance with AS 1428.1.
Yes
3.3 – Services and Equipment (Section E, NCC) Clause &
Description Requirements/Comments Compliance Yes/No
Part E1 Fire Fighting Equipment E1.0 DtS Provisions Applicable performance requirements
for building solutions Note only
E1.1 ***** Blank clause. N/A
E1.2 ***** Blank clause. N/A
E1.3 Fire hydrants. Fire hydrant coverage is required in accordance with AS 2419.1-2005.
Internal hydrants are required to the
fire isolated stairs to provide coverage
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 20 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
to the building and so hose reels are
not passing though smoke doors.
If the booster is likely to be within 10m of the building, the booster must be
protected 2m either side and 3m above the booster must achieve an
FRL of 90/90/90.
Direct access must be provided to the
fire hydrant pump room, which can be from a fire isolated stair.
Further details are required from the hydraulic engineer to confirm
compliance.
E1.4 Fire hose reels. Fire hose reels are not required for the
Class 2 parts.
The Class 7a and 7b parts must have
fire hose reels, which will be located within 4m of the two fire isolated
stairs. Coverage is from a 36m hose
and 4m spray.
Yes
E1.5 Sprinklers NSW Variation NSW Table E1.5
Sprinklers are required to the carpark
as more than 40 vehicles are permitted.
Direct access must also be provided to the sprinkler valve set at basement
level one between grid line H-I, which requires a minor layout change to this
area. REFER TO DESIGN CONSIDERATIONS
Yes, subject to
minor design change
E1.6 Portable fire extinguisher. Portable fire extinguishers will be
installed in accordance with this clause and additional PFE’s are required to
serve the Class 2 part not provided
with hose reel coverage.
Yes
E1.7 ***** Blank clause. N/A
E1.8 Fire control centres. Not required or proposed. N/A
E1.9 Fire precautions during construction.
Not less than one fire extinguisher to suit Class A, B and C fires and
electrical fires must be provided at all
times on each storey adjacent to each required exit or temporary stairway or
exit.
Yes
E1.10 Provision for special hazards. Not required or proposed.
N/A
Part E2 Smoke Hazard Management E2.0 DtS Provisions Applicable performance requirements
for building solutions Note only
E2.1 Application of Part. Part applies. Applicable
E2.2 General requirements. The building will require an automatic smoke detection and alarm system
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 21 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
(BOWS) complying with NCC Clause
E2.2a, Clause 3 or 4, & 6 of Spec. E2.2a, AS 3786-2014.
This will require:
- At least one hard wired smoke alarm within each residential
unit; and
- hard wired and interconnected smoke alarms on ground, first,
second, third and roof, so that if one alarm detects smoke, all
smoke alarms in the common
area activate to form the building occupant warning
system; - speaker to the carpark that
activates if the above smoke alarms in the common areas
detect smoke activate.
The carpark ventilation system
requires compliance with Clause E2.2a, Clause 5.5 of AS 1668.1-2015 & AS
1668.2-2012. This requires:
- smoke detectors to the mechanical supply air parts;
- auto shutdown of the supply air on detection of smoke by
the supply air smoke detectors;
- auto full ventilation rate where
smoke detection or sprinklers installed activated by thermals
in accordance with AS 1670.1-2015;
- Override control switch at the
designated building entry point or the at the FDCIE (aka FIP).
E2.3 Provision of special hazards. NSW variations NSW Table E2.2a NSW Table E2.2b
The building is not considered to be
subject to the provision of special hazards.
N/A
Part E3 Lift Installations E3.0 DtS Provisions Applicable performance requirements
for building solutions. Note only
E3.1 Lift installations. The electric passenger lift must
comply with Specification E3.1.
Yes
E3.2 Stretcher facility in lifts. A stretcher facility is NOT required as the effective height of the building is
NOT more than 12 metres, based on three metres per storey. Check
effective height at CC stage.
N/A
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 22 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
E3.3 Warnings against the use of lifts
in fire.
Signage will be provided to comply
with this clause.
Yes
E3.4 Emergency lifts. An emergency lift is not required or
proposed.
N/A
E3.5 Landings. Landings to the lift comply with this clause.
Yes
E3.6 Passenger lifts. The passenger lift will comply with this
clause. The required disabled access provisions.
a) Hand rail to AS 1735.12; b) Lift floor of 1400 (w) x 1600 (d);
c) Lifts doors that have passenger protection to AS 1735.12;
d) Lift landing doors at the upper
landing; e) Lift car control buttons to AS
1735.12; f) Lighting to AS 1735.12;
g) Automatic audible information,
visual indicators to identify the level and when the lift stops.
h) Emergency button to call centre
Yes
E3.7 Fire service controls. The passenger lift does NOT require
fire service controls as it has effective
height less than 12m.
N/A
E3.8 Aged care buildings. Not an aged care building. N/A
E3.9 Fire service recall operation
switch.
The passenger lift does NOT require
fire service controls as it has effective height less than 12m.
N/A
E3.10 Lift car service drive control
switch.
The passenger lift does NOT require
fire service controls as it has effective height less than 12m.
N/A
Part E4 Emergency Lighting, Exit Signs and Warning Systems
E4.0 DtS Provisions Applicable performance requirements for building solutions.
Note only.
E4.1 ***** Blank clause. N/A
E4.2 Emergency lighting
requirements.
Emergency lighting is required to be
installed to all internal and external
stairs that are part of the path of travel to the road in accordance with
this clause, including the rooftop.
Yes
E4.3 Measurement of distance. Noted. Note only.
E4.4 Design and operation of
emergency lighting.
Emergency lighting must be installed
in accordance with AS 2293.1-2005.
Yes
E4.5 Exit signs. Exit signs to be installed on all levels above or adjacent to the exit.
Yes
E4.6 Direction signs. NSW Variation NSW E4.6
If the exit is not readily apparent,
additional directional exit signs must be installed to guide occupants to the
exit.
Yes
E4.7 Class 2 & 3 buildings and Class
4 parts: Exemption.
The Class 2 parts are entitled to use
the with the word “EXIT” in capital
letters 25 mm high in a colour
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 23 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
contrasting with that of the background, on the side remote from the exit or balcony of every exit door.
E4.8 Design and operation of exit signs.
Every required exit sign must comply with—
AS 2293.1; or for a photoluminescent exit sign, Specification E4.8; and
be clearly visible at all times when the building is occupied by any person
having the right of legal entry to the
building.
Yes
E4.9 Sound systems and intercom
systems for emergencies
Not a class 3, a Class 9b building
having a RIS of 3 or more, or over
25m in Effective Height building.
N/A
3.4 – Health & Amenity (Part F, NCC) Clause Description Clause Requirements/Comments Compliance
Yes/No Part F1 Damp and Waterproofing F1.0 DtS Provisions Applicable performance requirements
for building solutions. Note only
F1.1 Stormwater drainage. The stormwater will comply with AS/NZS 3500.3-2015.
Yes
F1.2 ***** Blank clause N/A
F1.3 ***** Blank clause N/A
F1.4 External above ground membranes.
Where external membranes are proposed, they must comply with AS
4654.1 & 2.
Yes
F1.5 Roof coverings. The new roof coverings must comply
with this clause. If metal deck roofing
is proposed it must comply with AS 1562.1.
Yes
F1.6 Sarking New sarking will comply with this
clause and AS/NZS 4200.1 & 2.
Yes
F1.7 Waterproofing of wet areas in
buildings.
Waterproofing of all wet areas will be
in accordance with this clause and AS
3740-2010.
Yes
F1.8 ***** Blank clause. N/A
F1.9 Damp-proofing New damp-proofing will comply with
this clause.
Yes
F1.10 Damp-proofing of floors on the
ground.
New damp-proofing on the ground will
comply with this clause.
Yes
F1.1 Provision of floor wastes. New floor wastes will be provided to the Class 2 parts within the bathrooms
and laundries.
Yes
F1.12 Sub-floor ventilation. New sub-floor ventilation must be upgraded to comply with this part.
Yes
F1.13 Glazed assemblies. New glazed members will comply with
this clause.
Yes
Part F2 Sanitary and Other Facilities F2.0 DtS Provisions Applicable performance requirements
for building solutions. Note only
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 24 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
F2.1 Facilities in residential buildings. Each SOU will be provided with a
kitchen, bathroom, toilet, shower.
Laundry facilities are proposed via a washing machine. Clothes drying will
be via dryer or 7.5m of clothes lines on balconies.
A cleaner’s toilet is required and is provided as the building has more than
10 units, as per Table F2.1.
Yes
F2.2 Calculation of number of occupants and facilities.
Population loads: Approximately less than 160.
Noted
F2.3 Facilities in Class 3-9 buildings. Facilities not required for the Class 7a or 7b parts as no employees.
N/A
F2.4 Accessible sanitary facilities. If common sanitary facilities are
utilised within building, this must be an accessible bathroom.
Yes
F2.5 Construction of sanitary
compartments.
The construction of sanitary
compartments will comply with this clause.
Yes
F2.6 Interpretation: Urinals and
washbasins.
Noted only. Yes
F2.7 Microbial.
NSW Variation NSW F2.7
Not applicable in NSW. N/A
F2.8 Waste management. Not Class 9a N/A
Part F3 Room Heights F3.0 DtS Provisions Applicable performance requirements
for building solutions. Applies
F3.1 Height of rooms and other spaces.
The height of rooms are required to be 2.4 meters in height in habitable
rooms and 2.1m in non-habitable rooms. It is noted that that normal
internal heights are 2.4 metres or
more.
Yes
Clause Description Clause Requirements/Comments Compliance Yes/No
Part F4 Light and Ventilation F4.0 DtS Provisions Applicable performance requirements
for building solutions. Applicable
F4.1 Provision of natural light. Natural lighting is provided to all habitable rooms within Class 2 parts.
Yes
F4.2 Methods and extent of natural
lighting.
Compliant natural lighting is provided
to all habitable rooms within Class 2 parts.
Yes
F4.3 Natural light borrowed from
adjoining room.
Borrowed light not required as direct
natural lighting provided.
N/A
F4.4 Artificial lighting. In non-habitable rooms, artificial
lighting will comply with this clause, the BASIX certificate and Part J6 and
AS 1680.0-2009.
Yes
F4.5 Ventilation of rooms. NSW Variation F4.5(b).
Excluding the basement and some bathrooms, the building is primarily
provided with natural ventilation. Parts
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 25 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
that are mechanical ventilated must
comply with the BASIX certificate, Part J5 and AS 1668.2-2012.
F4.6 Natural ventilation. Excluding the basement and some bathrooms, the building is primarily
provided with natural ventilation. Parts
that are mechanical ventilated must comply with the BASIX certificate, Part
J5 and AS 1668.2-2012.
Yes
F4.7 Ventilation borrowed from adjoining room.
Borrowed ventilation may be relied upon for small study / non-habitable
rooms. However, it is likely that the non-habitable components will be
mechanically ventilated.
Yes
F4.8 Restriction of position of water closets and urinals.
Toilet doors open to hallways or the like or must be mechanical ventilated
to comply with Clause F4.9(a)(ii).
Yes
F4.9 Airlocks. Toilet doors open to hallways or the like or must be mechanical ventilated
to comply with Clause F4.9(a)(ii).
Yes
F4.10 ***** Blank clause. N/A
F4.11 Carparks The basement carpark part must be
mechanically ventilated as per AS 1668.2-2012.
Some supply is detailed, however, exhaust is not detailed on the current
plans, which is subject to detailed engineering design that is co-ordinated
with other engineering disciplines.
Yes
F4.12 Kitchen and local exhaust ventilation.
No commercial kitchens. N/A
Part F5 Sound Transmission and Insulation
F5.0 DtS Provisions Applicable performance requirements for building solutions.
Noted.
F5.1 Application of Part. Applies to Class 2 parts. Applies
F5.2 Determination of airborne sound
insulation ratings.
Airborne sound insulation requirement. Noted
F5.3 Determination of impact sound insulation ratings.
Airborne sound insulation ratings must be determined in accordance with
Clause F5.2(a) or comply with
Specification F5.2.
Noted
F5.4 Sound insulation of floors. The residential floors must have an Rw
+ Ctr (airborne) not less than 50 and an Ln,w (impact) not more than 62.
Yes
F5.5 Sound insulation of walls.
The walls separating Units must have
an Rw + Ctr (airborne) not less than 50.
Discontinuous construction is required
around the lift shafts, garage rooms, and other rooms which are habitable
and back on to non-habitable areas.
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 26 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
F5.6 Sound insulation of internal
services.
Pipework, including stormwater pipes,
must have an Rw + Ctr (airborne) not less than—
(i) 40 if the adjacent room is a habitable room (other than a kitchen);
or
(ii) 25 if the adjacent room is a kitchen
or non-habitable room.
Yes
F5.7 Sound insulation of pumps. A flexible coupling must be used at the point of connection between the
service pipes in a building and any
circulating or other pump.
Yes
3.6 – Energy Efficiency. (Part J, NCC) Note 1: The residential Class 2 part of the building is to be designed to comply with the requirements of two MANDATORY points for energy efficiency. They are:
• A, BASIX assessment and a BASIX certificate will be required to be lodged with the
development application.
• In addition to the BASIX certificate compliance with NSW J (A) is required for the Class
2 part. The relevant/applicable sections of NSW J (A) are to be complied with. The clauses within Section J (A) are listed below.
• NSW J(A) 1.0 – Building Fabric,
• NSW J(A) 2.0 – Building Sealing
• NSW J(A) 3.0 – Air Conditioning and ventilating systems
• NSW J(A) 4.0 – Hot Water Supply
• NSW J(A) 5.0 – Access for Maintenance
Clause Description Clause
Requirements/Comments Compliance
Yes/No
NSW PART J(A)1
Building Fabric
NSW J(A)1.1(a)
&(b)
Application of Part. NSW J(A)1.1(a)&(b). The DTS provisions do not apply as the
Development Consent
D/2015/326/C, does NOT require
the installation of insulation.
N/A
NSW
J(A)1.1(c)
Application of Part. The Deemed-to-Satisfy provisions of
this Part for thermal breaks apply to
all Class 2 buildings
Part applies
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 27 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
NSW
J(A)1.2
Compliance with BCA provisions
The sole-occupancy units of the
Class 2 parts must comply with the national BCA provisions of J0.2(b) to
(e), as stated below, excluding J1.2 if the DA does not mandate
insulation.
(b) for general thermal construction, comply with J1.2; and
(c) for thermal breaks, comply with J1.3(d) and J1.5(c); and
(d) for compensating for a loss of ceiling insulation, comply with J1.3(c), other than where the house energy rating software used can automatically compensate for a loss of ceiling insulation; and
(e) for floor edge insulation, comply with J1.6(c) and J1.6(d); and
Part applies
NSW PART J(A)2
Building Sealing
NSW
J(A)2.1
Application of Part. Parts applies as Class 2 parts have
air conditioning.
Part applies
NSW
J(A)2.2
Compliance with BCA
provisions
Class 2 parts must comply with the
following national BCA provisions, as
applicable—
(a) J3.2 Chimneys and flues; and
(b) J3.3 Roof lights; and
(c) J3.4 Windows and doors; and
(d) J3.5 Exhaust fans; and
(e) J3.6 Construction of roofs, walls
and floors; and
(f) J3.7 Evaporative coolers.
Subject to Section J Report
NSW PART J(A)3
Air-Conditioning & Ventilation Systems
NSW J(A)3.1 Application of Part. Parts applies to Class 2 parts. Part applies
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 28 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
NSW J(A)3.2 Compliance with BCA
provisions
Class 2 buildings and Class 4 parts of
buildings must comply with the following national BCA provisions, as
applicable—
(a) J5.2 (a) to (d) and (f) to (g) Air
conditioning systems; and
(b) J5.3 Mechanical ventilation
systems; and
(c) J5.4 Miscellaneous exhaust
systems.
Note: Compliance is not required
with the national BCA provisions of
J5.2(e) as those matters are
regulated under BASIX.
Subject to Section J Report
NSW PART J(A)4
Heated Water Supply
NSW J(A)4.1 Application of Part. Parts applies to Class 2 parts. Part applies
NSW J(A)4.2 Compliance with BCA
provisions
Class 2 buildings and Class 4 parts of
buildings must comply with the national BCA provisions of J7.2
Heated water supply.
Note: Compliance is not required
with the national BCA provisions of J7.3 and J7.4 as those matters are
regulated under BASIX.
Subject to Section J Report
NSW PART J(A)5
Heated Water Supply
NSW J(A)5.1 Application of Part. Applies to Class 2 common areas. Part applies
NSW J(A)5.2 Compliance with BCA
provisions
a) A building or sole-occupancy unit with a floor area of more than 500
m2 must have the facility to record the consumption of gas and
electricity. This will be provided as
required.
Yes
3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 29 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
The following NCC Section J National provisions will be applicable to the Class 7a and 7b part.
Item Comment
Building Fabric
Should the basement be heated or cooled, or be a conditioned space, it
must be insulated in accordance with Part J1 of the NCC.
Glazing
No applicable as no windows to the basement levels.
Building Sealing
Should the basement be heated or cooled, or be a conditioned space, it
must be sealed in accordance with Part J3 of the NCC.
Air-Conditioning and Ventilation System
If proposed, the air-conditioning and ventilation system to the basement portion of the development must be designed to comply with Part J5 of
the NCC.
Artificial Lighting and Power
The Class 7a and 7b parts must maintain maximum lighting power levels and control systems as applicable. The design of lighting systems must
comply with NCC Part J6.
Hot Water Supply
Hot water supply systems must be installed in accordance with Part J7 of the NCC and AS/NZS 3500.4.
Access for Maintenance
The building is to have facilities for maintenance and energy monitoring
in compliance with NCC Part J8 and the NSW variations.
4.0 – FIRE SAFETY AND OTHER MEASURES
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 30 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
4.0 – Fire Safety and Other Measures
4.1 – Proposed Fire Safety Measures The building will have the following fire safety measures: - Measure Standard of Performance
Access panels to fire-resisting shafts. BCA Clause C3.13
Alarm signalling equipment BCA Clause E1.5, Spec. E1.5, AS 2118.1-1999, AS 1670.3-2004
Automatic fire detection and alarms systems (BOWS)
BCA Clause E2.2a, Clause 3 or 4 & 6 of Spec. E2.2a, AS 3786-2014.
Automatic fire suppression (carpark sprinkler systems)
BCA Clause E1.5, Specification E1.5, AS 2118.1-1999.
Emergency lighting BCA Clause E4.2 & E4.4, AS 2293.1-2005
Exit signs BCA Clause E4.5, NSW E4.6, E4.7 & E4.8, AS 2293.1-2005
Fire doors BCA Spec C3.8, C3.11, AS 1905.1-2005
Fire engineering Fire Engineering Report by XYZ.
Fire hydrant systems BCA Clause E1.3, AS 2419.1-2005
Fire seals (protecting openings in fire resisting components of the building)
BCA Clause C3.15, and manufacturers specifications.
Mechanical air handling systems (carpark)
BCA Clause E2.2a, Clause 5.5 of AS 1668.1-2015 & AS 1668.2-2012, AS 1670.1-2015.
Portable fire extinguishers BCA Clause E1.6, AS 2444-2001
Wall wetting sprinklers (drenchers to U15) BCA Clause D1.7(c), AS 2118.2-2010
Warning and operational signage - Fire door signs; - Fire isolated stairway notices; - Lift notices - Hydrant, hose reel, PFE signs..
BCA Clause D2.23, D3.6, E1.3, E1.4, E1.6, E3.3, and EP&A Regs 2000.
5.0 – CONCLUSION
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 31 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
5.0 – Conclusion This BCA 2016 Report has been prepared to assess the proposed plans appurtenant to the Development Application that is to be submitted to Blacktown Council for a new residential flat building with 75 apartments and basement carparking for 130 vehicles. The assessment of the documentation has revealed that the building is primarily capable of complying with the Deemed-to-Satisfy [herein ‘DTS’] provisions of the BCA 2016 Code 2016 (Volume 1, Class 2-9 Buildings) [herein ‘BCA 2016’], and where necessary the Performance Requirements, without modification that require a development consent to be modified. Prepared by:
Greg Evans Director Accredited Certifier BPB 1870 360 Certification Date: 24 June 2017
6.0 – REFERENCES
Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 32 of 32
360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825
6.0 – References & Plans
See attached plans.