3UA Overload RelaysDescription

3UA series are bimetal thermal relays with release class 10A.With differential phase- failure protectionWith continuous current adjusting scaleWith temperature compensationWith ON/OFF indicatorWith TEST(OFF) buttonWith Manual/Auto reset buttonWith Auxiliary contacts 1 NO +1 NC insulated each otherSIGUT - Siemens patent terminal, ensures easy and reliable connection, strong shock resistance and perfect safety protection.Mounting: plug in connection with contactor or install as a single unit.

3UA Series Overload Relays are suitable for overload and phase - failure protection of AC motors with frequency of 50/60Hz, voltage up to 690 ~1000V, current up to 0.1 ~ 400A under 8 - hours duty or uninterrupted duty. The relays are also suitable for overload protection of DC magnetand DC motors.The relays comply with IEC947-4, VDE0660 and GB14048. Several functions provided by these relays are: phase-failure protection, temperaturecompensation, ON/OFF indication and manual/automatic reset. The relays can be mounted onto contactors or installed as single units.Operating Conditions

Features

The altitude of the site of installation does not exceed 2000 meters above sea levels.The ambient air temperature: -25 ~ +55°CRelative humidity does not exceed 90% at +25°C

Selection and ordering data

3UA50 40 - 0A 0.1 - 0.16 35 0.53UA50 40 - 0C 0.16 - 0.25 35 1 0.143UA50 40 - 0E 0.25 - 0.4 35 1.63UA50 40 - 0G 0.4 - 0.63 35 23UA50 40 - 0J 0.63 - 1 35 4 0.14

3UA50 40 - 0K 0.8 - 1.25 35 43UA50 40 - 1A 1 - 1.6 35 6 0.143UA50 40 - 1B 1.25 - 2 35 63UA50 40 - 1C 1.6 - 2.5 35 63UA50 40 - 1D 2 - 3.2 35 10 0.143UA50 40 - 1E 2.5 - 4 35 103UA50 40 - 1F 3.2 - 5 35 163UA50 40 - 1G 4 - 6.3 35 16 0.143UA50 40 - 1H 5 - 8 35 203UA50 40 - 1J 6.3 - 10 35 253UA50 40 - 1K 8 - 12.5 35 25 0.143UA50 40 - 2S 10 - 14.5 35 25

Order No. Setting rangeFuse links(A)IEC947 - 4

“1” “2”For contactor Weightkg3UA50

3TF303TF313TF403TF41

3TD401)3TD401)3TE403TB403TB41

1) lnstalling as a single unit with individual wiring only.2) use 3UX1210 links for connection to 3TF53 contactors.

(A)

Page 2: 3UA OLR

3/2

Selection and ordering dataOrder No. Setting range(A)

Fuse links(A)IEC947 - 4

“1” “2”For contactor Weightkg3UA52

3UA Overload Relays

Order No. Setting range(A)Fuse links(A)IEC947 - 4

“1” “2”For contactor Weightkg3UA54

3UA52 40 - 0A 0.1 - 0.16 63 0.53UA52 40 - 0C 0.16 - 0.25 63 1 0.143UA52 40 - 0E 0.25 - 0.4 63 1.63UA52 40 - 0G 0.4 - 0.63 63 23UA52 40 - 0J 0.63 - 1 63 4 0.143UA52 40 - 0K 0.8 - 1.25 63 43UA52 40 - 1A 1 - 1.6 63 63UA52 40 - 1B 1.25 - 2 63 6 0.143UA52 40 - 1C 1.6 - 2.5 63 63UA52 40 - 1D 2 - 3.2 63 103UA52 40 - 1E 2.5 - 4 63 10 0.143UA52 40 - 1F 3.2 - 5 63 163UA52 40 - 1G 4 - 6.3 63 163UA52 40 - 1H 5 - 8 63 20 0.143UA52 40 - 1J 6.3 - 10 63 253UA52 40 - 1K 8 - 12.5 63 253UA52 40 - 2A 10 - 16 63 35 0.143UA52 40 - 2B 12.5 - 20 63 353UA52 40 - 2C 16 - 25 63 50

3UA54 40 - 1G 4 - 6.3 100 16 3TB443UA54 40 - 1J 6.3 - 10 100 25 0.203UA54 40 - 2A 10 - 16 100 353UA54 40 - 2B 12.5 - 20 100 503UA54 40 - 2C 16 - 25 100 50 0.203UA54 40 - 2D 20 - 32 100 803UA54 40 - 2Q 25 - 36 100 80

3TF323TF333TF423TF43

3TD421)3TD431)3TE423TB423TB43

1) Installing as a single unit with individual wiring only

Page 3: 3UA OLR

3/3

3

Selection and ordering dataOrder No. Setting range(A)

Fuse links(A)IEC947 - 4

“1” “2”For contactor Weightkg3UA55

3UA Overload Relays

3UA55 40 - 1A 1 - 1.6 100 6 3TF343UA55 40 - 1B 1.25 - 2 100 6 3TF35 0.203UA55 40 - 1C 1.6 - 2.5 100 6 3TF443UA55 40 - 1D 2 - 3.2 100 10 3TF453UA55 40 - 1E 2.5 - 4 100 10 3TD441) 0.203UA55 40 - 1F 3.2 - 5 100 16 3TD451)

3UA55 40 - 1G 4 - 6.3 100 16 3TE443UA55 40 - 1H 5 - 8 100 20 0.203UA55 40 - 1J 6.3 - 10 100 253UA55 40 - 1K 8 - 12.5 100 253UA55 40 - 2A 10 - 16 100 35 0.203UA55 40 - 2B 12.5 - 20 100 503UA55 40 - 2C 16 - 25 100 503UA55 40 - 2D 20 - 32 100 80 0.203UA55 40 - 2Q 25 - 36 100 803UA55 40 - 2R 32 - 40 100 803UA55 40 - 8M 36 - 45 100 80 0.20

Order No. Setting range(A)Fuse links(A)IEC947 - 4

“1” “2”Weightkg3UA58

3UA58 40 - 2B 12.5 - 20 160 50 0.43UA58 40 - 2C 16 - 25 160 503UA58 40 - 2D 20 - 32 160 633UA58 40 - 2E 25 - 40 160 803UA58 40 - 2F 32 - 50 160 100 0.43UA58 40 - 2T 40 - 57 160 1003UA58 40 - 2P 50 - 63 160 1003UA58 40 - 2V 57 - 70 160 125 0.43UA58 40 - 2U 63 - 80 250 160 3UA58 40 - 8W 70 - 88 250 160

For contactor

3TF463TF473TF483TF49

3TD461)3TD471)3TD481)3TE463TE473TE48

1) Installing as a single unit with individual wiring only

Page 4: 3UA OLR

3/4

Selection and ordering dataOrder No. Setting range(A)

Fuse links(A)IEC947 - 4

“1” “2”For contactor

3TE481)3TF491)3TF503TE503TD501)3TB50

Weightkg3UA60

3UA Overload Relays

3UA60 40 - 2H 55 - 80 250 1603UA60 40 - 2W 63 - 90 250 160 0.73UA60 40 - 2X 80 - 110 315 2003UA60 40 - 3H 90 - 120 315 2243UA60 40 - 3J 110 - 135 315 224 0.7

Order No. Setting range(A)Fuse links(A)IEC947 - 4

“1” “2”For contactor

3TF51

Weightkg3UA61

3UA61 40 - 2H 55 - 80 250 1603UA61 40 - 2W 63 - 90 250 160 0.73UA61 40 - 2X 80 - 110 315 2003UA61 40 - 3H 90 - 120 315 2243UA61 40 - 3J 110 - 135 315 224 0.73UA61 40 - 3K 120 - 150 315 224

Order No. Setting range(A)Fuse links(A)IEC947 - 4

“1” “2”Weightkg3UA59

3UA59 40 - 0A 0.1 - 0.16 25 0.53UA59 40 - 0C 0.16 - 0.25 25 1 0.283UA59 40 - 0E 0.25 - 0.4 25 1.63UA59 40 - 0G 0.4 - 0.63 25 23UA59 40 - 0J 0.63 - 1 25 4 0.283UA59 40 - 0K 0.8 - 1.25 25 43UA59 40 - 1A 1 - 1.6 25 63UA59 40 - 1B 1.25 - 2 25 6 0.283UA59 40 - 1C 1.6 - 2.5 25 63UA59 40 - 1D 2 - 3.2 25 103UA59 40 - 1E 2.5 - 4 25 10 0.283UA59 40 - 1F 3.2 - 5 25 163UA59 40 - 1G 4 - 6.3 25 163UA59 40 - 1H 5 - 8 25 16 0.283UA59 40 - 1J 6.3 - 10 25 163UA59 40 - 1K 8 - 12.5 35 253UA59 40 - 2A 10 - 16 63 35 0.283UA59 40 - 2B 12.5 - 20 63 503UA59 40 - 2C 16 - 25 63 503UA59 40 - 2D 20 - 32 80 63 0.283UA59 40 - 2E 25 - 40 125 803UA59 40 - 2M 32 - 45 160 1003UA59 40 - 2T 40 - 57 160 125 0.283UA59 40 - 2P 50 - 63 160 125

For contactor

mounting seperatly

Page 5: 3UA OLR

3/5

3

Selection and ordering dataOrder No. Setting range(A)

Fuse links(A)IEC947 - 4

“1” “2”For contactor

3TF523TE523TD521)3TF532)3TB52

Weightkg3UA62

3UA Overload Relays

3UA62 40 - 2H 55 - 80 250 1603UA62 40 - 2W 63 - 90 250 160 0.73UA62 40 - 2X 80 - 110 315 2003UA62 40 - 3H 90 - 120 315 2243UA62 40 - 3J 110 - 135 315 224 0.73UA62 40 - 3K 120 - 150 315 2243UA62 40 - 3L 135 - 160 355 224 3UA62 40 - 3M 150 - 180 355 224 0.7

Order No. Setting range(A)Fuse links(A)IEC947 - 4

“1” “2”For contactor Weightkg3UA66

3UA66 40 - 2K 80 - 125 500 2503UA66 40 - 3B 125 - 200 500 315 2.53UA66 40 - 3C 160 - 250 500 4003UA66 40 - 3D 200 - 320 500 4003UA66 40 - 3E 250 - 400 800 500 2.5

Name Order No. Application WeightkgCable release 3UX1015 3UX1015 400mm long3UX1016 3UX1016 600mm longFor resetting relays at a long distance

Relay base For installing 3UA50 as a single unit

Relay base For installing 3UA52, 3UA54 as a single unit

Relay base For installing 3UA58 as a single unit

Relay base For installing 3UA55 as a single unit

Box terminal block For installing 3UA60 as a single unit

3UX1418

3UX1420

3UX1421

3UX1425

3UX1424

0.07

0.05

0.05

0.05

0.05

0.2

Accessories

1) Installing as a single unit with individual wiring only2) Use 3UX1210 links for connection to 3TF53 contactors

Page 6: 3UA OLR

3/6

3UA Overload Relays

1) Release time with 3-pole symmetrical load at ambient termperature +20¼C2) Release time with 3-pole unsymmetrical load (phase-failure) at ambient termperature +20¼C

Technical dataRated operational current(A)Rated insulation voltage(V)Rated operational voltage(V)Type of current, frequencyAmbient temperature(°C)Phase - failure protectionManual/Auto resetTemperature compensation(-25~+55°C)Switch position indicatorTest buttonTerminal for contactor coilAuxiliary contactsSwitching capacity(380V) AC - 15Mounting

3UA50 3UA52 3UA54 3UA55 3UA59 3UA58 3UA60 3UA61 3UA62 3UA6614.5 25 36 45 63 88 135 150 180 400

690 690 690 1000 1000 1000 1000 1000690 690 690 1000 1000 1000 1000 1000

-25~+55 -25~+55 -25~+55 -25~+55 -25~+55 -25~+55 -25~+55 -25~+55Yes Yes Yes Yes Yes Yes Yes YesYes Yes Yes Yes Yes Yes Yes YesYes Yes Yes Yes Yes Yes Yes YesYes Yes Yes Yes Yes Yes Yes YesYes Yes Yes Yes Yes Yes Yes YesYes Yes No No No No No No

1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC1.1A 1.1A 1.1A 1.1A 1.1A 1.1A 1.1A 1.1A

Plug - in Plug - in as a single unit Plug - in as a single unit as a single unit as a single unit as a single unit

DC; AC up to 400Hz AC 50 to 400Hz

Solid or strandedconductorFinely strandedconductor withend sleeveTerminal screwSingle core orstranded conductor

Finely strandedconductor withend sleeveTerminal screw

Maincircuit

Auxiliarycircuit

Conduc-torcross-section(mm2)

2.5~6 1.5~25 1.5~25 2.5~35 25~70 50~120 50~12025~95 25~95 20 3/1.5~4 1~16 1~16 1.5~25 25~50 20 3 20 3 2 30 5Flat bars Flat bars Flat bars

M4 M5 M5 M5 M6 M8 M8 M8/M102 2 2 2 2 2 2 2(0.5~1) (0.5~1) (0.5~1) (0.5~1) (0.5~1) (0.5~1) (0.5~1) (0.5~1)2 2 2 2 2 2 2 2(0.5~1) (0.5~1) (0.5~1) (0.5~1) (0.5~1) (0.5~1) (0.5~1) (0.5~1)M3.5 M3.5 M3.5 M3.5 M3.5 M3.5 M3.5 M3.5

200A 185> 200A 240

Protection characteristics

pre - heated for 2 hours with 1 timesetting current

Hot state means heat the overload relay into steady state with the current as shown in “Item 1”.

Item No. Release time Test condition5 1.0 0.96 1.15 0

Hot state means heat the overload relay into steady state with the current as shown in “Item 1”.

Times the setting currentAny two phases Another phase

>2h 2) Cold state<2h 2) Hot state

Item No. Times the setting current Release time Test condition1 1.052 1.203 1.504 7.2 2s<Tp 10s, Class 10A

>2h 1) Cold state<2h 1) Hot state

<2min 1)Cold state

Page 7: 3UA OLR

3/7

3

3.Release time with 3-pole symmetrical load form the cold state (as reference)Setting range Conductor Times the setting current e(A) corss-sections(mm2)3UA50, 3UA52 Release time: (in sec.)0.1-0.16 1 16.7 10.3 7.5 5.9 4.8 4.10.16-0.25 1 20.5 12.8 9.5 7.5 6.3 5.40.25-0.4 1 18 11.2 8.2 6.5 5.4 4.60.4-0.63 1 20.8 12.8 9.5 7.6 6.3 5.40.63-1 1 23.3 14.4 10.5 8.3 6.8 5.80.8-1.25 1 28 17.5 12.7 9.8 8.1 6.81-1.6 1 22.6 14.3 10.4 8.3 6.8 5.91.25-2 1 22.3 14 10.3 8.4 6.9 6.01.6-2.5 1 24.5 15.5 11.5 9 7.5 6.42-3.2 1 23.8 15 11 8.8 7.3 6.32.5-4 1 24.4 15.6 11.4 9.1 7.6 6.53.2-5 1 27.5 17 12.2 9.5 7.8 6.54-6.3 1 23.4 14.4 10.4 8 6.5 5.55-8 1 22.5 13.5 9.5 7.2 5.7 4.76.3-10 1.5 24 13.9 9.3 6.8 5.3 4.38-12.5 2.5 24.5 14.8 10.2 7.8 6.2 5.210-14.5 2.5 23.2 13.9 9.5 7.2 5.6 4.610-16 2.5 23.2 13.9 9.5 7.2 5.6 4.612.5-20 2.5 23 13 8.6 6.3 4.8 3.916-25 4 31 17 11 7.7 5.8 4.63UA54 Release time: (in sec.)4-6.3 1 23.4 14.4 10.4 8 6.5 5.56.3-10 1.5 24 13.9 9.3 6.8 5.3 4.310-16 2.5 26.2 15.8 10.8 8.1 6.4 5.212.5-20 2.5 26.6 14.8 9.7 7.0 5.3 4.316-25 4 29 15.4 9.8 7.0 5.3 4.220-32 6 28 16.1 10.8 8.2 6.3 5.225-36 10 33.4 19 12.8 9.3 7.2 5.83UA55 Release time: (in sec.)1-1.6 1 22.6 14.3 10.4 8.3 6.8 5.91.25-2 1 22.3 14 10.3 8.4 6.9 61.6-2.5 1 24.5 15.5 11.5 9 7.5 6.42-3.2 1 23.8 15 11 8.3 7.3 6.32.5-4 1 24.4 15.5 11.4 9.1 7.6 6.53.2-5 1 27.5 17 12.2 9.5 7.8 6.54-6.3 1 25.4 14.4 10.4 8 6.5 5.55-8 1 22.5 13.5 9.5 7.2 5.7 4.76.3-10 1.5 24 13.9 9.3 6.8 5.3 4.38-12.5 2.5 24.5 14.8 10.2 7.8 6.2 5.210-16 2.5 26.2 15.8 10.8 8.1 6.4 5.212.5-20 2.5 26.6 14.8 9.7 7 5.3 4.316-25 4 29 15.4 9.8 7 15.3 4.220-32 6 28 16.1 10.8 8.2 6.3 5.225-36 10 33.4 19 12.8 9.3 7.2 5.832-40 10 24.3 13.6 8.8 6.6 5 4.236-45 10 23 13 8.5 6.2 4.5 3.3

3UA Overload RelaysTechnical data

3 4 5 6 7 8

Page 8: 3UA OLR

3/8

3UA Overload RelaysTechnical dataSetting range Conductor Times the setting current(A) corss-sections

(mm2)3UA58 Release time: (in sec.)16-25 4 34 19.5 13.2 9.7 7.6 6.220-32 6 33 18.5 12.8 9.4 7.4 625-40 10 30 17 11.5 8.4 6.5 5.332-50 10 29 16.6 11 8 6.2 540-57 16 35 19.4 12.3 8.7 6.6 5.350-63 16 37 20.5 13.3 9.6 7.3 5.857-70 25 40 21.5 14 9.8 7.4 5.863-80 25 40 21.5 13.8 9.7 7.3 5.870-88 35 33.9 17.6 11.8 8 6.5 4.93UA59 Release time: (in sec.)0.1-0.16 1 16.7 10.3 7.5 5.9 4.8 4.10.16-0.25 1 20.5 12.8 9.5 7.5 6.3 5.40.25-0.4 1 18 11.2 8.2 6.5 5.4 4.60.4-0.63 1 20.8 12.8 9.5 7.6 6.3 5.40.63-1 1 23.3 14.4 10.5 8.3 6.8 5.80.8-1.25 1 28 17.5 12.7 9.8 8.1 6.81-1.6 1 22.6 14.3 10.4 8.3 6.8 5.91.25-2 1 22.3 14 10.3 8.4 6.9 6.01.6-2.5 1 24.5 15.5 11.5 9 7.5 6.42-3.2 1 23.8 15 11 8.8 7.3 6.32.5-4 1 24.4 15.6 11.4 9.1 7.6 6.53.2-5 1 27.5 17 12.2 9.5 7.8 6.54-6.3 1 23.4 14.4 10.4 8 6.5 5.55-8 1 22.5 13.5 9.5 7.2 5.7 4.76.3-10 1.5 24 13.9 9.3 6.8 5.3 4.38-12.5 2.5 31 17 11 7.7 5.8 4.610-16 2.5 16.1 9.5 6.6 5.1 3.9 3.312.5-20 2.5 17.3 10.1 7 5.2 4.2 3.416-25 4 16.7 9.8 6.7 5.1 3.9 3.220-32 6 17.5 10 6.8 5.1 4 3.325-40 10 17.3 10.1 7 5.2 4.2 3.432-45 10 16.7 9.8 6.7 5.1 3.9 3.240-57 16 17.5 10 6.8 5.1 4 3.350-63 16 17 9.7 6.7 5.1 4 3.33UA60, 3UA61, 3UA62 Release time: (in sec.)55-80 25 36 21 13.5 9.8 7.5 6.163-90 35 44 24 15.5 11 8.5 6.780-110 35 43 22 14 10 7.7 6.190-120 50 40 21.8 14 10 7.5 5.9110-135 50 32 18 11.7 8.4 6.4 5.1120-150 50 35 19.5 12.8 9.4 7.2 5.8135-160 70 38 20.6 13.8 10 7.6 6.2150-180 95 37 20.5 13.5 9.7 7.4 6.03UA66 Release time: (in sec.)80-125 50 25 16.8 13.1 11.1 9.9 9.1125-200 95 24.4 16.1 11.9 9.8 8.4 7.4160-250 120 23.8 13.9 10.3 8.5 7.3 6.5200-320 185 25.6 15.5 10.9 8.5 7 6.4250-400 240 25 15 10.5 8.5 7 6.2

3 4 5 6 7 8

Page 9: 3UA OLR

3/9

3

The current-time curves show the relationshipbetween the tripping time from cold state andmultiples of the set current E. When the relayis at operating temperature and carrying 1.0 x

E, the tripping times are reduced to approxi-mately 25%. Tripping curve 3 is applicable to3-pole loads and curve 2 to 2-pole loads. Forsingle-pole loads the tripping curves liebetween curves 2 and 3. For normaloperation, all 3 bimetallic strips of theoverload relay must be heated, The overloadrelays 3UA are suitable for protecting motorswith phase control. For protecting single-phase or DC-loads, therefore, all three mainconducting paths must be connected inseries.Tripping curve 3 is then applicable.The release current with a 3-pole symmetricalload is between 105% and 120% of the setcurrent.

Tripping characteristics

Fig. 3/19 Typical tripping characteristicsTripping current (average)

3UA Overload Relays

Page 10: 3UA OLR

3/10

3UA Overload RelaysInternal connection diagrams

3UA50, 3UA52, 3UA54, 3UA55 3UA58, 3UA59, 3UA60, 3UA61, 3UA62

3UA66, 3UA68 3UA66, 3UA68 separate mounting of current transformer and releaserelay

Technical date of auxiliary contacts1. Conventional thermal current (at 35°C) th=6A2. Rated insulation voltage Ui

Unequal potential (NO+NC)400V Equal potential (NO+NC connected aschangeover contact)690V

3. Switching capacityAC-15 DC-13

Ue e Ue e(V) (A) (V) (A)24 260 1.5 24 2125 1.25 60 0.5230 1.15 110 0.3400 1.1 220 0.2500 1690 0.8

Reset button

OFF button

Reset button

OFF button

Reset button

OFF button

Current transformerTripping relay

Connection leadsCu 4 mm2, 4 m long

Page 11: 3UA OLR

3/11

3Panel of 3UA50 3UA52 3UA54 3UA55

3UA Overload RelaysSpecification of installation

Panel of 3UA58 3UA59 3AU60 3UA61 3UA62 3UA66

Overload relays with 3TF or 3TB contactors Overload relay with 3UX14 tripping relay installed as a single unitterminal brackets as a single unit

1. Marks on panel of 3UA.

Terminal for contactor coil A2.Setting current adjusting scaleReset button (blue)H-manualA-automaticSwitch position indicator (green)Tripping of a manual-resetting relay is indicated by a pin projecting from the front-plate.Test button (red)Auxiliary contact terminals shown in 95.96.97.98.NC contacts and NO contacts are shown in positions 95.96 and 97.98 respectively.Main circuit connection terminal No. It must correspond with terminal No. of contactor.In case of separate mounting of 3UA6, the set current must be set on the scale against the reference mark.

2. Set the scale to the rated current of the load.3. If the reset button points to H (manual) and the relay has been tripped, pressing the button puts the relay in operation again.With the door of panel closed, manual reset can be performed by means of the cable release which can be ordered (see accessories in detail).Changing to automatic reset by pressing and turning the button anti-clock wise from H to A.4. When the test button is actuated, the NC contact opens and the NO contact closes, therefore the auxililary circuit (simulation of overloadtripping) can be tested.In the “manual” position, the relay is resetted when the blue reset button is pressed. In the “Automatic” postion, the relay is resetautomatically when the button is released.5. Mounting and operating position, the relays are shown in drawings.

Page 12: 3UA OLR

3/12

3UA Overload RelaysDimension drawings

3UA50+3TF30/31 contactor 3UA50+3TF40/41 contactor.( contactor with 1NO+ or 1NC aux. Contact.contactor with 1NO+NC or 2NO+NC aux. contact)

3UA52+3TF32/33 contactor 3UA52+3TF42/43 3TB42/43 contactor.

3UA54+3TB44 contactorNote: ) The distance to earthed part.) The distance to square OFF-button (stroke 3mm)The distance to round RESET-button (stroke 2.5mm) less 2.5mm.1) For 35mm standard mounting rail (DIN EN 50 022).

3UA55+3TF34/35 contactor.

b1 b2 c1 c2I 125 55 80 108II 130 60 95 100

Page 13: 3UA OLR

3/13

3

3UA Overload RelaysDimension drawings

3UA55+3TF44/45 contactorNote: ) The distance to earthed part.) The distance to square OFF-button (stroke 3mm)The distance to round RESET-button (stroke 2.5mm)less 2.5mm1) For 35mm standard mounting rail (DIN EN 50 022).

3UA58+3UX1421 terminal bracket as a single unit. 3UA59 for installing as a single unit.

3UA50, 3UA52, 3UA54 relays with terminal bracket as a single unit.

Overload relays with terminal brackets d e f3UA50 with 3UX1 418 10 M4 M3.53UA52 with 3UX1 420 14.3 M4 M43UA54 with 3UX1 420 14.3 M4 M4

Page 14: 3UA OLR

3/14

3UA Overload RelaysDimension drawings

3UA50+3TF46, 3TF48, 3TF49, 3TB46, 3TB47, 3TB48 (plug-in type)

3UA58+ a1 a2 a3 b1 b2 b3 c1 d1 d2 d3 e e1 f1 f2 f3 g ∅g1 ∅g23TF46, 3TF47 90 113 70 117 175 100 132 10.5 26.5 25 102 31.5 80 63 122 28 4.8 6.13TF48, 3TF49 100 123 80 133 194 110 140 10.5 26.5 25 116 31.5 89 71 132 39 5.5 6.1

3TB46 90 117 70 118 176 100 123 - 29 - - 34 79 61 122 - 4.8 M53TB47, 3TB48 100 127 80 130 192 110 140 - 30 - - 36 86 68 128 - 5.8 M5/M6

3UA60 for mounting on to contactors or mounting as a single unitwith 3UX1424. 3UA61 3UA62 for mounting on to contactors and for intalling as asingle unit

The distance to earthed part.The distance to square OFF-button (stroke 3mm)The distance to round RESET-button (stroke 2.5mm) less 2.5mm1) For 35mm standard mounting rail (DIN EN 50 022).2) Height and spacing of the connection rails can accmodated to 3TF50/3TF52 contactors (not for 3UA61).

Page 15: 3UA OLR

3/15

3

3UA Overload RelaysDimension drawings

The distance to earthed partThe distance to square OFF-button (stroke 3mm). The distance to round RESET-button (stroke 2.5mm) less 2.5mm.1) Box terminals only for 3TF502) For 75mm standard mounting rail to DIN EN 50023

3UA60, 3UA61, 3UA62+3TB50/52, 3TF50/51/52 Contactors.

Type a b c d e f3UA66 40-2K-3B 46 140 69 ∅9 160 20 33UA66 40-3C,-3D,-3E 50 140 70 ∅11 171 25 4

a1 a2 a3 b1 b2 b3 c1 d1 d2 d3 e e1 e2 f1 f2 f3 ∅g1 ∅g2 g3TB50 120 147 100 150 230 130 150 37 15 - 133 213 43 90 89 149 7 M6 -3TF51 120 143 100 150 232 130 150 20 42 37 139 215.5 40.5 93 80 146 6.3 M8 453TB52 135 162 110 180 257 160 185 42 20 - 154 234 38 115 93 153 7 M8 -3TF50 120 143 100 150 232 130 150 15 37 37 130 213 40 93 80 146 6.3 6.6 453TF52 135 158 110 180 257 160 185 20 42 42 154 234 40 115 93 153 7 M8 48

For installing as a single unit