430 Series Master Mixing Valve Responds to temperature fluctuations instantly

Upload: vodien

Post on 25-Apr-2018

218 views

Category:

Documents


2 download

TRANSCRIPT

430 Series Master Mixing Valve

Responds to temperature fluctuations instantly

B_e430_v3 10/27/04 12:12 PM Page 3

New ATA actuator is easilyretrofitted to existing Powers 430Master Mixing Valve bases.

Triple duty checkstops withscreens trap large particles foreasy maintenance.

Rotatable union checkstops allow forhorizontal or verticalmounting.

Advanced Thermal Actuator(ATA) technology providesunprecedented sensitivity,responding rapidly to temperature changes.

• Tamper-resistant temperature adjustment.

• Advanced Thermal Actuator reacts quickly to correct fluctuations in inlet temperature.

• Solid brass poppets and seats provide precise control without tight-fitting parts to stick or bind.

• ASSE 1017 listed, CSA B125 Certified.

Over 50 years of reliability andunparalleled sensitivity make the430 the unbeatable choice fornew applications and retrofittingexisting 430 valves.

e 4 3 0 M a s t e r M i x i n g V a l v e

Adjustment stem sets outlettemperature ranges from 40° to 160° F.

Time-tested, balanced and double-seated poppetshave been used in Powers’valves for over 50 years.

Vandal-resistant lockingmechanism to secure temperature setting.

®

A v a l v e s o r e l i a b l e , i t t o o k 5 0 y e a r s t o i m p r o v e i t .

B_e430_v3 10/27/04 12:12 PM Page 4

The 430 HydroGuard incorporates ATA technology that holds the mixed water temperatureto within 5°F of setpoint– within the range of 40°Fto 160°F– meeting the requirements of both ASSE

1017 and CSA B125. It compensates for both temperature and pressurechanges in supply lines and

reduces water flow during supply failure. The 430 isavailable in a variety of sizes to suit virtually anyapplication, and comes in two finishes: roughbronze or polished chrome. Recommended applications include shower rooms and group showers, small building domestic water and tempered water for light industrial processes.

QualityQualityfrom

Flow rate based on 140˚ F (60˚ C ) hot inlet, and 100˚ F (38˚ C ) delivery temperature. Valves were tested in full open position, with strainer checkstops, and no outlet restrictions

Advanced Thermal Actuator (ATA) reacts to temperature or pressure changes to temper water.

A. When hot water flows increase, ATA actuator expands, moving poppet and seat to reduce hot water flow and increasing cold water flow. The result is precisely tempered water.

B. When cold water supply fails, ATA actuator contracts, shutting off hot water flow to the outlet.

The cost-effective way to upgrade existing HydroGuard 430 valvesWant to upgrade existing valves to the most advanced level of control? The new Powers 430 ATA Upgrade option is the fast, easy and cost-effective way to achieve cutting-edge performance.

Upgrade Kit431 390 - 016432 390 - 017433 390 - 511434 390 - 512

Model

Temperature range 40˚F (7˚C) - 160˚F (71˚C).

S i n g l e V a l v e a n d M a n i f o l d S y s t e m s

B_e430_v3 10/27/04 12:12 PM Page 5

Pressure Drop Across ValveValve Minimum Min. Flow to (CV) 1 psi 5 psi 10 psi 15 psi 20 psi 30 psi 45 psi 60 psiModel Flow Rate* ASSE 1017 (7 kPa) (35 kPa) (69 kPa) (103 kPa) (138 kPa) (207 kPa) (310 kPa) (414 kPa)

431 0.5 gpm 4.0 gpm 3.59 7.5 gpm 11.0 gpm 14.0 gpm 16.0 gpm 20.0 gpm 25.0 gpm 29.0 gpm(1.9 lpm) (15.0 lpm) (29.0 lpm) (42.0 lpm) (53.0 lpm) (61.0 lpm) (76.0 lpm) (95.0 lpm) (110.0 lpm)

432 0.5 gpm 7.0 gpm 6.79 15.0 gpm 20.0 gpm 26.0 gpm 30.0 gpm 36.0 gpm 45.0 gpm 52.0 gpm(1.9 lpm) (26.0 lpm) (57.0 lpm) (76.0 lpm) (98.0 lpm) (114.0 lpm) (136.0 lpm) (170.0 lpm) (197.0 lpm)

433 0.5 gpm 10.0 gpm 11.41 24.0 gpm 34.0 gpm 44.0 gpm 51.0 gpm 64.0 gpm 80.0 gpm 93.0 gpm(1.9 lpm) (38.0 lpm) (91.0 lpm) (129.0 lpm) (167.0 lpm) (193.0 lpm) (242.0 lpm) (303.0 lpm) (352.0 lpm)

434 0.5 gpm 15.0 gpm 18.27 40.0 gpm 55.0 gpm 71.0 gpm 82.0 gpm 101.0 gpm 125.0 gpm 146.0 gpm(1.9 lpm) (57.0 lpm) (151.0 lpm) (208.0 lpm) (269.0 lpm) (310.0 lpm) (382.0 lpm) (473.0 lpm) (553.0 lpm)

The second main area of concern when it comes to bather safety & comfort

Proper Circulation…• prevents cool down of hot water line during low/no use periods.• saves water and energy.• is required by many plumbing codes when length of hot water

piping exceeds 100 feet.

Most commercial establishments with properly sized valves have little difficulty accommodating the hot water demands placed on asystem during periods of peak usage. The basic guidelines listedbelow will help insure stable control of the domestic water systemduring normal to low/no use periods (see Figure 1).

• Locate master mixer close to hot water source to minimize pressure variations.

• DO NOT recirculate low temperature hot water (LTHW) and high temperature hot water (HTHW) with the same pump, return water may come back hotter than mixer setpoint.

• To ensure that flowpaths remain separate, use TWO (2) circulating pumps, and use check valves to prevent reverse flow.

• Always use an aquastat set at a temperature below the setpointof the mixer.

• Be certain HTHW cannot be introduced into cold side of mixer.

• Always tie LTHW return to cold water side of mixing valve, as well as to the cold water inlet of the water heater.

(CAUTION: Omission of this connection can be extremely dangerous!)

• Be sure to properly size master mixing valve (see Proper Valve Sizing on the other side of this page).

• To minimize natural heat convection, locate master mixer below hot water source…or install a heat trap, which is about a two foot drop in the hot water pipe before going up to the mixing valve.

Flow Rate Pressure Drop (ft. H2O)GPM 431 432 433 434

1 0.18 0.05 0.02 0.012 0.72 0.21 0.07 0.033 1.61 0.47 0.16 0.064 2.86 0.84 0.28 0.115 4.47 1.31 0.44 0.176 6.44 1.89 0.64 0.257 8.77 2.57 0.87 0.348 11.45 3.36 1.14 0.569 14.49 4.25 1.44 0.5610 17.89 5.24 1.77 0.6911 21.65 6.35 2.15 0.8412 25.76 7.55 2.55 1.0013 30.24 8.86 3.00 1.1714 35.07 10.28 3.48 1.3615 40.26 11.80 3.99 1.56

*Minimum flow when the valves are installed at or near hot water source with re-circulated tempered water with a properly sized continuously operating re-circulating pump.

P r o p e r V a l v e S i z i n g a n d C i r c u l a t i o n S y s t e m D e s i g n

Flow Capacity When Tested to ASSE 1017 Standards

WATERHEATER

STEAMINPUT

HTHW

LTHW

HTHW RETURN

HEAT TRAP

Hi

AQUASTAT

AQUASTAT

LTHWRETURN

PUMP

PUMPCOLD

COLD WATER

430HOT

EXPANSIONTANK

CheckstopsHi

Figure 1. Circulation System Design.

B_e430_v3 10/27/04 12:12 PM Page 6

Typical SpecificationMaster mixing valve for tempered water controlshall be of the thermostatic type, capable of maintaining water temperature to any set pointwithin the range of 40˚F to 160˚F (4.5˚-71˚C).Valve must compensate for inlet temperaturechanges. It shall have bronze body constructionwith non-corrosive parts. Valve constructionshall employ poppets which are independentlyseated, balanced, and self-aligning. Valve musthave a quick-acting actuator in order to guaran-tee precise control when tested in accordance toASSE 1017 and CSA B125. Union inlets withstrainers and checkstops must be provided.

Master mixing valves shall be of Powers Series430. Any alternate must have a written approvalprior to bidding.

Specification Table

Maximum Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . 100 psid (689 kPa)Maximum Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . 125 psid (861 kPa)Maximum Hot Water Temp. . . . . . . . . . . . . . . . . . . . . . . . . . 200° F (93° C)Minimum Hot Water Approach Temp. . . . . . 15° F (8.3° C) above set pointOutlet Temperature Range . . . . . . . . . . . . . . . . . . . 40°-160° F (4.5°-71° C)Flow Rate Minimum Flow✝

431: . . . . . . . . . . . . . . . . . . . . 25 gpm @ 45 psid (95.0 lpm at 310 kPa) 431: . . . . . . . .4.0 gpm (15.0 lpm)432: . . . . . . . . . . . . . . . . . . . 45 gpm @ 45 psid (170.0 lpm at 310 kPa) 432: . . . . . . . .7.0 gpm (26.0 lpm)433: . . . . . . . . . . . . . . . . . . . 80 gpm @ 45 psid (303.0 lpm at 310 kPa) 433: . . . . . . . .10.0 gpm (38.0 lpm)434: . . . . . . . . . . . . . . . . . . 125 gpm @ 45 psid (473.0 lpm at 310 kPa) 434: . . . . . . . .15.0 gpm (57.0 lpm)

Certified . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CSA B125Listed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASSE 1017

✝Minimum flow at which value will control to specification at ASSE 1017

The single most critical component of insuringbather safety & comfortGood plumbing system design takes into account both peakhot water demands as well as the typical demands of thebuilding as they fluctuate around the clock. When designinga system, the trick is to provide an adequate supply of hotwater regardless of whether there are one or many bathers at any point in time, and to maintain a comfortable hotwater temperature regardless of the demand placed on thesystem. The key to good plumbing system design is propervalve sizing.

Proper valve sizing is typically achieved by employing one oftwo methods of calculating demand — Hunter’s CurveMethod and the Full Flow Method.

Why Some Master Mixing Valves Perform PoorlyPoor valve operation occurs when the valve selected is drastically under or over-sized, or if the recirculation system is piped improperly causing erratic temperature fluctuations (See Circulation Systems on other side).

Hunter’s Curve Method – Demand is assessed byassigning a specific rating to each fixture, totaling up the ratings and determining the total gallons per minute requiredon the ASPE curve. A valve is then selected that can accommodate this demand.

Full Flow Method – Demand is determined by multiplying the flow rate of each fixture by the estimated usage for that fixture. This is done for all fixtures, then theresults are added up to provide total demand.

Call or visit us Online for a copy

of our PowerSpec Valve Sizing CD.

www.powerscontrols.com

P r o p e r V a l v e S i z i n g

Project _____________________________

Contractor___________________________

Architect/Engineer ____________________

Engineering Approval

B_e430_v3 10/27/04 12:12 PM Page 1

Valve (capacity at 45 psid)

25 gpm 43145 gpm 43280 gpm 433125 gpm 434

Valve and Pipe FinishRough Bronze APolished Chrome C

Piping Inlets/OutletsTop/Top DBottom/Top EBottom/Bottom FBottom/Side GTop/Double Top HBottom/Double Top JBack/Back (exposed fixtures only) KBack/Side (exposed fixtures only) L

Cabinet Style ∆

Exposed, no cabinet MStainless Steel, Recessed NStainless Steel, Semi-Recessed PStainless Steel, Wall Mount QPainted, Recessed RPainted, Semi-Recessed TPainted, Wall Mount U∆ Window on the cabinet door, please consult Powers

Technical Support Dept. for the part number.

Motor Range StandardStandard 40°–160°F (4.5° – 71°C) S

OptionsNone 0Vacuum Breaker (VB) 1Cold Water By-pass 2Vacuum Breaker and Cold Water By-Pass 3Combination T/P Gauge on inlets 4VB & Combination T/P Gauge on inlets 5Cold Water By-pass & Comb. T/P Gauge on inlets 6VB, Cold Water By-Pass & Comb. T/P Gauge on inlets 7

AquaSentry 2 Alarm Systems* 4* Not available in all configurations.

Please consult Powers Technical Support Dept. for availability.

HydroGuard® Series 430 Supply Fixtures

Finish Model Model Model ModelRough Bronze 431-1000 432-1000 433-1000 434-1000Polished Chrome 431-2000 432-2000 433-2000 434-2000

For added safety, the AquaSentry2temperature alarm system

senses and reports abnormal temperature conditions.

Valves

Order Code

© 2004 Powers, A Division of Watts Water Technologies, Inc.USA Phone: 1-800.669.5430 • 1-847.824.9723 Fax: 1-847.824.0627www.powerscontrols.comCanada Phone: 1-888.208.8927 • Fax: 1-888.882.1979

Printed in USA.Form B e430 v3 0444

How to specify and ordera supply fixture:

4 3 S