Revision NotesThe following list provides notes concerning revisions of this document.

Rev. ID Date Notes 111 13/45 IECEx and INMETRO approvals added 112 15/14 PESO/CCOE approval added GOST approval replaced with EAC approval

Page 3: 5333 - PR electronics

5333V112-ES 1

TRANSMISOR DE 2 HILOS PROGRAMABLE

5333

CONTENIDO

Aplicación ................................................................................................... 2Características técnicas ....................................................................... 2Montaje / instalación ............................................................................. 2Aplicaciones .............................................................................................. 3Pedido: 5333 ............................................................................................ 4Especificaciones eléctricas ................................................................. 4Conexiones ................................................................................................ 7Diagrama de bloques ............................................................................. 8Programación ............................................................................................ 9Especificaciones mecánicas ............................................................... 10Montaje de los hilos del sensor ........................................................ 10Appendix .................................................................................................... 11

ATEX Installation Drawing - 5333A ............................................ 12ATEX Installation Drawing - 5333D ............................................ 13IECEx Installation Drawing - 5333A ............................................ 15IECEx Installation Drawing - 5333D ............................................ 16FM Installation Drawing - 5333D ................................................. 18CSA Installation Drawing - 5333D ............................................... 20INMETRO Instruções de Segurança - 5333A ........................... 21INMETRO Instruções de Segurança - 5333D ........................... 22

Page 4: 5333 - PR electronics

2 5333V112-ES

TRANSMISOR DE 2 HILOS PROGRAMABLE 5333

• Entrada RTD u Ohm

• Precisión en la medida alta

• Conexión 3 hilos

• Valor de error en el sensor programable

• Versión de 1 ó 2 canales

Aplicación

• MedidadetemperaturalinealizadaconPt100…Pt1000,Ni100…Ni1000.

• Conversióndelavariacióndelaresistencialinealaseñaldecorrienteanalógicaestándar,porejemplodeválvulasosensoresdenivelóhmicos.

Características técnicas

• EnsólounospocossegundoselusuariopuedeprogramarPR5333paramedirtemperaturas dentro de todos los rangos definidos por la normativa.

• LasentradasderesistenciayRTDtienencompensacióndehilopara3hilosdeconexión.

Montaje / instalación

• ParacabezalesdesensorDINformatoB.Enáreasnopeligrosas,el5333puedeser montado en carril DIN con el aplique PR tipo 8421.

Page 5: 5333 - PR electronics

5333V112-ES 3

V+

mA

+-

V+

mA

+-

RTD a 4...20 mA

Instalación de 2 hilos en sala de control

Resistencia a 4...20 mA

Instalación de 2 hilos en sala de control

APLICACIONES

Page 6: 5333 - PR electronics

4 5333V112-ES

Especificaciones eléctricasRango de especificaciones:-40ºC a +85ºCEspecificaciones comunes:Voltajedealimentación,CC Estándar .................................................................. 8...35 VCC CSA,FM,ATEX,IECEx&INMETRO ......... 8...30 VCC Consumo interno ...................................................... 25mW...0,8W Caída de tensión ...................................................... 8 VCC Tiempo de calentamiento..................................... 5 min. Interfase de comunicaciones .............................. LoopLink Relaciónseñal/ruido ............................................ Mín.60dB Tiempo de respuesta (programable) ................ 0,33...60s Señaldinámica,entrada ........................................ 19 bits Señaldinámica,salida ............................................ 16 bits Temperatura de calibración ................................. 20...28°C

Precisión,lamayordelosvaloresgeneralesybásicos:

Pedido: 5333

Valores generales

Tipo de entrada

Precisión absoluta

Coeficiente de temperature

Todas ≤±0,1%d. intervalo ≤±0,01%d. intervalo / °C

Valores básicos

Tipo de entrada

Precisión básica

Coeficiente de temperature

RTD ≤±0,3°C ≤±0,01°C/°C

Resistencia lin. ≤±0,2Ω ≤ ±20 mΩ / °C

Influencia sobre la inmunidad - EMC ................. <±0,5%d.intervalo

Tipo Versión

5333 Estándar : A CSA,FM,ATEX,IECEx&INMETRO :D

Page 7: 5333 - PR electronics

5333V112-ES 5

Efecto del cambio del voltaje de alimentación ......................................... ≤0,005%d.intervalo/VCC Vibración...................................................................... IEC 60068-2-6 : 2007 2...25Hz .................................................................. ±1,6mm 25...100Hz ...................................................... ±4 g Tamañomáx.delcable .......................................... 1x1,5mm2cabletrenzadoHumedad ..................................................................... <95%HR(nocond.)Dimensiones .............................................................. Ø44x20,2mmGrado de protección (recinto / terminales) ..... IP68 / IP00Peso ............................................................................... 50 gEspecificaciones eléctricas, entradas:Entrada RTD y resistencia lineal:

Offset máx .................................................................. 50%delvalormáx.selec.Resistencia del hilo (máx.) ................................... 10 ΩCorriente del sensor ............................................... >0,2mA,<0,4mAEfecto de la resistencia del cable del sensor (3 hilos) .............................. <0,002Ω/ΩDetección de error en el sensor ......................... SíSalidas:Salidas de corriente:Rangodelaseñal .................................................... 4...20 mARangomín.delaseñal .......................................... 16 mATiempodeactualización ....................................... 135 msResistencia de carga .............................................. ≤ (Valiment.-8)/0,023[Ω]Estabilidad de carga................................................ <±0,01%delintervalo/100ΩDetección de error en el sensor:Programable ............................................................... 3,5...23mANAMUR NE43 Escala alta ..................................... 23 mA NAMUR NE43 Escala baja .................................... 3,5mA

Intervalo = Del rango seleccionado presencialmente

Tipo RTD

Valor mín.

Valor máx

Intervalo mín

Estándar

Pt100Ni100R lin.

-200°C-60°C

0 Ω

+850°C+250°C

10000 Ω

25°C25°C30 Ω

IEC 60751DIN 43760

-----

Page 8: 5333 - PR electronics

6 5333V112-ES

Aprobaciones:EMC 2004/108/CE .................................................. EN 61326-1CCOE .............................................................................. P337392/3EAC TR-CU 020/2011 ............................................ EN 61326-1Aprobación marina:DetNorskeVeritas,Ships&Offshore ............. Stand. f. Certific. No. 2.4Ex / S.I.:ATEX 94/9/CE 5333A ...................................................................... KEMA 10ATEX0003 X 5333D...................................................................... KEMA 03ATEX1535 XCertificado FM ........................................................... 2D5A7 Certificado CSA ......................................................... 1125003IECEx ............................................................................. DEK 13.0036 XINMETRO ..................................................................... DEKRA 13.0002 XCCOE .............................................................................. P337392/4EAC Ex TR-CU 012/2011 ..................................... RUC-DK.GB08.V.00410

Page 9: 5333 - PR electronics

5333V112-ES 7

1 2

mA -+

3 4 63 4 6 3 4 63 4 6

Instalación de 2 hilos

Salida:

Entrada:RTD, 2 hilos RTD, 3 hilos Resistencia, 2 hilos Resistencia, 2 hilos

CONExIONES

Page 10: 5333 - PR electronics

8 5333V112-ES

DIAGRAMA DE BLOquES

0...1

6 m

A

1

36

2m

A

MU

X

4 m

A

5333

PGA

D / A

A /

D

CPU

EE

PR

OM

DC

DC

4

Alim

enta

ción

-

4...

20

mA

Alim

enta

ción

+8

...3

5 V

CC

Circuito Ex, únicamente 5333D

Entr

ada

+

Com

p. +

RT

D

Entr

ada

-

R li

n.Co

m.

Page 11: 5333 - PR electronics

5333V112-ES 9

1

2

*

*

LoopLink

5909 - USB

File Product Input O utput C ommunication Language O ption 08:30:00

PRetop 5331

Date: 2004-8-10

043201594

PRelectronics

Analog inputAnalog output

Serial no:

Input type:O utput type: 4 - 20mA

UpscaleSensor error:Pt100 DIN/IEC

0.00 - 50.00 C

3-wire

1.00 sec------

Input range:

Connection:

Cold junction com p:

Response time:

Tag no:

5333

Desconectar

+Valimentación

* Conectado únicamente para la programacíon en línea

Negro

Rojo Amarillo

Verde

Entrada

Equiporeceptor

Conector

PROGRAMACIóN• ElLoopLinkesuninterfasedecomunicacionesalimentadoporpilaquees

necesario para programar el 5333.

• Paraprogramar,porfavor,mirareldibujodeabajoylasfuncionesdeayudaenel PReset.

• ElLoopLinknoestáaprobadoparacomunicaciónconmódulosinstaladosenáreas peligrosas (Ex).

Pedido: Loop Link

Page 12: 5333 - PR electronics

2 0 . 2 m m

+ -

+ -

ø 6 mm

33 mm

ø 44 mm

10 5333V112-ES

Especificaciones mecánicas Montaje de los hilos del sensor

Loshilosdelsensordebensermontados entre las placas metálicas.

Page 13: 5333 - PR electronics

APPENDIxATEx Installation Drawing - 5333A

ATEx Installation Drawing - 5333D

IECEx installation drawing - 5333A

IECEx installation drawing - 5333D

FM Installation Drawing - 5333D

CSA Installation Drawing - 5333D

INMETRO Instruções de Segurança - 5333A

INMETRO Instruções de Segurança - 5333D

5333V112-ES 11

Page 14: 5333 - PR electronics

12 5333V112-ES

5333QA02LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2013-08-07 Version Revision

V2R0-ES01 Page:

1/1

Esquema de instalación ATEX Para una instalación segura del 5333A, deberán seguirse las siguientes normas. El módulo deberá ser instalado solamente por personal cualificado, personal que esté familiarizado con las normas, directivas y estándares, nacionales e internacionales, que se aplican en estas zonas. Los dos primeros dígitos del número de serie muestran el año de fabricaciónnumber.

.

Certificado ATEX KEMA 10ATEX 0003X Marcado

Estándares EN 60079-0 : 2012, EN 60079-11 : 2012, EN 60079-15 : 2010

Condiciones especiales para un uso seguro: Por tipo de protección Ex nA el transmisor debe ser montado en una pastilla que dispone de un nivel de protección contra la intergridad de, al menos, IP54, conforme con la EN 60529. En atmósferas potencialmente explosivas causadas por la presencia de polvo combustible, el transmisor debe ser montado en una pastilla que dispone de un nivel de protección contra la intergridad de, al menos, IP6X, conforme con la EN 60529. La temperatura de la superficie de la pastilla exterior es de 20 K por encima de la temperatura ambiente. Para una temperatura ambiente ≥ 60°C, la resistencia de los cables al calor debería disponer de un ratio de, al menos, 20 K por encima de la temperatura ambiente.

T4: -40 ≤ Ta ≤ 85ºC T6: -40 ≤ Ta ≤ 60ºC

II 3 G Ex nA [ic] IIC T4 … T6 Gc II 3 G Ex ic IIC T4…T6 Gc II 3 D Ex ic IIIC Dc

Terminal: 3,4,6 Ex nA [ic] Uo: 5V Io: 4.0 mA Po: 20 mW Lo: 900 mH Co: 1000 μF

Terminal: 1,2 Ex nA Umáx. ≤ 35 VCC

Terminal: 1,2 Ex ic Ui = 35 VCC Ii = 110mA Li = 10 μH Ci = 1,0 nF

Page 15: 5333 - PR electronics

5333V112-ES 13

5333QA01LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2013-08-07 Version Revision V2R0-ES01

Page: 1/2

Esquema de instalación ATEX

Para una instalación segura del 5333D, deberán seguirse las siguientes normas. El módulo deberá ser instalado solamente por personal cualificado, personal que esté familiarizado con las normas, directivas y estándares, nacionales e internacionales, que se aplican en estas zonas. Los dos primeros dígitos del número de serie muestran el año de fabricación.

Certificado ATEX KEMA 03ATEX 1535 X Marcado

Estándares EN 60079-0 : 2012, EN 60079-11 : 2012, EN 60079-26 : 2007, EN 60079-15 : 2010

Area no peligrosa Area peligrosa Zona 0, 1, 2, 20, 21, 22

II 1 G Ex ia IIC T4...T6 Ga II 1 D Ex ia IIIC Da II 1 M Ex ia I Ma

Terminal: 3,4,6 Uo: 27 VCC Io: 7 mA Po: 45 mW Lo: 35 mH Co: 90 nF

Terminal: 1,2 Ui: 30 VCC Ii: 120 mA Pi: 0,84 W Li: 110 μH Ci: 1,0 nF

1

2

6

5

4

3

+

-

Barrier

5333D

T4: -40 ≤ Ta ≤ 85ºC T6: -40 ≤ Ta ≤ 60ºC

Barrera

Page 16: 5333 - PR electronics

14 5333V112-ES

5333QA01LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2013-08-07 Version Revision V2R0-ES01

Page: 2/2

Notas de la instalación En atmósferas potencialmente explosivas causadas por la presencia por gases inflamables, el transmisor debe ser instalado en una pastilla que dispone de un nivel de protección contra la intergridad de, al menos, IP20, conforme con la EN 60529. Si el transmisor está instalado en atmósferas explosivas que requieren el uso del equipo de la categoría 1 G, 1 M ó 2 M, y si la pastilla se hace del aluminio, debe ser instalado de tal manera que, incluso en el caso de incidentes raros, las fuentes de ignición debido al impacto y a la fricción, sean resistidas; si la pastilla se hace de materiales no metálicos, las cargas electrostáticas debe ser evitadas. Para el uso en atmósferas potencialmente explosivas causadas por la presencia de polvo combustible deberán seguirse las siguientes normas: El transmisor debe ser instalado en una caja metálica de formato B, de acuerdo con la DIN 43729, ya que dispone de un nivel de protección contra la intergridad de, al menos, IP 6X, conforme con la EN 60529, siempre que sea válido para la aplicación y esté correctamente instalado. Los cables descubiertos y los elementos escondidos deberían ser usados cuando sean válidos para la aplicación y estén correctamente instalados. Para una temperatura ambiente ≥ 60°C, la resistencia de los cables al calor debería disponer de un ratio de, al menos, 20 K por encima de la temperatura ambiente. La temperatura superfical de la pastilla es igual a la temperatura ambiente más 20 K para una capa de polvo con un espesor hasta 5 mm.

Page 17: 5333 - PR electronics

5333QI02LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2013-06-03 Version Revision

V1R0 Page:

1/1

IECEx Installation drawing For safe installation of 5333A or 5343A the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.

Certificate IECEx DEK 13.0036X Marking

Standards IEC 60079-0 : 2011, IEC 60079-11 : 2011, IEC 60079-15 : 2010

Terminal Ex nA [ic] Ex ic

1,2 Umax = 35V Ui : 35V, Ii:110mA, Ii:10µH, Ci:1,0nF

3,4,6 Uo: 5V, Io: 4mA, Po: 20mW, Lo: 900mH, Co: 1000µF

Installation note:

For installation in a potentialy explosive gas atmosphere, the following instructions apply:

For nA installation the transmitter must be installed in an metal enclosure e.g. a form B enclosure, providing a degree of protection of at least IP54 according to IEC60529 or in an enclosure with type of protection Ex n or Ex e. For ic installation the transmitter must be installed in enclosure providing a degree of protection of at least IP20 according to IEC60529 and that is suitable for the application. Cable entry devices and blanking elements shall fulfill the same requirements For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least 20 K above the ambient temperature.

For installation in a potentially explosive dust atmposphere, the following instructions apply: The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a dust layer with a thickness up to 5 mm. The transmitter must be mounted in a enclosure according to DIN 43729 that provides a degree of protection of at least IP6X according to IEC60529, and that is suitable for the application. Cable entry devices and blanking elements shall fulfill the same requirements.

T4: -40 ≤ Ta ≤ 85ºC T6: -40 ≤ Ta ≤ 60ºC

Ex nA [ic] IIC T6..T4 Gc Ex ic IIC T6..T4 Gc Ex ic IIIC Dc

5333V112-ES 15

Page 18: 5333 - PR electronics

5333QI01LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2013-06-03 Version Revision

V1R0 0Page:

1/2

IECEx Installation drawing For safe installation of 5333D or 5343B the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.

Certificate IECEx DEK 13.0036X Marking

Standards IEC 60079-0 : 2011, IEC 60079-11 : 2011, IEC 60079-26:2006

Non Hazardous Area Hazardous area Zone 0, 1, 2, 20, 21, 22, M1

Ex ia IIC T4…T6 Ga Ex ia IIIC Da Ex ia I Ma

1

2

6

5

4

3

+

-

Barrier

5333D5343B

Terminal: 1,2 Ui: 30 VDC Ii: 120 mA Pi: 0.84 W Li: 10μH Ci: 1.0nF

T4: -40 ≤ Ta ≤ 85ºC T5: -40 ≤ Ta ≤ 60ºC T6: -40 ≤ Ta ≤ 45ºC

Terminal: 3,4,6 Uo: 30 VDC Io: 8 mA Po: 60 mW Lo: 35 mH Co: 66 nF

16 5333V112-ES

Page 19: 5333 - PR electronics

5333QI01LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2013-06-03 Version Revision

V1R0 0Page:

2/2

Installation notes.

In a potentially explosive gas atmosphere, the transmitter shall be mounted in a metal form B enclosure in order to provide a degree of protection of at least IP20 according to IEC60529. If however the environment requires a higher degree of protection, this shall be taken into account. If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Ga, Ma and Mb, and if the enclosure is made of aluminum, it must be installed such, that ignition sources due to impact and friction sparks are excluded. For installation in a potentially explosive dust atmosphere, the following instructions apply: For explosive dust atmospheres, the surface temperature of the outer enclosure is 20 K above the ambient temperature. The transmitter shall be mounted in a metal enclosure form B according to DIN43729 that is providing a degree of protection of at least IP6X according to IEC60529, that is suitable for the application and correctly installed. Cable entries and blanking elements shall be used that are suitable for the application and correctly installed. For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least 20 K above the ambient temperature.

.

5333V112-ES 17

Page 20: 5333 - PR electronics

5300QF01LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2014-03-31 Version Revision

V8R0 Doc. No.

5300Q502 Rev AH Page: 1/2

FM Installation Drawing 5300Q502 Rev AH

Model 5331C,5331D, 5333C, 5333D and 5343B

Model 5335C, 5335D, 5336D, 5337D

Non Hazardous LocationHazardous (Classified) Location

Associated Apparatusor Barrier

with entity Parameters:

SENSOR

1 2

345

6

UM < 250VVoc or Uo < Vmax or UiIsc or Io < Imax or IiPo < PiCa or Co > Ci + CcableLa or Lo > Li + Lcable

This device must not be connected to any associated apparatus which uses or generates more than 250 VRMS

+

‐Terminal 1 , 2Vmax or Ui: 30 VImax or Ii: 120 mAPmax or Pi: 0.84 WCi: 1 nFLi:10 uH

Terminal 3,4,5,6Vt or Uo: 9.6 VIt or Io: 28 mAPt or Po: 67.2 mWCa or Co: 3.5 uFLa or Lo: 35 mH

Ambient temperature limitsT4: ‐40 to + 85 deg. CelciusT6: ‐40 to + 60 deg. Celcius

Class I,Division1, Groups, A,B,C,D T4..T6Class I, Zone 0, AEx ia IIC T4..T6

Non Hazardous LocationHazardous (Classified) Location

Associated Apparatusor Barrier

with entity Parameters:

SENSOR

1 2

345

6

UM < 250VVoc or Uo < Vmax or UiIsc or Io < Imax or IiPo < PiCa or Co > Ci + CcableLa or Lo > Li + Lcable

This device must not be connected to any associated apparatus which uses or generates more than 250 VRMS

+

‐Terminal 1 , 2Vmax or Ui: 30 VImax or Ii: 120 mAPmax or Pi: 0.84 WCi: 1 nFLi:10 uH

Terminal 3,4,5,6Vt or Uo: 9.6 VIt or Io: 28 mAPt or Po: 67.2 mWCa or Co: 3.5 uFLa or Lo: 35 mH

Ambient temperature limitsT4: ‐40 to + 85 deg. CelciusT6: ‐40 to + 60 deg. Celcius

Class I,Division1, Groups, A,B,C,D T4..T6Class I, Zone 0, AEx ia IIC T4..T6

18 5333V112-ES

Page 21: 5333 - PR electronics

5300QF01LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2014-03-31 Version Revision

V8R0 Doc. No.

5300Q502 Rev AH Page: 2/2

The entity concept The Transmitter must be installed according to National Electrical Code (ANSI-NFPA 70) and shall be installed with the enclosure, mounting, and spacing segregation requirement of the ultimate application.

Equipment that is FM-approved for intrinsic safety may be connected to barriers based on the ENTITY CONCEPT. This concept permits interconnection of approved transmitters, meters and other devices in combinations which have not been specifically examined by FM, provided that the agency's criteria are met. The combination is then intrinsically safe, if the entity concept is acceptable to the authority having jurisdiction over the installation.

The entity concept criteria are as follows:

The intrinsically safe devices, other than barriers, must not be a source of power. The maximum voltage Ui(VMAX) and current Ii(IMAX), and maximum power Pi(Pmax), which the device can receive and remain intrinsically safe, must be equal to or greater than the voltage (Uo or VOC or Vt) and current (Io or ISC or It) and the power Po which can be delivered by the barrier. The sum of the maximum unprotected capacitance (Ci) for each intrinsically device and the interconnect-ing wiring must be less than the capacitance (Ca) which can be safely connected to the barrier. The sum of the maximum unprotected inductance (Li) for each intrinsically device and the interconnecting wiring must be less than the inductance (La) which can be safely connected to the barrier. The entity parameters Uo,VOC or Vt and Io,ISC or It, and Ca and La for barriers are provided by the barrier manufacturer. NI Field Circuit Parameters Model 5331C, 5331D, 5333C, 5333D, 5335C, 5335D, 5336D, 5337D and 5343B

Non Hazardous LocationHazardous (Classified) Location

Associated Apparatusor Barrier

SENSOR

1 2

345

6 This device must not be connected to any associated apparatus which uses or generates more than 250 VRMS

+

Terminal 1 , 2Vmax : 35 VCi: 1.0 nFLi:10 uH

Ambient temperature limitsT4: ‐40 to + 85 deg. CelciusT6: ‐40 to + 60 deg. Celcius

Class I,Division2, Groups, A,B,C,D T4..T6Class I, Zone 2, IIC T4..T6

5333V112-ES 19

Page 22: 5333 - PR electronics

5335QE01LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2014-03-31 Version Revision

V4R0 Doc. No.

533XQC03

Page: 1/1

CSA Installation drawing 533XQC03

CLASS 2258 04 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous Locations Class I, Division 1, Groups A, B, C and D Ex ia IIC, Ga CLASS 2258 84 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous Locations - Certified to US Standards Class I, Division 1, Groups A, B, C and D Class I, Zone 0, AEx ia IIC, Ga

Warning:

Substitution of components may impair intrinsic safety.

The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in the Canadian Electrical Code (CEC) or for US the National Electrical Code (NEC).

Non Hazardous Area Hazardous area

1

2

6

5

4

3

+

-

Barrier

Module 5335D, 5336D and 5337D Terminal: 3,4,5,6 Uo: 9.6 VDC Io: 28 mA Po: 67.2 mW Lo: 35 mH Co: 2.5 μF

Terminal: 1,2 Ui: 30 VDC Ii: 120 mA Pi: 0.84 W Li: 10 μH Ci: 1.0 nF

T4: -40 ≤ Ta ≤ 85ºC T6: -40 ≤ Ta ≤ 60ºC

Module 5331D, 5333D Terminal: 3,4,5,6 Only passive, or non-energy storing devices such as RTD’s and Thermocouples may be connected

20 5333V112-ES

Page 23: 5333 - PR electronics

5333QB02LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2013-06-03 Version Revision

V1R0 Page:

1/1

Desenho de Instalação InNMETRO Para instalação segura do 5333A ou 5343A o seguinte deve ser observado. O modo deve apenas ser instalado por pessoas qualificadas que são familiarizadas com as leis nacionais e internacionais, diretrizes e padrões que se aplicam a esta área. Ano de fabricação pode ser pego dos dois primeiros dígitos do número de série.

Certificado IECEx DEK 13.0002 X Indicaçã

Padrões ABNT NBR IEC 60079-0 : 2008, ABNT NBR IEC 60079-11 : 2009, IEC 60079-15 : 2010, ABNT NBR IEC 60079-26 : 2008

Terminal Ex nA [ic] Ex ic

1,2 Umax = 35V Ui : 35V, Ii:110mA, Ii:10µH, Ci:1,0nF

3,4,6 Uo: 5V, Io: 4mA, Po: 20mW, Lo: 900mH, Co: 1000µF

Notas para instalação Para a instalação em uma atmosfera de gás potencialmente explosivo, se aplicam as instruções a seguir:

Para a instalação nA o transmissor deve ser instalado em um gabinete de metal, por exemplo, gabinete em forma B que forneça um grau de proteção de pelo menos IP54 de acordo com IEC60529 ou em um caixa com tipo de proteção Ex n ou Ex e. Para a instalação iC o transmissor deve ser instalado em um invólucro proporcionando um grau de proteção de IP20, pelo menos, de acordo com a norma IEC60529 que é adequado para a aplicação. Dispositivos de entrada de cabos e elementos de supressão devem cumprir os mesmos requisitos. Para uma temperatura ambiente ≥ 60 º C, os cabos resistentes ao calor precisam ser utilizados com uma classificação de pelo menos 20 K acima da temperatura ambiente.

Para a instalação em uma atmosfera de poeira potencialmente explosiva , se aplicam as instruções a seguir:

A temperatura da superfície do invólucro é igual à temperatura ambiente mais 20 K, para uma camada de pó , com uma espessura superior a 5 mm. O transmissor deve ser montado em um invólucro de acordo com a norma DIN 43729 , que proporciona um grau de proteção de, pelo menos, IP6X de acordo com a norma IEC60529, e que seja apropriado para a aplicação. Dispositivos de entrada de cabos e elementos de supressão devem cumprir as mesmas exigências

T4: -40 ≤ Ta ≤ 85ºC T6: -40 ≤ Ta ≤ 60ºC

Ex nA [ic] IIC T6..T4 Gc Ex ic IIC T6..T4 Gc Ex ic IIIC Dc

5333V112-ES 21

Page 24: 5333 - PR electronics

5333QB01LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2013-06-03 Version Revision

V1R0 Page:

1/2

Desenho de Instalação InNMETRO Para instalação segura do 5333D ou 5343B o seguinte deve ser observado. O modo deve apenas ser instalado por pessoas qualificadas que são familiarizadas com as leis nacionais e internacionais, diretrizes e padrões que se aplicam a esta área. Ano de fabricação pode ser pego dos dois primeiros dígitos do número de série.

Certificado DEKRA 13.0002 X Indicação Padrões ABNT NBR IEC 60079-0 : 2008, ABNT NBR IEC 60079-11 : 2009, IEC 60079-15 : 2010, ABNT NBR IEC 60079-26 : 2008

Sem áreas perigosas Áreas perigosas Zona 0, 1, 2, 20, 21, 22, M1

Ex ia IIC T6…T4 Ga Ex ia IIIC Da

1

2

6

5

4

3

+

-

Barrier

5333D5343B

Terminal: 1,2 Ui: 30 VDC Ii: 120 mA Pi: 0,84 W Li: 10 μH Ci: 1,0 nF

T4: -40 ≤ Ta ≤ 85ºC T5: -40 ≤ Ta ≤ 60ºC T6: -40 ≤ Ta ≤ 45ºC

Terminal: 3,4,5,6 Uo: 30 VDC Io: 8 mA Po: 60 mW Lo: 35 mH Co: 66 nF

22 5333V112-ES

Page 25: 5333 - PR electronics

5333QB01LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Revision date:

2013-06-03 Version Revision

V1R0 Page:

2/2

Notas de Instalação.

Em uma atmosfera de gás potencialmente explosiva, o transmissor deve ser montado em um enclousure a fim de garantir um grau de proteção de no mínimo IP20 de acordo com EN60529. Se contudo o ambiente requer um nível de proteção maior, isso deve ser levado em conta Se o transmissor é instalado em uma atmosfera explosiva exigindo o uso de equipamento de categoria Ga e se o enclosure é feito de alumínio, ele deve ser instalado de modo que, mesmo em caso de avaria rara, fontes de ignição devido a impacto e fricção, faíscas são eliminadas; se o enclosure é feito de materiais não metálicos, cargas eletroestáticas devem ser evitadas. Para instalação em atmosfera de poeira potencialmente explosiva, as instruções a seguir: O transmissor deve ser montado em enclosure de metal forma B de acordo com DIN43729 que está fornecendo um grau de proteção de pelo menos IP6X de acordo com EN60529. Isso é adequado para aplicação e corretamente instalado. As entradas dos cabos e os elementos de obturação que podem ser utilizados são adequados para a aplicação e corretamente instalados. Para temperatura ambiente >= 60ºC, fios de resistência ao calor devem ser usados com uma faixa de pelo menos 20K acima da temperatura ambiente.

A temperatura da superfície do enclosure é igual à temperatura ambiente mais de 20 K, por uma camada de pó, com uma espessura até 5 mm.

5333V112-ES 23

Page 26: 5333 - PR electronics

Displays programables con una ampliaselección de entradas y salidas para visualizar temperatura,volumen, peso, etc. Disponen de linealización, escalado yfuncionesdemedidadiferencial, programablesvíael softwarePReset.

Displays

Una amplia selección de transmisores para montajeDINformatoBymódulosencarrilDINconcomunicaciónde bus analógica y digital abarcando desde aplicacionesespecíficas hasta transmisores universales.

Temperatura

Aislamiento galvánico para señales analógicasy digitales, así como para señales HART®. Un amplio rango de productostantoparaalimentaciónen lazocomoparaaisladoresuniversales,disponiendodelinea-lización,inversiónyescaladodelasseñalesdesalida.

Aislamiento

Interfasesparaseñalesanalógicasydigitales,así como señales HART®. entre sensores, convertidores I/P,señalesdefrecuenciaysistemasdecontrolenzonasEx0,1y2yporalgunosmódulosenzonas20,21y22.

Interfases Ex

Módulos programables frontalmente o mediante PC con opciones universales para entrada, salida yalimentación. Esta familia de productos ofrece un gran número de opciones avanzadas tales como calibración de proceso,linealizaciónyautodiagnósticos.

Universal