Scientific Rational for Avtec’sThermashield™ Fire Retardant Coating

Thermashield™ is an innovative air-dried solvent based fire retardant surface coating

Thermashield™ is Bromine, Antimony and Magnesium Free

It can be easily be applied to Structural Steel, Aluminum, Metal alloys, and polymeric composite materials

Thermashield™ can be applied as an interior or exterior coating due to its ability to withstand harsh environmental conditions

Page 3: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

This product forms a ceramic/carbonaceous, open-cell matrix barrier when exposed to open flame or excessive heat

This three-dimensional swollen glassy char layer shields the underlying material from open flame, attack by oxygen, radiant heat and suppresses afterglow and smoke

Thermashield™ is non-conducting and insulating, will not flake, peel or dust, and withstands multiple high intensity impacts

Is resistant to water, weather, sea spray, and chemical attack

Thermashield™ bonds well to a wide variety of substrates, is non-corrosive and is non-toxic

Avtec’s Thermashield™ Has Been Designed to Bring in a New Era of Fire and Thermal Protection for Industrial, Transportation, and Structural Applications

Page 4: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

a) A catalyst / initiator.b) A carbonific, or source of carbon.c) A source of non-flammable gasesd) Ceramic / inorganics.

Each of the groups of the composition contributes a specific property to the formulation and each is critical to the success of the coating in overcoming the disadvantages associated with other fire retardant coatings.

Thermashield™ Is a Composition of Materials Where Each Constituent Falls Into One of Four Fire Retarding Functional Groups:

Page 5: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

Upon Exposure to an Open Flame or High Radiant Heat Source, the Active Material Operates Stepwise in the Following Orderly Format:

In the earliest phase of the fire retardant activity reaction, the catalyst / initiator decomposes to release a strong acid by-product.

Whereupon it dehydrates the pyrolysing polymer coating resin and reacts with the carbonific to form initiator based esters.

After this series of reactions and decompositions, the original strong acid by-product of the catalyst decomposition is also released for further reaction to continue the cycle. Unsaturated compounds are formed with subsequent charring.

a)

Page 6: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

As the temperature rises, the catalyzed carbonific begins to decompose along a much different route and at a lower temperature than would have occurred for a non-catalyzed carbonific.

A functional component in the carbonific binds with the dehydrated polymer coating to lock the forming carbonaceous layer to the underlying substrate and impart structural integrity to the char layer.

Additionally, decomposition of the carbonific constituents produces large volumes of char, carbon dioxide and water.

The original strong acid by-product of the catalyst decomposition continues to be regenerated for the reaction cycle to continue until final termination.

Stepwise Format

b)

Page 7: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

Stepwise Format

The blowing agent then begins to decompose, yielding large volumes of non-flammable gases, water, and additional char.

the carbonaceous char bubbles and foams, forming a swollen insulative heat shield.

c)

Page 8: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

Stepwise Format

The ceramic / inorganic constituents perform several functions:1) To form a protective ceramic coating which is resistant to

extremely high temperatures.2) To add rigidity and strength to the char.3) To reflect the infrared radiation (IR) radiances.4) Absorb IR and irradiate by emissivity.5) Suppress smoke and afterglow.

After the reaction cycle is complete, the ceramic / inorganic components dispersed throughout the carbonaceous barrier keep even higher temperatures and high velocity pressure gradients from attacking the substrate.

d)

Page 9: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

Avtec Industries Case Studies Simulated Pool Fire Test

Test was carried out at the Socorro Proving Grounds, Socorro, New Mexico

This test was designed to simulate a 1600° F hydrocarbon fuel pool fire

A 1/8 in. steel plate was coated on one side with 1/16 in. Thermashield™ and fitted with 9 thermocouples on the uncoated side

Coated side was exposed to the flaming pool of fuel, the uncoated side was left dry and away from flame

Test requirements state the thermocouples shall not exceed 800° F after a minimum of 100 min.

Results are as follows…

Page 10: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

Pool Fire Data

None of the 9 Thermocouples ever exceeded 250° F after 2 Hours and 39 Minutes

Page 11: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

Avtec Industries Case StudiesASTM E-119 Test on 5/8” Steel Plate

This test method is intended to evaluate the duration for which assemblies will contain a fire, or retain their structural integrity, or, exhibit both properties

Steel Plates, 12” x 12” x 5/8”, with Thermashield™ Coating thicknesses of 0.020”; 0.040”; 0.055”; and 0.060” on one side were exposed to the E-119 time/temperature curve at 2000° F

The unexposed side was instrumented with two type K sheathed, grounded thermocouples

The tests were conducted at V-TEC Laboratories, Bronx, New York

Test results are as follows…

Page 12: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

Avtec Industries Case StudiesASTM E-119 Test on 5/8” Steel Plate

Backside time to reach 1000 deg F (532 deg C)

125

35

75

110

0

20

40

60

80

100

120

140

0.02 0.04 0.055 0.06

Thickness(in.)

Tim

e (

min

)

Page 13: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

Performance Characteristics

Avtec IndustriesThermashield™

PPG IndustriesPitt-Char XP

International CoatingsChartek IV

1 hr .035 in. (NO Reinforcement)

.280 in. (with Steel or Glass Wire Mesh Reinforcement)

.270 in. (with Steel Flange Edge Reinforcement)

1 ½ hr .050 in. (NO Reinforcement)

.400 in. (with Steel or Glass Wire Mesh Reinforcement)

.410 in. (with Steel Flange Edge Reinforcement)

2 hr .060 in. (NO Reinforcement)

.520 in. (with Steel or Glass Wire Mesh Reinforcement)

.550 in. (with Steel Flange Edge Reinforcement)

Page 14: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

Avtec Industries Case StudiesVisual Torch Test

This test is designed to demonstrate the properties of Avtec’s Thermashield™ Fire Retardant Coating on steel plate

A 4”x 6” hot rolled steel panel 1/16” thick was spray coated with 1/16” Thermashield™ Fire Retardant Coating and allowed to air-dry

The panel was then subjected to a 2500° F flame front These pictures show how the Thermashield™ reacts to

the excessive heat and flame, insulating the panel and moving the flame front away from the substrate

Page 15: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

START

Page 16: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

After 1 MIN.

Page 17: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

After 5 MIN.

Page 18: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

After 10 MIN.

Page 19: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

STOP 20 MIN.

Page 20: 9 Kane Industrial Drive Hudson, MA 01749 Phone: 978 562-2300 FAX: 978 562-8900  UNEQUALED TECHNOLOGY UNSURPASSED PERFORMANCE

SIDE VIEW