92-21916-27 rev. 09 rrka 3 phase only gas/electric package...
TRANSCRIPT
92-21916-27-09SUPERSEDES 92-21916-27-08
INSTALLATION INSTRUCTIONSFOR COMBINATION HEATING AND COOLING ROOFTOPUNITS EQUIPPED WITH INTERMITTENT IGNITIONRRKA/RRMA/RRNA SERIES
ISO 9001:2000
RRKA 3-5 TON (3 PHASE MODELS ONLY)
(carbon monoxide)
Standard 380Standard 210/240 UAC
2
USE ONLY WITH TYPE OF GASAPPROVED FOR THIS UNIT.REFER TO THE UNIT RATINGPLATE.
INSTALL THIS UNIT ONLY IN ALOCATION AND POSITION ASSPECIFIED IN THE LOCATIONREQUIREMENTS ANDCONSIDERATIONS SECTION OFTHESE INSTRUCTIONS. PROVIDEADEQUATE COMBUSTION ANDVENTILATION AIR TO THE UNITSPACE AS SPECIFIED IN THEVENTING SECTION OF THESEINSTRUCTIONS.
PROVIDE ADEQUATECOMBUSTION AND VENTILATIONAIR TO THE UNIT SPACE ASSPECIFIED IN THE COMBUSTIONAND VENTILATION AIR SECTIONOF THESE INSTRUCTIONS.
COMBUSTION PRODUCTS MUSTBE DISCHARGED OUTDOORS.CONNECT THIS UNIT TO ANAPPROVED VENT SYSTEM ONLY,AS SPECIFIED IN VENT PIPEINSTALLATION SECTION OFTHESE INSTRUCTIONS.
NEVER TEST FOR GAS LEAKSWITH AN OPEN FLAME. USE ACOMMERCIALLY AVAILABLESOAP SOLUTION MADESPECIFICALLY FOR THEDETECTION OF LEAKS TO CHECKALL CONNECTIONS, ASSPECIFIED IN GAS SUPPLY ANDPIPING SECTION OF THESEINSTRUCTIONS.
ALWAYS INSTALL UNIT TOOPERATE WITHIN THE UNIT'SINTENDED TEMPERATURE-RISERANGE WITH A DUCT SYSTEMWHICH HAS AN EXTERNALSTATIC PRESSURE WITHIN THEALLOWABLE RANGE, ASSPECIFIED IN DUCTING SECTIONOF THESE INSTRUCTIONS. SEEALSO UNIT RATING PLATE.
WHEN A UNIT IS INSTALLED SOTHAT SUPPLY DUCTS CARRY AIRCIRCULATED BY THE UNIT TOAREAS OUTSIDE THE SPACECONTAINING THE UNIT, THERETURN AIR SHALL ALSO BEHANDLED BY DUCT(S) SEALEDTO THE UNIT CASING ANDTERMINATING OUTSIDE THESPACE CONTAINING THE UNIT.
! WARNING
! WARNING
! WARNING
! WARNING
! WARNING! WARNING
! WARNING
! WARNING
SAFETY INFORMATION
THIS UNIT MAY BE USED TOHEAT THE BUILDING OR STRUC-TURE DURING CONSTRUCTION IFTHE FOLLOWING INSTALLATIONREQUIREMENTS ARE MET.INSTALLATION MUST COMPLYWITH ALL INSTALLATIONINSTRUCTIONS INCLUDING:
• PROPER VENT INSTALLATION;
• FURNACE OPERATING UNDERTHERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TOTHE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE ANDTEMPERATURE RISE PER RAT-ING PLATE MARKING;
• MEANS OF PROVIDING OUT-DOOR AIR REQUIRED FORCOMBUSTION;
• RETURN AIR TEMPERATUREMAINTAINED BETWEEN 55°F(13°C) AND 80°F (27°C); AND
• INSTALLATION OF EXHAUSTAND COMBUSTION AIR INLETHOODS COMPLETED;
• CLEAN FURNACE, DUCT WORKAND COMPONENTS UPON SUBSTANTIAL COMPLETION OFTHE CONSTRUCTION PROCESS,VERIFY FURNACE OPERATINGCONDITIONS INCLUDING IGNITION, INPUT RATE, TEM-PERATURE RISE AND VENTING,ACCORDING TO THE INSTRUC-TIONS.
3
A. GENERALThe Combination Gas Heating/ElectricCooling Rooftop is available in 40, 60, 80and 100 BTU/Hr. heating inputs andcooling capacities of 3, 31/2, 4 and 5 nominal tons of cooling. Units areconvertible from end supply and return tobottom supply and return by relocation ofsupply and return air access panels. Seecover installation detail.The units are weatherized for mountingoutside of the building.
UNITS ARE NOT DESIGN CERTIFIEDTO BE INSTALLED INSIDE THESTRUCTURE. DOING SO CAN CAUSEINADEQUATE UNIT PERFORMANCEAS WELL AS PROPERTY DAMAGEAND CARBON MONOXIDE POISONINGRESULTING IN PERSONAL INJURY ORDEATH.The information on the rating plate is incompliance with the FTC and DOE ratingfor single phase units. The followinginformation is for three phase units whichare not covered under the DOEcertification program.1. The energy consumption of the
ignition system used with this unit is 9watts.
2. The efficiency rating of this unit is aproduct thermal efficiency ratingdetermined under continuousoperating conditions independent ofany installed system.
B. MAJOR COMPONENTSThe unit includes a hermetically-sealedrefrigerating system (consisting of acompressor, condenser coil, evaporatorcoil with capillary tube assembly), acirculation air blower, a condenser fan, aheat exchanger assembly, gas burner andcontrol assembly, combustion air motorand fan, and all necessary internalelectrical wiring. The cooling system ofthese units is factory-evacuated, chargedand performance tested. Refrigerantamount and type are indicated on ratingplate.
INTRODUCTION I. SPECIFICATIONSTABLE OF CONTENTS
Recognize this symbol as anindication of Important SafetyInformation!
!
! WARNING
! WARNING
Page No.SAFETY INFORMATION 2
I. SPECIFICATIONSComponents 3Unit Dimensions 5-6Access Locations 6
II. INSTALLATIONGeneral 7Location Considerations 7Exhaust & Combustion
Hoods 8Cover Panel Installation 8,9Clearances 10Rooftop 11Ducting 11,12Return Air 12
III. GAS SUPPLY & PIPING 14-16IV. ELECTRICAL WIRING
Power Supply 17Hook-up 18Internal Wiring 18Thermostat 18
V. FURNACE CONTROLS 19,20VI. OPERATION INFO 21,22VII. AIRFLOW 23,24VIII. TROUBLESHOOTING 25,26IX. WIRING DIAGRAMS 27,28X. CHARGE CHARTS 29-35
THE MANUFACTURER’S WARRANTYDOES NOT COVER ANY DAMAGE ORDEFECT TO THE AIR CONDITIONERCAUSED BY THE ATTACHMENT ORUSE OF ANY COMPONENTS,ACCESSORIES OR DEVICES (OTHERTHAN THOSE AUTHORIZED BY THEMANUFACTURER) INTO, ONTO OR INCONJUNCTION WITH THE AIRCONDITIONER. YOU SHOULD BEAWARE THAT THE USE OFUNAUTHORIZED COMPONENTS,ACCESSORIES OR DEVICES MAYADVERSELY AFFECT THE OPERATIONOF THE AIR CONDITIONER AND MAYALSO ENDANGER LIFE ANDPROPERTY. THE MANUFACTURERDISCLAIMS ANY RESPONSIBILITY FORSUCH LOSS OR INJURY RESULTINGFROM THE USE OF SUCHUNAUTHORIZED COMPONENTS,ACCESSORIES OR DEVICES.This booklet contains the installation andoperating instructions for your combinationgas heating/electric cooling unit. There aresome precautions that should be taken toderive maximum satisfaction from it.Improper installation can result inunsatisfactory operation or dangerousconditions.Read this booklet and any instructionspackaged with separate equipmentrequired to make up the system prior toinstallation. Give this booklet to the ownerand explain its provisions. The ownershould retain this booklet for futurereference.
CHECKING PRODUCTRECEIVEDUpon receiving the unit, inspect it for anydamage from shipment. Claims fordamage, either shipping or concealed,should be filed immediately with theshipping company. IMPORTANT: Checkthe unit model number, heating size,electrical characteristics, and accessoriesto determine if they are correct.
Installation Instructions are updated on aregular basis. This is done as productchanges occur or if new informationbecomes available. In this publication, anarrow () denotes changes from theprevious edition or additional newmaterial.
26, 2728
29-30
The following information is for threephase units which are not covered underthe DOE certification program.
1. The energy consumption of theignition system used with this unit is 9watts.
2. The efficiency rating of this unit is aproduct thermal efficiency ratingdetermined under continuousoperating conditions independent ofany installed system.
B. MAJOR COMPONENTSThe unit includes a hermetically-sealedrefrigerating system (consisting of acompressor, condenser coil, evaporatorcoil with capillary tube assembly), acirculation air blower, a condenser fan, aheat exchanger assembly, gas burner andcontrol assembly, combustion air motorand fan, and all necessary internalelectrical wiring. The cooling system ofthese units is factory-evacuated, chargedand performance tested. Refrigerantamount and type are indicated on ratingplate.
4
*WE
IGH
TVA
RIE
S D
EP
EN
DIN
G O
N H
EAT
ING
INP
UT.
MA
XIM
UM
PO
SS
IBLE
WE
IGH
TS
HO
WN
.
TAB
LE
1. E
LE
CT
RIC
AL
AN
D P
HY
SIC
AL
DA
TAF
OR
GA
S H
EA
T R
OO
FTO
PM
OD
EL
S
NO
MIN
ALCO
OLI
NG
CAPA
CITY
TON
S
EFFI
CIEN
CY(S
EER
)PH
ASE
HER
TZVO
LTS
COM
PR.
RLA
COM
PR.
LRA
FAN
MO
TOR
FLA
BLR
MO
TOR
FLA
MIN
IMU
MCI
RCU
ITAM
PACI
TYAM
PS
FUSE
OR
HAC
RCI
RCU
IT B
REA
KER
*
MIN
.AM
PER
ESM
AX.
AMPE
RES
ELEC
TRIC
ALPH
YSIC
AL
DR
IVE
TYPE
FILT
ER
REC
OM
MEN
DED
NO
. AN
D S
IZE
OU
TDO
OR
CO
IL
AREA
SQ. F
T.(S
Q. M
)N
O.
RO
WS
CFM
(L/S
)
R22 OZ. (G)
NET WT.
LBS
(KG
)
SHIP
WT.
LBS.
(KG
)
3.0
103-
60-2
08/2
3012
.5/1
2.5
881.
32.
420
/20
25/2
530
/30
DIR
24”
X 24
”X
1”
4.0
103-
60-2
08/2
3014
.8/1
4.8
115
1.7
4.4
25/2
530
/30
35/3
5D
IR24
”X
24”
X 1”
5.0
103-
60-2
08/2
3018
.6/1
8.6
128
1.7
4.4
30/3
035
/35
45/4
5D
IR24
”X
30”
X 1”
10.5
1.0
2730
6242
646
6(.9
75)
(128
8)(1
758)
(193
.2)
(211
.4)
12.8
1.0
3200
7846
250
2(1
.189
)(1
510)
(221
1)(2
09.6
)(2
27.7
)12
.82.
029
0011
952
356
8(1
.189
)(1
368)
(337
3)(2
37.7
)(2
58.2
)
3.5
103-
60-2
08/2
3012
.5/1
2.5
881.
32.
420
/20
25/2
530
/30
DIR
24”
X 24
”X
1”12
.81.
028
7574
437
477
(1.1
89)
(126
2)(2
098)
(198
.2)
(216
.4)
5
Unit DimensionsFOR CLEARANCESSEE PAGE 9, FIGURE 12.
FIGURE 1BOTTOM VIEW
I616
153 /83
1 /4
11 /8
11 /8
451 /8
INSIDE491 /2
INSIDE
47 /8
33 /4
33 /4
21 /2
191 /2141 /8
TYP.
1 /2
1 /2
FIGURE 2CABINET DIMENSIONS 1.5-4 TONS
I258
475/8 507/8
31/2
85/8
13/4
41/2
47/8
15
FLUEEXHAUSTHOOD
GASSUPPLYENTRANCE
BLOWER /EVAPORATORACCESSPANEL
SIDE SUPPLYDUCT OPENING
SIDE RETURNDUCT OPENING
191/8133/4
335/8
31/8
4
BOTTOM
RETURN
DUCT
OPENING
BOTTOM
SUPPLY
DUCT
OPENING
FLUEEXHAUSTHOOD
GASSUPPLYENTRANCE
50 7/847 5/8
1 3/4
8 5/8
3 1/2
15
4 7/819 1/8
3 1/8
13 3/4
33 5/8
4
4 1/2
BLOWER /EVAPORATORACCESSPANEL
SIDE SUPPLY DUCT OPENING
SIDE RETURN DUCT OPENING
6
FIGURE 4ACCESS LOCATIONS
FIGURE 3CABINET DIMENSIONS
I259
A0940-01-00
OUTDOOR FAN GRILLEAND COMPRESSOR ACCESS
FURNACE/CONTROLSACCESS PANEL
COMBUSTION AIRINLET HOOD
FIELD POWERWIRE ENTRANCE
FIELD CONTROLWIRE ENTRANCE
LIQUID PRESSURESERVICE PORT
SUCTION PRESSURESERVICE PORT
THREADED PVC CONDENSATEDRAIN CONNECTION (3/4 NPT)
OUTDOOR COILPROTECTIVE GRILLE
FILTER ACCESSPANEL (FOR UNITMOUNTED FILTERACCESSORY)
FLUE EXHAUST
205/115/ 5
223/4
207/8
FLUEEXHAUSTHOOD
GASSUPPLYENTRANCE
BLOWER /EVAPORATORACCESS PANEL
SIDE SUPPLYDUCT OPENING
SIDE RETURNDUCT OPENING
Unit Dimensions(continued)
205/8
115/8
5
FLUEEXHAUSTHOOD
GASSUPPLYENTRANCE
50 7/847 5/8
1 3/4
8 5/8
3 1/2
15
4 7/819 1/8
3 1/8
13 3/4
33 5/84
4 1/2
BLOWER /EVAPORATORACCESSPANEL
SIDE SUPPLY DUCT OPENING
SIDE RETURN DUCT OPENING
OUTDOOR COILPROTECTIVE GRILLE
OUTDOOR FAN GRILLE AND COMPRESSOR ACCESS
FIELD CONTROL WIRE ENTRANCE
FLUE EXHAUSTHOOD
COMBUSTION AIRINLET HOOD
FIELD POWERWIRE ENTRANCE
LIQUID PRESSURESERVICE PORT
THREADEDPVC CONDENSATEDRAIN CONNECTION(3/4 NPT) SUCTION PRESSURE
SERVICE PORT
FURNACE/CONTROLSACCESS PANEL
FLUE EXHAUST
20 5/8
20 7/8
22 3/4
11 5/8
5
7
II. INSTALLATION2. Regular cleaning and waxing of the
cabinet with a good automobile polishwill provide some protection.
3. Use a good liquid cleaner severaltimes a year to remove matter that willnot wash off with water.
Several different types of protectivecoatings are offered in some areas. Thesecoating may provide some benefit, but theeffectiveness of such coating materialscannot be verified by the equipmentmanufacturer.The best protection is frequentcleaning, maintenance and minimalexposure to contaminants.
B. OUTSIDE INSTALLATION
THESE UNITS ARE DESIGNEDCERTIFIED FOR OUTDOORINSTALLATION ONLY. INSTALLATIONINSIDE ANY PART OF A STRUCTURECAN RESULT IN INADEQUATE UNITPERFORMANCE AS WELL AS
1. Avoid having lawn sprinkler headsspray directly on the unit cabinet.
2. In coastal areas locate the unit on theside of the building away from thewaterfront.
3. Shielding by a fence or shrubs maygive some protection.
4. Elevate the unit off its slab or baseenough to allow air circulation andavoid holding water against thebasepan.
DISCONNECT ALL POWER TO UNITBEFORE STARTING MAINTENANCE.FAILURE TO DO SO CAN CAUSEELECTRICAL SHOCK RESULTING INPERSONAL INJURY OR DEATH.REGULAR MAINTENANCE WILLREDUCE THE BUILDUP OFCONTAMINANTS AND HELP TOPROTECT THE UNIT’S FINISH.1. Frequent washing of the cabinet, fan
blade and coil with fresh water willremove most of the salt or othercontaminants that build up on the unit.
A. GENERAL1. INSTALLATION — Install this unit in
accordance with The AmericanNational Standard Z223.1-latestedition booklet entitled “National FuelGas Code,” and the requirements orcodes of the local utility or otherauthority having jurisdiction.Additional helpful publicationsavailable from the “National FireProtection Association” are: NFPA-90A - Installation of Air Conditioniongand Ventilating Systems 1985 orlatest edition. NFPA-90B - Warm AirHeating and Air ConditioningSystems 1984.These publications are availablefrom:
National Fire ProtectionAssociation, Inc.
Batterymarch ParkQuincy, MA 02269
NOTE: Remove wood shipping basebefore installing unit.2. PRE-INSTALLATION CHECK-
POINTS — Before attempting anyinstallation, carefully consider thefollowing points:Structural strength of supportingmembers
(Rooftop Installation)Clearances and provision forservicingPower supply and wiringGas supply and pipingAir duct connectionsDrain facilities and connectionsLocation for minimum noise and
vibration
LOCATION CONSIDERATIONSThe metal parts of this unit may besubject to rust or deterioration in adverseenvironmental conditions. This oxidationcould shorten the equipment’s useful life.Salt spray, fog or mist in seacoast areas,sulphur or chlorine from lawn wateringsystems, and various chemicalcontaminants from industries such aspaper mills and petroleum refineries areespecially corrosive.If the unit is to be installed in an areawhere contaminants are likely to be aproblem, give special attention to theequipment location and exposure.
! WARNING
! WARNING
FIGURE 5OUTSIDE SLAB INSTALLATION. CLOSET DISTRIBUTION SYSTEM. SLAB FLOORCONSTRUCTION
SUPPLYDUCT ATCLOSETCEILING
FILTERGRILLE
SLABFLOOR
BRANCHCIRCUITDISCONNECT
UNIONTRAP
GAS SHUT-OFF VALVE
GAS SUPPLY
SERVICE ACCESS PANELS.DO NOT BLOCK ACCESS.
POWERSUPPLYCONDUIT
THERMOSTATWIRECONDUIT
I251
IMPORTANT: PITCH UNIT TOWARD DRAINTO ALLOW FOR PROPER WATERDRAINAGE. SEE FIGURE 5.
FIGURE 5OUTSIDE SLAB INSTALLATION. CLOSET DISTRIBUTION SYSTEM. SLAB FLOORCONSTRUCTION
2. PRE-INSTALLATION CHECK-POINTS — Before attempting anyinstallation, carefully consider thefollowing points:Structural strength of supportingmembers
(Rooftop Installation)Clearances and provision forservicingPower supply and wiringGas supply and pipingAir duct connectionsDrain facilities and connectionsLocation for minimum noise and
vibration
LOCATION CONSIDERATIONSThe metal parts of this unit may besubject to rust or deterioration in adverseenvironmental conditions. This oxidationcould shorten the equipment’s useful life.Salt spray, fog or mist in seacoast areas,sulphur or chlorine from lawn wateringsystems, and various chemicalcontaminants from industries such aspaper mills and petroleum refineries areespecially corrosive.If the unit is to be installed in an areawhere contaminants are likely to be aproblem, give special attention to theequipment location and exposure.
8
PROPERTY DAMAGE. INSTALLATIONINSIDE CAN ALSO CAUSERECIRCULATION OF FLUEPRODUCTS INTO THE CONDITIONEDSPACE RESULTING IN PERSONALINJURY OR DEATH.(Typical outdoor slab installation isshown in Figure 5.)1. Select a location where external
water drainage cannot collect aroundunit.
2. Provide a slab sufficiently highenough above grade to preventsurface water from entering the unit.Where snowfall is anticipated, mountthe unit above the anticipatedmaximum snow depth for your area.The slab should be isolated from thefoundation wall.
3. Pitch the slab approximately 1/2” sothat the unit will be pitched towardthe drain. See Figure 6.
4. The location of the unit should besuch as to provide proper access forinspection and servicing as shown inFigure 12.
5. Locate unit where operating soundswill not disturb owner or neighbors.
6. Locate unit so roof runoff water doesnot pour directly on the unit. Providegutter or other shielding at roof level.Do not locate unit in an area whereexcessive snow drifting may occur oraccumulate.
7. Where snowfall is anticipated, theheight of the unit above the groundlevel must be considered. Mount unithigh enough to be above averagearea snowfall and to allowcombustion air to enter thecombustion air inlet.
C. ATTACHING EXHAUST ANDCOMBUSTION AIR INLETHOODSIMPORTANT: Do not operate this unitwithout the exhaust and combustion airinlet hood properly installed. These hoodsare shipped in a carton in the return aircompartment inside the unit and must beattached when the unit is installed. SeeFigure 6.To attach exhaust and combustion air inlethoods:
1. Remove 3 screws securing filter accesspanel and remove filter access panel.For location of filter access panel, seeFigure 4.
2. Remove both exhaust and combustionair inlet hoods from their carton, locatedinside the return air compartment.
3. Attach filter access panel.4. Attach the combustion air inlet hood and
the exhaust hood each with 4 screws asshown in Figure 7. Screws are in partsbag shipped in the burner compartment.
5. Vent the unit using the flue exhausthood, as supplied from the factory,without alteration or addition. The onlyexception is with factory approvedadditions. Consult your local utility orother authority having jurisdiction foraccepted venting techniques.
D. COVER PANELINSTALLATION/CONVERSION PROCEDURE
1. HORIZONTAL TO DOWNFLOWa. Remove screws and covers from
the supply and return bottomsections. NOTE: Rotate the supplycover 90° and remove.
b. Install gasket (supplied with partsbag) around perimeter of cover onthe insulated side. See Figure 9.
c. Secure covers to the side of the unitusing existing screws and thosesupplied in the parts bag.
2. DOWNFLOW TO HORIZONTALa. Remove screws and covers from
the outside of the supply and returnsections.
b. Install gasket (supplied with partsbag) around perimeter of cover asillustrated in Figure 8.
c. Install covers in the unit bottom withthe insulated side up. NOTE: Supplycover must be inserted through supplyopening with narrow side toward unit.Once cover is through opening, rotate90° and slip back flange of coverunder tab at the back of bottom ductopening. See Figure 11.
d. Secure supply cover to base of unitwith 2 screws, engaging prepunchedholes in raised duct opening flange.
e. Secure return covers to base of unitwith screws engaging prepunchedholes in raised duct opening flange.
FIGURE 6PITCHING UNIT TO INSURE PROPER CONDENSATE DRAINAGE.
I655
FIGURE 7COMBUSTION AIR INLET HOOD & EXHAUST HOODINSTALLATION
I250
EXHAUSTHOOD W/(4)SCREWS
COMBUSTIONAIR INLETHOOD W/(4)SCREWS
LEVEL FRONT OF UNIT
LEVEL PLANECONDENSATE DRAIN CONNECTION
1/8 BUBBLE OFF LEVEL
THIS END APPROX.1/2” HIGHER THAN FRONT
EXHAUSTHOOD W/(4)SCREWS
COMBUSTIONAIR INLETHOOD W/(4)SCREWS
9
FIGURE 10DUCT COVER INSTALLATION SIDE MOUNTING
I264
FIGURE 9COVER GASKET DETAIL FOR UNITS SHIPPED FOR SIDE DISCHARGEAPPLICATION BEING CONVERTED TO DOWNFLOW
TAPEAROUND FLANGE
SUPPLY/RETURNAIR COVER
FIGURE 8COVER GASKET DETAIL FOR UNITS SHIPPED FOR DOWNFLOWAPPLICATION BEING CONVERTED TO SIDE DISCHARGE
TAPEAROUND FLANGE
SUPPLY/RETURNAIR COVER
RETURNDUCT COVER
(ATTACH WITH 6 SCREWS)
SUPPLYDUCT COVER
(ATTACH WITH 6 SCREWS)
I654
FIGURE 7DUCT COVER INSTALLATION SIDE MOUNTING
I264
RETURNDUCT COVER
(ATTACH WITH 6 SCREWS)
SUPPLYDUCT COVER
(ATTACH WITH 6 SCREWS)
FIGURE 10DUCT COVER INSTALLATION SIDE MOUNTING
10
THIS UNIT MUST NOT BE INSTALLEDDIRECTLY ON WOOD FLOORING,CLASS A, CLASS B OR CLASS C ROOFCOVERING MATERIALS, OR ANYOTHER COMBUSTIBLE STRUCTUREEXCEPT AS SPECIFIED IN FIGURE 13.FAILURE TO ADHERE TO THIS WARINGCAN CAUSE A FIRE OR EXPLOSIONRESULTING IN PROPERTY DAMAGE,PERSONAL INJURY OR DEATH.
FIGURE 11DUCT COVER INSTALLATION BASE PAN MOUNTING
I265
BASE PAN
SUPPLY DUCTCOVER *(INSULATIONSIDE UP),ATTACH WITHTWO SCREWS.
RETURNDUCTCOVER(INSULATIONSIDE UP,ATTACHWITH 4SCREWS)
SUPPLY DUCTCOVER
*ROTATE SUPPLY COVER 90° AFTER IT IS INSERTEDTHROUGH OPENING. SLIP FLANGE OF COVERUNDER LANCE AT BACK OF BOTTOM SUPPLY DUCTOPENING. SEE DETAIL AT LEFT. THEN SECURECOVER BY INSTALLING 2 SCREWS USING HOLENEAREST THE OUTSIDE OF UNIT.
LANCE AT BACK OF BOTTOMSUPPLY DUCT OPENING
E. CLEARANCESThe following minimum clearances mustbe observed for proper unit performanceand serviceability. See Figure 12.1. Provide 48” minimum clearance at
front of the unit. Provide 24”minimum clearance on right side ofunit. If economizer is used, a 24”minimum clearance is required onleft side of unit. (See Figure 12.) If noeconomizer is required, then a 12”clearance is required on left side ofunit.
2. Provide 60” minimum clearancebetween top of unit and maximum 3foot overhang.
3. Unit is design certified for 2”minimum clearance between supplyduct and a combustible structure forthe first 3 feet of duct. 0” clearance isallowed after 3 feet.
FIGURE 12CLEARANCES
I252
60” MINIMUMOVERHEADCLEARANCE
12” MINIMUMCLEARANCEWITHOUTECONOMIZER24” MINIMUMCLEARANCEWITHECONOMIZER ORINTERNALFILTER KIT
NON-COMBUSTIBLESTRUCTURE ONLY.SEE FIG. 4 FOREXCEPTION
48” MINIMUMCLEARANCE TOSERVICE CONTROLS
24” MINIMUM CLEARANCETO SERVICE BLOWER &
EVAPORATOR
2” CLEARANCEAROUND SUPPLY
PLENUM TOCOMBUSTIBLE
STRUCTURE, FORFIRST 3 FEET.
0” AFTER 3 FEET.
2” MINIMUMCLEARANCETO WALL
! WARNING
FIGURE 8DUCT COVER INSTALLATION BASE PAN MOUNTING
I265
BASE PAN
SUPPLY DUCTCOVER *(INSULATIONSIDE UP),ATTACH WITHTWO SCREWS.
RETURNDUCTCOVER(INSULATIONSIDE UP,ATTACHWITH 4SCREWS)
SUPPLY DUCTCOVER
*ROTATE SUPPLY COVER 90° AFTER IT IS INSERTEDTHROUGH OPENING. SLIP FLANGE OF COVERUNDER LANCE AT BACK OF BOTTOM SUPPLY DUCTOPENING. SEE DETAIL AT LEFT. THEN SECURECOVER BY INSTALLING 2 SCREWS USING HOLENEAREST THE OUTSIDE OF UNIT.
LANCE AT BACK OF BOTTOMSUPPLY DUCT OPENING
FIGURE 11DUCT COVER INSTALLATION BASE PAN MOUNTING
FIGURE 12CLEARANCES
11
G. ROOFTOP INSTALLATION1. Before locating the unit on the roof,
make sure that the roof structure isadequate to support the weightinvolved. (See electrical and physicaltables in this book for weight of unit.)THIS IS VERY IMPORTANT ANDTHE INSTALLER’SRESPONSIBILITY.
2. For rigging and roofcurb details, seeFigures 17, 18 and 19.
3. The location of the unit on the roofshould be such as to provide properaccess for inspection and servicing.
IMPORTANT: If unit will not be put intoservice immediately, block off supply andreturn air openings to prevent excessivecondensation.
H. DUCTINGThe installing contractor should fabricateductwork in accordance with local codes.Use industry manuals as a guide whensizing and designing the duct system.Contact Air Conditioning Contractors ofAmerica, 1513 16th St. N.W.,Washington, D.C. 20036.
DO NOT, UNDER ANYCIRCUMSTANCES, CONNECTRETURN DUCTWORK TO ANY OTHERHEAT PRODUCING DEVICE SUCH ASFIREPLACE INSERT, STOVE, ETC.UNAUTHORIZED USE OF SUCHDEVICES MAY RESULT IN FIRE,CARBON MONOXIDE POISONING,EXPLOSION, PERSONAL INJURY ORPROPERTY DAMAGE.
FIGURE 13EXCEPTION TO NON-COMBUSTIBLE FLOORING REQUIREMENT
I458
BOTH ENDSMUST BEOPEN FORDOWNFLOWOR SIDEFLOWDUCTWORKTO PROVIDEVENTILATION
COMBUSTIBLESTRUCTURE
1” MIN.
NOMINAL4 x 4 TIMBER(SIDES ONLY)
SIDEFLOWSUPPLYPLENUM
CONNECTION
SUPPLYPLENUM
(DOWNFLOW)RETURN PLENUM
(DOWNFLOW)
SIDEFLOWRETURN PLENUM
CONNECTION
! WARNING
3-1/2” MIN.
FIGURE 14FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING DISTRIBUTING SYSTEM. MOUNTED ONROOFCURB. PITCH UNIT TOWARD DRAIN. SEE FIGURE 5.
I256
SERVICE ACCESSPANELS. DO NOTBLOCK ACCESS.
BRANCHCIRCUITDISCONNECT
GAS SUPPLY
TRAPGAS SHUT-OFF VALVE
UNION
THERMOSTATWIRE CONDUITCONDENSATE
INTOROOFDRAIN
IF REQ’DBY LOCAL
CODES.
POWERSUPPLYCONDUIT
I257
SERVICE ACCESSPANELS. DO NOTBLOCK ACCESS.
SUPPLY PLENUM
GASSHUT-OFFVALVE
GAS SUPPLY
TRAP
UNION
THERMOSTATWIRE CONDUIT
BRANCH CIRCUITDISCONNECT
CONDENSATEDRAIN INTO
ROOFDRAIN IFREQ’D BY LOCAL
CODES
POWER SUPPLYCONDUIT
FIGURE 15PITCHED ROOFTOP INSTALLATION, ON ANGLE-IRON STAND, SIDE FLOW DUCTWORK,ATTIC OR DROP CEILINGDISTRIBUTING SYSTEM.PITCH UNIT TOWARD DRAIN.SEE FIGURE 5.
FIGURE 15PITCHED ROOFTOP INSTALLATION, ON ANGLE-IRON STAND, SIDE FLOW DUCTWORK,ATTIC OR DROP CEILINGDISTRIBUTING SYSTEM.PITCH UNIT TOWARD DRAIN.
12
Place the unit as close to the conditionedspace as possible allowing clearancesas indicated. Run ducts as directly aspossible to supply and return outlets.Use of non-flammable weatherproofflexible connectors on both supply andreturn connections at unit to reducenoise transmission is recommended.On ductwork exposed to outsidetemperature and humidity, use aminimum of 2” of insulation and a vaporbarrier. Distribution system in attic, furredspace or crawl space should beinsulated with at least 2” of insulation. 1/2”to 1” thick insulation is usually sufficientfor ductwork inside the air conditionedspace.Provide balancing dampers for eachbranch duct in the supply system.Properly support ductwork from thestructure.IMPORTANT: In the event that the returnair ducts must be run through an“unconfined” space containing other fuelburning equipment, it is imperative thatthe user/homeowner must be informedagainst future changes in constructionwhich might change this to a “confinedspace.” Also, caution theuser/homeowner against any futureinstallation of additional equipment (suchas power ventilators, clothes dryers, etc.,within the existing unconfined and/orconfined space which might create anegative pressure within the vicinity ofother solid, liquid, or gas fueledappliances.
FIGURE 17LIFTING DETAIL
! WARNINGRETURN AIR
NEVER ALLOW PRODUCTS OFCOMBUSTION OR THE FLUEPRODUCTS TO ENTER THE RETURNAIR DUCTWORK, OR THECIRCULATING AIR SUPPLY. ALLRETURN DUCTWORK MUST BEADEQUATELY SEALED AND SECUREDTO THE FURNACE WITH SHEET
I253
RIGGINGNOT PROVIDED
LIFT BRACKET(4 REQ’D
FIGURE 16PITCHED ROOFTOP INSTALLATION, ON ROOFJACK, DOWNFLOW DUCTWORK, ATTIC ORDROP CEILING DISTRIBUTING SYSTEM. PITCH UNIT TOWARD DRAIN. SEE FIGURE 5.
I257B
SERVICE ACCESS PANELS.DO NOT BLOCK ACCESS.
SUPPLYPLENUM
GAS SUPPLY
TRAP
GAS SHUT-OFF VALVE
UNION
THERMOSTATWIRE CONDUIT
BRANCH CIRCUITDISCONNECT
CONDENSATEDRAIN INTO
ROOFDRAIN IFREQ’D BY LOCAL
CODES.
POWER SUPPLYCONDUIT
METAL SCREWS, AND JOINTS TAPED.ALL OTHER DUCT JOINTS MUST BESECURED WITH APPROVEDCONNECTIONS AND SEALEDAIRTIGHT.FAILURE TO PREVENT PRODUCTS OFCOMBUSTION FROM BEINGCIRCULATED INTO THE LIVING SPACECAN CREATE POTENTIALLYHAZARDOUS CONDITIONS,INCLUDING CARBON MONOXIDEPOISONING THAT COULD RESULT INPERSONAL INJURY OR DEATH.
I. FILTERSThe installer must install field suppliedfilters in the return air duct. A field installedfilter grille is recommended for easy andconvenient access to the filters for periodicinspection and cleaning. Filters must haveadequate face area for the rated airquantity of the unit. See air delivery tablesfor recommended filter size. A fieldinstalled internal filter kit RXRY-B01 isavailable.
FIGURE 17LIFTING DETAIL.
ALTERNATE RIGGING HOLES(4 SIDES)
13
FIGURE 20DUCTWORK COVER INSTALLATION DETAIL
FIGURE 21RESIDENTIAL ROOFTOP DUCTWORK INSTALLATION DETAIL
I342
I610A
I610B
RETURN PLENUM161/2MAX.
201/2 MAX.
163/8 MAX.
INSULATIONPANELS
NAILINGSTRIP
CAULK ALLJOINTSWATERTIGHT
SUPPLYPLENUM
DUCTFLANGE(NOT TOEXCEED 1()
ROOFCURB
FIGURE 18ROOFCURB
I255
**BY CONTRACTOR**FOR INSTALLATION OF DUCT AS SHOWN, USE RECOMMENDED
DUCT SIZES FROM ROOFCURB INSTALLATION INSTRUCTIONS. FORDUCT FLANGE ATTACHMENT TO UNIT, SEE UNIT INSTALLATIONINSTRUCTIONS (FIGURE 1) FOR SIZE OF DUCT OPENINGS.
ROOFTOP UNIT
TIE DOWN SCREW *
ROOFCURB
ROOF FLASHING *
ROOFING *CANT STRIP *
ROOF DECK *
GASKET
NAILING STRIP
INSULATION *
INSULATION *
** DUCT *
RECOMMENDED SHEET METALDUCTWORK COVER CAULKED WATERTIGHT
CAULK ALL JOINTSWATERTIGHT
90° FLANGE ON DUCT
SUPPLY AIR DUCT
ATTACH DUCTS TO UNITWITH SCREWS AS SHOWN
RETURN AIR DUCT
INSULATED DUCTWORKINSIDE DUCTWORK COVER
FIGURE 19ROOFCURB
FIGURE 21RESIDENTIAL ROOFTOP DUCTWORK INSTALLATION DETAIL.
FIGURE 20DUCTWORK COVER INSTALLATION DETAIL
14
TO CHECK FOR GAS LEAKS, USE ASOAP AND WATER SOLUTION OROTHER APPROVED METHOD. DO NOTUSE AN OPEN FLAME.
DO NOT USE AN OPEN FLAME TOCHECK FOR LEAKS. THE USE OF ANOPEN FLAME CAN RESULT IN FIRE,EXPLOSION, PROPERTY DAMAGE,PERSONAL INJURY OR DEATH.IMPORTANT: Check the rating plate tomake certain the appliance is equipped toburn the type of gas supplied. Care shouldbe taken after installation of thisequipment that the gas control valve notbe subjected to high gas supply linepressure.In making gas connections, avoid strainsas they may cause noise and damage thecontrols. A backup wrench is required tobe used on the valve to avoid damage.
III. GAS SUPPLY, CONDENSATE DRAIN AND PIPINGA. GAS CONNECTIONIMPORTANT: Connect this unit only togas supplied by a commercial utility.1. Install gas piping in accordance with
local codes and regulations of thelocal utility company. In the absenceof local codes, the installation mustconform to the specifications of theNational Fuel Gas Code, ANSIZ223.1 - latest edition.NOTE: The use of flexible gasconnectors is not permitted.NOTE: The Commonwealth ofMassachusetts requires the gasshut-off valve to be a T-handle gascock.
2. Connect the gas line to the gas pipeinlet opening provided into the 1/2”inlet valve. See Figure 5 for typicalpiping.
3. Size the gas line to the furnaceadequate enough to prevent unduepressure drop and never less than1/2(.
4. Install a drip leg or sediment trap inthe gas supply line as close to theunit as possible.
5. Install an outside ground joint unionto connect the gas supply to thecontrol assembly at the burner tray.
6. Gas valves have been factoryinstalled. Install a manual gas valvewhere local codes specify a shut-offvalve outside the unit casing. (SeeFigure 22.)
7. Make sure piping is tight. A pipecompound resistant to the actionof liquefied petroleum gases mustbe used at all threaded pipeconnections.
8. IMPORTANT: any additions,changes or conversions required forthe furnace to satisfactorily meet theapplication should be made by aqualified installer, service agency orthe gas supplier, using factory-specified or approved parts. In thecommonwealth of Massachusetts,installation must be performed by alicensed plumber or gas fitter forappropriate fuel.
IMPORTANT: Disconnect the furnaceand its individual shutoff valve from thegas supply piping during any pressuretesting of that system at test pressuresin excess of 1/2 psig or isolate thesystem from the gas supply pipingsystem by closing its individual manualshutoff valve during any pressure testingof this gas supply system at pressuresequal to or less than 1/2 PSIG.
! WARNING
FIGURE 22SUGGESTED GAS PIPING
The capacities of gas pipe of differentdiameters and lengths in cu. ft. per hr. withpressure drop of 0.3 in. and specificgravity of 0.60 (natural gas) are shown inTable 2.
After determining the pipe length, selectthe pipe size which will provide theminimum cubic feet per hour required forthe gas input rating of the furnace. Byformula:
Gas Input of Furnace(BTU/HR)
Cu. Ft. Per Hr. Required =Heating Value of Gas(BTU/FT3)
The gas input of the furnace is marked onthe furnace rating plate. The heating valueof the gas (BTU/FT3) may be determinedby consulting the local natural gas utility orthe L.P. gas supplier.
NominalIron Pipe
Size,Inches
Equivalent Length of Pipe, Feet
10 20 30 40 50 60 70 801/2 132 92 73 63 56 50 46 433/4 278 190 152 130 115 105 96 901 520 350 285 245 215 195 180 170
11/4 1,050 730 590 500 440 400 370 35011/2 1,600 1,100 890 760 670 610 560 530
TABLE 2GAS PIPE CAPACITY TABLE (CU. FT./HR.)
FROM GASMETER
*Factory supplied grommet must be utilized.
MANUAL GASSHUT-OFFVALVE
UNIT GAS SUPPLYCONNECTION *
ROOF OR GROUND LEVEL INSTALLATION
15
B. LP CONVERSION
THIS UNIT IS EQUIPPED AT THEFACTORY FOR USE ON NATURALGAS ONLY. CONVERSION TO LP GASREQUIRES A SPECIAL KIT SUPPLIEDBY THE DISTRIBUTOR ORMANUFACTURER. MAILINGADDRESSES ARE LISTED ON THEFURNACE RATING PLATE, PARTSLIST AND WARRANTY. FAILURE TOUSE THE PROPER CONVERSION KITCAN CAUSE FIRE, CARBONMONOXIDE POISONING, EXPLOSION,PERSONAL INJURY, PROPERTYDAMAGE OR DEATH.Convert the valve to use liquefiedpetroleum (LP) gas by replacing thepressure regulator spring with theconversion kit spring. This LP kit springallows the regulator to maintain theproper manifold pressure for LP gas.The correct burner LP orifices areincluded in the kit. See Figure 23.NOTE: Order the correct LP conversionkit from the furnace manufacturer. SeeConversion Kit Index shipped withunit for proper LP kit number.Furnace conversion to LP gas mustbe performed by a qualifiedtechnician.
! WARNING
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleumgases (at 11 inches water column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
TABLE 3LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
NominalIron PipeSize, Inches 10 20 30 40 50 60 70 80 90 100 125 150
275 189 152 129 114 103 96 89 83 78 69 63
567 393 315 267 237 217 196 182 173 162 146 132
1,071 732 590 504 448 409 378 346 322 307 275 252
2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511
3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787
6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496
1/2
3/4
1
1-1/4
1-1/2
2
Length of Pipe, Feet
Example (LP): Input BTU requirement of unit, 150,000
Equivalent length of pipe, 60 ft. = 3/4” IPS required.
NOx MODELSWhen converting units equipped withNOx inserts to LP gas, the stainlesssteel mesh inserts in the entrance of thetubular exchangers are not required tomeet SCAQMD NOx emission levels.Carefully remove these inserts beforefiring this furnace on LP gas. Thisfurnace is not designed to operate on LPgas with the NOx inserts in place.
Step by step instructions on removing theNOx inserts and retaining rod are includedin the Conversion Kit InstallationInstructions.
C. ADJUSTING OR CHECKINGFURNACE INPUT
– Natural Gas Line Pressure 5” - 10.5”W.C.– LP Gas Line Pressure 11” - 13” W.C.– Natural Gas Manifold Pressure 3.5” W.C– LP Gas Manifold Pressure - 10” W.C.Supply and manifold pressure taps arelocated on the gas valve body 1/8” N.P.T.).Use properly calibrated manometer gaugefor accurate gas pressure readings.Only small variations in the gas flow shouldbe made by means of the pressureregulator adjustment. Furnaces functioningon LP gas must be set by means of thetank or branch supply regulators. Thefurnace manifold pressure should be set at10” W.C. at the gas control valve.
To adjust the pressure regulator, removethe regulator cap and turn the adjustmentscrew clockwise to increase pressure orcounterclockwise to decrease pressure.Then replace the regulator capsecurely.Any necessary major changes in the gasflow rate should be made by changing thesize of the burner orifices. To changeorifice spuds, shut off the manual maingas valve and remove the gas manifold.For elevations up to 2,000 feet, ratingplate input ratings apply. For highaltitudes (elevations over 2,000 ft.), seeconversion kit index 92-21519-XX forderating and orifice spud sizes.Check of input is important to preventover-firing of the furnace beyond itsdesign-rated input. NEVER SET INPUTABOVE THAT SHOWN ON THE RATINGPLATE. Use the following table orformula to determine input rate.
FIGURE 23
16
ONE 1 21 1 30 1 34 1 39 3 4540,000 TEN 13 30 15 0 15 36 16 30 37 30ONE 0 54 1 0 1 3 1 6 2 3060,000 TEN 9 0 10 0 10 24 11 0 25 0ONE 0 41 0 45 0 47 0 50 1 5380,000 TEN 6 45 7 30 7 48 8 15 18 45ONE 0 33 0 36 0 38 0 40 1 30100,000 TEN 5 24 6 0 6 15 6 36 15 0
Heating Value of Gas(BTU/Cu. Ft.) x 3600
Cu. Ft. Per Hr. Required =Time in Seconds(for 1 Cu. Ft.) of Gas
Start the furnace and measure the timerequired to burn one cubic foot of gas.Prior to checking the furnace input, makecertain that all other gas appliances areshut off, with the exception of pilotburners. Time the meter with only thefurnace in operation.IMPORTANT NOTE FOR ALTITUDESABOVE 2,000 FEET (610 METERS): Themain burner orifices in your furnace andin these kits are sized for the nameplateinput and intended for installations atelevations up to 2,000 feet in the USA orCanada, or for elevations of 2,000 - 4,500feet (610 -1,373 meters) in Canada if theunit has been derated at the factory. For
METER TIME IN MINUTES AND SECONDS FOR NORMALINPUT RATING OF FURNACES EQUIPPED FOR NATURAL
OR LP GAS
INPUTBTU/HR
METERSIZE
CU. FT.
HEATING VALUE OF GAS BTU PER CU. FT.900 1000 1040 1100 2500
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
TABLE 4
elevations above 2,000 feet (610meters) IN THE USA ONLY (see ANSI-Z223.1), the burner orifices must besized to reduce the input 4% for each1,000 feet (305 meters) above sea level.NOTICE: DERATING OF THEHEATING INPUT FOR HIGH ALTITUDEIN THE FIELD IS UNLAWFUL INCANADA (REFER TO CAN/CGA 2.17).UNITS INSTALLED IN ALTITUDESGREATERS THAN 2,000 FEET (610METERS) MUST BE SHIPPED FROMTHE FACTORY OR FROM A FACTORYAUTHORIZED CONVERSION STATIONWITH THE HEATING INPUT DERATEDBY 10% SO AS TO OPERATEPROPERLY IN ALTITUDES FROM2,000 - 4,500 FEET (610 - 1,373METERS).
D. CONDENSATE DRAINThe evaporator coil condensate drain endswith an threaded 3/4” nominal PVC stub. Atrap is built in for proper condensatedrainage and to prevent debris from beingdrawn into the unit. Do not connect thedrain to a closed sewer line. Connection toa vented sewer line is allowed. It isrecommended that a PVC cement not beused so that the drain line can be easilycleaned in the future.IMPORTANT: DO NOT INSTALL ANEXTERNAL TRAP. DOING SO CANCAUSE IMPROPER DRAINAGE OF THECONDENSATE AND RESULT INFLOODING WITHIN THE UNIT.
17
A. POWER SUPPLY
TURN OFF THE MAIN ELECTRICALPOWER AT THE BRANCH CIRCUITDISCONNECT CLOSEST TO THE UNITBEFORE ATTEMPTING ANY WIRING.FAILURE TO DO SO CAN CAUSEELECTRICAL SHOCK RESULTING INPERSONAL INJURY OR DEATH.1. All wiring should be made in
accordance with the NationalElectrical Code. Consult the localpower company to determine theavailability of sufficient power tooperate the unit. Check the voltageat power supply to make sure itcorresponds to the unit’s RATEDVOLTAGE REQUIREMENT. Install abranch circuit disconnect near therooftop, in accordance with theN.E.C. or local codes.
2. It is important that proper electricalpower is available at the unit.Voltage should not vary more than10% from that stamped on the unitnameplate. On three phase units,phases must be balanced within 3%.
3. For branch circuit wiring (main powersupply to unit disconnect), theminimum wire size for the length ofrun can be determined from Table 5using the circuit ampacity found on theunit rating plate. Use the smallest wiresize allowable in Table 5 from the unitdisconnect to unit. The disconnectmust be in sight and readilyaccessible of the unit.
NOTES:
IV. WIRING
! WARNING
1. Wire size based on 60°C rated wireinsulation and 30°C Ambient Temp.(86°F).
2. For more than 3 conductors in araceway or cable, see the N.E.C. forderating the ampacity of eachconductor.When installed, the unit must beelectrically grounded in accordancewith local codes or, in the absence oflocal codes, with the NationalElectrical Code, ANSI/NFPA 70, if anexternal electrical source is utilized.
IMPORTANT: THIS UNIT IS AP-PROVED FOR USE WITH COPPERCONDUCTORS ONLY CONNECTEDTO UNIT CONTACTOR.WARRANTY MAY BE JEOPARDIZEDIF ALUMINUM WIRE IS CONNECTEDTO UNIT CONTACTOR.Special instructions apply for powerwiring with aluminum conductors:Warranty is void if connections arenot made per instructions.
Attach a length (6” or more) ofrecommended size copper wire to the
200 6 4 4 4 3 3 2 2150 8 6 6 4 4 4 3 3100 10 8 8 6 6 6 4 450 14 12 10 10 8 8 6 6
15 20 25 30 35 40 45 50
TABLE 5BRANCH CIRCUIT COPPER WIRE SIZE(BASED ON 1% VOLTAGE DROP)*
unit contactor terminals L1 and L3 forsingle phase, L1, L2 and L3 for threephase.Select the equivalent aluminum wire sizefrom the tabulation below:Splice copper wire pigtails to aluminumwire with U.L. recognized connectors forcopper-aluminum splices. Please exercisethe following instructions very carefully toobtain a positive and lasting connection:1. Strip insulation from aluminum
conductor.2. Coat the stripped end of the aluminum
wire with the recommended inhibitor,and wire brush the aluminum surfacethrough inhibitor. INHIBITORS:Brundy-Pentex “A”; Alcoa-No. 2EJC; T& B-KPOR Shield.
3. Clean and recoat aluminum conductorwith inhibitor.
4. Make the splice using the above listedwire nuts or split bolt connectors.
5. Coat the entire connection withinhibitor and wrap with electricalinsulating tape.
AWG Copper AWG Aluminum Connector Type and SizeWire Size Wire Size (or equivalent)
#12 #10 T & B Wire Nut PT2#10 # 8 T & B Wire Nut PT3# 8 # 6 Sherman Split Bolt TSP6# 6 # 4 Sherman Split Bolt TSP4# 4 # 2 Sherman Split Bolt TSP2
TABLE 6
SUPPLY WIRELENGTH-FEET
*Taken from National Electric Code
BRANCH CIRCUIT AMPACITY
18
B. HOOK-UPTo wire unit, refer to the following hook-up diagram.Refer to Figure 3 for location of wiringentrances.Wiring to be done in the field betweenthe unit and devices not attached to theunit, or between separate devices whichare field installed and located, shallconform with the temperature limitationfor Type T wire [63°F rise (35°C)] wheninstalled in accordance with themanufacturer’s instructions.
C. INTERNAL WIRINGIMPORTANT: Some single phase unitsare equipped with a single polecontactor. Caution must be exercisedwhen servicing as only one leg of thepower supply is broken with thecontactor.A diagram of the internal wiring of thisunit is located under the electrical boxcover. If any of the original wire assupplied with the appliance must bereplaced, the wire gauge and insulationmust be same as original wiring.Transformer is factory wired for 230 voltson 208/230 volt models and must bechanged for 208 volt applications. Seeunit wiring diagram for 208 volt wiring.
D. THERMOSTATThe room thermostat must be compatiblewith the spark ignition control on the unit.Generally, all thermostats that are not ofthe “current robbing” type are compatiblewith the integrated furnace control. Thelow voltage wiring should be sized asshown in Table 7.Install the room thermostat in accordancewith the instruction sheet packed in thebox with the thermostat. Run thethermostat lead wires inside the blowercompartment and connect to low voltageterminals as shown on the wiring diagram.
FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS
SOLID COPPER WIRE - AWG.3.0 16 14 12 10 10 102.5 16 14 12 12 12 102.0 18 16 14 12 12 10
50 100 150 200 250 300Length of Run – Feet (1)Th
erm
osta
t Loa
d - A
mps
TABLE 7
(1) The total wire length is the distance from the furnace to thethermostat and back to the furnace.NOTE: DO NOT USE CONTROL WIRING SMALLER THAN NO. 18AWG.
Never install the thermostat on an outsidewall or where it will be influenced by drafts,concealed hot or cold water pipes orducts, lighting fixtures, radiation fromfireplace, sun rays, lamps, televisions,radios or air streams from registers. Referto instructions packed with the thermostatfor “heater” selection or adjustment.The following is a list of recommendedthermostats to be used with and withoutan economizer:
*
*L2 connection 3Phase only
SINGLE STAGE COOL W/OECONOMIZER
MAPLE CHASE - MODEL #0970HONEYWELL - MODEL #T8602CMAPLE CHASE - MODEL #0960WHITE RODGERS - MODEL #1F91-59ROBERTSHAW - MODEL #CM64A-USAJ
TWO STAGE COOL W/ECONOMIZER
HONEYWELL - MODEL #T7300-A1005HONEYWELL - MODEL #T874D-1959
19
V. FURNACE SECTION CONTROLS AND IGNITION SYSTEM• The induced draft blower and main
burner will shut off when the thermostat
is satisfied.
• The circulating air blower will start and
run on the heating speed if the
thermostat fan switch is in the “ON”
position.
The integrated furnace control is
equipped with diagnostic LED. The LED
is lit continuously when there is power to
the control, with or without a call for heat.
If the LED is not lit, there is either no
power to the control or there is an
internal component failure within the
control, and the control should be
replaced.
If the control detects the following
failures, the LED will flash on for
approximately 1/4 second, then off for 3/4
second for designated failure detections.
1 Flash: Failed to detect flame within the
three tries for ignition.
2 Flash: Pressure switch or induced draft
blower problem detected.
3 Flash: High limit or auxiliary limit open.
4 Flash: Flame sensed and gas valve not
energized or flame sensed with
no “W” signal.
5 Flash: Overtemperature switch open.
OPERATING INSTRUCTIONSThis appliance is equipped with a direct
spark intermittent ignition device. This
device lights the main burners each time
the room thermostat (closes) calls for
heat. See operating instructions on the
back of the furnace/controls access
panel.
DO NOT ATTEMPT TO MANUALLYLIGHT THIS FURNACE WITH A MATCHOR ANY OPEN FLAME. ATTEMPTINGTO DO SO CAN CAUSE ANEXPLOSION OR FIRE RESULTING INPROPERTY DAMAGE, PERSONALINJURY OR DEATH.
TO START THE FURNACE
1. Set the thermostat to its lowest
setting.
2. Turn off all electric power to the
appliance.
3. This appliance does not have a pilot. It
is equipped with an ignition device
which automatically lights the burner.
Do not try to light the burner by hand.
4. Remove control door.
5. Depress the control knob and move to
the “OFF” position. Turn the knob by
hand only, do not use any kind of tool.
6. Wait five (5) minutes to clear out any
gas. Then smell for gas, including
near the floor. If you smell gas, STOP!
Follow B in the safety information on
the Operating Instructions located on
the back of the controls/access panel.
step.
7. Move the gas control knob from “OFF”
position to “ON” position. Operate this
appliance with the gas control knob in
the “ON” position only. Do not use the
gas control knob as a means for
throttling the burner input rate.
8. Replace the control door.
9. Turn on all electric power to the
appliance.
10. Set the thermostat to the desired
setting.
11. If the appliance will not operate, follow
the instructions below on how to shut
down the furnace.
THE SPARK IGNITOR AND IGNITIONLEAD FROM THE IGNITION CONTROLARE HIGH VOLTAGE. KEEP HANDS ORTOOLS AWAY TO PREVENTELECTRICAL SHOCK. SHUT OFFELECTRICAL POWER BEFORESERVICING ANY OF THE CONTROLS.FAILURE TO ADHERE TO THISWARNING CAN RESULT IN PERSONALINJURY OR DEATH. The initial start-up
on a new installation may require the
control system to be energized for some
time until any air has bled through the
system and fuel gas is available at the
burners.
NORMAL FURNACEOPERATING SEQUENCEThis unit is equipped with an integrated
direct spark ignition control.
1. The thermostat calls for heat.
2. The control board will run a self
check to verify that the limit control
and manual reset overtemperature
control are closed and that the
pressure switch is open. If so, the
induced draft blower (inducer)
begins a prepurge cycle.
3. The air proving negative pressure
switch closes.
4. 15 seconds after the pressureswitch closes, the gas valve opens
and the spark is initiated for a 7
second trial for ignition.
5. Burners ignite and flame sensor
proves all burners have lit.
6. The circulating air blower is
energized after 30 seconds.
7. The control board enters a normal
operation loop in which all safety
controls are monitored continuously.
8. Thermostat is satisfied and opens.
9. The gas valve is de-energized and
closes, shutting down the burner
flame.
10. The control board will de-energize
the inducer after a five second post
purge.
11. The circulating air blower is de-
energized after 90 seconds.
• The integrated control board has a
three try ignition system.
• After a total of three trials for ignition
without sensing main burner flame, the
system goes into a 100% lockout
mode.
• After one hour, the ignition control
repeats the prepurge and ignition
cycles for 3 tries and then goes into
100% lockout mode again.
• It continues this sequence of cycles
and lockout each hour until igniton is
successful or power is interrupted.
• During the lockout mode, neither the
spark ignition control or gas valve will
be energized until the system is reset
by turning the thermostat to the “OFF”
position or interrupting the electrical
power to the unit for 3 seconds or
longer.
! WARNING! WARNING
If you don’t smell gas, go to the next
1. STOP! Read the safety information onthe Operating Instructions Labellocated on this appliance.
IF YOU DO NOT FOLLOW THESEINSTRUCTIONS EXACTLY, A FIRE OREXPLOSION MAY RESULT CAUSINGPROPERTY DAMAGE, PERSONALINJURY OR LOSS OF LIFE.
2. Set the thermostat to its lowestsetting.
3. Turn off all electric power to theappliance.
4. This appliance does not have a pilot.It is equipped with an ignition devicewhich automatically lights the burner.Do NOT try to light the burner byhand.
5. Remove control door/access panel.
7. Wait five (5) minutes to clear out anygas. Then smell for gas, includingnear the floor. If you smell gas, STOP!Follow ‘B’ in the safety information onthe Operating Instruction Labellocated on this appliance. If you don’tsmell gas, go to the next step.
8. Move the switch from “OFF” positionto “ON” position.
9. Replace the control door.
10. Turn on all electric power to theappliance.
11. Set the thermostat to the desiredsetting.
12. If the appliance will not operate, followthe instructions below on how to shutdown the furnace.
THE SPARK IGNITOR AND IGNITIONLEAD FROM THE IGNITION CONTROLARE HIGH VOLTAGE. KEEP HANDS ORTOOLS AWAY TO PREVENTELECTRICAL SHOCK. SHUT OFFELECTRICAL POWER BEFORESERVICING ANY OF THE CONTROLS.FAILURE TO ADHERE TO THISWARNING CAN RESULT IN PERSONALINJURY OR DEATH. The initial start-upon a new installation may require thecontrol system to be energized for sometime until any air has bled through thesystem and fuel gas is available at theburners.
!
!
WARNING
WARNING
6. Move switch to the “OFF” position.
1. STOP! Read the safety information onthe Operating Instructions Labellocated on this appliance.
IF YOU DO NOT FOLLOW THESEINSTRUCTIONS EXACTLY, A FIRE OREXPLOSION MAY RESULT CAUSINGPROPERTY DAMAGE, PERSONALINJURY OR LOSS OF LIFE.
2. Set the thermostat to its lowestsetting.
3. Turn off all electric power to theappliance.
4. This appliance does not have a pilot.It is equipped with an ignition devicewhich automatically lights the burner.Do NOT try to light the burner byhand.
5. Remove control door/access panel.
6. Move switch to the “OFF” position.
7. Wait five (5) minutes to clear out anygas. Then smell for gas, includingnear the floor. If you smell gas, STOP!If you don’t smell gas, go to the nextstep.
• Do not try to light any appliance.
• Do not touch any electric switch; donot use any phone in your building.
• Immediately call your gas supplierfrom a neighbor’s phone. Follow thegas supplier’s instructions.
• If you cannot reach your gassupplier, call the fire department.
8. Move the switch from “OFF” positionto “ON” position.
9. Replace the control door.
10. Turn on all electric power to theappliance.
11. Set the thermostat to the desiredsetting.
12. If the appliance will not operate, followthe instructions below on how to shutdown the furnace.
THE SPARK IGNITOR AND IGNITIONLEAD FROM THE IGNITION CONTROLARE HIGH VOLTAGE. KEEP HANDS ORTOOLS AWAY TO PREVENTELECTRICAL SHOCK. SHUT OFFELECTRICAL POWER BEFORESERVICING ANY OF THE CONTROLS.FAILURE TO ADHERE TO THISWARNING CAN RESULT IN PERSONALINJURY OR DEATH. The initial start-upon a new installation may require thecontrol system to be energized for sometime until any air has bled through thesystem and fuel gas is available at theburners.
WARNING!
WARNING!
1. STOP! Read the safety information onthe Operating Instructions Labellocated on this appliance.
IF YOU DO NOT FOLLOW THESEINSTRUCTIONS EXACTLY, A FIRE OREXPLOSION MAY RESULT CAUSINGPROPERTY DAMAGE, PERSONALINJURY OR LOSS OF LIFE.
2. Set the thermostat to its lowestsetting.
3. Turn off all electric power to theappliance.
4. This appliance does not have a pilot.It is equipped with an ignition devicewhich automatically lights the burner.Do NOT try to light the burner byhand.
5. Remove control door/access panel.
6. Move switch to the “OFF” position.
7. Wait five (5) minutes to clear out anygas. Then smell for gas, includingnear the floor.
• Do not try to light any appliance.
• Do not touch any electric switch; donot use any phone in your building.
• Immediately call your gas supplierfrom a neighbor’s phone. Follow thegas supplier’s instructions.
• If you cannot reach your gassupplier, call the fire department.
If you smell gas, STOP! If you don’tsmell gas, go to the next step.
8. Move the switch from “OFF” positionto “ON” position.
9. Replace the control door.
10. Turn on all electric power to theappliance.
11. Set the thermostat to the desiredsetting.
12. If the appliance will not operate, followthe instructions below on how to shutdown the furnace.
THE SPARK IGNITOR AND IGNITIONLEAD FROM THE IGNITION CONTROLARE HIGH VOLTAGE. KEEP HANDS ORTOOLS AWAY TO PREVENTELECTRICAL SHOCK. SHUT OFFELECTRICAL POWER BEFORESERVICING ANY OF THE CONTROLS.FAILURE TO ADHERE TO THISWARNING CAN RESULT IN PERSONALINJURY OR DEATH. The initial start-upon a new installation may require thecontrol system to be energized for sometime until any air has bled through thesystem and fuel gas is available at theburners.
WARNING!
WARNING!
1. STOP! Read the safety information onthe Operating Instructions Labellocated on this appliance.
IF YOU DO NOT FOLLOW THESEINSTRUCTIONS EXACTLY, A FIRE OREXPLOSION MAY RESULT CAUSINGPROPERTY DAMAGE, PERSONALINJURY OR LOSS OF LIFE.
2. Set the thermostat to its lowestsetting.
3. Turn off all electric power to theappliance.
4. This appliance does not have a pilot.It is equipped with an ignition devicewhich automatically lights the burner.Do NOT try to light the burner byhand.
5. Remove control door/access panel.
6. Move switch to the “OFF” position.
7. Wait five (5) minutes to clear out anygas. Then smell for gas, includingnear the floor. If you smell gas, STOP!
• Do not try to light any appliance.
• Do not touch any electric switch; donot use any phone in your building.
• Immediately call your gas supplierfrom a neighbor’s phone. Follow thegas supplier’s instructions.
• If you cannot reach your gassupplier, call the fire department.
If you don’t smell gas, go to the nextstep.
8. Move the switch from “OFF” positionto “ON” position.
9. Replace the control door.
10. Turn on all electric power to theappliance.
11. Set the thermostat to the desiredsetting.
12. If the appliance will not operate, followthe instructions below on how to shutdown the furnace.
THE SPARK IGNITOR AND IGNITIONLEAD FROM THE IGNITION CONTROLARE HIGH VOLTAGE. KEEP HANDS ORTOOLS AWAY TO PREVENTELECTRICAL SHOCK. SHUT OFFELECTRICAL POWER BEFORESERVICING ANY OF THE CONTROLS.FAILURE TO ADHERE TO THISWARNING CAN RESULT IN PERSONALINJURY OR DEATH. The initial start-upon a new installation may require thecontrol system to be energized for sometime until any air has bled through thesystem and fuel gas is available at theburners.
WARNING!
WARNING!
20
BURNERSBurners for these units have beendesigned so that field adjustment is notrequired. Burners are tray-mounted andaccessible for easy cleaning whenrequired.
MANUAL RESETOVERTEMPERATURECONTROLA manual reset overtemperature controlis located on the burner shield. Thisdevice senses blockage in the heatexchanger or insufficient combustion air.This shuts off the main burners ifexcessive temperatures occur in theburner compartment.Operation of this control indicates anabnormal condition. Therefore, the unitshould be examined by a qualifiedinstaller, service agency, or the gassupplier before being placed back intooperation.
DO NOT JUMPER THIS DEVICE! DONOT reset the overtemperature controlwithout taking corrective action toassure that an adequate supply ofcombustion air is maintained under allconditions of operation. Failure to doso can result in carbon monoxidepoisoning or death. Replace thiscontrol only with the identicalreplacement part.
! WARNING
TO SHUT DOWN FURNACE1. Set the thermostat to the lowest
setting.2. Turn off all electric power to the
appliance if service is to beperformed.
3. Remove control door.
5. Replace control door.
SHOULD OVERHEATING OCCUR ORTHE GAS SUPPLY FAIL TO SHUT OFF,SHUT OFF THE MANUAL GAS VALVETO THE APPLIANCE BEFORESHUTTING OFF THE ELECTRICALSUPPLY. FAILURE TO DO SO CANRESULT IN AN EXPLOSION OR FIRECAUSING PROPERTY DAMAGE,SEVERE PERSONAL INJURY ORDEATH!
PRESSURE SWITCHThis furnace has a pressure switch forsensing a blocked exhaust or a failedinduced draft blower. It is normally openand closes when the induced draft blowerstarts, indicating air flow through thecombustion chamber.
LIMIT CONTROLThe supply air high temperature limit cut-off is set at the factory and cannot beadjusted. It is calibrated to prevent the airtemperature leaving the furnace fromexceeding the maximum outlet airtemperature. WARNING: DO NOTJUMPER THIS DEVICE! Replace thiscontrol only with the identicalreplacement part.
! WARNING
4. Move switch to the “OFF” position.
21
ADVISE THE CUSTOMER1. Keep the air filters clean. The
heating system operates better,more efficiently and moreeconomically.
2. Arrange the furniture and drapes sothat the supply air registers and thereturn air grilles are unobstructed.
3. Close doors and windows. Thisreduces the heating load on thesystem.
4. Avoid excessive use of exhaust fans.5. Do not permit the heat generated by
television, lamps or radios toinfluence the thermostat operation.
6. Except for the mounting platform,keep all combustible articles threefeet from the unit and exhaustsystem.
7. IMPORTANT: Replace all blowerdoors and compartment cover afterservicing the unit. Do not operate theunit without all panels and doorssecurely in place.
8. Do not allow snow or other debris toaccumulate in the vicinity of theappliance.
FURNACE SECTIONMAINTENANCEThe unit’s furnace should operate formany years without excessive scalebuild-up in flue passageways; however,it is recommended that a qualifiedinstaller, service agency, or the gassupplier annually inspect the fluepassageways, the exhaust system andthe burners for continued safe operation,paying particular attention todeterioration from corrosion or othersources.If during inspection the fluepassageways and exhaust system aredetermined to require cleaning, thefollowing procedures should be followed(by a qualified installer, service
agency, or gas supplier):
1. Turn off the electrical power to the
unit and set the thermostat to the
lowest temperature.
2. Shut off the gas supply to the unit
either at the meter or at manual
valve in the supply piping.
LABEL ALL WIRES PRIOR TO
DISCONNECTION WHEN SERVICING
CONTROLS. WIRING ERRORS CAN
CAUSE IMPROPER AND DANGEROUS
OPERATION RESULTING IN FIRE,
ELECTRICAL SHOCK, PROPERTY
DAMAGE, PERSONAL INJURY OR
DEATH.
3. Remove the furnace controls accesspanel and the control box cover.
4. Disconnect the gas supply pipingfrom the gas valve.
5. Disconnect the wiring to the induceddraft blower motor, gas valve, flamesensor, and flame roll-out control,and ignitor cable. Mark all wires
disconnected for proper
reconnection.6. Remove the screws (4) connecting
the burner tray to the heat exchangermounting panel.
7. Remove the burner tray and themanifold assembly from the unit.
8. Remove the screws (4) connectingthe induced draft blower to thecollector box and screws (16)connecting the collector box to theheat exchanger mounting panel.Remove the induced draft blower andthe collector box from the unit.
9. Remove the turbulators from insidethe heat exchangers by inserting theblade of a screwdriver under thelocking tabs. Pop the tabs out of theexpanded grooves of the heatexchanger. Slide the turbulators out ofthe heat exchangers.
10. Direct a water hose into the outlet ofthe heat exchanger top. Flush theinside of each heat exchanger tubewith water. Blow out each tube with airto remove excessive moisture.
11. Reassemble (steps 1 through 10 inreverse order). Be careful not to
strip out the screw holes used to
mount the collector box and
inducer blower. Replace inducer
blower gasket and collector box
gasket with factory replacements if
damaged.
HOLES IN THE EXHAUST
TRANSITION OR HEAT EXCHANGER
CAN CAUSE TOXIC FUMES TO ENTER
THE HOME. THE EXHAUST
TRANSITION OR HEAT EXCHANGER
MUST BE REPLACED IF THEY HAVE
HOLES OR CRACKS IN THEM.
FAILURE TO DO SO CAN CAUSE
CARBON MONOXIDE POISONING
RESULTING IN PERSONAL INJURY OR
DEATH.
The manufacturer recommends that aqualified installer, service agency or thegas supplier visually inspect the burnerflames for the desired flame appearance atthe beginning of the heating season andapproximately midway in heating season.The manufacturer also recommends that aqualified installer, service agency or thegas supplier clean the flame sensor withsteel wool at the beginning of the heatingseason.
DISCONNECT MAIN ELECTRICAL
POWER TO THE UNIT BEFORE
ATTEMPTING MAINTENANCE.
FAILURE TO DO SO MAY RESULT IN
ELECTRICAL SHOCK OR SEVERE
PERSONAL INJURY OR DEATH.
LUBRICATIONIMPORTANT: DO NOT attempt tolubricate the bearings on the blower motoror the induced draft blower motor. Additionof lubricants can reduce the motor life andvoid the warranty.The blower motor and induced draftblower motor are prelubricated by themanufacturer and do not require furtherattention.A qualified installer, service agency or thegas supplier must periodically clean themotors to prevent the possibility ofoverheating due to an accumulation ofdust and dirt on the windings or on themotor exterior. And, as suggestedelsewhere in these instructions, the airfilters should be kept clean because dirtyfilters can restrict air flow and the motordepends upon sufficient air flowing acrossand through it to prevent overheating.
COOLING SECTIONMAINTENANCE
DISCONNECT MAIN ELECTRICAL
POWER TO THE UNIT BEFORE
ATTEMPTING MAINTENANCE.
FAILURE TO DO SO CAN CAUSE
ELECTRICAL SHOCK RESULTING IN
SEVERE PERSONAL INJURY OR
DEATH.
VI. SYSTEM OPERATING INFORMATION! WARNING
! WARNING
! WARNING
! WARNING
22
It is recommended that at the beginningof each cooling season a qualifiedinstaller or service agency inspect andclean the cooling section of this unit. Thefollowing areas should be addressed:evaporator coil. condenser coil,condenser fan motor and venturi area.To inspect the evaporator coil:1. Remove the filter access panel and
the blower/evaporator coil accesspanel.
LABEL ALL WIRES PRIOR TODISCONNECTION WHEN SERVICINGTHE UNIT. WIRING ERRORS CANCAUSE IMPROPER ANDDANGEROUS OPERATIONRESULTING IN FIRE, ELECTRICALSHOCK, PROPERTY DAMAGE,SEVERE PERSONAL INJURY ORDEATH.2. Unplug the wires from the circulating
air blower and the limit control.Remove the two screws and slidethe blower out of the unit sideways.
3. Shine a flashlight on the evaporatorcoil (both sides) and inspect foraccumulation of lint, insulation, etc.
4. If coil requires cleaning, follow thesteps shown below.
Cleaning Evaporator Coil1. Remove screws from condenser fan
grille assembly and lay grille over onthe unit top panel.
2. Remove the controls access paneland the control box cover.
3. Disconnect the outdoor fan motorwiring from the compressor contactorand capacitor. Remove the strainrelief in the bulkhead and pull the fanmotor wires through. Set grilleassembly to the side.
4. Remove the screws that secure theunit top to the unit. Remove the topand set the unit top to the side.
5. The coil should be cleaned when it isdry. If the coil is coated with dirt orlint, vacuum it with a soft brushattachment. Be careful not to bendthe coil fins.
6. If the coil is coated with oil or grease,clean it with a mild detergent-and-water solution. Rinse the coilthoroughly with water. IMPORTANT:Do not use excessive waterpressure. Excessive water pressurecan bend the fins and tubing of thecoil and lead to inadequate unitperformance. Be careful not tosplash water excessively into unit.
7. Go to next section for cleaning thecondenser coil.
Cleaning Condenser Coil, Drain Pan,Condensate Drain, Condenser Fan,Circulation Air Blower and Venturi1. Remove the screws from the
condenser coil protective grille andremove the grille from the unit.Ensure the filter access panel is stillremoved to access all of the screwssecuring the grille.
2. The coil should be cleaned when it isdry. If the coil is coated with dirt orlint, vacuum it with a soft brushattachment. Be careful not to bendthe coil fins.
3. If the coil is coated with oil or grease,clean it with a mild detergent-and-water solution. Rinse the coilthoroughly with water. IMPORTANT:Do not use excessive waterpressure. Excessive water pressurecan bend the fins and tubing of thecoil and lead to inadequate unitperformance. Be careful not to splashwater excessively into unit.
4. Inspect the drain pan andcondensate drain at the same timethe condenser coil is checked. Cleanthe drain pan by flushing with waterand removing any matters ofobstructions which may be present.
5. Flush the drain tube with water. If thedrain tube is blocked, it can usuallybe cleared with high pressure water.
6. may cause inadequate unitperformance.
7. The venturi should also be inspectedfor items of obstruction such ascollections of grass, dirt or spiderwebs. Remove any that are present.
8. Inspect the circulating air blowerwheel and motor for accumulation oflint, dirt or other obstruction andclean it necessary. Inspect the blowermotor mounts and the blowerhousing for loose mounts or otherdamage. Repair or replace ifnecessary.
Re-assembly1. Place the condenser coil protective
grille back on unit and replace allscrews.
2. Place top panel back on unit andreplace all screws.
3. Set condenser fan grille assembly ontop of the unit with the fan on top andthe motor wires on the venturi side.run the fan motor wires through thebulkhead and pull wires through thehole on the bottom of the control boxon the left side and into the controlbox. Reconnect fan motor wires perthe wiring diagram attached to theback of the control box cover.
4. Replace wire strain relief in bulkheadafter the slack is pulled out of thewires on the fan side. This will assurewires will not be damaged by the fanduring unit operation.
5. Turn the condenser fan grilleassembly over and into the recess inthe unit top. Secure the grille to theunit with the four long #8 screwsremoved earlier.
6. Replace the circulating air blower,making sure that all wires are properlyreconnected per the unit wiringdiagram.
7. Replace the filter andblower/evaporator coil access panels.
8. Replace the control box cover andcontrols access panel.
9. Restore electrical power to the unitand check for proper operation,especially the condenser fan motor.
REPLACEMENT PARTSContact your local distributor for acomplete parts list.
TROUBLESHOOTINGRefer to Figures 27 and 28 for determiningcause of unit problems.
WIRING DIAGRAMFigures 29 and 30 are complete wiringdiagrams for the unit and its powersources.
CHARGINGSee Figure 31 through 38 for propercharging information.
! WARNING
23
RPM 734 810
3.0 [10.55] LowMed
886
Med
CFM 1222 [577] 1197 [565] 1179 [556] 1162 [548] 1137 [537] 1097 [518] 1033 [488]
923
RPM 765 810 855 890 920 960 995
Inputs
40,000 [11.72]60,000 [17.58]80,000 [23.45]
100,000 [29.31]
10 x 91/2 HP
3 Speed Motor
959
Watts 423 415 407 397 386 370 351
988
RPM 895 930 965 985 1005 1025 1045
1016
Watts 538 514 493 473 454 434 412
Watts 476 468 450 427 403 380 363
Med
CFM 1674 [790] 1620 [765] 1566 [739] 1511 [713] 1451 [685] 1384 [653] 1305 [616]
RPM
3.5 [12.31] LowHigh
997 1019
High
CFM 1514 [715] 1461 [670] 1415 [668] 1370 [647] 1322 [624] 1266 [597] 1197 [565]
1040 1058 1076 1088 11004.0 [14.07] Low
High
SeeNote
Below
AllInputs
60,000 [17.58]80,000 [23.45]
100,000 [29.31]
10 x 93/4 HP
3 Speed Motor
Low
CFM 1204 [568] 1202 [567] 1191 [562] 1171 [553] 1143 [539] 1107 [522] 1065 [503]
Watts 625 596 567 539 512 484 455
RPM 1085 1094 1102 1110 1118 1126 1134
Watts 699 663 632 604 576 548 517
High
CFM �1843 [870] �1763 [832] 1693 [799] 1627 [768] 1560 [736] 1485 [701] 1398 [660]
RPM 674 707 793 841 896 938 977
Watts 501 489 471 463 446 427 406
Med
CFM 1741 [821] 1721 [811] 1693 [798] 1645 [775] 1583 [746] 1521 [717] 1437 [677]
RPM 891 943 978 1004 1029 1047 10705.0 [17.59] LowHigh 100,000 [29.31]10 x 93/4 HP
3 Speed Motor
Low
CFM 1187 [560] 1174 [553] 1161 [547] 1148 [541] 1135 [535] 1105 [521] 1065 [502]
Watts 743 709 674 640 602 566 531
RPM 1036 1050 1064 1083 1092 1102 1116
Watts 831 801 754 716 682 640 605
High
CFM 2062 [972] 1988 [937] 1926 [908] 1832 [864] 1773 [836] 1684 [794] 1578 [744]
NOTE: On 4 ton models, switch to medium speed for cooling if external static pressure is less than 0.4” W.C. at 230 volts or less than 0.3” W.C. at 208 volts.� WARNING: Observe airflow operating limits if operating in area of airflow table shown in bold.
DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)
Pressure Drop—Inches W.C. [kPa] .00 .01 [.002] .02 [.005] .03 [.007] .05 [.012] .07 [.017] .08 [.019] .09 [.022]
Nominal Cooling Capacity Tons [kW] 1.5 [5.28] 2.0 [7.03] 2.5 [8.79] – 4.0 [14.07] 5.0 [17.59]
Minimum Filter Size—Inches [mm] 16 x 20 x 1 [406 x 508 x 25] 20 x 20 x 1 [508 x 508 x 25] 24 x 24 x 1 [610 x 610 x 25] 24 x 30 x 1 [610 x 762 x 1]
CFM [L/s] 600 [283] 800 [378] 1000 [472] 1200 [566] 1400 [661] 1800 [850]1600 [755] 2000 [944]
MINIMUM RECOMMENDED FILTER SIZES
[ ] Designates Metric Conversions
AllInputs
40,000 [11.72]60,000 [17.58]80,000 [23.45]
100,000 [29.31]
10 x 91/2 HP
3 Speed Motor
INDOOR AIRFLOW PERFORMANCE—208 VOLTSNominalCoolingCapacity
Tons [kW]
Motor Speedfrom
Factory
HeatingInput
BTU/HR [kW]
Blower Size/Motor HP [W] &
# of Speeds
MotorSpeed External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts—208 VoltsSide Discharge—Wet Coil
Cool 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]Heat
TABLE 8. AIR-FLOW PERFORMANCE – RRKA MODELS
24
3.0 [10.55] LowMed MedCFM 1411 [666] 1368 [646] 1327 [626] 1285 [606] 1238 [584] 1183 [558] 1116 [527]RPM 865 900 935 970 1000 1020 1035
Inputs
40,000 [11.72]60,000 [17.58]80,000 [23.45]
100,000 [29.31]
10 x 91/2 HP
3 Speed Motor Watts 498 481 464 447 430 411 391
RPM 980 1000 1020 1035 1050 1065 1080Watts 589 565 543 523 503 481 456
3.5 [12.31] LowHigh HighCFM 1641 [774] 1577 [744] 1515 [715] 1455 [687] 1393 [657] 1329 [627] 1262 [596]
RPM 859 905 951 981 1011 1034 1057Watts 557 530 506 483 461 437 409
MedCFM �1793 [846] �1731 [817] 1665 [786] 1594 [752] 1519 [717] 1440 [680] 1356 [640]RPM 1053 1067 1080 1091 1101 1110 11194.0 [14.07] Low
High
SeeNote
Below
AllInputs
60,000 [17.58]80,000 [23.45]
100,000 [29.31]
10 x 93/4 HP
3 Speed Motor
LowCFM 1412 [666] 1395 [658] 1371 [647] 1339 [632] 1296 [612] 1242 [586] 1176 [555]
Watts 667 637 606 574 543 512 483
RPM 1110 1117 1124 1129 1133 1139 1144Watts 736 715 683 646 608 574 551
HighCFM �1889 [892] �1826 [862] �1753 [827] 1672 [789] 1586 [749] 1499 [707] 1413 [667]
RPM 741 794 858 904 947 985 1021Watts 595 583 564 539 510 484 453
MedCFM 1943 [916] 1895 [893] 1840 [867] 1774 [836] 1700 [801] 1618 [763] 1525 [719]RPM 995 1024 1040 1057 1041 1087 11005.0 [17.59] LowHigh 100,000 [29.31]
10 x 93/4 HP
3 Speed Motor
LowCFM 1388 [654] 1380 [651] 1371 [646] 1351 [637] 1325 [625] 1294 [610] 1225 [577]
Watts 785 751 717 674 643 599 561
RPM 1080 1093 1100 1106 1115 1123 1130Watts 889 884 796 768 725 687 651
HighCFM 2150 [1014] 2072 [977] 1991 [939] 1917 [904] 1820 [858] 1722 [812] 1627 [767]
NOTE: On 4 ton models, switch to medium speed for cooling if external static pressure is less than 0.4” W.C. at 230 volts or less than 0.3” W.C. at 208 volts.� WARNING: Observe airflow operating limits if operating in area of airflow table shown in bold.
[ ] Designates Metric Conversions
AllInputs
40,000 [11.72]60,000 [17.58]80,000 [23.45]
100,000 [29.31]
10 x 91/2 HP
3 Speed Motor
NominalCoolingCapacity
Tons [kW]
Motor Speedfrom
Factory
HeatingInput
BTU/HR [kW]
Blower Size/Motor HP [W] &
# of Speeds
MotorSpeed External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts—230 VoltsSide Discharge—Wet Coil
Cool 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]Heat
INDOOR AIRFLOW PERFORMANCE—230 VOLTS
TABLE 8. AIR-FLOW PERFORMANCE – RRKA MODELS (CONTINUED)
25
BLOWER MOTOR SPEEDTAPSAfter determining necessary CFM andspeed tap data from Table 8, follow thesteps below to change speeds.1. Remove the furnace/control access
panel.2. Remove the control box cover. See
Figure 23 for location of the furnacecontrol board.
3. Reference Figure 24 for the properlocation of the red and black wireson the speed tap block and on thefurnace control board to obtain thespeed tap you have chosen.
4. After adjusting the wires accordingly,attach the control box cover, furnacecontrol access panel and the bloweraccess panel to the unit.
FIGURE 26FACTORY SET BLOWER SPEEDS W/ELEC. HEAT
FACTORY SETBLOWER SPEED
1.5 TON W/40K HEAT LOW LOW1.5 TON W/60K HEAT LOW HIGH2.0 TON W/40K HEAT HIGH LOW2.0 TON W/60K HEAT HIGH HIGH2.0 TON W/80K HEAT HIGH HIGH2.5 TON/ALL HEATS LOW LOW3.0 TON/ALL HEATS MED. LOW3.5 TON/ALL HEATS HIGH LOW4.0 TON/ALL HEATS HIGH LOW5.0 TON/ALL HEATS HIGH LOW
MODELCOOL HEAT
FIGURE 25
FIGURE 24INTEGRATED FURNACE CONTROL BOARD
HEATCOOL
FACTORY SETBLOWER SPEEDMODEL
FIGURE 26FACTORY SET BLOWER SPEEDS W/ELEC. HEAT
3.0 TON/ALL HEATS3.5 TON/ALL HEATS4.0 TON/ALL HEATS5.0 TON/ALL HEATS
MED.HIGHHIGHHIGH
LOWLOWLOWLOW
26
WARNING!
FIGURE 27COOLING TROUBLE SHOOTING CHART
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURETO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM POSSIBLE CAUSE REMEDY
Unit will not run • Power off or loose electrical connection • Check for correct voltage at compressor contactor in controlbox
• Thermostat out of calibration-set too high • Reset• Failed contactor • Check for 24 volts at contactor coil - replace if contacts are
open• Blown fuses • Replace fuses• Transformer defective • Check wiring-replace transformer• High pressure control open (if provided) • Reset-also see high head pressure remedy-The high pressure
control opens at 450 PSIG• Interconnecting low voltage wiring damaged • Replace thermostat wiring
Condenser fan runs, compressor • Run or start capacitor failed (single phase only) • Replacedoesn’t • Start relay defective 9single phase only) • Replace
• Loose connection • Check for correct voltage at compressor -check & tighten all connections
• Compressor stuck, grounded or open motor winding • Wait at least 2 hours for overload to reset.open internal overload. If still open, replace the compressor.
• Low voltage condition At compressor terminals, voltage must be within 10% of ratingplate volts when unit is operating.
• Low voltage condition • Add start kit components
Insufficient cooling • Improperly sized unit • Recalculate load• Improper airflow • Check - should be approximately 400 CFM per ton.• Incorrect refrigerant charge • Charge per procedure attached to unit service panel.• Air, non-condensibles or moisture in system • Recover refrigerant, evacuate & recharge, add filter drier• Incorrect voltage • At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
Compressor short cycles • Incorrect voltage • At compressor terminals, voltage must be ± 10% ofnameplate marking when unit is operating.
• Defective overload protector • Replace - check for correct voltage• Refrigerant undercharge • Add refrigerant
Registers sweat • Low evaporator airflow • Increase speed of blower or reduce restriction - replace airfilter
High head-low vapor pressures • Restriction in liquid line, expansion device or filter drier • Remove or replace defective component• Flow check piston size too small • Change to correct size piston• Incorrect capillary tubes • Change coil assembly• TXV does not open • Replace TXV
High head-high or normal vapor • Dirty condenser coil • Clean coilpressure - Cooling mode • Refrigerant overcharge • Correct system charge
• Condenser fan not running • Repair or replace• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
Low head-high vapor pressures • Defective Compressor valves • Replace compressor• Incorrect capillary tubes • Replace coil assembly
Low vapor - cool compressor - • Low evaporator airflow • Increase speed of blower or reduce restriction - replace airiced evaporator coil filter
• Operating below 65°F outdoors • Add Low Ambient Kit• Moisture in system • Recover refrigerant - evacuate & recharge - add filter drier
High vapor pressure • Excessive load • Recheck load calculation• Defective compressor • Replace
Fluctuating head & vapor • TXV hunting • Check TXV bulb clamp - check air distribution on coil - replacepressures TXV
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
Gurgle or pulsing noise at • Air or non-condensibles in system • Recover refrigerant, evacuate & rechargeexpansion device or liquid line
Circulating air blower & inducer • Manual reset overtemperature control • Reset or replacerun continuously, • tripped
compressor will not start • Wire loose in limit circuit • Check wiring
27
FIGURE 28
15 SECOND PREPURGE
28
FIGURE 29
29
3 TO
N CO
OLI
NG -
(-)RK
A
SYST
EM C
HARG
E CH
ARTS
FIG
UR
E 3
0
30
SYST
EM C
HARG
E CH
ARTS
FIG
URE
364
TON
COO
LING
- (-)
RKA
FIG
URE
353
1/2
TON
COO
LING
- (-)
RKA
FIG
UR
E 3
1F
IGU
RE
32
31
32 CM 0206