a - catalog 2013 inverter packaged fd series - hb91-13p01-e-a-218 feb (pls do not delete)

Upload: ck-see

Post on 14-Oct-2015

7 views

Category:

Documents


0 download

DESCRIPTION

A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb

TRANSCRIPT

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    2013

    13P01E

    R410A

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    2

    -15C +43C

    -20C +20C

    50403020100-10-20-30

    Heating

    Cooling

    : Heating operation down to -20C

    : Nominal heating capacity maintained at -15C

    -20C-15C

    FDC100VSX(4HP, 3phase 380V)

    FDC125VSX(5HP, 3phase 380V)

    FDC140VSX(6HP, 3phase 380V)

    Micro InverterHyper Inverter

    12.5

    16.0

    16.5

    16.0

    18.0

    20.0

    Max.heating capacity (kW)

    Heightdifference(Outdoor higherthan Indoor)

    30mPipinglength

    100m

    Thanks to optimization of refrigeration control with use of electric expansion valve anddevelopment of new twin rotary compressors, max heating capacity has been increased.Hyper Inverter series can reach the set temperature very quickly, keeping nominalheating capacity when outdoor temperature is -15C.It is effective to be used even in cold area.

    Temperature of supply air can reach 40C in 4minutes after start up under low temperatureoperation conditions (at both indoor and outdoortemperature of 2C) and can reach 50C in 8minutes after that.

    FDC100VSX(4HP, 3phase 380V)

    FDC125VSX(5HP, 3phase 380V)

    FDC140VSX(6HP, 3phase 380V)

    11.2kW

    14.0kW

    16.0kW

    nominal heating capacity(kW at outdoor temperature of 7C)model name

    11.2kW

    14.0kW

    16.0kW

    heating capacityat outdoor temperature of -15C

    Heating capacity (in case of 5HP, 3phase 380V)

    nominalheatingcapacity14.0kW

    Keeping nominal heatingcapacity at -15C

    (kW)

    18.0

    14.514.0

    8.8

    0-15C 2C 7C

    Hyper Inverter

    Micro Inverter

    Heating capacity

    50C

    40C

    30C

    20C

    10C

    0C4minutes 8minutes

    Hyper Inverter

    Micro Inverter

    Please refer to our technical manual for installation conditions, operation range and heating/cooling capacities. (including 1phase 220V)

    Leading powerful heating capacity in the industry

    Our new advanced technology has realized high efficiency,

    strong heating and long piping.

    This contributes to the environmental protection through energy

    saving and permits installation of the units (3~6HP) considering

    a heating operation under temperature conditions down to -

    20C and design flexibility has been improved by extension of

    piping length to 100m.Hyper Inverter

    1.5 2 2.5 3 4 5 6 8 10

    - -

    HPLine up

    Long piping(in case of 4~6HP)Strong heating(in case of 3~6HP)

    SRC40ZJX-S (1.5HP)SRC50ZJX-S (2.0HP)SRC60ZJX-S (2.5HP) FDC71VNX (3.0HP)

    FDC100VNX/VSX (4.0HP)FDC125VNX/VSX (5.0HP)FDC140VNX/VSX (6.0HP)

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    3

    Employment of the scrollinverter compressors(8/10HP)

    A control over wide range of capacity and a high efficiency has

    been realized by inverter-driven scroll compressors.In addition, the starting current significantly is improved.The size has also been reduced by 3.2% in height and 31.8% involume.

    Wide range of operation

    Though the nominal efficiency is lower than that ofFDC71VNX (Hyper inverter), higher SEER & SCOP areachieved by optimizing control.

    Compact Design of outdoor unitsHigh SEER & SCOP Refer to page 41

    Our new advanced technology has expanded the heating and coolingoperation range.This permits installation of the units under a low outdoor temperatureconditions down to -20C In heating operation and -15C in coolingoperation.

    * Vector control meansa. technique to realizean optimum control byconverting the currentwave to a smoothsinusoidal waveform

    Employment of DC twin rotary compressor has enabled to utilize a high-speed range of up to 120 rps at the maximum to secure the requiredcapacity.Optimum compressor control has been realized by employing the vectorcontrol* and the starting current has been improved significantlycompared with former models. Moreover, vibration has been reduced.

    Formercompressor

    New modelDC rotary compressor

    Heightat440mm

    Outside diameter of shell

    185mm

    Heigh

    tat342mm

    Reduction in height by 22.3%Reduction in volume by 44.1%

    133mm

    Micro Inverter

    Standard Inverter

    Size reduction and high efficiencyperformance on the DC twinrotary compressors(Micro Inverter 4-6HP)

    (FDC 100/125/140)

    50403020100-10-20-30

    Heating

    Cooling +43C

    +20C

    -15C

    -20C

    Micro Inverter

    1.5 2 2.5 3

    - - - -

    4 5 6 8 10

    HPLine up

    3

    Standard Inverter

    1.5 2 3.5

    - -

    4 5 6 8 10

    HP

    - - - --

    Line up

    FDC100VN/VS (4.0HP)FDC125VN/VS (5.0HP)FDC140VN/VS (6.0HP)

    FDC200VS(8.0HP)

    FDC250VS(10.0HP)

    Fits into elevators

    Easyinstallation

    FDC71VNP (3.0HP) FDC90VNP (3.5HP)

    FDC71VNX FDC71VNP

    Volume

    33% lessWeight

    25% lessSCOP

    6

    7

    5

    4

    3

    4.09 4.27

    SEER

    5.726.14

    FDC71VNX FDC71VNP FDC71VNX FDC71VNP

    2.5

    -

    (in case of indoor unit: FDT71VF1)

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    4

    Previous New

    Due to optimization of outlet design of air flow with ournew advanced technology, sufficient air flow is securedand long reach of air flow is realized.(FDT)

    For person who is farfrom the indoor unit

    For both persons who arefeeling hot or cold

    Can cool both the kitchenand the guests

    Expansion of outlet air flow area realizes

    reduction of pressure loss caused by air flow

    in the indoor unit. Load of fan motor is

    decreased and efficiency is increased.

    Reduction of air flow pressure loss

    Previous New

    Shape of heat exchanger365mm

    298mm

    FDT125~140

    18%reduction!!

    Increase of heat transfer efficiency

    Applying high efficient piping in heat exchanger and

    optimization of heat exchanger (2parts 1part)

    increases heat transfer efficiency.

    Individual flap control system

    According to room temperature conditions, four

    directions of air flow can be controlled individually by

    following Flap control system.

    As individual flap control is available even after

    installation, installation area became wider than before.

    The thinnest design

    Thanks to new design of heat exchanger changed from 2 parts to 1 part, the height of

    indoor unit is reduced drastically.

    High efficiency

    Selectedupper position

    Max swingrange

    Selectedlower position

    Flap control system

    The flap can swing within the range of upper and

    lower flap position selected with wired remote control.(this system is applied for FDEN, SRK type also)

    *Wireless remote control and RCH-E3 is not applicable to the Individual flapcontrol system and the Flap control system.

    Ceiling Cassette -4way- Indoor units

    FDT.FDTC

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    5

    External Static Pressure(E.S.P) control

    Reduction of sound pressure level

    FDU

    Duct Connected -High Static Pressure-

    NEW

    Keep the same

    air flow volume

    Longer DuctDuct

    Ceiling

    New

    FDUDuct

    External Static Pressure (E.S.P.) canbe set by E.S.P. button.

    *Range of 80~150 Pa is set at ex-factory default. Range of 10~200 Pa is available by setting SW8-4 switch on at site.

    E.S.P. button

    RC-E5

    Setting No.

    E.S.P.

    No.8

    80Pa

    No.9

    90Pa

    No.10

    100Pa

    No.11

    110Pa

    No.12

    120Pa

    No.13

    130Pa

    No.14

    140Pa

    No.15

    150Pa

    case1 case2

    Current

    10~130PaNew

    10~200Pa

    FDU71/100 37 25 12dB less!!

    New

    New

    Lo mode(FDU71VF1, in the Lo mode) Current

    Current

    FDU125/140 38 30 8dB less!!

    0 5 10 15 20 25 30 35 40 dB(A)

    12dB less!!

    You can set External Static Pressure (E.S.P.) by method

    of manual setting on remote control. Indoor unit will

    control fan-speed to keep rated air

    flow volume at each fan speed setting.

    You can set required E.S.P. by wired

    remote control that calculated with the

    set air flow rate and pressure loss ofthe duct connected.

    FDU71 297 280 17mm less!!

    NewCurrent

    FDU100/125/140 350 280 70mm less!!

    Thin design

    Reduction of weight

    FDU71 40 34 6kg less!!

    NewCurrent

    FDU100/125/140 63 34 29kg less!!

    FDUM has the same E.S.P. control.

    FDUMDUCT CONNECTED -Middle Static Pressure-

    FDUM

    Refer to page 14.

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    6

    SINGLE [OUTDOOR UNIT : INDOOR UNIT = 1 : 1]

    CEILINGSUSPENDED

    Type

    4way

    FDT

    4way compact(600 x 600mm)

    FDTC

    Low/MiddleStaticpressure

    FDUM

    High Static

    pressure

    FDU

    FDEN

    CEILINGCASSETTE

    DUCT

    CONN

    ECTED

    Indoor

    unit

    Outdoor

    unit

    Indoor

    unit

    Outdoor unit

    Indoor

    unit

    Indoor

    unit

    Indoor

    unit

    Set 1phase

    1phase1phase

    3phase

    1phase

    3phase

    1phase

    1phase

    1phase

    3phase

    1phase

    3phase

    1phase

    3phase

    1phase

    3phase

    1.5

    FDT40VF

    FDT40ZJXVF FDT50ZJXVF FDT60ZJXVF FDT71VNXVF1

    FDT50VF FDT60VF FDT71VF1

    Set

    FDTC40VF

    FDTC40ZJXVF FDTC50ZJXVF

    FDTC50VF

    Set

    FDU71VF1

    Set FDUM50ZJXVF FDUM60ZJXVF FDUM71VNXVF1

    3phase

    FDUM50VF FDUM60VF FDUM71VF1

    Set

    FDEN40VF

    FDEN40ZJXVF FDEN50ZJXVF FDEN60ZJXVF FDEN71VNXVF1

    SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S FDC71VNX

    SRC40ZJX-S SRC50ZJX- S

    FDTC60ZJXVF

    FDTC60VF

    SRC60ZJX-S

    FDC71VNX

    SRC50ZJX-S SRC60ZJX-S FDC71VNX

    3phase

    SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S FDC71VNX

    FDEN50VF FDEN60VF FDEN71VF1

    HP

    kW

    Btu/h

    kcal/h

    2.0 2.5 3.0

    4.013,7003,440

    5.0

    17,100

    4,300

    6.0

    19,100

    4,816

    7.1

    23,900

    6,020

    Capacity

    FDU71VNXVF1

    FDT100VNXVF1

    FDT100VSXVF1

    FDT100VF1

    FDUM100VNXVF1

    FDUM100VSXVF1

    FDUM100VF1

    FDEN100VNXVF1

    FDC100VNX

    FDC100VSX

    FDU100VNXVF1

    FDU100VSXVF1

    FDU100VF1

    FDC100VNX

    FDC100VSX

    FDC100VNX

    FDC100VSX

    FDC100VNX

    FDEN100VSXVF1

    FDC100VSX

    FDEN100VF1

    4.0

    10.0

    34,100

    8,600

    Outdoor

    unit

    Outdoor

    unit

    Outdoor

    unit

    FLOOR

    STANDING

    OUTDOOR UNIT

    FDF

    Indoor

    unit

    1phase

    3phase

    1phase

    3phaseSet

    FDF71VNXVD1

    FDC71VNX

    FDF71VD1

    FDF100VNXVD1

    FDC100VNX

    FDF100VSXVD1

    FDC100VSX

    FDF100VD1

    Outdoor

    unit

    NEW

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    7

    FDT100VF1 FDT125VF FDT140VF

    FDU100VSVF1 FDU125VSVF FDU140VSVF FDU200VSVF FDU250VSVF

    FDU125VF FDU140VF FDU100VF1 FDU125VF FDU140VF FDU200VF FDU250VF

    FDUM100VNVF1FDUM125VNVF FDUM140VNVF

    FDUM100VSVF1 FDUM125VSVF FDUM140VSVF

    FDUM100VF1 FDUM125VF FDUM140VF

    FDEN100VNVF1 FDEN125VNVF FDEN140VNVF

    FDEN100VSVF1

    FDU125VSXVF

    FDUM125VNXVF

    FDUM125VSXVF

    FDEN125VNXVF

    FDEN125VSXVF

    FDU140VSXVF

    FDUM140VNXVF

    FDUM140VSXVF

    FDEN140VNXVF

    FDEN140VSXVF FDEN125VSVF FDEN140VSVF

    FDC100VS FDC125VS FDC140VS

    FDC100VN FDC125VN FDC140VN

    FDC125VNX FDC140VNX FDC100VN FDC125VN FDC140VN

    FDC100VS

    FDC125VSX

    FDC125VSX

    FDC140VSX

    FDC140VSX

    FDEN125VF FDEN140VF

    FDC125VNX FDC140VNX

    FDC125VSX FDC140VSX

    FDUM125VF FDUM140VF

    FDC125VNX FDC140VNX

    FDC125VSX FDC140VSX

    FDC125VS FDC140VS FDC200VS FDC250VS

    FDU71VF1 FDU100VF1

    FDC100VN FDC125VN FDC140VN

    FDUM71VNPVF1 FDUM90VNPVF1

    FDUM71VF1 FDUM100VF1

    FDC71VNP FDC90VNP

    FDC100VS FDC125VS FDC140VS

    FDC100VS FDC125VS FDC140VS

    FDC100VN FDC125VN FDC140VN

    FDEN100VF1 FDEN125VF FDEN140VF

    FDEN71VNPVF1 FDEN90VNPVF1

    FDC71VNP FDC90VNP

    FDEN71VF1 FDEN100VF1

    4.0 5.0 6.0 8.0 10.05.0

    FDT125VF FDT140VF

    FDC125VNX FDC140VNX

    6.0

    12.5

    42,700

    10,750

    14.0

    47,800

    12,040

    10.0

    34,100

    8,600

    12.5

    42,700

    10,750

    14.0

    47,800

    12,040

    20.0

    68,300

    17,200

    25.0

    85,400

    21,500

    3.0 3.5

    7.1

    23,900

    6,020

    9.0

    30,300

    7,630

    Range(Rated Cooling Capacity)

    FDT100VNVF1 FDT125VNVF FDT140VNVF

    FDT100VSVF1

    FDT125VNXVF

    FDT125VSXVF

    FDT140VNXVF

    FDT140VSXVF FDT125VSVF FDT140VSVF

    FDT71VF1 FDT100VF1

    FDC71VNP FDC90VNP

    FDT71VNPVF1 FDT90VNPVF1

    FDU100VNVF1 FDU125VNVF FDU140VNVF

    FDC71VNP FDC90VNP

    FDU71VNPVF1 FDU90VNPVF1FDU125VNXVF FDU140VNXVF

    Micro Inverter Standard Inverter

    FDF100VNVD1 FDF125VNVD FDF140VNVD

    FDF100VSVD1

    FDF125VNXVD

    FDF125VSXVD

    FDF140VNXVD

    FDF140VSXVD FDF125VSVD FDF140VSVD

    FDF125VD FDF140VD

    FDC125VNX FDC140VNX

    FDC125VSX FDC140VSX FDC100VS FDC125VS FDC140VS

    FDC100VN FDC125VN FDC140VN

    FDF100VD1 FDF125VD FDF140VD

    FDF71VNPVD1 FDF90VNPVD1

    FDC71VNP FDC90VNP

    FDF71VD1 FDF100VD1

    NEW

    NEWNEW

    NEW NEW

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    8

    FDTCEILING CASSETTE -4way-

    Dimensions(Unit:mm)

    R410A

    Easy checking of drain pan

    condition is available by

    removing corner lid only.

    Due to new design

    changing fan motor is

    available without removinga panel. Temporally setting

    of drain pan is also

    available.

    Point

    2 Easy checking of drain panDrain can be discharged

    upwards by 700mm from the

    ceiling surface. It allows a

    piping layout with a high

    degree of freedom

    Depending on the installationlocation and 260mm flexible

    hose as a standard

    equipment supports easy

    workability.

    Point

    3 700mm Drain Pump

    Flexible hose

    less than

    700mm

    Models FDT100VF1,125VF,140VFModels FDT40VF,50VF,60VF,71VF1

    [ INDOOR UNIT ]

    Point

    1 Arrangement of installationbalance of indoor unit

    Checking from access ports with

    detachable covers at each corner,arrangement of installation balance of

    indoor unit can be available without

    removing a panel. Workability is improved

    and time of installation is reduced.

    RCN-T-36W-E

    Wireless

    RC-E5

    Wired

    RCH-E3RC-EX1AFDT 40/50/60/71/

    100/125/140

    Remote control (Option)

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    9

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).

    Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural

    wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    SPECIFICATIONS

    Powerful-Hi can be selected. Sound level: 40/50ZJXVF 39dB, 60ZJXVF 46dB, 71VNXVF1 46dB, 100VN(S)XVF1 51dB, 125/140VN(S)XVF 51dBAir flow: 40/50ZJXVF 20m3/min, 60ZJXVF 28m3/min, 71VNXVF1 28m3/min, 100VN(S)XVF1 37m3/min, 125/140VN(S)XVF 37m3/min

    Set model name FDT40ZJXVF FDT50ZJXVF FDT60ZJXVF FDT71VNXVF1 FDT100VNXVF1

    Indoor unit FDT40VF FDT50VF FDT60VF FDT71VF1 FDT100VF1

    Outdoor unit SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S FDC71VNX FDC100VNX

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cooling capacity (Min~Max) kW 4.0 ( 1.1 ~ 4.7 ) 5.0 ( 1.1 ~ 5.6 ) 5.6 ( 1.1 ~ 6.3 ) 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 )

    Nominal heating capacity (Min~Max) kW 4.5 ( 0.6 ~ 5.4 ) 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 7.1 ) 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 )

    Power consumption Cooling/Heating kW 0.93 / 1.06 1.29 / 1.29 1.52 / 1.70 2.04 / 1.94 2.50 / 2.58

    EER/COP Cooling/Heating 4.30 / 4.25 3.88 / 4.19 3.68 / 3.94 3.48 / 4.12 4.00 / 4.34

    Inrush current 220/230/240 VA

    5 5 5 5 5

    Max. running current 12 15 15 17 24

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    55 / 55 55 / 55 60 / 60 64 / 64 65 / 65

    Outdoor Cooling/Heating 63 / 63 63 / 63 64 / 64 66 / 66 70 / 70

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 33 / 31 / 30 33 / 31 / 30 33 / 31 / 30 35 / 33 / 31 40 / 37 / 35

    Heating (Hi/Me/Lo) 33 / 31 / 30 33 / 31 / 30 33 / 31 / 30 35 / 33 / 31 40 / 37 / 35

    Outdoor Cooling/Heating 50 / 50 54 / 50 54 / 54 51 / 48 48 / 50

    Air owIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    18 / 16 / 14 18 / 16 / 14 18 / 16 / 14 21 / 19 / 17 27 / 24 / 20

    Heating (Hi/Me/Lo) 18 / 16 / 14 18 / 16 / 14 18 / 16 / 14 21 / 19 / 17 27 / 24 / 20

    Outdoor Cooling/Heating 36 / 33 40 / 33 41.5 / 39 60 / 50 100 / 100

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    Unit: 246 x 840 x 840 Panel: 35 x 950 x 950 Unit: 298 x 840 x 840 Panel: 35 x 950 x 950

    Outdoor 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370

    Net weight

    Indoor

    kg

    27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5) 32.5(Unit:27 Panel:5.5)

    Outdoor 45 60 105

    Ref.piping size Liquid/Gas mm 6.35(1/4") / 12.7(1/2") 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.30 Max. 50 Max. 100

    Vertical height differences Outdoor is higher/lower m Max.20 / Max.20 Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -15~20 -20~20

    Panel T-PSA-3BW-E

    Air lter, Q'ty Pocket plastic net x 1(Washable)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E

    Set model name FDT125VNXVF FDT140VNXVF FDT100VSXVF1 FDT125VSXVF FDT140VSXVF

    Indoor unit FDT125VF FDT140VF FDT100VF1 FDT125VF FDT140VFOutdoor unit FDC125VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz

    Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )

    Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )

    Power consumption Cooling/Heating kW 3.28 / 3.43 4.19 / 4.20 2.50 / 2.58 3.28 / 3.43 4.19 / 4.20

    EER/COP Cooling/Heating 3.81 / 4.08 3.34 / 3.81 4.00 / 4.34 3.81 / 4.08 3.34 / 3.81

    Inrush current 220/230/240 VA

    5 5 5 5 5

    Max. running current 26 26 15 15 15

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    68 / 68 68 / 68 65 / 65 68 / 68 68 / 68

    Outdoor Cooling/Heating 70 / 70 72 / 72 70 / 70 70 / 70 72 / 72

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 42 / 40 / 37 43 / 41 / 38 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38

    Heating (Hi/Me/Lo) 42 / 40 / 37 43 / 41 / 38 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38

    Outdoor Cooling/Heating 48 / 50 49 / 52 48 / 50 48 / 50 49 / 52

    Air owIndoor

    Cooling (Hi/Me/Lo)

    m3

    /min

    30 / 27 / 23 30 / 27 / 23 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23

    Heating (Hi/Me/Lo) 30 / 27 / 23 30 / 27 / 23 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    Unit: 298 x 840 x 840 Panel: 35 x 950 x 950

    Outdoor 1,300 x 970 x 370

    Net weightIndoor

    kg32.5(Unit:27 Panel:5.5)

    Outdoor 105

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.100

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -20~20

    Panel T-PSA-3BW-E

    Air lter, Q'ty Pocket plastic net x 1(Washable)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    10

    FDTC

    R410A

    CEILING CASSETTE -4way Compact (600 X 600mm)-

    Point

    3 CLEARERAir Flow

    Point

    4 Installation Workability

    RCN-TC-24W-ER

    New shape & angled louver redirects the air

    current away from the ceiling, to reduce

    ceiling stains

    For wireless control simply insert the

    infrared receiver kit on a corner of thepanel

    wirelessremote control

    Point

    5 Compact and Convenient

    Fits into standard600 x 600 ceiling

    Point

    1 Taking OA (Outside Air) into inside Point

    2 Quiet operation(Sound Pressure level in the Lo mode)

    Current(Cooling/Heating)

    New(Cooling)

    New(Heating)

    36

    35

    34

    33

    32

    31

    30

    29

    28

    27

    26

    25

    (dB)

    35dB

    30dB

    32dB

    5dBDown

    3dBDown

    [ INDOOR UNIT ]

    600mm Drain PumpDrain can be discharged upward by 600 mm from the ceiling

    surface close to the indoor unit.

    It allows a piping layout with a high degree of freedom

    depending on the installation location.

    600 x 600 ceilingIndoor unit size (W:570 x D:570) brings easy installation for

    600 x 600 ceiling and Panel size (700 x 700) is suitable for

    600 x 600 ceiling. Height is the industry's lowest height level

    248mm and weight is 15kg only.

    Flexible hose

    248mm

    600mm

    FDTC 40/50/60

    RCN-TC-24W-ERRC-E5RC-EX1A

    WirelessWired

    RCH-E3

    Remote control (Option)

    OA Spacer TC-OAS-E (option)

    Joint Duct TC-OAD-E (option)

    Utilizing OA spacer which comes as optional equipment, outside aircan be taken inside.

    OA OAPanel

    300mm

    Ceilingsurface

    Indoor Unit FDTC

    OA Spacer

    Joint Duct

    Using 1 joint duct:OA up to 1.3m3/min.

    Using 2 joint ducts:OA from 1.3 to 2.6m3/min.

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    11

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural

    wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Dimensions(Unit:mm)

    Powerful-Hi can be selected. Sound level: 40/50/60ZJXVF 47dB Air flow: 40/50/60ZJXVF 13.5m3/min

    Set model name FDTC40ZJXVF FDTC50ZJXVF FDTC60ZJXVF

    Indoor unit FDTC40VF FDTC50VF FDTC60VF

    Outdoor unit SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cooling capacity (Min~Max) kW 4.0 ( 1.1 ~ 4.7 ) 5.0 ( 1.1 ~ 5.6 ) 5.6 ( 1.1 ~ 6.3 )

    Nominal heating capacity (Min~Max) kW 4.5 ( 0.6 ~ 5.4 ) 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 6.7 )

    Power consumption Cooling/Heating kW 1.04 / 1.10 1.56 / 1.45 1.99 / 2.07

    EER/COP Cooling/Heating 3.85 / 4.09 3.21 / 3.72 2.81 / 3.24

    Inrush current 220/230/240 VA

    5 5 5

    Max. running current 12 15 15

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    60 / 60 60 / 60 60 / 60

    Outdoor Cooling/Heating 63 / 63 63 / 63 64 / 64

    Soundpressurelevel*

    1

    IndoorCooling (Hi/Me/Lo) 42 / 36 / 30 42 / 36 / 30 46 / 39 / 30

    Heating (Hi/Me/Lo) 42 / 36 / 32 42 / 36 / 32 46 / 39 / 32

    Outdoor Cooling/Heating 50 / 50 54 / 50 54 / 54

    Air flowIndoor Cooling (Hi/Me/Lo)

    m3/min11.5 / 9 / 7 11.5 / 9 / 7 13.5 / 10 / 7

    Heating (Hi/Me/Lo) 11.5 / 9 / 8 11.5 / 9 / 8 13.5 / 10 / 8

    Outdoor Cooling/Heating 36 / 33 40 / 33 41.5 / 39

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    Unit: 248 x 570 x 570 Panel: 35 x 700 x 700

    Outdoor 640 x 800(+71) x 290

    Net weightIndoor

    kg18.5(Unit:15 Panel:3.5)

    Outdoor 45

    Ref.piping size Liquid/Gas mm 6.35(1/4") / 12.7(1/2")

    Refrigerant line (one way) length m Max.30

    Vertical height differences Outdoor is higher/lower m Max.20 / Max.20

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -15~20

    Panel TC-PSA-25W-E

    Air filter, Q'ty Pocket plastic net x 1(Washable)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TC-24W-ER

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    12

    Quiet, Lightweight and Compact

    With the FDU71, the noise level is

    only 25dB (low), weight is only 34kgand height is only 280mm.

    In addition 600mm Drain Pump is

    mounted in FDU71/100/125/140.

    The indoor unit is completely

    hidden in the ceiling, so this is

    suitable for spaces with classy

    interior decoration.

    Dimensions (Unit:mm)

    R410A

    FDU 71/100/125/140

    FDU

    DUCT CONNECTED -High Static pressure-

    Model FDU71VF1 Models FDU100VF1,125VF,140VF

    Models FDU200,250VF (Micro inverter only, refer to P23)

    RC-E5RC-EX1A

    Wired

    RCH-E3 RCN-KIT3-E

    Wireless

    600mm

    [ INDOOR UNIT ]

    Remote control (Option)

    Enhanced installation workability

    NEW

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    13

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.External static pressure is 35Pa(71), 60Pa (100/125/140).

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level

    become 5dB(A) higher at external static pressure of 200Pa.

    *3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    SPECIFICATIONS

    Powerful-Hi can be selected. Sound level: 71VNXVF1 38dB, 100VN(S)XVF1 44dB, 125VN(S)XVF 45dB, 140VN(S)XVF 47dBAir flow: 71VNXVF1 24m3/min, 100VN(S)XVF1 36m3/min, 125VN(S)XVF 39m3/min, 140VN(S)XVF 48m3/min

    Set model name FDU100VSXVF1 FDU125VSXVF FDU140VSXVF

    Indoor unit FDU100VF1 FDU125VF FDU140VF

    Outdoor unit FDC100VSX FDC125VSX FDC140VSXPower source 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz

    Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0)

    Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )

    Power consumption Cooling/Heating kW 2.68 / 3.02 3.49 / 3.77 4.28 / 4.42

    EER/COP Cooling/Heating 3.73 / 3.71 3.58 / 3.71 3.27 / 3.62

    Inrush current 220/230/240 VA

    5 5 5

    Max. running current 16 18 19

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    65 / 65 67 / 67 70 / 70

    Outdoor Cooling/Heating 70 / 70 70 / 70 72 / 72

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30

    Heating (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30

    Outdoor Cooling/Heating 48 / 50 48 / 50 49 / 52

    Air owIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    28 / 25 / 19 32 / 26 / 20 35 / 28 / 22

    Heating (Hi/Me/Lo) 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22

    Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100External static pressure*2 Pa Standard:60 Max:200

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    280 x 1,370 x 740

    Outdoor 1,300 x 970 x 370

    Net weightIndoor

    kg54

    Outdoor 105

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.100

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*3

    Heating -20~20

    Air lter Procure locally

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E

    Set model name FDU71VNXVF1 FDU100VNXVF1 FDU125VNXVF FDU140VNXVF

    Indoor unit FDU71VF1 FDU100VF1 FDU125VF FDU140VF

    Outdoor unit FDC71VNX FDC100VNX FDC125VNX FDC140VNX

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cooling capacity (Min~Max) kW 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )

    Nominal heating capacity (Min~Max) kW 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 )

    Power consumption Cooling/Heating kW 2.05 / 2.01 2.68 / 3.02 3.49 / 3.77 4.28 / 4.42

    EER/COP Cooling/Heating 3.46 / 3.98 3.73 / 3.71 3.58 / 3.71 3.27 / 3.62

    Inrush current 220/230/240 VA

    5 5 5 5

    Max. running current 17 25 29 30

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    65 / 65 65 / 65 67 / 67 70 / 70

    Outdoor Cooling/Heating 66 / 66 70 / 70 70 / 70 72 / 72

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30

    Heating (Hi/Me/Lo) 33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30

    Outdoor Cooling/Heating 51 / 48 48 / 50 48 / 50 49 / 52

    Air owIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22

    Heating (Hi/Me/Lo) 19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22

    Outdoor Cooling/Heating 60 / 50 100 / 100 100 / 100 100 / 100

    External static pressure*2 Pa Standard:35 Max:200 Standard:60 Max:200

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    280 x 950 x 635 280 x 1,370 x 740

    Outdoor 750 x 880(+88) x 340 1,300 x 970 x 370

    Net weightIndoor

    kg34 54

    Outdoor 60 105

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.50 Max.100

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*3

    Heating -20~20

    Air lter Procure locally

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    14

    R410A

    FDUM

    DUCT CONNECTED -Middle Static pressure-

    FDUM 50/60/71/

    100/125/140

    Dimensions (Unit:mm)Model FDUM50VF

    Models FDUM100VF1,125VF,140VF

    Models FDUM60VF,71VF1

    Automatic external static pressure (E.S.P.) control

    [ INDOOR UNIT ]

    RC-E5RC-EX1A

    Wired

    RCH-E3

    Filter kit (option)

    UM-FL1EF : for 50UM-FL2EF : for 60, 71UM-FL3EF : for 100, 125, 140external static pressure loss:5pa

    RCN-KIT3-E

    WirelessRemote control (Option)

    Round duct adapterIn case of requirements of

    round duct adapter, please

    access the followings for

    details.Company

    e-mailtel

    : AIRZONE: [email protected]: +34-902-400-445

    Duct design was simplified.

    Using DC motor, the most optimum air flow volume can be achieved by

    this automatic control.

    Indoor unit will recognize external static pressure by itself automatically

    and keep rated air flow volume.

    Keep the sameair flow volume

    Longer DuctDuct

    Ceiling

    New

    FDUMDuct

    Setting No.

    E.S.P.

    No.1

    10Pa

    No.2

    20Pa

    No.3

    30Pa

    No.4

    40Pa

    No.5

    50Pa

    No.6

    60Pa

    No.7

    70Pa

    No.8

    80Pa

    No.9

    90Pa

    No.10

    100PaExternal Static Pressure (E.S.P.)can be set by E.S.P. button.

    E.S.P. button

    RC-E5

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    15

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    External static pressure is 35Pa (50/60/71), 60Pa (100/125/140).*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level

    become 5dB(A) higher at external static pressure of 100Pa.

    *3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    SPECIFICATIONS

    Powerful-Hi can be selected. Sound level: 50ZJXVF 37dB, 60ZJXVF 36dB, 71VNXVF1 38dB, 100VN(S)XVF1 44dB, 125VN(S)XVF 45dB, 140VN(S)XVF 47dBAir flow: 50ZJXVF 13m3/min, 60ZJXVF 20m3/min, 71VNXVF1 24m3/min, 100VN(S)XVF1 36m3/min, 125VN(S)XVF 39m3/min, 140VN(S)XVF 48m3/min

    Set model name FDUM50ZJXVF FDUM60ZJXVF FDUM71VNXVF1 FDUM100VNXVF1

    Indoor unit FDUM50VF FDUM60VF FDUM71VF1 FDUM100VF1

    Outdoor unit SRC50ZJX-S SRC60ZJX-S FDC71VNX FDC100VNX

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cooling capacity (Min~Max) kW 5.0 ( 1.1~ 5.6 ) 5.6 ( 1.1~ 6.3 ) 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 )

    Nominal heating capacity (Min~Max) kW 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 7.1 ) 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 )

    Power consumption Cooling/Heating kW 1.38 / 1.45 1.54 / 1.75 2.03 / 1.99 2.68 / 3.02

    EER/COP Cooling/Heating 3.62 / 3.72 3.64 / 3.83 3.50 / 4.02 3.73 / 3.71

    Inrush current 220/230/240 VA

    5 5 5 5

    Max. running current 15 15 17 24

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    60 / 60 60 / 60 65 / 65 65 / 65

    Outdoor Cooling/Heating 63 / 63 64 / 64 66 / 66 70 / 70

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 32 / 29 / 26 31 / 28 / 25 33 / 29 / 25 38 / 36 / 30

    Heating (Hi/Me/Lo) 32 / 29 / 26 31 / 28 / 25 33 / 29 / 25 38 / 36 / 30

    Outdoor Cooling/Heating 54 / 50 54 / 54 51 / 48 48 / 50

    Air owIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    10 / 9 / 8 15 / 13 / 10 19 / 15 / 10 28 / 25 / 19

    Heating (Hi/Me/Lo) 10 / 9 / 8 15 / 13 / 10 19 / 15 / 10 28 / 25 / 19

    Outdoor Cooling/Heating 40 / 33 41.5 / 39 60 / 50 100 / 100

    External static pressure*2 Pa Standard:35 Max:100 Standard:60 Max:100

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    280 x 750 x 635 280 x 950 x 635 280 x 1,370 x 740

    Outdoor 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370

    Net weightIndoor

    kg29 34 54

    Outdoor 45 60 105

    Ref.piping size Liquid/Gas mm 6.35(1/4") / 12.7(1/2") 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.30 Max.50 Max.100

    Vertical height differences Outdoor is higher/lower m Max.20 / Max.20 Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*3

    Heating -15~20 -20~20

    Air lter Filter kit : UM-FL1EF/UM-FL2EF/UM-FL3EF (option)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E

    Set model name FDUM125VNXVF FDUM140VNXVF FDUM100VSXVF1 FDUM125VSXVF FDUM140VSXVF

    Indoor unit FDUM125VF FDUM140VF FDUM100VF1 FDUM125VF FDUM140VF

    Outdoor unit FDC125VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSXPower source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz

    Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0)

    Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 17.0) 16.0 ( 4.0 ~ 18.0) 11.2 ( 4.0 ~ 16.0) 14.0 ( 4.0 ~ 18.0) 16.0 ( 4.0 ~ 20.0)

    Power consumption Cooling/Heating kW 3.49 / 3.77 4.28 / 4.42 2.68 / 3.02 3.49 / 3.77 4.28 / 4.42

    EER/COP Cooling/Heating 3.58 / 3.71 3.27 / 3.62 3.73 / 3.71 3.58 / 3.71 3.27 / 3.62

    Inrush current 220/230/240 VA

    5 5 5 5 5

    Max. running current 26 26 15 15 15

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    67 / 67 70 / 70 65 / 65 67 / 67 70 / 70

    Outdoor Cooling/Heating 70 / 70 72 / 72 70 / 70 70 / 70 72 / 72

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30

    Heating (Hi/Me/Lo) 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30

    Outdoor Cooling/Heating 48 / 50 49 / 52 48 / 50 48 / 50 49 / 52

    Air owIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22

    Heating (Hi/Me/Lo) 32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22

    Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100External static pressure*2 Pa Standard:60 Max:100

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    280 x 1,370 x 740

    Outdoor 1,300 x 970 x 370

    Net weightIndoor

    kg54

    Outdoor 105

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.100

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*3

    Heating -20~20

    Air lter Filter kit : UM-FL3EF (option)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    17

    SPECIFICATIONS

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Powerful-Hi can be selected. Sound level: 40/50ZJXVF 46dB, 60ZJXVF 48dB, 71VNXVF1 50dB, 100VN(S)XVF1 46dB, 125/140VN(S)XVF 50dBAir flow: 40/50ZJXVF 11m3/min, 60ZJXVF 20m3/min, 71VNXVF1 20m3/min, 100VN(S)XVF1 28m3/min, 125/140VN(S)XVF 32m3/min

    Set model name FDEN40ZJXVF FDEN50ZJXVF FDEN60ZJXVF FDEN71VNXVF1 FDEN100VNXVF1

    Indoor unit FDEN40VF FDEN50VF FDEN60VF FDEN71VF1 FDEN100VF1

    Outdoor unit SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S FDC71VNX FDC100VNX

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cooling capacity (Min~Max) kW 4.0 ( 1.1 ~ 4.7 ) 5.0 ( 1.1 ~ 5.6 ) 5.6 ( 1.1 ~ 6.3 ) 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 )

    Nominal heating capacity (Min~Max) kW 4.5 ( 0.6 ~ 5.4 ) 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 7.1 ) 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 )

    Power consumption Cooling/Heating kW 1.02 / 1.10 1.53 / 1.46 1.78 / 1.87 2.11 / 2.11 2.80 / 2.88

    EER/COP Cooling/Heating 3.92 / 4.09 3.27 / 3.70 3.15 / 3.58 3.36 / 3.79 3.57 / 3.89

    Inrush current 220/230/240 VA

    5 5 5 5 5

    Max. running current 12 15 15 17 24

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    60 / 60 60 / 60 60 / 60 62 / 62 64 / 64

    Outdoor Cooling/Heating 63 / 63 63 / 63 64 / 64 66 / 66 70 / 70

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 39 / 38 / 37 39 / 38 / 37 41 / 39 / 38 41 / 39 / 38 44 / 41 / 39

    Heating (Hi/Me/Lo) 39 / 38 / 37 39 / 38 / 37 41 / 39 / 38 41 / 39 / 38 44 / 41 / 39

    Outdoor Cooling/Heating 50 / 50 54 / 50 54 / 54 51 / 48 48 / 50

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    10 / 9 / 7 10 / 9 / 7 16 / 14 / 12 16 / 14 / 12 26 / 23 / 21

    Heating (Hi/Me/Lo) 10 / 9 / 7 10 / 9 / 7 16 / 14 / 12 16 / 14 / 12 26 / 23 / 21

    Outdoor Cooling/Heating 36 / 33 40 / 33 41.5 / 39 60 / 50 100 / 100

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    210 x 1,070 x 690 210 x 1,320 x 690 250 x 1,620 x 690

    Outdoor 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370

    Net weight

    Indoor

    kg

    28 37 37 49

    Outdoor 45 60 105

    Ref.piping size Liquid/Gas mm 6.35(1/4") / 12.7(1/2") 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.30 Max.50 Max.100

    Vertical height differences Outdoor is higher/lower m Max.20 / Max.20 Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -15~20 -20~20

    Air filter, Q'ty Pocket Plastic net x2(Washable)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E1R

    Set model name FDEN125VNXVF FDEN140VNXVF FDEN100VSXVF1 FDEN125VSXVF FDEN140VSXVF

    Indoor unit FDEN125VF FDEN140VF FDEN100VF1 FDEN125VF FDEN140VFOutdoor unit FDC125VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz

    Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )

    Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )

    Power consumption Cooling/Heating kW 3.86 / 3.77 4.98 / 4.69 2.80 / 2.88 3.86 / 3.77 4.98 / 4.69

    EER/COP Cooling/Heating 3.24 / 3.71 2.81 / 3.41 3.57 / 3.89 3.24 / 3.71 2.81 / 3.41

    Inrush current 220/230/240 VA

    5 5 5 5 5

    Max. running current 26 26 15 15 15

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    67 / 67 67 / 67 64 / 64 67 / 67 67 / 67

    Outdoor Cooling/Heating 70 / 70 72 / 72 70 / 70 70 / 70 72 / 72

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43

    Heating (Hi/Me/Lo) 46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43

    Outdoor Cooling/Heating 48 / 50 49 / 52 48 / 50 48 / 50 49 / 52

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3

    /min

    29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23

    Heating (Hi/Me/Lo) 29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    250 x 1,620 x 690

    Outdoor 1,300 x 970 x 370

    Net weightIndoor

    kg49

    Outdoor 105

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.100

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -20~20

    Air filter, Q'ty Pocket Plastic net x2(Washable)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E1R

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    18

    Dimensions(Unit:mm)

    R410A

    Piping and drain hose connection can be selected out of 4-directions

    and the selection makes installation workability more effective.

    Due to slim design (Depth: 320mm), easy transportation and

    installation are realized.

    Easy MaintenanceThe surface of heat exchanger can be appeared only removing the

    front panel. Easy cleaning of heat exchanger is possible.

    Point

    1 Wide and powerful air flowFDF

    FLOOR STANDING

    [ INDOOR UNIT ]

    RCN-KIT3-E

    Wirelessremote control (Option)

    Wide and powerful air flow increase your comfort, realizing high

    efficiency in combination with our highly advanced outdoor units.

    Point

    2Easy Transportation and Installation workability

    FDF 71/100/125/140

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    19

    SPECIFICATIONS

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Powerful-Hi can be selected. Sound level:71VNXVD1 42dB, 100VN(S)XVD1 54dB, 125/140VN(S)XVD 54dBAir flow: 71VNXVD1 20m3/min, 100VNXVD1 29m3/min, 125/140VN(S)XVD 29m3/min

    Set model name FDF71VNXVD1 FDF100VNXVD1 FDF125VNXVD FDF140VNXVD

    Indoor unit FDF71VD1 FDF100VD1 FDF125VD FDF140VD

    Outdoor unit FDC71VNX FDC100VNX FDC125VNX FDC140VNX

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cooling capacity (Min~Max) kW 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )

    Nominal heating capacity (Min~Max) kW 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 )

    Power consumption Cooling/Heating kW 2.21 / 2.21 2.83 / 3.04 3.89 / 3.88 4.65 / 4.69

    EER/COP Cooling/Heating 3.21 / 3.62 3.53 / 3.68 3.21 / 3.61 3.01 / 3.41

    Inrush current 220/230/240 VA

    5 5 5 5

    Max. running current 17 24 26 24

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    61 / 61 65 / 65 73 / 73 73 / 73

    Outdoor Cooling/Heating 66 / 66 70 / 70 70 / 70 72 / 72

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 39 / 35 / 33 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44

    Heating (Hi/Me/Lo) 39 / 35 / 33 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44

    Outdoor Cooling/Heating 51 / 48 48 / 50 48 / 50 49 / 52

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    18 / 16 / 14 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19

    Heating (Hi/Me/Lo) 18 / 16 / 14 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19

    Outdoor Cooling/Heating 60 / 50 100 / 100 100 / 100 100 / 100

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    1,850 x 600 x 320

    Outdoor 750 x 880(+88) x 340 1,300 x 970 x 370

    Net weight

    Indoor

    kg

    49 52

    Outdoor 60 105

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.50 Max.100

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -20~20

    Air filter, Q'ty Plastic net x 1(washable)

    Remote control wired:RC-E5 (installed) wireless:RCN-KIT3-E(option)

    Set model name FDF100VSXVD1 FDF125VSXVD FDF140VSXVD

    Indoor unit FDF100VD1 FDF125VD FDF140VDOutdoor unit FDC100VSX FDC125VSX FDC140VSX

    Power source 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz

    Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )

    Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )

    Power consumption Cooling/Heating kW 2.83 / 3.04 3.89 / 3.88 4.65 / 4.69

    EER/COP Cooling/Heating 3.53 / 3.68 3.21 / 3.61 3.01 / 3.41

    Inrush current 220/230/240 VA

    5 5 5

    Max. running current 15 15 15

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    65 / 65 73 / 73 73 / 73

    Outdoor Cooling/Heating 70 / 70 70 / 70 72 / 72

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44

    Heating (Hi/Me/Lo) 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44

    Outdoor Cooling/Heating 48 / 50 48 / 50 49 / 52

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3

    /min

    26 / 23 / 19 26 / 23 / 19 26 / 23 / 19

    Heating (Hi/Me/Lo) 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    1,850 x 600 x 320

    Outdoor 1,300 x 970 x 370

    Net weightIndoor

    kg52

    Outdoor 105

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.100

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -20~20

    Air filter, Q'ty Plastic net x 1(washable)

    Remote control wired:RC-E5 (installed) wireless:RCN-KIT3-E(option)

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    20

    FDT

    FDT 100/125/140

    CEILING CASSETTE -4way-

    R410A

    [ INDOOR UNIT ]

    RC-E5RC-EX1A

    Wired

    RCH-E3 RCN-T-36W-E

    Wireless

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural

    wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Powerful-Hi can be selected. Sound level: 100VN(S)VF1 51dB, 125/140VN(S)VF 51dBAir flow: 100VN(S)VF1 37m3/min, 125/140VN(S)VF 37m3/min

    Dimensions : refer to page 8

    Micro Inverter

    Remote control(Option)

    Set model name FDT100VNVF1 FDT125VNVF FDT140VNVF FDT100VSVF1 FDT125VSVF FDT140VSVF

    Indoor unit FDT100VF1 FDT125VF FDT140VF FDT100VF1 FDT125VF FDT140VF

    Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz

    Nominal cooling capaci ty (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )

    Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )

    Power consumption Cooling/Heating kW 2.76 / 2.74 4.05 / 3.77 4.98 / 4.57 2.76 / 2.74 4.05 / 3.77 4.98 / 4.57

    EER/COP Cooling/Heating 3.62 / 4.09 3.09 / 3.71 2.81 / 3.50 3.62 / 4.09 3.09 / 3.71 2.81 / 3.50

    Inrush current 220/230/240 VA

    5 5 5 5 5 5

    Max. running current 24 24 24 15 15 15

    Sound powerlevel*

    1

    Indoor Cooling/Heating

    dB(A)

    65 / 65 68 / 68 68 / 68 65 / 65 68 / 68 68 / 68

    Outdoor Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38

    Heating (Hi/Me/Lo) 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38

    Outdoor Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    27 / 24 / 20 30 / 27 / 23 30 / 27 / 23 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23

    Heating (Hi/Me/Lo) 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23

    Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    Unit: 298 x 840 x 840 Panel: 35 x 950 x 950

    Outdoor 845 x 970 x 370

    Net weightIndoor

    kg32.5(Unit:27 Panel:5.5)

    Outdoor 81 83

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.50

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -20~20

    Panel T-PSA-3BW-E

    Air filter, Q'ty Pocket plastic net x 1(Washable)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    21

    FDU 100/125/140

    FDU

    DUCT CONNECTED -High Static pressure-

    FDU 200/250

    U-FCRA[For FDU 200/250]

    Fan control kit(100~200Pa) (option)

    RC-E5RC-EX1A

    Wired

    RCH-E3

    SPECIFICATIONSDimensions : refer to page 12

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7 CDB, 6CWB.External static pressure is 60Pa (100/125/140), 100Pa (200/250).

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level

    become 5dB(A) higher at external static pressure of 200Pa.

    *3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    R410A

    SPECIFICATIONS

    RCN-KIT3-E

    Wireless

    Remote control (Option)

    Control box

    Fan motorHigh static pressuresilent fan

    Slide type fan system

    Thin type duct connectionopening

    Adaptability to higher static pressures

    High static pressure of 200 Pa

    NEW

    Powerful-Hi can be selected. Sound level: 100VN(S)VF1 44dB, 125VN(S)VF 45dB, 140VN(S)VF 47dBAir flow: 100VN(S)VF1 36m3/min, 125VN(S)VF 39m3/min, 140VN(S)VF 48m3/min

    Set model name F DU100VNVF1 F DU125VNVF

    Indoor unit FDU100VF1 FDU125VFOutdoor unit FDC100VN FDC125VN

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cool ing capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 )

    Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 )

    Power consumption Cooling/Heating kW 2.80 / 3.02 3.90 / 3.88

    EER/COP Cooling/Heating 3.57 / 3.71 3.21 / 3.61

    Inrush current 220/230/240 VA

    5 5

    Max. running current 25 27

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    65 / 65 67 / 67

    Outdoor Cooling/Heating 70 / 70 72 / 72

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29

    Heating (Hi/ Me/Lo) 38 / 36 / 30 40 / 34 / 29

    Outdoor Cooling/Heating 49 / 49 50 / 51

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    28 / 25 / 19 32 / 26 / 20

    Heating (Hi/ Me/Lo) 28 / 25 / 19 32 / 26 / 20

    Outdoor Cooling/Heating 75 / 73 75 / 73

    External static pressure*2 Pa Standard:60 Max:200

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    280 x 1,370 x 740

    Outdoor 845 x 970 x 370

    Net weightIndoor

    kg54

    Outdoor 81

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.50

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*3

    Heating -20~20

    Air filter Procure locally

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E

    Set model name FDU140VNVF FDU100VSVF1 FDU125VSVF FDU140VSVF FDU200VSVF FDU250VSVF

    Indoor unit FDU140VF FDU100VF1 FDU125VF FDU140VF FDU200VF FDU250VF

    Outdoor unit FDC140VN FDC100VS FDC125VS FDC140VS FDC200VS FDC250VS

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz

    Nominal cooling capacity (Min~Max) kW 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0) 14.0 ( 5.0 ~ 14.5) 20.0 (7.0 ~ 22.4 ) 25.0 ( 10.0 ~ 28.0)

    Nominal heating capacity (Min~Max) kW 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 22.4 ( 7.6 ~ 25.0 ) 28.0 ( 9.5 ~ 31.5 )

    Power consumption Cooling/Heating kW 4.95 / 4.69 2.80 / 3.02 3.90 / 3.80 4.95 / 4.6950Hz:6.59 / 6.08 50Hz:9.91 / 8.50

    60Hz:6.58 / 5.84 60Hz:10.21 / 8.22

    EER/COP Cooling/Heating 2.83 / 3.41 3.57 / 3.71 3.21 / 3.61 2.83 / 3.4150Hz:3.03 / 3.68 50Hz:2.52 / 3.29

    60Hz:3.04 / 3.84 60Hz:2.45 / 3.41

    Inrush current 220/230/240 VA

    5 5 5 5 5 5

    Max. running current 28 16 18 19 24 27

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    70 / 70 65 / 65 67 / 67 70 / 70 75 / 75 76 / 76

    Outdoor Cooling/Heating 73 / 73 70 / 70 72 / 72 73 / 73 74 / 74 74 / 74

    Soundpressure

    level*1

    IndoorCooling (Hi/Me/Lo) 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 51 / 51 52 / 52

    Heating (Hi/ Me/Lo) 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 51 / 51 52 / 52

    Outdoor Cooling/Heating 51 / 51 49 / 49 50 / 51 51 / 51 57 / 57 57 / 58

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 51(Hi) / 60(Hi) 68(Hi) / 80(Hi)

    Heating (Hi/ Me/Lo) 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 51(Hi) / 60(Hi) 68(Hi) / 80(Hi)

    Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 150 / 145

    External static pressure*2 Pa Standard:60 Max:200 Standard:100 Max:200

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    280 x 1,370 x 740 360 x 1,570 x 830

    Outdoor 845 x 970 x 370 1,300 x 970 x 370 1,505 x 970 x 370

    Net weightIndoor

    kg54 92

    Outdoor 81 83 122 140

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8") 9.52(3/8") / 25.4(1") 12.7(1/2") / 25.4(1")

    Refrigerant line (one way) length m 50 Max.70

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15 Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*3 -15~43*3

    Heating -20~20 -15~20

    Air filter Procure locally

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    22

    R410A

    RCN-KIT3-E

    Wireless

    FDUM 100/125/140

    RC-E5RC-EX1A

    Wired

    RCH-E3

    Filter kit (option)

    UM-FL3EF : for 100, 125, 140

    external static pressure loss:5pa

    Remote control (Option)

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    External static pressure of indoor units is 60Pa.*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level

    become 5dB(A) higher at external static pressure of 100Pa.

    *3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Powerful-Hi can be selected. Sound level: 100VN(S)VF1 44dB, 125VN(S)VF 45dB, 140VN(S)VF 47dBAir flow: 100VN(S)VF1 36m3/min, 125VN(S)VF 39m3/min,140VN(S)VF 48m3/min

    FDUM

    DUCT CONNECTED -Low/Middle Static pressure-

    [ INDOOR UNIT ]Micro Inverter

    Dimensions : refer to page 14

    Set model name FD UM 10 0V NV F1 FDU M12 5V NV F FD UM 14 0VN VF FD UM1 00 VS VF1 FD UM 12 5VS VF FD UM1 40 VS VF

    Indoor unit FDUM100VF1 FDUM125VF FDUM140VF FDUM100VF1 FDUM125VF FDUM140VF

    Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz

    Nominal cooling capaci ty (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )

    Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )

    Power consumption Cooling/Heating kW 2.80 / 3.02 3.90 / 3.88 4.95 / 4.69 2.80 / 3.02 3.90 / 3.88 4.95 / 4.69

    EER/COP Cooling/Heating 3.57 / 3.71 3.21 / 3.61 2.83 / 3.41 3.57 / 3.71 3.21 / 3.61 2.83 / 3.41

    Inrush current 220/230/240 VA

    5 5 5 5 5 5

    Max. running current 24 24 24 15 15 15

    Sound powerlevel*

    1

    Indoor Cooling/Heating

    dB(A)

    65 / 65 67 / 67 70 / 70 65 / 65 67 / 67 70 / 70

    Outdoor Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30

    Heating (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30

    Outdoor Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51

    Air flow

    IndoorCooling (Hi/Me/Lo)

    m

    3

    /min

    28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22

    Heating (Hi/Me/Lo) 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73

    External static pressure*2 Pa Standard:60 Max:100

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    280 x 1,370 x 740

    Outdoor 845 x 970 x 370

    Net weightIndoor

    kg54

    Outdoor 81 83

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.50

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*3

    Heating -20~20

    Air filter Filter kit : UM-FL3EF (option)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    23

    Remote control(Option)

    R410A

    FDEN 100/125/140

    RCN-E1R

    Wireless

    RC-E5RC-EX1A

    Wired

    RCH-E3

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural

    wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Powerful-Hi can be selected. Sound level: 100VN(S)VF1 46dB, 125/140VN(S)VF 50dBAir flow: 100VN(S)VF1 28m3/min, 125/140VN(S)VF 32m3/min

    FDEN

    CEILING SUSPENDED

    Dimensions : refer to page 16

    Set model name FD EN 10 0V NVF1 FD EN 125V NVF FD EN 14 0V NV F FD EN 10 0VS VF1 FD EN 12 5V SVF FDE N14 0VS VFIndoor unit FDEN100VF1 FDEN125VF FDEN140VF FDEN100VF1 FDEN125VF FDEN140VF

    Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz

    Nominal cool ing capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )

    Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )

    Power consumption Cooling/Heating kW 2.85 / 2.97 4.45 / 4.08 5.80 / 4.92 2.85 / 2.97 4.45 / 4.08 5.80 / 4.92

    EER/COP Cooling/Heating 3.51 / 3.77 2.81 / 3.43 2.41 / 3.25 3.51 / 3.77 2.81 / 3.43 2.41 / 3.25

    Inrush current 220/230/240 VA

    5 5 5 5 5 5

    Max. running current 24 24 26 15 15 15

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    64 / 64 67 / 67 67 / 67 64 / 64 67 / 67 67 / 67

    Outdoor Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43

    Heating (Hi/Me/Lo) 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43

    Outdoor Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    26 / 23 / 21 29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23

    Heating (Hi/Me/Lo) 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23

    Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    250 x 1,620 x 690

    Outdoor 845 x 970 x 370

    Net weightIndoor

    kg49

    Outdoor 81 83

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.50

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -20~20

    Air filter, Q'ty Pocket Plastic net x2(Washable)

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    24

    R410A

    RCN-KIT3-E

    Wireless remote control (Option)

    Dimensions : refer to page 18

    FDF

    FLOOR STANDING

    [ INDOOR UNIT ]Micro Inverter

    FDF 100/125/140

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural

    wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Powerful-Hi can be selected. Sound level:100VN(S)VD1 54dB, 125/140VN(S)VD 54dBAir flow: 100VN(S)VD1 29m3/min, 125/140VN(S)VD 29m3/min

    Set model name FDF100VNVD1 FDF125VNVD FDF140VNVD FDF100VSVD1 FDF125VSVD FDF140VSVD

    Indoor unit FDF100VD1 FDF125VD FDF140VD FDF100VD1 FDF125VD FDF140VD

    Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz

    Nominal cooling capaci ty (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )

    Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )

    Power consumption Cooling/Heating kW 3.12 / 3.10 4.40 / 4.36 5.15 / 5.31 3.12 / 3.10 4.40 / 4.36 5.15 / 5.31

    EER/COP Cooling/Heating 3.21 / 3.61 2.84 / 3.21 2.72 / 3.01 3.21 / 3.61 2.84 / 3.21 2.72 / 3.01

    Inrush current 220/230/240 VA

    5 5 5 5 5 5

    Max. running current 24 24 24 15 15 15

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    65 / 65 73 / 73 73 / 73 65 / 65 73 / 73 73 / 73

    Outdoor Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73

    Soundpressurelevel*1

    IndoorCooling (Hi/Me/Lo) 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44

    Heating (Hi/Me/Lo) 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44

    Outdoor Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19

    Heating (Hi/Me/Lo) 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19

    Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    1,850 x 600 x 320

    Outdoor 845 x 970 x 370

    Net weightIndoor

    kg52

    Outdoor 81 83

    Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")

    Refrigerant line (one way) length m Max.50

    Vertical height differences Outdoor is higher/lower m Max.30 / Max.15

    Outdoor operatingtemperature range

    CoolingC

    -15~43*2

    Heating -20~20

    Air filter, Q'ty Plastic net x 1(Washable)

    Remote control wired:RC-E5 (installed) wireless:RCN-KIT3-E (option)

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    25

    FDC200VS(8.0HP)

    FDC71VNX(3.0HP)

    FDC250VS(10.0HP)

    FDC71VNP(3.0HP)

    FDC90VNP(3.5HP)

    OUTDOOR UNIT (1.5-10.0HP)

    Installation workabilityEnhanced installation workability thanks to the extended pipe length longest levelin the industry and pre-charged refrigerant.

    Refrigerant precharged piping length extends up to 30m. This eliminates the need to add refrigerant on site, which sets it free from trouble of

    excessive or insufficient charging of refrigerant, and allows carrying out the installation smoothly. That of Hyper inverter 1.5~2.5HP & Standard

    inverter is up to 15m.

    Point

    1Piping length 100m (Hyper Inverter 4~6HP)

    Point

    2 Refrigerant precharged piping length extending to 30m

    Hyper InverterHyper Inverter

    Micro InverterMicro Inverter Standard InverterStandard Inverter

    FDC125VNXFDC125VSX

    (5.0HP)

    FDC140VNXFDC140VSX

    (6.0HP)

    FDC100VNXFDC100VSX

    (4.0HP)

    SRC40ZJX-SSRC50ZJX-S*SRC60ZJX-S*(1.5HP~2.5HP)

    *SRC50/60ZJX-S is common for both of outdoor units ofSRK50/60ZJX-S (Residential Air-conditioners) and 1.5,2, 2.5HP of Inverter Packaged Air-Conditioners.Common components make for easy inventory controland the installation procedure will be the same.

    Due to application of blue coated fins (KS101) for the heatexchanger of new outdoor unit, corrosion resistance has beenimproved compared to current models.

    Blue Fin(3~10HP)

    This kit is recommended to be used in an area where thelowest temperature drops below 0C.

    Base heater kit(option)

    CW-H-E1applied forFDC71VNXFDC100~250VN,VSFDC100~140VNX,VSX

    Heightdifference(Outdoor higher

    than Indoor)

    Pipinglength

    Micro Inverter Standard Inverter

    HP

    1.5~2.5

    3

    4~6

    30m

    50m

    100m

    20m

    30m

    30m

    Piping length Height difference

    50m

    70m

    30m

    30m

    Piping length Height differenceHP

    4~6

    8.10

    30m 20m

    Piping length Height difference

    3.3.5

    HP

    FDC100VNFDC125VNFDC140VN

    FDC100VSFDC125VSFDC140VS

    (4.0HP~6.0HP)

    Refer to our Technical Manual in detail

    Installation workability (FDC200VS,250VS)Using piping attachment that has flared connection and

    brazed connection ends, there is no need conduct

    brazing work inside the outdoor unit.Brazedconnection22.2mm

    232mm

    Flared

    connection19.05mm

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    26

    Standard Inverter [ INDOOR UNIT ]

    4way

    FDTLow/Middle Static pressure

    FDUMHigh Static pressure

    FDU

    FDEN FDF Wired

    RC-E5 RCH-E3RC-EX1A

    Remote control(Option)

    Wireless

    RCN-KIT3-E

    (For FDU, FDUM, FDF)RCN-E1R

    (For FDEN)RCN-TC-36W-E

    (For FDT)

    Filter kit(option)

    UM-FL2EF : for 71

    UM-FL3EF : for 100

    CEILING CASSETTE DUCT CONNECTED

    CEILING SUSPENDED FLOOR STANDING

    SPECIFICATIONS

    (For FDT, FDU, FDUM, FDE)

    (For FDUM)external static pressure loss:5pa

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural

    wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Poewrful-Hi for FDT can be selected. Sound level : FDT71VNPVF1 46dB(A), FDT90VNPVF1 51dB(A) Air flow : FDT71VNPVF1 28m3/min, FDT90VNPVF1 37m3/minPoewrful-Hi for FDU can be selected. Sound level : FDU71VNPVF1 38dB(A), FDU90VNPVF1 44dB(A) Air flow : FDU71VNPVF1 24m3/min, FDU90VNPVF1 36m3/min

    NEW

    Standard Inverter

    Set model name FDT71VNPVF1 FDT90VNPVF1 FDU71VNPVF1 FDU90VNPVF1

    Indoor unit FDT71VF1 FDT100VF1 FDU71VF1 FDU100VF1

    Outdoor unit FDC71VNP FDC90VNP FDC71VNP FDC90VNP

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cooling capacity (Min~Max) kW 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 ) 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 )

    Nominal heating capacity (Min~Max) kW 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 ) 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 )

    Power consumption Cooling/Heating kW 2.50 / 1.90 2.67 / 2.19 2.63 / 1.96 2.65 / 2.25

    EER/COP Cooling/Heating 2.84 / 3.74 3.37 / 4.11 2.70 / 3.62 3.40 / 4.00

    Inrush current 220/230/240 VA

    5 5 5 5

    Max. running current 14.5 18.0 14.5 18.0

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    64 / 64 65 / 65 65 / 65 65 / 65

    Outdoor Cooling/Heating 67 / 67 69 / 69 67 / 67 69 / 69

    Sound

    pressurelevel*1

    IndoorCooling (Hi/Me/Lo) 35 / 33 / 31 40 / 37 / 35 33 / 29 / 25 38 / 36 / 30

    Heating (Hi/Me/Lo) 35 / 33 / 31 40 / 37 / 35 33 / 29 / 25 38 / 36 / 30Outdoor Cooling/Heating 54 / 54 57 / 55 54 / 54 57 / 55

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    21 / 19 / 17 27 / 24 / 20 19 / 15 / 10 28 / 25 / 19

    Heating (Hi/Me/Lo) 21 / 19 / 17 27 / 24 / 20 19 / 15 / 10 28 / 25 / 19

    Outdoor Cooling/Heating 36 / 36 63 / 49.5 36 / 36 63 / 49.5

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    unit: 246 x 840 x 840panel: 35 x 950 x 950

    unit: 298 x 840 x 840panel: 35 x 950 x 950

    280 x 950 x 635 280 x 1,370 x 740

    Outdoor 640 x 800 x 290 750 x 880 x 340 640 x 800 x 290 750 x 880 x 340

    Net weightIndoor

    kg29.5 ( unit: 24 panel: 5.5 ) 32.5 ( unit: 27 panel: 5.5 ) 34 54

    Outdoor 45 57 45 57

    Ref.piping size Liquid/Gas mm 6.35 / 12.7 9.52 / 15.88 6.35 / 12.7 6.35 / 15.88

    Refrigerant line (one way) length m 30

    Vertical height differences Outdoor is higher/lower m Max.20 / Max.20

    Outdoor operatingtemperature range

    CoolingC

    -15~46*2

    Heating -15~20

    Air filter, Q'ty Pocket Plastic net x1(Washable) Procure locally

    Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E

  • 5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...

    http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe

    27

    SPECIFICATIONS

    SPECIFICATIONS

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7 CDB, 6CWB.

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural

    wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Powerful-Hi can be selected. Sound level: FDF71VNPVD1 42dB, FDF90VNPVD1 54dB Air flow: FDF71VNPVD1 20m3/min, FDF90VNPVD1 29m3/min

    The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

    *1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural

    wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

    Poewrful-Hi for FDUM can be selected. Sound level : FDUM71VNPVF1 38dB(A), FDUM90VNPVF1 44dB(A) Air flow : FDUM71VNPVF1 24m3/min, FDUM90VNPVF1 36m3/minPoewrful-Hi for FDEN can be selected. Sound level : FDEN71VNPVF1 50dB(A), FDEN90VNPVF1 46dB(A) Air flow : FDEN71VNPVF1 20m3/min, FDEN90VNPVF1 28m3/min

    Standard Inverter

    Set model name FDF71VNPVD1 FDF90VNPVD1

    Indoor unit FDF71VD1 FDF100VD1

    Outdoor unit FDC71VNP FDC90VNP

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cooling capacity (Min~Max) kW 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 )

    Nominal heating capacity (Min~Max) kW 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 )

    Power consumption Cooling/Heating kW 2.63 / 2.08 2.79 / 2.25

    EER/COP Cooling/Heating 2.70 / 3.41 3.23 / 4.00

    Inrush current 220/230/240 VA

    5 5

    Max. running current 14.5 18.0

    Sound powerlevel*1

    Indoor Cooling/Heating

    dB(A)

    61 / 61 65 / 65

    Outdoor Cooling/Heating 67 / 67 69 / 69

    Soundpressurelevel*1

    Indoor Cooling (Hi/Me/Lo) 39 / 35 / 33 50 / 48 / 44Heating (Hi/Me/Lo) 39 / 35 / 33 50 / 48 / 44

    Outdoor Cooling/Heating 54 / 54 57 / 55

    Air flowIndoor

    Cooling (Hi/Me/Lo)

    m3/min

    18 / 16 / 14 26 / 23 / 19

    Heating (Hi/Me/Lo) 18 / 16 / 14 26 / 23 / 19

    Outdoor Cooling/Heating 36 / 36 63 / 49.5

    Exteriordimensions

    IndoorHeightxWidthxDepth mm

    1,850 x 600 x 320

    Outdoor 640 x 800 x 290 750 x 880 x 340

    Net weightIndoor

    kg49 52

    Outdoor 45 57

    Ref.piping size Liquid/Gas mm 6.35 / 12.7 6.35 / 15.88

    Refrigerant line (one way) length m 23

    Vertical height differences Outdoor is higher/lower m Max.20 / Max.20

    Outdoor operatingtemperature range

    CoolingC

    -15~46*2

    Heating -15~20

    Air filter, Q'ty Plastic net x1(Washable)

    Remote control (option) wired:RC-E5 installed wireless:RCN-KIT3-E

    Standard Inverter

    Set model name FDUM71VNPVF1 FDUM90VNPVF1 FDEN71VNPVF1 FDEN90VNPVF1

    Indoor unit FDUM71VF1 FDUM100VF1 FDEN71VF1 FDEN100VF1

    Outdoor unit FDC71VNP FDC90VNP FDC71VNP FDC90VNP

    Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz

    Nominal cooling capacity (Min~Max) kW 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 ) 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 )

    Nominal heating capacity (Min~Max) kW 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 ) 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 )

    Power consumption Cooling/Heating kW 2.63 / 1.96 2.65 / 2.25 2.50 / 1.96 2.75 / 2.25

    EER/COP Cooling/Heating 2.70 / 3.62 3.40 / 4.00 2.84 / 3.62 3.27 / 4.00

    Inrush current 220/230/240 VA

    5 5 5 5

    Max. running current 14.5 18.0 14.5 18.0

    Sound powerlevel*

    1

    Indoor Cooling/Heating

    dB(A)

    65 / 65