1 A Comprehensive Approach to Energy Management for Hotels & Resorts PRESENTED BY: ROBERT GREENWALD, PEng, MBA May 18, 2011

Upload: others

Post on 05-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1

A Comprehensive Approach to Energy Management for Hotels & Resorts

PRESENTED BY:

ROBERT GREENWALD, PEng, MBA May 18, 2011

Page 2: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

22

A Comprehensive Approach to Energy

Management

Continuous Improvement

Page 3: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

33

Energy Management Technical Aspects

Page 4: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

44

A Technical Approach: The Seven Steps

3. UnderstandWhen

4. UnderstandWhere

6. MaximizeEfficiency

5. EliminateWaste

7. OptimizeSupply

Find the Savings

Opportunities

2. CompareYourself

1. UnderstandCosts

UnderstandPresentUsage

1. From the

point of

Purchase

2. To the point of

End-Use

3. And, back to

the point of

Purchase

(or supply)

Source: NRCan Dollars to $ense Workshop

Page 5: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

55

Step 1Understand Cost

• Electricity

– Demand ($/kW or KVA)

– Energy ($/kWh)

• Natural Gas

– Supply ($/m3 or $/GJ or lbs steam)

– Delivery ($/m3 or $/GJ)

• Contracted Daily Demand ($/m3/day)

• What is the incremental cost?

– The next unit used or saved

– How about Carbon Taxes, fees, HST…

Page 6: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

66

Step 2 Sector Benchmarks & Good/Best

Practices

Source: http://oee.nrcan.gc.ca/publications/commercial/m144-10-2003e.cfm?attr=16

Page 7: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

77

Step 3 Daily Interval ProfilesPeak Demand: 2107.9 kW on a 15 minute interval.

PF at Peak: 0%

When:

Integral of Overview Period Energy 1,052,289 kWh 26-Jun-07 to 26-Jul-07 Integral of Peak Week Energy 247,285 kWh 08-Jul-07 to 14-Jul-07

Integral of Peak Day Energy 40,202 kWh 09-Jul-07 Integral of 3 Days Energy 113,988 kWh 08-Jul-07 to 10-Jul-07

Demand Profiles for: ACUTE CARE

7/9/07 10:45 AM Sun Mon Tue Wed Thu Fri Sat

3 Days - Around Peak Day

0

500

1000

1500

2000

2500

0:0

0

3:0

0

6:0

0

9:0

0

12

:00

15

:00

18

:00

21

:00

0:0

0

3:0

0

6:0

0

9:0

0

12

:00

15

:00

18

:00

21

:00

0:0

0

3:0

0

6:0

0

9:0

0

12

:00

15

:00

18

:00

21

:00

Time / Date

kilo

watt

s (

kW

)

kWDay of Peak

0

500

1000

1500

2000

2500

0:0

0

1:0

0

2:0

0

3:0

0

4:0

0

5:0

0

6:0

0

7:0

0

8:0

0

9:0

0

10:0

0

11:0

0

12:0

0

13:0

0

14:0

0

15:0

0

16:0

0

17:0

0

18:0

0

19:0

0

20:0

0

21:0

0

22:0

0

23:0

0

Time / Date

kil

ow

att

s (

kW

)

kW

Week Around Peak

0

500

1000

1500

2000

2500

0:0

0

6:0

0

12:0

0

18:0

0

0:0

0

6:0

0

12:0

0

18:0

0

0:0

0

6:0

0

12:0

0

18:0

0

0:0

0

6:0

0

12:0

0

18:0

0

0:0

0

6:0

0

12:0

0

18:0

0

0:0

0

6:0

0

12:0

0

18:0

0

0:0

0

6:0

0

12:0

0

18:0

0

Time / Date

kil

ow

att

s (

kW

)

kWOverview Profile

0

500

1000

1500

2000

2500

26

27

28

29

30 1 2 3 4 5 6 7 8 9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

Time / Date

kil

ow

att

s (

kW

)

kW

Page 8: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

88

Step 4 Understand Where Your Buildings

Use Energy

• Focus your efforts

• Establish a basis for savings calculations

Source: http://oee.nrcan.gc.ca/publications/commercial/m144-10-2003e.cfm?attr=16

Page 9: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

99

Step 5 Eliminate Energy Waste –

Match the Need

• Turn it off– Lights, fans, pumps, conveyors

– Compressed air leaks

– Steam traps

• Turn it down– Temperature, water & air flow

– Compressed air & steam pressure & flow

• Control it– Exhaust / make-up air balance

– Light levels

Page 10: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1010

Step 6 Maximize Efficiency

• Filters and lubrication

• Clean heat exchangers, pipes, ducts and coils

• Motor conditions

– voltage & cooling

• Combustion efficiencies

• Sequence compressors, pumps and fans

• Equipment replacement (boilers, chillers, rooftop units)

Page 11: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1111

Step 7 Optimize Energy Supply

• Heat recovery

• Renewable energy

– Solar PV

– Solar thermal

• On-site generation

• Revised supply contracts

Page 12: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1212

EMOs in Energy

Consuming

Systems

Establish Need

Eliminate Waste

Increase Efficiency

Optimize Supply

Page 13: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1313

Hotel Examples Waste, Efficiency and Supply

Page 14: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1414

Economizer Program for Tower Air

Handlers

• Situation: mechanical cooling when

opportunity for free cooling

• Measure: program to modulate the outside

and atrium air dampers

Cost Savings:

$4,000 / yr

Page 15: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1515

Chilled Water and Condenser Water

Supply Temperature Setpoint Reset

Cost Savings: $5,000 / yr

• Situation: Chilled water supply temperature

fixed at 5C, condenser water supply

temperature fixed at 26C.

• Measure: Chilled water system efficiency

improvements by raising chilled water

temperature (based on valve position), and

lowering condenser water temperature

(based on OAT).

Page 16: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1616

Water Side Economizer

• Situation: Hotel has a year-round requirement of

chilled water. Chiller operating inefficiently at low load

conditions.

• Measure: Install a plate-and-frame heat exchanger

to generate chilled water using the cooling tower in

the winter. Allows for chiller to be shut off. Energy

usage of cooling tower fans is far less than chiller.

Page 17: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1717

Pool Humidity Control

• Situation: fresh air brought in to control

humidity. Humidity sensor error, coupled

with low setpoint (45%) result in excessive

fresh air requirements.

• Measure: increase humidity setpoint to

60% and re-calibrate humidity sensor

Cost Savings: $6,200 / yr

Page 18: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1818

Install Pool Dehumidifier for Pool

Heating

• Situation: Humidity in pool air provides

opportunities to heat pool water

• Measure: Install pool dehumidifier (heat

pump recovering latent energy) to pre-heat

pool water, on facility roof due to space

constraints.

Cost Savings:

$11,400 / yr

Page 19: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

1919

Reduce Run Hours of Slide Pump & Install VFD

• Situation: Pool water slide

pump operates continuously

and flow is excessive, requiring

throttling. Throttling at the outlet

is energy-inefficient. Throttling

at the inlet can damage the

pump (cavitation).

• Measure: Install occupancy

sensor and Variable Frequency

Drive

Cost Savings: $1,400 / yr

Occ. Sensor to

turn on pump

VFD runs at a

reduced speed

to match flow

requirements

Page 20: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2020

Integrate Room Booking System with

DDC

• Situation: 200 rooms conditioned

continuously to 18°C to 28°C setpoints.

• Measure: Put empty rooms in unoccupied

setback mode by integrating room booking

system with DDC

Page 21: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2121

Implement a Key Card Energy Control

System for Hotel Rooms

• Situation: Additional savings possible

through key card energy control system.

• Measure: Occupant insert key cards to

activate switch. Linked to the DDC system

and puts room into occupied mode.

Page 22: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2222

Banquet or Conference Hall Air

Handler Control Optimization

• Situation: Air handling systems have

demand control ventilation, but CO2 sensor

reads 2,000 ppm continuously, resulting in

100% fresh air brought in and heated/cooled.

Schedules also found to be excessively long.

• Measure: Re-calibrate CO2 sensor and trim

operating hours.

Cost Savings: $3,600 / yr

Page 23: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2323

Lighting: LED Lamp Replacement

• Hotel in Downtown Vancouver replaced lighting

with dimmable LED downlights for conference

and boardrooms and exterior lighting.

• A lamp and PAR lamp shapes

Page 24: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2424

Lighting: Chandelier Options

Relamped incandescent

flame shaped lamps with

dimmable 8W cold

cathode compact

fluorescent lamps

Relamped incandescent

lamps with dimmable

LED’s

Page 25: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2525

Lighting: Integrate Lighting Upgrades

into Replacement Schedule

• Measure: When larger lighting upgrade are

not possible, integrate lighting upgrades into

maintenance / replacement schedule.

• Replace:

• 400W HID with lower wattage

(330W) energy efficient lamp

• 50W MR16 with 37W

MR16 IR

Page 26: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2626

Lighting – Use LED Technologies in

Parkades and Parking lots

Page 27: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2727

Lethbridge Lodge

• Comparing compressor power consumption of

high efficiency vs. standard products.

• Results: Payback between 15 and 25 years

• The longer operating hours per year or

increase of electricity cost, the shorter will be

the payback for the incremental cost of $30K

Page 28: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2828

Saskatoon Radisson:

Roof-Top Unit Replacement

• Comparison of 5 ton rooftop units

• Landmark Series (SEER 13) vs.

Energence Series (SEER 17)

• Price difference $1,000

• Simple Payback 5 years (based on 15%

annual compressor operation time)

• Recommendation: Higher efficiency

SEER 17 unit

high

efficiency

condensing

boilers

Page 29: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

2929

Cascadia Heating Plant Upgrade

→ Efficiency of the upgraded plant is expected

to be 20% higher, resulting in approx 2,500

GJ annual savings

DHW heaters Boilers

Page 30: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3030

Regina Inn: Life Cycle Costs

Analysis

• Three Retrofit Options for Variable Refrigerant

Flow (VRF) Systems

• VRF with ceiling mounted horizontal

concealed units

• VRF with wall mounted units

• PTAC in outside wall mounted units

Page 31: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3131

Energy Management Behavioural Aspects

Page 32: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3232

Employee Engagement Programs

People, not just technology, control, use and

save energy.

Employee engagement programs

about involving staff and

harnessing their abilities to reduce

energy . . . every day.

Page 33: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3333

Behaviours Change

• Select high impact and “easy to

target” behaviours first.

• Identify the target audience.

• Identify barriers and benefits for

each behaviour

• Use techniques / strategies to

address barriers

Page 34: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3434

Coast Hotels “Coast Saver” Program

• Each property created a small “e.team”

• Housekeeping and maintenance staff

• Competed to create and implement energy

saving initiatives

• Each initiative earned a credit

• Winners - $250 each and a pizza lunch

Page 35: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3535

BOMA Energy Training

• Addresses technology, behaviour and organizational

• Online training for building operations staff on energy

management

• Self-learning format

• Participants learn at their own pace and have access from

remote locations

• Designed for commercial buildings but transferrable to Health

Care Sector.

www.bomalearning.com

Page 36: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3636

The Topics

www.bomalearning.com

Page 37: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3737

Animation and Graphics

www.bomalearning.com

Page 38: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3838

Interactive Activities

www.bomalearning.com

Page 39: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

3939

Energy Management Organizational Aspects

Page 40: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4040

Leadership

Demonstrated

Corporate Commitment

UnderstandingEnergy Performance and

Savings Opportunities

PlanningTargets, KPI’s

Plans

PeopleAccountabilit ies

Awareness & training

Resourcing

Financial

Management

Supply

Management

Operations &

MaintenanceOperating procedures

Maintenance

Plant &

Equipment

Monitoring &

Reporting

Achievement

Existing design

New Plant Design/selection

Innovation & new technology

Metering and monitoring

Reporting & Control

Documentation & records

Purchasing Procedures

Quality and Reliabi li ty

Load Management

Capital Expenditure

Operating Budgets

Leadership

Demonstrated

Corporate Commitment

UnderstandingEnergy Performance and

Savings Opportunities

PlanningTargets, KPI’s

Plans

PeopleAccountabilit ies

Awareness & training

Resourcing

Financial

Management

Supply

Management

Operations &

MaintenanceOperating procedures

Maintenance

Plant &

Equipment

Monitoring &

Reporting

Achievement

Existing design

New Plant Design/selection

Innovation & new technology

Metering and monitoring

Reporting & Control

Documentation & records

Purchasing Procedures

Quality and Reliabi li ty

Load Management

Capital Expenditure

Operating Budgets

Leadership

Demonstrated

Corporate Commitment

UnderstandingEnergy Performance and

Savings Opportunities

PlanningTargets, KPI’s

Plans

PeopleAccountabilit ies

Awareness & training

Resourcing

Financial

Management

Supply

Management

Operations &

MaintenanceOperating procedures

Maintenance

Financial

Management

Supply

Management

Operations &

MaintenanceOperating procedures

Maintenance

Plant &

Equipment

Monitoring &

Reporting

Plant &

Equipment

Monitoring &

Reporting

Achievement

Existing design

New Plant Design/selection

Innovation & new technology

Metering and monitoring

Reporting & Control

Documentation & records

Purchasing Procedures

Quality and Reliabi li ty

Load Management

Capital Expenditure

Operating Budgets

Source: Hatch Consulting: An Overview of One-2-Five Energy Diagnostic and Benchmarking Tool

Organizational Characteristics

Page 41: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4141

ANSI/MSE 2000:2008

Management System for Energy

Source: tp://innovate.gatech.edu/Default.aspx?tabid=2005

Page 42: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4242

Continuous Improvement

Page 43: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4343

Continuous Improvement for Energy

Measure

Analyze

Take Action

Data

Information

Result

Page 44: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4444

Page 45: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4545

PUMA Dashboard

Page 46: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4646

PUMA Meter History and Cost

Page 47: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4747

Targeting a Level of Energy Use &

Measuring Savings

Page 48: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4848

Resources

Page 49: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

4949

Costs of Operating Equipment

Do-It-Yourself using RETScreen® v4

Download from www.retscreen.net

Page 51: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

51

Technical Web Resources

Natural Resources Canada

www.oee.nrcan.gc.ca/publications

US Dept of Energy

http://www.energy.gov/

UK Gov’t Carbon Trust

www.carbontrust.co.uk

Energy Star

http://www.energystar.gov/

Page 52: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

5252

Our Firm

Energy management

consulting services to

address technical,

behavioural and

organizational aspects

We design and implement cost effective approaches to address

comfort, efficiency and reliability.

650 energy audits in over 1000 buildings, which is equal to 73 million

square feet of building area audited and 9,000 energy accounts analyzed.

Identified $22 million dollars in annual energy savings equivalent to

taking 18,000 cars off the road every year.

Page 53: A Comprehensive Approach to Energy Management for Hotels & … · 2018-05-03 · 7 Step 3 Daily Interval Profiles Peak Demand: 2107.9 kW on a 15 minute interval. PF at Peak: 0% When:

53

Thank You!