TEST REPORT FOR SOIL RESISTIVITY MEASURMENT SITE: 400KV VELODA SS DATE OF TESTING: 26.10.2012 A-PDF Merger DEMO : Purchase from www.A-PDF.com to remove the watermark

Upload: hoangque

Post on 27-May-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

TEST REPORTFOR SOIL

RESISTIVITYMEASURMENT

SITE: 400KV VELODA SS

DATE OF TESTING: 26.10.2012

A-PDF Merger DEMO : Purchase from www.A-PDF.com to remove the watermark

Wenner Test Method

Fig. shows the general measurement setup. The four earth probes should be driven into theground in a straight line, at a distance ‘a’ metres apart and driven to a depth of ‘P’ cm.

The maximum depth of the probe should not exceed 20cm nor exceed 1/20TH of the probe spacingdistance ‘a’. A series of resistance readings are taken for various spacings of the probes. For large sitesthe maximum spacings are increased to enable the soil resistivity to be assessed at a greater depth.

The four probes should be connected to the tester, with the outer probes connected to the C1 and C2terminals, and the inner probes to the P1 and P2 terminals. The instrument should be kept in a centralposition and a series of resistance measurements made as the four electrodes are moved out in equaldistances from the central point. A calculation is made to determine the average soil resistivity of alllayers of soil between the surface and a depth ‘d’ which is taken to be ¾ of the separation distance ‘a’.The meter should be left on to allow the built in filters to operate and the value after 30 seconds shouldbe taken. If the reading is varying significantly, this may be due to :-• Electrical interference• High contact resistance at the test probes• Damaged test leads• Reading at the lower limit of the instrument’s measuring capability

The apparent soil resistivity is then given by ρ=2paR (Ohm-meter)where:-ρ= ground resistivity in Ohm-meterp = 3.142a = electrode spacing in metresR = measured resistance in O at spacing 'a'

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

1 2.16 0.54 0.03 0.04 13.56 6.78 0.94 2.512 2.39 0.64 0.03 0.03 15.01 8.04 0.94 1.883 0.22 0.08 0.07 0.04 1.38 1.00 2.20 2.514 2.18 0.35 0.07 0.06 13.69 4.40 2.20 3.775 2.13 0.24 0.07 0.06 13.38 3.01 2.20 3.776 0.53 0.28 0.13 0.09 3.33 3.52 4.08 5.657 0.34 0.19 0.12 0.09 2.14 2.39 3.77 5.658 0.33 0.2 0.13 0.09 2.07 2.51 4.08 5.659 0.28 0.13 0.07 0.09 1.76 1.63 2.20 5.65

SITE: 400 KV VELODA SS (400KV SIDE)

Measured Soil Resistance (in Ω)Date: 24-OCT-2012

Calculated Soil Resistivity (in Ω-M)Location

No.Remarks

TEST REPORT OF SOIL RESISTIVITYMEASURMENT

FRO

M E

AST

-SO

UTH

TO

WES

T N

ORT

H

9 0.28 0.13 0.07 0.09 1.76 1.63 2.20 5.6510 0.36 0.24 0.09 0.06 2.26 3.01 2.83 3.7711 0.39 0.24 0.09 0.08 2.45 3.01 2.83 5.0212 0.29 0.19 0.11 0.08 1.82 2.39 3.45 5.0213 0.32 0.21 0.13 0.10 2.01 2.64 4.08 6.2814 0.28 0.17 0.09 0.09 1.76 2.14 2.83 5.6515 0.25 0.17 0.11 0.09 1.57 2.14 3.45 5.6516 0.28 0.18 0.12 0.07 1.76 2.26 3.77 4.4017 0.23 0.15 0.11 0.08 1.44 1.88 3.45 5.0218 0.27 0.18 0.13 0.07 1.70 2.26 4.08 4.4019 0.87 0.18 0.12 0.10 5.46 2.26 3.77 6.2820 0.23 0.13 0.11 0.08 1.44 1.63 3.45 5.0221 0.27 0.15 0.12 0.09 1.70 1.88 3.77 5.6522 0.31 0.16 0.13 0.08 1.95 2.01 4.08 5.0223 0.36 0.17 0.11 0.08 2.26 2.14 3.45 5.0224 0.37 0.19 0.15 0.08 2.32 2.39 4.71 5.0225 0.40 0.21 0.14 0.09 2.51 2.64 4.40 5.6526 0.34 0.22 0.13 0.08 2.14 2.76 4.08 5.0227 0.32 0.28 0.16 0.09 2.01 3.52 5.02 5.6528 0.36 0.22 0.13 0.08 2.26 2.76 4.08 5.0229 0.25 0.19 0.11 0.08 1.57 2.39 3.45 5.0230 0.38 0.20 0.12 0.07 2.39 2.51 3.77 4.40

FRO

M E

AST

-SO

UTH

TO

WES

T N

ORT

H

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

31 0.41 0.21 0.14 0.08 2.57 2.64 4.40 5.0232 0.36 0.19 0.12 0.08 2.26 2.39 3.77 5.0233 0.34 0.21 0.12 0.07 2.14 2.64 3.77 4.4034 0.36 0.22 0.11 0.08 2.26 2.76 3.45 5.0235 0.32 0.21 0.11 0.08 2.01 2.64 3.45 5.0236 0.36 0.19 0.12 0.07 2.26 2.39 3.77 4.4037 0.33 0.21 0.11 0.07 2.07 2.64 3.45 4.40

Date: 25-OCT-2012

LocationNo.

Measured Soil Resistance (in Ω) Calculated Soil Resistivity (in Ω-M)

Remarks

TEST REPORT OF SOIL RESISTIVITYMEASURMENT

SITE: 400 KV VELODA SS (400KV SIDE)

FRO

M N

OET

H-E

AST

TO

SO

UTH

-WES

T

37 0.33 0.21 0.11 0.07 2.07 2.64 3.45 4.4038 0.36 0.23 0.12 0.07 2.26 2.89 3.77 4.4039 0.39 0.24 0.11 0.06 2.45 3.01 3.45 3.7740 0.34 0.25 0.12 0.08 2.14 3.14 3.77 5.0241 0.33 0.21 0.14 0.09 2.07 2.64 4.40 5.6542 0.29 0.16 0.06 0.08 1.82 2.01 1.88 5.0243 0.34 0.21 0.14 0.09 2.14 2.64 4.40 5.6544 0.36 0.22 0.16 0.09 2.26 2.76 5.02 5.6545 0.33 0.2 0.12 0.06 2.07 2.51 3.77 3.7746 0.36 0.21 0.11 0.08 2.26 2.64 3.45 5.0247 0.48 0.19 0.09 0.07 3.01 2.39 2.83 4.4048 0.56 0.21 0.11 0.09 3.52 2.64 3.45 5.6549 0.87 0.24 0.16 0.08 5.46 3.01 5.02 5.0250 2.19 0.59 0.17 0.10 13.75 7.41 5.34 6.2851 1.29 0.69 0.17 0.12 8.10 8.67 5.34 7.5452 2.24 0.82 0.18 0.08 14.07 10.30 5.65 5.0253 1.38 0.28 0.16 0.03 8.67 3.52 5.02 1.8854 1.26 0.31 0.17 0.06 7.91 3.89 5.34 3.7755 1.3 0.43 0.12 0.06 8.16 5.40 3.77 3.7756 1.33 0.37 0.15 0.06 8.35 4.65 4.71 3.7757 1.57 0.41 0.08 0.04 9.86 5.15 2.51 2.5158 1.58 0.38 0.12 0.04 9.92 4.77 3.77 2.5159 1.42 0.34 0.11 0.05 8.92 4.27 3.45 3.1460 1.54 0.39 0.15 0.07 9.67 4.90 4.71 4.40

FRO

M N

OET

H-E

AST

TO

SO

UTH

-WES

T

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

61 0.42 0.2 0.07 0.05 2.64 2.51 2.20 3.1462 0.64 0.24 0.09 0.04 4.02 3.01 2.83 2.5163 0.31 0.26 0.12 0.07 1.95 3.27 3.77 4.4064 0.32 0.22 0.11 0.04 2.01 2.76 3.45 2.5165 0.34 0.24 0.1 0.05 2.14 3.01 3.14 3.1466 0.32 0.22 0.12 0.06 2.01 2.76 3.77 3.77 SI

DE

BORD

ER

AVERAGE SOIL RESISTIVITY FOR 400KV YARD

Calculated Soil Resistivity (in Ω-M)

TEST REPORT OF SOIL RESISTIVITYMEASURMENT

SITE: 400 KV VELODA SS (400KV SIDE)Date: 25-OCT-2012

LocationNo.

Measured Soil Resistance (in Ω) Calculated Soil Resistivity (in Ω-M)

Remarks

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

4.25 3.25 3.66 4.57

FOR ASIA TELECOM

AVERAGE SOIL RESISTIVITY FOR 400KV YARD

Calculated Soil Resistivity (in Ω-M)

DHARMENDRA PRAJAPATI(B.E. ELECTRICAL)

TESTED BY

TEST REPORT OF SOIL RESISTIVITYSITE: 400 KV VELODA SS (400KV SIDE)

Date: 24-OCT-2012

2.00

2.50

3.00

3.50

4.00

4.50

5.00

SOIL RESISTIVITY

SOIL RESISTIVITY OF 400KV SIDE

0.00

0.50

1.00

1.50

2.00

1 MTR 2 MTR 5 MTR 10 MTR

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

1 1.30 1.48 0.42 0.3 8.16 18.59 13.19 18.842 1.33 1.24 0.8 0.19 8.35 15.57 25.12 11.933 0.66 0.62 0.64 0.16 4.14 7.79 20.10 10.054 0.97 0.5 0.22 0.09 6.09 6.28 6.91 5.655 0.93 0.48 0.29 0.08 5.84 6.03 9.11 5.026 0.64 0.28 0.19 0.08 4.02 3.52 5.97 5.027 0.39 0.18 0.15 0.06 2.45 2.26 4.71 3.77

FRO

M E

AST

-NO

RTH

TO

WES

T SO

UTH

TEST REPORT OF SOIL RESISTIVITYMEASURMENT

SITE: 400 KV VELODA SS (220KV SIDE)Date: 26-OCT-2012

LocationNo.

Measured Soil Resistance (in Ω) Calculated Soil Resistivity (in Ω-M)

Remarks

7 0.39 0.18 0.15 0.06 2.45 2.26 4.71 3.778 0.24 0.18 0.12 0.08 1.51 2.26 3.77 5.029 0.25 0.15 0.14 0.06 1.57 1.88 4.40 3.77

10 0.32 0.17 0.11 0.07 2.01 2.14 3.45 4.4011 0.29 0.21 0.15 0.07 1.82 2.64 4.71 4.4012 0.31 0.19 0.14 0.1 1.95 2.39 4.40 6.2813 0.34 0.22 0.18 0.09 2.14 2.76 5.65 5.6514 0.59 0.21 0.13 0.09 3.71 2.64 4.08 5.6515 0.35 0.19 0.13 0.1 2.20 2.39 4.08 6.2816 0.39 0.24 0.18 0.09 2.45 3.01 5.65 5.6517 0.36 0.21 0.16 0.10 2.26 2.64 5.02 6.2818 0.35 0.25 0.17 0.09 2.20 3.14 5.34 5.6519 0.37 0.18 0.12 0.08 2.32 2.26 3.77 5.0220 0.38 0.21 0.14 0.08 2.39 2.64 4.40 5.0221 0.31 0.24 0.18 0.11 1.95 3.01 5.65 6.9122 0.34 0.19 0.12 0.08 2.14 2.39 3.77 5.02

FRO

M E

AST

-NO

RTH

TO

WES

T SO

UTH

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

23 0.27 0.16 0.12 0.08 1.70 2.01 3.77 5.0224 0.29 0.17 0.12 0.08 1.82 2.14 3.77 5.0225 0.28 0.18 0.13 0.09 1.76 2.26 4.08 5.6526 0.28 0.15 0.11 0.07 1.76 1.88 3.45 4.4027 0.22 0.16 0.12 0.08 1.38 2.01 3.77 5.0228 0.32 0.16 0.11 0.07 2.01 2.01 3.45 4.4029 0.26 0.17 0.12 0.09 1.63 2.14 3.77 5.65

LocationNo.

Measured Soil Resistance (in Ω) Calculated Soil Resistivity (in Ω-M)

Remarks

FRO

M N

OET

H-W

EST

TO S

OU

TH -E

AST

TEST REPORT OF SOIL RESISTIVITYMEASURMENT

SITE: 400 KV VELODA SS (220KV SIDE)Date: 26-OCT-2012

29 0.26 0.17 0.12 0.09 1.63 2.14 3.77 5.6530 0.27 0.2 0.12 0.08 1.70 2.51 3.77 5.0231 0.28 0.17 0.12 0.09 1.76 2.14 3.77 5.6532 0.29 0.21 0.13 0.09 1.82 2.64 4.08 5.6533 0.33 0.2 0.15 0.11 2.07 2.51 4.71 6.9134 0.34 0.2 0.14 0.09 2.14 2.51 4.40 5.6535 0.29 0.18 0.13 0.09 1.82 2.26 4.08 5.6536 0.36 0.18 0.12 0.09 2.26 2.26 3.77 5.6537 0.39 0.22 0.11 0.08 2.45 2.76 3.45 5.0238 0.29 0.16 0.11 0.07 1.82 2.01 3.45 4.4039 0.32 0.21 0.13 0.09 2.01 2.64 4.08 5.6540 0.38 0.23 0.14 0.09 2.39 2.89 4.40 5.6541 0.38 0.22 0.13 0.09 2.39 2.76 4.08 5.6542 0.39 0.23 0.17 0.11 2.45 2.89 5.34 6.9143 1.19 0.31 0.16 0.09 7.47 3.89 5.02 5.6544 1.32 0.56 0.31 0.18 8.29 7.03 9.73 11.30

FRO

M N

OET

H-W

EST

TO S

OU

TH -E

AST

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

45 0.37 0.19 0.15 0.12 2.32 2.39 4.71 7.5446 0.37 0.19 0.15 0.11 2.32 2.39 4.71 6.9147 0.25 0.18 0.14 0.09 1.57 2.26 4.40 5.6548 1.21 0.49 0.25 0.12 7.60 6.15 7.85 7.5449 1.36 0.65 0.38 0.21 8.54 8.16 11.93 13.1950 1.52 1.32 0.45 0.35 9.55 16.58 14.13 21.98

SIDE

BO

RDER

AVERAGE SOIL RESISTIVITY FOR 220KV YARD

Calculated Soil Resistivity (in Ω-M)

SITE: 400 KV VELODA SS (220KV SIDE)Date: 26-OCT-2012

LocationNo.

Measured Soil Resistance (in Ω) Calculated Soil Resistivity (in Ω-M)

Remarks

TEST REPORT OF SOIL RESISTIVITYMEASURMENT

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

3.17 3.89 5.90 6.59

(B.E. ELECTRICAL)

FOR ASIA TELECOM

AVERAGE SOIL RESISTIVITY FOR 220KV YARD

Calculated Soil Resistivity (in Ω-M)

TESTED BY

DHARMENDRA PRAJAPATI

TEST REPORT OF SOIL RESISTIVITYMEASURMENTSITE: 400 KV VELODA SS (220KV SIDE)

Date: 26-OCT-2012

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00SOIL RESISTIVITY IN OHM-METER

SOIL RESISTIVITY OF 220KV SIDE

0.00

1 MTR 2 MTR 5 MTR 10 MTR

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

1 0.3 0.15 0.08 0.06 1.88 1.88 2.51 3.772 0.31 0.14 0.06 0.04 1.95 1.76 1.88 2.513 0.24 0.15 0.09 0.04 1.51 1.88 2.83 2.514 0.22 0.12 0.08 0.04 1.38 1.51 2.51 2.515 0.31 0.15 0.09 0.05 1.95 1.88 2.83 3.146 0.28 0.15 0.08 0.04 1.76 1.88 2.51 2.517 0.29 0.13 0.08 0.04 1.82 1.63 2.51 2.51

SITE: 400 KV VELODA SS (66KV SIDE)

TEST REPORT OF SOIL RESISTIVITYMEASURMENT

Date: 25-OCT-2012

LocationNo.

Measured Soil Resistance (in Ω) Calculated Soil Resistivity (in Ω-M)Remarks

7 0.29 0.13 0.08 0.04 1.82 1.63 2.51 2.518 0.29 0.14 0.09 0.05 1.82 1.76 2.83 3.149 0.27 0.13 0.07 0.03 1.70 1.63 2.20 1.88

10 0.22 0.14 0.07 0.06 1.38 1.76 2.20 3.7711 0.21 0.13 0.1 0.05 1.32 1.63 3.14 3.1412 0.38 0.18 0.11 0.07 2.39 2.26 3.45 4.40

with S=1mtr.

with S=2mtr.

with S=5mtr.

with S=10mtr.

1.74 1.79 2.62 2.98

AVERAGE SOIL RESISTIVITY FOR 66KV YARD

FOR ASIA TELECOM

Calculated Soil Resistivity (in Ω-M)

TESTED BY

DHARMENDRA PRAJAPATI(B.E. ELECTRICAL)

TEST REPORT OF SOIL RESISTIVITYSITE: 400 KV VELODA SS (66KV SIDE)

Date: 25-OCT-2012

0.00

0.50

1.00

1.50

2.00

2.50

3.00

3.50

1 MTR 2 MTR 5 MTR 10 MTR

SOIL RESISTIVITY IN OHM-METER

SOIL RESISTIVITY OF 66KV SIDE

1 MTR 2 MTR 5 MTR 10 MTR