a ramset srb ed3 full edition pdf
TRANSCRIPT
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
1/312
SpecifiersResource
BookEdition 3
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
2/312
RamsetProducts are Tested in AustraliaIS09001 accredited test facility
Tested in Australian building materials
Tested to Australian Standards
Australian Engineers derive performance data
It means our customers canspecify with confidence!
Ramsetextensive technical support literature is available from www.ramset.com.au
or a Ramset
Engineer in your state.
2 www.ramset.com.au 1300 780 063
IntroductionSpecifiers Resource Book
Quality
ISO 9001
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
3/312
www ramset com au 1300 780 063 3
Welcome To The Ramset
Specifiers Resource BookThis concise and systematically presented book contains the information most useful to Specifiers, Engineers and
Architects when selecting the concrete anchoring solution that best suits their project.Selection of a concrete anchoring product is made on the basis of the basic type of fixing (bolt, stud or internallythreaded), macro environment, (e.g. coastal or inland), micro environment (particular chemicals) and of course thecapacity that best meets the design load case.Where the fixing is simple and does not warrant strength limit state calculations, selection on the basis of load caseis made simple with working load limit tables for each concrete anchor.Where more rigorous design and strength limit state calculation is required, the simplified step-by-step methodpresented in this booklet will allow rapid selection and verification of the appropriate concrete anchor.The Brick and Block anchoring section gives design professionals guidance as to the behaviour of a number offixings suitable for use in a variety of both solid and hollow pre-manufactured masonry units.
The capacity information presented considers the elemental nature of pre-manufactured masonry units and advisesdesigners as to suitable locations within the units accordingly.We're confident that you will find this book both useful and informative.
For additional information or any further enquiries, contact your local Ramsetengineer:NSW/ACT [email protected] or call 0412 592 075QLD [email protected] or call 0412 592 037
VIC/TAS [email protected] or call 0412 559 612SA/NT [email protected] or call 0412 579 206WA [email protected] or call 0412 264 658NATIONAL [email protected] or call 0418 653 711
IntroductionSpecifiers Resource Book
NEWWhats in this edition?
At Ramsetwe are committed to ongoing innovation in our engineering resources. As a reflection of ourcontinued product innovation and development, this latest edition includes the following improvements andnew products:
New Cracked Concrete Section (pg 274-306)
New Sustained Load data for EPCONC8, SpaTecPlus and FIX ZA4
New Fire Rated Performance Data for Mechanical and Chemical Anchors (pg 257-273)
New ETA (European Technical Approval) for the latest systems and products
New internally Threaded Inserts - Chemical Injection (pg 88-95)
New Faster Curing High Performance Chemical Injection Structaset401 (pg 63-70/115-122)
New 16mm AnkaScrew- Flanged head (pg 195-202)
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
4/312
4 www ramset com au 1300 780 063
Section PageNoINTRODUCTION 31 LEGEND OF SYMBOLS 52 NOTATION 6
3 DESIGN PROCESS 7
3.1 Simplified Design Approach 8-113.2 Worked Example 12-15
4 ANCHOR DESIGN SOFTWARE 16-18
5 ANCHOR SELECTION GUIDE 19-235.1 Environmental Considerations 195.2 Installation Considerations 195.3 Anchor Feature Guide 205.4 Anchor Application Guide 215.5 Chemical Resistance Guide 22-23
6 ANCHORING TECHNOLOGY 24-436.1 Derivation of Capacity 246.2 Anchoring Principles 25-276.3 Base Materials 28-296.4 Design 306.5 Tension 31-346.6 Shear 35-366.7 Bending 37
6.8 Combined Loading 386.9 Anchor Groups 396.10 Assembly Torque and Preload 406.11 Long Term Preload Degradation 416.12 Slip Load and Cyclic Loading 426.13 Long Term Slip and Cyclic Loading 426.14 Corrosion 436.15 Fire 43
CHEMICAL ANCHORING -Anchor StudsIntroduction & Estimating Chart 447 ChemSet Anchor Studs7.1 General Information 457.2 Description and Part Numbers 457.3 Engineering Properties 458 ChemSet REO502 Injection8.1 General Information 478.2 Description and Part Numbers 488.3 Engineering Properties 48
8.4 Strength Limit State Design 49-549 ChemSet 801 Injection9.1 General Information 559.2 Description and Part Numbers 569.3 Engineering Properties 569.4 Strength Limit State Design 57-6210 Structaset 401 Injection10.1 General Information 6310.2 Description and Part Numbers 6410.3 Engineering Properties 6410.4 Strength Limit State Design 65-7011 ChemSet 101 PLUS Injection11.1 General Information 7111.2 Description and Part Numbers 7211.3 Engineering Properties 7211.4 Strength Limit State Design 73-7812 ChemSet Maxima Spin Capsules12.1 General Information 7912.2 Description and Part Numbers 8012.3 Engineering Properties 80
12.4 Strength Limit State Design 81-86
CHEMICAL ANCHORING -Threaded InsertsIntroduction 8813 Threaded Inserts13.1 General Information 8913.2 Description and Part Numbers 9013.3 Engineering Properties 9013.4 Strength Limit State Design 91-95
CHEMICAL ANCHORING -Reinforcing Bar AnchorageIntroduction 96ChemSet Reinforcing Bar14.1 Estimating Charts 97-9814.2 Engineering Properties 9815 ChemSet REO502 Injection15.1 General Information 9915.2 Description and Part Numbers 100
15.3 Engineering Properties 10015.4 Strength Limit State Design 101-10616 ChemSet 801 Injection16.1 General Information 10716.2 Description and Part Numbers 10816.3 Engineering Properties 10816.4 Strength Limit State Design 109-114
Section PageNo17 Structaset 401 Injection17.1 General Information 11517.2 Description and Part Numbers 11617.3 Engineering Properties 11617.4 Strength Limit State Design 117-122
18 ChemSet 101 PLUS Injection18.1 General Information 12318.2 Description and Part Numbers 12418.3 Engineering Properties 12418.4 Strength Limit State Design 125-130
CHEMICAL ANCHORING -Post Installed Reinforcing BarIntroduction 13219 Design Process19.1 Design Process to AS3600-2009 13419.2 Worked Example 13519.3 Estimating Charts 136-13719.4 Engineering Properties 13820 ChemSet Reo 502 Injection20.1 General Information 13920.2 Description and Part Numbers 13920.3 Strength Limit State Design 140-14721 ChemSet 801 Injection21.1 General Information 149
21.2 Description and Part Numbers 14921.3 Strength Limit State Design 150-15722 ChemSet 101 PLUS Injection22.1 General Information 15922.2 Description and Part Numbers 15922.3 Strength Limit State Design 160-167
MECHANICAL ANCHORINGIntroduction 16823 SpaTec Plus Safety Anchors23.1 General Information 16923.2 Description and Part Numbers 17023.3 Engineering Properties 17023.4 Strength Limit State Design 171-17624 Boa Coil Expansion Anchors24.1 General Information 17724.2 Description and Part Numbers 17824.3 Engineering Properties 17824.4 Strength Limit State Design 179-18425 TruBolt Stud Anchors
25.1 General Information 18525.2 Description and Part Numbers 18625.3 Engineering Properties 18725.4 Strength Limit State Design 188-19426 AnkaScrew Screw In Anchors26.1 General Information 19526.2 Description and Part Numbers 19626.3 Engineering Properties 19626.4 Strength Limit State Design 197-20227 DynaBolt Plus Sleeve Anchors27.1 General Information 20327.2 Description and Part Numbers 20427.3 Engineering Properties 20427.4 Strength Limit State Design 205-21028 DynaSet Drop In Anchors28.1 General Information 21128.2 Description and Part Numbers 21228.3 Engineering Properties 21228.4 Strength Limit State Design 213-218
BRICK AND BLOCK ANCHORINGIntroduction 22029 Typical Masonry Units 221-22330 ChemSet Injection 101 PLUS30.1 General Information 22430.2 Description and Part Numbers 22530.3 Engineering Properties 22531 AnkaScrew Screw In Anchors31.1 General Information 22631.2 Description and Part Numbers 22731.3 Engineering Properties 22732 DynaBolt Plus Anchor Hex Bolt32.1 General Information 22832.2 Description and Part Numbers 22932.3 Engineering Properties 22933 RamPlug Anchors33.1 General Information 23033.2 Description and Part Numbers 23134 Typical Bolt Performance InformationIntroduction
34.1 Strength Limit State Design Info. 23334.2 Working Load Limit Design Info. 233
CONSTRUCTION CHEMICALSIntroduction 23435.1 Estimating Charts 23535.2 Joint Configuration & Design 235-236
ContentsSpecifiers Resource Book
Section PageNo36 Ramset Epoxy Grout36.1 General Information 23736.2 Typical Properties 23736.3 Curing 23836.4 Anchor Installation - Epoxy Grout 238
36.5 Description and Part Numbers 23837 Ramset Premier Grout MP37.1 General Information 23937.2 Typical Properties 239-24037.3 Curing 24037.4 Description and Part Numbers 240
FIRE RATED PROTECTIONIntroduction 24238 BlazeBrake Polyurethane Foam38.2 General Information 24338.3 Typical Properties 243-24438.4 Description and Part Numbers 24439 BlazeBrake Acrylic Sealant39.1 General Information 24539.2 Typical Properties 245-24639.3 Curing 24639.4 Joint Design 24739.5 Description and Part Numbers 24740 FyreBrake Polyurethane Sealant
40.1 General Information 24840.2 Typical Properties 248-24940.3 Curing 24940.4 Joint Design 24940.5 Description and Part Numbers 25041 Stackwork Fire Collars41.1 General Information 25141.2 Description and Part No. Cast-in 25241.3 Description and Part No. Retrofit 25342 Fire Rated Mech. Anchors42.1 General Information 254-255AnkaScrew Rod & Stud/AnkaScrew /RediDr ive/DynaSet43 SpaTec Plus Fire Rated Mech. Anchors43.1 General Information 25743.2 Description and Part Numbers 25843.3 Engineering Properties 25843.4 Fire Resistance Loads 259-26244 FIX Z A4 Fire Rated Mech. Anchors
44.1 General Information 26344.2 Description and Part Numbers 26444.3 Engineering Properties 26444.4 Fire Resistance Loads 265-26845 EPCON C8 Fire Rated Chem. Anchors45.1 General Information 26945.2 Description and Part Numbers 27045.3 Engineering Properties 27045.4 Fire Resistance Loads 271-273
CRACKED CONCRETEIntroduction 27446 EPCON C8 Chemical Injection Anchor Studs46.1 General Information 27546.2 Description and Part Numbers 27646.3 Engineering Properties 27646.4 Strength Limit State Design 277-282Sustained Loading 28247 EPCON C8 Chemical Inject. Reinforcing Bar47.1 General Information 283
47.2 Description and Part Numbers 28447.3 Engineering Properties 28447.4 Strength Limit State Design 285-290Sustained Loading 29048 SpaTec Plus Safety Anchor48.1 General Information 29148.2 Description and Part Numbers 29248.3 Engineering Properties 29248.4 Strength Limit State Design 293-298Sustained Loading 29849 FIX Z A4 Stud Anchor49.1 General Information 29949.2 Description and Part Numbers 30049.3 Engineering Properties 30049.4 Strength Limit State Design 301-306Sustained Loading 306
Cast-in ANCHORINGIntroduction 30850 Reid Elephant Foot Ferrules
50.1 General Information 30951 Reid Round Bar Ferrules51.1 General Information 309
SPECIFIERS RESOURCE BOOKDESIGN WORKSHEET 310-311
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
5/312
www ramset com au 1300 780 063 5
Suitable for elevated temperate applications.
Structural anchor components made from steel.
Any plastic or non-ferrous parts make no contribution
to holding power under elevated temperatures.
Suitable for use in seismic design.
Anchor has an effective pull-down feature,
or is a stud anchor. It has the ability to clamp
the fixture to the base material and provide
high resistance to cyclic loading.
Has good resistance to cyclic and dynamic
loading. Resists loosening under vibration.
May be used close to edges (or another
anchor) without risk of splitting the concrete.
AISI Grade 316 Stainless Steel, resistant to corrosive
agents including chlorides and industrial pollutants.
Recommended for internal or external applications
in marine or corrosive environments.
Stainless Steel High Corrosion resistance.
HCR Grade 1.4529/1.4565.
Steel Zinc Plated
Minimum thickness 5 micron.
Recommended for internal applications only.
Steel Hot Dipped Galvanised to AS4680-2006
and AS1214-1983.
Minimum thickness 42 micron.
For external applications.
Steel Mechanically Galvanised
Minimum thickness 42 micron.
For external applications.
Anchor can be through fixed into substrate
using fixture as template.
Temporary or removable anchor.
Suitable for wall applications.
Suitable for overhead applications.
Suitable for floor applications.
Suitable for hollow brick/block and hollow
core concrete applications.Suitable for use in drilled holes.
Suitable for use in cored holes.
Anchors suitable for use in dry holes.
Anchors suitable for use in damp holes.
Anchors suitable for use in holes
filled with water.
PERFORMANCE RELATED SYMBOLS
Indicates the suitability of product to specific types of performance related situations.
MATERIAL SPECIFICATION SYMBOLS
Indicates the base material and surface finish to assist in selection with regard to corrosion or environmental issues.
INSTALLATION RELATED SYMBOLS
Indicates the suitable positioning and other installation related requirements.
Suitable for contact with drinking water
for human consumption
Suitable for AAC and lightweight concrete
applications.
Corrosion resistant.
Not recommended for direct exposure to sunlight.
Cracked concrete.
HCR
MGAL
We have developed this set of easily recognisable icons to assist with product selection.
1Legend of SymbolsSpecifiers Resource Book
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
6/312
6 www ramset com au 1300 780 063
2NotationSpecifiers Resource Guide
GENERAL NOTATIONa = actual anchor spacing (mm)
ac
= critical anchor spacing (mm)
am = absolute minimum anchor spacing (mm)
Ab = reinforcing bar stress area (mm2)
As = stress area (mm2)
Ast = stress area of reinforcing bar (mm2)
bm = minimum substrate thickness (mm)
db = bolt diameter (mm)
df = fixture hole diameter (mm)
dh = drilled hole diameter (mm)
e = actual edge distance (mm)
ec = critical edge distance (mm)
em = absolute minimum edge distance (mm)
fc = concrete cylinder characteristiccompressive strength (MPa)
fcf = concrete flexural tensile strength (MPa)
fsy = reinforcing bar steel yield strength (MPa)
fu = characteristic ultimate steel
tensile strength (MPa)
fy = characteristic steel yield strength (MPa)
h = anchor effective depth (mm)
hn = nominal effective depth (mm)
g = gap or non-structural thickness (mm)
k1 = see AS3600 - 2009
k2 = see AS3600 - 2009k3 = see AS3600 - 2009
L = anchor length (mm)
Le = anchor effective length (mm)
Lst = length of reinforcing bar to develop
tensile stress st (mm)
Lsy.t
= reinforcing bar length to developsteel yield in tension (mm)
Lsy.t (nom)
= length of reinforcing bar to developfull steel yield in 32 MPa concrete (mm)
Lt = thread length (mm)
n = number of fixings in a group
Nsy= tensile steel yield load capacity
Nub= characteristic ultimate tensile
adhesive bond capacity (kN)
PL = long term, retained preload (kN)
PLi = initial preload (kN)
Pr = proof load (kN)
t = total thickness of fastenedmaterial(s) (mm)
Tr = assembly torque (Nm)
Xe = edge distance effect, tension
Xna = anchor spacing effect, tension
Xnae
= anchor spacing effect, end of a row, tension
Xnai= anchor spacing effect, internal to a row,tension
Xnc = concrete compressive strength effect,
tension
Xne = edge distance effect, tension
Xuc = characteristic ultimate capacity
Xva = anchor spacing effect, concrete edge shear
Xvc = concrete compressive strength effect, shear
Xvd = load direction effect, concrete edge shear
Xvn = multiple anchors effect, concrete edge shear
Xvs = corner edge shear effect, shear
Xvsc
= concrete compressive strength effect,combined concrete/steel shear
Xns= Cracked concrete service temperaturelimits effect
Z = section modulus (mm3)
= concrete cube characteristiccompressive strength (N/mm2)
T = torque co-efficient of sliding friction
x = mean ultimate capacity
st= steel tensile stress
st (nom) = steel tensile stress of reinforcing barbonded into 32 MPa concrete
STRENGTH LIMIT STATE NOTATIONM* = design bending action effect (kN.m)M
u = characteristic ultimate moment
capacity (kN.m)
N* = design tensile action effect (kN)
Ntf = nominal ultimate bolt tensile capacity (kN)
Nu = characteristic ultimate tensile
capacity (kN)
Nuc = characteristic ultimate concrete
tensile capacity (kN)
Nup= characteristic ultimate pull-through capacity (kN)
Nucr= factored characteristic ultimateconcrete tensile capacity (kN)
Nur = design ultimate tensile capacity (kN)
Nurc
= design ultimate concrete tensilecapacity (kN)
Nurp= design ultimate pull-through capacity (kN)
PERMISSIBLE STRESS NOTATIONf
s = factor of safety
fsc = factor of safety for substrate = 3.0
fss = factor of safety for steel in tension
and bending = 2.2
fsv = factor of safety for steel in shear = 2.5M = applied moment (kNm)
Ma = working load limit moment capacity (kNm)
N = applied tensile load (kN)
Na = working load limit tensile capacity (kN)
Nac = working load limit concrete tensile
capacity (kN)
Nar = factored working load limit tensile
capacity (kN)N
as = working load limit steel tensile
capacity (kN)
Nasr
= factored working load limit steeltensile capacity (kN)
Ra = working load limit capacity (kN)
V = applied shear load (kN)
Va = working load limit shear capacity (kN)
Var = factored working load limit shear
capacity (kN)V
as = working load limit steel shear
capacity (kN)
Nus = characteristic ultimate steel tensile
capacity (kN)
Nusr
= factored characteristic ultimatesteel tensile capacity (kN)
Ru = characteristic ultimate capacity
V* = design shear action effect (kN)
Vsf = nominal ultimate bolt shear capacity (kN)
Vu = ultimate shear capacity (kN)
Vuc = characteristic ultimate concrete
edge shear capacity (kN)
Vur = design ultimate shear capacity (kN)
Vurc = design ultimate concrete edge shearcapacity (kN)
Vus = characteristic ultimate steel shear
capacity (kN)
Vusc
= characteristic ultimate combinedconcrete/steel shear capacity (kN)
= capacity reduction factor
c = capacity reduction factor, concrete tension
recommended as 0.6
m = capacity reduction factor, steel bending
recommended as 0.8
n = capacity reduction factor, steel tension
recommended as 0.8
q = capacity reduction factor, concrete edge
shear recommended as 0.6
v = capacity reduction factor, steel shear
recommended as 0.8
p= capacity reduction factor, pull-throughrecommended as 0.65
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
7/312
www ramset com au 1300 780 063 7
This information is provided for the guidance of qualified structural engineers or other suitably skilled persons in the design of anchors. It isthe designers responsibility to ensure compliance with the relevant standards, codes of practice, building regulations, workplace regulationsand statutes as applicable.
This manual allows the designer to determine load carrying capacities based on actual application and installation conditions.
The designer must first select the anchor style/type to suit application and environmental conditions through the use of tables 5.1, 5.2, 5.3,5.4 and 5.5 to identify the specific product features, dimensional properties and environmental characteristics required.
Then select an appropriate anchor size to meet the required load case through the use of either the working load information provided or byuse of the simplified design process described on the page opposite to arrive at recommendations in line with strength limit statedesign principles.
Ramsethas developed this Simplified Design Approachto achieve strength limit state design, and to allow for rapid selection of asuitable anchor and through systematic analysis, establish that it will meet the required design criteria under strength limit state principles.
The necessary diagrams, tables etc. for each specific product are included in this publication.
Ramsethas also developed a software tool Ramset Anchor Design to enable engineers to quickly select suitable anchors for a specificset of design conditions and output the results for project file reference.
See section 4 of this publication for further details and an example of how to use the Ramset Anchor Design software.
3Design ProcessSpecifiers Resource Guide
DesignPr
ocess
N0Rd,c= Cracked concrete cone resistance reduced characteristic
NRk,c = Cracked concrete cone resistance characteristic
N0Rd,p= Cracked concrete combined pull-out concrete cone (pull-through)resistance reduced characteristic
N0Rk,p= Cracked concrete combined pull-out (pull-through) concrete coneresistance - characteristic
NRd,s = Cracked concrete steel tensileresistance reduced characteristic
NRk,s = Cracked concrete steel tensileresistance - characteristic
NRd,p = Design cracked concrete combined
pull-out and concrete cone (pull-through) resistance
NRd = Design cracked concrete tensileresistance
V0Rd,c = Cracked concrete edge resistance reduced characteristic
V0Rk,c = Cracked concrete edge resistance -characteristic
V0Rd,cp= Cracked concrete Pryout failure reduced characteristic
VRk,cp = Cracked concrete Pryout failure -characteristic
VRd,c = Design cracked concrete edge shearresistance
VRd,cp = Design cracked concrete Pryoutfailure
VRd,s = Cracked concrete steel shearresistance reduced characteristic
VRk,s = Cracked concrete steel shearresistance characteristic
VRd = Design cracked concrete shearresistance
Ms
= Partial safety factor for steelresistance (tension and shear)
Msp
= Partial safety factor for combinedpull-out concrete cone (pull-through)resistance
Mc
= Partial safety factor for concrete edgefailure
Mpr
= Partial safety factor for concretepryout failure
STRENGTH LIMIT STATE NOTATION (CRACKED CONCRETE)
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
8/312
8 www ramset com au 1300 780 063
We have developed this design process to provide accurate anchor performance predictions and allow appropriate design solutions in an efficient
and time saving manner.
Our experience over many years of anchor design has enabled us to develop this process which enables accurate and quick solutions without theneed to work labouriously from first principles each time.
PRELIMINARY SELECTION
Establish the design action effects, N* and V* (Tension and Shear) acting on each anchor being examined using the appropriate load combinations
detailed in the AS1170series of Australian Standards.
Refer to charts 5.1, 5.2, 5.3, 5.4 and 5.5 in order to select an anchor type that best meets the needs of your application.
STRENGTH LIMIT STATE DESIGN
Refer to table 1a, Indicative combined loading Interaction Diagram
for the anchor type selected, looking up N* and V* to select the anchor
size most likely to meet the design requirements.
Note that the Interaction Diagram is for a specific concretecompressive strength and does not consider edge distance and anchor
spacing effects, hence is a guide only and its use should not replace a
complete design process.
ACTION Note down the anchor size selected.
Having selected an anchor size, check that the design values for edgedistance and anchor spacing comply with the absolute minima detailedin table 1b. If your design values do not comply, adjust the design
layout.
Calculate the anchor effective depth as detailed in step 1c.
This is an important structural dimension that will be referred to in
subsequent tables.
Typically, greater effective depths will result in greater concretetensile capacities.
ACTION Note down the anchor effective depth, h. Note also the product part no. referenced.
If the above questions are answered satisfactorily,
proceed to step 2.
Select anchor to be evaluated
STEP 1
Checkpoint 1
Anchor size selected ?
Absolute minima compliance achieved ?
Anchor effective depth calculated ?
3.1Simplified DesignApproach
DesignProcess
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
9/312
www ramset com au 1300 780 063 9
Referring to table 2a, determine the reduced characteristic ultimate
concrete tensile capacity (Nuc). This is the basic capacity,
uninfluenced by edge distance or anchor spacings and is for the
specific concrete compressive strength(s) noted.
ACTION Note down the value for Nuc
Calculate the concrete compressive strength effect, tension, Xncby
referring to table 2b. This multiplier considers the influence of the
actual concrete compressive strength compared to that used in table
2a above.
ACTION Note down the value for Xnc
If the concrete edge distance is close enough to the anchor beingevaluated, that anchors tensile performance may be reduced. Use
table 2c, edge distance effect, tension, Xneto determine if the design
edge distance influences the anchors tensile capacity.
ACTION Note down the value for Xne
For designs involving more than one anchor, consideration must be
given to the influence of anchor spacing on tensile capacity. Use either
of tables 2d or 2e to establish the anchor spacing effect, tension, Xnae
or Xnai.
ACTION Note down the value of Xnaeor Xnai
This calculation takes into consideration the influences of concretecompressive strength, edge distance and anchor spacing to arrive at the
design reduced concrete tensile capacity.
ACTION Note down the value of Nurc
Verify concrete tensile capacity - per anchorSTEP 2
Design reduced concrete tensile capacity, Nurc
Nurc
= Nuc*X
nc*X
ne*( X
naeor X
nai) (kN)
Having calculated the concrete tensile capacity above (Nurc),
consideration must now be given to other tensile failure mechanisms.
Calculate the reduced characteristic ultimate steel tensile capacity
(Nus) from table(s) 3a.
ACTION Note down the value of Nus
For internally threaded anchoring products that utilise a separate
bolt such as the DynaSetanchor, make use of step 3b to verify the
reduced characteristic ultimate bolt steel tensile capacity (Ntf).
Now that we have obtained capacity information for all tensile failure
mechanisms, verify which one is controlling the design.
This completes the tensile design process, we now look to verify that
adequate shear capacity is available.
Verify anchor tensile capacity - per anchorSTEP 3
Design reduced ultimate tensile capacity, Nur
Nur= minimum of N
urc, N
us, N
tf
Check N* / Nur1,
if not satisfied return to step 1
3.1Simplified DesignApproach
DesignPr
ocess
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
10/312
10 www ramset com au 1300 780 063
Referring to table 4a, determine the reduced characteristic ultimate
concrete edge shear capacity (Vuc). This is the basic capacity,
uninfluenced by anchor spacings and is for the specific edge distance
and concrete compressive strength(s) noted.
ACTION Note down the value for Vuc
Calculate the concrete compressive strength effect, shear, Xvcby
referring to table 4b. This multiplier considers the influence of the
actual concrete compressive strength compared to the nominal value
used in table 4a above.
ACTION Note down the value for Xvc
The angle of incidence of the shear load acting towards an edge isconsidered through the factor Xvd, load direction effect, shear.
Use table 4c to establish its value.
ACTION Note down the value for Xvd
For a row of anchors located close to an edge, the influence of the
anchor spacing on the concrete edge shear capacity is considered by
the factor Xva, anchor spacing effect, concrete edge shear.
Note that this factor deals with a row of anchors parallel to the edgeand assumes that all anchors are loaded equally.
If designing for a single anchor, Xva= 1.0
ACTION Note down the value for Xva
In order to distribute the concrete edge shear evenly to all anchorswithin a row of anchors aligned parallel to an edge, calculate the
multiple anchors effect, concrete edge shear, Xvn.
If designing for a single anchor, Xvn= 1.0
Examples
This calculation takes into consideration the influences of concrete
compressive strength, edge distance and anchor spacing to arrive at
the design reduced concrete shear capacity.
For a design involving two or more anchors in a row parallel to an
edge, this value is the average capacity of each anchor assuming each
is loaded equally.
ACTION Note down the value of Vurc
Note:Consider capacity of two anchors in rowclosest to edge only,
ie. anchor load = V*TOTAL/2 to each anchor.
ACTION Note down the value for Xvn
Verify concrete shear capacity - per anchorSTEP 4
Design reduced concrete shear capacity, Vurc
Vurc
= Vuc*X
vc*X
vd*X
va*X
vn(kN)
n = 3
V*TOTAL
n = 2
V*TOTAL
n = 2
V*TOTAL
Assume slotted holes toprevent shear take up.
3.1Simplified DesignApproach
DesignProcess
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
11/312
www ramset com au 1300 780 063 11
Having calculated the concrete shear capacity above (Vurc),
consideration must now be given to other shear failure mechanisms.
Calculate the reduced characteristic ultimate steel shear capacity
(Vus) from table(s) 5a.
ACTION Note down the value for Vus
For internally threaded anchoring products that utilise a separate
bolt such as the DynaSetanchor, make use of step 5b to verify the
reduced characteristic ultimate bolt steel shear capacity (Vsf).
Verify anchor shear capacity - per anchorSTEP 5
Now that we have obtained capacity information for all shear failure
mechanisms, verify which one is controlling the design.
This completes the shear design process, we now look to verify that
adequate combined capacity is available for load cases having both
shear and tensile components.
Design reduced shear capacity, Vur
Vur= minimum of Vurc, Vus, Vsf
Check V* / Vur1,
if not satisfied return to step 1
For load cases having both tensile and shear components, verify that
the relationship represented here is satisfied.
Combined loading and specificationSTEP 6
Check
N*/Nur
+ V*/Vur
1.2,
if not satisfied return to step 1
3.1Simplified DesignApproach
DesignPr
ocess
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
12/312
12 www ramset com au 1300 780 063
Verify capacity of the anchors detailed below:
Given data:
As the design process considers design action effects PER anchor,
distribute the total load case to each anchor as is deemed appropriate.
In this case, equal load distribution is considered appropriate hence,
Given that each of the interior anchors is influenced by two adjacent
anchors, verify capacity for anchor B in this case.
From the information presented in tables 5.1 5.5, it is established
that SpaTecPlus anchors will be suitable for selection.
Having completed the preliminary selection component of the design
process, commence the Strength Limit State Design process.
Concrete compressive strength fc 50 MPa
Design tensile action effect N*TOTAL 80 kN
Design shear action effect V*TOTAL 180 kN
Edge distance e 250 mm
Anchor spacing a 150 mm
Fixture plate + grout thickness t 17 mm
No. of anchors in shear n 4
Design tensile action effect (per anchor) N* 20 kN
Design shear action effect (per anchor) V* 45 kN
A B C D
V*TOTAL
= 30
250
150 150 150
3.2Worked ExampleStrength Limit State Design
DesignProcess
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
13/312
www ramset com au 1300 780 063 13
Refer to table 1a, Indicative combined loading interaction diagram
on page 171. Applying both the N* value and V* value to the
interaction, it can be seen that the intersection of the two values falls
within the M16 band.
ACTION M16 anchor size selected.
Confirm that absolute minima requirements are met.
From table 1b (page 171) for M16 SpaTecPlus, it is required that
edge distance, e > 160 mm. and that anchor spacing,
a > 105 mm.
The design values of e = 250 mm and a = 150 mm comply with
these minima, hence continue to step 1c.
The effective depth, h, is calculated by making reference to the
Description and Part Numbers table on page 170 and calculating
effective depth, h = Le- t.
Hence, h = 125 - 17
= 108 mm
ACTION h = 108Anchor selected is SP16145
Select anchor to be evaluatedSTEP 1
Anchor size selected ? M16
Absolute minimaYes
compliance achieved ?
Anchor effectiveh = 108 mm with SP16145
depth calculated ?
Referring to table 2a, consider the value obtained for an M16 anchor
at h = 110 mm (closest to our design value of h = 108 mm).
ACTION Nuc= 54.6 kN
Verify the concrete compressive strength effect, tension, Xncvalue
from table 2b.
ACTION Xnc= 1.25
Verify the edge distanced effect, tension, Xnevalue from
table 2c.
ACTION Xne= 1.00 (no effect)
As we are considering anchor B for this example, use table 2e
on page 173 to verify the anchor spacing effect, internal to a row,
tension, Xnaivalue. If we were inspecting anchors A or D we would
use table 2d for anchors at the end of a row.
ACTION Xnai= 0.45
ACTION Nurc= 30.7 kN
Verify concrete tensile capacity - per anchorSTEP 2
Design reduced concrete tensile capacity, Nurc
Nurc
= Nuc*X
nc*X
ne*X
nai (kN)
= 54.6*1.25
*1.00
*0.45
= 30.7 kN
3.2Worked ExampleStrength Limit State Design
DesignPr
ocess
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
14/312
14 www ramset com au 1300 780 063
From table 3a, verify the reduced characteristic ultimate steel tensile
capacity, Nus.
For an M16 SpaTecPlus, Nus= 100.5 kN.
ACTION Nus= 100.5 kN
Verify anchor tensile capacity - per anchorSTEP 3
Nur= minimum of N
urc, N
us
In this case Nur= 30.7 kN(governed by concrete capacity).
Check N* / Nur1,
20 / 30.7 = 0.65 1Tensile design criteria satisfied, proceed to Step 4.
Referring to table 4a, consider the value obtained for an M16 anchor
at e = 250 mm.
ACTION Vuc= 80.2 kN
Verify the concrete compressive strength effect, tension, Xvcvalue
from table 4b.
ACTION Xvc= 1.25
Verify the load direction effect, concrete edge shear, Xvd
value using table 4c.
ACTION Xvd= 1.32 for angle of 30 degrees to normal.
Verify the anchor spacing effect, concrete edge shear, Xva
value using table 4d.
ACTION Xva= 0.62
In order to distribute the shear load evenly to all anchors in the group,
the multiple anchors effect, concrete edge shear, Xvnvalue is retrieved
from table 4e.
The ratio of (a / e) for this design case is 150 / 250 = 0.6.
ACTION Xvn= 0.69
ACTION Vurc= 56.6 kN
Verify concrete shear capacity - per anchorSTEP 4
Design reduced concrete shear capacity, Vurc
Vurc
= Vuc*X
vc*X
vd*X
va*X
vn (kN)
= 80.2*1.25
*1.32
*0.62
*0.69
= 56.6 kN
From table 5a, verify the reduced characteristic ultimate
steel shear capacity, Vus.
The shear capacity available from the SpaTecPlus anchor is
subject to its effective depth, h value. As was noted earlier
h = 108 mm for this example, hence,
for an M16 SpaTec
Plus at h = 108 mm, Vus= 104.5 kN
ACTION Vus= 104.5 kN
Verify anchor shear capacity - per anchorSTEP 5
Vur= minimum of V
urc, V
us
In this case Vur= 56.6 kN
(governed by concrete capacity).
Check V* / Vur1,
45 / 56.6 = 0.80 1Shear design criteria satisfied, proceed to Step 6.
3.2Worked ExampleStrength Limit State Design
DesignProcess
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
15/312
www ramset com au 1300 780 063 15
Check that the combined loading relationship is satisfied:
Review the design process and examine the critical factors influencing
the overall anchor capacity.
For tension (governed by concrete failure),
Nuc = 54.6 kN
Xnc = 1.25
Xne = 1.00
Xnai = 0.45
It can be seen from the above values that whilst the concrete
compressive strength effect, Xncimproves the design ultimate tensile
capacity, the anchor spacing effect, Xnaisignificantly reduces designultimate tensile capacity.
Possible solution: Increase anchor spacing to raise the value of Xnai.
For shear (governed by concrete failure),
Vuc = 80.2 kN
Xvc = 1.25Xvd = 1.32
Xva = 0.62
Xvn = 0.69
Again, the concrete compressive strength effect, Xvcimproves thedesign ultimate shear capacity. Anchor spacing effect, Xvareduces the
design ultimate shear capacity.
Possible solution: Increase anchor spacing to raise the value of Xva.
Note that increasing the anchor spacing for this design will improve
Xnai, Xvaand Xvn.
Re-consider the design using the adjusted values with anchor spacing,
a set at 200 mm.
Nuc = 54.6 kNXnc = 1.25
Xne = 1.00
Xnai = 0.61
Hence Nurc= 41.6 kN (at a = 200 mm).
Vuc = 80.2 kN
Xvc = 1.25Xvd = 1.32
Xva = 0.66
Xvn = 0.74 (at a = 200 mm, hence a / e = 0.8)
Hence Vurc= 64.6 kN (at a = 200 mm).
Now,
Combined loading and specificationSTEP 6
N*/Nur+ V*/V
ur1.2,
20 / 30.7 + 45 / 56.6 = 1.44 > 1.2
Combined loading criteria FAILED.
N*/Nur+ V*/V
ur1.2,
20 / 41.6 + 45 / 64.6 = 1.17 < 1.2
Combined loading criteria PASSES.
3.2Worked ExampleStrength Limit State Design
DesignPr
ocess
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
16/312
16 www ramset com au 1300 780 063
4.1.1 RAMSETANCHOR DESIGN SOFTWAREv1.3
RamsetAnchor Design Software is provided to assist in the choiceof a suitable fastener which meets a specific set of design inputs and
is intended for use by suitably qualified design professionals.
The program attempts to acquire the minimum data needed to fullyspecify the anchoring problem,
substrate details
adverse environments
interfering edges and anchorsload case information
and to offer a range of anchors which meet the requirement.
Additional information prompts with defaults, ensuring it has been
considered. Once a selection has been made all inputs, calculated
values and installation details are available as output.
The RamsetAnchor Design Software is ideal for consideringcomplex anchor layouts and grouped anchor configurations. Note
that the calculations being performed relate to the single fastener
currently at the reference location. The software provides acalculation of the viability of THAT anchor and assumes that all
other anchors:
are the same typehave the same installation conditions,are subject to the same force.
For multiple anchor connections, the design professional must
therefore distribute the applied load case(s) to each anchor in thegroup and evaluate each anchor separately.
This approach allows the designer flexibility in distributing loads
to anchors so as to optimise the connection detail without the
constraints of a software imposed distribution method.
The software will check that the substrate thickness is adequate for
allowing anchor capacity to be generated. The Structural Engineershould check the substrates sectional capacity for resisting the
applied load.
By default the software will select from a wide range of fasteners
types that suit the design parameters of the specific anchor.
4.1.2 USE OF THE RAMSETDESIGNSOFTWARE
Having installed and run the program proceed to the toolbar at the topof the screen and select the New button, this will bring you to thefirst of four input screens.
Project/Customer Details
On the first screen (Fig. 1) enter Project/Customer Details.These are simply details that will help identify the project you are
designing and will form part of the printed output that can be stored as
part of the project documentation.
Fig. 1
On completion of these details, the Next button located on thebottom of the screen will move you onto the second input screen.
Material Details
On the second screen (Fig. 2) enter the Material Details.These refer directly to the substrate properties of the project you are
designing.
Fields which must be completed are;
Fixture and Non Structural Space Thickness
This refers to the thickness of the fixture and the non structural gapwhich is any non structural material (e.g. plaster, grout, packer,
foam) in between the substrate and the fixture.
Structural Depth and Compressive StrengthThis refers to the substrate thickness and its compressive
strength. Note that the program assumes the substrate is a solid
homogeneous material with a particular compressive strength.
Therefore it cannot design hollow block fixings, however core-filled blockwork can be analysed using an equivalent compressive
strength value.
4Anchor DesignSoftware
AnchorD
esignSoftware
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
17/312
www ramset com au 1300 780 063 17
Fields which may be completed to help define the anchor selection
criteria are:
(Note if these fields are left blank then the program will consider allpossible anchors in the range that would be suitable for the designconditions you impose.)
Fastener EnvironmentThese boxes can be ticked if there is a particular attribute the
anchor must exhibit. e.g. Selecting the Corrosive attribute will
ensure only galvanised and stainless steel fixings are considered and
ignore zinc plated anchors.
Anchor for ConsiderationYou can individually select specific anchor types to be considered in
the design, and ignore any that you do not wish to be evaluated.
The screen should then be similar to the following.
On completion of the details, the Next button will move you onto thethird input screen, or alternatively hit Previous to make any changesto the first input screen.
Layout of Dimensional Considerations
On the third screen (Fig. 3) enter the layout of edges and otherfasteners which may affect the design.
These are details on the anchor layout, which enable any loss in
capacity due to being close to an edge or a neighbouring fastener, of
the particular connection you are designing to be taken into account.
Select the Layout button.
Select your anchor group configuration, e.g. for a 2 x 2 anchor layout
select the four line. Now fill out all the applicable edge distances
and spacings. Note that you do not have to enter in all the edges ifthe anchors are located internally within a slab or panel. Once you are
satisfied with the layout, select the Finish button.
Fig. 2
You will notice from Fig. 4 that the fastener in the cross hairs is the
reference fastener location upon which all calculations are made. You
are able to change the fastener being evaluated to one of the otheranchors - details on how to do this can be found by selecting the
Help button.
The Concrete Compaction Factor represents the quality of theconcrete. For well vibrated and compacted concrete, this value should
be set at 1.0. For poorly finished or unsupervised edge concrete, set
the value at 1.5.
On Completion of all details, the Next
button moves you onto thefinal input screen, or alternatively select Previous to make anychanges to the second input screen.
Limit State or Working Load Design
The fourth screen (Fig. 4) requires you to enter either theLimit Stateor Working Load Design Loads - applied load on thesingle anchor position selected. This refers to the loads appliedon the anchor in question, and can either be entered in as a strength
Limit State Load or a Working Load.
To design in strength Limit State, select the Change to Limit State
Design button. You can then adjust the reduction factors as required.
Finally input the applied loads on the anchor you are designing,remembering that this load is applied to the single anchor position
only.
You will note that the Shear force is split into Y and Z axiscomponents. Entering a +ve load in the Y box will mean it will bedirected toward the top of the screen, if you wish to direct the load in
the opposite direction simply input the value as a -ve load. Likewise for
the Z axis.
Fig. 3
4Anchor DesignSoftware
AnchorDesign
Software
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
18/312
18 www ramset com au 1300 780 063
You will notice on the above screen that the anchors are listed in orderof capacity utilised and also display a relative cost, which is an indexcost allowing you to compare the approximate installed cost of the
various types of suitable anchors.
Select your preferred anchor via the Select button and the screenwill then show the design output screen. This screen shows you the
Design Inputs, parameters which you have entered and computed
Design Outputs which includes capacities, governing factors
and installation dimensions. If you would like to see the detailed
calculations, then select the relevant tabs, i.e. Design, Layout, CrossSection and Installation.
On completion, the Finish button will commence the computation
of all the possible solutions for the parameters you have entered.The possible solutions will be displayed in the Possible Acceptable
Anchors dialogue box.
It is important to note that if the input design parameterswere incomplete or no possible solutions could be found,the program will advise as to the reasons why, (e.g. anchorstoo close to edge). You are then able to adjust the design asdetailed, using the design input icons on the summary outputscreen (Fig. 6).
Fig. 4
Fig. 5
The icons in the top right hand corner of the screen enable you to
navigate through the completed design.
The first four from the left are actually the four design input screens
you have just completed.
The fifth icon (calculator icon) allows you to recalculate for possible
solutions in case you make any amendments or would like to select adifferent anchor.
The next icon (printer icon) allows you to print a summary of the
design, which will show the project description, anchor layout, design
inputs and outputs. More detailed printouts are available if you go to
File then Print... then select the printout you would like.
The next icon (disk icon) allows you to save the design for futurereference and can be retrieved at a later date.
For a copy of our latest Design Software, contact your local specialist
RamsetSales Engineer (details on inside front cover) for ademonstration.
Fig. 6
4 Anchor DesignSoftware
AnchorD
esignSoftware
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
19/312
www ramset com au 1300 780 063 19
ANCHORSpaTecPlus
BoaCoil
FIXZA4
TruBolt
AnkaScrew
DynaBolt
DynaSet
Plus
RamPlug
EPCONC8
ChemSetReo
502
ChemSet
801
Structaset
401
ChemSet
101
Plus
ChemSet
Spin
Coastal Environment External (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS)
Coastal Environment Internal (SS) (SS) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal)
Inland Environment External (Zn) (Zn) (SS) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn)
Inland Environment Internal (Zn) (Zn) (SS) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn)
Tropical Environment External (SS) (SS) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal)
Tropical Environment Internal (Zn) (Zn) (SS) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn)
Alpine Environment External (SS) (SS) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal)
Alpine Environment Internal (Zn) (Zn) (SS) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn) (Zn)
Industrial Environment External (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS)
Industrial Environment Internal (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS)
Internal Wet Areas (SS) (SS) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal)
ANCHOR
SpaTecPlus
BoaCoil
FIXZA4
TruBolt
AnkaScrew
DynaBoltPlus
DynaSet
RamPlug
EPCONC8
ChemSet
Reo
502
ChemSet
801
Structaset
401
ChemSet
101
Plus
ChemSet
Spin
Dry Hole
Damp Hole (SS) (SS) (Gal) (Gal) (Gal) (SS) (Gal) (Gal) (Gal) (Gal) (Gal) (Gal)
Water Filled Hole (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS)Submerged Hole
After Set (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS) (SS)
Fire Resistant
Solid Concrete Hollow Block
(Cavity) * *
Solid Clay Brick
Wire Cut Clay Brick * *
Cracked Concrete
Sustained Loading * With accessories
5.1-2ConsiderationsEnviromental / Installation
AnchorSelectionGuide
5.2 Installation Considerations
5.1 Environmental Considerations
LEGEND = Recommended = Possible
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
20/312
20 www ramset com au 1300 780 063
PRODUCT PERFORMANCE RELATED MATERIAL SPECIFICATION
SpaTecPlus Safety Anchor BoaCoil Anchor FIX ZA4 Anchor TruBoltAnchor
AnkaScrewScrew-In Anchor DynaBoltPlus Anchor DynaBoltPlus Anchor Hex Bolt DynaSetDrop-In Anchor RamPlugAnchor EPCONC8 Injection & Stud EPCONC8 Injection & Rebar ChemSetReo 502Injection & Stud ChemSetReo 502Injection & Thr'd Ins ChemSet801 Injection & Stud Structaset401 Injection & Stud Structaset401 Injection & Thr'd Insert ChemSet101 Plus Injection & Stud ChemSetMaximaSpin Capsule & Stud
The following chart provides a quick guide for selecting the appropriate RamsetConcrete Anchor to suit your needs.Please refer to the Legend of Symbols below each table for a detailed explanation of the symbols used.
5.3Anchor FeatureGuide
5.3 Anchor Feature Guide
Suitable for elevated temperate applications.
Structural anchor components made from steel.
Any plastic or non-ferrous parts make no contribution
to holding power under elevated temperatures.
Suitable for use in seismic design.
Anchor has an effective pull-down feature,
or is a stud anchor. It has the ability to clamp
the fixture to the base material and provide
high resistance to cyclic loading.
Has good resistance to cyclic and dynamic
loading. Resists loosening under vibration.
May be used close to edges (or another
anchor) without risk of splitting the concrete.
AISI Grade 316 Stainless Steel, resistant to corrosive
agents including chlorides and industrial pollutants.
Recommended for internal or external applications
in marine or corrosive environments.
Stainless Steel High Corrosion resistance.
HCR Grade 1.4529/1.4565.
Steel Zinc Plated
Minimum thickness 5 micron.
Recommended for internal applications only.
Steel Hot Dipped Galvanised to AS4680-2006
and AS1214-1983.
Minimum thickness 42 micron.
For external applications.
Steel Mechanically Galvanised
Minimum thickness 42 micron.For external applications.
Temporary or removable anchor.
PERFORMANCE RELATED SYMBOLS
Indicates the suitability of product to specific types of performance related situations.
MATERIAL SPECIFICATION SYMBOLS
Indicates the base material and surface finish to assist in selection with regard to corrosion or environmental issues.
Corrosion resistant.Not recommended for direct exposure to sunlight.
Cracked concrete.
HCR
MGAL
AnchorS
electionGuide
LEGEND = Recommended
HCRMGAL
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
21/312
www ramset com au 1300 780 063 21
5.4Anchor ApplicationGuide
5.4 Anchor Application Guide
Anchor can be through fixed into substrate
using fixture as template.
Suitable for wall applications.
Suitable for overhead applications.
Suitable for floor applications.
Suitable for hollow brick/block and hollow
core concrete applications.Suitable for use in drilled holes.
Suitable for use in cored holes.
Anchors suitable for use in dry holes.
Anchors suitable for use in damp holes.
Anchors suitable for use in holes
filled with water.
INSTALLATION RELATED SYMBOLS
Indicates the suitable positioning and other installation related requirements.
Suitable for contact with drinking water
for human consumption
Suitable for AAC and lightweight concrete
applications.
AnchorSelectionGuide
PRODUCT APPLICATIONS
SpaTecPlus Safety Anchor StainlessSteel
BoaCoil Anchor
FIX ZA4 Anchor StainlessSteel
TruBoltAnchor StainlessSteel
AnkaScrewScrew-In Anchor
DynaBoltPlus Anchor StainlessSteel
DynaBoltPlus Anchor Hex Bolt
DynaSetDrop-In Anchor StainlessSteel
RamPlugAnchor
EPCONC8 Injection & Stud StainlessSteel
EPCONC8 Injection & Rebar StainlessSteel
ChemSetReo 502Injection & Stud ChemSetReo 502Injection & Threaded Insert
ChemSet801 Injection & Stud StainlessSteel
Structaset401 Injection & Stud Stainless
Steel
Structaset401 Injection & Threaded Insert StainlessSteel
ChemSet101 Plus Injection & Stud ChemSetMaximaSpin Capsule & Stud
LEGEND = Recommended
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
22/312
22 www ramset com au 1300 780 063
5.5Chemical ResistanceGuide
AnchorS
electionGuide
Resistance of anchors exposed to:
Adhesives Fixings
Chemical Environment Concentration
ChemSet
101 Plus
Structaset
401
ChemSet
801 Reo 502
Maxima SS Gal ZincAcetic Acid Aqueous Solution 10% - -
Acetic Acid Glacial 100% -
Acetone 100% - - -
Ammonia 100% - - - -
Ammonium Hydroxide 5% - - - - -
Ammonium Hydroxide 9% - - - C - - - -
Aniline 100% - - - - - - -
Aqueous Solution Aluminium Chloride Saturated - - - -
Aqueous Solution Aluminium Nitrate 10% - - - -
Beer 100% - - - -
Benzene 100% - - -
Benzoic Acid Saturated - - - - -Benzyl Alcohol 100% - - - - -
Butyl Alcohol 100% C C C - - - - -
Butyl Lactic Acid 100% - - - - - - -
Calc ium Sulphate Aqueous Solution Saturated - - - - -
Carbon Dioxide 100% - - - - - -
Carbon Monoxide Gas - - -
Carbon Tetrachloride 100% C C C - - - -
Caustic Soda 20% - - - - - - -
Cement in suspension Saturated - - - - - -
Chlorine Water Saturated - - - -
Chloro Benzene 100% - - - - -
Citric Acid Aqueous Solution Saturated - - -
Cyclohexanol 100% - - - - -
Diesel fuel 100% C - - - -
Diethylene Glycol 100% - - - - -
Ethanol 95% C C - - - - -
Ethanol Aqueous Solution 20% C C C - - -
Ethanol Aqueous Solution 15% - - - - - -
Ethyl Acetate 100% - - - - - -
Ethylene Glycol 100% - - - - - - -
Heptane 100% C - - -
Hexane 100% C C C - - - -
Hydrochloric Acid 4% C - -
Hydrochloric Acid 15% - - -
Hydrochloric Acid 25% C C C - - -
Hydrogen Fluoride 20% - - - - -
LEGEND
= Retains 80% of properties when exposed up to 75C = Not Resistant C = Occasional contact up to 25C - = Information not available at time of publication
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
23/312
www ramset com au 1300 780 063 23
5.5Chemical ResistanceGuide
AnchorSelectionGuide
Resistance of anchors exposed to:
Adhesives Fixings
Chemical Environment ConcentrationChemSet
101 Plus
Structaset
401
ChemSet
801Reo 502 Maxima SS Gal Zinc
Hydrogen Peroxide (Bleach) 5% - - - - -
Hydrogen Peroxide (Bleach) 40% - - - - -
Hydrogen Sulphide Gas 100% - - - - -
Isopropyl Alcohol 100% C C - - - -
Jet Fuel 100% - - - - -
Linseed Oil 100% - -
Lubricating Oil 100% - - - -
Methanol 15% - - - -
Methanol 100% - - - - -
Methylene Chloride 100% - - - - - - -
Mineral Oil 100% - - - -
Nitric Acid < 20% - - - -
Nitric Acid 20 - 70% - - - - -
Parafin / Kerosene (Domestic) 100% C - - - - -
Perchloroethylene 100% - - - - - -
Petroleum 100% - - -
Phenol Aqueous Solution 1% - -
Phenol Aqueous Solution 100% - -
Phosphoric Acid 9% C -
Phosphoric Acid 50% - - -
Potassium Hydroxide (Caustic Potash) 10% / pH 13 C C C - - - -
Potassium Hydroxide (Caustic Potash) 100% - - - - - - -
Sea Water 100% C -
Sodium Hydroxide 20% - - - - - - -
Sodium Hypochlorite Solution 5 - 15% C C - - - - -
Styrene 100% - - - - -
Sulphur Dioxide (40C) 5% - - - - -
Sulphur Dioxide Solution 10% - - - - -
Sulphuric Acid 10% C
Sulphuric Acid 30% - -
Sulphuric Acid 50% - - -
Suphurous Acid 100% - - - - -
Toluene 100% - - - C - -
Turpentine 100% C C C - - - -
Washing Powder 100% - - - -
Water 100%
White Spirit 100% - - - - -Xylene 100%
LEGEND
= Retains 80% of properties when exposed up to 75C = Not Resistant C = Occasional contact up to 25C - = Information not available at time of publication
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
24/312
24 www ramset com au 1300 780 063
AnchoringTechnology
6.1DERIVATION OF CAPACITYInternationally, design standards are becoming more probabilistic in
nature and require sound Engineering assessment of both load case
information and component capacity data to ensure safety as well as
economy.
Published capacity data for RamsetFasteners anchoring productsare derived from Characteristic Ultimate Capacities.
From a series of controlled performance tests, Ultimate Failure Loads
are established for a product.
Obviously, the value obtained in each test will vary slightly, and after
obtaining a sufficient quantity of test samples, the Ultimate FailureLoads are able to be plotted on a chart.
Test values will typically centre about a mean value.
Once the mean Failure Load is established, a statistically sound
derivation is carried out to establish the Characteristic Ultimate
Capacity which allows for the variance in results as well as mean
values.
The Characteristic Value chosen is that which ensures that a 90%
confidence is obtained that 95% of all test results will fall above
this value.
x = Mean Ultimate Capacity
Xuc = Characteristic Ultimate Capacity
Tested ultimate load
Quantityoftestresults
xXuc
AnchoringTechnology
1Derivation of CapacityAnchor Technology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
25/312
www ramset com au 1300 780 063 25
6.2.1 GENERAL
Ramsetanchors are high quality, precision made fastenings secured
with either a torque induced setting action, a displacement inducedsetting action or a chemical bonding action.
Resistance to tensile loads is provided by mechanisms which depend
upon the type of anchor and its method of setting. Information on the
elements that comprise the resistance mechanisms is given separately
for each type of anchor.
Generally, shear load resistance mechanisms are more uniform amongst
anchors, and comprise these elements:
the bolt or stud, and in some cases, the steel spacer of the anchor.the ability of the anchor to resist the bending moment induced by
the shear force.the compressive strength of the concrete.
the shear and tensile strength of the concrete at the surface of the
potential concrete failure wedge.
When loaded to failure in concrete shear, an anchor located near an
edge breaks a triangular wedge away from the concrete.
e
Load
Anchor
Concrete Wedge
Drilled hole
CONCRETE WEDGE FAILURE MODE
6.2.2 TORQUE SETTING ANCHORS
SpaTecPlus, TruBolt, and DynaBolt Plus anchors are inserted
through the hole in the fixture, into a hole drilled into the concrete, andare set by the application of assembly torque to the nut or bolt head.
The diameter of the drilled hole is slightly larger than the outer
diameter of the anchor. When torque is applied to the bolt head or
nut of the anchor, the cone is drawn up into the sleeve to expand its
effective diameter. The wedge action of the cone nut in the sleeve
increases with increasing torque. The reaction of the concrete against
the expanded sleeve of the anchor creates a high friction force
between the anchor and the wall of the drilled hole. The body of the
concrete contains and restricts the expansion forces. The application
of assembly torque produces a preload between the fixture and theconcrete.
If increasing load were to be applied to the fixture, preload would
reduce and finally be removed. At this point, the steel cone would
begin to be drawn further into the expansion sleeve. When loaded to
failure in concrete tension, the failure mode of a correctly installedanchor is characterised by the formation of a concrete cone, the apex
of which is located at the effective depth of the anchor.
Alternatively, if the tensile capacity of the steel is exceeded, the anchor
will break.
TORQUE SETTING ACTION
SpaTecPlus, TruBolt& DynaBolt Plus Anchors
continued over
AnchoringTe
chnology
6.2 Anchoring PrinciplesAnchoring Technology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
26/312
26 www ramset com au 1300 780 063
6.2.2 TORQUE SETTING ANCHORS cont.
Effective depth is the effective length, Leof the anchor less the fixture
thickness, t.
h = Le- t
Note that for the purpose of calculating h, the fixture thickness t
should include the thickness of non structural grout, packing, etc.
Applied tensile loads are resisted by these elements:
the anchor bolt or stud.
the wedge action of the steel cone in the sleeve.
friction between the expanded sleeve and the drilled hole.
shear and tension at the surface of the potential concrete cone.
6.2.3 ROTATION SETTING ANCHORS
The BoaCoil anchor is set by driving the anchor into the hole with
a hammer up to the depth set mark and then, using a spanner orwrench, rotating the bolt through the coil, thereby setting the anchor.
The diameter of the drilled hole is a similar size to that of the anchor.
Resistance to tensile load is provided by the two (2) components which
make up the BoaCoil anchor, the bolt and the coil.
The reaction of the concrete against the expanded anchor creates a
high friction force and an undercut forms between the anchor and
the hole wall. The body of the concrete contains and restricts the
expansion forces. The action of tightening the anchor bolt against thefixture produces a preload between the fixture and the concrete.
As the applied tensile load increases, a commensurate decrease in
preload occurs, until at some point after all preload has been removed,
first slip occurs.
Concrete is locally crushed around the coil as it beds in further,
accompanied by an increase in load capacity.
When failure occurs in the concrete the mode of failure is a broaching
effect whereby load is still being held until the applied load is
equivalent to the shear and tensile capacity of the concrete, at this
point a cone of failure occurs.
h
Le
t
Applied tensile load
Anchor
CONCRETE CONE FAILURE MODE
AnchoringTechnology
6.2 Anchoring PrinciplesAnchoring Technology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
27/312
www ramset com au 1300 780 063 27
6.2.4 DISPLACEMENT SETTING ANCHORS
DynaSetanchors are inserted into a drilled hole, and set
by the displacement of the expander plug.
The diameter of the drilled hole is slightly larger than the outer
diameter of the anchor. When the expander plug is fully driven home
(displaced), it expands the lower portion of the anchor body, to
increase its effective diameter. Because the anchor is expanded by
a series of blows from a setting punch, a certain amount of shock
loading is imparted to the concrete immediately adjacent. The reaction
of the concrete against the expanded body of the anchor creates a
high friction force between the anchor and the wall of the drilled hole.The body of the concrete contains and restricts the expansion forces.
A bolt is subsequently screwed into the anchor.
The mode of failure in concrete tension is characterised by the formation
of a shear cone, the apex of which is located at the effective depth of the
anchor.
Applied tensile loads are resisted by the following elements:
the bolt.
the steel annulus of the anchor.
friction between the expanded anchor and the drilled hole.
shear and tension at the surface of the potentialconcrete cone.
6.2.5CHEMICAL ANCHORS
ChemSetInjection Systems, ChemSetMaximaSpin Capsules,
ChemSetHammer Capsules anchors are set in a drilled hole by thehardening of the chemical adhesive.
The adhesive penetrates the pores and irregularities of the basematerial and forms a key around the threads of the stud. The curedadhesive becomes a hard, strong material that transfers load to the
base material via mechanical and adhesive bonds with the surface of
the drilled hole.
When tested to failure, a shallow concrete cone may form at the top
of the anchor. This cone does not necessarily contribute to the tensile
strength of the anchor, but simply registers the depth at which the
concrete cone strength happens to equate to the cumulative bond
strength of the adhesive to the sides of the hole. For a given concretestrength, the stronger the adhesive bond, the deeper the cone.
Applied tensile loads are resisted by:
the stud.bond between the stud and the adhesive shear in the adhesive bond
between the adhesive and the concrete.shear and tension in the concrete.
Setting tool
DISPLACEMENT SETTING DYNASET ANCHORS
CHEMICAL ANCHORING
Adhesive
covered stud
Applied tensile loadAnchor
Concrete cone
CONCRETE BOND FAILURE MODE
AnchoringTe
chnology
6.2 Anchoring PrinciplesAnchoring Technology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
28/312
28 www ramset com au 1300 780 063
6.3.1 SUITABILITY
Ramsetanchors can be used in plain or in reinforced concrete.
It is recommended that the cutting of reinforcement be avoided. Thespecified characteristic compressive strength fc will not automatically
be appropriate at the particular location of the anchor. The designershould assess the strength of the concrete at the location of the anchor
making due allowance for degree of compaction, age of the concrete,
and curing conditions.
Particular care should be taken in assessing strength near edges and
corners, because of the increased risk of poor compaction and curing.
Where the anchor is to be placed effectively in the cover zone of closely
spaced reinforcement, the designer should take account of the risk of
separation under load of the cover concrete from the reinforcement.
Concrete strength fc determined by standard cylinders, is useddirectly in the equations. Where strength is expressed in concrete
cubes, a conversion is given in the following table:
Where structural base materials are covered with a non-structural
material such as plaster or render, anchors should be embedded to
the design depth in the structural base material. Allowance must be
made for the thickness of the non-structural material when consideringthe application of shear loads, and in determining the moment arm ofapplied bending moments.
In hollow block masonry, where the cores are filled with concrete
grout, Ramsetanchors may be designed and specified similarly as inconcrete, provided the designer assesses the effective strength of the
masonry including the joints.
However, it is not advisable to use certain heavy duty anchors in
unfilled hollow masonry units (either bricks or blocks).These heavy duty anchors include all SpaTecPlus, TruBoltand
ChemSetcapsule anchors, and DynaBolt Plus, BoaCoil anchor,
DynaSet, and Chemical Injection anchors greater than M12 indiameter. In any case the designer should assess the effective strength
of the masonry including the joints, and determine how the loading
is to be transferred to the masonry structure. Load tests should be
conducted on site to assist in assessing masonry strength.
Ramsetheavy and medium duty anchors are not recommended forlow strength base materials such as autoclaved aerated concrete,
except for ChemSetInjection System studs up to M12.
Cube Strength (N/mm2) 20 30 40 50 60
Cylinder Strength fc(MPa) 15 24 33 42 51
AnchoringTechnology
6.3 Base MaterialsAnchoring Technology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
29/312
www ramset com au 1300 780 063 29
Concrete Edge
am
Prohibited zone
Free zone
em
Prohibitedzone
PROHIBITED ZONES FOR SPACINGS AND EDGESMinimumconcretethickness
'bm'
Edge distance "e"
2em
2.0h
em
CONCRETE THICKNESS
Concrete Edge
2*em
Prohibited zone
Free zone
emProhibited
zone
PROHIBITED ZONES AT CORNER FOR
EXPANSION ANCHORS
Spacings, edge distances, and concrete thicknesses are limited to
absolute minima, in order to avoid risks of splitting or spalling ofthe concrete during the setting of Ramsettorque, rotation anddisplacement setting anchors. Absolute minima for stress-freeanchorages such as chemical anchors are defined on the basis of
notional limits, which take account of the practicalities of anchor
placement.
Absolute minimum spacing am and absolute minimum edge distance
em, define prohibited zones where no anchor should be placed. The
prohibited spacing zone around an anchor has a radius equal to the
absolute minimum spacing. The prohibited zone at an edge has a
width equal to the absolute minimum edge distance.
6.3.2 ABSOLUTE MINIMUM DIMENSIONS
Where an expansion anchor is placed at a corner, there is less
resistance to splitting, because of the smaller bulk of concrete around
the anchor. In order to protect the concrete, the minimum distance
from one of the edges is increased to twice the absolute minimum.
The concrete thickness minima given below, does not include concrete
cover requirements, and are not a guide to the structural dimensionsof the element. It is the responsibility of the design engineer to
proportion and reinforce the structural element to carry the loads
and moments applied to it by the anchorage, and to ensure that the
appropriate cover is obtained.
In order to avoid breakthrough during drilling of the hole into which
anchors will be installed, maintain a cover value to the base ofthe hole equal to 2x the drilled hole diameter, dh. ie. for a hole of
20mm diameter allow 40mm cover to the rear face of the substrate
component.
In certain circumstances, it may be possible to install anchors in
thinner concrete elements. If cover to the anchor is not required,and a degree of spalling can be tolerated between the end of the
expansion sleeve and the far surface of the concrete, embedmentclose to the far surface may be feasible. More information on the
conditions for reduced concrete thickness may be obtained from
RamsetEngineers.
Where an anchor is installed at the absolute minimum edge distance
em, substrate thickness must be a minimum of 2 * h.
AnchoringTe
chnology
6.3 Base MaterialsAnchoring Technology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
30/312
30 www ramset com au 1300 780 063
6.4.1 WORKING LOAD DESIGN
Using the permissible stress method which is still valid in many
design situations:
L (applied load) Ra(working load limit capacity)
Working load limits are derived from characteristic ultimate capacities
and factor of safety:
Ra = Ru/ Fs
Factors of safety are related to the mode of failure, and material type,
and the following are considered appropriate for structural anchoring
designs:
fss = factor of safety for steel in tension and bending
= 2.2
fsv = factor of safety for steel in shear
= 2.5
fsc = factor of safety for concrete
= 3.0
6.4.2 STRENGTH LIMIT STATE DESIGN
Designers are advised to adopt the limit state design approach which
takes account of stability, strength, serviceability, durability, fireresistance, and any other requirements, in determining the suitability
of the fixing. Explanations of this approach are found in the designstandards for structural steel and concrete. When designing for
strength the anchor is to comply with the following:
Ru S*
where:
= capacity reduction factor
Ru = characteristic ultimate load carrying capacity
S* = design action effect
Ru = design strength
Design action effects are the forces, moments, and other effects,
produced by agents such as loads, which act on a structure. They
include axial forces (N*), shear forces (V*), and moments (M*), whichare established from the appropriate combinations of factored loads as
detailed in the AS1170Minimum Design Load on Structures seriesof Australian Standards.
Capacity reduction factors are given below, these typically comply
with those detailed in AS4100- Steel Structures and AS3600-Concrete Structures. The following capacity reduction factors are
considered typical:
c = capacity reduction factor, concrete tension
= 0.6
q = capacity reduction factor, concrete shear
= 0.6
n = capacity reduction factor, steel tension
= 0.8
v = capacity reduction factor, steel shear
= 0.8
m = capacity reduction factor, steel bending
= 0.8
Whilst these values are used throughout this document, other values
may be used by making the adjustment for as required.
AnchoringTechnology
6.4 DesignAnchoring Technology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
31/312
www ramset com au 1300 780 063 31
6.5.1 STEEL TENSION
The characteristic ultimate tensile capacity for the steel of an anchor is
obtained from:
Nus = Asfu
where:
Nus = characteristic ultimate steel tensile capacity (N)
As = tensile area (mm2)
= stress area for threaded sections (mm2)
fu = characteristic ultimate tensile strength (MPa)
The tensile working load limit (permissible stress method) for the steel
of a Ramsetanchor is obtained from:
Nas = Nus/ 2.2
The appropriate concrete compressive strength fc is the actual strength
at the location of the anchor, making due allowance for site conditions,
such as degree of compaction, age of concrete, and curing method.Concrete tensile working load limits (permissible stress method) for
anchors are obtained from:
Nac = Nuc/ 3.0
hh
air gap
h
EFFECTIVE DEPTH FOR ANCHORS
6.5.2CONCRETE CONE
Characteristic ultimate tensile capacities for mechanical anchors vary
in a predictable manner with the relationship between:- hole diameter (dh)
- effective depth (h), and- concrete compressive strength (fc)
within a limited range of effective depths, h.
This is typically expressed by a formula such as:
Nuc = factor *dbfactor*h1.5*fc
Anchors may have constraints that apply to the effective depth of theanchor or the maximum or minimum concrete strength applicable.
Anchor effective depth (h) is taken from the surface of the substrate
to the point where the concrete cone is generated. In establishing the
effective depth for mechanical anchors, the designer should allow for
any gap expected to exist between the fixture and the concrete prior to
clamping down.
AnchoringTe
chnology
6.5 TensionAnchoring Technology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
32/312
32 www ramset com au 1300 780 063
6.5.3 PULL-THROUGH
This mode of failure occurs in expansion anchors under tensile loading,
where the applied load exceeds the frictional resistance between eitherthe cone and the expansion sleeve, or the sleeve and the sides of the
drilled hole in the concrete. Failures of this type are often associatedwith anchors that are improperly set, or used in larger diameter holes
drilled into the concrete with over-sized drill bits.
The load carrying capacities of anchors with thick-walled expansion
sleeves such as SpaTecPlus and correctly set DynaSetanchors,
are not sensitive to this mode of failure.
The recommended limits on concrete strength fc in the
determination of concrete cone strength for DynaBoltand TruBoltanchors, act as a precaution against this mode of failure.
6.5.4CONCRETE BOND
Chemical Anchors
Characteristic ultimate tensile load carrying capacities for concrete
bond failure in the compression zone varies with hole depth, effective
depth and concrete strength in a similar manner to concrete cone
failure in mechanical anchors.
Effective anchor depth h is taken from the start of the adhesive,
(usually the surface of the concrete) to the bottom of the stud. For
chemical capsule anchors, it is not usual to deviate from the depths
given in the Section Properties and Data. Whilst it is essential toprovide sufficient resin to fill the space between the stud and the
concrete, the installer must avoid excessive overspill. Hole depths
for capsule anchors may be increased in increments related to the
volume of capsules available. It is recommended to seek advice fromRamsetTechnical Staff before deviating from the recommended holedepths or hole diameters.
The appropriate concrete strength fc to be used in these equations,
is the actual strength at the location of the anchor, making dueallowance for site conditions, such as degree of compaction, age of
concrete, and curing method.
Concrete tensile working load limits (permissible stress method) forRamsetchemical anchors are obtained from:
Nac = Nuc/ 3.0
h
EFFECTIVE DEPTH FOR CHEMICAL ANCHORS
6.5 TensionAnchoring Technology
AnchoringTechnology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
33/312
www ramset com au 1300 780 063 33
6.5.5CRITICAL SPACING
In a group of mechanical anchors loaded in tension, the spacing at
which the cone shaped zones of concrete failure just begin to overlapat the surface of the concrete, is termed the critical spacing, ac.
For chemical anchors the critical spacing is determined by interference
between the cylindrically shaped zones of stress surrounding theanchors.
At the critical spacing, the capacity of one anchor is on the point of
being reduced by the zone of influence of the other anchor. Ramsetanchors placed at or greater than critical spacings are able to develop
their full tensile capacity, as limited by concrete cone or concrete bond
capacity. Anchors at spacings less than critical are subject to reduction
in allowable concrete tensile capacity.
Both ultimate and working loads on anchors spaced between the
critical and the absolute minimum, are subject to a reduction factor
Xna, the value of which depends upon the position of the anchor
within the row:
Nucr= Xna*Nuc
for strength limit state design.
And, for permissible stress method analysis:
Nar = Xna*Nac
For anchors influenced by the cones of two other anchors, as a result
for example, of location internal to a row:
Xna = a / ac 1
Unequal distances (a1 and a2, both < ac) from two adjacent
anchors, are averaged for an anchor internal to a row:
Xna = 0.5 (a1+ a2) / ac
If the anchors are at the ends of a row, each influenced by
the cone of only one other anchor:
Xna = 0.5 (1 + a/ac) 1
The cone of anchor A is influenced by the cones of anchors
B and C, but not additionally by the cone of anchor D. Xna is theappropriate reduction factor as a conservative solution.
Critical spacing (ac) defines a critical zone around a given anchor,
for the placement of further anchors. The critical spacing zone has
a radius equal to the critical spacing. The concrete tensile strengths
of anchors falling within the critical zone are reduced. For clarity, thefigure includes the prohibited zone as well as the critical zone.
ac
Cone of Failure
Anchors
a
aacBond cylinders
Anchors
a a aCone of Failure
Anchors
ANCHORS IN A ROW
A B
C D
ANCHOR GROUP INTERACTION
CRITICAL
No influence. Interaction
occurs between
failure cones.
Capacity reduction
necessary.
Risk of cracking.
REDUCTION PROHIBITED
a ac a < amac> a > am
6.5 TensionAnchoring Technology
AnchoringTe
chnology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
34/312
34 www ramset com au 1300 780 063
6.5.6CRITICAL EDGE DISTANCE
At the critical edge distance for anchors loaded in tension, reduction in
tensile capacity just commences, due to interference of the edge withthe zone of influence of the anchor.
Expansion Anchors
The critical edge distance (ec) for expansion anchors is taken as one
and a half times effective depth:
ec = 1.5 *h
Chemical and Screw In Anchors
For chemical and screw in anchors the critical edge distance is
determined by interference between the edge and the cylindricallyshaped zones of stress surrounding the anchors.
ec = 4 *db
If the edge lies between the critical and the absolute minimum
distance from the anchor, the concrete tensile load reduction
co-efficient Xe, is obtained from the following formula:
Xe = 0.3 + 0.7 *e / ec 1
Applies to em e ec
where:
Xe = edge reduction factor tension
Critical edge distances define critical zones for the placement
of anchors with respect to an edge. The critical edge zone has a width
equal to the critical edge distance. The concrete tensile strengths of
anchors falling within the critical zone are reduced. For clarity, the
figure includes the prohibited zone as well as the critical zone.
Rotation Set Anchors
The critical edge distance for BoaCoil anchor is taken as:
ec = 6 *db
e
ec
Cone of Failure
Anchor
INTERFERENCE OF EDGE WITH CONCRETE CONES
ec
Bond cylinder
Anchor
INTERFERENCE OF EDGE WITH BOND CYLINDER
Concrete Edgeem
ec
Prohibited zone
Free zone Critical zone
CRITICAL EDGE ZONE
6.5 TensionAnchoring Technology
AnchoringTechnology
-
7/27/2019 A Ramset SRB Ed3 Full Edition PDF
35/312
www ramset com au 1300 780 063 35
4 *dh
Minimum for bolt shear
1.25 *dbMinimum for boltand spacer shear
dh
MINIMUM INSERTION FOR BOLT SHEAR
e
Load
Anchor
Concrete Wedge
Drilled hole
CONCRETE WEDGE FAILURE MODE
h = 3 *dh
Minimum for bolt shear
dh
MINIMUM INSERTION FOR BOLT SHEAR
h =3dh For min. bolt shear
h =6dh For max. bolt shear
6.6.1ANCHOR STEEL SHEAR
For an anchor not located close to another anchor nor to a free
concrete edge, the ultimate shear load will be determined by thesteel shear strength of the anchor, provided the effective depth of the
anchor is compliant with the following:
SpaTecPlus