aadvance comprehensive training manual (rev 1.7 oct 2012)

Upload: sandystays

Post on 02-Jun-2018

224 views

Category:

Documents


3 download

TRANSCRIPT

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    1/296

    System Training Manual

    Operation,

    System Build,

    Configuration,

    Programming,

    Troubleshooting,

    & Maintenance

    For the AADvance

    Programmable Controller

    Revision 1.7

    October 2012

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    2/296

    2 AADvance System Training Manual, version 1.7

    Copyright Notice and Disclaimers

    Notice

    In no event will Rockwell Automation be responsible or liable for indirect or consequential

    damages resulting from the use or application of this equipment. The examples given in

    this manual are included solely for illustrative purposes. Because of the many variables andrequirements associated with any particular installation, Rockwell Automation does not

    assume responsibility or reliability for actual use based on the examples and diagrams.

    No patent liability is assumed by Rockwell Automation, with respect to use of information,

    circuits, equipment, or software described in this manual.Reproduction of this manual in whole or in part, without written permission of Rockwell

    Automation is prohibited.

    All trademarks are acknowledged.

    Disclaimer

    It is not intended that the information in this publication covers every possible detail about

    the construction, operation, or maintenance of a control system installation. You shouldrefer to your own (or supplied) system safety manual, installation instructions and

    operator/maintenance manuals.

    Revision and Updating Policy

    This document is based on information available at the time of its publication; however, the

    document contents are subject to change from time to time. You should contact Rockwell

    Automation Technical Support by e-mail [email protected] to check if you

    have the latest version of this publication.

    Copyright Notice, Rockwell Automation 2012This document contains proprietary information that is protected by copyright. All rights

    are reserved.

    Documentation Feedback

    Your comments will help us to serve your documentation needs better. If you discover any

    errors or have any suggestions on how to improve this publication send your comments toour product support group: [email protected]

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    3/296

    Table of Contents 3

    Warning

    Radio Frequency Interference

    Most electronic equipment is influenced by radio frequency interference (RFI). Caution

    should be exercised with regard to the use of portable communications equipment around

    such equipment. Signs should be posted in the vicinity of the equipment cautioning againstthe use of portable communications equipment.

    Maintenance

    Maintenance must be performed only by qualified personnel. Otherwise personal injury or

    death, or damage to the system may result.

    Company BackgroundICS Triplex has been manufacturing and supplying safety critical shutdown and control

    systems since 1969.

    The Regent Triple Modular Redundant (TMR) system was introduced in 1986. Itincorporated Hardware-Implemented Fault Tolerance (HIFT). The Regent system has been

    field-proven in hundreds of installation world-wide.

    The Regent + Plus product family was introduced in 1995 and provided additional features

    and lower cost to the marketplace.

    The Trusted TMR system was introduced in 1997. The Trusted system is compatible with

    legacy Regent and Regent + Plus systems allowing a direct migration path for existing

    systems.

    AADvance was released in 2008. AADvance is a flexible and scalable system designed to

    enhance Trusted, not replace it. AADvance components can be configured as simplex, dual

    or triplicated. Systems may be small and standalone, or large and distributed.

    ApplicabilityThis Training Manual applies to release 1.3.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    4/296

    4 AADvance System Training Manual, version 1.7

    Issue Record

    Issue Date Comments

    1.6 June 2011 Updated for Release 1.2

    1.7 July 2012 Integrated with user manuals and updated for release 1.3

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    5/296

    Table of Contents 5

    Table of Contents

    Chapter 1: Introduction

    Course Goals .................................................................................................................... 1-1Who This Course is Intended For .................................................................................... 1-2

    Recommended Prerequisites ............................................................................................ 1-2

    Course Length .................................................................................................................. 1-2

    Chapter 2: System OverviewPurpose ............................................................................................................................. 2-1

    Objectives ......................................................................................................................... 2-1AADvance System Overview .......................................................................................... 2-2

    Features ......................................................................................................................... 2-2

    General System Layout ................................................................................................. 2-3Internal Bus Structure ................................................................................................... 2-5

    Flexible Configurations .................................................................................................... 2-6

    Non-Redundant, Fail Safe Architecture ........................................................................ 2-7Dual Processor, Non-Redundant I/O ............................................................................ 2-8

    Dual Architecture .......................................................................................................... 2-9

    TMR Input & Processor, Fault Tolerant Output ......................................................... 2-10

    Mixed Architecture ..................................................................................................... 2-11Distributed Architecture .............................................................................................. 2-12

    Test Your Knowledge .................................................................................................... 2-13

    Chapter 3: System ComponentsPurpose ............................................................................................................................. 3-1

    Objectives ......................................................................................................................... 3-1

    System Components ......................................................................................................... 3-2Hardware ........................................................................................................................ 3-2

    Software .......................................................................................................................... 3-3

    Processor Module ............................................................................................................. 3-4

    Processor Base Unit ......................................................................................................... 3-8Digital Input Modules .................................................................................................... 3-10

    Analog Input Modules ................................................................................................... 3-12

    Digital Output Module ................................................................................................... 3-14I/O Module Base Unit .................................................................................................... 3-16

    Field I/O Termination Assemblies ................................................................................. 3-18

    Digital Input Termination Assemblies ......................................................................... 3-18Analog Input Termination Assemblies ......................................................................... 3-22

    Digital Output Termination Assemblies ....................................................................... 3-26Test Your Knowledge .................................................................................................... 3-29

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    6/296

    6 AADvance System Training Manual, version 1.7

    Chapter 4: System BuildPurpose ............................................................................................................................. 4-1Objectives ......................................................................................................................... 4-1

    System Build .................................................................................................................... 4-2

    Environmental Limits ...................................................................................................... 4-3

    Component Sizes and Weights ........................................................................................ 4-4Free Space ........................................................................................................................ 4-6

    Mount a Processor Base Unit ........................................................................................... 4-7

    Mount the I/O Base Units ................................................................................................ 4-8Mount Termination Assemblies ..................................................................................... 4-10

    Mount I/O Expansion Cables ......................................................................................... 4-12

    Module Power ................................................................................................................ 4-14Module Power Supply Requirements.......................................................................... 4-15

    Module Power Connections ........................................................................................ 4-16

    Grounding ...................................................................................................................... 4-18

    Security Dongle .............................................................................................................. 4-19

    Processor Fault Alarm Contacts ..................................................................................... 4-20Serial Connections ......................................................................................................... 4-22

    Field Power .................................................................................................................... 4-23Wire the Field Connections ............................................................................................ 4-24

    Digital Inputs ............................................................................................................... 4-25

    Analog Inputs .............................................................................................................. 4-27Digital Outputs ............................................................................................................ 4-30

    Cable Management ........................................................................................................ 4-32

    Module Polarization ....................................................................................................... 4-34Installing Modules and Blanks ....................................................................................... 4-36

    Heat Dissipation ............................................................................................................. 4-38Parts List ........................................................................................................................ 4-40

    Test Your Knowledge .................................................................................................... 4-42

    Chapter 5: Workbench Overview and ProgrammingPurpose ............................................................................................................................. 5-1

    Objectives ......................................................................................................................... 5-1Workbench ....................................................................................................................... 5-2

    Workbench Overview ...................................................................................................... 5-4

    Dictionary ......................................................................................................................... 5-6Data Types .................................................................................................................... 5-8

    Import / Export Variables ........................................................................................... 5-19

    Equipment Editor ........................................................................................................... 5-23Inserting an I/O Module .............................................................................................. 5-30

    Creating Programs .......................................................................................................... 5-36

    Saving a Project ............................................................................................................. 5-46

    Test Your Knowledge .................................................................................................... 5-47

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    7/296

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    8/296

    8 AADvance System Training Manual, version 1.7

    Chapter 10: Bindings Between ResourcesPurpose ........................................................................................................................... 10-1Objectives ....................................................................................................................... 10-1

    Variable Bindings........................................................................................................... 10-2

    Plan Your Project ........................................................................................................... 10-3

    Prepare Your Project ...................................................................................................... 10-4Linking Resources .......................................................................................................... 10-7

    Simulate and Test Your Bindings ................................................................................ 10-10

    Test Your Knowledge .................................................................................................. 10-12

    Chapter 11: Version Source ControlPurpose ........................................................................................................................... 11-1Objectives ....................................................................................................................... 11-1

    Version Source Control .................................................................................................. 11-2

    Repository ..................................................................................................................... 11-2

    Check In and Check Out ................................................................................................ 11-4

    Version Status Icons ....................................................................................................... 11-5Comparing Version ........................................................................................................ 11-6

    Retrieving Earlier Versions ............................................................................................ 11-8Test Your Knowledge .................................................................................................... 11-9

    Chapter 12: Miscellaneous Workbench FeaturesPurpose ........................................................................................................................... 12-1

    Objectives ....................................................................................................................... 12-1Cross Reference Browser ............................................................................................... 12-2

    Printing ........................................................................................................................... 12-4Passwords ....................................................................................................................... 12-7

    POU Access Control ..................................................................................................... 12-8

    Resource Access Control .............................................................................................. 12-9

    Configuration (Controller) Access Control ................................................................ 12-10Project Access Control ............................................................................................... 12-11

    Export / Import Workbench Elements ......................................................................... 12-12

    Export ........................................................................................................................ 12-12Import ........................................................................................................................ 12-13

    Archive / Restore Projects ............................................................................................ 12-16

    Archive ...................................................................................................................... 12-16Restore ...................................................................................................................... 12-18

    Test Your Knowledge .................................................................................................. 12-22

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    9/296

    Table of Contents 9

    Chapter 13: OPCPurpose ........................................................................................................................... 13-1Objectives ....................................................................................................................... 13-1

    OPC Server .................................................................................................................... 13-2

    Data Access vs. Alarm & Event ................................................................................... 13-3

    Configuring the OPC Server .......................................................................................... 13-4Configuring OPC Clients ............................................................................................... 13-7

    Test Your Knowledge .................................................................................................. 13-10

    Chapter 14: TroubleshootingPurpose ........................................................................................................................... 14-1Objectives ....................................................................................................................... 14-1

    Self Test Cycle Times .................................................................................................... 14-2

    Latching and Unlatching Faults ..................................................................................... 14-3

    Fault Types ..................................................................................................................... 14-4

    Viewing Variables Live ................................................................................................ 14-6I/O State and LED Indications ...................................................................................... 14-7

    Processor Event Log ...................................................................................................... 14-9Test Your Knowledge .................................................................................................. 14-13

    Chapter 15: Replacing ModulesPurpose ........................................................................................................................... 15-1

    Objectives ....................................................................................................................... 15-1Removing Modules ........................................................................................................ 15-2

    Installing Modules .......................................................................................................... 15-3Test Your Knowledge .................................................................................................... 15-5

    Appendix 1: AADvance Discover Util ityPurpose .......................................................................................................................... A1-1

    Objectives ...................................................................................................................... A1-1

    Processor Base Unit Configuration ............................................................................... A1-2

    Appendix 2: GlossaryPurpose .......................................................................................................................... A2-1

    Objectives ...................................................................................................................... A2-1

    Glossary ........................................................................................................................ A2-2

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    10/296

    10 AADvance System Training Manual, version 1.7

    Appendix 3: Puzzles and ExercisePurpose .......................................................................................................................... A3-1Objectives ...................................................................................................................... A3-1

    Hardware Puzzle ........................................................................................................... A3-2

    Software Puzzle ............................................................................................................. A3-3

    Programming Exercise .................................................................................................. A3-4

    Appendix 4: Safety Manual ConsiderationsPurpose .......................................................................................................................... A4-1

    Objectives ...................................................................................................................... A4-1

    Please Read the Safety Manual! .................................................................................... A4-2Rules vs. Recommendations ...................................................................................... A4-2

    High Demand, SIL 3 and Energize to Action Applications ....................................... A4-3

    Utilizing I/O Module Diagnostics .............................................................................. A4-3

    Degraded Run Time Restrictions ............................................................................... A4-7

    I/O Forcing ................................................................................................................. A4-8Safety Manual Checklists ......................................................................................... A4-10

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    11/296

    Introduction 1-1

    Introduction

    Course Goals

    To teach users of the AADvance system:

    How the AADvance system operates as a non-redundantand fault tolerant programmable logic controller.

    What modules and components are used in the

    AADvance system.

    How to put an AADvance system together.

    How to use the workbench to create, modify, test,download and update projects and programs to the

    system.

    How to create user defined functions and functionblocks.

    How to pass safety critical data between controllers.

    How to communicate with the system using OPC.

    How to utilize the version control features.

    How to troubleshoot a system and replace modules.

    Chapter 1

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    12/296

    1-2 AADvance System Training Manual, version 1.7

    Who This Course Is Intended For

    Personnel responsible for designing, configuring andprogramming an AADvance system.

    Personnel responsible for installation, troubleshooting

    and maintenance of an AADvance system.

    Personnel designing a control system that needs tocommunicate with an AADvance system.

    Recommended Prerequisites

    A general knowledge of programmable logic controllers

    (PLCs).

    A background in industrial electronic control principles

    and practices.

    A level of competence using Microsoft Windows

    operating systems and programs.

    Course Length

    4 days

    The majority of the course is hands-on. Students implement

    working solutions using actual hardware and software.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    13/296

    System Overview 2-1

    System Overview

    Purpose

    To provide an overview of the AADvance system and itscomponents.

    Objectives

    To understand the different system components andconfigurations.

    To understand what module configurations meet whatSafety Integrity Levels (SIL).

    To understand the types and names of modules used inthe AADvance system.

    To understand the configuration limits of the system.

    Chapter 2

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    14/296

    2-2 AADvance System Training Manual, version 1.7

    AADvance System Overview

    AADvance is an industrial controller that can be configured fornon-redundant and fault tolerant control and safety applications.It is a scalable system consisting of different modules and

    interconnecting base units. AADvance can be used for a widevariety of applications such as:

    Critical process control

    Emergency shutdown

    Fire and gas detection/protection

    Rotating machinery control

    Burner management

    Boiler and furnace control

    Distributed monitoring and control

    The system is designed for both high and low demandapplications.

    Features

    The main features of AADvance are:

    Flexible modular construction using individual modulesto build a system.

    Operates as a stand alone system or part of a largerdistributed network.

    Easily transforms from a non-redundant to a faulttolerant system.

    I/O module expansion/additions without systeminterruption.

    IEC 61508 certified system; reviewed and approved byTV.

    Handles the full range of IEC 61131 programminglanguages.

    Supports industry standard protocols such as HART,Ethernet, Modbus RTU, Open Modbus TCP, CIP andOPC.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    15/296

    System Overview 2-3

    General System Layout

    The AADvance system consists of:

    A processor base unit (that can hold up to three

    processor modules) I/O base units (that can hold up to three I/O modules)

    I/O termination assemblies (that are inserted into the I/O

    base units)

    Processor and I/O modules (that are inserted into the

    base units)

    Figure 2-1: System Components

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    16/296

    2-4 AADvance System Training Manual, version 1.7

    A processor base unit can support up to 8 I/O base units (up to

    24 I/O modules) on its right side (Bus 1), and up to the same

    number on its left side (Bus 2), for a total of 48 modules.

    Module positions within the I/O base units are numbered from

    01 to 24, the left most position being slot 01. Any individualmodule position within the system is uniquely identified by the

    combination of its bus and slot number, for example 1-01.

    Expansion cables may be used to connect base units, as shown

    in Figure 2-2.

    Figure 2-2: Example System Layout

    I/O base units do

    not plug directly

    into the left

    connector of theprocessor base unit.

    Use an extension

    cable.

    48 simplex

    modules, 24 dual,

    or 16 triplicated.

    There can be a mixwithin a system.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    17/296

    System Overview 2-5

    Internal Bus Structure

    Internal communications between the processor and I/Omodules are supported by command and response buses that arerouted through the processor and I/O base units.

    The processor modules send commands to the I/O modules andprocess their returned responses. Each I/O module has adedicated response line back to the processors. An inter-processor link (IPL) provides the communication links betweendual or triple processor modules.

    Figure 2-3: Internal Bus Structure

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    18/296

    2-6 AADvance System Training Manual, version 1.7

    Flexible Configurations

    The AADvance system is flexible and scalable. Configurationsrange from non-redundant fail safe to triplicated fault tolerant.

    Individual modules are designed as fail safe. Redundantmodules are implemented for fault tolerance.

    Processor Modules

    A single processor module meets SIL 2 requirements.Redundant processor modules (two or more) meet SIL 3requirements. High demand applications also require the use ofredundant processor modules.

    Input Modules

    Individual input modules meet SIL 3 requirements. Redundantmodules are implemented for fault tolerance.

    Output Modules

    Individual output modules meet SIL 2 requirements in a

    normally de-energized application and SIL 3 requirements in anormally energized application. Redundant (dual) modules meetSIL 3 requirements in a normally de-energized application andprovide fault tolerance in a normally energized application.

    Output modules incorporate dual redundant circuitry internally.A dual module configuration provides a quad redundant outputcircuit arrangement.

    Typical system configurations are covered in the following

    pages.

    Triplicated output

    modules are not

    necessary and are

    not supported.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    19/296

    System Overview 2-7

    Non-Redundant, Fail Safe Architecture

    Non-redundant modules will fail safe on the first detected fault

    and the process under control will shut down.

    This configuration meets SIL2 requirements (due to the single

    processor) and is suitable for low demand mode applications

    with either de-energise or energise to trip outputs.

    This configuration is also known as 1oo1D.

    Figure 2-4: 1oo1D Configuration

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    20/296

    2-8 AADvance System Training Manual, version 1.7

    Dual Processors, Non-Redundant I/O

    Non-redundant I/O modules will fail safe on the first detected

    fault and the process under control will shut down.

    The processor modules will degrade to 1oo1D on the first fault

    and must be replaced within the MTTR (Mean Time To Repair)

    assumed in the PFD (Probability of Failure on Demand)

    calculations in order to maintain the SIL 3 rating.

    This configuration is suitable for high as well as low demand

    mode applications and meets SIL3 requirements (SIL 2 for

    energize to trip outputs).

    Figure 2-5: 1oo2D Processors, 1oo1D I/O Configuration

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    21/296

    System Overview 2-9

    Dual Architecture

    Redundant I/O modules provide fault tolerance. Duplicated

    output modules also meet SIL3 requirements for energise to trip

    outputs.

    Input modules will degrade to 1oo1D (fail safe configuration)

    on the first detected fail danger fault with no time limit to

    repair.

    Processor modules will degrade to 1oo1D on a module fault and

    must be replaced within the MTTR (Mean Time To Repair)

    assumed in the PFD (Probability of Failure on Demand)

    calculations in order to maintain the SIL 3 rating.

    A failed output module used for a SIL3 energise to trip must be

    replaced within the MTTR assumed in the PFD calculations.There is no time limit in normally energized applications.

    This configuration is also known as 1oo2D.

    Figure 2-6: Dual Configuration

    Termination

    assemblies can

    span across I/O

    base units.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    22/296

    2-10 AADvance System Training Manual, version 1.7

    TMR Input and Processor, Fault Tolerant

    Output

    Redundant I/O modules provide fault tolerance. Duplicated

    output modules also meet SIL3 requirements for energise to trip

    outputs.

    Input modules will degrade to 1oo2D on a first fault. They will

    degrade to 1oo1D on a second fault with no time limit to repair.

    Processor modules will degrade to 1oo2D on a first fault. They

    will degrade to 1oo1D on second module fault and a processor

    must be replaced within the (Mean Time To Repair) assumed in

    the PFD (Probability of Failure on Demand) calculations in

    order to maintain the SIL 3 rating.

    Output modules will degrade to 1oo1D on the first fault and

    must be replaced within the MTTR assumed in the PFD

    calculations (only for energize to trip outputs). There is no time

    limit for normally energized applications.

    Figure 2-7: TMR (2oo3D) Inputs & Processors, Fault TolerantOutput Configuration

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    23/296

    System Overview 2-11

    Mixed Architecture

    There can be a mixture of architectures and SILs within one

    system. Figure 2-7 shows non-redundant and dual I/O

    configurations with dual processors. Triplicated inputs and/or

    processors may also be included.

    Figure 2-8: Mixed Architecture

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    24/296

    2-12 AADvance System Training Manual, version 1.7

    Distributed Architecture

    It is possible to locate I/O modules in separate systems and link

    the data using a network connection certified for safety

    applications. The systems share variables using bindings, as

    covered in Chapter 10.

    Figure 2-9: Distributed Architecture

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    25/296

    System Overview 2-13

    Test Your Knowledge

    1.

    How many of each I/O module are required to meet SIL3 in a normally energized application?

    2.

    How many processor modules are required to meet SIL3?

    3. What is the minimum number of modules required forfault tolerance?

    4. What is the total number of I/O modules that a processorcan support?

    5.

    Are triplicated output modules supported?

    6. How many response buses does a processor have?

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    26/296

    This page intentionally blank

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    27/296

    System Components 3-1

    System Components

    Purpose

    To provide an overview of the AADvance system and its

    components.

    Objectives

    To understand the types and names of modules andcomponents used in the AAdvance system.

    To understand module and component features.

    Chapter 3

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    28/296

    3-2 AADvance System Training Manual, version 1.7

    System Components

    Hardware

    The current release of AADvance consists of a 9110 processormodule, 9401 & 9402 24V isolated digital input modules (8 &16 channel), 9431 & 9432 4 20mA isolated analog input

    modules (8 & 16 channel), 9451 24V digital output module and

    9481 & 9482 isolated analog output modules (3 & 8 channel).Other components required to complete the systems are a 9100

    processor base unit, 9300 I/O base units for connecting the I/O

    modules to the processor, 9310 bus extension cable and

    termination assemblies for connecting the I/O modules to fielddevices.

    The hardware is modular. A processor base unit supports up tothree processor modules. I/O base units support up to three I/O

    modules. I/O base units mate directly with the processor base

    unit and other I/O base units. I/O base units provide the inter-module communications buses and route power from the

    processor base unit to the I/O modules. The system becomes

    one interconnected mechanical and electrical assembly once

    assembled.

    Figure 3-1: AADvance System

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    29/296

    System Components 3-3

    1 9110

    2 C C

    3 9401 24

    4 9451 24

    5 9852 24 8 C. A

    6 9802 16 C.

    A

    7 9100 B

    8 C

    9

    Table 3-1: AADvance Components

    Hardware may be mounted on a DIN rail or flat panel. The

    system does not require forced air cooling fans.

    Software

    AADvance can be a distributed system where each node

    (referred to as a configuration) has at least a single processor

    module and its associated I/O. Each node is a stand alone

    system configured using IEC 61131-3 languages. Data mayeasily be transferred between nodes using bindings. Programs

    may be simulated offline for testing. AADvance runs a certified

    for safety operating system.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    30/296

    3-4 AADvance System Training Manual, version 1.7

    Processor Module

    The 9110 processor module communicates with the network,

    handles I/O scanning and solves application logic. Itincorporates the following features:

    Rated for applications up to SIL2 (non-redundant) and SIL 3(dual & triple)

    IEC 61508 certified

    Handles full range of IEC61131-3 languages

    Application processor,

    communications co-processor

    and math co-processor Two Ethernet and two serial

    ports (RS485) per processor

    MODBUS, CIP and AADvancesafety network protocols

    Built in diagnostic testing andindependent watchdog

    Removal and replacementwithout system interruption in

    dual or triple configurations System self-discovery at start-

    up

    Figure 3-2: AADvance

    Processor Module

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    31/296

    System Components 3-5

    Battery

    A replaceable battery is used to retain

    the following during a power loss:

    1) system diagnostic logs

    2) keep the real time clock running

    3) variables flagged as retained

    Resources and programs are stored inflash memory that does not need a

    battery.

    The battery is a coin type BR2032 and is secured in a holderunder the front cover of the module. The holder is provided

    with a ribbon to facilitate removal of the battery, as shown in

    Figure 3-3.

    You gain access to the battery by unscrewing the protective

    cover on the lower portion of the front panel.

    Fault Reset Button

    There is a fault reset button on the front of each processor

    module. It is used to clear any fault indications and allow

    replaced I/O modules to come online. However, if a fault is stillpresent, the diagnostic system will report a fault again so

    quickly there will be no visible change in the status indications.

    Module Locking Mechanism

    Each module (processor and I/O) has a locking mechanism that

    secures the module onto its base unit. The locking mechanism is

    a screw visible on the front panel of the module. It is engaged

    by a clockwise quarter turn of a flat blade screwdriver. Themodule incorporates an interlock which detects when a module

    is locked or unlocked.

    Figure 3-3:Processor Battery

    Pressing the fault

    reset button does

    not impact scan

    time or the

    handling of I/O.

    The battery will last

    for approximately

    ten years under

    normal conditions(powered) and six

    months unpowered.

    Modules will only

    run when the screw

    is in the locked

    position.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    32/296

    3-6 AADvance System Training Manual, version 1.7

    LEDs

    There are 10 LEDs on the front of the module. The meaning of

    each LED is described in Table 3-2.

    / ; ;

    /

    ()

    A

    ()

    .

    .

    A ,

    ;

    .

    .

    ()

    A ()

    / .

    .

    /

    A A /,

    A

    A

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    33/296

    System Components 3-7

    A

    ()

    A

    Table 3-2: Processor LED Status

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    34/296

    3-8 AADvance System Training Manual, version 1.7

    Processor Base Unit

    Figure 3-4: AADvance Processor Base Unit

    The 9100 processor base unit accepts up to three processormodules and incorporates the following features:

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    35/296

    System Components 3-9

    Provides redundant connections for the system power

    Provides the connection for ground

    Provides the connections for the external redundant control

    network via two Ethernet connectors per processor

    Provides the connections for two serial ports per processor

    Provides the connection for a security dongle

    Figure 3-5: AADvance Processor Base Unit Detail

    11, 12 1 2 A

    21, 22 1 2 B

    31,33 1 2 C

    11, 12 1 2 A

    21, 22 1 2 B

    31, 32 1 2 C

    1, 2 +24 & 0 1 2

    A C ( )

    C

    Table 3-3: Processor Base Unit Connection Information

    Module power is

    connected to the

    processor base unit

    and connects

    through the I/O

    base units to powerall I/O modules.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    36/296

    3-10 AADvance System Training Manual, version 1.7

    Digital Input Modules

    The 9401 (8 channel) and 9402 (16 channel) are 24Vdc digital

    input modules. They accept galvanically isolated inputs andperform signal conditioning and conversion.

    The modules incorporate extensivediagnostics. Individual modules are

    non-redundant, fail-safe, and

    certified for use in SIL 3

    applications.

    Redundancy and fault tolerance is

    achieved by grouping two or threemodules together with common

    field connections.

    Modules can be removed and

    replaced online without system

    interruption when used in

    redundant (dual or triple)configurations.

    Sequence of events (SOE)resolution is 10 msec.

    The modules measure analog

    voltage in order to perform linemonitoring and field fault detection

    (e.g., open / short circuits).

    Switching levels for each input

    channel are configurable in the

    workbench. The default parametersare:

    Off: 0 to 5V dc

    On: 15 to 30V dc

    There are 11 LEDs on the front of

    the module. The meaning of eachLED is described in Table 3-4.

    Figure 3-6: AADvanceDigital Input Module

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    37/296

    System Components 3-11

    ()

    A (.., )

    C ( )/

    C ( )

    A ( )

    C

    Table 3-4: Digital Input Module LED Status Indications

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    38/296

    3-12 AADvance System Training Manual, version 1.7

    Analog Input Modules

    The 9431 (8 channel) and 9432 (16 channel) are 24Vdc analog

    input modules. They accept galvanically isolated 4 20mAinputs and perform signal conditioning and conversion.

    The modules incorporate extensivediagnostics. Individual modules are

    non-redundant, fail-safe, and

    certified for use in SIL 3

    applications.

    Redundancy and fault tolerance is

    achieved by grouping two or threemodules together with common

    field connections.

    Modules can be removed and

    replaced online without system

    interruption when used in

    redundant (dual or triple)configurations.

    Monitoring levels for each analogchannel are configurable in the

    workbench. The default parameters

    are:

    Fault: 0 to 3.8mA

    Normal: 3.8 to 22.0mA

    Fault: >22.0mA

    The modules support HART

    (Highway Addressable Remote

    Transducer) communications.

    There are 11 LEDs on the front of

    the module. The meaning of each

    LED is described in Table 3-5.Figure 3-7: AADvanceAnalog Input Module

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    39/296

    System Components 3-13

    ()

    A (.., )

    C

    A ( , , )

    C

    Table 3-5: Analog Input Module LED Status Indications

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    40/296

    3-14 AADvance System Training Manual, version 1.7

    Digital Output Module

    The 9451 isolated digital output module connects to eight

    isolated circuits and incorporates the following features:

    Dual series output switchesper channel (1oo2)

    Built in overload protectionper channel

    1A continuous rating for eachcircuit

    Voltage and currentmonitoring (feedback) per

    channel

    Short circuit and open circuitline fault detection for on andoff channels

    Dual redundant field powerwithout the need for external

    diodes

    Output channel reversecurrent protection

    The modules incorporate

    extensive diagnostics. Individualmodules are fail-safe and certifiedfor use in SIL 2 normally de-

    energized and SIL 3 normally

    energized applications.

    Redundancy and fault tolerance is

    achieved by grouping twomodules together with common

    field connections. Two modules

    provide a quad output circuit

    arrangement and full faulttolerance.

    Modules can be removed andreplaced online without system

    interruption when used in

    redundant (dual) configurations.

    Figure 3-8: AADvance

    Digital Output Module

    Triplicated output

    modules are not

    necessary and are

    not supported.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    41/296

    System Components 3-15

    There are 11 LEDs on the front of the module. The meaning of

    each LED is described in Table 3-6.

    ()

    A (.., )

    C /

    C /

    A

    C

    Table 3-6: Digital Output Module LED Status Indications

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    42/296

    3-16 AADvance System Training Manual, version 1.7

    I/O Module Base Unit

    Figure 3-9: AADvance I/O Module Base Unit

    The 9300 I/O module base unit connects the processor to I/Omodules. You can install up to three modules on a base unit.

    The base unit will also allow you to fit the same number of

    termination assemblies in different combinations. For, example,you can fit three simplex termination assemblies; or one dual

    and one simplex together, or one triple termination assembly.The combination will depend entirely on your required

    configuration.

    Termination

    assemblies can

    span across base

    units.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    43/296

    System Components 3-17

    The I/O base unit incorporates the following features:

    Provides connection for one, two or three input/outputmodules depending on the redundancy requirements

    Provides connections with termination assemblies that

    connect to the field input/outputs

    Routes power to the I/O modules from the processor baseunit

    Routes common processor commands to the I/O modules

    Routes responses between the I/O modules and processors

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    44/296

    3-18 AADvance System Training Manual, version 1.7

    Field I/O Termination Assemblies

    Field wiring is connected to termination assemblies (TAs).

    Digital Input Termination Assemblies

    A 9801 digital input termination assembly is a non-redundnatunit that provides connections for 16 non-isolated digital input

    channels and mates with a single 9401 or 9402 24Vdc digital

    input module.

    Figure 3-10: AADvance DI Non-Redundant Termination Assembly

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    45/296

    System Components 3-19

    Figure 3-11 & 12: AADvance DI Non-Redundant

    Termination Assembly and Fuses

    Fuse (shown in the figures above) will blow when an extreme

    over voltage is applied. Fuses can be replaced without removing

    a module using needle-nose pliers.

    The assembly incorporates the following features:

    16 input channels for a simplex configuration

    Industry standard field device connections at the terminalblocks

    Fail safe design with individually fused channels and overvoltage protection

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    46/296

    3-20 AADvance System Training Manual, version 1.7

    The 9802 termination assembly is the dual version and mates

    with two 9401 or 9402 modules, as shown in Figure 3-13.

    Figure 3-13: AADvance DI Dual Termination Assembly

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    47/296

    System Components 3-21

    The 9803 termination assembly is the triplicated version and

    mates with three 9401 or 9402 modules, as shown inFigure 3-14.

    Figure 3-14: AADvance DI Triplicated Termination Assembly

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    48/296

    3-22 AADvance System Training Manual, version 1.7

    Analog Input Termination Assemblies

    A 9831 termination assembly is a non-redundant assembly that

    provides connections for 16 non-isolated analog input channelsand mates with a single 9431 or 9432 analog input module.

    Figure 3-15: AADvance AI Non-Redundant Termination Assembly

    Each channel has a 50mA fuse to prevent component damage inover-current situations. Fuses can be replaced without removing

    a module using needle-nose pliers

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    49/296

    System Components 3-23

    Figure 3-16: AADvance AI Simplex Termination Assembly

    The assembly incorporates the following features:

    16 input channels for a simplex configuration

    Industry standard field device connections at the terminalblocks

    Fail safe design with individually fused channels

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    50/296

    3-24 AADvance System Training Manual, version 1.7

    The 9832 termination assembly is the dual version and mates

    with two 9431 or 9432 modules.

    Figure 3-17: AADvance AI Dual Termination Assembly

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    51/296

    System Components 3-25

    The 9833 termination assembly is the triplicated version and

    mates with three 9431 or 9432 modules.

    Figure 3-18: AADvance AI Triplicated Termination Assembly

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    52/296

    3-26 AADvance System Training Manual, version 1.7

    Digital Output Termination Assemblies

    Figure 3-19: AADvance DO Non-Redundant Termination Assembly

    A 9851 termination assembly is a non-redundant assembly that

    provides termination for 8 digital outputs and mates with asingle 9451 24Vdc digital output module.

    The termination assembly routes the module output channelsvia the mating connector to the field connection terminal

    blocks.

    The 24Vdc field voltages VFIELD 1 and VFIELD 2, used bythe output module for the output field voltages, are connected at

    the terminal blocks and routed via two replaceable 10A fuses F1

    and F2. These fuses, shown in Figures 3-19 through 21, giveprotection for the output module against field faults.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    53/296

    System Components 3-27

    Figure 3-20 & 21: AADvance DO Termination Assemblyand Field Power Fuses

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    54/296

    3-28 AADvance System Training Manual, version 1.7

    Figure 3-22: AADvance DO Dual Termination Assembly

    A 9852 termination assembly is a dual assembly that provides

    termination for 8 digital outputs and mates with two 945124Vdc digital output modules.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    55/296

    System Components 3-29

    Analog Output Termination Assemblies

    Figure 3-19: AADvance AO Non-Redundant Termination Assembly

    A 9881 termination assembly is a non-redundant assembly that

    provides termination for 8 analog outputs and mates with asingle 9481 or 9482 analog output module.

    The termination assembly routes the module output channels

    via the mating connector to the field connection terminal

    blocks.

    Although it has a fuse cover, there are no fuses. The visible

    components are capacitors for EMC suppression.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    56/296

    3-30 AADvance System Training Manual, version 1.7

    Figure 3-22: AADvance DO Dual Termination Assembly

    A 9882 termination assembly is a dual assembly that provides

    termination for 8 analog outputs and mates with two 9481 or9482 analog output modules.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    57/296

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    58/296

    This page intentionally blank

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    59/296

    System Build 4-1

    System Build

    Purpose

    To summarize how to assemble an AADvance system.

    Objectives

    To understand the environmental limits of the system.

    To understand module power requirements, heatdissipation and weight.

    To be able to install base plates, termination assemblies,cables and modules.

    To be able to wire field devices to the system.

    Chapter 4

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    60/296

    4-2 AADvance System Training Manual, version 1.7

    System Build

    Note: This chapter is a condensed version of the AADvanceSystem Build Manual, which system integrators are

    highly encouraged to read.

    AADvance is a modular system. Base units snap together usingmating connectors and retaining clips.

    The base units provide the interconnections for module power,processor and I/O data. Once connected, the base units form a

    single mechanical assembly.

    The insertion and removal of modules will not disturb the

    electrical connections with field devices.

    AADvance modules are suitable for wall mounting or forinstallation within an enclosure. The system is designed to meet

    its electromagnetic compatibility criteria without further

    protection from an enclosure.

    AADvance can be panel or DIN rail mounted (using TS35

    35mm x 7.5mm standard symmetric rails).

    Use the following steps to assemble a system.

    1)

    Mount a processor base unit

    2)

    Mount the I/O base units

    3)

    Mount termination assemblies

    4)

    Mount I/O expansion cables (optional)

    5)

    Wire the field connections

    6) Connect power and ground

    7) Mount the processor and I/O modules

    8) Ensure adequate power and heat dissipation

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    61/296

    System Build 4-3

    Environmental Limits

    The design of each installation must ensure that the operatingenvironment is within the tolerances of the equipment.

    Consideration must be given to proper control of:

    Temperature

    Humidity

    Vibration and shock

    EMI / RFI

    Temperature

    Operating temperature: -20 to 70C (-4 to 158F)

    Note: Processors limited to 60C (140F)

    Storage & transport temperature: -40 to 70C (-40 to 158F)

    Humidity

    The system is designed to operate in the range of 10 to 95%

    relative humidity, non-condensing. It is important to avoidchanges of humidity and temperature that could produce

    condensation. Condensation on any type of electrical equipment

    can result in equipment failures or improper operation.

    Vibration and shock

    The modules are designed to withstand a 15g peak shock andvibration to 0.5g sinusoidal sweep between 10Hz to 150Hz.

    Care must be taken to isolate the system from any sources of

    extreme mechanical shock or vibration.

    EMI / RFI

    The modules have been designed to meet the requirements of

    EN500081/82 and EN55011/55022.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    62/296

    4-4 AADvance System Training Manual, version 1.7

    Component Size and Weights

    (

    233 126 18

    (9 5 )

    166 42 118

    (6 1 4 )

    Table 4-1: AADvance Component Sizes

    The total depth of a base unit and module is 136 mm (5-in).

    Figure 4-1: Component Dimensions (in mm)

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    63/296

    System Build 4-5

    Ensure that the mounting assembly can support the weight of

    the AADvance components using the Table 4-2.

    (

    460 (16)

    / 133 (5) 430 (15)

    (8 ) 280 (10)

    (16 ) 340 (12)

    (8 ) 280 (10)

    (16 ) 340 (12)

    340 (12)

    (8 ) 290 (10.5)

    133 (5)

    260 (10)

    360 (13)

    40 (1)

    / 50 (2)

    (2 ) 670 (24)

    Table 4-2: AADvance Component Weights

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    64/296

    4-6 AADvance System Training Manual, version 1.7

    Free Space

    The system requires a free space at least 140mm deep (fromfront to back) between the rear panel of an enclosure and the

    inside of an enclosure door.

    Allow sufficient free space around the base units. Every

    application needs space on at least three sides, as follows:

    Space above, to manipulate and install field wiring

    Space below, to enable modules to fit and to be able tograsp a module during removal

    Space to the right, to maneuver an I/O base unit duringassembly or in the event of installing a new base unit.

    If an expansion cable is to connect to the left-most base unit, thecontroller also needs space to the left, to fit the expansion cable

    adaptor.

    Figure 4-2 shows the minimum recommended clearances for

    DIN rail mounting.

    Figure 4-2: Required Free Space (in mm)

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    65/296

    System Build 4-7

    Mount a Processor Base Unit

    A processor base unit will support up to three processormodules.

    Figure 4-3: Installing a Processor Base Unit

    1) Place the processor base unit onto the DIN rail.

    2) Secure the base unit by pushing the bottom retaininglever as far to the left as it will go until it latches in the

    locked position.

    Note: Base plates may also be mounted flush on a panel wallusing screws without a DIN rail.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    66/296

    4-8 AADvance System Training Manual, version 1.7

    Mount the I/O Module Base Units

    You can install up to three I/O modules on an I/O base unit.

    Figure 4-4: Installing an I/O Base Unit

    1)

    Mount a 9300 I/O base unit onto the DIN rail and slide it

    towards the 9100 processor base unit.

    2)

    Ensure the joining connectors are fully mated.

    3) Secure the base unit by pushing the bottom retaining

    lever as far to the left as it will go until it latches in thelocked position.

    4)

    Insert the plastic retaining clips into the top and the

    bottom slots.

    Note: Base plates mounted flush on a panel wall will need to

    be connected before mounting.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    67/296

    System Build 4-9

    This page is intentionally blank.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    68/296

    4-10 AADvance System Training Manual, version 1.7

    Mount Termination Assemblies

    Termination assemblies connect to I/O base units. You can fitthree simplex assemblies, or one dual and one simplex, or a

    single triplicated termination assembly. The combination used

    will depend on your systems specific configurationrequirements.

    1) Insert the termination assembly (TA) retaining clip (at

    the rear of the TA) into the slot on the plastic base unit,as shown in Figure 4-5. Press down and slide the

    assembly upwards as far as it will go.

    2) Ensure the retaining tab clips over the circuit board to

    secure the TA in position, as shown in Figure 4-6.

    Figure 4-5: Installing a Termination Assembly

    Termination

    assemblies can

    span across base

    units.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    69/296

    System Build 4-11

    Figure 4-6: Installing a Termination Assembly

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    70/296

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    71/296

    System Build 4-13

    Figure 4-8: I/O Expansion Cable Adapters

    Standard expansion cable assemblies are two meters long.(Custom lengths can be supplied.) The maximum possible

    length of an entire bus (the combination of I/O base units and

    expansion cables) is 8 meters.

    Terminators are notrequired at the end

    of the bus (last base

    unit).

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    72/296

    4-14 AADvance System Training Manual, version 1.7

    Module Power

    Power supplies should be installed in a position where the 24Vdc supply wiring can be kept reasonably short. Figure 4-9

    shows an arrangement with one power supply unit for a non-

    redundant, fail safe controller.

    Figure 4-9: Power Supply Mounting

    It is recommended that the negative side of the field supply begrounded. This will avoid possible fail danger conditions that

    can be caused by some earth fault monitors used with floating

    power supplies.

    The power supply protection of the system is within the

    modules, not the base units. To protect the base units, the powerdistribution arrangement must provide a circuit breaker on the

    input side of each power source. The system can withstand a

    reverse polarity connection without permanent damage.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    73/296

    System Build 4-15

    Module Power Supply Requirements

    AADvance requires 24Vdc power with a tolerance between

    18Vdc and 32Vdc. The system has been designed to operatewith most commercially available industrial uninterruptable

    power supplies (UPS). To select a suitable power supply,calculate the overall system load that must be powered (usingTable 4-3), include any additional devices and add a

    contingency allowance between 25% and 50%.

    9110 8

    9401 3.3

    9402 4.0

    9431 3.3

    9432 4.0 9451 3.0

    9482 3.6

    Table 4-3: AADvance Module Power Requirements

    Field devicesrequire an

    additional source of

    power.

    High Availability

    I/O (1715) use the

    same hardware but

    ratings are different

    these arecalculated as worst

    case using different

    methods.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    74/296

    4-16 AADvance System Training Manual, version 1.7

    Module Power Connections

    AADvance modules are designed to operate from twoindependent 24Vdc sources with a common return. Power is

    connected to the two plugs PWR-1 and PWR-2 on the processor

    base plate, as shown in Figures 4-10 and 4-11. The centerterminals are normally left unconnected.

    Figure 4-10: Processor Base Unit Power Connection

    Figure 4-11: Module Power Connection

    Power is distributedto the I/O modules

    through the base

    units.

    The terminal blocks

    can be removed for

    easy access.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    75/296

    System Build 4-17

    The processor base unit links the +24V dc connections to thecenter terminal of each connector, as shown in Figure 4-12.

    This link may be used to connect the +24V dc supply to other

    processor base units.

    Figure 4-12: Processor Base Unit Power Connection Detail

    ,

    2.5 2(12 )

    ,

    2.5 2(12 )

    7 (9/32 )

    Table 4-4: Module Power Wiring Sizes

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    76/296

    4-18 AADvance System Training Manual, version 1.7

    Grounding

    AADvance systems may have up to three separate groundsystems:

    An AC safety ground(sometimes called the dirtyground) to protect people in the event of a fault. Theground stud on the processor base unit, shown in Figure

    4-13, should be connected to the AC safety ground,

    along with all exposed metalwork such as DIN rails.

    An instrument ground(sometimes called the cleanground or 0 Vdc ground) to provide a good stable 0Vreference for the system. Every signal return should be

    referenced to the instrument ground, which will be

    isolated from the AC safety ground.

    Some field wiring will need shielded (screened) cable.There may be a shield groundin addition to the ACsafety and instrument grounds to provide a common

    point to terminate cable shields.

    Figure 4-13: AADvance Processor Base Unit SafetyGround Connection Detail

    Systems may also be supplied with an IS (intrinsic safety)

    ground as required.

    Copper bus bars are normally used for grounding.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    77/296

    System Build 4-19

    Security Dongle

    The system uses a dongle to control security. The dongle mustbe connected in order to download programs, make online

    changes, or perform locking (forcing). The dongle is supplied

    with the processor base unit.

    Figure 4-14: Security Dongle

    Processor Fault Alarm Contacts

    The terminal block marked 'FLT' is no longer used and does not

    work from release 1.1.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    78/296

    4-20 AADvance System Training Manual, version 1.7

    Serial Connections

    Each processor has two serial RS485 connections. The systemsupports both 2 wire (half duplex) and 4 wire (full duplex)

    configurations, with multi-drop supported in both

    configurations.

    The pin-outs for the six serial connections on the processor base

    unit are shown in Figure 4-17 and Table 4-6.

    Figure 4-17: Serial Connections

    Table 4-6: Serial Connections

    ( (

    ()

    /

    ()

    ()

    /

    ()

    0

    ()

    ()

    The terminal blocks

    can be removed for

    easy access.

    'Receive' and

    'transmit') are with

    respect to the

    processor base unit.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    79/296

    System Build 4-21

    Field Power

    Field devices require an external source of power. This may bethe power source used for the controller or a separate power

    source, depending on the application.

    Each input circuit should be fused. Each output module group(e.g., a module pair) should also have the field power fused. For

    a typical system, it is recommended that you provide a single

    breaker on the output of the field power source, followed by oneor more fused terminals.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    80/296

    4-22 AADvance System Training Manual, version 1.7

    Wire the Field Connections

    Field wiring is connected direct to the terminal blocks of atermination assembly (TA).

    ,

    1.5 2(16 )

    ,

    1.5 2(16 )

    6 ( )

    Table 4-7: Field Connection Wiring Sizes

    Non-redundant termination assemblies have commoned power.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    81/296

    System Build 4-23

    Digital Inputs

    Figure 4-18: Simplex Digital Input Field Connections

    Figure 4-19: Dual and Triplicated Digital Input Field Connections

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    82/296

    4-24 AADvance System Training Manual, version 1.7

    Figure 4-20: Standard Digital Input Field Loop Circuit

    Figure 4-21: Line Monitored Digital Input Field Loop Circuit

    Note: Please refer to the System Build manual for more detailson normally de-energized inputs, recommended resistor

    values and input voltage threshold settings, etc.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    83/296

    System Build 4-25

    Analog Inputs

    Figure 4-22: Simplex Analog Input Field Connections

    Figure 4-23: Dual and Triplicated Analog Input Field Connections

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    84/296

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    85/296

    System Build 4-27

    Figure 4-26: Four Wire Analog Input Loop Circuit

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    86/296

    4-28 AADvance System Training Manual, version 1.7

    Digital Outputs

    Figure 4-27: Simplex & Dual Digital Output FieldTerminations

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    87/296

    System Build 4-29

    Figure 4-28: Digital Output Field Loop Circuit

    For inductive loads, connect a diode at the actuator to protectthe controller against back EMF.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    88/296

    4-30 AADvance System Training Manual, version 1.7

    Cable Management

    The field, power and other system wiring will be connected toterminals along the top of the base units. It is recommended a

    length of trunking be located above each set of base units for

    cable management.

    Figure 4-29: Cable Management

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    89/296

    System Build 4-31

    This page is intentionally blank.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    90/296

    4-32 AADvance System Training Manual, version 1.7

    Module Polarization

    Module polarization prevents the wrong module from beinginserted into the wrong base unit. Modules are supplied with

    plugs already fitted, as shown in Figure 4-30.

    The legend for the polarization pins is shown in the lower left ofthe processor base unit and on each I/O termination assembly,

    as shown in Figure 4-31. The positions are numbered 1 through6. The three pins are lettered A, B and C with A being on thetop. Each pin, shown in Figure 4-32, is fitted in the base unit so

    that the index recess is next to the relevant numbered position

    shown in Table 4-8, as shown in Figures 4-32 and 33.

    9110 1 1 1

    9401 2 1 1

    9402 2 1 1

    9431 2 1 39432 2 1 3

    9451 3 1 1

    9481 3 1 2

    9482 3 1 2

    Table 4-8: Module Polarizing Pin Allocation

    Figure 4-30: ModulePolarization

    Figure 4-31: ModulePolarizing Pin Base

    Unit Positions

    Terminationassemblies are

    supplied with the

    pins already

    inserted.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    91/296

    System Build 4-33

    Figure 4-32: Polarizing Pin

    Figure 4-33 shows the pins inserted for a 9401 digital input

    module and TAs.

    T9801/2/3 TA T9401 TA

    Figure 4-33: Inserted Polarizing Pins

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    92/296

    4-34 AADvance System Training Manual, version 1.7

    Installing Modules and Blanks

    Installing Modules

    Modules are installed by carefully pressing them onto the base

    unit, as shown in Figure 4-34, using the following procedure.

    1.

    Inspect the connectors on the back of the module for

    bent or damaged pins.

    2. Make sure the slot on the head of the module clamp

    screw is vertical.

    3.

    Place the new module on to the dowel pins on the base

    unit.

    4. Push the module home until the connectors are fully

    mated.5. Turn the locking screw located on the front of the

    module turn clockwise using a broad flat bladed

    screwdriver.

    Figure 4-34: Installing a Module

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    93/296

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    94/296

    4-36 AADvance System Training Manual, version 1.7

    Heat Dissipation

    AADvance is designed to operate without forced air cooling.

    Ensure that adequate ventilation is provided. Ambient

    temperature within an enclosure should not exceed 60C

    (140F), unless the enclosure does not contain the processors, inwhich case the limit is 70C (158F).

    The system dissipates all the power it uses as heat. Module

    power is connected to the processor base plate. Field power is

    connected to I/O termination assemblies and some of that powerwill also be dissipated as heat. Use Table 4-9 to estimate the

    maximum heat generated by the modules.

    8

    (8 ) 3.3

    (16 ) 4.0

    0.11

    (8 ) 3.3

    (16 ) 4.0

    (25) 0.06

    3.0

    (1) 0.5

    (8 ) 3.6

    Table 4-9: AADvance Module Heat Dissipation

    Base plates and

    modules must be

    mounted vertically

    to allow proper air

    circulation through

    the modules.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    95/296

    System Build 4-37

    This page is intentionally blank.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    96/296

    4-38 AADvance System Training Manual, version 1.7

    Parts ListNote:Parts may be added to this list in future releases. Please

    consult Rockwell Automation for an updated list of availableparts.

    Software Development Environment

    9082 IEC61131 Workbench suite with single user, single

    controller license9083 IEC61131 Workbench suite with single user,

    unlimited controller license

    9084 IEC61131 Workbench suite with five user, unlimited

    controller license9085 Five additional user license (for use with item 9084)

    9030 OPC portal server

    Processor Equipment9100 Processor base unit9110 Processor module

    9193 Blanking cover (short), for unused position on

    processor base unit

    Expansion Cable Assemblies

    Expansion cable assembly, comprising expansion cable and two

    adaptors (handed):9310-02 2 meter expansion cable (approximately 6 feet)

    9310-xx Custom length expansion cable

    I/O Equipment

    9300 I/O base unit9401 Digital input module, 24V dc, 8 channel

    9402 Digital input module, 24V dc, 16 channel

    9431 Analog input module, 8 channel

    9432 Analog input module, 16 channel9451 Digital output module, 24V dc, 8 channel

    9481 Analog output module, 3 channel

    9482 Analog output module, 8 channel9191 Blanking cover (tall), for unused position on I/O base

    unit

    The 9193 blanking cover may be used for positions on an I/Obase unit with a termination assembly fitted.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    97/296

    System Build 4-39

    Termination Assemblies

    9801 Digital input TA, 16 channel, simplex, non-isolated

    9802 Digital input TA, 16 channel, dual9803 Digital input TA, 16 channel, TMR

    9831 Analog input TA, 16 channel, simplex, non-isolated

    9832 Analog input TA, 16 channel, dual9833 Analog input TA, 16 channel, TMR9851 Digital output TA, 24V dc, 8 channel, simplex, non-

    isolated

    9852 Digital output TA, 24V dc, 8 channel, dual, non-isolated

    9881 Analog output TA, 8 channel, simplex

    9882 Analog output TA, 8 channel, dual

    Consumable Spares

    9901 Input fuse, 50mA (pack of 20)

    9902 Output fuse, 10A (pack of 20)

    9903 Coding peg / Polarizing Pins (pack of 20)9904 Backplane clip (pack of 20)

    9905 Battery, lithium, 3V 255mAh, coin pattern BR2032 or

    equivalent, for 9110 processor module (pack of 10)

    9906 Replacement security dongle

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    98/296

    4-40 AADvance System Training Manual, version 1.7

    Test Your Knowledge

    1.

    What temperature range are the processors designed to

    operate within?

    2.

    What are the two ways to mount base plates?

    3. Where is I/O module field power connected?

    4. How much power would a system with the followingmodules require? Assume all input modules are 16

    channel.

    dual processors

    two sets of triplicated analog input modules

    five simplex analog input modules

    four simplex digital input modules

    two sets of dual digital output modules

    three simplex digital output modules

    5.

    How much would the system described in question 4

    weigh?

    6.

    How many I/O module base units would be required for

    the system described in question 4?

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    99/296

    Workbench Overview and Programming 5-1

    Workbench Overview and

    Programming

    Purpose

    To review the steps required to develop programs.

    Objectives

    To be able to create projects.

    To be able to add variable names to the dictionary.

    To be able to build an I/O configuration and assignvariable names.

    To be able to configure the hardware: serial portsettings, input module thresholds, watchdog timers, etc.

    To be able to create, edit and compile programs.

    Chapter 5

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    100/296

    5-2 AADvance System Training Manual, version 1.7

    Workbench

    The AADvance workbench is used to build control and safetyprograms. These programs can be distributed across several

    hardware platforms referred to as configurations.

    Configurations communicate with each other throughnetworks. Configurations run resourceswhich are groups ofprograms (up to 250) that are compiled and downloaded.

    The workbench is IEC 61131-3 compliant, offering all fivelanguages (ladder, function block, structured text, instruction

    list and sequential function chart). Programs can be simulated

    and tested on the PC before downloading to actual hardware.

    Starting the Workbench

    Start the workbench: StartAll ProgramsAADvance

    AADvance Workbench. The workbench will run in demo mode

    for 30 days without a license. Full functionality requires alicense (e.g., USB dongle).

    This manual

    describes software

    functionality

    included in release

    1.31 (Build

    1.20.508).

    Please refer to the

    Configuration

    Guide for more

    information on the

    licensing options

    and the operation

    of the License

    Manager.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    101/296

    Workbench Overview and Programming 5-3

    Start a New Project

    To start a new project, select File | New Project/Library, or use

    the New button. The following dialog box will appear.

    Figure 5-1: New Project Dialog Box

    The name is used as the project folder name. Project file namesare always PRJLIBRARY.MDB.

    The Workbench allows multiple people to work on a project atthe same time. This requires locating certain files in a location

    that others can access (if you wish to utilize this capability). The

    Destination Folderis the location on your PC where various

    local files are stored. The Repository Pathis the location folderwhere other centralized version information is stored. The

    default location for both folders is on the C drive of the PC that

    has the software loaded, but the Repository folder can belocated on a central server.

    The topics of the

    repository, version

    control and check-

    in/out are covered

    in Chapter 11.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    102/296

    5-4 AADvance System Training Manual, version 1.7

    Workbench Overview

    The link architecture view graphically displays the resources ofa project and any links between them. This is the default view

    of the workbench providing a main entry point to all editors.

    Figure 5-2: Link Architecture View

    A configurationrepresents a hardware target (controller).

    AADvance configurations run a single resource. A resourceconsists of the dictionary of tag names, I/O configuration and

    POUs (Program Organization Units).

    If you do not see the

    Project Tree on the

    left, click Window |

    Show Project Tree.

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    103/296

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    104/296

    5-6 AADvance System Training Manual, version 1.7

    Dictionary

    The typical first step is to define variable (tag) names in thedictionary. These names can then be connected to processor

    variables, I/O modules, I/O channels and then used in programs.

    However, it is not mandatory to define variables first. You cancreate programs first and enter variable names in the program

    editor. When doing so, the workbench will request basic

    information on the variable (i.e., type, scope, direction,attribute). While variables created this way will later appear in

    the dictionary, you may need to define them in more detail in

    the dictionary before compiling and running your program(s)(e.g., MODBUS address, SOE, initial value, retain, etc).

    Open the dictionary using the Project | Variables menu selection

    or the dictionary button. Expand the tree on the left to see thewindow displayed in Figure 5-4.

    Figure 5-4: Workbench Dictionary View

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    105/296

    Workbench Overview and Programming 5-7

    The various components are sorted in a tree-like hierarchy. The

    tree name is displayed on the window title bar. The fourdictionary tree views, as shown in Figure 5-5, are: variables,

    parameters, types and defined words.

    Figure 5-5: Dictionary Views

    In the All Variables workspace on the right, you can toggle

    between Grid Mode and Row Mode by right clicking in theworkspace and making the appropriate selection in the pop-up

    menu, as shown in Figure 5-6.

    Figure 5-6: Switching Between Grid and Row Mode

  • 8/10/2019 AADvance Comprehensive Training Manual (Rev 1.7 Oct 2012)

    106/296

    5-8 AADvance System Training Manual, version 1.7

    Data Types

    Variables are unique identifiers of data which can be used in theprograms of a project. There are many different variables types,

    such as:

    BOOL: Boolean (true / false)

    SINT: Signed short integer (8 bit) from -128 to +127.

    USINT: Unsigned short integer (8 bit) from 0 to 255.

    BYTE: Byte (8 bit) from 0 to 255.

    INT: Signed single integer (16 bit) from -32,768 to32,767.

    UINT: Unsigned single integer (16 bit) from 0 to

    65,535. WORD: Word (16 bit) from 0 to 65,535.

    DINT: Signed double integer (32 bit) from-2,147,483,648 to +2,147,483,647.

    UDINT: Unsigned double integer (32 bit) from 0 to4,294,967,295.

    DWORD: Double Word (32 bit) from 0 to4,294,967,295.

    LINT: Signed long integer (64 bit) from

    -9,223,372,036,854,775,808 to9,223,372,036,854,775,807.

    ULINT: Unsigned Long Integer (64 bit) from 0 to18,446,744,073,709,551,615.

    LWORD: Long Word (64 bit) from 0 to18,446,744,073,709,551,615.

    REAL: Real (floating, single precision) (32 bit), 1 signbit + 23 mantissa bits + 8