Ashley-Edison Servo Electronic SES Series Three Phase AC Voltage Regulators, are designed to ensure that, should the incoming mains voltage drift high or low, the output voltage remains continuously constant. With inbuilt Transient Voltage Surge Suppression (TVSS), they also protect electrical and electronic load equipment against, all to common, harmful high-energy surges, transients and voltage spikes. With over 25 years of unrivalled experience, gained in some of the world’s most challenging and demanding power environments, SES AC Voltage Regulators & Stabilizers include as standard many advanced protection and control features - such as Independent Phase Sensing, TVSS, Input Circuit Breaker, Bypass Control Switch and Soft-Switch On - which others only offer as expensive add-on options. SES SERIES AC VOLTAGE REGULATORS THREE PHASE (LOW VOLTAGE) 6kVA to 400kVA AC Voltage Regulators & Stabilizers Ashley-Edison I Global Power Protection FEATURES Automatic Voltage Regulation Step less automated voltage regulation - ideal for 95% of all applications. Wide Range of Power Ratings Three Phase 6 to 400KVA Broad Input Voltage Swing Ranges Input Swing - ±15% (S15), ±20% (S20), ±25% (S25), ±30% (S30) - (To Specify) High Efficiency Better than 98% for low running costs. Precise Output Voltage Regulation Output Voltage Accuracy ± 0.5% / ± 1% Transient Voltage Surge Suppression TVSS - Protects loads against harmful high-energy surges, transients and spikes. Independent Phase Balancing & Control Independent phase voltage sensing and control to ensure the individual phase voltages remain stable - regardless of load unbalance . Inbuilt High Overload Capability Ideal for loads with an inherent initial high current draw on start up. Soft-Switch On / Start Up Load Protection Protection of the load from momentary over voltage situations on start up. Over / Low Voltage Protection Ability to automatically shutdown the Voltage Stabilizer in the event of the input supply voltage going outside the input voltage window. Bypass Control Switch Manual electronic controls bypass facility. Phase Failure Protection Protection of the load in the event of phase failure. Front Panel Status Monitoring & Metering Front Panel display showing system status with internal output Voltmeter with phase selector switch. Input Circuit Breaker Input over current protection fitted as standard on all models. Optional Accessories Output Circuit Breaker, Manual Maintenance Bypass Switch, Ammeter with Phase Selector Switch, No Volt Remote Monitoring Contacts, Digital Power Metering (with RS-485 interface option) & Lightning Arrestors. Compliance with International Standards Designed, manufactured and supplied to comply with leading international standards CE Conformity Fully compliant and labelled Warranty 3 Years / 36 Months as Standard www.AshleyEdison.com SES-LY/LD-3P-JAN-2012 AC mains voltage fluctuations can cause equipment to behave erratically and malfunction. Some systems may even break down due to these fluctuations, noise or spikes. Failure to ensure the incoming mains voltage is stable and clean, can often result in costly equipment repairs. Cost Efficient Voltage Regulation with Fast Speed of Response, High Output Voltage Accuracy and inbuilt Energy Saving Ability. With tight output voltage regulation of 1%, or better, and high efficiency, SES Series Three Phase AC Voltage Regulators are configurable to optimize energy usage and deliver energy cost savings. Generating no magnetic interference, they are completely unaffected by Power Factor, or Load and Frequency variations and are capable of withstanding high instantaneous overloads. Their compact and quiet nature means these Voltage Regulators are suitable for indoor use and may be located near to sensitive equipment. When looking for affordable durable Quality voltage protection, the SES Range of AC Voltage Regulators & Stabilizers from Ashley-Edison lead the market in all respects. TYPICAL APPLICATIONS Computers Medical Equipment Electronics Equipment Testing Equipment Laboratory Equipment POS Terminals TV / Radio Broadcasting Stations Process Control Systems Elevators / Lifts Audio / Video Systems Security Systems Production Lines CNC Equipment SMT Equipment SES Status Monitoring Panel

Upload: ashleyedison

Post on 11-Apr-2015

691 views

Category:

Documents


0 download

DESCRIPTION

Ashley Edison SES Low Voltage 208 / 120V Three Phase Voltage Stabilizers with an input voltage swing of +/-15% delivering cost efficient voltage stabilisation at unbeatable prices from 6 to 200 kVA - http://www.AshleyEdison.com

TRANSCRIPT

Page 1: AC Voltage Stabilizers Three Phase 6 to 200 kVA - Ashley Edison 208V / 120V SES-LY-3P-S15 Sales Brochure

Ashley-Edison Servo Electronic SES Series Three Phase AC Voltage Regulators,

are designed to ensure that, should the incoming mains voltage drift high or low, the

output voltage remains continuously constant. With inbuilt Transient Voltage Surge

Suppression (TVSS), they also protect electrical and electronic load equipment

against, all to common, harmful high-energy surges, transients and voltage spikes.

With over 25 years of unrivalled experience, gained in some of the world’s most

challenging and demanding power environments, SES AC Voltage Regulators &

Stabilizers include as standard many advanced protection and control features - such

as Independent Phase Sensing, TVSS, Input Circuit Breaker, Bypass Control Switch

and Soft-Switch On - which others only offer as expensive add-on options.

SES SERIES AC VOLTAGE REGULATORS

THREE PHASE (LOW VOLTAGE)

6kVA to 400kVA

AC Voltage Regulators

& Stabilizers

Ashley-Edison I Global Power Protection

FEATURES

Automatic Voltage Regulation

Step less automated voltage regulation - ideal for

95% of all applications.

Wide Range of Power Ratings

Three Phase 6 to 400KVA

Broad Input Voltage Swing Ranges

Input Swing - ±15% (S15), ±20% (S20), ±25% (S25),

±30% (S30) - (To Specify)

High Efficiency

Better than 98% for low running costs.

Precise Output Voltage Regulation

Output Voltage Accuracy ± 0.5% / ± 1%

Transient Voltage Surge Suppression

TVSS - Protects loads against harmful high-energy

surges, transients and spikes.

Independent Phase Balancing & Control

Independent phase voltage sensing and control to

ensure the individual phase voltages remain stable -

regardless of load unbalance .

Inbuilt High Overload Capability

Ideal for loads with an inherent initial high current

draw on start up.

Soft-Switch On / Start Up Load Protection

Protection of the load from momentary over voltage

situations on start up.

Over / Low Voltage Protection

Ability to automatically shutdown the Voltage

Stabilizer in the event of the input supply voltage

going outside the input voltage window.

Bypass Control Switch

Manual electronic controls bypass facility.

Phase Failure Protection

Protection of the load in the event of phase failure.

Front Panel Status Monitoring & Metering

Front Panel display showing system status with

internal output Voltmeter with phase selector switch.

Input Circuit Breaker

Input over current protection fitted as standard on all

models.

Optional Accessories

Output Circuit Breaker, Manual Maintenance Bypass

Switch, Ammeter with Phase Selector Switch, No Volt

Remote Monitoring Contacts, Digital Power Metering

(with RS-485 interface option) & Lightning Arrestors.

Compliance with International Standards Designed, manufactured and supplied to comply with leading international standards

CE Conformity Fully compliant and labelled

Warranty 3 Years / 36 Months as Standard

www.AshleyEdison.com SES-LY/LD-3P-JAN-2012

AC mains voltage fluctuations

can cause equipment to

behave erratically and

malfunction. Some systems

may even break down due to

these fluctuations, noise or

spikes. Failure to ensure the

incoming mains voltage is

stable and clean, can often

result in costly equipment

repairs.

Cost Efficient Voltage

Regulation with Fast Speed

of Response, High

Output Voltage Accuracy

and inbuilt Energy

Saving Ability.

With tight output voltage regulation of 1%, or better, and high

efficiency, SES Series Three Phase AC Voltage Regulators are

configurable to optimize energy usage and deliver energy cost

savings. Generating no magnetic interference, they are completely

unaffected by Power Factor, or Load and Frequency variations

and are capable of withstanding high instantaneous overloads.

Their compact and quiet nature means these Voltage Regulators

are suitable for indoor use and may be located near to sensitive

equipment.

When looking for affordable durable Quality voltage protection,

the SES Range of AC Voltage Regulators & Stabilizers from

Ashley-Edison lead the market in all respects.

TYPICAL APPLICATIONS

Computers

Medical Equipment

Electronics Equipment

Testing Equipment

Laboratory Equipment

POS Terminals

TV / Radio Broadcasting Stations

Process Control Systems

Elevators / Lifts

Audio / Video Systems

Security Systems

Production Lines

CNC Equipment

SMT Equipment

SES Status Monitoring Panel

Page 2: AC Voltage Stabilizers Three Phase 6 to 200 kVA - Ashley Edison 208V / 120V SES-LY-3P-S15 Sales Brochure

SES SERIES Low Voltage - Three Phase - 50/60Hz

Voltage Choices Available

LY & LD SERIES - Three Phase Input Voltage Windows (Line to Line) & Output Accuracy

Nominal Three Phase

Voltage

Output Voltage Accuracy

± % of Nominal

INPUT VOLTAGE SWINGS /SWING MODEL NO VARIANTS

S15 S20 S25 S30

LY Series (LD) Series

6 to 200 kVA 6 to 400 kVA

6 to 120 kVA 6 to 300 kVA

6 to 100 kVA 6 to 250 kVA

6 to 75 kVA 6 to 200 kVA

190V

± 0.5% (± 1%) 162v to 219v (± 15%)

152v to 228v (± 20%)

143v to 238v (± 25%)

133v to 247v (± 30%)

± 3% 158v to 224v (-17% / +18%)

148v to 234v (-22% / +23%)

139v to 243v (-27% / +28%)

129v to 253v (-32% / +33%)

± 5% 154v to 230v (-19% / +21%)

144v to 239v (-24% / +26%)

135v to 249v (-29% / +31%)

125v to 258v (-34% / +36%)

200V

± 0.5% (± 1%) 170v to 230v (± 15%)

160v to 240v (± 20%)

150v to 250v (± 25%)

140v to 260v (± 30%)

± 3% 166v to 236v (-17% / +18%)

156v to 246v (-22% / +23%)

146v to 256v (-27% / +28%)

136v to 266v (-32% / +33%)

± 5% 162v to 242v (-19% / +21%)

152v to 252v (-24% / +26%)

142v to 262v (-29% / +31%)

132v to 272v (-34% / +36%)

208V

± 0.5% (± 1%) 177v to 239v (± 15%)

166v to 250v (± 20%)

156v to 260v (± 25%)

146v to 270v (± 30%)

± 3% 173v to 245v (-17% / +18%)

162 to 256v (-22% / +23%)

152v to 266v (-27% / +28%)

141v to 277v (-32% / +33%)

± 5% 168v to 252v (-19% / +21%)

158v to 262v (-24% / +26%)

148v to 272v (-29% / +31%)

137v to 283v (-34% / +36%)

220V

± 0.5% (± 1%) 187v to 253v (± 15%)

176v to 264v (± 20%)

165v to 275v (± 25%)

154v to 286v (± 30%)

± 3% 183v to 260v (-17% / +18%)

172v to 271v (-22% / +23%)

161v to 282v (-27% / +28%)

150v to 293v (-32% / +33%)

± 5% 178v to 266v (-19% / +21%)

167v to 277v (-24% / +26%)

156v to 288v (-29% / +31%)

145v to 299v (-34% / +36%)

240V

± 0.5% (± 1%) 204v to 276v (± 15%)

192v to 288v (± 20%)

180v to 300v (± 25%)

168v to 312v (± 30%)

± 3% 199v to 283v (-17% / +18%)

187v to 295v (-22% / +23%)

175v to 307v (-27% / +28%)

163v to 319v (-32% / +33%)

± 5% 194v to 290v (-19% / +21%)

182v to 302v (-24% / +26%)

170v to 314v (-29% / +31%)

158v to 326v (-34% / +36%)

SES-LY/LD-S* Ashley-Edison

Voltage Stabilizer

In situations where there is a

reasonably good mains supply, a

Stabilizer offering an input variation

swing of ±15% (S15 Models) will

usually be more than acceptable, but

in more remote locations, or countries

where the national supply

infrastructure is less developed,

variations of ±20% or greater may be

needed to be accommodated by the

Stabilizer.

An output voltage to within ±0.5%

(±1%) of the preset output voltage is

the norm when specifying a Voltage

Stabilizer. However if a lower output

voltage accuracy of ±3%, or ±5%, can

be accommodated by the load

equipment, the input voltage window

can be further widened proportionally.

Given that the cost of the Stabilizer is

linked to the size of the input voltage

range it has to handle, accepting a

lower output voltage accuracy may

prove to be a more cost

efficient

solution than simply opting

for a larger standard

swing model.

INPUT

VOLTAGE

OUTPUT

VOLTAGE

± 0.5% / ± 1%

www.AshleyEdison.com SES-LY/LD-3P-JAN-2012

Input Voltage Window Options - Low Voltage LY & LD Models

4 WIRE SOLUTIONS THREE PHASE WITH NEUTRAL (4 WIRE SYSTEMS)

LY SERIES 6 to 200 kVA

Low Voltage Models:

190/110V, 200/115V, 208/120V or 220/127V.

H SERIES 6 to 600 kVA

High Voltage Models:

380/220V, 400/230V & 415/240V. (440/254V & 480V/277V- Special Order).

3 WIRE SOLUTIONS THREE PHASE - NO NEUTRAL (3 WIRE SYSTEMS)

LD SERIES 6 to 400 kVA

Low Voltage Models:

190V, 200V, 208V, 220 or 240V.

HD SERIES 6 to 600 kVA

High Voltage Models:

380V, 400V & 415V. (440V & 480V- Special Order).

Other voltages, including step up / step down voltage options, available on individual request / quotation.

Selecting the right Output Voltage

Accuracy for your needs.

Copyright © 2012 Ashley-Edison reserve the right to change any

or all of the specifications indicated or implied without prior notice.

Please Note – These Stabilisers are not

designed to support / protect voltage “back

feed” applications, where energy is required

to be also fed back into the utility supply.

Page 3: AC Voltage Stabilizers Three Phase 6 to 200 kVA - Ashley Edison 208V / 120V SES-LY-3P-S15 Sales Brochure

SES-LY-3P-S15 SERIES 6 to 200 KVA - Three Phase - 4 Wire

Technology: Servo Electronic - Variable Transformer controlled, series regulation transformer (buck-boast transformer with secondary wired in series with the load).

Input Voltage Swing: ±15% (or -17% +18% or -19% +21%) Three Phase, 4 Wire (3P+N)

Output Voltage: Presettable for any voltage between 190/110V, 200/115V, 208/120V or 220/127V, (Customer to specify), Three Phase, 4 Wire

The permissible input voltage swing is relative to the preset output voltage.

Output Voltage Accuracy:

± 0.5%, ± 3% & ± 5% - auto selection based on

the input voltage swing.

Frequency : 47 - 65Hz

Response Time: <1.5ms

Correction Time: A 10% supply variation will be corrected to

within 2.5% in 0.6 seconds

Efficiency: 98%

Power Factor: Any lagging to 0.95 leading

Surge ratings: 10 x max. current rating for 2 seconds 3 x max. current rating for 1 minute 2 x max. current rating for 2 minutes

Surge Suppression: TVSS - Protects loads against harmful high-energy Spikes and Transient voltages.

Total Harmonic Distortion:

Less than 1%

Technical Specifications

Independent Phase Control:

Maintains each phase voltage stable irrespective of load unbalance, even up to 100% load unbalance.

Soft-Switch On: Ensures the output voltage is set at minimum upon Switch-On before commencing stabilization - protects load equipment from damaging start up voltage surges.

Environment: Temperature range –15 to 45 °C. Derate by 2% for each additional °C Up to max 60 °C . Suitable for indoor tropical use 95% RH (non-condensing). Maximum altitude 1000m. Derate by 2.5% for each additional 500m.

Construction: Enclosures to IP20 (NEMA 1 Style) - BS EN 60529

Paint Color: RAL 7032 (Grey - Powder Coating)

Conformance: Complies with BS EN 55022 and the relevant parts of the BS EN 61000 series of standards – as updated.

CE Conformity: CE Marked - being fully compliant with European Union Directives 2004/108/EC (The EMC Directive) and 2006/95/EC (The Low Voltage Directive) in force from January 2007.

Standard Warranty: Three Years / 36 Months from date of supply

Standard Features: Status Monitoring Panel, Input Circuit Breaker, Over/Low Voltage Protection, Phase Failure Protection, Bypass Control Switch Voltmeter / Phase Selector Switch (internal)

Optional Accessories: Output Circuit Breaker, Manual Maintenance Bypass Switch, Ammeter with Phase Selector Switch, No Volt Remote Monitoring Contacts, Digital Power Metering (with RS-485 interface option) & Lightning Arrestors.

Optional Step-Up Voltage Feature:

Ideal for applications where the utility supply voltage is different from the load equipment’s requirement - see SES-LH SERIES Step-Up AC Voltage Stabilizers / Regulators.

Optional Isolation Transformer:

Shielded isolation transformer providing extra protection between the utility and the load. Protects against common and transverse mode electrical noise - see PCS SERIES AC Power Conditioners.

www.AshleyEdison.com

SES-LY-3P-S15 - JAN– 2012

Copyright © 2012 Ashley-Edison reserve the right to change any or all of the specifications indicated or implied

without prior notice.

Note: Optional Accessories added may affect dimensions - subject to confirmation.

AC Voltage Regulators & Stabilizers

Note: Higher KVA rating and alternative voltage options available to order / individual request.

S15 Product Selection Table

Model: Rating

KVA

Amps @

190V

Amps @

200V

Amps @

220V

Dimensions (mm)

W x H x D

Weight

(KG)

Enclosure No:

Amps @

208V

SES-6LY-3P-S15 6 18 17 15 300 x 550 x 590 65 331 16

SES-10LY-3P-S15 10 30 28 26 300 x 550 x 590 66 331 27

SES-15LY-3P-S15 15 45 43 39 300 x 550 x 590 74 331 41

SES-20LY-3P-S15 20 60 57 52 300 x 550 x 590 81 331 55

SES-30LY-3P-S15 30 91 86 78 300 x 550 x 590 91 331 83

SES-45LY-3P-S15 45 136 129 118 380 x 670 x 780 144 332 124

SES-60LY-3P-S15 60 182 173 157 490 x 800 x 990 166 333 166

SES-75LY-3P-S15 75 227 216 196 500 x 900 x 1000 214 334 208

SES-100LY-3P-S15 100 303 288 262 500 x 900 x 1000 260 334 277

SES-120LY-3P-S15 120 364 346 314 1000 x 1300 x 580 410 335 333

SES-150LY-3P-S15 150 455 432 393 1000 x 1300 x 580 650 335 416

SES-180LY-3P-S15 180 546 519 472 1000 x 1300 x 580 700 335 499

SES-200LY-3P-S15 200 607 577 524 1000 x 1300 x 580 750 335 555

S15 Enclosure Types

331 to 332 - SES-6LY-3P-S15 to SES-45LY-3P-S15 (On Castors)

333 to 334 - SES-60LY-3P-S15 to SES-100LY-3P-S15 (On Castors)

335 - SES-120LY-3P-S15 to SES-200LY-3P-S15

FRONT VIEW REAR VIEW RIGHT SIDE VIEW

FRONT VIEW REAR VIEW RIGHT SIDE VIEW

FRONT VIEW REAR VIEW LEFT VIEW RIGHT VIEW

WANT TO KNOW MORE . . . . .

Want to learn more about our

Servo Electronic AC Voltage

Regulators / Stabilizers and Power

Conditioners?

Please ask for a copy of our . . . .

Servo Electronic

Overview Brochure

ALSO AVAILABLE IN OUTDOOR IP54 (NEMA 3 STYLE) ENCLOSURES - OSES / OPCS SERIES