accc®-uls monte carlo - ctc global · 2019-01-22 · *accc® conductor is produced with 1350...
TRANSCRIPT
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 228.5 mm2 450.9 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-011) 10.54 mm 0.415 in.
Nominal Cross-sectional Area of Core 87.3 mm2 0.135 in
2
Overall Diameter of Conductor 20.78 mm 0.818 in.
Nominal Cross-sectional Area of the Conductor 315.8 mm2 0.489 in
2
Ultimate Tensile Strength of Conductor1,2 238.5 kN 53.6 kips
Rated Strength of Core - 375 ksi (2586 MPa) 225.6 kN 50.7 kips
Core Nominal Mass per unit length 157 kg/km 106 lb/kft
Conductor Nominal Mass per unit length 791.8 kg/km 532.2 lb/kft
Aluminum Nominal Mass per unit length** 634.8 kg/km 426.7 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.21E-05 /oC 6.72E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 82.5 GPa 12.0 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.1230 ohm/km 0.1979 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.1257 ohm/km 0.2024 ohm/mile
AC Nominal Resistance at 75ºC 0.1504 ohm/km 0.2422 ohm/mile
AC Nominal Resistance at 180ºC 0.2024 ohm/km 0.3258 ohm/mile
691 @ 100C & 50 Hz
1027 @ 180C & 50 Hz
GMR (estimated) 0.009 m 0.029 ft
Inductive Reactance 0.222 ohm/km 0.429 ohm/mile
Capacitive Reactance 0.194 Mohm-km 0.100 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-140-E ACCC-TW ULS 229 (451 kcmil) Monte Carlo Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 235.2 sq. mm (464.2 kcmil)
ACCC®-ULS Monte Carlo
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 313.8 mm2 619.3 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-008) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in
2
Overall Diameter of Conductor 22.40 mm 0.882 in.
Nominal Cross-sectional Area of the Conductor 374.1 mm2 0.580 in
2
Ultimate Tensile Strength of Conductor1,2 173.6 kN 39.0 kips
Rated Strength of Core - 375 ksi (2586 MPa) 155.9 kN 35.1 kips
Core Nominal Mass per unit length 109 kg/km 73 lb/kft
Conductor Nominal Mass per unit length 976.7 kg/km 656.4 lb/kft
Aluminum Nominal Mass per unit length** 867.7 kg/km 583.1 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.57E-05 /oC 8.75E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 72.3 GPa 10.5 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0893 ohm/km 0.1437 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0915 ohm/km 0.1476 ohm/mile
AC Nominal Resistance at 75ºC 0.1095 ohm/km 0.1764 ohm/mile
AC Nominal Resistance at 180ºC 0.1471 ohm/km 0.2369 ohm/mile
827 @ 100C & 50 Hz
1233 @ 180C & 50 Hz
GMR (estimated) 0.009 m 0.030 ft
Inductive Reactance 0.220 ohm/km 0.424 ohm/mile
Capacitive Reactance 0.189 Mohm-km 0.098 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-152-E ACCC-TW ULS 314 (619 kcmil) Oslo Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 323 sq. mm (637.5 kcmil)
ACCC®-ULS Oslo
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 383.2 mm2 756.2 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-011) 10.54 mm 0.415 in.
Nominal Cross-sectional Area of Core 87.3 mm2 0.135 in
2
Overall Diameter of Conductor 25.00 mm 0.984 in.
Nominal Cross-sectional Area of the Conductor 470.5 mm2 0.729 in
2
Ultimate Tensile Strength of Conductor1,2 247.2 kN 55.6 kips
Rated Strength of Core - 375 ksi (2586 MPa) 225.6 kN 50.7 kips
Core Nominal Mass per unit length 157 kg/km 106 lb/kft
Conductor Nominal Mass per unit length 1216.0 kg/km 817.3 lb/kft
Aluminum Nominal Mass per unit length** 1059.0 kg/km 711.8 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.49E-05 /oC 8.27E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 74.5 GPa 10.8 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0730 ohm/km 0.1175 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0750 ohm/km 0.1210 ohm/mile
AC Nominal Resistance at 75ºC 0.0896 ohm/km 0.1445 ohm/mile
AC Nominal Resistance at 180ºC 0.1203 ohm/km 0.1938 ohm/mile
943 @ 100C & 50 Hz
1412 @ 180C & 50 Hz
GMR (estimated) 0.010 m 0.034 ft
Inductive Reactance 0.212 ohm/km 0.410 ohm/mile
Capacitive Reactance 0.183 Mohm-km 0.095 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-150-E ACCC-TW ULS 383 (756 kcmil) 25 mm Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 394.5 sq. mm (778.5 kcmil)
ACCC®-ULS 25 mm
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 406.4 mm2 802.0 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-007) 9.53 mm 0.375 in.
Nominal Cross-sectional Area of Core 71.3 mm2 0.111 in
2
Overall Diameter of Conductor 25.14 mm 0.990 in.
Nominal Cross-sectional Area of the Conductor 477.7 mm2 0.740 in
2
Ultimate Tensile Strength of Conductor1,2 207.1 kN 46.6 kips
Rated Strength of Core - 375 ksi (2586 MPa) 184.2 kN 41.4 kips
Core Nominal Mass per unit length 128 kg/km 86 lb/kft
Conductor Nominal Mass per unit length 1253.1 kg/km 842.2 lb/kft
Aluminum Nominal Mass per unit length** 1125.1 kg/km 756.1 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.62E-05 /oC 8.99E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 71.2 GPa 10.3 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0690 ohm/km 0.1110 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0710 ohm/km 0.1147 ohm/mile
AC Nominal Resistance at 75ºC 0.0848 ohm/km 0.1368 ohm/mile
AC Nominal Resistance at 180ºC 0.1138 ohm/km 0.1833 ohm/mile
971 @ 100C & 50 Hz
1454 @ 180C & 50 Hz
GMR (estimated) 0.010 m 0.034 ft
Inductive Reactance 0.213 ohm/km 0.411 ohm/mile
Capacitive Reactance 0.183 Mohm-km 0.095 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-154-E ACCC-TW ULS 406 (802 kcmil) Leipzig Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 418.4 sq. mm (825.6 kcmil)
ACCC®-ULS Leipzig
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 453.7 mm2 895.4 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-008) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in
2
Overall Diameter of Conductor 26.40 mm 1.039 in.
Nominal Cross-sectional Area of the Conductor 514.0 mm2 0.797 in
2
Ultimate Tensile Strength of Conductor1,2 181.4 kN 40.8 kips
Rated Strength of Core - 375 ksi (2586 MPa) 155.9 kN 35.1 kips
Core Nominal Mass per unit length 109 kg/km 73 lb/kft
Conductor Nominal Mass per unit length 1363.8 kg/km 916.6 lb/kft
Aluminum Nominal Mass per unit length** 1254.8 kg/km 843.4 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.74E-05 /oC 9.68E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 68.4 GPa 9.9 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0617 ohm/km 0.0993 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0637 ohm/km 0.1031 ohm/mile
AC Nominal Resistance at 75ºC 0.0760 ohm/km 0.1228 ohm/mile
AC Nominal Resistance at 180ºC 0.1019 ohm/km 0.1642 ohm/mile
1039 @ 100C & 50 Hz
1560 @ 180C & 50 Hz
GMR (estimated) 0.011 m 0.035 ft
Inductive Reactance 0.210 ohm/km 0.406 ohm/mile
Capacitive Reactance 0.180 Mohm-km 0.093 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-155-E ACCC-TW ULS 454 (895 kcmil) Stockholm 3L Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 467 sq. mm (921.7 kcmil)
ACCC®-ULS Stockholm 3L
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 463.3 mm2 914.3 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-008) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in
2
Overall Diameter of Conductor 26.40 mm 1.039 in.
Nominal Cross-sectional Area of the Conductor 523.6 mm2 0.812 in
2
Ultimate Tensile Strength of Conductor1,2 182.0 kN 40.9 kips
Rated Strength of Core - 375 ksi (2586 MPa) 155.9 kN 35.1 kips
Core Nominal Mass per unit length 109 kg/km 73 lb/kft
Conductor Nominal Mass per unit length 1390.6 kg/km 934.6 lb/kft
Aluminum Nominal Mass per unit length** 1281.6 kg/km 861.3 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.75E-05 /oC 9.73E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 68.2 GPa 9.9 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0605 ohm/km 0.0974 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0625 ohm/km 0.1011 ohm/mile
AC Nominal Resistance at 75ºC 0.0746 ohm/km 0.1205 ohm/mile
AC Nominal Resistance at 180ºC 0.0999 ohm/km 0.1610 ohm/mile
1049 @ 100C & 50 Hz
1576 @ 180C & 50 Hz
GMR (estimated) 0.011 m 0.035 ft
Inductive Reactance 0.210 ohm/km 0.406 ohm/mile
Capacitive Reactance 0.180 Mohm-km 0.093 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-156-E ACCC-TW ULS 463 (914 kcmil) Stockholm 2L Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 476.9 sq. mm (941.2 kcmil)
ACCC®-ULS Stockholm 2L
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 507.5 mm2 1001.5 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-008) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in
2
Overall Diameter of Conductor 27.72 mm 1.091 in.
Nominal Cross-sectional Area of the Conductor 567.8 mm2 0.880 in
2
Ultimate Tensile Strength of Conductor1,2 184.4 kN 41.5 kips
Rated Strength of Core - 375 ksi (2586 MPa) 155.9 kN 35.1 kips
Core Nominal Mass per unit length 109 kg/km 73 lb/kft
Conductor Nominal Mass per unit length 1515.3 kg/km 1018.4 lb/kft
Aluminum Nominal Mass per unit length** 1406.3 kg/km 945.2 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.79E-05 /oC 9.94E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 67.4 GPa 9.8 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0553 ohm/km 0.0890 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0573 ohm/km 0.0928 ohm/mile
AC Nominal Resistance at 75ºC 0.0683 ohm/km 0.1104 ohm/mile
AC Nominal Resistance at 180ºC 0.0914 ohm/km 0.1474 ohm/mile
1112 @ 100C & 50 Hz
1673 @ 180C & 50 Hz
GMR (estimated) 0.011 m 0.037 ft
Inductive Reactance 0.207 ohm/km 0.401 ohm/mile
Capacitive Reactance 0.177 Mohm-km 0.092 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-195-E ACCC-TW ULS 508 (1002 kcmil) Warsaw Data Sheet www.ctcglobal.com Date Produced: 7/14/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 522.4 sq. mm (1031 kcmil)
ACCC®-ULS Warsaw
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 524.5 mm2 1035.1 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-007) 9.53 mm 0.375 in.
Nominal Cross-sectional Area of Core 71.3 mm2 0.111 in
2
Overall Diameter of Conductor 28.14 mm 1.108 in.
Nominal Cross-sectional Area of the Conductor 595.8 mm2 0.923 in
2
Ultimate Tensile Strength of Conductor1,2 213.7 kN 48.0 kips
Rated Strength of Core - 375 ksi (2586 MPa) 184.2 kN 41.4 kips
Core Nominal Mass per unit length 128 kg/km 86 lb/kft
Conductor Nominal Mass per unit length 1579.2 kg/km 1061.3 lb/kft
Aluminum Nominal Mass per unit length** 1451.2 kg/km 975.3 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.73E-05 /oC 9.63E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 68.6 GPa 10.0 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0534 ohm/km 0.0859 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0553 ohm/km 0.0897 ohm/mile
AC Nominal Resistance at 75ºC 0.0660 ohm/km 0.1067 ohm/mile
AC Nominal Resistance at 180ºC 0.0883 ohm/km 0.1423 ohm/mile
1136 @ 100C & 50 Hz
1711 @ 180C & 50 Hz
GMR (estimated) 0.011 m 0.038 ft
Inductive Reactance 0.206 ohm/km 0.398 ohm/mile
Capacitive Reactance 0.176 Mohm-km 0.091 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-157-E ACCC-TW ULS 525 (1035 kcmil) Dublin Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 539.9 sq. mm (1065.5 kcmil)
ACCC®-ULS Dublin
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 543.5 mm2 1072.6 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-007) 9.53 mm 0.375 in.
Nominal Cross-sectional Area of Core 71.3 mm2 0.111 in
2
Overall Diameter of Conductor 28.62 mm 1.127 in.
Nominal Cross-sectional Area of the Conductor 614.8 mm2 0.953 in
2
Ultimate Tensile Strength of Conductor1,2 214.8 kN 48.3 kips
Rated Strength of Core - 375 ksi (2586 MPa) 184.2 kN 41.4 kips
Core Nominal Mass per unit length 128 kg/km 86 lb/kft
Conductor Nominal Mass per unit length 1638.9 kg/km 1101.5 lb/kft
Aluminum Nominal Mass per unit length** 1510.9 kg/km 1015.5 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.75E-05 /oC 9.72E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 68.3 GPa 9.9 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0517 ohm/km 0.0832 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0536 ohm/km 0.0870 ohm/mile
AC Nominal Resistance at 75ºC 0.0639 ohm/km 0.1034 ohm/mile
AC Nominal Resistance at 180ºC 0.0855 ohm/km 0.1378 ohm/mile
1160 @ 100C & 50 Hz
1748 @ 180C & 50 Hz
GMR (estimated) 0.012 m 0.038 ft
Inductive Reactance 0.205 ohm/km 0.396 ohm/mile
Capacitive Reactance 0.175 Mohm-km 0.091 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-194-E ACCC-TW ULS 544 (1073 kcmil) Kolkata Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 559.5 sq. mm (1104.1 kcmil)
ACCC®-ULS Kolkata
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 544.9 mm2 1075.3 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-011) 10.54 mm 0.415 in.
Nominal Cross-sectional Area of Core 87.3 mm2 0.135 in
2
Overall Diameter of Conductor 29.00 mm 1.142 in.
Nominal Cross-sectional Area of the Conductor 632.2 mm2 0.980 in
2
Ultimate Tensile Strength of Conductor1,2 256.3 kN 57.6 kips
Rated Strength of Core - 375 ksi (2586 MPa) 225.6 kN 50.7 kips
Core Nominal Mass per unit length 157 kg/km 106 lb/kft
Conductor Nominal Mass per unit length 1663.0 kg/km 1117.7 lb/kft
Aluminum Nominal Mass per unit length** 1506.0 kg/km 1012.2 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.66E-05 /oC 9.23E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 70.3 GPa 10.2 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0514 ohm/km 0.0827 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0536 ohm/km 0.0863 ohm/mile
AC Nominal Resistance at 75ºC 0.0638 ohm/km 0.1027 ohm/mile
AC Nominal Resistance at 180ºC 0.0852 ohm/km 0.1370 ohm/mile
1165 @ 100C & 50 Hz
1758 @ 180C & 50 Hz
GMR (estimated) 0.012 m 0.039 ft
Inductive Reactance 0.204 ohm/km 0.394 ohm/mile
Capacitive Reactance 0.174 Mohm-km 0.090 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-141-E ACCC-TW ULS 545 (1075 kcmil) Mahakam Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 560.9 sq. mm (1107 kcmil)
ACCC®-ULS Mahakam
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 546.4 mm2 1078.3 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-008) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in
2
Overall Diameter of Conductor 28.62 mm 1.127 in.
Nominal Cross-sectional Area of the Conductor 606.7 mm2 0.940 in
2
Ultimate Tensile Strength of Conductor1,2 186.6 kN 41.9 kips
Rated Strength of Core - 375 ksi (2586 MPa) 155.9 kN 35.1 kips
Core Nominal Mass per unit length 109 kg/km 73 lb/kft
Conductor Nominal Mass per unit length 1622.8 kg/km 1090.7 lb/kft
Aluminum Nominal Mass per unit length** 1513.8 kg/km 1017.4 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.82E-05 /oC 1.01E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 66.8 GPa 9.7 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0514 ohm/km 0.0827 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0534 ohm/km 0.0866 ohm/mile
AC Nominal Resistance at 75ºC 0.0636 ohm/km 0.1030 ohm/mile
AC Nominal Resistance at 180ºC 0.0850 ohm/km 0.1372 ohm/mile
1163 @ 100C & 50 Hz
1752 @ 180C & 50 Hz
GMR (estimated) 0.012 m 0.038 ft
Inductive Reactance 0.206 ohm/km 0.397 ohm/mile
Capacitive Reactance 0.175 Mohm-km 0.091 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-158-E ACCC-TW ULS 546 (1078 kcmil) Hamburg Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 562.5 sq. mm (1110 kcmil)
ACCC®-ULS Hamburg
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 567.7 mm2 1120.3 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-008) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in
2
Overall Diameter of Conductor 29.10 mm 1.146 in.
Nominal Cross-sectional Area of the Conductor 628.0 mm2 0.973 in
2
Ultimate Tensile Strength of Conductor1,2 187.8 kN 42.2 kips
Rated Strength of Core - 375 ksi (2586 MPa) 155.9 kN 35.1 kips
Core Nominal Mass per unit length 109 kg/km 73 lb/kft
Conductor Nominal Mass per unit length 1681.6 kg/km 1130.2 lb/kft
Aluminum Nominal Mass per unit length** 1572.6 kg/km 1056.9 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.83E-05 /oC 1.02E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 66.5 GPa 9.6 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0494 ohm/km 0.0795 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0514 ohm/km 0.0835 ohm/mile
AC Nominal Resistance at 75ºC 0.0612 ohm/km 0.0991 ohm/mile
AC Nominal Resistance at 180ºC 0.0818 ohm/km 0.1320 ohm/mile
1191 @ 100C & 50 Hz
1797 @ 180C & 50 Hz
GMR (estimated) 0.012 m 0.039 ft
Inductive Reactance 0.205 ohm/km 0.395 ohm/mile
Capacitive Reactance 0.174 Mohm-km 0.090 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-159-E ACCC-TW ULS 568 (1120 kcmil) Milan Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 584.4 sq. mm (1153.3 kcmil)
ACCC®-ULS Milan
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 592.5 mm2 1169.3 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-007) 9.53 mm 0.375 in.
Nominal Cross-sectional Area of Core 71.3 mm2 0.111 in
2
Overall Diameter of Conductor 29.89 mm 1.177 in.
Nominal Cross-sectional Area of the Conductor 663.8 mm2 1.029 in
2
Ultimate Tensile Strength of Conductor1,2 217.5 kN 48.9 kips
Rated Strength of Core - 375 ksi (2586 MPa) 184.2 kN 41.4 kips
Core Nominal Mass per unit length 128 kg/km 86 lb/kft
Conductor Nominal Mass per unit length 1769.9 kg/km 1189.5 lb/kft
Aluminum Nominal Mass per unit length** 1641.9 kg/km 1103.5 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.78E-05 /oC 9.91E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 67.5 GPa 9.8 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0474 ohm/km 0.0763 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0494 ohm/km 0.0802 ohm/mile
AC Nominal Resistance at 75ºC 0.0588 ohm/km 0.0952 ohm/mile
AC Nominal Resistance at 180ºC 0.0785 ohm/km 0.1267 ohm/mile
1225 @ 100C & 50 Hz
1850 @ 180C & 50 Hz
GMR (estimated) 0.012 m 0.040 ft
Inductive Reactance 0.203 ohm/km 0.391 ohm/mile
Capacitive Reactance 0.173 Mohm-km 0.089 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-160-E ACCC-TW ULS 593 (1169 kcmil) Rome Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 609.9 sq. mm (1203.7 kcmil)
ACCC®-ULS Rome
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 629.2 mm2 1241.7 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-008) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in
2
Overall Diameter of Conductor 30.42 mm 1.198 in.
Nominal Cross-sectional Area of the Conductor 689.5 mm2 1.069 in
2
Ultimate Tensile Strength of Conductor1,2 191.3 kN 43.0 kips
Rated Strength of Core - 375 ksi (2586 MPa) 155.9 kN 35.1 kips
Core Nominal Mass per unit length 109 kg/km 73 lb/kft
Conductor Nominal Mass per unit length 1848.2 kg/km 1242.2 lb/kft
Aluminum Nominal Mass per unit length** 1739.2 kg/km 1168.9 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.87E-05 /oC 1.04E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 65.8 GPa 9.5 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0445 ohm/km 0.0716 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0466 ohm/km 0.0758 ohm/mile
AC Nominal Resistance at 75ºC 0.0554 ohm/km 0.0898 ohm/mile
AC Nominal Resistance at 180ºC 0.0738 ohm/km 0.1192 ohm/mile
1269 @ 100C & 50 Hz
1918 @ 180C & 50 Hz
GMR (estimated) 0.012 m 0.040 ft
Inductive Reactance 0.202 ohm/km 0.390 ohm/mile
Capacitive Reactance 0.172 Mohm-km 0.089 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-161-E ACCC-TW ULS 629 (1242 kcmil) Vienna Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 647.7 sq. mm (1278.2 kcmil)
ACCC®-ULS Vienna
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 668.3 mm2 1318.9 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-007) 9.53 mm 0.375 in.
Nominal Cross-sectional Area of Core 71.3 mm2 0.111 in
2
Overall Diameter of Conductor 31.50 mm 1.240 in.
Nominal Cross-sectional Area of the Conductor 739.6 mm2 1.146 in
2
Ultimate Tensile Strength of Conductor1,2 221.8 kN 49.9 kips
Rated Strength of Core - 375 ksi (2586 MPa) 184.2 kN 41.4 kips
Core Nominal Mass per unit length 128 kg/km 86 lb/kft
Conductor Nominal Mass per unit length 1979.5 kg/km 1330.4 lb/kft
Aluminum Nominal Mass per unit length** 1851.5 kg/km 1244.4 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.83E-05 /oC 1.02E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 66.6 GPa 9.7 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0420 ohm/km 0.0676 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0440 ohm/km 0.0717 ohm/mile
AC Nominal Resistance at 75ºC 0.0523 ohm/km 0.0849 ohm/mile
AC Nominal Resistance at 180ºC 0.0697 ohm/km 0.1126 ohm/mile
1318 @ 100C & 50 Hz
1996 @ 180C & 50 Hz
GMR (estimated) 0.013 m 0.042 ft
Inductive Reactance 0.200 ohm/km 0.385 ohm/mile
Capacitive Reactance 0.170 Mohm-km 0.088 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-162-E ACCC-TW ULS 668 (1319 kcmil) Budapest Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 688 sq. mm (1357.7 kcmil)
ACCC®-ULS Budapest
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 685.4 mm2 1352.6 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-007) 9.53 mm 0.375 in.
Nominal Cross-sectional Area of Core 71.3 mm2 0.111 in
2
Overall Diameter of Conductor 31.77 mm 1.251 in.
Nominal Cross-sectional Area of the Conductor 756.7 mm2 1.173 in
2
Ultimate Tensile Strength of Conductor1,2 222.8 kN 50.1 kips
Rated Strength of Core - 375 ksi (2586 MPa) 184.2 kN 41.4 kips
Core Nominal Mass per unit length 128 kg/km 86 lb/kft
Conductor Nominal Mass per unit length 2030.6 kg/km 1364.7 lb/kft
Aluminum Nominal Mass per unit length** 1902.6 kg/km 1278.7 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.84E-05 /oC 1.02E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 66.4 GPa 9.6 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0410 ohm/km 0.0660 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0431 ohm/km 0.0701 ohm/mile
AC Nominal Resistance at 75ºC 0.0511 ohm/km 0.0830 ohm/mile
AC Nominal Resistance at 180ºC 0.0681 ohm/km 0.1101 ohm/mile
1336 @ 100C & 50 Hz
2025 @ 180C & 50 Hz
GMR (estimated) 0.013 m 0.042 ft
Inductive Reactance 0.199 ohm/km 0.384 ohm/mile
Capacitive Reactance 0.169 Mohm-km 0.088 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-163-E ACCC-TW ULS 685 (1353 kcmil) Mumbai Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 705.6 sq. mm (1392.4 kcmil)
ACCC®-ULS Mumbai
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 690.7 mm2 1363.1 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-008) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in
2
Overall Diameter of Conductor 31.77 mm 1.251 in.
Nominal Cross-sectional Area of the Conductor 751.0 mm2 1.164 in
2
Ultimate Tensile Strength of Conductor1,2 194.8 kN 43.8 kips
Rated Strength of Core - 375 ksi (2586 MPa) 155.9 kN 35.1 kips
Core Nominal Mass per unit length 109 kg/km 73 lb/kft
Conductor Nominal Mass per unit length 2026.2 kg/km 1361.8 lb/kft
Aluminum Nominal Mass per unit length** 1917.2 kg/km 1288.5 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.90E-05 /oC 1.06E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 65.1 GPa 9.4 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0407 ohm/km 0.0655 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0428 ohm/km 0.0699 ohm/mile
AC Nominal Resistance at 75ºC 0.0508 ohm/km 0.0826 ohm/mile
AC Nominal Resistance at 180ºC 0.0676 ohm/km 0.1093 ohm/mile
1340 @ 100C & 50 Hz
2032 @ 180C & 50 Hz
GMR (estimated) 0.013 m 0.042 ft
Inductive Reactance 0.199 ohm/km 0.385 ohm/mile
Capacitive Reactance 0.169 Mohm-km 0.088 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-143-E ACCC-TW ULS 691 (1363 kcmil) Prague Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 711 sq. mm (1403.2 kcmil)
ACCC®-ULS Prague
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 733.2 mm2 1446.9 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-007) 9.53 mm 0.375 in.
Nominal Cross-sectional Area of Core 71.3 mm2 0.111 in
2
Overall Diameter of Conductor 32.85 mm 1.293 in.
Nominal Cross-sectional Area of the Conductor 804.5 mm2 1.247 in
2
Ultimate Tensile Strength of Conductor1,2 225.4 kN 50.7 kips
Rated Strength of Core - 375 ksi (2586 MPa) 184.2 kN 41.4 kips
Core Nominal Mass per unit length 128 kg/km 86 lb/kft
Conductor Nominal Mass per unit length 2165.9 kg/km 1455.6 lb/kft
Aluminum Nominal Mass per unit length** 2037.9 kg/km 1369.6 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.86E-05 /oC 1.04E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 65.9 GPa 9.6 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0384 ohm/km 0.0618 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0405 ohm/km 0.0661 ohm/mile
AC Nominal Resistance at 75ºC 0.0480 ohm/km 0.0781 ohm/mile
AC Nominal Resistance at 180ºC 0.0638 ohm/km 0.1032 ohm/mile
1392 @ 100C & 50 Hz
2113 @ 180C & 50 Hz
GMR (estimated) 0.013 m 0.043 ft
Inductive Reactance 0.197 ohm/km 0.381 ohm/mile
Capacitive Reactance 0.167 Mohm-km 0.087 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-144-E ACCC-TW ULS 733 (1447 kcmil) Munich Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 754.8 sq. mm (1489.5 kcmil)
ACCC®-ULS Munich
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 749.5 mm2 1479.1 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-011) 10.54 mm 0.415 in.
Nominal Cross-sectional Area of Core 87.3 mm2 0.135 in
2
Overall Diameter of Conductor 33.40 mm 1.315 in.
Nominal Cross-sectional Area of the Conductor 836.8 mm2 1.297 in
2
Ultimate Tensile Strength of Conductor1,2 267.8 kN 60.2 kips
Rated Strength of Core - 375 ksi (2586 MPa) 225.6 kN 50.7 kips
Core Nominal Mass per unit length 157 kg/km 106 lb/kft
Conductor Nominal Mass per unit length 2235.6 kg/km 1502.5 lb/kft
Aluminum Nominal Mass per unit length** 2078.6 kg/km 1397.0 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.80E-05 /oC 9.98E-06 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 67.3 GPa 9.8 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0375 ohm/km 0.0604 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0395 ohm/km 0.0645 ohm/mile
AC Nominal Resistance at 75ºC 0.0469 ohm/km 0.0762 ohm/mile
AC Nominal Resistance at 180ºC 0.0624 ohm/km 0.1008 ohm/mile
1415 @ 100C & 50 Hz
2148 @ 180C & 50 Hz
GMR (estimated) 0.014 m 0.044 ft
Inductive Reactance 0.196 ohm/km 0.378 ohm/mile
Capacitive Reactance 0.166 Mohm-km 0.086 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-165-E ACCC-TW ULS 750 (1479 kcmil) Warwick Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 771.5 sq. mm (1522.6 kcmil)
ACCC®-ULS Warwick
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 759.0 mm2 1497.9 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-009) 9.78 mm 0.385 in.
Nominal Cross-sectional Area of Core 75.1 mm2 0.116 in
2
Overall Diameter of Conductor 33.40 mm 1.315 in.
Nominal Cross-sectional Area of the Conductor 834.1 mm2 1.293 in
2
Ultimate Tensile Strength of Conductor1,2 236.9 kN 53.3 kips
Rated Strength of Core - 375 ksi (2586 MPa) 194.2 kN 43.7 kips
Core Nominal Mass per unit length 135 kg/km 91 lb/kft
Conductor Nominal Mass per unit length 2239.9 kg/km 1505.4 lb/kft
Aluminum Nominal Mass per unit length** 2104.9 kg/km 1414.7 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.86E-05 /oC 1.03E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.1 GPa 21.2 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 65.9 GPa 9.6 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0370 ohm/km 0.0595 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0391 ohm/km 0.0639 ohm/mile
AC Nominal Resistance at 75ºC 0.0464 ohm/km 0.0754 ohm/mile
AC Nominal Resistance at 180ºC 0.0616 ohm/km 0.0996 ohm/mile
1424 @ 100C & 50 Hz
2164 @ 180C & 50 Hz
GMR (estimated) 0.013 m 0.044 ft
Inductive Reactance 0.196 ohm/km 0.379 ohm/mile
Capacitive Reactance 0.166 Mohm-km 0.086 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-164-E ACCC-TW ULS 759 (1498 kcmil) London Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 781.3 sq. mm (1541.9 kcmil)
ACCC®-ULS London
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 813.7 mm2 1605.8 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-008) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in
2
Overall Diameter of Conductor 34.16 mm 1.345 in.
Nominal Cross-sectional Area of the Conductor 874.0 mm2 1.355 in
2
Ultimate Tensile Strength of Conductor1,2 201.7 kN 45.3 kips
Rated Strength of Core - 375 ksi (2586 MPa) 155.9 kN 35.1 kips
Core Nominal Mass per unit length 109 kg/km 73 lb/kft
Conductor Nominal Mass per unit length 2361.8 kg/km 1587.3 lb/kft
Aluminum Nominal Mass per unit length** 2252.8 kg/km 1514.1 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.95E-05 /oC 1.08E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 64.1 GPa 9.3 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0345 ohm/km 0.0555 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0368 ohm/km 0.0604 ohm/mile
AC Nominal Resistance at 75ºC 0.0435 ohm/km 0.0710 ohm/mile
AC Nominal Resistance at 180ºC 0.0576 ohm/km 0.0933 ohm/mile
1480 @ 100C & 50 Hz
2254 @ 180C & 50 Hz
GMR (estimated) 0.014 m 0.045 ft
Inductive Reactance 0.195 ohm/km 0.377 ohm/mile
Capacitive Reactance 0.165 Mohm-km 0.085 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-166-E ACCC-TW ULS 814 (1606 kcmil) Paris Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 837.6 sq. mm (1653 kcmil)
ACCC®-ULS Paris
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 880.9 mm2 1738.4 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-011) 10.54 mm 0.415 in.
Nominal Cross-sectional Area of Core 87.3 mm2 0.135 in
2
Overall Diameter of Conductor 35.76 mm 1.408 in.
Nominal Cross-sectional Area of the Conductor 968.2 mm2 1.501 in
2
Ultimate Tensile Strength of Conductor1,2 275.2 kN 61.9 kips
Rated Strength of Core - 375 ksi (2586 MPa) 225.6 kN 50.7 kips
Core Nominal Mass per unit length 157 kg/km 106 lb/kft
Conductor Nominal Mass per unit length 2595.0 kg/km 1744.0 lb/kft
Aluminum Nominal Mass per unit length** 2438.0 kg/km 1638.5 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.86E-05 /oC 1.03E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 66.0 GPa 9.6 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0318 ohm/km 0.0512 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0340 ohm/km 0.0559 ohm/mile
AC Nominal Resistance at 75ºC 0.0402 ohm/km 0.0656 ohm/mile
AC Nominal Resistance at 180ºC 0.0532 ohm/km 0.0861 ohm/mile
1560 @ 100C & 50 Hz
2379 @ 180C & 50 Hz
GMR (estimated) 0.014 m 0.047 ft
Inductive Reactance 0.192 ohm/km 0.370 ohm/mile
Capacitive Reactance 0.162 Mohm-km 0.084 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-170-E ACCC-TW ULS 881 (1738 kcmil) Bordeaux Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 906.8 sq. mm (1789.6 kcmil)
ACCC®-ULS Bordeaux
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 944.9 mm2 1864.7 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-009) 9.78 mm 0.385 in.
Nominal Cross-sectional Area of Core 75.1 mm2 0.116 in
2
Overall Diameter of Conductor 36.85 mm 1.451 in.
Nominal Cross-sectional Area of the Conductor 1020.0 mm2 1.581 in
2
Ultimate Tensile Strength of Conductor1,2 247.4 kN 55.6 kips
Rated Strength of Core - 375 ksi (2586 MPa) 194.2 kN 43.7 kips
Core Nominal Mass per unit length 135 kg/km 91 lb/kft
Conductor Nominal Mass per unit length 2751.5 kg/km 1849.2 lb/kft
Aluminum Nominal Mass per unit length** 2616.5 kg/km 1758.5 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.93E-05 /oC 1.07E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.0 GPa 21.2 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 64.5 GPa 9.4 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0297 ohm/km 0.0478 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0321 ohm/km 0.0529 ohm/mile
AC Nominal Resistance at 75ºC 0.0378 ohm/km 0.0619 ohm/mile
AC Nominal Resistance at 180ºC 0.0498 ohm/km 0.0808 ohm/mile
1623 @ 100C & 50 Hz
2483 @ 180C & 50 Hz
GMR (estimated) 0.015 m 0.048 ft
Inductive Reactance 0.190 ohm/km 0.367 ohm/mile
Capacitive Reactance 0.161 Mohm-km 0.083 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-142-E ACCC-TW ULS 945 (1865 kcmil) Antwerp Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 972.7 sq. mm (1919.6 kcmil)
ACCC®-ULS Antwerp
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 1006.5 mm2 1986.3 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-011) 10.54 mm 0.415 in.
Nominal Cross-sectional Area of Core 87.3 mm2 0.135 in
2
Overall Diameter of Conductor 38.20 mm 1.504 in.
Nominal Cross-sectional Area of the Conductor 1093.8 mm2 1.695 in
2
Ultimate Tensile Strength of Conductor1,2 282.2 kN 63.4 kips
Rated Strength of Core - 375 ksi (2586 MPa) 225.6 kN 50.7 kips
Core Nominal Mass per unit length 157 kg/km 106 lb/kft
Conductor Nominal Mass per unit length 2941.9 kg/km 1977.2 lb/kft
Aluminum Nominal Mass per unit length** 2784.9 kg/km 1871.7 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.90E-05 /oC 1.06E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.7 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 65.1 GPa 9.4 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0278 ohm/km 0.0447 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0303 ohm/km 0.0499 ohm/mile
AC Nominal Resistance at 75ºC 0.0356 ohm/km 0.0583 ohm/mile
AC Nominal Resistance at 180ºC 0.0467 ohm/km 0.0759 ohm/mile
1692 @ 100C & 50 Hz
2594 @ 180C & 50 Hz
GMR (estimated) 0.015 m 0.050 ft
Inductive Reactance 0.188 ohm/km 0.363 ohm/mile
Capacitive Reactance 0.159 Mohm-km 0.082 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-167-E ACCC-TW ULS 1007 (1986 kcmil) Berlin Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1036.1 sq. mm (2044.7 kcmil)
ACCC®-ULS Berlin
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 1013.1 mm2 1999.3 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-009) 9.78 mm 0.385 in.
Nominal Cross-sectional Area of Core 75.1 mm2 0.116 in
2
Overall Diameter of Conductor 38.20 mm 1.504 in.
Nominal Cross-sectional Area of the Conductor 1088.2 mm2 1.687 in
2
Ultimate Tensile Strength of Conductor1,2 251.2 kN 56.5 kips
Rated Strength of Core - 375 ksi (2586 MPa) 194.2 kN 43.7 kips
Core Nominal Mass per unit length 135 kg/km 91 lb/kft
Conductor Nominal Mass per unit length 2939.3 kg/km 1975.5 lb/kft
Aluminum Nominal Mass per unit length** 2804.3 kg/km 1884.7 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.95E-05 /oC 1.09E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.1 GPa 21.2 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 64.1 GPa 9.3 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0276 ohm/km 0.0444 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0302 ohm/km 0.0498 ohm/mile
AC Nominal Resistance at 75ºC 0.0354 ohm/km 0.0581 ohm/mile
AC Nominal Resistance at 180ºC 0.0464 ohm/km 0.0755 ohm/mile
1696 @ 100C & 50 Hz
2602 @ 180C & 50 Hz
GMR (estimated) 0.015 m 0.050 ft
Inductive Reactance 0.188 ohm/km 0.363 ohm/mile
Capacitive Reactance 0.159 Mohm-km 0.082 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-168-E ACCC-TW ULS 1013 (1999 kcmil) Madrid Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1042.9 sq. mm (2058.1 kcmil)
ACCC®-ULS Madrid
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial
DATA SHEET:
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area* 1409.7 mm2 2782.0 kcmil
Nominal Diameter of Composite Core (CTC Part Number 210-011) 10.54 mm 0.415 in.
Nominal Cross-sectional Area of Core 87.3 mm2 0.135 in
2
Overall Diameter of Conductor 44.75 mm 1.762 in.
Nominal Cross-sectional Area of the Conductor 1497.0 mm2 2.320 in
2
Ultimate Tensile Strength of Conductor1,2 304.9 kN 68.5 kips
Rated Strength of Core - 375 ksi (2586 MPa) 225.6 kN 50.7 kips
Core Nominal Mass per unit length 157 kg/km 106 lb/kft
Conductor Nominal Mass per unit length 4058.4 kg/km 2727.6 lb/kft
Aluminum Nominal Mass per unit length** 3901.4 kg/km 2622.1 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 o
C 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /
oF
Coefficient of Linear Expansion Below Thermal Kneepoint 2.00E-05 /oC 1.11E-05 /
oF
Final Modulus of Elasticity Above Thermal Kneepoint 146.8 GPa 21.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 63.2 GPa 9.2 Msi
Electrical Specifications
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0199 ohm/km 0.0320 ohm/mile
Temperature Coefficient of Resistance 0.00403 0.00403
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0231 ohm/km 0.0388 ohm/mile
AC Nominal Resistance at 75ºC 0.0267 ohm/km 0.0402 ohm/mile
AC Nominal Resistance at 180ºC 0.0343 ohm/km 0.0432 ohm/mile
2050 @ 100C & 50 Hz
3189 @ 180C & 50 Hz
GMR (estimated) 0.018 m 0.058 ft
Inductive Reactance 0.178 ohm/km 0.345 ohm/mile
Capacitive Reactance 0.150 Mohm-km 0.077 Mohm-mile
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
F-730-169-E ACCC-TW ULS 1410 (2782 kcmil) Athens Data Sheet www.ctcglobal.com Date Produced: 7/10/2015
Metric Imperial
AC Current Rating at Given Temperature3
The information contained herein is offered in good faith. The ACCC® manufacturer’s specification may have some variation from the indicated values in this spec
sheet, with the weight and cross sectional area being no more than ±2% of the value indicated.
**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
*ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1451.2 sq. mm (2863.8 kcmil)
ACCC®-ULS Athens
NOT RELEASED
For questions, please contact CTC Application Engineering Department: [email protected]
Metric Imperial