acoustic product catalogue...arma-chek r barrier non-metallic cladding with barrier performance...

48
PRODUCT CATALOGUE ACOUSTIC For more information on Armacell visit www.barbourproductsearch.info

Upload: others

Post on 21-Jan-2021

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

PRODUCT CaTalOgUe aCOUSTIC

For more information on Armacell visit www.barbourproductsearch.info

Page 2: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Professional Acoustic Systems from Armacell

Class O Armaflex Sheets & Rolls Sound Absorption with Closed Cell Protection

Class O Armaflex Tubes De-Coupling for pipework with closed cell protection

Armaflex Punched Sheets Dust and Fibre Free Sound Absorption with a Class O Fire Rating

ArmaSound RD High Performance Sound Absorption for a Quieter Environment

ArmaSound Floor High Performance Noise Reduction for a Quieter Environment

ArmaSound Industrial Systems Acoustic Pipe Insulation Which Minimise Corrosion Under Insulation

ArmaSound Barriers High Performance Barrier for a Quieter Environment

Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance

Armaflex R Reducing Break-Out Noise with Closed Cell Protection

Armaload Acoustic De-coupling for Duct and Pipe supports

Tubolit Fonoblok Acoustic De-coupling for Waste Water Pipes

Select the right Acoustic Solution for your application ...

Industry Application

Air-borne Structure-borne

Sound

Absorption

Sound

Barrier

DeCoupling

(Isolation)

Vibration

Damping

Building and Construction

Walls and Partitions

Ceilings

Flooring

Building Services

Water supply and wastewater / drainage

HVAC - Ducting

HVAC – Compressors / heat exchangers

Industrial, Petro-chemical and LNG

Control & plant rooms,Engine compartments

Compressor pump housing / Control valve boxes

Pipe lagging

Heavy Industry

Machine enclosures and screens

Plant room

OEM (Generators, Compressors etc.)

Enclosures

For more information on Armacell visit www.barbourproductsearch.info

Page 3: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Sound Absorption with Closed Cell Protection Class O Armaflex SHEET

New! Built-In Anti-Microbial Protection Reduces Mould and Bacteria Growth

Dustandfibrefreeinsulationwiththermalandacousticproperties

Impressiveairbornenoiseabsorptionatproblemfrequencies

Sound Absorption with Closed Cell Protection

SHEET & RollS

S o u n d Ab

so

rp

tio

n

S o u n d De

- Co

up

lin

g

For more information on Armacell visit www.barbourproductsearch.info

Page 4: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Sound Absorption with Closed Cell ProtectionClass O Armaflex SHEET

Class O Armaflex Sheet & RollsSound Absorption with Closed Cell Protection

ArmaflexisaflexibleclosedcellelastomericsheetwithaClassOfirerat-ingandenergysavingthermalperformance.Beingaclosedcellmaterial,Armaflexrequiresnoexternalvapourbarrierandwillnotabsorbmoistureby“wicking”.

Armaflexhastheuniquecapabilityofprovidingsignificantsoundabsorptionwhileremainingcompletelyclosedcell.AerodynamicandfannoisewithintheductingcanbereducedwhenArmaflexisusedasaninternallining.Duetoitsexcellentthermalvalues,Armaflexalsoperformsasathermalinsula-torwhichnegatestheneedforadditionalthermalinsulationontheexterioroftheductwork.

WhenArmaflexisusedasanexternalacousticlining,noisebreak-outfromtheductwallcanbesignificantlyreduced.

ClassOArmaflexnowalsocomeswithMicrobananti-microbialprotectionbuilt-in,offeringenhanced resistanceagainstbacteriaandmouldgrowth.ThismakesClassOArmaflexsuitableforuseinoffices,schoolsandhos-pitals.

Armaflexisdust,fibreandformaldehydefree,andinhibitstheonsetof“sickbuildingsyndrome”.

NewBuilt-inanti-microbialprotectionreducesmouldandbacteriagrowth

Dustandfibrefreeinsulationwiththermalandacousticproperties

Impressiveairbornenoiseabsorptionatproblemfrequencies

MeetsrecommendedPartLenergyperformancewheninternallylining ductwork*

Excellentde-couplingandisolationperformanceonpipesandductsin contactwithotherstructuralandserviceelements

Suitableforuseinareasofhighhumidityandareaswithpossibleoiland chemicalcontact

*Appliestowarmductworkonlyat32mmthickness.Assumesahighemissivityductworkfinish.

Plant Room

Lining Ductwork Internally

Insulating Ductwork Externally

Allstatementsand technical informationarebasedon resultsobtainedundertypical conditions. It is the responsibility of the recipient to verifywithus thattheinformationisappropriateforthespecificuseintendedbytherecipient.Forupdatestothisdocumentpleaserefertoourwebsitewww.armacell.com/uk.4 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

For more information on Armacell visit www.barbourproductsearch.info

Page 5: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Sound Absorption with Closed Cell Protection Class O Armaflex SHEET

ACoUSTIC PERFoRMANCE

Insertion Loss, dBacc.toENISO15665

Octavebandcentrefrequency,Hz

125 250 500 1000 2000 4000

10mmsheet 0.02 0.04 0.08 0.19 0.53 0.4432mmsheet 0.08 0.17 0.51 0.56 0.25 0.24

Testacc.toENISO11654 10mm 32mm

WeightedSoundAbsorptionCoefficientαw 0.02(H) 0.35

SoundAbsorptionClass E D

acc.toASTMC423 10mm 32mm

NRCRating 0.2 0.35

PRoDUCT PRoFIlE

Values RemarksMaterial Foamednitrilerubber

Max. Surface Temperature +105°C*Fortemperaturesbetween-50°Cand-200°C,pleaseconsultourTechnicalDepartment. Tel.+44(0)1612877038·Fax+44(0)1616332685

Max. Temperature for Flat Surface +85°C

Min. Surface Temperature -200°C*

Thermal Conductivity at 0°C 0.034W/(m·K)

Testacc.toENISO8497Thermal Conductivity at +20°C 0.036W/(m·K)

Thermal Conductivity at +40°C 0.038W/(m·K)

Water Vapour PermeabilityMoistureResistanceFactorµ 7,000BSENISO9346:1996 2.79·10(-14)kg/(msPa)

Water Absorption 0.2%byvolume Testacc.ASTMC209

Surface Spread of Flames Class1 SurfaceSpreadofFlameacc.BS476Part7:1997FirePropagationacc.BS476Part6:1989

TestresultsforSurface Spread of Flames and Fire Propagation meets• BuildingRegulations2000(EnglandandWales)• BuildingStandards(Scotland)Regulations1990• BuildingRegulations2000(NorthernIreland)• BuildingRegulations1997(RepublicofIreland)fortheClassOfirecategory

TestedinaccordancewithUL94

Fire Propagation TotalIndexPerformance(I) ≤12SubIndex(i1) ≤6

Fire Performance acc. to Building Regulation Class O

Reaction to fire Self-extinguishing,doesnotdrip

Noise Reduction SoundAbsorptionCoefficientISO354:2003 upto0.8 Alsosuitableforuseinthepreventionofsoundpas-sage

Resistance toBuilding Materials Very GoodChemicals ConsultProductTestListOzone VeryGood

Environmental Aspects ODP zero, GWP zero

Health AspectsDust & Fibre FreeMicroban anti-microbial protection

Outdoor applications: ClassOArmaflexshouldbepaintedwithArmafinishFRpainttotherecommendedthicknesswithin3days.Twoormorecoatsmayberequired.

©ArmacellUKLtd.·Subjecttoalterations 2009 (AC) 5

For more information on Armacell visit www.barbourproductsearch.info

Page 6: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Sound Absorption with Closed Cell ProtectionClass O Armaflex SHEET

ClASS o ARMAFlEX Flat SheetColourblack,skinonbothsides

Standard Sheet (skinonbothsides)

Sheet with Self-Adhesive Backing

Insulation Thickness

mmWidth m

Length m Reference

Carton Content

m2 Reference

Carton Content

m2

9 0.5 2 CO-09MM 13 CO-09MM/A 13

13 0.5 2 CO-13MM 9 CO-13MM/A 9

19 0.5 2 CO-19MM 7 CO-19MM/A 7

25 0.5 2 CO-25MM 5 CO-25MM/A 5

32 0.5 2 CO-32MM 4 CO-32MM/A 4

ClASS o ARMAFlEX Continuous SheetColourblack,skinonbothsides

Continuous Sheet(skinonbothsides)

Continuous Sheet with Self-Adhesive Backing

Insulation Thickness

mmWidth m

Length m Reference

Carton Content

m2 Reference

Carton Content

m2

3 1 30 AC-03-99/E 30

6 1 15 AC-06-99/E 15 AC-06-99/EA 15

9 1 10 CO-09MM/E 10 CO-09MM/EA 10

13 1 8 CO-13MM/E 8 CO-13MM/EA 8

19 1 6 CO-19MM/E 6 CO-19MM/EA 6

25 1 4 CO-25MM/E 4 CO-25MM/EA 4

32 1 3 CO-32MM/E 3 CO-32MM/EA 3

ClASS o ARMAFlEX DUCTlINER Flat SheetFoilcoveredClassOArmaflexsheet,Colour:silver

Standard Sheet (skinonbothsides)

Sheet with Self-Adhesive Backing

Insulation Thickness

mmWidth m

Length m Reference

Carton Content

m2 Reference

Carton Content

m2

9 0.5 2 CO-09-99/AL 13 CO-09-99/AL-A 13

13 0.5 2 CO-13-99/AL 9 CO-13-99/AL-A 9

19 0.5 2 CO-19-99/AL 7 CO-19-99/AL-A 7

25 0.5 2 CO-25-99/AL 5 CO-25-99/AL-A 5

32 0.5 2 CO-32-99/AL 4 CO-32-99/AL-A 4

6 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

For more information on Armacell visit www.barbourproductsearch.info

Page 7: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

De-Coupling for Pipework with Closed Cell Protection Class O Armaflex TUBE

New! Built-In Anti-Microbial Protection Reduces Mould and Bacteria Growth

Dustandfibrefreeinsulationwiththermalandacousticproperties

Excellentde-couplingandisolationperformance

Builtinwatervapourbarrierpreventscondensation

De-Coupling for Pipework with Closed Cell Protection

Class O Armaflex TUBE

S o u n d De

- Co

up

lin

g

For more information on Armacell visit www.barbourproductsearch.info

Page 8: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

De-Coupling for Pipework with Closed Cell ProtectionClass O Armaflex TUBE

Class O Armaflex TubesDe-Coupling For Pipework With Closed Cell Protection

ArmaflexisaflexibleclosedcellelastomerictubewithaClassOfirerat-ingandenergysavingthermalperformance.Beingaclosedcellmaterial,Armaflexrequiresnoexternalvapourbarrierandwillnotabsorbmoistureby“wicking”.

Insulating theentirepipeworksystemprior tofixingensureseffectivede-couplingfromsupportingandstructuralelementsaswellasotherserviceinstallations.Thispreventsacousticbridging,oftenresponsibleforthema-jorityofpipeworknoiseheardwithinthebuilding.

At thesame timeArmaflexperformsashighlyefficient thermal insulationandpreventscondensationoncoldlines.ClassOArmaflexnowalsocomeswithMicroban anti-microbial protection built-in, offering enhanced resist-ance against bacteria andmould growth. Thismakes ClassOArmaflexsuitableforuseinoffices,schoolsandhospitals.

AllArmaflexisdust,fibreandformaldehydefree,minimisinganyimpacton“sickbuildingsyndrome”.

NewBuilt-inanti-microbialprotectionreducesmouldandbacteriagrowth

Dustandfibrefreeinsulationwiththermalandacousticproperties

Excellentde-couplingandisolationperformance

Builtinwatervapourbarrierpreventscondensation

Suitableforuseinareasofhighhumidityandareaswithpossibleoiland chemicalcontact

PreventsThermalandAcousticBridging

ACOUSTIC PERFORMANCE

acc.toENISO3822-1* dB (A)

DLAF,10 dB (A) 28.2*testedwithtube13mmx35mm

Insertion Loss, dBacc.toENISO15665(1)

Octavebandcentrefrequency,Hz

125 250 500 1000 2000 4000

10mmsheet 0.02 0.04 0.08 0.19 0.53 0.4432mmsheet 0.08 0.17 0.51 0.56 0.25 0.24

Testacc.toENISO11654(1) 10mm 32mm

WeightedSoundAbsorptionCoefficientαw 0.02(H) 0.35

SoundAbsorptionClass E D

acc.toASTMC423(1) 10mm 32mm

NRCRating 0.2 0.35(1) testedwithsheetmaterial

De-Coupling Pipework

Allstatementsand technical informationarebasedon resultsobtainedundertypical conditions. It is the responsibility of the recipient to verifywithus thattheinformationisappropriateforthespecificuseintendedbytherecipient.Forupdatestothisdocumentpleaserefertoourwebsitewww.armacell.com/uk.8 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

For more information on Armacell visit www.barbourproductsearch.info

Page 9: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

De-Coupling for Pipework with Closed Cell Protection Class O Armaflex TUBE

©ArmacellUKLtd.·Subjecttoalterations 2009 (AC) 9

PROdUCT PROFIlE

Values RemarksMaterial Foamednitrilerubber

Max. Surface Temperature +105°C*Fortemperaturesbetween-50°Cand-200°C,pleaseconsultourTechnicalDepartment. Tel.+44(0)1612877038·Fax+44(0)1616332685

Max. Temperature for Flat Surface +85°C

Min. Surface Temperature -200°C*

Thermal Conductivity at 0°C 0.034W/(m·K)

Testacc.toENISO8497Thermal Conductivity at +20°C 0.036W/(m·K)

Thermal Conductivity at +40°C 0.038W/(m·K)

Water Vapour PermeabilityMoisture Resistance Factor µ 7,000BSENISO9346:1996 2.79·10(-14)kg/(msPa)

Water Absorption 0.2%byvolume Testacc.ASTMC209

Surface Spread of Flames Class1 SurfaceSpreadofFlameacc.BS476Part7:1997FirePropagationacc.BS476Part6:1989

TestresultsforSurface Spread of Flames and Fire Propagation meets• BuildingRegulations2000(EnglandandWales)• BuildingStandards(Scotland)Regulations1990• BuildingRegulations2000(NorthernIreland)• BuildingRegulations1997(RepublicofIreland)fortheClassOfirecategory

TestedinaccordancewithUL94

Fire Propagation TotalIndexPerformance(I) ≤12Sub Index (i1) ≤6

Fire Performance acc. to Building Regulation Class O

Reaction to fire Self-extinguishing,doesnotdrip

Noise Reduction SoundAbsorptionCoefficientISO354:2003 upto0.8 Alsosuitableforuseinthepreventionofsoundpas-sage

Resistance toBuildingMaterials VeryGoodChemicals ConsultProductTestListOzone VeryGood

Environmental Aspects ODP zero, GWP zero

Health AspectsDust & Fibre FreeMicroban anti-microbial protection

Outdoor applications: ClassOArmaflexshouldbepaintedwithArmafinishFRpainttotherecommendedthicknesswithin3days.Twoormorecoatsmayberequired.

For more information on Armacell visit www.barbourproductsearch.info

Page 10: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

De-Coupling for Pipework with Closed Cell ProtectionClass O Armaflex TUBE

10 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

ClASS O ARMAFlEX TubesLength2m,colourblack

Copper pipeCu

Iron and steel pipe Fe

Min IDmm

6 mm Nominal thickness

9 mm Nominal thickness

NBinch

NomODinch

NomODmm

NBinch

NomODmm

Nomthick-ness Reference

m/carton

Nomthick-ness Reference

m/carton

1/4 6 6.5 6mm CO-06X006 544

1/4 6 9.5 9mm CO-09X006 352

3/8 10 10.5 6mm CO-06X010 400 9mm CO-09X010 280

3/8 1/2 12 12.5 6mm CO-06X012 336 9mm CO-09X012 240

1/2 5/8 15 16.0 6mm CO-06X015 266 9mm CO-09X015 192

5/8 3/4 20.0 6mm CO-06X020 210 9mm CO-09X020 156

3/4 7/8 22 1/2 21.3 22.5 6mm CO-06X022 172 9mm CO-09X022 140

1 11/8 28 3/4 26.9 29.0 6mm CO-06X028 # 112 9mm CO-09X028 98

11/4 13/8 35 1 33.7 9mm CO-09X035 84

11/2 15/8 42 11/4 42.4 9mm CO-09X042 60

11/2 48.3 9mm CO-09X048 56

2 21/8 54 9mm CO-09X054 54

2 60.3 9mm CO-09X060 42

Copper pipeCu

Iron and steel pipe Fe

Min ID mm

13 mm Nominal thickness

19 mm Nominal thickness

NB inch

NomODinch

NomODmm

NB inch

NomODmm

Nomthick-ness Reference

m/carton

Nomthick-ness Reference

m/carton

1/4 6 9.5 13mm CO-13X006 226

3/8 10 10.5 13mm CO-13X010 188 19mm CO-19X010 104

3/8 1/2 12 12.5 13mm CO-13X012 162 19mm CO-19X012 92

1/2 5/8 15 16.0 13mm CO-13X015 136 19mm CO-19X015 78

5/8 3/4 20.0 13mm CO-13X020 112 19mm CO-19X020 70

3/4 7/8 22 1/2 21.3 22.5 13mm CO-13X022 104 19mm CO-19X022 64

1 11/8 28 3/4 26.9 29.0 13mm CO-13X028 78 19mm CO-19X028 50

11/4 13/8 35 1 33.7 35.5 13mm CO-13X035 60 19mm CO-19X035 40

11/2 15/8 42 11/4 42.4 43.5 13mm CO-13X042 56 19mm CO-19X042 32

11/2 48.3 49.0 13mm CO-13X048 40 19mm CO-19X048 30

2 21/8 54 55.0 13mm CO-13X054 42 19mm CO-19X054 24

2 60.3 61.0 13mm CO-13X060 36 19mm CO-19X060 24

21/2 25/8 67 68.0 13mm CO-13X067 34 19mm CO-19X067 20

213/16 3 76.1 21/2 76.1 77.0 13mm CO-13X076 28 19mm CO-19X076 18

3 31/8 80 81.0 13mm CO-13X080 26 19mm CO-19X080 16

3 88.9 90.0 13mm CO-13X089 20 19mm CO-19X089 16

31/2 32/3 93 94.0 13mm CO-13X093 18 19mm CO-19X093 16

4 4 1/4 108 109.0 13mm CO-13X108 16 19mm CO-19X108 12

4 114.3 115.5 13mm CO-13X114 14 19mm CO-19X114 10

For more information on Armacell visit www.barbourproductsearch.info

Page 11: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

De-Coupling for Pipework with Closed Cell Protection Class O Armaflex TUBE

©ArmacellUKLtd.·Subjecttoalterations 2009 (AC) 11

ClASS O ARMAFlEX TubesLength2m,colourblack

Copper pipeCu

Iron and steel pipe Fe

Min IDmm

25 mm Nominal thickness

32 mm Nominal thickness

NBinch

NomODinch

NomODmm

NBinch

NomODmm

NomThick-ness Reference

m/carton

Nomthick-ness Reference

m/carton

3/8 1/2 12 12.5 25mm CO-25X012 50

1/2 5/8 15 16.0 25mm CO-25X015 48 32mm CO-32X018 (1) 32

5/8 3/4 20.0 25mm CO-25X020 40

3/4 7/8 22 1/2 21.3 22.5 25mm CO-25X022 40 32mm CO-32X022 32

1 11/8 28 3/4 26.9 29.0 25mm CO-25X028 32 32mm CO-32X028 24

11/4 13/8 35 1 33.7 35.5 25mm CO-25X035 24 32mm CO-32X035 22

11/2 15/8 42 11/4 42.4 43.5 25mm CO-25X042 24 32mm CO-32X042 16

11/2 48.3 49.0 25mm CO-25X048 22 32mm CO-32X048 12

2 21/8 54 55.0 25mm CO-25X054 18 32mm CO-32X054 12

2 60.3 61.0 25mm CO-25X060 18 32mm CO-32X060 10

21/2 25/8 67 68.0 25mm CO-25X067 16 32mm CO-32X067 # 8

213/16 3 76.1 21/2 76.1 77.0 25mm CO-25X076 14 32mm CO-32X076 8

3 31/8 80 81.0 25mm CO-25X080 12

3 88.9 90.0 25mm CO-25X089 12 32mm CO-32X089 6

31/2 22/3 93 94.0 25mm CO-25X093 12

4 4 1/4 108 109.0 25mm CO-25X108 8

4 114.3 115.5 25mm CO-25X114 8 32mm CO-32X114 4

ClASS O ARMAFlEX DHCG Compliant RangeMeetsBuildingRegulationsPartL(England&Wales)domesticcompliancerequirements;Length2m,colourblack

Copper pipeCu

Max.PermissibleHeatloss(1)

Insulation Thickness Reference

m/carton

NomODinch

NomODmm

8 7.06 13mm CO-13X010 188

3/8 10 7.23 13mm CO-13X010 188

1/2 12 7.35 19mm CO-19X012 92

5/8 15 7.89 19mm CO-19X015 78

7/8 22 9.12 25mm CO-25X022 40

11/8 28 10.07 25mm CO-25X028 32

13/8 35 11.08 25mm CO-25X035 24

15/8 42 12.19 25mm CO-25X042 24

21/8 54 14.12 32mm CO-32X054 12

• 13mm,19mm&25mmtubes:Deliveryquotedonrequestfrom80mmto114mm

• (1)Theadditional3mmtoleranceenchancingthesleavingover

• AllClassOArmaflextubesavailableasSLITitems.Add5p/mnetafterdiscounthasbeenapplied.Fororderingadd-SLTto abovecodes(e.g.CO-19X010-SLT)

• Itemsmarkedwith#-delivery:10workingdays

For more information on Armacell visit www.barbourproductsearch.info

Page 12: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

De-Coupling for Pipework with Closed Cell ProtectionClass O Armaflex TUBE

12 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

ClASS O ARMAFlEX 15m CoilsCoillength15m,everycoilineasycarrybag,colourblack

Copper pipeCu

Iron and steel pipe Fe

MinID mm

6 mm Nominal thickness

9 mm Nominal thickness

NBinch

NomODinch

NomODmm

NBinch

NomODmm Reference

Coils/carton

m/carton Reference

Coils/carton

m/carton

1/4 6 6.5 CO-06X006/E-15 20 300

1/4 6 7.0 CO-09X006/E-15 12 180

3/8 10 10.5 CO-06X010/E-15 14 210 CO-09X010/E-15 10 150

3/8 1/2 12 12.5 CO-06X012/E-15 12 180 CO-09X012/E-15 9 135

1/2 5/8 15 16.0 CO-06X015/E-15 9 135 CO-09X015/E-15 9 135

5/8 3/4 20.0 CO-06X020/E-15 9 135 CO-09X020/E-15 7 105

3/4 7/8 22 1/2 21.3 22.5 CO-06X022/E-15 7 105 CO-09X022/E-15 6 90

1 11/8 28 3/4 26.9 29.0 CO-06X028/E-15 # 5 75 CO-09X028/E-15 5 75

Copper pipeCu

Iron and steel pipe Fe

MinID mm

13 mm Nominal thickness

NBinch

NomODinch

NomODmm

NBinch

NomODmm Reference

Coils/carton

m/carton

1/4 6 9.5 CO-13X006/E-15 9 135

3/8 10 10.5 CO-13X010/E-15 7 105

3/8 1/2 12 12.5 CO-13X012/E-15 6 90

1/2 5/8 15 16.0 CO-13X015/E-15 6 90

5/8 3/4 20.0 CO-13X020/E-15 6 90

3/4 7/8 22 1/2 21.3 22.5 CO-13X022/E-15 5 75

1 11/8 28 3/4 26.9 29.0 CO-13X028/E-15 4 60

ClASS O ARMAFlEX Tape

ReferenceThickness

mmLengthm

Width mm Cartoncontent

CO-TAPE 3 15 50 12rolls

• Allflatandcontinuoussheetswithself-adhesivebacking:deliveryquotedonrequest

For more information on Armacell visit www.barbourproductsearch.info

Page 13: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Dust and Fibre Free

Sound Absorption with a Class O Fire Rating Class O Armaflex PUNCHED

New! Built-In Anti-Microbial Protection Reduces Mould and Bacteria Growth

Nopotentialforfibrecontributiontotheairstream

MeetsBuildingRegulationsClassOfireclassification

Thin,flexibleandlightweightforuseinirregularandconfinedareas

Dust and Fibre Free Sound Absorption with a Class O Fire Rating

Class O Armaflex PUNCHED

S o u n d Ab

so

rp

tio

n

For more information on Armacell visit www.barbourproductsearch.info

Page 14: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Dust and Fibre Free

Sound Absorption with a Class O Fire Rating Class O Armaflex PUNCHED

Plant Room

Lining Ductwork Internally

Class O Armaflex PunchedDust and Fibre Free Sound Absorption with a Class O Fire Rating

ClassOArmaflexPunchedisasemi-closedcellelastomericsheet“punched”togiveanacousticabsorberwhichishighlyflexibleandlightweight.

Itssemi-closedcellstructuregivesClassOArmaflexPunchedanabsorptionprofiledistinctivefromotherclosedcellsheets.ClassOArmaflexPunchedoffersadustandfibrefreealternativetotraditionallyusedabsorptionma-terials.

NewBuilt-inanti-microbialprotectionreducesmouldandbacteriagrowth

Nopotentialforfibrecontributiontotheairstream

MeetsBuildingRegulationsClassOfireclassification

Thin,flexibleandlightweightforuseinirregularandconfinedareas

Pleasing aesthetic appearance allows for use in public view

Formaldehydefree

Low VOC

Dustandfibrefree

Cost-effective alternative to traditional absorbers

In-built Water Vapour Barrier

0 GWP

Nomechanicalfixingsneeded

ACOUSTIC PERFORMANCE

Random incidence absorption coefficient acc.toENISO354

Octave band centre frequency, Hz

125 250 500 1000 2000 4000

@12.5mm(cellside) 0.03 0.06 0.18 0.40 0.76 0.76@32mm 0.08 0.17 0.51 0.56 0.25 0.24

acc.toASTMC423 12.5mm(cellside)

NRC Rating 0.35

Allstatementsand technical informationarebasedon resultsobtainedundertypical conditions. It is the responsibility of the recipient to verifywithus thattheinformationisappropriateforthespecificuseintendedbytherecipient.Forupdatestothisdocumentpleaserefertoourwebsitewww.armacell.com/uk.14 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

For more information on Armacell visit www.barbourproductsearch.info

Page 15: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Dust and Fibre Free

Sound Absorption with a Class O Fire Rating Class O Armaflex PUNCHED

©ArmacellUKLtd.·Subjecttoalterations 2009 (AC) 15

PRODUCT PROFILE Sound Reducing Function SoundAbsorption

Polymer Nitrile Rubber

Cell Structure Semi-closed(punched)

Temperature Range

Max.SurfaceTemperature-tubularsurface +105° C DIN53515(tubular)

Max.SurfaceTemperature-flatsurface +85° C DIN53515(flatsurface)

Min.SurfaceTemperature -50° C DIN53515(tubular)

NCR 0.47??? ???

Visco-elastomeric Properties ??? ??

Air-flow errosion resistance ??? ??

Flammability

FireSpreadofFlames Class 1 BS476Part7:1997

FirePropagation:TotalIndexPerformance(I) > 12 BS476Part6:1997

FirePropagation:SubIndex(i1) >6 BS476Part6:1997

Fire Performance acc. Building Regulation Class O

England&Wales:BuildingRegulations2000

Scotland:BuildingStandards1990

NorthernIreland:BuildingRegulations2000

RepublicofIreland:BuildingRegulations1997

Reaction to Fire Self-extinguishing,doesnotdrip

Reaction to water

NonWicking

Waterrepellant(Hydrophobic)

Health Aspects

Microbananti-microbialprotection

Formaledhydefree

Low VOC

Environmental Aspects

0 ODP

0 GWP

Waste Free Production

CFC + H-CFC free

PH-value Neutral

Resistance to ...

Chemicals Good:seeproducttestlist

Ozone Very Good

Other Attributes

Lead free

Bitumenfree

Flexible

Application

Easytoapply

Easytocut

Noneedofmetallfixings

Self-adhesiveapplication

NOTrecommendedforoutdoorapplications

Product Range FlatSheet

Thickness 15mm

WidthxLength 300x2000mm

Colour Black

For more information on Armacell visit www.barbourproductsearch.info

Page 16: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Dust and Fibre Free

Sound Absorption with a Class O Fire Rating Class O Armaflex PUNCHED

16 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

CLASS O ARMAFLEX Punched SheetColourblack,Punched

Punched Sheet Punched Sheet with Self-Adhesive Backing

Insulation Thickness

mmWidth m

Length m Reference

Carton Content

m2 Reference

Carton Content

m2

15 0.3 2 CO-09MM-P075 13 CO-09MM-P075/A 13

For more information on Armacell visit www.barbourproductsearch.info

Page 17: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

ArmaSound RDHigh Performance Sound Absorption For a Quieter Environment

Excellent absorption and vibration damping performance

Water repellant (Hydrophobic)

No mechanical fixings needed

High Performance Sound Absorption for a Quieter Environment

ArmaSound RD

S o u n d Ba

r rie

r

S o u n d Ab

so

rp

tio

n

S o u n d De

- Co

up

lin

g

V i b r a t i on

Da

mp

ing

Arm

aSou

nd R

D

For more information on Armacell visit www.barbourproductsearch.info

Page 18: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

High Performance Sound Absorption For a Quieter EnvironmentArmaSound RD

ArmaSound RDHigh Performance Sound Absorption for a Quieter Environment

ArmaSound RD is a versatile acoustic absorber designed for use in a va-riety of different acoustic applications. A high performance sound absorber which also offers additional barrier (transmission loss) performance and both vibration damping and de-coupling (isolation) properties.

Delivering optimal performance at lower thicknesses than traditional materi-als, ArmaSound RD is a uniquely advanced open cell acoustic insulation material. Depending on the thickness chosen, ArmaSound RD240 offers excellent sound absorption behaviour across the frequency range.

With a density much greater than traditional acoustic absorption materials, ArmaSound RD is also suitable for some applications that may also call for an acoustic airborne noise barrier.

ArmaSound RD provides a dust and fibre free solution that is suitable for use in a range of demanding environments.

The acoustic properties of ArmaSound RD vary depending on formulation, density and thickness. The best results will be achieved by selecting the most appropriate product grade for the type of noise in question.

ACOUSTIC PERFORMANCE RD 240

Absorption coefficient acc. to EN ISO 354

Octave band centre frequency, Hz

125 250 500 1000 2000 4000

@ 6 mm 0.01 0.03 0.07 0.18 0.39 0.74@ 10 mm 0.01 0.04 0.15 0.46 0.87 0.94@ 15 mm 0.03 0.11 0.38 0.80 1.03 0.89@ 25 mm 0.09 0.28 0.77 1.03 0.94 0.90

Test acc. to EN ISO 11654 6 mm 10 mm at 32 mm

Weighted Sound Absorp-tion Coefficient αw

0.15 (H) 0.25 (H) 0.40 (MH) 0.60 (MH)

Sound Absorption Class E E D C

acc. to ASTM C423 6 mm 10 mm 15 mm 25 mm

NRC Rating 0.15 0.40 0.60 0.75The ‘practical sound absorption coefficient, αp , can be determined by rounding the octave band values listed to nearest NRC is calculated in accordance with ASTM C423 (H) denotes at least 0.25 positive deviation from reference curve value at 2000Hz or 4000Hz (M) denotes at least 0.25 positive deviation from reference curve value at 500Hz or 1000Hz (L) denotes at least 0.25 positive deviation from reference curve value at 125Hz or 250Hz

Sound Absorption

Open cell structure with complex pore geometry allows for effective absorp- tion of air-borne sound across a broad frequency range

Unique combination of physical prop- erties allows absorption to be max- imised at key “nuisance” frequencies

Sound Barrier (Transmission Loss)

Relatively high density and high flow resistance offers an effective barrier to sound.

May be suitable for use as an alter- native to complex ‘foam-barrier’ multi-layers.

Vibration Damping and De-Coupling (Isolation)

Visco-elastic properties help dampen or deaden resonance effects in metal panelwork (e.g. enclosures or duct- ing) which helps to reduce associated ‘re-raditaion’ effects

Reduces structure-borne noise trans- mission in flooring when used as isolation pads.

Plant Room

Lining Ductwork Internally

All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropriate for the specific use intended by the recipient. For updates to this document please refer to our website www.armacell.com/uk.18 2009 (AC) © Armacell UK Ltd. · Subject to alterations

Arm

aSou

nd R

DFor more information on Armacell visit www.barbourproductsearch.info

Page 19: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

ArmaSound RDHigh Performance Sound Absorption For a Quieter Environment

© Armacell UK Ltd. · Subject to alterations 2009 (AC) 19

PRODUCT PROFILE Values Remarks

Max. Surface Temperature +105° CFor temperatures below -20° C and above +105° C, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685

Max. Temperature for Flat Surface +85° C

Min. Surface Temperature -20° C

Fire Performancein accordance with UL94 V0

in accordance with FMVSS 302 Pass

Density 240 kg/m3

Tensile Strength 190 kPa

Elongation 54%

Resistance to ChemicalsOrganic solvents Very GoodDilute inorganic acids & bases Very GoodMineral oils Very Good

For more comprehensive list please consult our Tech-nical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685

Health Aspects Dust & Fibre Free

Armaflex Adhesive 520 is recommended.

TyPICAL PERFORMANCE ARMASOUND RD 240Application Typical Reduction Used System Legislation met

Pipelines Up to 55dB Combination System ArmaSound RD & Arma-Chek Systems

Class A, B & C acc. to ISO 15665 Class A, B, C & D acc. to Shell DEP Spec. No. 31

Waste water pipes Up to 20dB Combination System ArmaSound RD & Arma-Chek Systems na

Washing machines 8dB 10 mm na

Vacuum cleaners 10db (peak) 6mm na

General Enclosures Up to 25db 10-25mm na

Generators Up to 20dB 15mm Various European Noise Standards

Telecommunication Up to 20dB 15mm ETSI 300 (Noise Standards)

Arm

aSou

nd R

D

For more information on Armacell visit www.barbourproductsearch.info

Page 20: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

High Performance Sound Absorption For a Quieter EnvironmentArmaSound RD

20 2009 (AC) © Armacell UK Ltd. · Subject to alterations

ARMASOUND RD 240 SheetsColor: black

ReferenceThickness

mmLength

mWidth

mSheets / carton

ASD-240-06 6 1 1 8

ASD-240-10 10 1 1 5

ASD-240-15 15 1 1 3

ASD-240-20 20 1 1 2

ASD-240-25 25 1 1 2

ARMASOUND RD 240 Self-Adhesive SheetsSelf-Adhesive backing, Colour: black

ReferenceThickness

mmLength

mWidth

mSheets / carton

ASD-240-06/A 6 1 1 8

ASD-240-10/A 10 1 1 5

ASD-240-15/A 15 1 1 3

ASD-240-20/A 20 1 1 2

ASD-240-25/A 25 1 1 2

ARMAFLEX Adhesive 520Armaflex 520 adhesive has been specially formulated for Armaflex insulation to guarantee uniform, safe seam bonding and to produce butt joints with the given object.

Reference DescriptionCarton content

cans

ADH520/2,5 Armaflex adhesive 520, 2.5 litre 8

ADH520/1,0 Armaflex adhesive 520, 1.0 litre 12

ADH520/0,5 Armaflex adhesive 520, 0.5 litre 12

ADH520/0,25 Armaflex adhesive 520, 0.25 litre 24

• For self-adhesive sheets: delivery quoted on request

Arm

aSou

nd R

DFor more information on Armacell visit www.barbourproductsearch.info

Page 21: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

ArmaSound FLOORHigh Performance Noise Reduction For a Quieter Environment

Superior acoustic performance goes beyond minimum requirements

Excellent thermal resistance values offer combined acoustic and thermal performance

Tough closed cell foam with tight cell structure

High Performance Noise Reduction For a Quieter Environment

ArmaSound FLOOR

S o u n d De

- Co

up

lin

g

Arm

aSou

nd F

LOO

R

For more information on Armacell visit www.barbourproductsearch.info

Page 22: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

High Performance Noise Reduction For a Quieter EnvironmentArmaSound FLOOR

ArmaSound Floor

Screed 65mm

Underscreed Flooring

ArmaSound FloorHigh Performance Noise Reduction For A Quieter Environment

ArmaSound Floor is a lightweight, closed cell elastomeric foam that has been designed to act as an under screed resilient layer. Resilient layers acoustically isolate the concrete subfloor from the surface screed which is laid on top.

Laboratory assessment and continued pre-completion (PCT) testing, in accordance with ISO 140 and ISO 717, have proven ArmaSound to be a superior under screed resilient layer solution. At only 10mm thickness, the product comfortably surpasses the acoustic requirements of the Building Regulations.

Superior acoustic performance goes beyond minimum requirements

Tough closed cell foam with tight cell structure - Effectively prevents screed bridging and ensures un-compromised acoustic performance

Excellent thermal resistance values offer combined acoustic and thermal performance

Single layered & supplied in continuous rolls to minimise joint details

Supplied in thinner sections (strips) for edge detailing

In-built Water Vapour Barrier

Underscreed load bearing capabilities

ISO 140 / 717 compliant

ACOUSTIC PERFORMANCE

Test acc. to to ISO 140 / 717 5 mm 10 mm

Airborne DnT,w + Ctr 55 (-6) = 49 54 (-6) = 48

Impact LnT,w 52 46

Lw n/a 18

STC 56 55

IIC 58 (Very Good) 62 (Excellent)

» Flooring construction details need to be understood before interpreting results above

» ISO 140-8, results, Lw , are for 65mm sand/cement screed

» STC = Sound Transmission Class acc. ASTM 413-4

» IIC = Impact Isolation Class acc. ASTM E989-6

All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropriate for the specific use intended by the recipient. For updates to this document please refer to our website www.armacell.com/uk.22 2009 (AC) © Armacell UK Ltd. · Subject to alterations

Arm

aSou

nd F

LOO

RFor more information on Armacell visit www.barbourproductsearch.info

Page 23: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

ArmaSound FLOORHigh Performance Noise Reduction For a Quieter Environment

© Armacell UK Ltd. · Subject to alterations 2009 (AC) 23

PROdUCT PROFILE

Values RemarksMax. Service Temperature +85° C For temperatures below 0° C, please consult our

Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685Min. Service Temperature 0° C

Acoustic PerformanceAirborne DnT,w+Ctr 48 dB Impact LnT,w 46 dB

Test acc. to ISO 140:1998 Part 4 & 7(for floor set-up: see drawing above)

R-ValueArmaSound Floor 10mm 0.26 m2 · (K/W)ArmaSound Floor 15mm 0.40 m2 · (K/W)ArmaSound Floor 25mm 0.67 m2 · (K/W)

Dynamic stiffness 10MN/m3 Test acc. to BS EN 29052 for ArmaSound Floor 25mm

Water Vapour Permeability Moisture Resistance Factor µ > 2,000

Water Absorption 0.2% by volume Test acc. to ASTM C 209

Resistance toBuilding Materials Very GoodChemicals Consult Product Test List

Environmental Aspects ODP zero, GWP zero

Health Aspects Dust & Fibre Free

Outdoor applications - ArmaSound Floor is NOT SUITABLE for outdoor applications

Arm

aSou

nd F

LOO

R

For more information on Armacell visit www.barbourproductsearch.info

Page 24: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

High Performance Noise Reduction For a Quieter EnvironmentArmaSound FLOOR

24 2009 (AC) © Armacell UK Ltd. · Subject to alterations

ARMASOUNd Floor Continuous SheetColour dark grey, skin on both sides

ReferenceThickness

mmWidth

mLength

mCarton content

m2

ASFL-10-1,5 10 1.5 10 15

ASFL-15-1,5 15 1.5 7 10.5

IT-25-99/E-B1 # 25 1 4 4

# 25 mm sheets meet dynamic stiffness acc. to Building Regulation Part E

ARMASOUNd Floor Edging ProfileEdging profile in flat rolls. Thickness: half 5mm other half 10mm - forms a L-Profile when installed; Colour black

Reference DescriptionThickness

mmWidth mm

Length m

Carton content m2

AFL-05-10/E ArmaSound Floor edging profile 5 / 10 20 15 t.b.a.

• For all ArmaSound Floor products: Delivery 10 working days

Arm

aSou

nd F

LOO

RFor more information on Armacell visit www.barbourproductsearch.info

Page 25: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

ARMASOUND Industrial SystemsAcoustic Pipe Insulation Systems Which Minimise Corrosion Under Insulation

Acoustic pipe insulation systems which minimise corrosion under insulation

Combined thermal and acoustic properties

The“built-inwater-vapour-barrier”providescontinuouslong-termthermalefficiency

Significantlyreducedinsulationthicknessandoverallsystemweight

ArmaSound INDUStRIAl SySteMS

S o u n d Ba

r rie

r

S o u n d Ab

so

rp

tio

n

S o u n d De

- Co

up

lin

g

AR

MA

SO

UN

D In

dust

rial

Sys

tem

s

For more information on Armacell visit www.barbourproductsearch.info

Page 26: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Acoustic Pipe Insulation Systems Which Minimise Corrosion Under InsulationARMASOUND Industrial Systems

InSertIon loSS of ArmASounD InDuStrIAl SyStemS ACC. to ISo 15665:2003 nom.pipe-Ø:≥300mmto<650mm

ArmaSoundIndustrialSystem Class

Octavebandcentrefrequency,Hz

125 250 500 1000 2000 4000 8000

Insertionloss,dB

ArmaSound Industrial System A (EL) A2 1.4 -3.7 3.9 12.8 18.9 28.6 38.9

ArmaSound Industrial System B (EL) B2 0.9 0.8 9.2 17.2 28.6 38.2 41.6

ArmaSound Industrial System C (EL) C2 -1.2 11.8 16.3 24.3 36.0 49.8 47.6

ArmaSound Industrial System D (EL) D2 -3.3 5.1 15.6 37.2 48.8 49.7 45.6

ArmaSound Industrial SystemsAcoustic Pipe Insulation Systems Which Minimise Corrosion

Under Insulation

ArmaSound Industrial Systems are high performance acoustic and ther-mal insulation systems for industrial,marine and offshore environments.ThesandwichsystemofArmaflex,ArmaSoundRD240andArma-ChekRcoveringreducestheriskofcorrosionunderinsulation(CUI)andprovidesexceptionalnoisereductionwhileminimisingtotalsystemweightandthick-ness.

ComplianttoISO15665ClassesAtoCandShellDEP31ClassD.Otherstandardsmet includeNORSOKR-004Classes6,7and8andASTME1222.

Combined thermal and acoustic properties

The “built-in water-vapour-barrier” provides continuous long-term thermal efficiency

Significantlyreducedinsulationthicknessandoverallsystemweight

Preventscondensationbyusingclosedcelltechnology

No galvanic corrosion

Non-metalcladdingsystem-reducesHealthandSafetyrisks

ResistsUV,oil,chemicalsandweatherisation

Considerable reduction in maintenance costs

Dust & Fibre free

ISO15665compliant

All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verifywithus thattheinformationisappropriateforthespecificuseintendedbytherecipient.Forupdatestothisdocumentpleaserefertoourwebsitewww.armacell.com/uk.26 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

AR

MA

SO

UN

D In

dust

rial

Sys

tem

sFor more information on Armacell visit www.barbourproductsearch.info

Page 27: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

ArmaSound BARRIERHigh performance sound barrier for a quieter environment

High performance sound barrier for a quieter environment

ArmaSound BARRIER

ArmaSound Barrier E: Vinyl sound barrier mat loaded with naturally occurring minerals

ArmaSound Barrier T: Bitumen based, lead free, sound barrier mat ideal for use with metal claddings.

S o u n d Ba

r rie

r

Arm

aSou

nd F

LOO

R

For more information on Armacell visit www.barbourproductsearch.info

Page 28: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

High performance sound barrier for a quieter environmentArmaSound BARRIER

50

40

30

20

10

0

100 1000 10000

Frequency (Hz)

Tran

smis

sio

n L

oss

(dB

)

Transmission Loss Curve acc. to ISO 140 Part 3 *

* The results above are based on 4mm ArmaSound Barrier E.

ArmaSound BarriersHigh Performance Barrier for a Quieter Environment

ArmaSound Barrier E: Vinyl sound barrier mat loaded with naturally oc-curring minerals. The product is free of lead, unrefined aromatic oils and bitumen. It is excellent at reducing the transmission of airborne sound and in enhancing the insertion loss performance of pipe insulation by providing a barrier to noise.

Lead free

Flexible

Meets recommended Part L energy performance when internally lining ductwork*

Excellent de-coupling and isolation performance on pipes and ducts in contact with other structural and service elements

Suitable for use in areas of high humidity and areas with possible oil and chemical contact

ArmaSound Barrier T: Bitumen based, lead free, sound barrier mat ideal for use with metal claddings. It is excellent at reducing the transmission of airborne sound and in enhancing the insertion loss performance of pipe insulation by providing a barrier to noise.

Efficient and weight saving

Anti-drumming of thin wall sheet metal

Excellent adhesion on stainless steel, sheet metal and plastics

Lead free

Flexible

ACOUSTIC PERFORMANCE

ArmaSound Barrier E5 kg/m2

(nom. 2 mm)

7.5 kg/ m2

(nom. 3 mm)

10 kg/ m2

(nom. 4 mm)

Mean Sound Reduction index, R (dB)

22 25 28

ArmaSound Barrier T: Loss Factor on 1 mm steel 0.15 at 200Hz, 20°C

All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropriate for the specific use intended by the recipient. For updates to this document please refer to our website www.armacell.com/uk.28 2009 (AC) © Armacell UK Ltd. · Subject to alterations

Arm

aSou

nd F

LOO

RFor more information on Armacell visit www.barbourproductsearch.info

Page 29: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

ArmaSound BARRIERHigh performance sound barrier for a quieter environment

PROdUCT PROFILE

ArmaSound Barrier E ArmaSound Barrier TMean Sound Reduction Index RW 28 dB (result valid for 4mm)

Loss factor (@ 20°C, 200 Hz, 1mm steel) ≥ 0.15

Max. Service Temperature * +65° C +80° C

Min. Service Temperature * -30° C -30° C

Application Temperature * > +5° C > +18° C

Thickness 2 mm 3 mm 4 mm 2.3 mm ± 0.2 mm

Weight 5 kg/m2 7.5 kg/m2 10 kg/m2 2 kg/m2 (approx.)

Tensile Strength 2.6 MPa 150 N/20 mm (acc. to DIN 53 112)

Elongation at Break 90%

Hardness Shore A 90

Adhesion on ono-corrosive sheet steel ≥ 7 N/cm

Colour black grey

Health Aspects free of lead free of lead

Storage Temperature +10° C to +25° C

Shelf life approx. 12 months approx. 12 months

Outdoor applications: - ArmaSound Barrier should be covered with Arma-Chek R or Arma-Chek D.

* For temperatures above +65° C (for BarrierT: +80° C and below -30° C, please consult our Technical Department.

© Armacell UK Ltd. · Subject to alterations 2009 (AC) 29

Arm

aSou

nd F

LOO

R

For more information on Armacell visit www.barbourproductsearch.info

Page 30: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

High performance sound barrier for a quieter environmentArmaSound BARRIER

30 2009 (AC) © Armacell UK Ltd. · Subject to alterations

ARMASOUNd Barrier EVinyl sound barrier mat, Colour black

Reference DescriptionThickness

mmWidth

mLength

mCarton content

m2

ASD-BAR-E-02 ArmaSound Barrier E 2mm 2 1.25 (1) 2 (1) t.b.a.

ASD-BAR-E-03 ArmaSound Barrier E 3mm 3 1.25 (1) 2 (1) t.b.a.

ASD-BAR-E-04 ArmaSound Barrier E 4mm 4 1.25 (1) 2 (1) t.b.a.

ARMASOUNd Barrier TBitumen-impregnated wool-felt with self-adhesive backing

Reference DescriptionThickness

mmWidth

mLength

mCarton content

m2

ASD-BAR-T-02 ArmaSound Barrier T 2.3 mm - with selfadhesive backing 2.3 0.5 1 t.b.a.

• (1) The dimensions for ArmaSound Barrier E are only guaranteed on: 2000 m2 for 4 mm; 3000 m2 for 3 mm; 4000 m2 for 2 mm.

• For all ArmaSound Barrier products: Delivery quoted on request

Arm

aSou

nd F

LOO

RFor more information on Armacell visit www.barbourproductsearch.info

Page 31: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Non Metallic Cladding with Barrier Performance Arma-Chek R Barrier

Cladding with combined acoustic barrier performance

Highly resistant to UV, oil and chemicals

Complies with international standards

Non Metallic Cladding with Barrier Performance

arma-Chek r Barrier

S o u n d Ba

r rie

r

r

For more information on Armacell visit www.barbourproductsearch.info

Page 32: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Non Metallic Cladding with Barrier PerformanceArma-Chek R Barrier

Arma-Chek R BarrierNon Metallic Cladding with Barrier Performance

Arma-Chek R is a particularly resilient, non metallic, acoustic barrier and protective covering system with an IMO certified fire performance. Markedly reducing the corrosion and installation issues associated with metallic cov-ering systems, Arma-Chek R has been designed to work in harmony with Armaflex insulation, expanding and contracting as required.

It is also used to enhance the insertion loss performance of our acoustic insulation systems by providing a barrier to noise.

Cladding with combined acoustic barrier performance

In-built Water Vapour Barrier

UV-resistant

Mechanical protection

0 GWP

Lead free

Class 1 surface spread of flame

Non-metallic cladding

Highly resistant to oil and chemicals

aCOUSTiC PerFOrMaNCe

Insertion Loss, dBacc. to EN ISO 15665

Octave band centre frequency, Hz

125 250 500 1000 2000 4000

2 mm* 1.4 -3.7 3.9 12.8 18.9 28.6

* 2mm Arma-Chek Barrier tested on pipework acc. to ISO 15665 - Class A2 with 25mm Armaflex

sheet

All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropriate for the specific use intended by the recipient. For updates to this document please refer to our website www.armacell.com/uk.32 2009 (AC) © Armacell UK Ltd. · Subject to alterations

rFor more information on Armacell visit www.barbourproductsearch.info

Page 33: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Non Metallic Cladding with Barrier Performance Arma-Chek R Barrier

© Armacell UK Ltd. · Subject to alterations 2009 (AC) 33

PrOdUCT PrOFile

Values RemarksMaterial Flexible polymeric barrier

Max. Surface Temperature+105° C (if based on Class O Armaflex, NH/Armaflex)+150° C (if based on HT/Armaflex)

* For temperatures between -50°C and -200°C, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685

Max. Surface Temperature for Flat Surface

+85° C (if based on Class O Armaflex, NH/Armaflex)+130° C (if based on HT/Armaflex)

Min. Surface Temperature -200° C*

Water Vapour Permeability Covering Moisture Resistance Factor µ > 50,000

Water Vapour Permeability Insulation No risk of Galvanic corrosion Moisture Resistance Factor depending on the used

Armaflex substrate

Resistance toImpact Extremely GoodUV Good

For more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685

Density 1.6 kg/ltr. (± 50g)For more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685

Tensile Strength 5.0 MPa (± 1 MPa)

acc. to ISO 37For more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685

Tear Strength 5.0 - 6.5 N/mm

acc. to ISO 34aFor more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685

ElongationArma-Chek R Black 450 - 650%Arma-Chek R Grey 150 - 250%

acc. to ISO 37For more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685

Health Aspects Dust & Fibre Free

r

For more information on Armacell visit www.barbourproductsearch.info

Page 34: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Non Metallic Cladding with Barrier PerformanceArma-Chek R Barrier

34 2009 (AC) © Armacell UK Ltd. · Subject to alterations

arMa-CHeK r (Grey) Barrier on RollsGrey covering for the insulation materials Class O Armaflex, NH/Armaflex HT/Armaflex

ReferenceThickness

mmWidth mm

Length of roll m m2 / roll

ACH-R20/1-07-GY 1 700 20 14

ACH-R10/2-07-GY 2 700 10 7

arMa-CHeK r (Grey) Mastic

Reference Description Carton content

ACH-MASTICS Light grey sealing compound for installing Arma-Chek R grey outdoors, 290 ml 12 cartridges

arMa-CHeK r (Black) Covering on RollsBlack covering for the insulation materials Class O Armaflex, NH/Armaflex HT/Armaflex

ReferenceThickness

mmWidth mm

Length of roll m m2 / roll

ACH-R20/0,7 1 700 20 14

arMa-CHeK r (Black) Mastic

Reference Description Carton content

ACH-MASTICD Black sealing compound for installing Arma-Chek R outdoors, 290 ml 12 cartridges

• Pre-FaBriCaTed BeNdS, T-PieCeS & CaP eNdS! A full range of pre-fabricated Arma-Chek R covers for bends, T-pieces and cap ends is available. For full details see either the separate product range document or call our customer service on 0044 (0)161 287 7100. Prices & delivery are quoted on request.

rFor more information on Armacell visit www.barbourproductsearch.info

Page 35: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Reducing Break-Out Noise with Closed Cell Protection Armaflex R SHEET

Dustandfibrefreeinsulationwiththermalandacousticproperties

Impressiveairbornenoiseabsorptionatproblemfrequencies

Excellentde-couplingandisolationperformanceonpipesandductsincontactwithother structuralandserviceelements.

Reducing Break-Out Noise with Closed Cell Protection

Armaflex R SHEET

S o u n d Ab

so

rp

tio

n

S o u n d De

- Co

up

lin

g

R

For more information on Armacell visit www.barbourproductsearch.info

Page 36: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Reducing Break-Out Noise with Closed Cell ProtectionArmaflex R SHEET

Armaflex RReducing Break-Out Noise with Closed Cell Protection

Armaflex R is a flexible closed cell elastomeric sheet pre-covered withArma-ChekRBarrier.Beingaclosedcellmaterial,ArmaflexRrequiresnoexternal vapour barrier andwill not absorbmoisture by “wicking”.WhenArmaflexRisusedasanexternallining,break-outnoisefromtheductwallcanbesignificantlyreduced.Armaflexisdust,fibreandformaldehydefree,andinhibitstheonsetof“sickbuildingsyndrome”.

Dustandfibrefreeinsulationwiththermalandacousticproperties

Impressiveairbornesoundabsorptionatproblemfrequencies

Excellentde-couplingandisolationperformanceonpipesandductsin contactwithotherstructuralandserviceelements

Suitableforuseinareasofhighhumidityandareaswithpossibleoiland chemicalcontact

NoadditionalMechanicalprotectionneeded

ACOUSTIC PERFORMANCE

Insertion Loss, dBacc.toENISO15665

Octavebandcentrefrequency,Hz

125 250 500 1000 2000 4000

at25mmsheet* 1.4 -3.7 3.9 12.8 18.9 28.6

Insulating Ductwork Externally

Insulating Industrial Process Pipework

Allstatementsand technical informationarebasedon resultsobtainedundertypical conditions. It is the responsibility of the recipient to verifywithus thattheinformationisappropriateforthespecificuseintendedbytherecipient.Forupdatestothisdocumentpleaserefertoourwebsitewww.armacell.com/uk.36 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

RFor more information on Armacell visit www.barbourproductsearch.info

Page 37: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Reducing Break-Out Noise with Closed Cell Protection Armaflex R SHEET

©ArmacellUKLtd.·Subjecttoalterations 2009 (AC) 37

PROdUCT PROFIlE

Values Remarks

Material FoamednitrilerubberprecoveredwiththeflexiblepolymericArma-ChekRbarrier

Max. Surface Temperature +105°C (basedonClassOArmaflex)

*Fortemperaturesbetween-50°Cand-200°C,pleaseconsultourTechnicalDepartment.Tel.+44(0)1612877038·Fax+44(0)1616332685

Max. Surface Temperature for Flat Surface +85°C (basedonClassOArmaflex)

Min. Surface Temperature -200°C*

Thermal Conductivity at 0°C 0.034W/(m·K)

Testacc.toENISO8497Thermal Conductivity at +20°C 0.036W/(m·K)

Thermal Conductivity at +40°C 0.038W/(m·K)

Water Vapour PermeabilityMoistureResistanceFactorµ 7,000BSENISO9346:1996 2.79·10(-14)kg/(msPa)

Resistance toBuildingMaterials VeryGoodChemicals ConsultProductTestListOzone VeryGood

Environmental Aspects ODP zero, GWP zero

Health AspectsDust & Fibre FreeMicroban anti-microbial protection

Armaflex R Pre-coated Class O Armaflex sheetsPrecoatedflatsheetsCovering:Grey;Length:2metre;Width:0.5metre

Insulation Thickness

mmWidth m

Length m Reference

Cartoncontentm2

13 0.5 2 COR-13MM-GY 9

19 0.5 2 COR-19MM-GY 7

25 0.5 2 COR-25MM-GY 5

Armaflex R (Grey) Mastic

Reference Description Cartoncontent

ACH-MASTICS LightgreysealingcompoundforinstallingArma-ChekRgreyoutdoors,290ml 12cartridges

R

For more information on Armacell visit www.barbourproductsearch.info

Page 38: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Reducing Break-Out Noise with Closed Cell ProtectionArmaflex R SHEET

38 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

RFor more information on Armacell visit www.barbourproductsearch.info

Page 39: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

ArmaloadAcoustic De-Coupling for Duct and Pipe Supports

Dustandfibrefreeinsulationwiththermalandacousticproperties

Excellentde-couplingandisolationperformance

PreventsThermalandAcousticBridging

Acoustic De-Coupling for Duct and Pipe Supports

SECTIONS

S o u n d De

- Co

up

lin

g

For more information on Armacell visit www.barbourproductsearch.info

Page 40: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Acoustic De-Coupling for Duct and Pipe SupportsArmaload

ArmaloadAcoustic De-Coupling for Duct and Pipe Supports

Armaloadpipesupportsandloadbearingsectionspreventacousticbridg-ingbyeliminatingdirectcontactofpipeandductworkwithhangingsupportstructures.Theseservicesaretheneffectivelyde-coupledfromthebuildingstructure.Havingthermalinsulationpropertiesandabuilt-inwatervapourbarrier,Armaload is fully compatiblewithArmaflex to create a seamlessinsulationsystem.Armaloadalsopreventsthermalbridging.

Dustandfibrefreeinsulationwiththermalandacousticproperties

Excellentde-couplingandisolationperformance

PreventsThermalBridging

PrOduCT PrOfIlE

Values RemarksDescription Highdensityflexibleelastomericpipesupport

Max. Surface Temperature +105° C Fortemperaturesbelow-50°C,pleaseconsultourTechnicalDepartment.Tel.+44(0)1612877038·Fax+44(0)1616332685Min. Surface Temperature -50°C

Thermal Conductivity at +20° C 0.045W/(m·K)

Water Vapour Permeability µ 7,000

Water Absorption 0.2%byvolume Testacc.toASTMC209

Surface Spread of Flame Class1

Reaction to fire Self-extinguishing,doesnotdrop

Environmental Aspects ODP zero, GWP zero

Health Aspects Dust & Fibre Free

Outdoor applicationsshouldbepaintedwithArmafinishFRpainttotherecommendedthickness.Twoormorecoatsmayberequired.

Allstatementsand technical informationarebasedon resultsobtainedundertypical conditions. It is the responsibility of the recipient to verifywithus thattheinformationisappropriateforthespecificuseintendedbytherecipient.Forupdatestothisdocumentpleaserefertoourwebsitewww.armacell.com/uk.40 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

For more information on Armacell visit www.barbourproductsearch.info

Page 41: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

ArmaloadAcoustic De-Coupling for Duct and Pipe Supports

©ArmacellUKLtd.·Subjecttoalterations 2009 (AC) 41

ArMAlOAd Pipe SupportHighDesityPipeSupport;Colour:black

Pipe O.D. mm

MinimumI.D.mm

Maxpipesupportinterval

m

19mmInsulation Thickness

CopperCuIronandsteelFe Reference

O.D.mm

Width mm Pcs./carton

15 15 2,00 PH-19-015 53 55 32

22 21,3 22 2,75 PH-19-022 60 55 32

28 26,9 28 3,00 PH-19-028 66 55 32

35 33,7 35 3,50 PH-19-035 73 65 28

42 42,4 42 3,75 PH-19-042 80 65 28

ArMAlOAd Pipe Support SectionArmaloadisusedasaloadbearinginsulatinginsertbetweeninsulatedpipesandtheirsupportinlowtemperatureinstallations.WhereArmaflexisincontactwithArmaloadsomecompressionoftheinsulationcanbeexpected,butthiswillnotaffecttheinsulativeproperties.

Reference DescriptionCartoncontent

m

ALOAD-UH 19mmx40mmx1000mmhalf-roundsections 40

For more information on Armacell visit www.barbourproductsearch.info

Page 42: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Acoustic De-Coupling for Duct and Pipe SupportsArmaload

42 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

For more information on Armacell visit www.barbourproductsearch.info

Page 43: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Acoustic De-Coupling for Waste Water Pipes AR FONOBLOK

Reducesnoisefromwastewaterpipesinflatsandhotels

Effectivelyeliminatesacousticbridges

Highlyflexibleforfastandeasysleevingoverpipes,elbowsandflanges

Acoustic De-Coupling for Waste Water Pipes

AR FONOBLOK

S o u n d De

- Co

up

lin

g

AR

For more information on Armacell visit www.barbourproductsearch.info

Page 44: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Acoustic De-Coupling for Waste Water Pipes AR FONOBLOK

Vertical drainage system, semi-protected in a side wall

Outerwall

Drainagesystem

Livingenvironment

Plaster,3cm

Tubolit AR

Tubolit AR FonoblokAcoustic De-Coupling For Waste Water Pipes

TubolitARFonobloktubeisaflexiblede-couplinginsulationtoreduceau-dible noise fromwastewater pipeswithin offices, flats, hotels, hospitalsandschools.Theproductoffersacertifiednoisereductionupto15dB(A).Insulating theentirepipework systemensureseffectivede-coupling fromsupportingandstructuralelementsaswellasotherserviceinstallations.

Atjust5mmthickness,TubolitARFonoblokcaneffectivelypreventacousticbridging,especiallywithinseverelyrestrictedplaces.Itshighflexibility,lowweightandoptimised tolerancesensureeasysleevingand installationoftheproduct-evenonelbowsandfittings.

Reduces noise from waste water pipes

»Suppliedintubeformtoreducelabourcosts

Effectivelyeliminatesacousticbridges

Combinedthermal&acousticinsulation

NonWicking

Dust&Fibrefree

Singlelayerapplication

Highlyflexibleforfastandeasysleevingoverpipes,elbowsandflanges

ACOUSTIC PERFORMANCE

Test acc. to EN 14366Installationsoundlevel,Lln

Q(l/s) withinsulation withoutinsulation difference

DN100castironpipe

1 16 (dB) 30 (dB) 14 (dB)2 19 (dB) 34 (dB) 15 (dB)4 24 (dB) 38 (dB) 14 (dB)

Allstatementsand technical informationarebasedon resultsobtainedundertypical conditions. It is the responsibility of the recipient to verifywithus thattheinformationisappropriateforthespecificuseintendedbytherecipient.Forupdatestothisdocumentpleaserefertoourwebsitewww.armacell.com/uk.44 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

AR

For more information on Armacell visit www.barbourproductsearch.info

Page 45: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Acoustic De-Coupling for Waste Water Pipes AR FONOBLOK

TUBOLIT AR Coils - Sound absorption for waste water pipesLength15m,Colour:metallicblue

Pipe Insulationthickness5 mm

Nom OD mm Reference m/carton rolls/carton

50 TL-50/5-AR 135 9

70 TL-70/5-AR 105 7

90 TL-90/5-AR 75 5

100 TL-100/5-AR 75 5

125 TL-125/5-AR 60 4

150 TL-150/5-AR 45 3

TUBOLIT AR TapeColourblue,self-adhesive

ReferenceThickness

mmLength

mWidthmm

Carton content rolls

TL-TAPE/50-AR 3 15 50 12

TL-TAPE/75-AR 3 15 75 8

TL-TAPE/100-AR 3 15 100 6

©ArmacellUKLtd.·Subjecttoalterations 2009 (AC) 45

AR

For more information on Armacell visit www.barbourproductsearch.info

Page 46: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

Acoustic De-Coupling for Waste Water Pipes AR FONOBLOK

46 2009 (AC) ©ArmacellUKLtd.·Subjecttoalterations

AR

For more information on Armacell visit www.barbourproductsearch.info

Page 47: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

1. ScopeThese Conditions of Sale apply to all contracts between Armacell and the Buyer for of sale and purchase of the Products (the Contract”) to the ex-clusion of any other terms and conditions contained or referred to in any order, letter, form of contract or other communication sent by the Buyer to Armacell. These Conditions shall not be modified unless with the prior written approval of an officer of Armacell. These Conditions shall prevail over any and all of the Buyer’s general and specific terms and conditions of purchase and shall supersede all previous communications with the Buyer, either oral or written. Any concession made or latitude allowed by Armacell to the Buyer shall not affect the strict rights of Armacell under the contract. If in any particular case any of these Conditions shall be or be held to be invalid or shall not apply to the contract the other Conditions shall continue in full force and effect.

2. Coming into effectThe contract between Armacell and the Buyer shall come into effect when the Buyer places an order upon these Conditions and it is accepted by Armacell.

3. Prices(a) The prices of the Products shall be the Armacell list price current at the date of the order(b) Prices are subject to change without notice [to take account of any variation in Armacell’s costs]. The Products will be invoiced at the price ruling on the date of despatch from Armacell’s premises. For any order for delivery at one place at one time where the net value is less than £150.00 a charge of £50.00 will be added to cover car- riage and administrative charges. VAT will be added as a separate item of account. Quantity terms current from time to time are avail- able on request. (c) Unless otherwise stated on Armacell’s invoice, payment by the Buyer must be made before the end of the month following the month in which Armacell’s invoice is dated.(d) Unless otherwise agreed in writing, Armacell operate to the following payment terms: (i) Receipt of payment in full on or before the 15th day following the date of invoice shall be subject to a 2% discount. (ii) Receipt of payment in full on or before the 20th day of the month following the date of the invoice shall be subject to a 1.5% discount. (iii) Net payment shall be made by the end of the month following the month of invoice. These payment terms shall appear on Armacell’s invoices as follows: “2%-15 days, 1.5%-20th proximo, net-30th proximo”.(e) Without prejudice to any other rights it may have, Armacell shall be entitled (both before and after any judgment) to charge interest on any overdue amounts at 5% over the base lending rate, from time to time, of Barclays Bank PLC.(f) The price of the Products shall be due in full to Armacell in accord- ance with the terms of the contract and the Buyer shall not be entitled to exercise any set-off, lien or any other similar right or claim. (g) The time of payment shall be of the essence of the contract.

4. Additional costsThe Buyer shall indemnify Armacell in respect of any loss, cost or expense incurred by Armacell as a result, directly or indirectly, of the Buyer’s in-structions or lack of instructions or through any failure or delay whatsoever in taking delivery or through any other act, neglect or default on the part of the Buyer, its servants, agents or employees.

5. Intellectual propertyThe Buyer shall indemnify Armacell against all costs, claims, losses, ex-penses and damages incurred by Armacell or for which it may be liable due to or arising directly or indirectly out of any infringement or alleged infringement of patents, trade marks, copyright, design right or other intel-lectual property right occasioned by the importation, manufacture or sale of the Products if made to the specification or special requirements of the Buyer.

6. Delivery and Passing of Risk and Title(a) Delivery shall be completed when made to the place of delivery in mainland United Kingdom, Northern Ireland or the Republic of Ireland, specified by the Buyer at the time of order, at which time all risks or loss or damage to the Products shall pass to the Buyer who shall be solely responsible for their custody and maintenance. Upon delivery the Buyer shall sign the Armacell delivery receipt notice. The unloading of the Products at the place of delivery and subse- quent storage is at the sole risk of the Buyer. Delivery elsewhere is subject to agreement by Armacell and an additional delivery charge. No part cartons will be supplied. (b) Title to the Products shall only pass to the Buyer after full payment for all goods sold by Armacell to the Buyer under the contract and any other contract between Armacell and the Buyer and on any other account whatsoever has been made to Armacell. The Buyer may sell the Products in the normal course of business. However, in the event of any resale by the Buyer of the Products Armacell’s beneficial entitlement shall attach to the proceeds of sale or other disposition thereof so that such proceeds or any claim therefor shall be assigned to Armacell and until such assignment shall be held on trust in a separate identified account for Armacell by the Buyer and such proceeds shall not be mingled with other moneys or paid into any overdrawn bank account and shall at all times be identifiable as Armacell’s moneys. Until full payments for all such goods, and in addition to any other remedy available at law, Armacell has the right, at any time without notice for all goods sold by Armacell to the Buyer, to take possession of and re-sell the Products, and for that purpose the Buyer authorises Armacell to enter its premises and agrees to store the Products in such a way that they are readily identifiable as the property of Armacell.(c) Pending payment of the full purchase price of the Products the Buyer shall at all times keep the Products comprehensively insured against loss or damage by accident, fire, theft and other risks usu- ally covered by insurance in the type of business carried on by the Buyer in an amount at least equal to the balance of the price for the same from time to time remaining outstanding. The policy shall bear an endorsement recording Armacell’s interest.(d) All times dates or periods given for delivery of the Products are given in good faith but without any responsibility on Armacell’s part. Time of delivery shall not be of the essence of the contract. Any period for delivery shall be calculated from the time of Armacell’s acceptance of the Buyer’s order or from Armacell’s receipt of all information necessary to enable Armacell to manufacture or procure the manufacture of the Products (whichever shall be the later).

ARMACELL UK LIMITED TERMS AND CONDITIONS FOR THE SALE OF ITS PRODUCTS (02/07)

(e) Where the Products are handed to a carrier for carriage to the Buyer or to United Kingdom port for export any such carrier shall be deemed to be an agent of Armacell and not of the Buyer for the purposes of sections 44, 45 and 46 of the Sale of Goods Act 1979. The Buyer agrees that (i) section 32(3) of the Sale of Goods Act 1979 shall not apply to Products sent by Armacell; and (ii) it shall be responsible for complying with any legislation or regulations govern- ing the importation of the Products into the country of destination, and into any country through which the Products are transported, and for the payment of any duties on or in respect of the importation or transportation of the Products.(f) Additions to orders will not be accepted after a vehicle loading schedule has been finalised. The Buyer’s instructions, which restrict the delivery vehicle, must be specified by the Buyer no later than the time of order, and may incur extra charges.(g) In respect of each order Armacell will not consider delivering ad- ditional quantities after Armacell has dispatched an order.(h) All Armaflex orders for pipe insulation shall be delivered by Armacell in tubular form unless the Buyer stipulates “slit” pipe insulation on order.(i) If for any reason the Buyer is unable to accept delivery of the Products at the time when the Products are due and ready for delivery Armacell may at its sole discretion without prejudice to its other rights and for such period as Armacell may determine store the Products at the Buyer’s risk and take all reasonable steps to safeguard and insure them at the Buyer’s cost, provided that the Buyer shall be immediately informed thereof.

7. Products ReturnedProducts supplied in accordance with the contract cannot be returned without prior written authority from an Armacell salesman (and only un-opened cartons and materials will be considered). Duly authorized returns shall be sent to Armacell’s premises at Mars Street, Oldham, Lancashire, OL9 6LY or such other address as notified to the Buyer. Unless other-wise agreed in writing, the Buyer will be liable to pay to Armacell a charge of 15% of the invoice value of the Products dispatched for the returned Products to cover the costs, expenses, damages and losses incurred by Armacell associated with such returns.

8. Warranty and defects(a) Armacell warrants Insulation Tube and Sheet products in general against defects in manufacturing and material and deviations from published technical characteristics for a period of twelve months from date of delivery or for three months after the date of completion of the building in which the products have been installed which ever is the shorter period of time, if installed, used and maintained in accordance with Armacell’s then current instructions and recom mendations and provided that Armacell receives notice of such defects within seven days of the Buyer becoming aware of such defects.(b) Further, Armacell warrants Armaflex insulation tube and sheet products in particular against defects in manufacturing and material and deviations from published technical characteristics for a period of five years from the date of installation if installed, used and maintained in accordance with Armacell’s then current instructions and recommendations.(c) In substitution for all rights which the Buyer would or might have but for these Conditions, Armacell undertakes, in the case of Products manufactured by Armacell, that in the unlikely event that within 3 months of delivery of any Product a defect appears (being a defect which would not be obvious on reasonable inspection, whether or not such an inspection was carried out) or the Product proves to be unable to meet the relevant technical criteria, Armacell will at its option and as appropriate subject to proof of delivery, completion or installation date, either (i) remove and replace the defective Product at no charge or (ii) refund the cost of such Product by way of credit note to the Buyer, save always that Armacell shall have no responsi- bility if the Product in question was installed with the knowledge that the Product was defective.(d) In order to exercise its rights under this condition 8, the Buyer shall inform Armacell with seven days of the date when such defect appeared or ought reasonably to have been discoverable.(e) These warranties do not extend to ancillary materials such as adhesives, paint and/or tape and exclude minor deviations from samples as well as damage or performance problems arising out of improper use or installation and/or maintenance contrary to Armacell’s then current recommendations.(f) The contract shall not constitute a sale by description or sample. These warranties are, as far as the law permits, in lieu of and exclude all other conditions warranties and terms whether expressed or implied in respect of the condition of the Products, their saleability or quality or fitness for any particular purpose. (g) Any guarantees are in addition to and do not affect your statutory rights.(h) Armacell shall not be liable for: (i) imperfect or defective Products caused by any inaccuracies in any drawing, bill of quantities or specification supplied by the Buyer; nor (ii) any defect in the Products arising out of the acts, omissions, negligence or default of the Buyer, its employees or agents including (but without prejudice to the generality of the foregoing) any failure by the Buyer to comply with any recommendations of Armacell as to storage and handling of the Products.

9. Damage, Shortages, Delay in Transit(a) No liability (whether in contract or for negligence or otherwise howso- ever) for loss of or damage to the Products occurring prior to delivery or for any claim that any item delivered pursuant to the contract is defective or is otherwise not in accordance with the contract (being a defect or loss, damage or non-compliance which would be obvious upon a reasonable inspection of the Products) or for non-delivery will attach to Armacell unless claims to that effect are notified in writing by the Buyer to Armacell (and in the case of claims for loss, damage or non-delivery with a copy to the carrier if Armacell’s own vehicles have not been used to deliver the Products): (i) within three days of delivery for loss, damage, defect or non- compliance with the contract; or (ii) within ten days of the date of the invoice for non-delivery.(b) In the event of a valid claim for loss, damage, or nondelivery,Armacell undertakes at its option either to repair, reprocess or replace the items concerned at its expense but shall not be under any further or other liability in connection with such non-delivery, loss or damage.(c) If the Buyer shall fail to give notice in accordance with 9(a) above the items delivered shall be deemed to be in all respects in accordance with the contract and without prejudice to earlier acceptance by the Buyer it shall be bound to accept and pay for the same accordingly and all claims in respect of non-delivery, loss, damage, defect or non- compliance shall (save as set out in 8 above) thereafter be wholly barred.

(d) If packaging is visibly damaged on delivery or there are delivery short- ages, the carrier’s delivery note must be signed accordingly.

10. Liability(a) The aggregate liability of Armacell (whether in contract or for negli- gence or breach of statutory duty or otherwise howsoever) to the Buyer for any loss or damage of whatsoever nature and howsoever caused shall be limited to and in no circumstances shall exceed the price of the Products the subject of the claim.(b) Armacell shall not be liable for any costs, claims, damages or expenses arising out of any tortious act or omission or any breach of contract or statutory duty calculated by reference to profits, income, production or accruals or loss of such profits, income, production or accruals or by reference to accrual of such costs, claims, damages or expenses on a time basis.(c) Nothing herein shall have the effect of excluding or restricting the liability of Armacell for death or personal injury resulting from its negligence in so far as the same is prohibited by United Kingdom statute.

11. Default or Insolvency of the Buyer If the Buyer shall be in breach of any of its obligations under the contract or if any distress or execution shall be levied on the Buyer’s property or assets or if the Buyer shall make or offer to make any arrangement or composition with his creditors or commit any act of bankruptcy or if any bankruptcy petition be presented against him or (if the Buyer is a compa-ny) if any resolution or petition to wind up such company shall be passed or presented or if a receiver, administrative receiver or administrator of the whole or any part of such company’s undertaking property or assets shall be appointed Armacell in its discretion and without prejudice to any other right or claim may by notice in writing determine wholly or in part any and every contract between Armacell and the Buyer or may (without prejudice to Armacell’s right subsequently to determine the contract for the same cause should it so decide) by notice in writing suspend delivery or any further deliveries (as the case may be) of Products until any default by the Buyer be remedied.

12. Rebates(a) Any rebates, including (without limitation) rebates by means of a discount on the price of the Products (“Rebate”) must be agreed in writing with Armacell and be subject to these Conditions of Sale.(b) In the event that Armacell has agreed a Rebate with the Buyer, the Buyer must within 4 weeks of the date of delivery of the Products write to Armacell detailing its entitlement to a Rebate and provide a copy of Armacell’s agreement to the Rebate (a “Rebate Claim”). (c) Provided that the Buyer has complied with the terms of clauses 12(a) and (b), Armacell will then calculate the Rebate due to the Buyer and will use its reasonable endeavors to provide a credit note to the Buyer for such sum within 4 weeks of the date of receipt by Armacell of the Rebate Claim. (d) In the event that the Buyer does not comply with the terms of clauses 12(a) and (b), the Buyer shall not be entitled to a Rebate payment from Armacell unless Armacell otherwise agrees in writing.

13. Tactical Support Arrangements(a) In circumstances where the Buyer is tendering for a large project or account which would require Armacell to supply it with a significant amount of the Products, Armacell and the Buyer may enter into a tactical support arrangement whereby they agree in writing to a specific discount provided that the Buyer (i) is successful with its tender; and (ii) demonstrates to Armacell’s satisfaction (in its absolute discretion) that the Products will be used solely for the purpose of that speci- fied project (“TSA Payment”). (b) In the event that Armacell has agreed a TSA Payment with the Buyer, the Buyer must within 4 weeks of the date of delivery of the Products write to Armacell detailing its entitlement to a TSA Payment and provide a copy of Armacell’s agreement to the TSA Payment (a “TSA Payment Claim”). (c) Provided that the Buyer has complied with the terms of clauses 13(a) and (b), Armacell will then calculate the TSA Payment due to the Buyer and will use its reasonable endeavors to provide a credit note to the Buyer for such sum within 4 weeks of the date of receipt by Armacell of the TSA Payment Claim. (d) In the event that the Buyer does not comply with the terms of clauses 13(a) and (b), the Buyer shall not be entitled to a TSA Payment from Armacell unless Armacell otherwise agrees in writing.

14. General(a) All Product dimensions and weights are approximate.(b) Each delivery of the Products shall constitute a separate contract.(c) Armacell reserves the right to make changes in the design and specifications of the Products.(d) In respect of any Products not appearing on the current Armacell product list from time to time, the Buyer must at the end of order provide complete details of such Products to Armacell. In respect of such products, additional terms and conditions may be agreed in writing between Armacell and the Buyer.(e) Armacell reserves the right to discontinue the production of items appearing in its current product list.(f) These Conditions of Sale and the orders accepted by Armacell pursuant there to contain the entire agreement between Armacell and the Buyer and there are no other obligations between Armacell and the Buyer.(g) No statement, description, information, warranty, condition or recom- mendation contained in any catalogue, price list, advertisement or communication or made verbally by any of Armacell’s agents or employees shall be construed to enlarge, vary or override in any way any of these conditions.(h) Armacell shall be entitled to delay or cancel delivery or to reduce the amount of Products delivered if and to the extent that it is prevented from or hindered in or delayed in manufacturing, obtaining or deliver- ing the Products by normal route or means of delivery through any circumstances beyond its control including (but not limited to) strikes, lock-outs, accidents, war, fire, reduction in or unavailability of power at manufacturing plant, breakdown of plant or machinery or shortage or unavailability of raw materials from normal sources of supply.(i) Save as provided for contracts may not be cancelled except by agreement in writing of both parties and upon the payment to Armacell of such amount as may be necessary to indemnify Armacell against all loss resulting from the said cancellation.(j) Armacell may assign the contract with the Buyer or sub-contract the whole or any part thereof to any person, firm or company.(k) A person who is not a party to the Contract has no right to enforce any of its terms under the Contracts (Rights of Third Parties) Act 1999.(l) All contracts of sale pursuant to these Conditions of Sale shall be governed by, and construed in accordance with English Law and shall be deemed to have been made in England and the Buyer and Armacell agree to submit to the non-exclusive jurisdiction of the English courts.

Armacell UK Ltd. · Mars Street · Oldham, Greater Manchester · OL9 6LY · Tel. +44 (0)161 287 7100 · Fax +44 (0)0161 633 2685 www.armacell.com/uk · [email protected] · Registration No. 3729805 · VAT Reg No G.B. 759 3872 74

For more information on Armacell visit www.barbourproductsearch.info

Page 48: Acoustic Product Catalogue...Arma-Chek R Barrier Non-Metallic Cladding with Barrier Performance Armaflex R Reducing Break-Out Noise with Closed Cell Protection Armaload Acoustic De-coupling

The Armaflex Assurance System - your peace-of-mind assurance that Armaflex is made to the strictest quality, technical performance and environmentally friendly standards.

Prevents Moisture Permeation Multi-layered closed wall cells provide a built-in vapour barrier which can’t be compromised by surface punc-tures or rips - this ensures the vapour barrier stays working for the lifetime of the insulation system.

Provides Long-Term Thermal PerformanceNon-wicking - No transmission of water vapour is possible through the insulation due to the closed cell nature of Armaflex. Moisture will not migrate through professionally installed Armaflex.

Long-Term Durability No fragile water vapour barrier - The built-in vapour barrier can’t be “damaged” during installation or over the lifetime of the insulation.

Avoids Thermal BridgingArmaflex is a seamless insulation system - these same technical properties provide a secure system.

Long-Term Energy EfficiencyBy minimising the ingress of water vapour into the insulation the multi-layered cells in Armaflex prevent the thermal conductivity from rising. Increased thermal conductivity can in the long term lead to increased energy costs and surface condensation.

Inhibits Growth of Mould• Minimises moisture permeation, the first require- ment for mould growth• Minimises the second requirement: No cellulosic vapour jacket, and the smooth surface doesn’t trap dust

Formaldehyde-FreeEnsures that Armaflex is a low-emitting product. It is also low VOC.

Support Requirements of Health & IAQ (Indoor-Air-Quality)

• Dust and Fibre-Free• Will not emit any particles or fibres - even when cut into shapes and fittings • No outgassing - CFC & HCFC free manufacturing process

Supervised Manufacturing & Technical ValuesFactory Mutual Approval Guide - guarantee consistent performance to published values by monitoring • Fire Performance (FM pipe chase test, Flammability test)

• Water Vapour Transmission• Thermal Conductivity

Supervised Quality StandardsISO Registration ensures that all Armacell manufactur-ing facilities consistently meet customer requirements . . . by managing all processes with ongoing quality assessments.

The Armaflex Assurance System

Armacell UK LimitedMars Street Oldham, Lancs. OL9 6LYTel. +44 (0)161 287 7100 · Fax +44 (0)0161 633 2685www.armacell.com/uk · [email protected]

All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropriate for the specific use intended by the recipient. For updates to this document please refer to our website www.armacell.com/uk.*MICROBAN is a registered trademark of Microban Products Company.

© Armacell UK Ltd. · Subject to alterations · Printed in UK · AC-000-0609-EN (UK,ZA,ROI)