*EUROVENT Certification *50mm double skins *Excellent casing insulation and strength *Flexible selection *Excellent Cooling Performance *Quiet Operation *Reliable and Durable 39XT Air-Handling Unit Air flow 2000200000m 3 /h

Upload: ngodieu

Post on 06-Feb-2018

254 views

Category:

Documents


1 download

TRANSCRIPT

*EUROVENT Certification *50mm double skins *Excellent casing insulation and strength *Flexible selection *Excellent Cooling Performance *Quiet Operation *Reliable and Durable

39XTAir-Handling Unit

Air flow 2000~200000m3/h

Carrier ChinaCarrier Corporation is a subsidiary of the United Technolo-gies Corp. (UTC), which ranks 123th in Fortune Top 500 in 2009 and has its operation in aerospace and building systems industries all over the world.

Carrier is the largest supplier of HVAC and refrigeration equipment around the world, and also a global leader to provide energy management and sustainable building services. Its products and sales cover China and other 170-plus countries. From the time our founder Dr. Carrier invented the first system of modern air conditioning in 1902, Carrier has been the world leader in the air conditioning industry, and up to now, holds several thousands of air-conditioning patented technologies as well as 11 R&D centers in China and other countreis. In 2009, Carrier ranked top in the industry with its sales volume of US $11.4 billion.

In 1987, Carrier established its first joint venture in Shanghai, China. Today, Carrier has more than 2,000 Chinese employees, and around the country, there are over 40 sales and after-sale service organizations to provide customers with quality products.

The world-class Carrier factory in China has a number of technically advanced production lines of units and compressors, manufacturing commercial and residential central air-conditioning units and air-end products. A wide range of products are able to meet diversified require-ments of different customers.

ContentsIdentification & DimensionAir VolumeFeatures Europe Standard (EUROVENT)Casing PropertiesSoftwareUnit OrientationQuick SelectionStandard ComponentsCoil ConnectionSteam Coil ConnectionFanFilterFilter Size SchedulePurification ClassificationElectric HeaterOthers

1

2456

789

11121617192021

39XT 2000~200000m3/h

01

Identification & Dimension

Air Volume

39XT 07 11

39XT

General rule of the height, width and length of a section or unit can be determined with the module concept:

Unit Type

Height Module

Width Module

Other Components

(1) Unit Height = Height Module × 100 + 104+ 100 (base)(2) Unit Width = Width Module × 100 +104

Example: 39XT 0711 07 Height Module Unit Height: 7 × 100 +104 +100 (base) = 904mm 11 Width Module Unit Width: 11 × 100 + 104 = 1,204mm

2002

Features

Unit panel inside

Quiet and vibration-free operation

High-performance coils

Treated with a special gap-filling glue, the inner wall is smooth, and free of cutting burr and welding marks. Panel sealing is more ensured.

All fan impellers and belts are subjected to static and dynamic balance calibrations, and overload tests before delivery.

All cooling and heating coils are composed of copper tubes and aluminum foils through mechanical expanders, and provided with a strong galvanized steel frame. The entire header is subjected to special anti-corrosive treatment after welding. Each coil is subjected to the reliability air pressure leak test at 2.8Mpa. Each coil is equipped with a vent valve and a drainage valve to ensure complete discharge. The entire coil is placed on a slide for easy movement.

Corrugated damper flexible to adjustManual or electric mode available. The corrugated linkage damper can be opened flexibly, and can also add an electric controller as required.

0303

The casing adopts a patented construction

High airtight construction, double-skin panel

Various filters available to meet different needs

Optional Stainless Steel Drain Pan

It can withstand severe weather, and possible wear and tear in operation, and avoid any possible damage in shipment or stacking casing. The casing and access door are of a patented double-skin structure to ensure that all performances reach internationally advanced level.

The high air-tightness of Carrier’s double-skin panel for air-handling units is from the special non-toxic and pollution-free gap-filling glue. This feature makes it not only applicable to general commercial air conditioning needs, but also meet stringent needs for industrial air conditioning and clean-room air conditioning.

Filters of various filtering levels are available ranging from low efficiency filters (Panel type, efficiency: G4), to medium efficiency filters (Bag type, efficiency: F8), and to high efficiency filters (H13).And some special filters such as activated carbon filters, cartridge filters and destatic filters can also be provided.

A standard drain pan may be constructed of stainless steel sheet, with 10mm thick insulation outside the drain pan. The drain pipe is arranged at the bottom of the drain pan to ensure complete drainage and side drainage. The inlet and outlet pipes of the drain pipe and coil are arranged on the same side.

High Efficiency Filter Bag Filter Panel Filter

04

Europe Standard (EUROVENT)

Max. Deflection refers to the maximum allowable elastic deflection of the unit at ±1000Pa.Withstand Max. Fan Pressure means that the unit will not suffer from permanent deformation at ±2500Pa.

Thermal Bridge Factor Kb=Tmin/Tair, where Tmin refers to the difference between temperature inside the unit and outer surface temperature of the unit, and Tair the difference between temperature inside the unit and ambient temperature.

The air leakage rate of the unit is measured at 400Pa internal negative pressure and 700Pa internal positive pressure.

EN1886: Europe standard for air-handling unit (39XT)

Mechanical Strength of Casing Thermal Bridge Factor Air Leakage Rate

Class TB1

Class TB2

Class TB3

Class TB4

Class TB5

0.75 Kb 1

0.6 Kb 0.75

0.45 Kb 0.6

0.3 Kb 0.45L1

L2

L3

l/sm2

(-400Pa)

0.15

0.44

1.32

l/sm2

(+700Pa)

0.22

0.63

1.90

Casing Class Casing Class

Withstand Max. Fan Pressure

Max. Deflection(mm.m-1)

No requirement No requirement

D1

D2

D3

4

10

Yes

Yes

Yes

Max. air leakage rateCasing air

leakage rate

Max. air leakage rate

39XT series unit is an air-handling unit for clean rooms designed with internationally up-to-date design, materials and technology, all technical parameters of which refer tovarious highest standards of European air handling units.

EUROVENT is a professional certification for ventilation and air conditioning of buildings for human comfort identified all over the world. It is awarded from EUROVENT certification company in France, which is one oft the most authoritative organization in the world.

EUROVENT Certification contains EN1886 and EN13053.

EN1886 is the standard for mechanical performance of air-handling unit, including Mechanical Strength, Cold Bridge Factor, Thermal Transmittance, Air Leakage Rate of Casing, Filter Bypass Rate and Acoustic Insulation of Casing.

EN13053 certification primarily targets machine performance testing to ensure that the actually measured values of air flow, air pressure, coil heating/cooling capacity, motor input power and octonary noise are superior to calculated values for selection procedures, i.e. the actual coil cooling capacity, heating capacity, air blow and air pressure are higher than the calculated values, but motor input power and noise are below the calculated values for selection proce-dures.

05

Excellent airtightnessThe casing is made up of panels, frame and sealing strips. The panels are connected accurately by adopting unique embedded abutting method. Type of sealing strips between the frame and the panels, and careful sealing design to all access panels and locations passing-through pipes ensure excellent air tightness of the unit,

Optimal thermal insulationBetween unit panels, a 50mm thick polyurethane foam insulation material is inserted, and even between aluminum frames are added polyurethane materials, with each junction subject to special heat insulation treatment. The units are ensured to have no condensation in a variety of damp conditions. The outer surface of the panels is treated with special spraying to ensure good fireproof and rust-preventive performance of the unit.

Robust casing strengthThe patented double-skin panel and joining-angle structure enable the units to maintain stable performance in all kinds of harsh environments and prevent the units from permanent deformation under the maximum design air pressure.

Casing properties

ZL03270350.3Patent No.:

Removable panels

Pipeline connection

Removable panels

Inside and outside of the panel are subjected to spraying treatment

Joining angles

07

Quick Selection

Unit Size

m3/h Area (m2)

39XT0608

39XT0609

39XT0711

39XT0811

39XT0912

39XT0913

39XT0914

39XT1015

39XT1117

39XT1317

39XT1418

39XT1420

39XT1621

39XT1822

39XT1825

39XT2025

39XT2125

39XT2226

39XT2328

39XT2333

39XT2532

39XT2832

39XT3132

39XT3438

39XT3841

39XT4444

39XT4750

2000

3000

4000

5000

6000

7000

8000

10000

12000

15000

18000

20000

25000

30000

32000

35000

40000

45000

50000

60000

73170

81081

89820

111240

132210

159480

198090

0.23

0.32

0.46

0.57

0.69

0.76

0.84

1.06

1.31

1.68

1.90

2.14

2.62

3.26

3.75

4.04

4.33

4.82

5.39

6.44

8.13

9.01

9.98

12.36

14.69

17.72

22.01

12.96

19.25

27.29

34.14

41.46

47.94

54.39

69.13

84.79

107.03

126.34

142.41

165.83

203.01

226.22

244.05

272.70

307.16

344.97

417.15*

470.33

513.83*

574.52*

668.53

812.74

1020.87

1297.04

10.61

16.03

23.18

29.02

35.46

41.32

47.35

60.56

65.95

83.28

99.39

114.02

143.03

175.65

197.13

212.48

237.86

268.70

299.37

365.29*

457.23

507.29

543.02*

625.96

759.88

932.70

1190.93

32.52*

46.15*

63.14

79.03

95.96

111.77

127.53

153.60

188.88

237.60

283.24

319.94

391.43*

469.86*

506.12*

564.12*

627.66*

693.83*

761.06*

880.6*

965.14*

1246.68*

1247.79*

1770.74*

2087.94*

2542.41*

3101.77*

30.6

36.2

61.8

29.2

97.5

107.8

118.1

151.5

206.7

241.6

280.8

317.1

363.1

442.7

533.0

595.5

624.5

672.5

738.0

898.4

704*322.5

804*322.5

1004*322.5

1004*322.5

1104*322.5

1204*480

1304*480

1404*480

1604*480

1604*480

1704*637

1904*637.5

2004*637.5

2104*795

2404*795

2404*795

2404*952.5

2504*952.5

2704*952.5

3204*952.5

3104*952.5

3104*952.5

3104*1267.5

3704*1267.5

4004*1582.5

4304*1582.5

4904*1582.5

704

704

804

904

1004

1004

1004

1104

1204

1404

1504

1504

1704

1904

1904

2104

2204

2304

2404

2404

2604

2904

3204

3504

3904

4504

4804

904

1004

1204

1204

1304

1404

1504

1604

1804

1804

1904

2104

2204

2304

2604

2604

2604

2704

2904

3404

3304

3304

3304

3904

4204

4504

5104

Cooling/Heating Coil Capacity(kW)

Air Volume Coil Face

Steam Coil Heating Capacity(kW)

Inside Dimension of

Damper39XT Dimensions

2R Heating 4R Heating 6R Heating 0.2MPa Hight Width(mm*mm)

1. The data of 2R coil heating capacity is under the standard condition. (Air temperature in is 15℃ db, water temperature in is 60℃) 2. The data of 4R coil cooling capacity is under the standard condition. (Air temperature in is 27℃ db/19.5℃ wb, water temperature in is 7℃) 3. The data of 6R coil cooling capacity is under the fresh air condition. (Air temperature in is 35℃ db/28℃ wb, water temperature in is 7℃) 4. The unit height does not include the damper on top and the base of 100mm (0608~2333) / 200mm (2532~4750) 5. The cooling and heating capacity of the coil in the table is just for your reference, the data with "*" means temperature difference of in/out is more than 5℃.

Please refer Carrier AHU selection software for detail information.

Note:

08

Standard Components

Note: The section with "*" is not available for 2532~4750 in the selection software, please contact Carrier sales office

No. Unit Section

Cooling Coil

Steam Humidifier

Fan

Combined MixingChamber

Attenuator

Plenum/Access

High EfficiencyFilter

Diagram Section Length (M: Module) Remark

Access section is recommended at upstream

May be installed directly in the coils and drain pan, no additional space needed

Four discharge configurations available

Access section is recommended at upstream

May be be installed together with the cold water coil if the cooling coil does not include a film humidifier and a drift eliminator

Refer to fan table

(0608~0912) 5M (0913~1317) 6M (1418~1621) 8M (1822~2025) 9M (2125~2333) 11M (2532~2832) 12M (3132~3438) 15M (3841~4750) 18M

Return/Mixing/Supply Chamber

1.Could be used as access section2.Could reduce the length of section suitably when the direction of in/out air is horizontal

Electrostatic/Bag/Combined Filter

3M/6M

3M、6M

5M or 6M;12M

Heating Coil

Steam Heating Coil

Electric Heating Coil

Film Humidifier*

Spray Humidifier*

Electric Humidifier

Energy Recovery*

6M(1 Level) 12M(2 Level)

(0608~0913) 10M (0914~1825) 12M (2025~2333) 18M (2532~2832) 26M (3132~3438) 32M (3841~4750) 38M

1.For 0608~2333, the section length is 5M with drift eliminator and 6M without drift eliminator2. For 2532~4750, the section length is 12M

Pay attention that the steam pressure could impact the heating capacity

Pay attention that the steam pressure could impact the humidifier capacity

Pay attention to the power stage of control

Could share the drift eliminator with cooling coil when it is installed next the coil.

Could be used as access section

The length can not be less than 5M, when it is used as access section.

Already include the access section at upstream

Pre-filter at upstream and access section at downstream are recommended

3M

3M

3M

3M

6M

6M

6M

9M

6M

(mm)

(mm)

(mm)

(mm)

09

Coil Connection

Supply/Return Water Conn ФC

Air Flow

Condensate Drain Conn

*MPT- Male Thread

Upper Coil Supply/Return Water Conn ФC

Lower Coil Supply/Return Water Conn ФC

Air Flow

MPT- Male Thread

Condensate Drain Conn

501-1/4 MPT 275E2

E1

D2

254

B72

726

100

D1

A

39XT

0608

0609

0711

0811

0912

0913

0914

1015

1117

1317

1418

1420

1621

1822

1825

A

804

804

904

1004

1104

1104

1104

1204

1304

1504

1604

1604

1804

2004

2004

B

357

421

472

599

647

647

647

774

824

1078

1142

1142

1332

1586

1586

øC

1-1/2" MPT

1-1/2" MPT

2" MPT

2" MPT

2-1/2" MPT

2-1/2" MPT

2-1/2" MPT

2-1/2" MPT

3" MPT

3" MPT

3" MPT

3" MPT

3" MPT

3" MPT

3" MPT

F

238

238

244

244

252

252

252

252

259

259

259

259

259

259

259

1-1/2" MPT

See above table

0608~1825

0608~1015

1117~1825

0608~0609

0711~0811

0912~1015

1117~1825

0608~1825

2Rows Hot Water

4Rows

4Rows

6Rows

6Rows

6Rows

6Rows

8Rows

55

91

84

63

70

77

84

84

øCED39XT Coil Row

138

174

181

201

194

187

180

226

39XT

39XT

2025

2125

2226

2328

2333

A

2204

2304

2404

2504

2504

B

951

1078

1205

1269

1269

øC

3" MPT

3" MPT

3" MPT

3" MPT

3" MPT

øF

259

259

259

259

259

1-1/2" MPT

See above table

øCEDCoil Row

138

206

206

226

2025~2333

2025~2333

2025~2333

2025~2333

2Rows Hot Water

4Rows

6Rows

8Rows

55

109

109

88

Cooling & Heating Coil(0608~2333)

10

Coil Connection

Figure 6:39XT 4444

Air Flow

Coil Model:570

Coil Model:670 Upper Coil Qty:2

Qty:2

Qty:2

Qty:2

Coil Model:670Lower Coil

Coil Model:570

Qty:1

Figure 3:39XT 3132

Air Flow

Coil Model:5100

Coil Model:7100 Upper Coil

Coil Model:7100 Lower Coil

Qty:1

Qty:1

Figure 5:39XT 3841

Air Flow

Coil Model:760 Upper Coil

Coil Model:770 Upper Coil

Coil Model:760Lower Coil

Coil Model:770Lower Coil

Qty:2

Qty:2

Qty:2

Qty:2

Figure 7:39XT 4750

Air Flow

Coil Model:580

Coil Model:680 Upper Coil

Coil Model:680 Upper Coil

Coil Model:680Lower Coil

Coil Model:680Lower Coil

Qty:2

Qty:2

Qty:2

Qty:2

Qty:2

Note:table and figure are just for your reference Both sides water connection for unit 3438~4750

Note: table and figure are just for your reference Both sides water connection for unit 3438~4750

Figure 1:39XT 2532

Air Flow

Coil Model:5100

Coil Model:5100

Qty:1

Qty:1

Figure 2:39XT 2832

Air Flow

Coil Model:5100

Coil Model:6100Lower Coil Qty:1

Qty:1Qty:1

Unit Size Total Qty of Coil Coil Model*Qty Coil Diameter*Qty

39XT 2532

39XT 2832

39XT 3132

39XT 3438

39XT 3841

39XT 4444

39XT 4750

2

2

2

4

4

6

6

5100*25100*1

6100*1

5100*1

7100*1

760*2

670*2

770*2

570*4

580*2

680*4

Φ89*4Φ89*2

Φ89*2

Φ89*8

Φ89*4

6100 Upper coil:Φ48*26100 Lower coil:Φ89*2

7100 Upper coil:Φ48*27100 Lower coil:Φ89*2

760*2760 Upper coil:Φ48*4760 Lower coil:Φ60*4

660*2660 Upper coil:Φ48*4660 Lower coil:Φ89*4

760 Upper coil:Φ48*4760 Lower coil:Φ89*4770 Upper coil:Φ48*4770 Lower coil:Φ89*4

670 Upper coil:Φ48*4670 Lower coil:Φ89*4

680 Upper coil:Φ48*8680 Lower coil:Φ89*8

Figu

re 2:

39C

BFI/3

9CBF

343

8,44

44,4

750

Air Flow

6-Φ48 both sides

Figu

re 1:

39C

BFI/3

9CBF

253

2,28

32,3

132

Air Flow

4-Φ48

Cooling Coil(2532~4750)

Unit Size Total Qty of Coil Coil Model*Qty Coil Diameter*Qty

39XT 2532

39XT 2832

39XT 3132

39XT 3438

39XT 3841

39XT 4444

39XT 4750

6

6

6

6

2

2

2

4100*15100*1

360*2460*4460*3470*3470*2570*4580*6

4100*2

5100*2

Φ48*4Φ48*2Φ48*2Φ48*4Φ48*4Φ48*8Φ48*6Φ48*6Φ48*4Φ48*8Φ48*12

Heating Coil(2532~4750)

Coil Model:6100 Upper Coil

Figure 4:39XT 3438

Air Flow

Coil Model:660 Upper Coil

Coil Model:760 Upper Coil

Coil Model:760Lower Coil

Coil Model:660Lower Coil

Qty:2

Qty:2

Qty:2

Qty:2

11

Note: the data above is just for your reference

Note: the data above is just for your reference

39XT

39XT

14

Steam Coil Connection

Supply/Return Water Conn ФC

Upper Coil Supply/Return Water Conn ФC

Lower Coil Supply/Return Water Conn ФC

Air Flow

E

D

D

E

100

BF

A

B15

0

39XT0608

39XT0609

39XT0711

39XT0811

39XT0912

39XT0913

39XT0914

39XT1015

39XT1117

B

347

347

418

560

631

631

631

738

738

øC

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

F

250

250

250

250

250

250

250

250

250

D

80

80

80

80

80

80

80

80

80

E

150

150

150

150

150

150

150

150

150

F

250

250

250

250

250

250

250

250

250

250

250

D

80

80

80

80

80

80

80

80

80

80

80

E

150

150

150

150

150

150

150

150

150

150

150

A

804

804

904

1004

1104

1104

1104

1204

1304

39XT1317

39XT1418

39XT1420

39XT1621

39XT1822

39XT1825

39XT2025

39XT2125

39XT2226

39XT2328

39XT2333

A

1504

1604

1604

1804

2004

2004

2204

2304

2404

2504

2504

B

489

520

520

631

738

738

844

844

844

884

884

øC

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

2" MPT

Connection Dimensions of unit 2532~4750 depend on the actual condition

Air Flow

E

100

FB

D (mm)

(mm)

12

Fan

Horizontal VerticalUnit Size Fan Model

Fan section length

39XT0608

39XT0609

39XT0711

39XT0811

39XT0912

39XT0913

39XT0914

39XT1015

39XT1117

39XT1317

39XT1418

39XT1420

39XT1621

39XT1822

39XT1825

39XT2025

39XT2125

39XT2226

39XT2328

39XT2333

(kW)Max. Motor Power Max. Motor Model

Y90

Y100

Y112

Y112

Y132

Y132

Y132

Y132

Y160

Y160

Y160

Y180

Y180

Y180

Y200

Y200

Y200

Y200

Y225

Y225

604

604

604

704

704

704

704

704

704

804

804

804

804

904

904

904

904

1104

904

1104

1104

1104

1104

1304

1304

1404

1304

1404

1404

1504

1404

1504

1504

1704

1504

1704

1704

1904

1704

1904

904

904

904

904

904

904

904

904

904

904

904

904

904

904

904

904

904

1104

904

1104

1104

1104

1104

1304

1304

1404

ADZ160

ADZ180

ADZ180

ADZ200

ADZ200

ADZ225

ADZ225

ADZ/RDZ250

ADZ/RDZ250

ADZ/RDZ280

ADZ/RDZ280

ADZ/RDZ315

ADZ/RDZ315

ADZ/RDZ355

ADZ/RDZ355

ADZ/RDZ400

ADZ/RDZ400

ADZ/RDZ450

ADZ/RDZ400

ADZ/RDZ450

ADZ/RDZ450

ADZ/RDZ500

ADZ/RDZ500

ADZ/RDZ560

ADZ/RDZ560

ADZ/RDZ630

ADZ/RDZ560

ADZ/RDZ630

ADZ/RDZ630

ADZ/RDZ710

ADZ/RDZ630

ADZ/RDZ710

ADZ/RDZ710

ADZ/RDZ800

ADZ/RDZ710

ADZ/RDZ800

ADZ/RDZ800

ADZ/RDZ900

ADZ/RDZ800

ADZ/RDZ900

1.5

2.2

3.7

3.7

5.5

5.5

7.5

7.5

11

15

15

18.5

18.5

18.5

30

30

30

30

37

45

Fan & Motor(0608~2333) (mm)

13

FHTFHB

36

Fan

Fan Arrangement- Horizontal Unit(0608-2333)

View A

Right Hand Left Hand

Right Hand Left Hand

View A

View B View B

Air Flow Air Flow

Air FlowAir Flow

UBF UBR

ETHF BHF UBF UBR

DAUnit Size Fan Model

39XT0608

39XT0609

39XT0711

39XT0811

39XT0912

39XT0913

39XT0914

39XT1015

39XT1117

39XT1317

39XT1418

39XT1420

39XT1621

39XT1822

39XT1825

39XT2025

39XT2125

39XT2226

39XT2328

39XT2333

ADZ160ADZ180ADZ180ADZ200ADZ200ADZ225ADZ225

ADZ/RDZ250ADZ/RDZ250ADZ/RDZ280ADZ/RDZ280ADZ/RDZ315ADZ/RDZ315ADZ/RDZ355ADZ/RDZ355ADZ/RDZ400ADZ/RDZ400ADZ/RDZ450ADZ/RDZ400ADZ/RDZ450ADZ/RDZ450ADZ/RDZ500ADZ/RDZ500ADZ/RDZ560ADZ/RDZ560ADZ/RDZ630ADZ/RDZ560ADZ/RDZ630ADZ/RDZ630ADZ/RDZ710ADZ/RDZ630ADZ/RDZ710ADZ/RDZ710ADZ/RDZ800ADZ/RDZ710ADZ/RDZ800ADZ/RDZ800ADZ/RDZ900ADZ/RDZ800ADZ/RDZ900

231.0 186.5 298.0 267.5 367.5 318.5 318.5 318.5 368.5 342.5 392.5 349.5 399.5 402.5 452.5 401.5 501.5 441.5 501.5 396.5 446.5 427.5 527.5 518.5 518.5 432.5 618.5 532.5 727.5 630.5 727.5 630.5 580.5 520.5 680.5 620.5 670.5 642.5 970.5 942.5

205.0 229.0 229.0 256.0 256.0 288.0 288.0 322.0 322.0 361.0 361.0 404.0 404.0 453.0 453.0 507.0 507.0 569.0 507.0 569.0 569.0 638.0 638.0 715.0 715.0 801.0 715.0 801.0 801.0 898.0 801.0 898.0 898.0

1007.0 898.0

1007.0 1007.0 1130.0 1007.0 1130.0

292.5 292.5 292.5 300.5 300.5 314.5 314.5 326.0 326.0 343.0 343.0 362.0 362.0 387.0 387.0 415.0 415.0 444.0 415.0 444.0 444.0 465.0 465.0 556.0 556.0 598.0 556.0 598.0 598.0 646.0 598.0 646.0 646.0 715.0 646.0 715.0 715.0 772.0 715.0 772.0

170.0 170.0 170.0 170.0 170.0 170.0 170.0 170.0 170.0 170.0 170.0 170.0 170.0 195.0 195.0 195.0 195.0 195.0 195.0 195.0 195.0 195.0 195.0 255.0 255.0 255.0 255.0 255.0 255.0 255.0 255.0 255.0 255.0 268.0 255.0 268.0 268.0 268.0 268.0 268.0

127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127127

199.0 224.0 224.0 233.0 233.0 270.0 270.0 259.0 259.0 308.0 308.0 295.0 295.0 317.0 317.0 347.0 347.0 375.0 347.0 375.0 375.0 397.0 397.0 428.0 428.0 471.0 428.0 471.0 471.0 518.0 471.0 518.0 518.0 574.0 518.0 574.0 574.0 631.0 574.0 631.0

(mm)

14

Fan

Fan Arrangement- Vertical Unit (0608~2333)

FHB

36View A

Right Hand Left Hand

Right Hand Left Hand

View A

View B View B

UBF UBR

A D ETHF BHF UBF UBR

Unit Size Fan Model

39XT0608

39XT0609

39XT0711

39XT0811

39XT0912

39XT0913

39XT0914

39XT1015

39XT1117

39XT1317

39XT1418

39XT1420

39XT1621

ADZ160ADZ180ADZ180ADZ200ADZ200ADZ225ADZ225

ADZ/RDZ250ADZ/RDZ250ADZ/RDZ280ADZ/RDZ280ADZ/RDZ315ADZ/RDZ315ADZ/RDZ355ADZ/RDZ355ADZ/RDZ400ADZ/RDZ400ADZ/RDZ450ADZ/RDZ400ADZ/RDZ450ADZ/RDZ450ADZ/RDZ500ADZ/RDZ500ADZ/RDZ560ADZ/RDZ560ADZ/RDZ630

231.0 186.5 298.0 267.5 367.5 318.5 318.5 318.5 368.5 342.5 392.5 349.5 399.5 402.5 452.5 401.5 501.5 441.5 501.5 396.5 446.5 427.5 527.5 518.5 518.5 432.5

205229229256256288288322322361361404404453453507507569507569569638638715715801

996.5996.5996.5

1004.51104.51118.51218.51230.01330.01347.01347.01366.01366.01391.01491.01519.01619.01648.01819.01848.01948.01969.01969.02060.02260.02302.0

874.0874.0874.0874.0974.0974.0

1074.01074.01174.01174.01174.01174.01174.01199.01299.01299.01399.01399.01599.01599.01699.01699.01699.01759.01959.01959.0

127127127127127127127127127127127127127127127127127127127127127127127127127127

199224224233233270270259259308308295295317317347347375347375375397397428428471

(mm)

15

39XT2532

39XT2832

39XT3132

39XT3438

39XT3841

39XT444439XT4750

Fan

Fan & Motor(2532~4750)

Unit Size Fan Model Max. Motor Power(kW) Max. Motor Model

Fan Section LengthTHF UBF

Fan Arrangement - Horizontal Unit (2532~4750)

A D E

THF UBF Unit Size Fan Model

Note: the datas in table are just for your reference

A Air Flow

Air Flow

View A

View B View B

View A

Right Hand Left Hand

Left HandRight Hand

36

UBF

39XT2532834

876.5876.5987

876.5987

11561156120812081347

39XT2832

39XT3132

39XT3438

39XT3841

39XT444439XT4750

(mm)

(mm)

16

Filter

The types of filters offered are as follows. 1" External High Velocity Filter 2" External Low Velocity Filter 1" Internal High Velocity Filter 2" Internal Low Velocity FilterInternal Primary Efficiency Bag Filter Internal Sub-High Efficiency Bag FilterPrimary & Medium Efficiency Filter Performance Efficiency: Primary Efficiency Panel Filter G3. Medium Efficiency Bag Filter F5

G3 (Panel)

Air

Fric

tion

Face Velocity

G4 (Panel)

Face Velocity

Air

Fric

tion

F5 (Bag)

Face Velocity

Air

Fric

tion

F6 (Bag)

Face Velocity

Air

Fric

tion

F7 (Bag)

Face Velocity

Air

Fric

tion

F8 (Bag)

Face Velocity

Air

Fric

tion

17

Filter Size Schedule

39XT

η=G3Unit Size External Panel Filter Cell Quantities

0608

0609

0711

0811

0912

0913

0914

1015

1117

1317

1418

1420

1621

1822

1825

2025

2125

2226

2328

2333

392×395

2

4

2

2

492×395

1

2

12

12

592×395

1

4

1

4

4

692×395

3

3

2

4

4

2

392×495

2

3

4

3

3

492×495

1

3

3

3

6

9

592×495

1

3

4

8

6

4

2

3

592×595

2

6

692×495

2

6

6

6

8

392×595

1

η=G3Unit Size Internal Panel Filter Cell Quantities

0608

0609

0711

0811

0912

0913

0914

1015

1117

1317

1418

1420

1621

1822

1825

2025

2125

2226

2328

2333

290×493

239XT 290×595

3

2

2

2

3

2

4

4

7

390×493

2

2

2

390×595

1

2

2

4

3

2

2

5

595×595

2

2

4

4

6

6

6

8

12

12

12

12

15

493×595

14

18

Filter Size Schedule

39XTUnit Size η=F5 Internal Bag Filter Cell Quantities

0608

0609

0711

0811

0912

0913

0914

1015

1117

1317

1418

1420

1621

1822

1825

2025

2125

2226

2328

2333

290×493

2

290×595

3

2

2

2

3

390×493

2

390×595

1

1

2

493×390

2

2

493×595 595×290

2

3

4

4

4

595×390

2

2

4

2

3

5

595×595

2

2

4

4

6

6

6

8

12

12

12

12

15

η=H11Unit Size High Efficiency Box Filter Cell Quantities

0608

0609

0711

0811

0912

0913

0914

1015

1117

1317

1418

1420

1621

1822

1825

2025

2125

2226

2328

2333

290×493

239XT 290×595

3

2

2

2

3

2

4

4

7

390×493

2

2

2

390×595

1

2

2

4

3

2

2

5

595×595

2

2

4

4

6

6

6

8

12

12

12

12

15

493×595

19

Filter Size Schedule

Unit Size Internal Panel Filter Cell Quantities

39XT2532

39XT2832

39XT3132

39XT3438

39XT3841

39XT4444

39XT4750

290×595

6

595×290

5

6

8

595×595

20

20

25

30

36

49

56

288×592

6

592×592

20

20

25

30

36

49

56

592×288

5

6

8

Internal Combine / Bag Filter Cell Quantities

Purification Classification

US Fed. Std. 209DPurification Level

US Fed. Std. 209E

VDI 2083Purification Level

Flow Pattern Turbulent Flow Transition Flow Laminar Flow

DIN EN 779First Level

DIN EN 779Second Level

DIN 24 183/EN 1822

DIN 24 183/EN 1822Third Level

100,000M6.5

10,000M5.5

1,000M4.5

100M3.5

10M2.5

1M1.5

0.1M0.5

09>08>07~0302~0101~5

6F5F4G

F7 F9H10

H10H12H13

H13

H12H13

H13 H14 H15 H16 H17

4 3 2 1 06 5

Filter Suffusion Rate (%)

20

Electric Heater

Electric Heater Selection

Max. Capacity of Single Pipe (W) (m 2) (kW)Unit Size1 Row Heater 2 Row Heater 3 Row HeaterFace Area

Note :1. Star connection is used in the wiring of electric heaters. Multi-group control is available, in which the capacity for each group is generally 30kW or less. The power supply is 3-phase 380V. 2. Minimum air velocity is 2m/s. 3. 3M module holds maximum of 3 row heater. 4. Capacity exceeding 3 row should choose two separated heaters in 6M module section.

power range power range(kW) power range(kW)

39XT060839XT060939XT071139XT081139XT091239XT091339XT091439XT101539XT111739XT131739XT141839XT142039XT162139XT182239XT182539XT202539XT212539XT222639XT232839XT233339XT253239XT283239XT313239XT343839XT384139XT444439XT4750

690 840 1140 1140 1290 1440 1590 1740 2040 2040 2200 2500 2650 2800 3250 3250 3250 3400 3700 4450 5380 5380 5380 6250 6820 7380 8510

0.21 0.25 0.34 0.49 0.65 0.72 0.80 0.99 1.29 1.56 1.83 2.08 2.55 3.07 3.56 4.00 4.21 4.63 5.29 6.36 6.33 7.24 8.15

10.56 12.66 16.03 19.98

〈5〈6〈8〈12〈14〈16〈18〈26〈30〈35〈40〈45〈48〈60〈70〈85〈90〈95〈105〈125〈145〈160〈175〈225〈285〈350〈455

5~106~128~16

12~2414~2816~3218~3626~5230~6035~7040~8045~9048~96

60~12070~14085~17090~18095~190

105~210125~250145~290160~320175~350225~450285~570350~700455~910

10~1510~1816~2424~3628~4232~4836~5452~7860~90

70~10580~12090~13596~144

120~180140~210170~255180~270190~285210~315250~375290~435320~480350~525450~675570~855

700~1050910~1365

No.

123456789101112131415161718192021222324252627

Unit Model

21

Others

1.Our company can help you select the best unit according to different requirements by our selection software.

2.The base requirements of the units: ● The base is designed according to the length and weight of units. ● Unit base shall be higher than the ground level in order to install condensate trap. See the figure below:

unit casing

Unit installation foundation

unit base

<1/2H

Note: H=the maximun negative pressure(mm)+50mm

3.Coil pressures: ● The working pressure of cooling coils and heating coils is 1.6MPa. ● The maximum pressure of steam coils is no more than 1.4MPa. 4.Preheat coils should be started or precautions taken before start to protect coil from freezing

operation with fresh air temperature below 0℃. 5.The fan outlet and discharge should be connected with canvas. 6.The water in the coil should be drawn off completely when the unit is stopped and below freezing

temperature. Antifreeze shall be poured into pipe if remaining water cannot be drawn off completely.

7.Insulation measures have been sufficiently considered and condensation in unit surface cannot happen in normal situation.

8.Check to keep enough space for daily maintenance. 9.The unit supply air temperature should be no more than 80℃ (when heating). If it is, please give

us clear indication, so we can adopt high temperature baring special motor. 10.Details should be illustrated in the order when customers have special requirements such as

effective air dampers, copper headers, stainless drainpans, film humidifiers, secondary high efficiency filters.

11.Details should be illustrated in the order when customers have requirements such as noise attenuators, secondary return air, purification, converter and heat recovery.

Steam pressure: (0.02~0.4) MPa.

E-39XT-1107-01-CHK

Reliability Product/system efficiency

Environmental protection refrigerant Reducing operating noise Indoor air quality Best air distribution