AlarmScout 961/962 (FM) AlarmScout 961/962 (FM) The AlarmScout 961/962 series are used to detect high or low level switch points in a broad range of viscous to light products. Switch points can be used for safety functions such as alarm or trip. Pulsed signal technology provides superior performance in applications suffering from foam or turbulence. Installation is easy and straightforward: no configuration or commissioning needed. The AlarmScout 961 has a tip sensitive set-point. The AlarmScout 962 offers 2 set-points on the same transducer, a tip sensitive set-point and a second set-point via a flow- through upper gap. The unit is used for level alarm or to control a pump in an auto fill/empty mode. The AlarmScout 961/962 has no moving parts and is equipped with advanced diagnostics that continuously check the trans- ducer and electronics, even in submerged condition. Both the AlarmScouts can be used in SIL-2 rated loops.

Upload: others

Post on 07-May-2020

21 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AlarmScout 961/962 (FM) - Honeywell...2000 Northfield Ct. Roswell, GA 30076 USA Phone: +1 770 475 1900 Email: enraf-us@honeywell.com Europe, Middle East and Africa Honeywell Enraf

AlarmScout 961/962 (FM)

AlarmScout 961/962 (FM)

The AlarmScout 961/962 series are used to detect high or low level switch points in a broad range of viscous to light products. Switch points can be used for safety functions such as alarm or trip. Pulsed signal technology provides superior performance in applications suffering from foam or turbulence. Installation is easy and straightforward: no configuration or commissioning needed. The AlarmScout 961 has a tip sensitive set-point. The AlarmScout 962 offers 2 set-points on the same transducer, a tip sensitive set-point and a second set-point via a flow-through upper gap. The unit is used for level alarm or to control a pump in an auto fill/empty mode. The AlarmScout 961/962 has no moving parts and is equipped with advanced diagnostics that continuously check the trans-ducer and electronics, even in submerged condition. Both the AlarmScouts can be used in SIL-2 rated loops.

Page 2: AlarmScout 961/962 (FM) - Honeywell...2000 Northfield Ct. Roswell, GA 30076 USA Phone: +1 770 475 1900 Email: enraf-us@honeywell.com Europe, Middle East and Africa Honeywell Enraf

Performance

Response time : 0.5 s typical

Repeatability : ± 2 mm (0.078”)

Ambient Temperature : -40 °C up to +70 °C (-40 °F up to +160 °F)

Electromagnetic Compatibility : Meets CE requirements (EN-61326: 1997 + A1 + A2) and NAMUR NE 21

Electronics

Input Voltage

- mA - version (Pos 5 = 5) : 2 wire loop powered , 11 - 35 V DC

- Relay - version (Pos 5 = 2 or 7) : 102 - 265 V AC 50/60 Hz or 18 - 32 V DC

Power consumption : < 3 Watt (relay version) – < 1 Watt (mA version)

Output

- mA - version (Pos 5 = 5) : 961: 8 mA (safe), 16 mA (alarm) ± 1 mA

962: 8 mA (safe), 12 mA (lower gap alarm), 16 mA (upper gap alarm) ± 1 mA

961/962: ≤ 3,6 or ≥ 22 mA error signal

- Relay - version (Pos 5 = 2 or 7) : 961: one 5 A DPDT relay

962: two 5 A SPDT relays

961/962: one 5 A SPDT malfunction relay

Time delay : 0,5 to 45 s adjustable (in addition to transducer response time)

Indication : LED’s for process alarm status, malfunction (error of transducer, electronics or electrical noise

interference) and wet/dry status of transducer (961 with relay only)

Selftest

- Automatic : Continuously verifies electronics, transducer and noise interference

- Manual : Via pushbutton for checking alarm output(s) and error output/function

Housing material : IP66, cast aluminium or cast stainless steel

Approvals: FM/CSA : Class I, Div. 1; Groups B, C & D

Class II, Div. 1; Groups E, F & G

Class III, NEMA Type 4X, T6

SIL (Safety Integrity Level) : Functional safety to SIL 2 in accordance to IEC 61508 – SFF > 90 %

Full FMEDA report and declaration sheets available at request

Electrical data : Ui = 28,4 V, li = 94 mA, Pi = 0,67 W (mA version)

Equivalent data : Ci = 10,4 nF (961) / Ci = 60 nF (962), Li = 400 µH (mA version)

Shock/Vibration : ANSI/ISA-S71.03 Class SA1 (shock), ANSI/ISA-S71.03 Class VC2 (vibration)

Net weight : Alu: 1 kg (2.2 lbs) – electronics only

SST: 2,5 kg (5.5 lbs) – electronics only

Transducer

Material : 316/316L SST (1.4401/1.4404)

Actuation length : From 2” up to 130”

Process temp. : -40 °C to +165 °C (-40 °F to +325 °F)

Max pressure : 103 bar @ +165 °C (1500 psi @ +325 °F)

Flanged models are downrated to the design pressure of the selected flange

Humidity : 0-99 %, non-condensing

PED : The PED directive 97/23/EC (pressure equipment directive).

Safety accessories per category IV module H1.

Technical specifications

Page 3: AlarmScout 961/962 (FM) - Honeywell...2000 Northfield Ct. Roswell, GA 30076 USA Phone: +1 770 475 1900 Email: enraf-us@honeywell.com Europe, Middle East and Africa Honeywell Enraf

1. Identification code for AlarmScout electronics

A COMPLETE CONFIGURATION CONSISTS OF 2 MODEL CODES 1. AlarmScout electronics2. AlarmScout transducer

Pos 1, 2, 3, 4 Instrument designationX 9 6 1 AlarmScout 961, electronics for single setpoint 9M1 transducersX 9 6 2 AlarmScout 962, electronics for dual setpoint 9M2 transducers

Pos 5, 6, 7 Input power5 0 A 24 V DC 2-wire loop powered electronics with current shift output2 D A 18 - 32 V DC line powered electronics with 5 A gold flash relays output7 D A 102 - 265 V AC line powered electronics with 5 A gold flash relays output

Pos 8 Accessories0 Blind housing cover1 Housing cover with glass window (only for aluminium housing: if Pos 11 = 0 or 1)

Pos 9 Mounting0 Integral mount electronics

Pos 10 Approvals1 FM explosion proof (only for loop powered electronics: if Pos 6 = 0)3 FM explosion proof (only for line powered electronics: if Pos 6 = D)

Pos 11 Housing / cable entry1 Cast aluminium housing with M20 x 1,5 cable entry (2 entries - one plugged)0 Cast aluminium housing with 3/4” NPT cable entry (2 entries - one plugged)3 Cast stainless steel with M20 x 1,5 cable entry (2 entries - one plugged)2 Cast stainless steel with 3/4” NPT cable entry (2 entries - one plugged)

X 9 6 1 7 D A 0 0 3 1 Typical identification code Typical identification code

X 9 6 A 0 Your identification code

2. Identification code for AlarmScout transducer

Pos 1, 2, 3, 4 Instrument designationX 9 A 1 AlarmScout 961, transducer with single setpointX 9 A 2 AlarmScout 962, transducer with dual setpoints

Pos 5 Transducer materialsA 316/316L (1.4401/1.4404) stainless steel

Pos 6, 7 Process connection Threaded1 1 3/4” NPT ANSI Flanges2 3 1” 150 lbs ANSI RF 2 4 1” 300 lbs ANSI RF 4 3 2” 150 lbs ANSI RF 4 4 2” 300 lbs ANSI RF

Pos 8 Sensor typeA Standard sensor: min -40 °C / max + 165 °C (-40 °F / +325 °F)

Pos 9 , 10, 11 Actuation length (see dimensional drawing)0 0 2 Minimum length = 2 inch (only if Pos 4 = 1)0 0 6 Minimum actuation length “A” = 6 inch (see dim. drawing 962) (only if Pos 4 = 2)1 3 0 Maximum length = 130 inch

X 9 A 1 A 1 1 A 0 6 0 Typical identification code Typical identification code

X 9 A A A Your identification code

NOTE: consult factory if CSA approval is required.

Page 4: AlarmScout 961/962 (FM) - Honeywell...2000 Northfield Ct. Roswell, GA 30076 USA Phone: +1 770 475 1900 Email: enraf-us@honeywell.com Europe, Middle East and Africa Honeywell Enraf

EN-12-06-ENGAPRIL 2012© 2012 Honeywell International Inc.

For More InformationTo learn more about Honeywell Enraf’ssolutions, contact your Honeywell Enraf account manager or visit www.honeywellenraf.com

AmericasHoneywell Enraf Americas, Inc.2000 Northfield Ct.Roswell, GA 30076 USAPhone: +1 770 475 1900Email: [email protected]

Europe, Middle East and AfricaHoneywell EnrafDelftechpark 392628 XJ DelftThe NetherlandsPhone: +31 (0)15 2701 100Email: [email protected]

Asia PacificHoneywell Pte Ltd.17 Changi Business Park Central 1Singapore 486073Phone: +65 6355 2828Email: [email protected]

Dimensional drawing

961 - Threaded connection 961 - Flanged connection

102(4)

102(4)

113 (4.43) without window123 (4.85) with window

113 (4.43) without window123 (4.85) with window

Actuation lengthfor NPT connection

Actuation lengthActuation

lengthfor BSP

connection

6 (0.25)

6 (0.25)

Ø 22,9 (0.90)

Ø 22,9 (0.90)

46 (1.8) Typical60 (2.35) Typical

NOTE: all dimensions in mm (inch) min actuation length between “A” and “B” = 8 cm min length for “B” = 7 cm allow 200 mm (8”) clearance for cover removal anchor sensor for lengths > 80 inch

962 - Threaded connection 962 - Flanged connection

102(4)

102(4)

113 (4.43) without window123 (4.85) with window

113 (4.43) without window123 (4.85) with window

Actuation length “A”for NPT connection

Actuation length “A”

Actuation length “B”

Actuation length “B” for BSP connection

Actuation length “A” for BSPconnection

6 (0.25)

6 (0.25)

Ø 22,9 (0.90)Ø 22,9 (0.90)

46 (1.8) Typical60 (2.35) Typical

Actuation length “B” for NPT

cable entry (both sides)(see position 11 of model code)