Stationary NiCd battery sizing
Visit our website alcad.com V4.4 06/07This document becomes contractual only after written confirmation
Date : 06/01/2011
Battery proposalProposed battery 1 x 96 x MC110P
Electrical data Rated capacity 110 AhFast charge voltage 139.20 VFloating charge voltage 134.40 VFinal voltage/cell 1.000 VShort-circuit current 1862 ATopping-up interval 4.0 Years
Physical data Battery weight 693.1 kg
Technical specificationsSizing method IEEE I
Voltage window Minimum system voltage 96.00 VMaximum system voltage 140.00 VNominal system voltage 125.00 V
Charge method Dual rate
Load profile Current / Power Time(hh:mm:ss)1 40.00 A 0:59:002 140.00 A 0:01:00
Options Nominal temperature 20 °CMinimum temperature 5 °CMaximum temperature 40 °CDesign margin 1Aging factor 1
![Page 2: ALCAD Battery Size Calculation](https://reader036.vdocument.in/reader036/viewer/2022081715/552072a24a795976718b477d/html5/thumbnails/2.jpg)
Stationary NiCd battery sizingLoad profile
Visit our website alcad.com V4.4 06/07This document becomes contractual only after written confirmation
Date : 06/01/2011
Amperes
00mn 10mn 20mn 30mn 40mn 50mn 60mn0
20
40
60
80
100
120
140
![Page 3: ALCAD Battery Size Calculation](https://reader036.vdocument.in/reader036/viewer/2022081715/552072a24a795976718b477d/html5/thumbnails/3.jpg)
Battery calculation worksheetIEEE 1115
Visit our website alcad.com V4.4 06/07This document becomes contractual only after written confirmation
Date : 06/01/2011
: MC : 96 : 1.000 V : 20.0°C : 5.0°C : 40.0°C
RangeNo. of cellsFinal voltage/cellNominal temperatureMinimum temperatureMaximum temperature
(1)Period
(2)Load
(Amperes)
(3)Changes
inLoad
(Amperes)
(4)Duration
ofPeriod
(minutes)
(5)Endof
Section(minutes)
(6)Kt
Factor *
(7)Temp
DeratingFactor
(8)RequiredSection
Size(3)x(6)x(7)=Rated Ah
Section 1 - First 1 Periods Only - If A2 > A1, go to Section 2 - Yes
Section 2 - First 2 Periods Only - If A3 > A2, go to Section 3 - No
1 A1=40.00 A1-0=40.00 M1=59.00 t=M1+M2=60.00 1.34 1.13 60.26
2 A2=140.00 A2-A1=100.00 M2=1.00 t=M2=1.00 0.37 1.23 45.91
Total 106.17
Random Equipment Load Only (if needed)
R AR= AR-0= MR= t=MR= 0.00(*) In this calculation, constant potential charging effects are included in our Kt factors
Maximum Section Size 106.17 + Random Size 0.00 = Uncorrected Size 106.17Uncorrected Size 106.17 x Design Margin 1.00 x Aging Factor 1.00 = 106.17When the cell size is greater than a standard cell size, the next larger cell is required.The required cell size is 106.17 Amperes-hours. Therefore cell MC110P is required