MARKET APPLICATION www.airolite.com AMCA 550 Test Method for High Velocity Wind-Driven Rain Resistant Louvers Did you know that, if located in the Hurricane Prone Region, all intake and exhaust louvers must comply with AMCA 550 (Test Method for High Velocity Wind Driven Rain Resistant Louvers) per the International Mechanical Code versions 2012 and 2015? The AMCA 550 test standard simulates external wind speeds up to 110 MPH with an external rainfall rate of 8.8 in. per hour. To pass AMCA 550, no more than 1% of the total sprayed water volume may penetrate the louver. If your state has adopted International Building Code 2012 or 2015, now is the time to ensure that all intake and exhaust louver specifications call for an AMCA 550 Listed louver, if located in the Hurricane Prone Region. HAWAII US Virgin Islands Guam Puerto Rico U.S. States or Territories Impacted In Part Or Whole By The Hurricane Prone Region (IBC Adoption As Of May 2016) Building code adoptions and interpretations may vary based on local municipality requirements. Reference local building code for actual requirements. Map as shown above is as interpreted by Airolite based on IBC 2012 figure 1609A and/or IBC 2015 figure 1609.3(1). Key IBC 2012/2015 IBC 2009 or prior Hurricane Prone Region

Upload: lambao

Post on 08-May-2018

228 views

Category:

Documents


7 download

TRANSCRIPT

MARKET APPLICATION

www.airolite.com

AMCA 550 Test Method for High Velocity Wind-Driven Rain Resistant Louvers

Did you know that, if located in the Hurricane Prone

Region, all intake and exhaust louvers must comply

with AMCA 550 (Test Method for High Velocity Wind

Driven Rain Resistant Louvers) per the International

Mechanical Code versions 2012 and 2015? The AMCA

550 test standard simulates external wind speeds up

to 110 MPH with an external rainfall rate of 8.8 in.

per hour. To pass AMCA 550, no more than 1% of the

total sprayed water volume may penetrate the louver.

If your state has adopted International Building Code

2012 or 2015, now is the time to ensure that all intake

and exhaust louver specifications call for an AMCA 550

Listed louver, if located in the Hurricane Prone Region.

HAWAII

US Virgin IslandsGuamPuerto Rico

U.S. States or Territories Impacted In Part Or Whole By The Hurricane Prone Region (IBC Adoption As Of May 2016)

Building code adoptions and interpretations may vary based on local municipality requirements. Reference local building code for actual requirements.

Map as shown above is as interpreted by Airolite based on IBC 2012 figure 1609A and/or IBC 2015 figure 1609.3(1).

Key

IBC 2012/2015IBC 2009 or prior

Hurricane Prone Region

Airolite AMCA 550 Market Application.indd 1 9/23/2016 9:21:53 AM

MARKET APPLICATION

The Airolite Company, LLC

PO Box 410 phone 715.841.8757 Schofield, WI 54476 fax 715.841.8773

www.airolite.comCopyright © 2016 The Airolite Company, LLC September 2016

For more information on the Hurricane Prone Region or louver requirements in the Hurricane Prone Region please contact your local Airolite representative.

Louver SelectionAirolite offers a complete line of AMCA 550 Listed louvers, ranging from high performance

vertical blade products, dual-module horizontal front/vertical rear louvers and combination

louver-dampers that will not only meet the function required, but the form desired.

SCV501MD• 5-inch frame depth• Vertical blades• 54% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified - Air Performance, Water Penetration and

Wind Driven Rain• AMCA 540 and 550 Listed

SCV660MD• 6-inch frame depth• Vertical blades• 46% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified - Air Performance, Water Penetration and

Wind Driven Rain• AMCA 540 and 550 Listed

SCC901• 9-inch frame depth• Horizontal front blade/vertical rear blade• 54% free area• AMCA 500-L Certified - Air Performance, Water Penetration and

Wind Driven Rain• AMCA 540 and 550 Listed

SCC901MD• 9-inch frame depth• Horizontal front blades/vertical rear blades• 54% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified - Air Performance, Water Penetration and

Wind Driven Rain• AMCA 540 and 550 Listed

K8206AMD• 6-inch frame depth• Horizontal blade combination

louver/damper• 48% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified - Air Performance, Water Penetration• AMCA 540 and 550 Listed - AMCA 550 with dampers in fully

closed position

SCH601MD with VCD-40• 6-inch louver frame depth• Horizontal blade louver with factory

attached control damper• 45% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified - Air Performance, Water Penetration and

Wind Driven Rain• AMCA 540 and 550 Listed - AMCA 550 with dampers in fully

closed position