22 40 00-1

SECTION224000PLUMBINGFIXTURES

PART1PARTONE:GENERAL

1.1 SectionIncludes

A. CommercialLavatories.

B. CommercialServiceBasins.

C. CommercialServiceSinks.

D. ClinicSinks.

E. PlasterInterceptors.

F. ScrubSinks.

G. Commercial,Vitreous-ChinaWaterClosets.

H. ResidentialWaterClosets.

I. ToiletSeats.

J. CommercialUrinals.

K. WaterlessUrinals.

L. CommercialShowers.

M. CommercialLavatoryFaucets.

N. SinkFaucets.

O. CommercialandResidentialShowerFaucets.

P. BedpanWashers.

Q. FaucetSupplyFittings.

R. SinkandLavatoryWasteFittings.

S. UrinalFlushometerValves.

T. WaterClosetFlushometerValves.

U. WaterClosetWasteCarriers.

22 40 00-2

V. SupportFixtures.

1.2 RelatedSections:

A. Section230500-CommonWorkResultsforHVAC.

B. Section221000-PlumbingPiping.

C. Section221426.13-RoofDrains.

D. Section-.

E. Section401000-GasandVaporProcessPiping.

1.3 References

A. AmericanSocietyofMechanicalEngineers(ASME):1. ASMEA112.6.1M-SupportsforOff-the-FloorPlumbingFixturesforPublic

Use.2. ASMEA112.6.7SanitaryFloorSinks3. ASMEA112.18.1/CSAB125.1-PlumbingSupplyFittings.4. ASMEA112.18.2/CSAB125.2-PlumbingWasteFittings.5. ASMEA112.18.6/CSAB125.6-FlexibleWaterConnectors.6. ASMEA112.19.1/CSAB45.2-EnameledCastIronandEnameledSteel

PlumbingFixtures.7. ASMEA112.19.2/CSAB45.1-VitreousChinaPlumbingFixturesandHydraulic

RequirementsforWaterClosetsandUrinals.8. ASMEA112.19.3/CSAB45.4-StainlessSteelPlumbingFixtures(Designedfor

ResidentialUse).9. ASMEA112.19.5/CSAB45.15-FlushValvesandSpudsforWaterClosets,

Urinals,andTanks.10. ASTMA1045StandardSpecificationforFlexiblePoly(VinylChloride)(PVC)

GasketsusedinConnectionofVitreousChinaPlumbingFixturestoSanitaryDrainageSystems.

11. ASMEA112.4.3.-PlasticFittingsforConnectingWaterClosetstotheSanitaryDrainageSystem.

12. ASMEB1.20.1-PipeThreads,GeneralPurpose,Inch.

B. AmericanSocietyofSafetyEngineers(ASSE):1. ASSE1016/ASMEA112.1016/CSA125.16-PerformanceRequirementsfor

AutomaticCompensatingValvesforIndividualShowersandTub/ShowersCombinations.

2. ASSE1037/ASMEA112.1037/CSAB125.37-PerformanceRequirementsforPressurizedFlushingDevicesforPlumbingFixtures.

C. ASTMInternational(ASTM):1. ASTMA1045StandardSpecificationforFlexiblePoly(VinylChloride)(PVC)

22 40 00-3

GasketsusedinConnectionofVitreousChinaPlumbingFixturestoSanitaryDrainageSystems.

D. InternationalCodeCounsel:1. ICC/ANSIA117.1-AccessibleandUsableBuildingsandFacilities.

E. NationalScienceFoundation:1. NSF61-DrinkingWaterSystemComponents-HealthEffects.

F. SafeDrinkingWaterAct:1. Section1417(d)oftheSafeDrinkingWaterAct

G. PlumbingandDrainageInstitute:1. PDI-WH201-WaterHammerArresters.

1.4 Submittals

A. SubmitunderprovisionsofSection013000-AdministrativeRequirements.

B. ProductData:Eachfixturetype.1. Includedimensions,finishes,constructioninformation,capacities,operation

instructionsandaccessories.2. Control,signalandpowerwiringdiagrams.

C. Maintenancedataforallproducts.1. Repairkitinformationforallfixtures.

1.5 QualityAssurance

A. ManufacturerQualifications:1. Minimum5yearsmanufacturingsimilarproducts.

B. InstallerQualifications:1. Minimum2yearsinstallingsimilarproducts.2. Installer'sresponsibilities:

a. Design,fabrication,andinstallationforfixturesandconnections.b. Professionalengineeringservicestoassumeengineeringresponsibility.

1) Workingplans.2) Calculations.3) Fieldtestreport.

C. RegulatoryComplianceRequirements:1. Utilitycompanysupplyingthewater.

a. Tappingofwatermains.b. Backflowprevention.

2. Authoritieshavingjurisdiction:Materials,installation,andtesting.

1.6 Delivery,Storage,andHandling

22 40 00-4

A. Deliverandstoreproductsinmanufacturer'sunopenedpackagingbearingthebrandnameandmanufacturer'sidentificationuntilreadyforinstallation.1. Protectinternalparts,valveends,andspecialtiesagainstcorrosion,dirt,and

damage.2. Storevalvessetinclosedposition.3. Storage:

a. Indoors:Higherthanambientdewpointtemperature.b. Outdoors:Watertightenclosuresoffground.

B. Handling:Complywithmanufacturer'srecommendations.Avoiddamagingcomponents.1. LargeValves:Operatinghandlesorstemsarenotriggingpointsforslings.

1.7 ProjectConditions

A. InterruptionofFire-SuppressionWater-ServicePiping:1. Arrangetemporarywater-distributionservice.2. NotifyOwnerorOwner'srepresentativenofewerthantwobusinessdaysin

advanceofproposedinterruptionofservice.a. Proceeduponwrittenpermission.

PART2PARTTWO:PRODUCTS

2.1 Manufacturers

A. InaccordancewithInteriorDesignspecification

2.2 CommercialLavatories

A. Enameled,CastIronCounterMountedLavatory:Oval,self-rimming.

B. VitreousChinaCounterMountedLavatory:Ovalorround,self-rimming.

C. VitreousChinaUndercounterMountedLavatory:Oval.

D. Enameled,CastIronWallMountedLavatory:Rectangular.

E. VitreousChinaWall-MountedLavatory:1. LavatoryAttributes:

a. Standard:ASMEA112.19.2/CSAB45.1.b. Faucet-HolePunching:

1) Onehole.2) Threeholes,4-inch(102-mm)centers.3) Threeholes,8-inch(203-mm)centers.

c. Faucet-HoleLocation:1) Top.2) OnCountertop.

d. Color:______.

22 40 00-5

e. MountingMaterial:1) Sealant.2) Undercountermountingkit.3) Wallbracket.4) ChairCarrier(wheelchairaccessible).

f. SupportFixture:ASMEA112.6.1M,TypeII,lavatorycarrier.1) Includerectangular,steeluprights.

g. Faucet:______.

F. SecurityVitreous-ChinaWallMountedLavatories:1. LavatoryAttributes:

a. Standard:ASMEA112.19.2/CSAB45.1.b. Material:Vitreouschina.c. Bowl:Ovalorrectangularbowl,soapdepression,andwallbracket.d. SupplyValves:Factory-installedpush-button,self-closing,chrome-

platedbrassfaucets;Hot-andCold-Water.e. Drain:GridwithNPS1-1/2(DN40)tailpiece.

2. WasteFittings:ASMEA112.18.2/CSAB125.2.a. TrapNPS1-1/4(DN32)minimumwaste.

3. SupportFixture:ASMEA112.6.1M,TypeIIlavatorycarrier.4. SupportFixture:ASMEA112.6.1M,TypeIIIlavatorycarrier.

2.3 CommercialServiceBasins

A. ServiceBasin:Plastic,floormounted.1. Mounting:Onfloorandflushtowall.2. ServiceBasinAttributes:

a. Standard:CSAB45.5/IAPMOZ124.b. Material:Castpolymer.c. NominalSize:

1) 24by24by10inches(610by915mmby255mm).2) 36by24by10inches(915by915by255mm).

d. TilingFlange:1) Ononeside.2) Ontwosides.3) Onthreesides.

e. RimGuard:Ontopsurfaces.1) Front.2) All.

f. Color:______.g. Drain:WithGrid

1) NPS2(DN50).2) NPS3(DN80).

2.4 CommercialServiceSinks

22 40 00-6

A. ServiceSinkwithBack:Enameled,castiron,trapstandardmounted

B. ServiceSinkwithBack:Vitreouschina,trapstandardmounted.

C. ServiceSinkwithFrontApronandraisedBack:Enameled,castiron,floormounted.a. ServiceSinkAttributes:b. Fixture:

1) Standard:ASMEA112.19.1/CSAB45.2.2) Back:

a) Twofaucetholes.b) Plain.

c. NominalSize:1) 22by18inches(560by457mm).2) 24by20inches(610by508mm).3) 28by28inches

d. Color:White.e. Mounting:P-trapstandardwithgridstrainerinlet,cleanout,andfloor

flange.1) NPS2(DN50).2) NPS3(DN80).

f. RimGuard:Onfrontandsides.

2.5 ClinicSinks

A. Vitreous-china,flushing-rim,Wall-MountedClinicSinks:a. Outlet:Back.b. Blowouttype.c. NominalSize:22by19inches(559by483mm).

B. Vitreous-china,flushing-rim,Floor-MountedClinicSinks:a. Outlet:Bottom.

1) NPS4(DN100).2) NPS3(DN80).

b. Siphon-jettype.c. NominalSize:27by20inches(685by510mm).

2. ClinicSinkAttributes:a. Standard:ASMEA112.19.2/CSAB45.1.b. Color:White.c. RimGuard:Stainlesssteel,onfront.

2.6 SolidsInterceptors

A. Basis-of-Design:1. Removablecover:Cast-ironorsteelbody.

a. Acid-resistant-enameledcoatinginteriorandexterior.b. MetalScreenorstrainer:Removable,corrosion-resistantmetal.

22 40 00-7

1) Inletandoutlet:a) NPS1-1/2(DN40).b) NPS2(DN50).

2.7 ScrubSinks

A. VitreousChina,Wall-Mounted,ScrubSinks:1. Standard:ASMEA112.19.2/CSAB45.1.2. NominalSize:Backledge,singlefaucethole.

a. 28by22inches(710by560mm).3. Color:White.4. Drain:Grid,NPS1-1/2(DN40).5. Faucet:,Model______.6. SupplyFittings:Model______.7. WasteFittings:Model______.8. Support:ASMEA112.6.1M,TypeIIIsinkcarrier.

2.8 Commercial,Vitreous-ChinaWaterClosets

A. Commercial:Floor-Mounted,Bottom-outlet,TopSpud:1. Basis-of-Design:

a. StandardHeight.b. ADAHeight.c. StandardHeightwitha14inch(356mm)roughin.

2. FlushometerValve:a. Manual.b. ManualPiston.c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

B. Commercial:Floor-Mounted,Bottom-Outlet,Child's:1. Basis-of-Design:2. FlushometerValve:

a. Manual.b. ManualPiston.c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10-yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

C. Commercial:Wall-Mounted,TopSpud,Accessible:1. Basis-of-Design:

22 40 00-8

2. FlushometerValve:a. Manual.b. ManualPiston.c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10-yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

D. Commercial:Floor-Mounted,BackOutlet,TopSpud:1. Basis-of-Design:2. FlushometerValve:

a. Manual.b. ManualPiston.c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10-yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

E. Commercial:Wall-Mounted,Blowout,BackSpud,Accessible:1. Basis-of-Design:2. FlushometerValve:3. Support;StandardAdjustableBlowoutStyleWaterClosetCarriers:

a. HorizontalWasteFitting:b. VerticalWasteFitting:

F. Commercial:Wall-Mounted,Blowout,TopSpud,Accessible:1. Basis-of-Design:2. FlushometerValve:

a. Manual.b. BatteryPoweredDiaphragm.c. Hardwireddiaphragminwallsensor.d. Hardwireddiaphragmsidemountedsensor.

3. Support;StandardAdjustableBlowoutStyleWaterClosetCarriers:a. HorizontalWasteFitting:b. VerticalWasteFitting:

G. Healthcare:Floor-Mounted,BottomOutlet,toporBackSpud.Accessible:1. Basis-of-Design:

a. Standardheight.b. AdaHeight.

2. FlushometerValve:a. Manual.b. ManualPiston.

22 40 00-9

c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10-yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

H. Healthcare:Floor-Mounted,BackOutlet,BackorTopSpud,Accessible:1. Basis-of-Design:2. FlushometerValve:

a. Manual.b. ManualPiston.c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10-yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

3. SupportWasteCarriers:

I. Healthcare:Wall-Mounted,ToporBackSpud,Accessible:1. Basis-of-Design:2. FlushometerValve:

a. Manual.b. ManualPiston.c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

3. Support:HighPerformance,AdjustableSiphonJetWaterClosetCarriers:a. HorizontalWasteFitting:b. VerticalWasteFitting:

J. Commercial:Floor-Mounted,BottomOutlet,BackSpud:1. Basis-of-Design:

a. Standardheight.b. ADAHeight.

2. FlushometerValve:a. Manual.b. BatteryPoweredDiaphragm.c. Hardwireddiaphragminwallsensor.

K. Commercial:Wall-Mounted,BackSpud,Accessible:1. Basis-of-Design:2. FlushometerValve:

a. Manual.

22 40 00-10

b. BatteryPoweredDiaphragm.c. Hardwireddiaphragminwallsensor.

3. Support:HighPerformance,AdjustableSiphonJetWaterClosetCarriers.a. HorizontalWasteFitting:b. VerticalWasteFitting:c. Bariatric,AdjustableSiphonJetWaterClosetCarriers:

1) HorizontalWasteFitting:d. VerticalWasteFitting:

L. Security:Floor-Mounted,BackOutlet,Blowout:1. Basis-of-Design:2. FlushometerValve:3. SupportWasteCarrier:

M. Security:Floor-Mounted,BackOutlet,SiphonJet,TopSpud:1. Basis-of-Design:2. FlushometerValve:3. SupportWasteCarrier:4. Vitreous-ChinaWaterClosetAttributes:

a. Standards:ASMEA112.19.2/CSAB45.1andASMEA112.19.5.b. Material:Vitreouschina.c. Type:Siphonjet.d. Reversetrap.e. Style:Flushometervalve.f. Height:

1) Standard.2) Child.3) Handicapped/elderly,complyingwithICC/ANSIA117.1.

g. RimContour:1) Elongated.2) Modifiedelongated.3) Elongatedwithbedpanlugsorslots.4) Elongatedwithintegraltrapandcontouredseat.5) Regular.

h. WaterConsumption:1) 1.28gal.(4.8L)2) 1.6gal.(6L)perflush.

i. SpudSizeandLocation:NPS1-1/2(DN40).1) Back.2) Top.

j. Color:__.k. Bowl-to-DrainConnectingFitting:ASTMA1045orASMEA112.4.3.l. ToiletSeat:

1) TypeA(residential),Shape3(elongatedrim),openfront,without

22 40 00-11

cover,andshapedtomatchbowl.

2.9 ResidentialWaterClosets

A. Floor-mounted,FloorOutlet,Close-Coupled(GravityTank),VitreousChina:1. Basis-of-Design:

B. Floor-mounted,FloorOutlet,CloseCoupled(FlushometerTank),VitreousChina:1. PressureAssistToilets,1.1-Gal./Flush(3.8-L/Flush)WaterClosets:

a. Basis-of-Design:2. PressureAssistToilets,1.6/1.1-Gal./Flush(6/3.8-L/Flush)DualFlushWater

Closets:a. Basis-of-Design:

3. PressureAssistToilet,1.6-Gal./Flush(6-L/Flush)WaterClosets:a. Basis-of-Design:b. ResidentialWaterClosetAttributes:c. Standards:ASMEA112.19.2/CSAB45.1.d. BowlType:Siphonjet.e. Height:

1) Standard.2) Child.3) Handicappedandelderly.

f. RimContour:1) Elongated.2) Regular.

g. WaterConsumption:1) Watersaving.2) Low.

h. Color:__.4. ToiletSeat:5. SupplyFittings:

a. Standard:ASMEA112.18.1/CSAB125.1.b. SupplyPiping:Chrome-platedbrasspipeorcoppertube.

1) Chrome-platedwallflange.c. Stop:Quarter-turn,Chrome-plated-brass,ballvalveorcompression

stop.1) Inletconnectiontypeandsize:matchsupplypiping.2) Operation:

a) Loosekey.b) Wheelhandle.

d. Riser:1) Size:

a) NPS3/8(DN10).b) NPS1/2(DN15).

2) Material:

22 40 00-12

a) Chrome-plated,soft-copperflexibletube.b) ASMEA112.18.6/CSAB125.6,braided-orcorrugated-

stainless-steelflexiblehose.

2.10 ToiletSeats

A. Basis-of-Design:1. Standard:IAPMO/ANSIZ124.5.2. Material:Plastic.3. Type:

a. Standard.b. Heavyduty.

4. Shape:a. Elongatedrim,openfront.b. Elongatedrim,closedfront.

5. Hinge:a. Check.b. Self-sustaining.c. Self-sustaining,check.d. Self-raising.

6. HingeMaterial:Noncorrosivemetal.7. SeatCover:

a. Required.b. Notrequired.

8. Color:__.

2.11 CommercialUrinals

A. Stall,WashoutType:1. Basis-of-Design:2. FlushometerValve:

a. Manualdiaphragm.b. ManualPiston.c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10-yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

B. Wall-Hung,BackOutlet,Blowout:1. Basis-of-Design:2. FlushometerValve:

a. Manualdiaphragm.b. ManualPiston.c. BatteryPoweredSolenoidSensor.

22 40 00-13

d. BatteryPoweredDiaphragm.e. 10-yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

C. Wall-Hung,BackOutlet,SiphonJet,Accessible:1. Basis-of-Design:2. FlushometerValve.

a. Manualdiaphragm.b. BatteryPoweredSolenoidSensor.c. BatteryPoweredDiaphragm.d. 10-yearbatterypoweredpistonoperated,solenoidactivated.e. Hardwireddiaphragminwallsensor.f. Hardwireddiaphragmsidemountedsensor.

D. Wall-Hung,BackOutlet,Washout,Accessible:1. Basis-of-Design:2. FlushometerValve:

a. Manualdiaphragm.b. ManualPiston.c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10-yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.

E. Wall-Hung,BottomOutlet,WashoutorWall-Hung,BottomOutlet,WashDown:1. Basis-of-Design:2. FlushometerValve:

a. Manualdiaphragm.b. ManualPiston.c. BatteryPoweredSolenoidSensor.d. BatteryPoweredDiaphragm.e. 10-yearbatterypoweredpistonoperated,solenoidactivated.f. Hardwireddiaphragminwallsensor.g. Hardwireddiaphragmsidemountedsensor.h. ASMEA112.6.1M,TypeII,Urinalcarrier.

3. WasteFitting:Two-piecetrapandswivelelbowandwallflange.a. Stainlesssteel.b. Chromeplatedbrass.

4. CommercialUrinalAttributes:a. Standards:ASMEA112.19.2/CSAB45.1.b. Material:Vitreous-china.c. Type:Siphonjet.

1) Extendedshields.

22 40 00-14

d. Drain:RemovabledomestrainerwithNPS1-1/2(DN40)tailpiece;chrome-plated.

e. StrainerorTrap-way:Withintegraltrap.f. WaterConsumption:

1) 0.125gal(0.47L)perflush.2) 0.5gal(1.9L)perflush.3) 1.0gal(3.8L)perflush.

g. SpudSizeandLocation:NPS3/4(DN20);1) Back.2) Top.

h. OutletSizeandLocation:NPS2(DN50);back.i. Color:__.

5. MountingFixture:a. PlateTypeSystemwallurinal.b. PlateTypesystemwithbearingplate.

2.12 WaterlessUrinals

A. Wallhung,backoutlet,waterless,vitreouschina,designedforliquid-trap-sealoperation:1. Basis-of-Design:2. WaterlessUrinalattributes:

a. Standard:ASMEA112.19.2/CSAB45.1,withoutwater.b. Trap-SealMethod:Liquidseal.c. OutletSize:Flange,NPS2(DN50).

1) Location:Back.d. Trap-SealingLiquid:Proprietary.e. Color:__.

3. WasteFitting:a. Standard:ASMEA112.18.2/CSAB125.2.b. Size:NPS2(DN50).

4. MountingFixture:a. PlateTypeSystemwallurinal.b. PlateTypesystemwithbearingplate.

2.13 CommercialShowers

A. InstitutionalWall-MountedShower.1. Basis-of-Design:2. PrefabricatedStainless-steel,wall-mounted,surface-enclosureshowerfixture

withindividualnozzle.3. Standards:

a. ASMEA112.18.1/CSAB125.1.b. ASSE1016/ASMEA112.1016/CSAB125.16.

4. NumberofShowerNozzles:__.

22 40 00-15

5. HeighttoNozzles:a. 66inches(1675mm).b. 72inches(1830mm).

6. Mixingvalvewithhotandcoldwateroperation:a. Thermostatic.

7. Control:Thermostaticmixingvalvewithindividual,tempered-watersupplyandhandleveroperation.

8. FlowControl:Pershowerhead:a. 1.25gpm(4.7L/m).b. 1.5gpm(5.7L/m).c. 1.75gpm(6.62L/m).d. 2gpm(7.6L/min.).e. 2.5gpm(9.5L/min.).

9. SoapDish:Pershowerhead.10. Supplies:

a. Coppertubing11. Shroud:Stainlesssteelofsizetocoversuppliesandventpiping.

a. Verticalextension.b. Horizontalextension.

12. DrainFittingOutlet:

2.14 CommercialLavatoryFaucets

A. SoldBrassManualLavatoryFaucets:1. Basis-of-Design:

a. Singlecontrolmixing.b. Series4inch(102mm)CentersetQuarterTurnFaucets.c. SingleBasin.d. MeteringFaucet

B. SolidBrass,AutomaticLavatoryFaucets:electronic-sensor-operated:1. Basis-of-Design:

a. Automatic-type,battery-powered.b. Automatic-type,hard-wired.

2. Standard:a. ASMEA112.18.1/CSAB125.1.b. NSF/ANSI61.

3. General:Indicators:Hot-andcold-water.4. Body:Commercial,solidbrass.

a. 4inch(102mm)Centerset.b. 8inch(203mm)Centerset.c. Widespread.d. Singlehole.

5. Finish:Polishedchromeplate.6. MaximumFlowRate:

22 40 00-16

a. 0.35gpm(0.95L/min).b. 0.5gpm(1.5L/m).c. 1.0gpm(3.8L/m).d. 1.5gpm(5.7L/m).e. 2.2gpm(8.3L/m).

7. MountingType:a. Deck,exposed.b. Deck,concealed.c. Back/wall,exposed.d. Back/wall,concealed.

8. ValveHandle(s):a. Singlelever.b. LeverHandles,2-1/2inches(63.5mm).c. Cross,fourarm.d. Wristblade,4inches(102mm).e. Elbow,6inches(152mm)f. Pushbutton.

9. SpoutType:a. Rigid.b. Swing.c. Rigid,gooseneck.d. Swivel,gooseneck.

10. SpoutOutlet:a. Aerator.b. Laminarflow.c. Spray.

11. Operation:a. Quarter-TurnHeavyDutyCeramic.b. SingleControlCeramicCartridge.c. Drain:ModelNotpartoffaucet.

C. Brass,Laminar-Flow,CommercialFaucet-SpoutOutlets:1. Basis-of-Design:2. Standards:

a. ASMEA112.18.1/CSAB125.1.b. NSF/ANSI61.

3. Non-aerating,laminarstream.4. Forattachmenttofaucetoutlets:Externalorinternalthread.5. Flow-raterangewithinflow-rateoffaucet.6. Finish:Chrome-plated.

2.15 SinkFaucets

A. ManualTypeMixingValve:Commercial,Solid-BrassFaucets:1. Basis-of-Design:

22 40 00-17

2. Standards:a. ASMEA112.18.1/CSAB125.1b. NSF/ANSI61.

3. Includehot-andcold-waterindicators;coordinatefaucetinletswithsuppliesandfixtureholepunchings;coordinateoutletwithspoutandsinkreceptor.

4. BodyType:a. 4inch(203mm)Centerset.b. Widespread.c. Singlehole.

5. BodyMaterial:Solidbrass.6. Finish:

a. Chromeplated.b. RoughChrome.c. PolishedChrome.

7. MaximumFlowRate:a. 0.35gpm(1.3L/m).b. 0.5gpm(1.9L/m).c. 1.0gpm(3.8L/m).d. 1.5gpm(5.7L/m).e. 2.2gpm(8.3L/m).f. 2.5gpm(9.5L/m).

8. Handle(s):a. Leverhandles,2-1/2inches(63.5mm).b. Cross,fourarm.c. Wristblade,4inches(102mm).d. Elbow,6inches(152mm).e. PushButton.f. Footpedal.g. Kneeaction.

9. MountingType:a. Deck,concealed.b. Deck,exposed.c. Back/wall,exposed.

10. SpoutType:a. Lowprofile.b. Rigid,solidbrass.c. Rigid,solidbrasswithwallbrace.d. Swing,roundtubular.e. Swing,shapedtube.f. Swing,solidbrass.g. Rigidgooseneck.h. Swivelgooseneck.

11. Operation:QuarterTurnHeavyDutyCeramic.12. VacuumBreaker:Forhoseoutlet.

22 40 00-18

13. SpoutOutlet:a. Aerator.b. Laminarflow.c. HosethreadaccordingtoASMEB1.20.7.d. Plainend.e. Spray.

14. SupplyFittings:15. WasteFittings:

2.16 CommercialandResidentialShowerFaucets

A. CommercialShowerFaucets:1. Basis-of-Design:2. Single-handle,pressure-balancemixingvalvewithhot-andcold-water

indicators;checkstops;andshowerhead.3. FaucetAttributes:

a. Standards:1) ASMEA112.18.1/CSAB125.1.2) ASSE1016/ASMEA112.16/CSAB125.16.

b. BodyMaterial:Solidbrass.c. Finish:Polishedchromeplate.d. MaximumFlowRate:2.5gpm(9.5L/min.)unlessotherwiseindicated.e. Mounting:

1) Concealed.2) Exposed.

f. Operation:Single-handlecontrol.1) Push-pull.2) Twistorrotate.

g. AntiscaldDevice:1) Integralwithmixingvalve.2) Separateunit.

h. CheckValveStops:Integralorattached.1) Hotandcoldsupply.

4. SupplyConnections:NPS1/2(DN15).5. ShowerHead:

a. S1.b. S5.c. S6.d. S7.e. S8.f. S9.g. S10.h. ShowerHeadAttributes:

1) Standard:ASMEA112.18.1/CSAB125.1.

22 40 00-19

2) Type:a) Balljointwitharmandflange.b) Withoutballjoint,butwitharmandflange.c) Balljointandheadintegralwithmountingflange.d) Integralwithmountingflange.

3) ShowerHeadMaterial:a) Metallicwithchrome-platedfinish.b) ABSPlasticwithchrome-platedfinish.

4) SprayPattern:a) Adjustable.b) Fixed.

5) IntegralVolumeControl.6) Shower-Arm,Flow-ControlFitting:

a) 1.5gpm(5.7L/m).b) 2.0gpm(7.6L/m).

7) TemperatureIndicator:Integralwithfaucet.

2.17 BedpanWashers

A. BedpanWashers:Wall-Mounted:1. BedpanWasherAttributes:

a. Standard:ASMEA112.18.1/CSAB125.1.1) HoseAssembly:Rubberorvinylhose,self-closing,hand-held

spraynozzle,wallbracket,andhook;hoselengthtobe48inch(1220mm).

b. VacuumBreaker:ASSE1001,atmospheric,wallmounted.c. ShutoffValve:Wall-mounted,upstreamofvacuumbreaker.d. ConnectingPiping:Concealed.e. Finish:Polishedchrome-platedfinishonexposedmetalparts.f. SupplyConnection:NPS1/2(DN15).g. ControlMounting:

1) Floor.2) Wall.3) Single-pedal.4) Double-pedal,hot-andcold-water.

2.18 FaucetSupplyFittings

A. Basis-of-Design:1. Standard:

a. ASMEA112.18.1/CSAB125.1.b. NSF61.

2. SupplyPiping:Chrome-platedbrasspipeorchrome-platedcoppertubematchingwater-supplypipingsize.Includechrome-platedbrassorstainless-steelwallflange.

22 40 00-20

3. SupplyStops:Chrome-platedbrass,one-quarter-turn,ball-typeorcompressionvalvewithinletconnectionmatchingsupplypiping.

4. Operation:a. Loose-key.b. Wheel-handle.

5. Risers:a. NPS3/8(DN10).b. NPS1/2(DN15).c. Material:

1) Chrome-plate,rigidcopperpipe.2) Chrome-plated,soft-copperflexibletube.3) ASMEA112.18.6/CSAB125.6,braided-orcorrugated-stainless-

steelflexiblehose.

2.19 SinkandLavatoryWasteFittings

A. Basis-of-Design:1. GridtypewithNPS1-1/2(DN40)offset.

B. Standard:ASMEA112.18.2/CSAB125.2.

C. Trap:Two-piecetrapandswivelelbowandwallflange.1. Size:NPS1-1/2(DN40).2. Stainlesssteel.3. Chromeplatedbrass.

2.20 UrinalFlushometerValves

A. Lever-Handle,DiaphragmFlushometerValves:1. Basis-of-Design:

a. 0.125gal(0.47L)perflush.b. 0.5gal(1.9L)perflush.c. 1.0gal(3.8L)perflush.

B. Solenoid-Actuator,DiaphragmFlushometerValves:1. Basis-of-Design:

a. 1.0gal(3.8L)perflush.

C. Hydraulic-Actuator,Push-Button,DiaphragmFlushometerValves:1. Basis-of-Design:

a. 0.125gal(0.47L)perflush.b. 0.5gal(1.9L)perflush.c. 1.0gal(3.8L)perflush.

D. Lever-Handle,PistonFlushometerValves:1. Basis-of-Design:

a. 1.0gal(3.8L)perflush.

22 40 00-21

b. 0.5gal(1.9L)perflush.

E. Hard-Wired,Solenoid-Actuator,PistonFlushometerValves:1. Basis-of-Design:

a. 0.5gal(1.9L)perflush.

F. Battery-Powered,Solenoid-Actuator,PistonFlushometerValves:1. Basis-of-Design:

a. 0.125gal(0.5L)perflush.b. 0.5gal(1.9L)perflush.c. 1.0gal(3.8L)perflush.

2. UrinalFlushomaticAttributes:a. Standard:ASSE1037/ASMEA112.37/CSAB125.37.b. MaximumPressureRating:125psig(860kPa).c. Features:Includeintegralcheckstopandbackflow-preventiondevice.d. Material:Brassbodywithcorrosion-resistantcomponents.e. ExposedFlushometer-ValveFinish:Chromeplated.f. PanelFinish:Chromeplatedorstainlesssteel.g. Style:

1) Exposed.2) Concealed.

h. Consumption:Perflush.1) 0.125gal.(0.47L).2) 0.5gal.(1.9L).3) 1.0gal.(3.8L.

i. MinimumInlet:1) NPS3/4(DN20).2) NPS1(DN25).

j. MinimumOutlet:1) NPS3/4(DN20).2) NPS1-1/4(DN32).

2.21 WaterClosetFlushometerValves

A. Lever-Handle,DiaphragmFlushometerValves:1. Basis-of-Design:

a. 1.6gal(6L)perflushvolume.b. 1.28gal(4.8L)perflushvolume:

B. Solenoid-Actuator,DiaphragmFlushometerValves:1. Basis-of-Design:

a. 1.6gal(6L)perflush.b. 1.6/1.1gal(6/4.125L)perflush.

C. Hydraulic-Actuator,Push-Button,DiaphragmFlushometerValves:1. Basis-of-Design:

22 40 00-22

a. 1.28gal(4.8L)perflush.b. 1.6gal(6L)perflush.

D. Lever-Handle,Push-Button,DiaphragmFlushometerValves:1. Basis-of-Design:ZurnIndustries,LLC:

a. Electronicpushbuttonactuator.b. Hydraulicpushbuttonactuator.c. Electronicactuator.

E. Lever-Handle,PistonFlushometerValves:1. Basis-of-Design:ZurnIndustries,LLC:

a. 1.6gal(6L)perflush.b. 1.28gal(4.8L)perflush.

F. Hard-Wired,Solenoid-Actuator,PistonFlushometerValves:1. Basis-of-Design:

G. Battery-Powered,Solenoid-Actuator,PistonFlushometerValves:1. Basis-of-Design:

a. 1.1gal(4.2L)perflushb. 1.28gal(4.8L)perflush.c. 1.6gal(6L)perflush.d. WaterClosetFlushometerAttributes:

1) Standard:ASSE1037/ASMEA112.37/CSAB125.37.2) MaximumPressureRating:125psig(860kPa).3) Features:Includeintegralcheckstopandbackflow-prevention

device.4) Material:Brassbodywithcorrosion-resistantcomponents.5) ExposedFlushometer-ValveFinish:Chromeplated.6) PanelFinish:Chromeplatedorstainlesssteel.7) Style:

a) Exposed.b) Concealed.

8) Consumption:Perflush.a) 1.6gal.(6L).b) 1.28gal.(4.8L).c) 1.1gal.(4.2L).

9) MinimumInlet:NPS1(DN25).10) MinimumOutlet:NPS1-1/4(DN32).

2.22 WaterClosetWasteCarriers

A. HighPerformance,AdjustableSiphonJetWaterClosetCarriers:1. Basis-of-Design:

a. HorizontalWasteFitting:b. VerticalWasteFitting:

22 40 00-23

B. Bariatric,AdjustableSiphonJetWaterClosetCarriers:1. Basis-of-Design:

a. HorizontalWasteFitting:b. VerticalWasteFitting:

C. Standard,AdjustableBlowoutStyleWaterClosetCarriers:1. Basis-of-Design:

a. HorizontalWasteFitting:b. VerticalWasteFitting:c. WaterClosetWasteCarrierAttributes:

1) Standard:ASMEA112.6.1M.2) LoadRating:

a) H=300lbs(227kg).b) N=300lbs(136kg).c) XH=750lbs(340kg).d) XB=1,000lbs(454kg).

3) Waste-fittingtomatchdrainagepipingmaterialandarrangement.Couplingsgaskets,faceplate,andfeet;Hardwaretomatchfixture.a) Widespaceinstallation:Extensioncoupling.

4) ConnectionType:a) No-Hub"N".b) HubandSpigot"H".

5) FlowDirection:a) Right"R".b) Left"L".c) Double"D".

6) WastePipeDiameter:a) 3in(76mm).b) 4in(102mm).

7) Faceplate:B(blowoutstylefaceplate).8) WaterConsumption:Perflush.

a) 1.1gal(4.2L).b) 1.28gal(4.8L)c) 1.6gal(6L).

9) Water-ClosetMountingHeight:a) Standard.b) Child.c) Handicapped/elderlyaccordingtoICCA117.1.

10) Coupling/WasteOrificeDiameter:3in(76mm).11) FootType:

a) Universal(standardorpre-fabinstallations).b) Bariatric.

12) Material:CastIron.

22 40 00-24

2.23 SupportFixtures

A. Lavatory,SupportFixtures:1. Basis-of-Design:

a. PlateTypeSystem;LavatoryBackCarrier.1) Lavatorysupportsystemwithtopsupportplate.2) Dura-Coatedrectangularsteeluprightswithweldedfeet.3) Adjustablesupportplate.,andmountingfasteners.

b. ConcealedArmSystem,withAlignmentTrussCarrier.1) Lavatorysupportsystemwithconcealedarms.2) Dura-Coatedrectangularsteeluprightswithweldedfeet.3) Castironadjustableheaders,concealedarms,steelsleeves,

alignmenttruss,andmountingfasteners.c. ConcealedArmSystemwithAdjustingBarsCarrier.

1) Lavatorysupportsystemwithconcealedarms.2) Dura-Coatedrectangularsteeluprightswithweldedfeet.3) Castironadjustableheaders,concealedarms,steelsleeves,

adjustingbars,andmountingfasteners.d. ConcealedArmSystemwithAdjustableUprightsandHeaderPlates.

1) WallHungLavatorySupportSystem.2) Dura-Coateduprightsupports;structuralcarbon-steelsquare

tubing.3) Weldedsteelplatemountingfeetwithseparateboltpatterns:4) AnchorscomplyingwithOSHPDspacingrequirements.

a) 3/8inch(10mm).b) 1/2inch(13mm).

5) LowerandupperEZ-installationplates,markedwithanindexedrulerguide;a) Accurateadjustability,uprightspacing,from15inch(381

mm)to22inch(560mm).6) Individualslottedheaderplateswithintegralweldedarmsleeves.

a) Provides2inch(51mm)additionalhorizontaladjustmentperplate.

b) Totalhorizontaladjustmentrangeis11inches(279mm)to26inches(660mm).

7) Arms:Dura-Coatedcastironwithlevelingscrewsandelastomericlockingdevices.

8) Factoryassembled:Uprights,EZ-installationplates,andheaderplates.

9) ComplieswithASMEStandardA112.6.1Matanyadjustmentposition.

e. ExposedArmSystemCarrier.1) Lavatorysupportsystemwithexposedarms.2) Dura-Coatedrectangularsteeluprightswithweldedfeet.

22 40 00-25

3) Castironadjustableheaders,acidresistantepoxycoatedcastironarms,alignmenttruss,andmountingfasteners.

B. UrinalSupportFixtures:1. Basis-of-Design:

a. PlateTypeSystemswallurinal.1) Dura-Coatedrectangularsteeluprights,weldedfeet,adjustable

supportplate,andmountingfasteners.b. PlateTypesystemwithbearingplate.

1) Dura-Coatedcarbonstructuralsteelrectangulartubinguprights.2) Weldedbasefeet,slottedflooranchorholes.3) Lowerbearingplate,verticallyadjustabletoaccommodate

bearingjackplacement.4) UpperUniversalhangerplate,pre-notchedforbackspudinlet.

a) Designedforvarioushardwarepositionsandfixtures.b) Includesmountingfastenersandhardware.c) Carriersystemexceedsloadanddeflectionrequirementsas

outlinedinASMEStandardA112.6.1M.

PART3EXECUTION

3.1 Examination

A. VerificationofConditions:ExamineareasandconditionsunderwhichWorkistobeperformedandidentifyconditionsthatmaybedetrimentaltoproperortimelycompletion.1. Rough-inforwater-supply,sanitarydrainageandventpipingsystems:Verify

locations;pipeandconnection.2. Wallsandpartitions:Suitablethickness.

B. FixtureandValveInteriors:Cleanandfreeofforeignmatter,andcorrosion.Removepackingusedtopreventdiscmovement.1. Operatevalvesfromfullyopentofullyclosedpositions.2. Verifyguidesandseatsarecleanandfreeofforeignmatter,andcorrosion.

C. ThreadsonValvesFittingsandFixtures:Inspectvalveandmatingpipeforformandcleanliness.

D. MatingFlangeFaces:Inspectforconditionsthatmaycauseleaking.1. Bolting:Propersize,length,andmaterial.2. Gaskets:Propersizeandmaterialcompositionsuitableforapplication;defect

anddamagefree.

E. Replacedefectivefixturesandvalveswithnew.

F. Donotproceeduntilunsatisfactoryconditionshavebeencorrected.

22 40 00-26

3.2 Installation

A. AllFixtures:levelandplumb.1. Forchildren:installatheightrequired.

B. Attachallsupportframingtobuildingsubstratepermanufacturer'swritteninstructions.

C. Wall-mountedfixtures:Installoff-the-floorcarriersupports.Installaccessible,wall-mountedwaterclosetsaccordingtoICC/ANSIA117.1.

D. Water-supplypiping:Ballorgateshutoffvalvesonsupplytoeachfixtureconnectedtodomestic-waterpiping.Seesection230500-CommonWorkResultsforHVAC"CommonWorkResultsforPlumbingPiping."1. Locations:easilyaccessible.

E. Fixturedrainoutlets:Installtrapandwastepipingtobeconnectedtosanitarydrainagesystem.

F. Escutcheonsandwallflanges:Wallpipingpenetrationsfinishedlocations.

G. Jointsbetweenfixturesandwalls:Sealwithsiliconesealant:1. Sanitary,one-part,mildew-resistant.Matchcolors.

H. Flushometers:1. Water-supplyfittingonsupplytowatercloset.2. Supplypiping:Attachtosupportsorsubstrateinspacebehindfixture.3. Accessiblewaterclosets:Handleonlever-handleflushometertobemounted

onopensideofwatercloset.Besureactuatorsaccessibletowithdisabilities.4. Freshbatteriesinbattery-powered,electronic-sensormechanisms.

3.3 FieldQualityControl

A. Testandinspectperauthoritieshavingjurisdiction.

B. PipingTests:priortocoveringandaftercuringandsettingofconcretethrustblocks.Fillandpressurizepipelinetotestpressureaminimumof24hoursbeforetesting.1. Usepotablewater.

C. HydrostaticTests:1. TestPressure:One-and-one-halftimestheworkingpressurefortwohours.

a. Increasepressureatincrementsof50-psig(350-kPa).1) Inspectjoints.

b. Maintaintestpressureforonehour,minimum.c. Decreasetestpressuretozeropsig(zerokPa).d. Increasepressureatincrementsof50-psig(350-kPa).

1) Inspectjoints.e. Maintaintestpressureforonehour,minimum.

22 40 00-27

f. Allowableleakage:2quarts(1.89L)perhourper100joints.2. Remakeleakingjointswithnewmaterialsandrepeattestuntilleakageis

withinallowedlimits.

D. Preparetestandinspectionreports.

3.4 Identification

A. ComplywithrequirementsforidentificationspecifiedinSection230553-IdentificationforHVACPipingandEquipment"IdentificationforPlumbingPipingSystems."

B. ComplywithrequirementsforidentificationspecifiedinSection-"IdentificationforElectricalSystems."

3.5 Adjusting

A. Flowregulators:Properflowofwaterthroughfixtures.

B. Flushometervalves:Adjustwaterpressure.

C. Replacedamagedfixtures,fittings,andcontrols

3.6 Cleaning

A. Removepaintspots,dirt,anddebris.Damagedfinishtomatchoriginalfinish.

B. Cleanfixtures,accordingtomanufacturer'swritteninstructions.

C. Provideprotectivecoveringforinstalledfixtures.

D. NottobeusesfortemporaryfacilitieswithoutwrittenapprovalbyOwner.

ENDOFSECTION