Firestop SystemsGuide for Specifiers2007 Edition
Fir
esto
p S
yste
ms G
uid
e f
or
Sp
ec
ifie
rs
20
07
Ed
itio
n
In the US: P.O. Box 21148 Tulsa, OK 74121Customer Service: 1-800-879-8000en espaol: 1-800-879-5000Fax: 1-800-879-7000
www.us.hilti.com
Hilti is an equal opportunity employer.Hilti is a registered trademark of Hilti, Corp.Copyright 2007 by Hilti, Inc. (U.S.)H181 3427488 07/07 DBS
The data contained in this literature was current as of the date of publication. Updates and changes may be madebased on later testing. If verification is needed that the data is still current, please contact the Hilti Technical SupportSpecialists at 1-800-879-8000. All published load values contained in this literature represent the results of testingby Hilti or test organizations. Local base materials were used. Because of variations in materials, on-site testing isnecessary to determine performance at any specific site. Laser beams represented by red lines in this publication.Printed in the United States
*14001 US only
In Canada: 6790 Century Avenue, Suite 300CDN-Mississauga, Ontario L5N 2V8 Customer Service: 1-800-363-4458Fax: 1-800-363-4459
www.hilti.ca Saving lives through innovation and education.Hilti. Outperform. Outlast.
-
Engineering Judgment Request Form
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
Date submitted (MM/DD/YY)
Initiators Name
DDAATT or Phone Fax
Project Name
Contractor Contact
Phone Fax
TP Through Penetration1. Type and thickness of wall or floor penetrated:
2. Type and size of penetrating item(s):
3. Size and shape of opening:
If sleeved, specify type and size:
4. Annular space (min. and max.):
5. Fire rating (hrs.):
J Joint1. Type and thickness of wall or curtain wall
(include stud size for gyp):
2. Type and thickness of floor or floor/ceiling assembly
(include flute size):
3. Orientation of wall to floor/ceiling assembly (circle one):
Perpendicular Parallel
4. Type of joint system (circle one):
Floor-to-floor Floor-to-wall Top-of-wall
Wall-to-wall Curtain wall
5. Maximum width of joint:
6. Fire rating (hrs.):
Comments:
Fax completed form to Hilti Fire Protection Engineering Team for processing : 918-254-1679
l TP Through Penetration OR l J Joint
PROFIS Firestop
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Lives through innovation and education
Hilti Professional Integrated Software has been developed to aid in the
selection, specification and submittal of tested and approved Hilti
firestop systems that meet todays tough building codes.
PROFIS Firestop features:
Comprehensive, easy-to-use interactive system selector
Database of exportable, tested and approved firestop systems
drawings and installation instructions
Complete submittal builder feature which outputs a customized,
professional-looking submittal package that includes the following:
Cover page stating who the submittal was created for and the
project information
Table of contents
Product information page(s)
Certificate(s) of Compliance
System(s) drawings complete with installation instructions
Material Safety Data Sheet(s)
Specify and submit with confidence when using PROFIS Firestop. This
easy-to-learn, powerful software makes specifying and installing the
correct firestop systems for your project fast and accurate.
Introducing PROFIS Firestop
Hilti PROFIS Firestop software will be available soon!To request your free copy of this powerful software either:
Call your Hilti Customer Service Representative at 1-800-879-8000
Register online at www.us.hilti.com and email your request
OR
Contact your local Hilti Account Manager
-
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.1
Firestop Design Center
Firestop specification made easy!
Access a state-of-the-art tool designed to make specification of Firestop even easier with the click of a mouse. Designed with you in mind,the Hilti Firestop Design Center makes solving application problems and downloading CAD-ready drawings easy.
Access our complete library of detailed drawings and specifications by registering today at www.us.hilti.com.
Once there, you will find:
Sample specifications
System drawings
Product information
Firestop terms and definitions
Building regulations and codes
Project references
Firestop FAQ
Additional Resources In-house, full-time degreed Fire Protection Engineers
Hilti Systems & Solutions Full Line Product Catalog
Hilti Product Technical Guide
Visit the Hilti Firestop Design Center Online today at www.us.hilti.com
(click on the Specification link under Planning & specifying)
Search by application: Joints or Through Penetrations
Design & Specification Resources System Drawing Search Featured New Products
1 2
34
Continuing Education CourseCourse name: Firestop A Life Safety Issue
Provides one hour of AIA and state credit
Qualifies for HSW
FREE
Presented by: Chad Stroike, CFPS, Hilti, Inc.
Description: Provides an overview of fire safe building construction,how to provide proper firestop protection via model building codes,and specifications. Proper and improper firestop installations, liabilityissues, and types of fire/smoke assemblies are also reviewed.
To take this course: www.aecdaily.com/en/1595881
-
Firestop Specialty Contractors
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
2
Hawaii
Hilti Accredited Firestop Specialty Contractors*Hilti Fire Protection Specialists
A Hilti Accredited Firestop SpecialtyContractor (HAFSC) is an independent professionalfirestop installer who has been provided specializedtraining by Hilti; and who has committed to provide
building owners, generalcontractors, and subcontractorswith a full service solution for alltheir firestopping needs. When youchoose to use a Hilti AccreditedFSC, you are selecting a trainedfirestop installationspecialist committed to applyingproven Hilti firestopping technology
and innovation in your building to minimize the risk ofloss due to fire, smoke, and toxic gases.
Hilti Accredited FSCs useHilti firestop products,which eliminates theconfusion caused bynumerous subcontractorsinstalling different firestopproducts on the same job. This also providescontinuity throughout the job, which helps reduceyour liability exposure. Their professionalexpertise in installing the appropriate Hilti firestopsystem can provide significant savings potential in timeand cost to the general contractor and building owner.
During firestop inspections, Hilti Accredited FSCs canoffer documented, step-by-step accountability. Theirfirestop expertise helps assure building officials thatthe proper installation techniques have been appliedand that all installed systems comply with localand national codes.
CONTAINMENT
SUPPRESSIONDETECTION
Hospitals
Nursing Homes
Schools
Universities
Office Buildings
Apartment Complexes
Retail Centers
Telecom Switching Stations
Telecom Central Offices
Entertainment Complexes
Hotels
Petroleum Plants
Chemical Plants
Nuclear Power Plants
Pharmaceutical Plants
Military Complexes
For a Hilti Firestop Specialty Contractor near you, call 1-800-879-8000 today.
Through the Firestop Specialty ContractorProgram, Hilti trains professional contractors in fireprotection systems installation procedures of Hilti productsthat meet all current standards and codes. For Architects andSpecifiers this is great news. By using a Hilti AccreditedFirestop Specialty Contractor (HAFSC) you get factory-trained professionals who are knowledgeable aboutfirestopping methods and quality installations.
Selecting a HAFSC has the following benefits:
Allows tradespeople to focus on their area of expertise,leaving firestopping to passive fire protection specialists
Help ensure one-source continuity and systemcompatibility for all firestop applications
Promote hassle-free inspection by officials who know andtrust professional firestop installers
Provide single contractor accountability for all firestopapplications
Increase your confidence that all firestopping is completedcorrectly the first time
* Hilti Accredited Firestop Specialty Contractors are independent companies who have hademployees participate in the Hilti firestop training program.
-
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
3
Intro
ductio
nC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
Firestop Systems Guide
Introduction Page 3
Dedicated to Life Safety Page 4
Application Review, Products and Selection Chart Page 9
Firestop Systems Application Review Page 10Product Information & Installation Instructions Page 14
Product Ordering Information Page 37Selection Chart Page 44
Firestop System Drawings Page 58
Most Common Systems Directory Page 58Alpha-Numeric System Directory Page 511
Through-Penetration Drawings Page 60Joint Drawings Page 356
Estimating Tables & Technical Data Page 463
Estimating Tables Page 465Firestop Terms & Definitions Page 469
Understanding System Nomenclature Page 471Material Safety Data Sheet (MSDS) Page 472
UL Certificates of Compliance Sheets Page 506Terms and Conditions of Sale Page 510
Engineering Judgment (EJ) Process & Form Page 512
-
Dedicated to Life Safety
Intr
od
uctio
nC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
4
Hilti is dedicatedto saving lives throughinnovation andeducationThe quality and excellence of HiltiFirestop products help ensurethat fire, smoke and toxic gasesare contained to reduce the tragicloss of human life and property.Through a combination ofsuperior products, advancedknowledge and unparalleledcustomer service we are able toprovide the highest qualityfirestop systems.
Hilti offers a comprehensive support packageThroughout the entireFirestopping process, whether itis specification, installation orinspection, Hilti will be there tooffer job site support andexpertise. The Hilti highly trainedSales Force, Fire ProtectionSpecialists, and in-house FireProtection Engineering team canhelp you select the correctproducts and systems to matchyour specific project needs. Hiltihas a support package that isunmatched in the passive firestopindustry.
Fire safetyFire safety is a major concern for allwho are responsible for the design andspecification of new buildings.
The causes of fire are varied andunpredictable, and often outside thecontrol of the designer. What can becontrolled, however, is the effect of fireonce it has started.
The control of fire within a building isnormally affected by a combination ofactive and passive fire protection systems.
Active fire protection systemsActive fire protection systems are designedto detect fire, and either to extinguish it bymeans of water sprinklers, halogeninstallations or fire extinguishers, or tominimize its effects by smoke ventilation.Active systems are also used to assist theescape of occupants by the provision ofalarms and emergency lighting.
Passive fire protection systemsPassive fire protection is designed intothe structure of the building, so that iffire breaks out, it is contained within afire compartment, surrounded by fire-resistive walls and floors. For the wallsand floors to maintain their fire-resistance, however, every opening,penetration and joint must be sealedagainst the escape of fire and smoke.
Intumescent fire sealsThe materials used to form the seals mustnot only fill all gaps at the time ofconstruction, but also, in the event of fire,expand to close any further gaps formed bymelted components. These intumescent fireseals, if properly installed, can help preventfire escaping from a compartment for arating period of up to four hours. This timeperiod can prove vital in allowing occupantsto escape, and fire-fighters to control the fire.
HiltiAround the world the red Hilti toolbox isa familiar sight on building sites, andthe Hilti name is known and respected.
To most people Hilti means precision toolsand secure fastenings. For many years
however, Hilti has applied their skills to anew area of construction where precisionand security are vital: firestopping.
Hilti firestop systemsThe aim of Hilti firestop systems is toprovide designers and specifiers withthe following: excellence finished solutions
that match the well known, highquality standards associated with theHilti product
easy installation all firestopcomponents are readily available andsimple and fast to install
tested and used world wide Hilti offers one-stop firestoppingsystems tested in accordance withmost relevant regulations
wide ranging solutions forvirtually any opening or penetrationthrough which heat or smoke might pass,Hilti offers a firestop solution that will helpminimize damage in the event of a fire
Hilti and thedesigner/specifierTo assist the designer or specifier inselecting and specifying the appropriatefirestop system, Hilti has developed twotools; PROFIS Firestop and the onlineFirestop Design Center.
PROFIS Firestop is a professionallyintegrated software that guides youthrough the system selection process.Once the appropriate system isselected, the software generates aprofessional looking submittal packagewith all the necessary documents.
The online Firestop Design Centerallows you to access specification toolsand resources by application or byproduct names. To visit the onlineFSDC, go to www.us.hilti.com and clickon the Specifications link. Then, followthe Firestop Design Center link to theright of the page.
Hilti customized solutionsIf none of the standard firestop systemsmeet the requirements of the design,Hilti is ready to offer their expertise andwork with the designer to producecustomized solutions.
-
Fire Safety Issues
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.5
Intro
ductio
nC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
Problem The illustration on the left indicates a rangeof typical problems facing the designer.
Construction may consist of:
concrete wood gypsum
The problem areas are:
Movement jointsRigid or low movement jointsHead of wall and perimeter jointsMetal and plastic pipesPlastic pipesMultiple penetrations, pipes and/orcablesCable trays (with permanent sealingof opening during construction, ortemporary sealing allowing additionalcables to be installed subsequently)Cable trays (with permanent sealingof opening during construction)Cables (single or bundled)Electrical outlet boxesHeating/ventilation/air conditioning
Fire Resistance RatingTo help prevent the rapid spread of firewithin a building, certain walls, floorsand joints are required to meet a specificfire resistance rating the period oftime during which a building componenthas been tested to confine a fire orcontinue to perform a structural functionor both. Through-penetrations and jointscreated during the construction processrequire the installation of firestopsystems in order to bring the wall orfloor back up to its original fire-rating.
FirestoppingIt is essential that every penetration orjoint in a fire-rated wall or floor isadequately protected by sealing orfirestopping such that the buildingcomponent is restored to its original fire-rated condition in order to maintaincompartmentalization. The quality andexcellence of Hilti Firestop Products helpensure that fire, smoke and toxic gasesare contained to reduce the tragic lossof human life and damage to property.
11
10
9
8
7
6
5
4
3
2
1
3
7
11
3
8
96
1
4
5
2
10
-
Hilti Firestop Solutions
Intr
od
uctio
nC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.6
Hilti firestop systems are suitablefor use with constructions of:
Concrete or concrete blockGypsumWoodW
G
C
Hilti Firestop SolutionsFor each of the firestopping problems illustrated on the facingpage, Hilti has designed and tested a specific solution. Notonly is there a solution for each type of opening, but Hilti alsooffers a choice of firestop systems for several applications,according to the size of the opening and whether theinstallation is permanent or temporary.
Hilti Product Description Application F rating Page
Metallic & Non-metallic Pipes
CP 680-P/M Cast-in Firestop Device Metal and plastic pipes with diameters up to 6" up to 4 hours 14CP 620 Fire Foam Metal and plastic pipes (in conjunction with CP 648-E) up to 3 hours 24CP 644 Firestop Collar Plastic pipes with diameters 8" to 10" up to 2 hours 32CP 643N Firestop Collar Plastic pipes with diameters 6" or less up to 4 hours 31FS-ONE Intumescent Firestop Metal and plastic pipes up to 4 hours 20CP 604 Self-Leveling Firestop Sealant Metal pipes up to 3 hours 23CP 648-S Firestop Wrap Strip Single wrap for plastic pipes up to 3 hours 33
Cables & Cable Trays
CP 680-P/M Cast-in Firestop Device Cable bundles up to 3 hours 14CP 658T Firestop Plug Single or bundled cables up to 4 hours 30CP 675T Firestop Board Temporary and permanent sealing of cables and cable trays up to 2 hours 27CP 620 Fire Foam Permanent sealing of cables and cable trays up to 2 hours 24FS-ONE Intumescent Firestop Jacketed cables and cable bundles up to 4 hours 20FS 657 Fire Block Temporary and permanent sealing of cables and cable trays up to 4 hours 26CP 637 Firestop Mortar Permanent sealing of cables and cable trays up to 4 hours 25CP 618 Firestop Putty Stick Single or bundled cables up to 4 hours 29CP 617-L/XL Firestop Putty Pad Electrical boxes up to 2 hours 28CP 604 Self-Leveling Firestop Sealant Cable bundles up to 3 hours 23
Multiple Penetrations
CP 648-E Firestop Wrap Strip Continuous wrap for plastic pipes up to 4 hours 34CP 648-S Firestop Wrap Strip Single wrap for plastic pipes up to 2 hours 33CP 620 Fire Foam Permanent sealing of metal and plastic pipes, up to 2 hours 24
cables, and cable traysFS-ONE Intumescent Firestop Metal and plastic pipes, jacketed cables and cable bundles up to 3 hours 20FS 657 Fire Block Temporary and permanent sealing of metal up to 4 hours 26
and plastic pipes, cables and cable traysCP 637 Firestop Mortar Permanent sealing of metal and plastic pipes up to 4 hours 25
cables and cable traysCP 680-P/M Cast-in Firestop Device Multiple metallic and non-metallic pipes up to 3 hours 14CP 675T Firestop Board Temporary and permanent sealing of cables, cable trays up to 2 hours 27
and metal pipes
Heating / Ventilation / Air-conditioning
FS-ONE Intumescent Firestop Sealing around metal ducts up to 3 hours 20CP 601S Elastomeric Firestop Sealant Sealing around metal ducts up to 3 hours 21CP 606 Flexible Firestop Sealant Sealing around metal ducts up to 3 hours 22CP 604 Self-Leveling Firestop Sealant Sealing around metal ducts up to 3 hours 23
Joints/Curtain Walls
CP 606 Flexible Firestop Sealant Sealing floor joints, head of wall and wall to wall joints up to 3 hours 22CP 601S Elastomeric Firestop Sealant Sealing floor, head of wall and wall to wall joints up to 4 hours 21CP 604 Self-Leveling Firestop Sealant Sealing floor to wall joints (Perimeter/Curtain Walls) up to 2 hours 23CP 672 Speed Spray Sealing head of wall, wall to wall and floor to walls up to 4 hours 35
(Perimeter/Curtain Walls)CP 767/777 Speed Plugs/Speed Strips Provides non-combustible backing for FS sealants - 3614
13
9
7
7
9
7
7
7
11
1
4
3
7
8
12
12
9
6
5
4
3
7
8
11
10
1
12
9
7
2
2
8
1
-
Hilti Firestop Solutions
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
7
Intro
ductio
nC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
Hilti Firestop SolutionsThe illustration on the right provides abasic guide to the range of HiltiFirestop products available for theapplications shown
CP 680-P/M Firestop Cast-InDevice
CP 643N Firestop CollarCP 644 Firestop Collar FS 657 Fire BlockCP 637 Firestop MortarCP 618 Firestop Putty StickCP 617 / CP 617L / CP 617XLFirestop Putty PadFS-ONE High Performance
Intumescent SealantCP 601S Elastomeric Firestop
SealantCP 606 Flexible Firestop SealantCP 620 Fire FoamCP 604 Self-Leveling Firestop
SealantCP 658T Firestop PlugCP 675T Firestop BoardCP 648-E/S Firestop Wrap StripCP 672 Speed SprayCP 767 Speed StripsCP 777 Speed Plugs
14
13
12
11
10
9
8
7
6
5
4
3
2
1
7
4
85
12
6
3
11 13
14
9
7
77
10
1
2
9
9
-
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
-
9Chap
ter T
ab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
Applications/Products
Firestop Systems Application Review Page 10
Product Information & Installation Instructions
CP 680-P Cast-In Firestop Device Page 14CP 680-M Cast-In Firestop Device Page 14
Height Extension Page 15Metal Deck Adapters Page 15Water Barrier Module Page 16
Top Seal Plug Page 16CP 681 Tub Box Kit Page 17
Closet Stub Page 18Shower and Floor Drain Page 19
Aerator Adapter Page 19FS-ONE High Performance Intumescent Firestop Sealant Page 20
CP 601S Elastomeric Firestop Sealant Page 21CP 606 Flexible Firestop Sealant Page 22
CP 604 Self-Leveling Firestop Sealant Page 23CP 620 Fire Foam Page 24
CP 637 Firestop Mortar Page 25FS 657 Fire Block Page 26
CP 675T Firestop Board Page 27CP 617, CP 617 L and CP 617 XL Firestop Putty Pad Page 28
CP 618 Firestop Putty Stick Page 29CP 658T Firestop Plug Page 30
CP 643N Firestop Collar Page 31CP 644 Firestop Collar Page 32
CP 648-S Firestop Wrap Strip Page 33CP 648-E Firestop Wrap Strip Page 34
CP 672 Speed Spray Page 35CP 777 Speed Plugs Page 36CP 767 Speed Strips Page 36
Hilti FACT Program Page 37
Product Ordering Information Page 38
Selection Chart Page 44
-
Product Information
Chap
ter
Tab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.10
Firestop SystemsApplication Review
Me
tal p
ipe
s
Pla
stic
/gla
ss p
ipe
s
Ca
ble
s/c
ab
le t
rays
Insu
late
d m
eta
l pip
es
Me
tal d
uc
ts
Mu
ltip
le p
en
etr
atio
ns
Join
ts
Application
See Page Description Features Benefits
CP 680-PCast-InFirestop DeviceA one-step cast-in firestopdevice for a wide varietyof pipe materials anddiameters
Quick and simple installation
Integrated moisture and smokeseal
Tested in concrete floorthicknesses from 2-1/2" (63 mm)
Innovative adapter for metal deckapplications
Ready to use no additionalcaulk required
Easy to specify, install and inspect
Cost effective solution
CP 680-MCast-InFirestop DeviceA one-step cast-in firestopdevice for a wide variety ofnon combustible pipematerials and diameters
Quick and simple installation
Integrated moisture and smokeseal
Tested in concrete floorthicknesses from 2-1/2" (63 mm)
Innovative adapter for metal deckapplications
Ready to use no additionalcaulk required
Easy to specify, install and inspect
Cost effective solution
HeightExtension For use with CP 680-P/M
One extension adds up to 6"
For concrete floors over 8"
Positive connection systempromotes a secure fit
Fast, modular installation
Color coded for easier topsidelayout
Metal DeckAdapters For use with CP 680-P/M
Positive connection systempromotes a secure fit to the base
Fast, modular installation
Color coded for easieridentification below deck
Water BarrierModule For use with CP 680-P/M
Available in 2", 3", 4" and 6" sizes
Adds 1" to the overall height
Secures to top of device
A pre-concrete casting waterbarrier solution
Many tested details meeting ULsClass I W-Rating
Top Seal Plug For use with 2 inch CP 680-P/M 1/2" to 2" diameter
pipes
Restricts water from flowingthrough pipe penetrations
Easy friction fit around pipes tocreate a water resistant seal
Forces pipe to be centered in theopening
A post-concrete casting waterbarrier solution
Many tested details meeting ULsClass I W-Rating (pending)
CP 681Tub Box KitA unique firestop cast-indevice for recessed tubdrain applications
Assembles easily with solventcement
Triangular shape makes workingaround rebar easy
3 fastening points instead of 4
Saves time and labor costs
Structurally stable during concretepouring
No special tools required forinstallation
14
14
15
15
16
16
17
-
Product Information
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.11
Chap
ter T
ab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
Firestop SystemsApplication Review
Me
tal p
ipe
s
Pla
stic
/gla
ss p
ipe
s
Ca
ble
s/c
ab
le t
rays
Insu
late
d m
eta
l pip
es
Me
tal d
uc
ts
Mu
ltip
le p
en
etr
atio
ns
Join
ts
Application
See Page Description Features Benefits
Closet Stub Cast-In device for toilet fixtures Durable PVC construction (ASTM
2665)
Material can be attached to pipesvia solvent welding or glue
Economical, dependable solutionfor toilets
Shower andFloor Drain
Cast-In device for shower/floordrains
Material can be attached to pipesvia solvent welding or glue
Economical, dependable solutionfor drains
AeratorAdapterUsed in Combinationwith CP 680-P/M forfirestopping aeratorapplications
Allows for vertical/horizontal and angle movement
FS-ONE HighPerformanceIntumescent Firestop SealantA water-based intumescentfirestop sealant, designed toexpand when exposed toheat
UL Listings for various penetratingitems
Several 1/4" depth systems
Available in foil pack (600 ml)
One product to specify, purchaseor inspect for most applications
Low cost per penetration
Quick and simple installationprocedure
sodfm,ev iJdjfiwhriuh. NoWE
Z8Z23awp3i4e0288u27uze
4i5kirdwiloi4jtf-x-.vbvbvh, ireiv
u9+12oeoo
tlke09^)&(/R 84tc )v 6453
CP 601SElastomericFirestop SealantA single componentsilicone firestop sealantfor joint and throughpenetration applications
Silicone based formula
1/4" depth systems
Available in foil pack (600 ml)
Meets 500 cycle requirements injoint applications (ASTM E 1966 &UL 2079)
Allows for movement andvibration
Cost effective solutions
Fast and easy dispensing
Smoke, fume and water resistant
Meets Class 1 W Ratingrequirements
CP 606 Flexible Firestop SealantAn acrylic based firestopsealant for throughpenetration applications
Acrylic based formula
Can be painted
Available in foil pack (600 ml)
Meets 500 cycle requirements (ASTM E 1966 & UL 2079)
Fast and easy clean-up with water
Allows for excellent finishedappearance
Fast and easy dispensing
CP 604Self-LevelingFirestop SealantA self-leveling, single-component, silicone-basedfirestop sealant for use withthrough-penetrations aswell as construction jointsin floors
1/4" depth systems
Excellent elongation/compressionproperties
Resistant to smoke, fumes andwater
Meets 500 cycle requirements (ASTM E 1966 & UL 2079)
Smoke, fume and water resistant
No tooling required
Meets Class 1 W Ratingrequirements
Creates a void in concrete thatallows for simple and flexibleinstallation
Available for 3" and 4" cast-inplace devices
18
19
19
20
21
22
23
-
Product Information
Chap
ter
Tab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.12
Firestop SystemsApplication Review
Me
tal p
ipe
s
Pla
stic
/gla
ss p
ipe
s
Ca
ble
s/c
ab
le t
rays
Insu
late
d m
eta
l pip
es
Me
tal d
uc
ts
Mu
ltip
le p
en
etr
atio
ns
Join
ts
Application
See Page Description Features Benefits
CP 620Fire FoamUniversal firestoppingsolution for commonconstruction materials.Can also be used inconjunction with CP 648EWrap Strip
One stop application
Virtually impervious to smoke
Fully cures in approximately 1minute
No additional materials required
High yield
One solution for various applications Easy handling for difficult to reach
applications Excellent mold resistance Meets Class I W Rating requirements
sodfm,ev iJdjfiwhriuh. NoWE4i5kirdwiloi4jtf-x-.vbvbvh, ireivu9+12oeoo
CP 620 Brandschutzbeschichtung
CP 637Firestop MortarA dry powder, when mixedwith water forms apourable, trowelablefirestop mortar. Can alsobe used in conjunctionwith CP 648E Wrap Strip
Some applications require minimum 2-1/2" depth
Cleans up with water
Economical and simple to use
Fast and easy clean-up
FS 657 Fire BlockAn innovative and simple to install firestop blockdesigned to expandwhen exposed to heat
Soft flexible design
Easy to cut and shape
User friendly UL systems
Innovative designs
Non-curing
Easy to install, reuse andrepenetrate
Simply trim block to fit aroundpenetrating items
Reduces need for extra labor,tools and parts
Easiest solution for large openingswith multiple penetrations
CP 675TFirestop BoardwithAccessoriesReady to use FirestopBoard designed for largeopenings with cable traysand multiple penetrations
Lightweight design
Variety of tested systems
Systems for one-sided installation
Easy to install; can be cut withoutpower tools
Solutions for low and highpenetrated openings
Solutions for access impededareas
CP 617, CP 617 Land CP 617 XLFirestop Putty PadAn intumescent puttysheet designed to helpprotect electrical outletboxes
Pad sizes 6" x 7", 7" x 7" or 9" x 9"
1 & 2 hour systems
Tested for wood and steel studs
Fits most common electricalboxes (refer to UL listings)
Only one pad to stock and install
Can be used for commercial andresidential applications
CP 618Firestop Putty StickAn intumescent puttywhich remains pliable overtime
Non-curing
No volatile solvents
Flexible, moldable product
Reusable and easily repenetrated
Approved for combustiblepenetrations (cables) along withconduit, EMT and steel pipe
CP 658TFirestop PlugA pre-sized, intumescentfirestop plug for blankopenings and cablepenetrations
Soft Flexible Design
Versatile in use
Non-curing
Fast and cost effective installation
Provides temporary or permanentfire protection
Reusable
* When used with CP 645 or CP 648E Wrap Strip
24
25
26
27
28
29
30
-
Product Information
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.13
Chap
ter T
ab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
Firestop SystemsApplication Review
Me
tal p
ipe
s
Pla
stic
/gla
ss p
ipe
s
Ca
ble
s/c
ab
le t
rays
Insu
late
d m
eta
l pip
es
Me
tal d
uc
ts
Mu
ltip
le p
en
etr
atio
ns
Join
ts
Application
See Page Description Features Benefits
CP 643NFirestop CollarA ready-to-use firestopdevice designed tocollapse plastic pipepenetrations whenexposed to fire conditions
Ready-to-use out of package
Adjustable mounting tabs
Low profile design
Simple and quick installation
Flexibility in positioning of collar
Allows for correct installation intight areas
. NoW
E
8u27 uz
e
bvbvh,
ireiv
utzma
nsch
.
CP 644Firestop CollarA ready-to-use firestopdevice designed tocollapse plastic pipepenetrations whenexposed to fire conditions
Ready-to-use out of package
Adjustable mounting tabs
Simple and quick installation
Flexibility in positioning of collar
Allows for correct installation intight areas
sodfm,ev
iJdjfiwhriu
h. NoWE
Z8Z23aw
p3i4e0
288u27u
ze
4i5kirdw
iloi4jtf-x-.
vbvbvh, irei
vCP 642
Brands
chutzm
ansch.
CP 648-SFirestop Wrap StripAn intumescent, flexiblefirestop wrap for plasticpipe penetrations
Pre-measured no cuttingrequired
Integrated fastening tape
No special tools required
CP 648-EFirestop Wrap StripAn intumescent, flexiblefirestop wrap forplastic and insulated pipepenetrations
May be continuously wrapped
Flexible
Versatile
No need to measure each layer formulti-wrap applications
Easy to use
May be used inside the annularspace or outside of the substrate
iwhriuh
. NoW
E
4e028
8u27 uz
e
f-x-.vb
vbvh, ir
eiv
ndsc
hutzm
ansc
h.
CP 672 Speed SprayA flexible fire-rated masticfor construction jointswhere movement up to50% is expected
Water based formulation
Maximum flexibility
Can be used with many standardtexture spray equipment
Meets 500 cycle requirements (ASTM E 1966 & UL 2079)
Fast and easy clean-up
No special modification or extraexpense for product application
FirestopSystem
CP 777 Speed PlugsPre-cut flute configurationfor top of wall firestopping
CP 767 Speed StripsPre-cut mineral wool stripssuitable for joint applications
Pre-cut
Superior finish
Safe to use
User friendly
Leaves no gaps or voids
Smooth surface provides cost effective spray coverage
No asbestos
Inorganic will not mildew
Up to 60% faster than castlecutting
14-15
Easy installation
User friendly
Saves time and labor costs
31
32
33
34
35
36
-
Product Information
Chap
ter
Tab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
14
CP 680-P and CP 680-M Technical DataID Footprint Opening Required thru Metal Deck2" 3-3/4" x 4-1/2" 3-1/2" diameter3" 4-3/4" x 5-5/8" 4-1/2" diameter4" 6-3/8" x 6-3/4" 5-1/2" diameter6" 9" x 9-1/2" 7-1/4" diameterExpansion temperature 392F (200C)Expansion rate 1:50 (unrestrained)
1:30 (Load expansion, Load = 20g/cm3)Standard Height 8"Temperature resistance Maximum 212F (100C)Color CP 680-P: red
CP 680-M: black ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:135, 4485-1200:136City of New York MEA 1-07-M, MEA 2-07-M Tested in accordance with UL 1479
ASTM E 814 ULC-S115
Internationally tested and approved
FMAPPROVED
F
For use in Dust and fiber free environments such as hospitals, computer
centers and laboratories
Concrete floor assemblies rated up to 4 hours
Product Description A one-step cast-in firestop device for a variety of pipe materials
and diameters
Helps reduce labor costs and increase productivity
Ready-to-use out of the package
Internationally tested and approved by UL and FM
Reduces the chance of project delays due to failed inspections
Product Features Quick & simple installation
SpeedLine Alignment system promotes faster layout
QuickTurn System creates fast, simple vertical connections
Integrated moisture and smoke seal
Innovative adapter for metal deck applications
Installation & Applications Concrete floors from 2.5" (63 mm) thickness for either flat concrete
or concrete over metal deck
CP 680-M:
- Insulated and non-insulated metal pipes
- EMT and electrical conduits
- Cable bundles
- Multiple pipes
CP 680-P:
Addresses all applications for CP 680-M as well as the following:- Plastic pipes such as PVC, CPVC, ABS, ENT and FRPP
- Fresh and waste water pipes
Not suited for Areas with high condensation
Outdoor areas
Wall applications
CP 680-P and CP 680-M Cast-In Firestop Devices
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Instructions for use Before pouring concrete, secure the cover cap in
place, thereby preventing the flow of concrete intothe cast-in device.
Do not use for wall applications.
Concrete floor with metal decking For concrete floor with metal decking applications usethe correct size CP 680 Metal Deck Adapter forinstalled cast-in device and follow the illustrations.
Concrete floor
Installation optionFollow the illustrations if CP 680 has to be cut to slabthickness before installation, or when riser clamps areused.
Installation Instructions
FIRESTOP DEVICEFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY
5N76
CP 680-P over metaldeck
CP 680-P in concrete over wood forms
CP 680-M over metaldeck
CP 680-M in concrete over wood forms
1
1 2
1 2
3 4
5 6
2
3 4
-
Product Information
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
15
Chap
ter T
ab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
Installation Instructions
Height Extension
Metal Deck Adapters
Product Description For use when concrete slabs are greater than 8" thick
Device may add up to 6" with each extension kit
QuickTurn Connection system promotes a fast, positiveconnection to the top of the appropriate cast-in device
Red (CP 680-P) and Black (CP 680-M) versions create for easieridentification when both combustible and non-combustiblepenetrants are employed for the same project
Color CP 680-P Kit Red cylinder with Red coupling band
CP 680-M Kit Black cylinder with Red coupling band
Product Description For use with concrete over metal deck applications
6" cylinder extension protrudes through even the thickest sprayfireproofing
QuickTurn Connection system promotes a fast, positiveconnection to the underside of the appropriate cast-in device
Red (CP 680-P) and Black (CP 680-M) versions create for easieridentification when both combustible and non-combustiblepenetrants are employed for the same project
Opening Required to Place the Cylinder Through a Metal Deck
For 2" Devices 3-1/2" diameter
For 3" Devices 4-1/2" diameter
For 4" Devices 5-1/2" diameter
For 6" Devices 7-1/4" diameter
Color CP 680-P Kit Red cylinder with two (2) metal plates
CP 680-M Kit Black cylinder with two (2) metal plates
Notice Before handling, read Material Safety DataSheet and product
label for safe usage and health information.
Instructions below are general guidelines always refer to theapplicable drawing in the UL Fire Resistance Directory or HiltiFirestop Systems Guide for complete installation information
Installation Instructions
Notice Before handling, read Material Safety DataSheet and product
label for safe usage and health information.
Instructions below are general guidelines always refer to theapplicable drawing in the UL Fire Resistance Directory or HiltiFirestop Systems Guide for complete installation information
-
Product Information
Chap
ter
Tab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
16
Water Barrier Module
Top Seal Plug Product Description A post-installed water barrier solution that impedes water
Meets W-Rating requirements for select penetrants
For use where a single penetrant is employed per cast-in device
Chemically stable elastomeric material will not react withcombustible pipes
Applications For single penetrants placed through a 2" cast-in place device
Iron Pipe Sizing (IPS) and Copper Pipe Sizing (CPS) offeringsavailable
For pipes ranging from nominal 0.5" to 2.0" in diameter
Color Red
Product Description A pre-installed water barrier solution that impedes water
Meets W-Rating requirements for select penetrants
For use where a single penetrant is employed per cast-in device
QuickTurn Connection system promotes a fast, positiveconnection to the top of the appropriate cast-in device
Dimension Adds 1" to all cast-in devices
Pipe Sizes Addressed (See UL Systems) For 2" Water Module: 2" Pipe
For 3" Water Module: 2.5" and 3" Pipe
For 4" Water Module: 4" Pipe
For 6" Water Module: 6" Pipe
Color Red housing with black gasket
(Pending)(Pending)
Installation Instructions
Notice Before handling, read Material Safety DataSheet and product
label for safe usage and health information.
Instructions below are general guidelines always refer to theapplicable drawing in the UL Fire Resistance Directory or HiltiFirestop Systems Guide for complete installation information
Installation Instructions
Notice Before handling, read Material Safety DataSheet and product
label for safe usage and health information.
Instructions below are general guidelines always refer to theapplicable drawing in the UL Fire Resistance Directory or HiltiFirestop Systems Guide for complete installation information
-
Product Information
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
17
Chap
ter T
ab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
CP 681 Tub Box Kit
FIRESTOP DEVICEFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY
5N76
Technical DataDimensions (LxWxH) 10-3/4" x 13" x slab thicknessApplication dimension Creates a 2-1/2" deep recess in the slabMinimum slab thickness 4-1/2"Intumescent activation Approx. 375F (190C)Expansion ratio (unrestricted) 1:10Temperature resistance Maximum 212F (100C)Color Red with white PVC legs and couplingStorage Store in dry locationApprovalsCalifornia State Fire Marshall Listing No. 4485-1200:122City of New York MEA 283-06-ETested in accordance with UL 1479
ASTM E 814
The Hilti cast-in solutions include an innovative tubbox solution Structurally stable stable during concrete pouring
Assembles easily with solvent cement no additional toolsrequired
Triangular shape makes working around rebar easy
3 fastening points instead of 4 reduces installation time
Pre-cut to customers height requirement upon request helpsreduce labor costs
One system for all pipe materials, easy to choose and inspect
Accepts a pass through 1-12" pipe (with a sealing bushing) or astandard 2" P-trap (direct connection to the coupling)
The CP 681 Tub Box Kit includes an ElastomericSealing Bushing Sealing bushings available for standard schedule 40 pipe or thin
wall piping
Versatile CP 681 tub box kit allows sealing bushing to be installedfrom top or bottom
Assembly & Installation instructions for CP 681 Tub Box KitNotice Before handling, read Material Safety DataSheet
and product label for safe usage and healthinformation.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Concrete on wood form 1. Secure the coupling sleeve flange (the larger of the
three flanges) to the floor deck using nails orscrews.
2. Using standard solvent cement on both plasticsurfaces, assemble the CP 681 Tub Box legs andsleeve to bottom of the Tub Box as follows:
Cement the two 3/4" PVC stabilizing legs to thematching connecting area on the bottom side of theCP 681 Tub Box.
Cement the CP 681 Tub Box and larger PVC plasticsleeve to the connecting area on the bottom side ofthe CP 681 Tub Box.
Secure the smaller leg flanges to the deck usingnails or screws.
3. Pour concrete to the proper height. CP 681 Tub Boxassembly is precut to the slab thickness.
4. After concrete is cured, remove the floor deck andfoam insert. Remove pressure test cap beforeinstalling drain piping.
5. Install the tub drain/overflow assembly piping(plastic or brass) through the CP 681 Tub Box andplastic coupling. Insert proper elastomeric bushinginto the bottom or top of the CP 681 Tub Boxassembly around the drain pipe.
Note: Install bushing before final drain/overflowassembly if installing from the top side. Completethe installation by installing branch and trap piping.
1 2 3 4 5
-
Product Information
Chap
ter
Tab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
18
Closet StubProduct Description A coupling device designed to address cast-in applications for
toilet fixtures
Material can be solvent welded to PVC piping
Available for 3" and 4" PVC applications
Product Dimensions (Diameter x Height) 3": 5-11/16" x* 3-1/8"
4": 6-3/4" x* 3-5/8"
Application Dimensions 3": 3-1/2" inner diameter (for use with 3" PVC pipe)
4": 4-1/2" inner diameter (for use with 4" PVC pipe)
Minimum Slab Thickness 6"
Color Red
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Hilti Firestop Closet Stubassembly concrete on woodform for floors A: Hilti Cast In Firestop Closet Stub
B: 3" or 4" PVC SCH 40 pipe (supplied by others)
C*: 3" or 4" Toilet Flange (supplied by others)
1. Secure the Hilti Cast-In Firestop Closet Stub to thefloor deck, using nails or screws. Pre-assemble A &B by solvent welding.
2. Close the top of the assembly to avoid concretefilling (tape or similar).
3. Pour concrete to proper height. After concrete iscured, remove the floor deck and tape.
4. Complete installation by installing Toilet Flange andelbow by solvent welding.
Installation Instructions
1 2 3 4
-
Product Information
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
19
Chap
ter T
ab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
Shower and Floor Drain
Aerator Adapters
Product Description An economical solution to address shower and floor drain
applications
The same trusted firestop material as the tub box
Two variations: (1) extended sleeve & (2) hub coupling
Designed to accommodate solvent welding to 2" PVC pipes
Product Dimensions Extended Sleeve: 5-3/4" base diameter 8" height
Hub Coupling: 5-3/4" base diameter; 2-13/16" height
Application Dimensions Extended Sleeve: 2-3/8" inner diameter (for use with 2" PVC pipe)
Hub Coupling: 2-3/8" inner diameter (for use with 2" PVC pipe)
Minimum Slab Thickness 4-1/2"
Color Extended Sleeve: red flange with white extended sleeve
Hub Coupling: red flange with white hub coupling
Aerator-Adapter Technical DataProduct Dimensions (WxLxH) 3": 6" x 6-7/8" x 3"
4": 6" x 8-3/4" x 4-1/2" Application Dimensions (WxLxH) 3": 5-3/4" x 2-3/8"
4": 5-7/8" x 7.5" x 4-1/2" Minimum Slab Thickness 3": 5-1/8"
4": 6-1/2" Color 3": Red
4": RedStorage Store in dry locationTested in Accordance with UL 1479
ASTM E 814
Product DescriptionWhen used in conjunction with the appropriate cast-in place device,creates an underside void for the installation of a single stack wastepipe aerator system
Product Features Up to a 4-1/2" recess created in the slab to reduce final ceiling
height
Allows for vertical, horizontal and angle movement to simplifyplumbing installations
Excellent sound insulation
For Use With Soil and Aerator assemblies
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Note: Before purchasing aerator adapters for yourproject, please confirm the following:
aerators may be employed on the project as perlocal codes and construction allowances
minimum concrete floor slab thickness
1. Secure the assembly to the floor deck using nails orscrews.
2. Attach the Aerator Adapter to the appropriatecast-in place device.
3. Before pouring concrete, confirm that the cover capof the assembly is properly secured. This willprevent flowing concrete into the CP 680-P/Mduring the concrete pour.
4. Complete installation by installing 3" or 4" cast ironaerator and pipe.
Assembly instructions for Aerator Adapter
1 2 3 4
-
Product Information
Chap
ter
Tab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.20
sodfm,ev iJdjfiwhriuh. NoWE
Z8Z23awp3i4e0288u27uze
4i5kirdwiloi4jtf-x-.vbvbvh, ireiv
u9+12oeoo
tlke09^)&(/R 84tc )v 6453
FS-ONEHigh Performance Intumescent Firestop Sealant
FS-ONE Technical DataChemical basis Water-based intumescent acrylic
dispersionColor RedApplication temperature 40F to 104F (5C to 40C) Skin forming time Approx. 20-30 min.Curing time Approx. 2 mm / 3 daysMovement capability Approx. 5%Expansion rate Up to 3-5 times (unrestricted): original volumeTemperature resistance (cured) 40F to 212F (40C to 100C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:108City of New York MEA 326-96-M Vol. IVTested in accordance with UL 1479
ASTM E 814 ASTM E 84
At 73F (23C) and 50% relative humidity
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY
66Y7
FMAPPROVED
F
Product description Intumescent (expands when exposed to fire) firestop sealant that
helps protect combustible and non-combustible penetrations forup to 4 hours fire rating
Product features Smoke, gas and water resistant after material has cured
Contains no halogen, solvents or asbestos
High fire rating properties
Water based, easy to clean
Protects most typical firestop penetration applications
Can be painted
Single component systems available
Meets LEED requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings
Areas of application Steel, copper and EMT pipes
Insulated steel and copper pipes
Cable bundles
Closed or vented plastic pipes
HVAC penetrations
For use with Concrete, masonry, drywall and wood floor assemblies
Wall and floor assemblies rated up to 4 hours
Examples Sealing around plastic pipe penetrations in fire rated construction
Sealing around combustible and non-combustible penetrations infire rated construction
1. Clean opening. 2. Pack mineral wool.(If required)
3. Apply FS-ONE. 4. Smooth FS-ONE.
5. Leave completedseal undisturbed for 48hours.
6. Fasten identificationplate (if required).
1. Clean opening. 2. Pack mineral wool.(If required)
3. Apply FS-ONE. 4. Smooth FS-ONE.
5. Leave completedseal undisturbed for 48hours.
6. Fastenidentification plate (ifrequired).
FirestopSystem
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Opening 1. Clean the opening. Surfaces to which FS-ONE will be
applied should be cleaned of loose debris, dirt, oil,moisture, frost and wax. Structures supportingpenetrating items must be installed in compliancewith local building and electrical standards.
Application of firestop sealant 2. Install the prescribed backfilling material type and
depth to obtain the desired rating (if required). Leavesufficient depth for applying FS-ONE.
3. Application of firestop sealant: Apply FS-ONE to therequired depth in order to obtain the desired fire rating.Make sure FS-ONE contacts all surfaces to providemaximum adhesion. For application of FS-ONE use astandard caulking gun, foil pack gun, bulk loader andbulk gun. With FS-ONE buckets, Graco type sealantpumps may be used. (Contact pump manufacturer forproper selection).
4. Smoothing of firestop sealant: To complete the seal,tool immediately to give a smooth appearance.Excess sealant, prior to curing, can be cleanedaway from adjacent surfaces and tools with water.
5. Leave completed seal undisturbed for 48 hours.
6. For maintenance reasons, a penetration seal couldbe permanently marked with an identification plate.In such a case, mark the identification plate andfasten it in a visible position next to the seal.
Not for use High movement expansion joints
Underwater
On materials where oil, plasticizers or solvents maybleed i.e. impregnated wood, oil based seals, greenor partially vulcanized rubber
In any penetration other than those specificallydescribed in this manual or the test reports
Storage Store only in the original packaging in a location
protected from moisture at temperatures between 40F (5C) and 86F (30C)
Observe expiration date on the packaging
Installation instructions for FS-ONE
FirestopSystem
FirestopSystem
CA
BLE
PIP
E
-
Product Information
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007 21
Chap
ter T
ab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
CP 601SElastomeric Firestop Sealant
CP 601S Technical DataChemical basis Natural Elastic siliconeDensity Approx. 1.25 g/cm3
Color RedApplication temperature 40F to 104F (5C to 40C)Skin-forming time Approx. 15 min.Curing rate Approx. 2 mm / 3 daysVolume shrinkage Approx. 0 5%Movement capability Approx. 25%Temperature resistance 40F to 320F (40C to 160C)Surface burning characteristics Flame spread: 0(ASTM E84-96) Smoke development: 30Sound transmission classification 50 (Relates to specific construction)(ASTM E 90-97): ApprovalsCalifornia State Fire Marshal Listing No. 1451-1200:115
Listing No. 1452-1200:113Listing No. 4485-1200:123
City of New York MEA 101-99-M, Vol. IVTested in accordance with UL 2079 ASTM E 814
ASTM E 1966 ASTM C 920 UL 1479 ASTM E 84
At 73F (23C) and 50% relative humidity
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS AND JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY 66Y7
FMAPPROVED
F
Product description A silicone based firestop sealant that provides maximum
movement in fire-rated joint applications and pipe penetrations
Product features Halogen and solvent free
Asbestos free
Simple to use and apply
Good adhesion without use of a primer
Smoke, fume, water, weather and UV resistant
Excellent movement capability, meets 500 cycle requirements
(ASTM E 1966 & UL 2079)
Meets Class I W-rating requirements
Meets LEED requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings
Areas of application Sealing construction/expansion joints
Top-of-wall joints
Metal pipes
Cable bundles
HVAC penetrations
For use with Various base materials such as masonry, concrete, metal, glass, etc.
Wall and floor assemblies rated up to 4 hours
Examples Where a gypsum wall assembly meets the underside of a metal or
concrete deck
Sealing expansion joints to impede the passage of fire, smoke andtoxic fumes
Sealing HVAC penetrations through fire-rated assemblies
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Opening 1. Clean the opening. Surfaces to which CP 601S will
be applied should be cleaned of loose debris, dirt,oil, wax and grease. The surface should bemoisture and frost free.
Application of firestop 2. Insert fill of mineral wool (or backer as required).
3. Apply firestop over backer.
4. Smooth firestop sealant with a trowel before theskin forms. Once cured, CP 601S can only beremoved mechanically.
5. For maintenance reasons, a penetration seal can bepermanently marked with an identification plate andfastened in a visible position next to the seal.
Chemical resistance At room temperature the cured silicone sealant is
resistant for a short time to diluted (15%) acids andlyes/alkalis as well as most commercially availablecleaning agents and disinfectants (except thosecontaining iodine).
Concentrated acids and lyes/alkalis destroy siliconerubber over time.
Solvents and mineral oils cause cured silicone toswell. Consequently, proper functioning of thesealant should be checked after exposure to asolvent or mineral oil. Please contact your local salesrepresentative or the nearest Hilti center if specialrequirements for chemical resistance have to be met.
Not for use In areas immersed in water
Not to be painted
Storage Store only in the original packaging in a location
protected from moisture at a temperature of 40F to77F (5C to 25C)
Observe expiration date on packaging
Installation instructions for CP 601S
1. Clean opening 2. Insert backingmaterial
3. Apply CP 601S 4. Smooth CP 601S 5. Fasten identificationplate (if required)
1. Clean opening 2. Insert backing
material
3. Apply CP 601S 4. Smooth CP 601S 5. Fasten identificationplate (if required)
FirestopSystem
FirestopSystem
JO
INT
DU
CT
Hilti. Outperform. Outlast.
-
Product Information
Chap
ter
Tab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
22
CP 606Flexible Firestop Sealant
CP 606 Technical DataChemical basis Acrylic based firestop sealantColor Available in red, white and grayApplication temperature 40F to 104F (5C to 40C)Skin-forming time Approx. 15 minCuring time Approx. 3 mm / 3 daysVolume shrinkage Less than 20%Movement capability Approx. 10%Temperature resistance 22F to 176F (30C to 80C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 1452-1200:112
Listing No. 1451-1200:121Listing No. 4485-1200:132
City of New York MEA 100-99-M, Vol. IVTested in accordance with UL 2079 ASTM E 814
ASTM E 1966 ASTM E 84 UL 1479
At 73F (23C) and 50% relative humidity
FMAPPROVED
F
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS AND JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY 66Y7
Product description An acrylic based firestop sealant that provides movement
capability in fire rated joints and seals through penetrationsapplications
Product features Silicone free
Halogen, asbestos and solvent free
UV-resistant
Paintable
Meets 500 cycle requirements (ASTM E 1966 & UL 2079)
Smoke, fume and water resistant
Easy clean up with water
Single component systems available
Meets LEED requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings
Areas of application Sealing construction/expansion joints
Top-of-wall joints
Metal pipes
Cable bundles
HVAC penetrations
For use with Various base materials such as masonry, concrete, metal, etc.
Wall and floor assemblies rated up to 3 hours
Examples Where a gypsum wall assembly meets the underside of
a metal or concrete deck
Sealing expansion joints to impede the passage of fire, smoke andtoxic fumes
Sealing around HVAC penetrations through fire-rated assemblies
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Opening1. Clean the opening. Surfaces to which CP 606 will
be applied should be cleaned of loose debris, dirt,oil, wax and grease. The surface should bemoisture and frost free.
Application of firestop2. Insert fill of mineral wool or backer (as required).
3. Apply firestop over backer.
4. Smooth firestop sealant with a trowel before theskin forms. Once cured, CP 606 can only beremoved mechanically.
5. For maintenance reasons, a penetration seal can bepermanently marked with an identification plate andfastened in a visible position next to the seal.
Not for use On areas immersed in water
Storage Store only in the original packaging in a location
protected from moisture at a temperature of 40F to77F (5C to 25C)
Observe expiration date on package
Installation instructions for CP 606
1. Clean opening 2. Insert backingmaterial compressedper UL System
3. Apply CP 606 4. Smooth CP 606 5. Fasten identificationplate (if required)
1. Clean opening 2. Insert backingmaterial
3. Apply CP 606 4. Smooth CP 606 5. Fasten identificationplate (if required)
FirestopSystem
FirestopSystem
JO
INT
DU
CT
-
Product Information
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
23
Chap
ter T
ab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
Product description Self-leveling, single-component, silicone-based firestop sealant for
use with through-penetrations as well as construction joints infloors.
Product features Self-levelingrequires no tooling
Excellent elongation/compression properties
Resistant to smoke and water
Meets 500 cycle requirements (ASTM E 1966 & UL 2079)
Smoke, fumes and water resistant
Meets Class I W-rating requirements
Meets LEED requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings
Areas of application Sealing construction/expansion joints
Metal pipes
Cable bundles
Sealing multiple penetrations in small or large openings
For use with Concrete floors rated up to 3-hours
Examples Penetrations for metal pipes between floor levels
Construction joints and expansion joints in floors
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Opening 1. Clean the opening. Surfaces to which CP 604 will
be applied should be cleaned of loose debris, dirt,oil, wax and grease. The surface should bemoisture and frost free.
Application of firestop 2. Insert fill of mineral wool (or backer as required).
3. Apply firestop over backer.
4. Allow firestop sealant to level. Once cured, CP 604can only be removed mechanically.
5. For maintenance reasons, a penetration seal couldbe permanently marked with an identification plate.In such a case, mark the identification plate andfasten it in a visible position next to the seal.
Chemical resistance At room temperature the cured silicone sealant is
resistant for a short time to diluted (15%) acids and
lyes/alkalis as well as commercially availablecleaning agents and disinfectants (except thosecontaining iodine).
Concentrated acids and lyes/alkalis destroy siliconerubber over time.
Solvents and mineral oils cause cured silicone toswell. Consequently, proper functioning of thesealant should be checked after exposure to asolvent or mineral oil. Please contact your localsales representative or the nearest Hilti Center ifspecial requirements for chemical resistance have tobe met.
Not for use In areas immersed in water
Not to be painted
Storage Store only in the original packaging in a location
protected from moisture at a temperature of 40F(5C) to 77F (25C)
Observe expiration date on packaging
CP 604Self-Leveling Firestop Sealant
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS, JOINT SYSTEMS AND PERIMETER FIRE CONTAINMENT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY 66Y7
FMAPPROVED
F
CP 604 Technical DataChemical basis Neutral elastic siliconeColor GrayApplication temperature 40F to 104F (5C to 40C)Skin forming time Approx. 15 minCuring time Approx. 2 mm/3 daysJoint movement capability Approx. +20%Temperature resistance 40F to 248F (40C to 120C)Surface burning characteristics Flame Spread: 5(ASTM E 84-00) Smoke Development: 60ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:117
Listing No. 1452-1200:134City of New York MEA 237-02-MTested in accordance with UL 1479 ASTM E 1966
UL 2079 ASTM E 814 ASTM E 2307 ASTM E 84
At 73F (23C) and 50% relative humidity
Installation instructions for CP 604
1. Clean opening 2. Insert backing materialcompressed per ULSystem
3. Apply CP 604 4. Self levels notooling required
5. Fasten identificationplate (if required)
1. Clean opening 2. Insert backing material 3. Apply CP 604 4. Self levels notooling required
5. Fasten identificationplate (if required)
FirestopSystem
FirestopSystem
FLO
OR
JO
INT
FLO
OR
Joint installation: For floor applications. Not to be used in walls.
Through Penetration Installation (Top View): For floor applications. Not to be used in walls.
-
Product Information
Chap
ter
Tab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
24
CP 620Fire FoamProduct description Innovative firestopping solution for complex applications
Product features Up to 6 times expansion
Repenetrable
Cures within 60 seconds
Easy handling for difficult to reach applications
Paintable
Virtually impervious to smoke
Mold resistant
No additional materials required
Excellent water vapor impermeability
Meets LEED requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings
Areas of application Sealing small to medium size openings
Cables and cable trays
Non-combustible pipes
Combustible pipes when used in conjunction with Hilti Wrap Strips
Where cables, steel, copper, cast iron or plastic pipes all passthrough the same opening
For use with floor and wall assemblies Concrete, drywall, masonry
Examples Multiple penetrations
Insulated metal pipes
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Application1-4.
Prepare dispenser and cartridges as shown below.The Fire Foam from the first few strokes of thedispenser should be discarded until the Fire Foam inthe mixer has a consistent red color.
5. Apply the CP 620 Fire Foam in the opening.
Begin applying CP 620 Fire Foam at the back ofthe opening and work toward the front. Fill theopening completely with CP 620 Fire Foam.
When dispensed slowly, the Fire Foam can beeasily built up.
When dispensed quickly, the consistency of theFire Foam is more liquid allowing it to flow betterbetween the cables. Note: The CP 620 Fire Foambecomes warm for a short time after application.
6. For maintenance reasons, the application can bepermanently marked with an installation plate. Markthe installation plate and fasten it in a visibleposition next to the seal.
Re-installing cables or pipes Additional cables or pipes can be installed later
without difficulty.
Use a suitable tool to create an opening(screwdriver, drill bit, etc.). Push the cable or pipethrough and then seal the remaining openingcarefully with CP 620 Fire Foam.
Notes The CP 620 Fire Foam can be cut back to no less
than the minimum specified installation depth (seeapplicable UL systems for depths).
Pieces of cured excess CP 620 Fire Foam whichhave been cut off can be laid in the next openingand fresh CP 620 Fire Foam can be applied aroundthese.
Not for use Exposed to weather
Exposed to UV
Storage Store only in the original packaging in a dry place at
a temperature of 40F to 77F (5C to 25C). Seetechnical data for application and substratetemperatures. Partly-used cartridges can be storedwith mixer attached until they are required again.When re-using a partially used cartridge, simplyattach a new mixer and dispense accordingly.
Installation instructions for CP 620
1. Hold the cartridgein the upright positionand unscrew the cap.
2. Fit the mixer andscrew in a clockwisemotion until secure.
3. Release thedispenser and pullback the piston rod.
4. Insert the cartridgein the dispenser.
5. Apply CP 620 FireFoam, building up a sealby working from theback towards the front.
6. Attach theinstallation plate (if required).
Aus-fhrungsschild
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FMAPPROVED
F
CP 620 Technical DataChemical basis Two component polyurethaneColor RedFire foam yield Up to 110 in3
Application temperature 32F to 104F (0C to 40C)Curing time Non-tacky after Approx. 35 seconds
Ready to cut after Approx. 1 minuteThermal insulation (R-value) 2.83.0 per inch of thicknessTemperature resistance 22F to 212F (30C to 100C)of cured foamSound transmission classification 50 (Relates to specific construction)(ASTM E90-97) Structure-borne sound insulation Pipe/wall 3050%Surface burning characteristics Flame spread: 0(ASTM E84-01) Smoke development: 15ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:119City of New York MEA 238-02-MTested in accordance with UL 1479 ASTM E 814 ASTM E 84At 73F (23C) and 50% relative humidity
sodfm,ev iJdjfiwhriuh. NoWE4i5kirdwiloi4jtf-x
-.vbvbvh, ireivu9+12oeoo
CP 620 Brandschutzbeschichtung
-
Product Information
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
25
Chap
ter T
ab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
sC
hap
ter T
ab
s
CP 637Firestop MortarProduct description Fire-resistant mortar suitable for firestopping large openings
Product features Quick-setting forms can be removed in as little as 2 hours
Superior working properties
Can be used in horizontal or vertical applications
Saves time
Versatile
Simple mixing
Areas of application Sealing medium size to large openings with non-combustible
pipes or cable trays
Permanent fire seal for cables, cable trays and non-combustiblepipes
For use with Concrete and masonry assemblies
Walls and floors rated up to 4-hours
Examples Large openings containing multiple steel,
conduit and EMT pipes
Large openings with single or multiple cable tray applications
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Mix ratio (recommended, mortar to water):
Trowelable 30 lb (14.6 kg) : 2 U.S. gal (8 L)Pourable 30 lb (14.6 kg) : 2.5 U.S. gal (9.5 L)
Installation instructions for CP 637
1. Clean penetration.Pre-moisten sides of penetration.
2. Important! First add clean waterto separate container. Then slowlyadd CP 637 to water while stirringby hand or power mixer to ensuresmooth, lump-free mix. See tableabove for mix ratio.
3. Work prepared mortar intoopening by troweling, pouring, orpumping with suitable pump. Useforms for large openings. Makesure application has been sealedaccording to the applicable UL FireResistance Directory or HiltiFirestop Manual.
4. Fasten identification plate (ifrequired).
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY
66Y7
CP 637 Technical DataColor Light red Application temperature (ideal) 40F to 110F(5C to 43C)Form removal Approx. 2 hours(depending on consistency)Density: Approx. 40.6 pcf (dry)Expansion on setting 0.08%(approx.)Compressive strength
24 hrs. after casting After full cure Pourable 508 psi (3.5 N/mm2) 725 psi (5.0 N/mm2) Plastic 696 psi (4.8 N/mm2) 1200 psi (8.3 N/mm2) Stiff 870 psi (6.0 N/mm2) 1784 psi (12.3 N/mm2)
Surface burning characteristics Flame spread: 5(ASTM E84-01) Smoke development: 0Yield (30 lb pail) 9001000 cubic inches depending on mix ratioApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:120City of New York MEA 239-02-MTested in accordance with ASTM E 814
UL 1479 ASTM E 84
At 73F (23C) and 50% relative humidity
-
Product Information
Chap
ter
Tab
sA
pp
ilcatio
ns/P
rod
ucts
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en espaol 1-800-879-5000 Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
26
FS 657Fire BlockProduct description Ready-to-use, intumescent flexible block based on a two-
component polyurethane foam
Product features Suitable for re-penetration or new penetrations
Economical to use with short installation times
Easy installation no special tools required
Ideal for use in floors no forming required
One sided wall systems available
Halogen, asbestos and solvent free
Operational immediately after installation
Can be painted
Smoke resistant
Areas of application Sealing single or multiple penetrations in small to large openings
Temporary or permanent sealing of cables and cable traypenetrations
Temporary or permanent sealing of insulated and non-insulatedmetallic pipes and combustible pipe penetrations
For use with Walls (UL tested up to max. opening 52" x 48")
Floors (UL tested up to max. opening 36" x 36")
Concrete, porous concrete, masonry and gypsum wall assemblies
Wall assemblies rated up to 4 hours
Floor assemblies rated up to 3 hours
Examples Completely dust and fiber free rooms and places where electrical
installations are frequently used (ie: computer centers, hospitals,laboratories, etc.)
New buildings in the construction phase and during renovation
Large openings containing multiple penetrations as found inproduction bays, warehouses, hospitals etc.
Installation instructions for FS 657
FS 657 Technical DataColor RedApplication temperature 40 F to 104 F (5 C to 40 C)Temperature resistance 5 F to 140 F(-15 C to 60 C)Intumescent Activation Approx. 572F (300C)Expansion ratio (unrestricted) Up to 1:3Surface burning characteristics Flame Spread Index: 0(ASTM E 84-96) Smoke Development Index: 25Sound transmission classification 54 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:106City of New York MEA 325-96-MTested in accordance with UL 1479
ASTM E 814 ASTM E 84
At 73F (23C) and 50% relative humidity
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY
66Y7
FMAPPROVED
F
Notice Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Opening1. Clean the opening. Penetration and penetration
supporting structures must be installed incompliance with local building and electricalstandards.
Application of Fire Blocks2a.If no penetrations are located, build up FS 657 FIRE
BLOCK firmly seated, within opening.
2b.If penetrations are located, build up FS 657 FIREBLOCK firmly seated, while cutting blocks with aknife to suit the placed penetrations.
3. Finish building up FIRE BLOCKS until entire openingis filled.
4. Completely fill cable spaces, gaps between blocksand pipes, and joints with FS-ONE Firestop Sealant.
5. For maintenance reasons, a penetration seal couldbe permanently marked with an identification plate.In such a case, mark the identification plate andfasten it in a visible position next to the seal.
Re-installing cables or otherpenetrations Remove or cut the block from the seal.
Install the penetrant and re-lay the block incompliance with the approval. Fill gaps and spaceswith FS-ONE.
Single cables can be run through joints betweenblocks or a hole can be drilled through a block usinga sharpened piece of metal pipe or tubing.
Not for use In wet rooms, outdoors or exposed to the weather
or UV radiation (can be done only after applying anadditional silicone coating, i.e. CP 601S).
Storage Store only in the original packaging in a location
protected from moisture and direct sunlight
1. Clean opening. 2a. Build up blocks 2b. Cut blocks to sizefor penetrations inplace
3. Build up blocks 4. Fill gaps with
FS-ONE,